Académique Documents
Professionnel Documents
Culture Documents
04/2009
Symbols
Danger
Thisalertsyoutothingsthatmaycauseseriousinjurytoaperson.
Onlyqualified,properlytrainedpersonnelshouldperformthese
procedures.
Caution
Thisalertsyoutothingsthatmaycauselossofdata,damagetoyour
computeroryourdevices.
Note
Anoteprovidesyouwithadditionalinformationthatyoumightwant
toconsider.
Tip
Thisdrawsyourattentiontoinformationthatwillhelpyouperform
ataskmorequicklyoreasily.
Terminology
Clear
Place the mouse cursor over the check box option, then click the mouse button
so that the check mark is removed from the check box.
Click
Place the mouse cursor over the specified option or button, then press and
release the mouse button.
Double-click
Place the mouse cursor over the specified option or button, then press and
release the mouse button twice.
Drag
Hold down the mouse button while moving the mouse cursor to the appropriate
location, then release the button.
Enter
Point
Position the mouse pointer over a submenu or menu command. For example,
point to the File menu.
Press
Press the specified key or key combination on your keyboard, for example, press
CTRL+ALT+DEL.
Right-click
Place the mouse cursor over the button or item, then press and release the right
mouse button1.
Select
Place the mouse pointer over the specified option or check box, then click the
mouse button. A selected check box receives a check mark; a selected radio
button is marked with a dot.
Type
Type the information, but DO NOT press the ENTER or RETURN key.
1. Mouse button means the the primary mouse button (left, by default), while right mouse button
means the secondary mouse button. This configuration can be switched for a left-handed user.
Contents
Chapter 1
Introduction .................................................................. 7
Before you begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Overview............................................................. 8
Quick start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Serial site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Modem site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Ethernet sites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Ethernet gateway sites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2
Chapter 3
Chapter 4
DeviceLabels ........................................................ 37
EN50160Setup....................................................... 38
Energy&Demand .................................................... 38
FrontPanelDisplay ................................................... 39
I/OSetup............................................................ 39
InputMetering ....................................................... 42
MeterResets......................................................... 42
MeteringStandards ................................................... 43
OnboardAlarms/Events ............................................... 43
ShiftEnergy.......................................................... 50
Trending&Forecasting................................................ 50
WaveformCapture ................................................... 51
Chapter 5
Chapter 6
Chapter 7
Introduction
PowerLogicIONSetupsoftwareisameterconfigurationutilityavailable
fromtheSchneiderElectricwebsiteatwww.powerlogic.com.
ThisguideassumesyouknowhowtouseIONSetup,andhavereadand
understoodtheinstallation,basicsetup,andallrelevantproceduresandwarnings
containedintheuserdocumentationforthedeviceyouwanttoconfigurewith
IONSetup.
Typically,basicsetupcanbeperformedthroughthemetersfrontpanelorremote
display.IONSetupismainlyusedforconfiguringadvancedfeaturesofthemeter,
orforsettingupameterthatdoesnothaveafrontpanel/remotedisplay.
DeviceconfigurationinstructionsusingIONSetupsoftwareareprovidedforthe
following:
PowerLogicE5600powermeter
PowerLogicPM700seriespowermeter
PowerLogicPM800seriespowermeter
PowerLogicBCPM(Branchcircuitpowermeter)
PowerLogicEnerceptmeter
PowerLogicION6200powermeter
FordetailedproceduresonsettingupotherIONdevices(suchasthe
PowerLogicION8600orPowerLogicION7550 / ION7650meters),refertothe
devicespecificinstallationoruserguide.
FordetailedinformationonusingIONSetupsoftware,refertotheonlinehelp.
Page 7
Chapter 1 - Introduction
Security considerations
Somedevicesrequireadditionalconfigurationinordertoaccessandmodify
certainsetupparameters.Forexample,arevenueclassorhardwarelockedmeter
mustbeunlockedbeforeyoucanconfigureit.Refertothedevicesdocumentation
forunlockingandbasicsetupprocedures.
Overview
IONSetupsupportsvarioustypesofcommunications.Typically,devicesare
groupedaccordingtoasharedcommunicationslinktype(IONSetuprefersto
thesecommunicationslinksassites).WhencreatingyourIONSetupnetwork
forthefirsttime,youwouldstartbyaddingasitetoyourworkstation,thenadd
devicestothesite.
Ethernet site
Ethernet devices
Ethernet Gateway
Modem site
RS-485 devices
remote serial device
NOTE
Most ION devices use the 8N1 standard (8 data bits, no parity, 1 stop bit) for serial communications. To
prevent communication errors, make sure all the devices on your serial communications loop are set to
8N1 (i.e. make sure the devices serial communications parameter is set to No parity).
Page 8
Chapter 1 - Introduction
Quick start
ThefollowingsummarizesthestepsforaddingsitesanddevicesinIONSetup.
1.
Installandwireyourmeters,followingtheinstructionsandwarningsinthe
meterspecificdocuments.
2.
Followtheinstructionsinthemeterinstallationmanualtoconfigurethebasic
communicationsparametersforeachmeter(forexample,protocol,baudrate,
parityanddeviceaddress/unitID).
NOTE
Make sure all the devices on the same RS-485 loop are set to the same baud rate, and their serial port
parameters are set to 8N1.
3.
Ifusingacommunicationsconverterorgateway,configureitscommunications
parameters,theninstallandwireittothemeter(s).
4.
StartIONSetupandlogonusingnetworkmode(i.e.,clearthe
Single ION device configuration modecheckbox).Thedefaultuseris
supervisorandpasswordis0(zero).
5.
Addandconfigureyoursites.ForEthernetorEthernetGatewaysites,usethe
followingtabletosettheportnumber,asappropriate.
IP Port1
23
502
Modbus TCP
7700
ION (direct)
7701
7800
7801
7802
7803
1. Some meters support email (SMTP through port 25) and web pages (HTTP through port 80).
6.
AddeachmetertotheappropriatesiteinIONSetup.
Page 9
Chapter 1 - Introduction
Serial site
IfthedeviceisequippedwithanRS232port,youcanuseanRS232cableto
directlyconnectthedevicetoanavailableserialportonthecomputer.
Toconnecttomorethanoneserialdevice,youcanuseanRS232 to RS485
communicationsconverter.TheRS232portontheconverterconnectstothe
computersserialport,andtheRS485portconnectstoupto32RS485devices.
RS-232 to RS-485
converter
RS-485 devices
(maximum 32)
Makesuretheserialcommunicationsparametersaresetcorrectlyforeachdevice
(forexample,protocol,baudrate,parityanduniquedeviceaddress/unitID).
Adding a serial site in ION Setup
1.
RightclicktheworkstationiconandselectInsertItem.
2.
SelectSiteandclickOK.
3.
OntheGeneraltab,usetheNameboxtoenteranameidentifyingthisserial
site.
UsetheCommLinkboxtoselectwhichserialportonthecomputeryouare
usingtocommunicatewiththemeter(s).
UsetheLinkSpeedboxtosettheserialportsbaudratetothesamevalueas
theserialdevice(s).
Fordirectserialcommunicationsthroughtheserialport(orthroughan
RS232 to RS485communicationsconverter),setLinkTypetoRS232/RS485
Direct.
4.
Page 10
TheTimingsandPollingtabscontainotherserialcommunicationsparameters.
Inmostcases,thedefaultsettingsdonotneedtobemodified.
Chapter 1 - Introduction
Modem site
Amodemsiteconsistsofalocalmodemconnectedtothecomputersserialport
andaremotemodemconnectedtooneormoreserialdevices.
IONSetupusesthelocalmodemtodialtheremotemodemstelephonenumber
andestablishcommunications.
telephone line
local
modem
RS-232 to RS-485
converter
RS-485
devices
remote
modem
RightclicktheworkstationiconandselectInsertItem.
2.
SelectSiteandclickOK.
3.
OntheGeneraltab,usetheNameboxtoenteranameidentifyingthismodem
site.Enterthephonenumberinthebox.SelectModem,thenusetheModem
configurationbuttontosetupthecommunicationsport.Followthedirections
provided.
4.
TheTimingsandPollingtabscontainothercommunicationsparameters;you
canmodify.In mostcases,youdonotneedtochangethedefaultsettings.
ModemGate feature
SomeIONmetersareequippedwithaninternalmodemthatyoucansetupasa
communicationsgatewaytoconnecttomultipleRS485devices(e.g.onaremote
site).Formoreinformation,refertothetechnicalnoteTheIONmeterasa
ModemGate.
Page 11
Chapter 1 - Introduction
Ethernet sites
IfthedeviceisequippedwithanEthernetcommunicationscard,youcanusean
Ethernetcabletoconnectittoyourlocalorwideareanetwork(LAN/WAN).
MakesuretheEthernetcommunicationsparametersaresetcorrectlyforeach
device(forexample,IP address,subnet mask,default gateway,media type).
Ethernet
devices
LAN / WAN
Page 12
1.
RightclicktheworkstationiconandselectInsertItem.
2.
SelectSiteandclickOK.
3.
SelectEthernet,thenclickOK.
4.
TheTimingsandPollingtabscontainothercommunicationsparameters;you
canmodify.In mostcases,youdonotneedtochangethedefaultsettings.
Chapter 1 - Introduction
NOTE
For the Ethernet gateway devices serial port, set the baud rate to the same setting as all the RS-485
devices connected to it. If the serial port parameter setting can be configured, set it to 8N1 (no parity).
Additionalsettingsmaybeavailablerefertothedocumentationthatcamewith
yourEthernetgatewaydevice.
Ethernet
gateway
device
LAN / WAN
Ethernet
RS-485
devices
serial RS-485
PM8ECC considerations
SimilartotheEGXseriesgateway,thePM8ECCEthernetcommunicationscard
providesEthernetaccesstomultipleRS485devicesthatareconnectedtothe
PM8ECCsRS485port.AfterwiringtheRS485devicestothePM8ECC,useaweb
browsertologintothePM8ECC.Browsetothedevicelistpageandentereach
devicethatisconnectedtothePM8ECCsRS485port.Settheappropriatedevice
addressanddevicetypeforeachdevice.RefertothePM8ECCInstallationGuide.
Page 13
Chapter 1 - Introduction
Page 14
1.
RightclicktheworkstationiconandselectInsertItem.
2.
SelectSiteandclickOK.
3.
SelectEthernet,thenselecttheGatewaybox.
4.
IntheGatewayInfoboxes,entertheIPaddress,thentypeorselectthe
appropriateportnumber.Forexample,select502forModbusTCP
communications.
5.
TheTimingsandPollingtabscontainothercommunicationsparameters;you
canmodify.In mostcases,youdonotneedtochangethedefaultsettings.
In This Chapter
E5600 meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
MetersetupthroughIRopticalport ..................................... 16
MetersetupthroughRS485............................................ 18
Firmware upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Meter protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Page 15
NOTE
Meter password protection can only be done through the IR optical port.
Tools required
PleaseensureyouhavethesethingsavailablebeforestartingtosetupyourE5600
meter:
Computer(loadedwithlatestversionofIONSetup)
Optional:ANSIC12.19typeIIopticalprobe(refertotheE5600Installationand
OperationGuideforthemetersfrontopticalportspecifications)
Optional:Strongmagnet(suchasarareearthorsimilarpermanentmagnet)
NOTE
Optional tools are required to communicate with your meter through the IR optical port.
Computer configuration
Thisdescribeshowtoconfigurethecomputerscommunicationportforoptical
probecommunication,andhowtoidentifywhichportisbeingusedbytheoptical
probe.
BeforestartingIONSetup,connecttheE5600metertoyourcomputerusingan
ANSIC12.19typeIIopticalprobe.IftheWindowsdriverfortheUSBopticalprobe
isnotinstalled,Windowsdetectstheopticalprobeasnewhardwareandprompts
youtosearchforacompatibledriver.Usetheinstallationdiscthatcamewiththe
opticalprobetoinstallthedriver,ordownloadtheappropriatedriverfromthe
opticalprobemanufacturerswebsite.
OpenyourcomputersDeviceManagertoseewhichserialportnumberis
assignedtotheopticalprobe:
Page 16
1.
RightclickMyComputerandselectManage.
2.
ExpandSystemToolsandselectDeviceManager.
3.
ExpandPorts.
4.
Notetheopticalprobesserialport#.
5.
ClosetheComputerManagementscreen.
Meter communication
Thisdescribeshowtoputthemeterintodiagnosticmodesothatitcanbe
configuredthroughtheIRopticalportusingIONSetup.
1.
Putthemeterintodiagnosticmode.
Toputthemeterintodiagnosticmode,holdastrongmagnetoverthemeter,
approximatelyatthe12oclockposition,toactivatethereedswitch.When
thereedswitchisactivated,themetersdisplaywillshowallsegments,then
ablankscreen,andthenwillstarttodisplaythediagnosticdisplay
sequence.
12 oclock
Donotremovethemagnetfromthemetersreedswitchwhilecommunicating
throughthemetersIRport.
NOTE
RS-485 (Modbus) data will not be updated while the meter is communicating via the front optical port.
2.
StartandlogontoIONSetupusingsingledeviceconfigurationmode(i.e.,make
suretheSingleIONdeviceconfigurationmodecheckboxisselected).
Page 17
3.
IntheConnectionTypedialog,selecttheopticalprobesserialportnumber.
4.
ClickOK.
IONSetupattemptstoestablishaconnection(9600baud,ANSIprotocol)tothe
device.Ifcommunicationattemptsfail,closeIONSetup,checktomakesure
thereisgoodphysicalconnectionbetweenthecomputerandthemeterand
ensurethatthemagnetisactivatingthereedswitch.RestartIONSetupandtry
connectingtothedeviceagain.
5.
ConfiguretheE5600meter.Thesetupscreensaredetailedinthesection,Meter
setupthroughRS485.
Page 18
1.
IfyourmeterisconnectedthroughtheIRopticalport,exitIONSetupthen
removethemagnetfromthemeter.
2.
MakesuretheE5600metersRS485portisconnectedtothecomputer(through
anRS232toRS485converteroranEthernetgatewaydevice).
3.
StartandlogontoIONSetupusingnetworkmode(makesuretheSingleION
deviceconfigurationmodecheckboxonthelogonpromptiscleared).
4.
CreateandconfigureanewsiteforyourE5600meter,oruseanexistingsiteif
appropriate(i.e.,ifanexistingsitealreadyexistsandyouhavewiredtheE5600
communicationsporttousethatcommunicationslink).Refertothe
Introductionsectionfordetailsonaddingsitesandmeters.
5.
AddtheE5600metertothesite.ForUnitID,entertheModbusaddressyouset
forthedevice(refertoRS485Commonpage 22).
6.
ConfiguretheE5600meterssetupparameters.
Basic Setup
Usethisscreentoconfigurethemetersprimaryandsecondarytransformer
values.
1.
SelectthePTMultiplierparameterandclickEdit.
2.
ThePT/CTMultiplierSetupscreenappears.EnterthePTMultipliervalueand
clickOK.
ThePTMultiplierisapositiveintegerthatrepresentsthePTprimarytoPT
secondaryratio.Forexample,ifPTprimary=480VandPTsecondary=120V,
thenPT Multiplier = 4.
3.
RepeatfortheCTMultiplierparameter.
TheCTMultiplierisapositiveintegerthatrepresentstheCTprimarytoCT
secondaryratio.Forexample,ifCTprimary=500AandCTsecondary=5A,
thenCTMultiplier=100
ClickSendtosaveyourchangestothemeter.
Clock
To manually set the meters local time
1.
SelecttheDate/TimeparameterandclickEdit.
2.
UsetheDatedropdownbuttontodisplaythecalendar.Youcanusetheleftor
rightscrollbuttontochangethemonth.Clickthecalendardaytosetthemeter
date.
3.
Clickthehour,minute,secondorAM/PMsetting,thenusetheup/downscroll
buttons(oruseyourcomputerskeyboard)tochangethevalue.
Thetimeinformationissenttothemeterexactlyasentered.Nocorrections(such
asDaylightSavingsTime)areappliedto,orsupportedbythemeter.
4.
ClickOKthenSendtosetthedateandtime.
NOTE
The E5600s front panel display shows hours and minutes in 24 hour clock format.
Page 19
Demand
Demandistheaveragepowerconsumptionoverafixedtimeperiod(demand
period),typically15 minutes.
1.
SelectIntervalLengthparameterandclickEdit.
2.
SelecteitherBlockDemandorSlidingWindowDemand.
BlockDemand:SelecttheBlockLengthfromthedropdownlist.
SlidingWindowDemand:SelecttheappropriatePeriod/SubIntervalfrom
thedropdownlist.Forexample,ifyourequirea30minuteintervalbroken
intotwoperiodsof15minuteseach,select2x15minutes.
3.
ClickOKthenSendtosaveyourchangestothemeter.
Device Labels
SelectDeviceIdentificationandclickEdit.TypethedevicelabelfortheE5600
meterintheEnterDeviceIdentificationbox.Thedevicelabelcanbe118ASCII
characters.
ClickOKthenSendtosaveyourchangestothemeter.
Energy Pulsing
EnergypulsingtransitionsthedigitaloutputKYrelay(fromlowhigh,orhigh
low)eachtimethesourceenergyparameterincreasesbytheKevalue.Thereare
twodigitaloutputsontheE5600.
Enable
UsethistoenableordisableenergypulsingforthatKYrelay.
Source
UsethistoselecttheenergymeasurementforKYrelaypulsing.
Ke Value
Usethistosettheamountthatthesourcemustincreasebeforethedigitaloutput
transitions.Youmustsetthistoanumericvaluebetween0.001and16,inorderto
enableenergypulsingthroughthedigitaloutput.
NOTE
If Ke is zero (0) the associated KY relay is disabled. You must enter a valid Ke value (between 0.001 and
16) before you can enable the associated KY relay.
Page 20
1.
Selectaparameter(Enable,SourceorKeValue),thenclickEdit.
2.
Modifytheparameterbyenteringtherequiredvalueorselectinganoptionfrom
thedropdownlist.
3.
ClickOKthenSendtosaveyourchangestothemeter.
Select#ofDisplays,thenclickEdit.
2.
UsetheDisplayEditorwindowtoedit,addordeletethedisplayedparameters.
Toeditthedisplayedparameter,selectit,thenclickEdit.IntheDisplay
ScreenSetupwindow,usetheParameterboxtoselectthequantityyouwant
todisplay.UsetheIndicatorboxtoassignathreecharacterlabelforthe
displayedparameter.
Toaddanewdisplayscreen,clickNew.SettheParameterandIndicatoras
describedabove.
Todeleteadisplayscreen,selectitthenclickDelete.
3.
ClickExittoreturntotheFrontPanelDisplaysetupscreen,thenclickSendto
saveyourchangestothemeter.
Display On Time
Youcanconfigureadurationfrom1secondto15seconds.
1.
SelectDisplayOnTime,thenclickEdit.
2.
EntertheDisplayOnTimeinthespaceprovidedandclickOK,thenclickSend
tosendyourchangestothemeter.
Meter Resets
Usethissetupscreentoenableordisableresetfunctionsforthemeter.
1.
SelectaresetparameterthenclickEdit.
PeakDemandReset:clearspeakdemandvalues.
MasterReset:clearsalldemandandenergyvalues,andclearstheload
profile.
EnergyReset:clearsallenergyaccumulatedvalues(total,delievered,
recieved).
2.
UsethedropdownboxtoselectResetorNoReset,thenclickOK.
ClickSendtosaveyourchangestothemeter.
Page 21
RS-485 Comm
UsethissetupscreentoconfiguretheE5600metersRS485communications
settings.
Default RS-485 settings
Parameter
Value
Modbus Address
Baud Rate
9600 bps
Parity
No parity or None
NOTE
Changing RS-485 Comm parameters while communicating through the RS-485 port will cause you to
lose communications with your meter.
Modbus Address
Usethistosetthedeviceaddress(unitID)fortheE5600meter.Theallowable
Modbusaddressrangeis1to247.MakesuretheModbusaddressisuniquetoeach
deviceonthatRS485loop.
Baud Rate
UsethistosetthebaudrateforRS485communications.Makesurealldevices
connectedonthesameRS485looparesettothesamebaudrate.
Parity
Makesurethecommunicationslink(site)andalldevicesconnectedtothatsiteare
settothesameparitysetting.
NOTE
For serial sites the parity must be set to no parity (Parity = None) for ION Setup to communicate. For
other site types, the meters RS-485 parity must match the site parity.
Page 22
1.
Selectaparameter(ModbusAddress,BaudRateorParity)andclickEdit.
2.
Aparametereditingscreenappears.Entertheappropriatevalueintothefieldor
usethedropdownlistsandclickOK.
3.
ClickSendtosaveyourchangestothemeter.
Firmware upgrade
YoucanupgradetheE5600communicationcardsfirmwarethroughtheRS485
port.
1.
MakesureallnecessaryinformationfromtheE5600meterhasbeenrecorded.
2.
SavetheE5600firmwareupgradefiletoyourcomputerdesktoporalocalfolder.
3.
RightclicktheE5600metericonandselectProperties.
4.
ClicktheToolstab,thenclickFirmwareUpgrade.
5.
Apromptdisplays,alertingyouthatallrecordeddataforthedevicewillbe
reset.ClickOKtoproceed.
NOTE
During firmware upgrade the meters I/O may de-energize or change state.
6.
Navigatetothelocationwhereyousavedthefirmwareupgradefile,selectit
thenclickOpen.
7.
EntertheIONSetuppasswordtoupgradethefirmware.
NOTE
Do not have any other communications taking place on your RS-485 network while your meter is going
through a firmware upgrade.
Whileyourmeterisundergoingafirmwareupgradeitwillcontinuetomeasure
andlogdata,butitwillnotupdaterealtimedisplayedvaluesuntiltheupgradeis
completed.
Page 23
Meter protection
Meterprotectioncanbeconfiguredonlythroughthefrontopticalport.SeeMeter
setupthroughIRopticalportonpage 16forconnectiondetails.StartIONSetup
insingledevicemode.
DoubleclickMeterProtection.
2.
SelectProtectionLockoutthenclickEdit.
3.
Typeanumericpasswordinthebox,thenclickEnable.Makesureyoudonot
loseorforgetthepassword,asthisistheonlywaytodisableprotectionlateron.
4.
ClickSendtosavethechangestothemeter.
WithapasswordprotectedE5600meter,youcanstillmakechangestothesesetup
screensthroughtheRS485connection(theseparametersarenotprotectedfrom
modifications):
FrontPanelDisplay
RS485Comm
NOTE
Do not lose or forget your password. If you lose your password and need to modify the locked
parameters, a factory reconfiguration is required, which will reset your meter to its factory defaults and
destroy all logged data.
Page 24
In this chapter
PM700 series meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
UsingIONSetup ..................................................... 26
PM700 series setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
BasicSetup .......................................................... 26
Demand ............................................................. 27
FrontPanelDisplay ................................................... 27
I/OSetup............................................................ 28
OnboardAlarms ..................................................... 28
SerialComms........................................................ 30
Page 25
NOTE
The procedures described here only apply to the meter models that are equipped with communications
(i.e., the PM710 and PM750 meters, but not the PM700 and PM700P).
ThePM700seriesmeterusesModbusRTUprotocoltocommunicatethroughits
RS485serialcommunicationsport.
Devicecommunicationssettings:MakesureallthedevicesonthesameRS485
looparesettothesamebaudrateandparity.Recommendedsettingforparityis
None(no parity).
Deviceaddress(unitID)settings:Makesurethedeviceaddress(unitID)is
uniqueforeachdeviceinagivenRS485loop(range=1to247forModbus
devices).
Basic Setup
System Type
SelecttheoptionthatdescribeshowyourPM700seriesmeteriswiredtothe
electricalservice.RefertothePM700seriesmeterinstallationguidefordetailson
thedifferentsystemtypes.
PT Ratio
Selecttheappropriatescalevalue(multiplier)forthePTprimary.Fordirect
connect,selectNo PTs.
Page 26
PT Primary
EnterthevalueforthePTprimary,inVolts.
PT Secondary
SelectthevalueforthePTsecondary.
CT Primary
EnterthevaluefortheCTprimary,inAmps.
CT Secondary
SelectthevaluefortheCTsecondary.
Service Frequency
Selectthesystemfrequencyoftheelectricalservice.
Demand
Demandistheaveragepowerconsumptionoverafixedtimeinterval(demand
period),typically15 minutes.
Demandvaluesarecalculatedforeachsubinterval,thenaveragedoverthe
numberofsubintervalsthatmakeupthedemandperiod.
Thermal Dmd Period (mins)
Enterthelengthofthedemandperiod,inminutes.
Block Dmd Period (mins)
Enterthelengthofeachrollingblockperiod(subinterval),inminutes.
Block # of Sub-Intervals
Enterthenumberofsubintervalsusedforcalculatingdemand
NOTE
Refer to the PM700 series documentation for details on how the meter calculates demand.
Page 27
I/O Setup
RefertothePM700seriesmeterdocumentationforI/Odescriptionsand
configurationdetails.
Digital Out KY
Label:ThisfieldidentifiestheKYdigitaloutput.
Mode:SelecttheKYdigitaloutputmodeofoperation.
ExternalControlconfigurestheoutputtobecontrolledbyacommandsent
overthecommunicationslink.
PMAlarmconfigurestheoutputtobecontrolledbythepowermeterin
responsetoasetpointcontrolledalarmcondition.
kWhoutpulsesetsthemetertogenerateafixeddurationpulseoutputthat
canbeassociatedwiththekWhconsumption.UsethePulseWeight
registertoenterhowmanykWhoutoftheloadareassociatedwitheach
pulseoftheKYdigitaloutput.ThenusethePulseDurationboxtoselect
thepulsewidth(inmilliseconds)foreachkWhpulse.
Digital In S1 and S2 (PM750 only)
Label:Thisfieldidentifiesthedigitalinput.
Mode:SelecttheoperationmodefortheSIdigitalinput:
Forsimpleon/offdigitalinputoperation,selectNormal.
SelectDemandIntervalSyncPulseiftheSIdigitalinputisconfiguredas
thedemandsyncinput.
Onboard Alarms
TheOnboardAlarmssetupscreenallowsyoutomakechangesto15
preconfiguredalarms(13standardalarmsand2digitalinputalarms).Refertothe
PM750ReferenceManualforalistingofthesealarms.
Page 28
SelectAllAlarms,thenclickEdit.
Alarm source
or input
Condition
Multiplier
2.
IntheAlarmSetupscreen,selectthestandardalarmyouwanttoset.
Enable:Selectthischeckboxtoenablethealarm
Label:Ifrequired,usethisboxtorenametheselectedalarm
SetpointPickup:Enterthemagnitudeabove(forOver)orbelow(for
Under)thatdefinesthealarmONcondition,thenintheDelayboxenter
thenumberofsecondsthealarmONconditionneedstobetruebeforethe
alarmisactivated.
SetpointDropout:Enterthemagnitudebelow(forOver)orabove(for
Under)thatdefinesthealarmOFFcondition,thenintheDelayboxenter
thenumberofsecondsthealarmOFFconditionneedstobetruebeforethe
alarmisdeactivated.
NOTE
Pay special attention to the multipliers for Setpoint Pickup and Setpoint Dropout settings, and adjust the
values if needed.
AssociateOutput:Selectthischeckboxtoassociatethealarmcondition
withanoutput(e.g.,themetersdigitaloutput).
Redefining a preconfigured alarm
Youcanredefineapreconfiguredalarmbychangingthealarmcondition(Over
orUnder)and/orselectingadifferentalarmsourceorinput.Makesureyou
updatetheLabelfieldasappropriate.
Forexample,StatusInputOncanmeanthealarmisactivatedwhenthedigital
inputisswitchedon,whileStatusInputOffcanmeanthealarmisactivated
whenthedigitalinputisswitchedoff.
Page 29
SelectAllAlarms,thenclickEdit.
Alarm source
or input
Condition
2.
IntheAlarmSetupscreen,selectthedigitalinputyouwanttoconfigurefor
alarming.
Enable:Selectthischeckboxtoenablethealarm
Label:Ifrequired,usethisboxtorenametheselectedalarm
AssociateOutput:Selectthischeckboxtoassociatethealarmcondition
withanoutput(e.g.,themetersdigitaloutput)
Serial Comms
Modbus Address
ThisdisplaystheModbusaddress(unitID)ofthemeter.
Baud Rate
Thisdisplaysthemetersbaudratesetting.
Page 30
In this chapter
PM800 series meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
PM8ECCconsiderations ............................................... 32
UsingIONSetup ..................................................... 33
PM800 series setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
AlarmLog ........................................................... 34
BasicSetup .......................................................... 34
BillingLog ........................................................... 35
Clock ............................................................... 36
CommECCCard .................................................... 36
CommOnboardSerial ............................................... 36
DataLog#1,DataLog#2,DataLog#3,DataLog#4....................... 37
DeviceLabels ........................................................ 37
EN50160Setup....................................................... 38
Energy&Demand .................................................... 38
FrontPanelDisplay ................................................... 39
I/OSetup............................................................ 39
InputMetering ....................................................... 42
MeterResets......................................................... 42
MeteringStandards ................................................... 43
OnboardAlarms/Events ............................................... 43
ShiftEnergy.......................................................... 50
Trending&Forecasting................................................ 50
WaveformCapture ................................................... 51
Page 31
PM8ECC considerations
IfyourPM800seriesmeterisequippedwiththePM8ECCEthernet
communicationcard,youcancommunicatetothemeterdirectlythroughits
Ethernetport.
NOTE
Refer to the PM8ECC documentation for instructions on how to set up the device parameters such as
Ethernet & TCP/IP settings.
Page 32
1.
StartIONSetupinNetworkMode(i.e.cleartheSingleIONdevice
configurationmodecheckboxwhenyoulogon).Youmustaddand
configureanEthernetsiteiftherearenoEthernetsitesonyourIONSetup
network.
2.
RightclicktheEthernetsiteiconandselectInsertItem.SelectMeterandclick
OK.
3.
TypeadescriptivenameforyourPM800seriesmeter.Selectthetypeofdevice
(i.e.,PM800series).TypetheIPaddressofthePM8ECC.IntheIP Portbox,type
502.SelectGroup.ClickOK.
StartIONSetupinNetworkMode(i.e.,cleartheSingleIONdevice
configurationmodecheckboxwhenyoulogon).
2.
Addanewsite.SelectEthernet,thenselecttheGatewaybox.
3.
IntheGatewayInfoboxes,entertheIPaddressofthePM8ECC.IntheIP Port
box,type502.ClickOK.
NOTE
The IP Port must be set to 502 for Modbus TCP communication.
Page 33
NOTE
Some setup screens only apply to particular models (e.g., waveform capture for the PM870), while other
screens apply only to installed options (such as the Comm - ECC setup screen for meters equipped with
the optional PM8ECC Ethernet communications card). Refer to your meter documentation for details on
supported features.
Alarm Log
Status
Selecttheappropriateoptiontoenableordisablealarmlogging.
Basic Setup
System Type
SelecttheoptionthatdescribeshowyourPM800seriesmeteriswiredtothe
electricalservice.RefertothePM800seriesmeterdocumentationfordetails.
Primary Scale Factor
Selecttheappropriatescalevalue(multiplier)forthePTprimary.Fordirect
connect,selectNo PTs.
PT Primary
EnterthevalueforthePTprimary,inVolts.
PT Secondary
SelectthevalueforthePTsecondary.
CT Primary
EnterthevaluefortheCTprimary,inAmps.
CT Secondary
SelectthevaluefortheCTsecondary.
Service Frequency
Selectthesystemfrequencyoftheelectricalservice.
Nominal Voltage
Enterthenormalordesignedvoltageleveloftheelectricalservice,inVolts.
Nominal Current
Enterthenormalordesignedcurrentleveloftheelectricalservice,inAmps.
Page 34
Billing Log
Status
Selecttheappropriateoptiontoenableordisablethebillinglog.
Interval (mins)
Enterhowoften(inminutes)thebillingquantitiesshouldbelogged.
Channels
Thisallowsyoutoselectwhichparameterstoincludeinthebillinglog.
1.
SelectChannels,thenclickEdit.
2.
Toaddorremoveaparameterfromthebillinglog:
Addingparameters:UnderAvailable,clickthe+signtoexpandand
displayindividualparameters.Clickaparametertoselectit,thenclickthe
buttontomovetheparametertoSelected.
Removingparameters:UnderSelected,clicktheparameteryouwantto
remove,thenclickthe
button.
3.
ClickSendtosavethechangestothemeter.Thefollowingpromptappears:
4.
NotethatclickingYeswillpowercycle(reset)thedevice.ClickYestoconfirm,
orNotocancelandgobacktothepreviousdialog.
Page 35
Clock
TheClocksetupscreenallowsyoutosetthedateandtimeonthemeter.ClickEdit
tochangethedate/timesetting,thenclickSend.
Page 36
NOTE
The remote display adapter (PM8RDA) provides an additional serial communications port (COM2).
However, this COM2 port becomes unavailable if you connect an Ethernet communications card
(PM8ECC) to the meter.
Data Log #1, Data Log #2, Data Log #3, Data Log #4
Status
Selecttheappropriateoptiontoenableordisablethedatalog.
Interval
Thisallowsyoutosettheloggingmodeandintervalforthedatalog.
1.
SelectInterval,thenclickEdit.
2.
UsetheModeboxtoselectOnlyOnEvent,Continuous,orStart/Stop(referto
themeterdocumentationformoreinformation).Enterhowoften(inminutes)
theparametersshouldberecordedinthedatalog.
3.
ClickOK.
Channels
Thisallowsyoutoselectwhichparameterstoincludeinthedatalog.Thesetup
procedureissimilartotheonedescribedintheBillingLogsection,under
Channelsonpage 35.
Device Labels
Device Label
Youcanusethistextfieldtoassignalabel(e.g.,anabbreviation)foryourmeter.
Device Nameplate
Youcanusethistextfieldtodescribeyourmeter(e.g.,type,locationorother
devicedetail).
Page 37
EN50160 Setup
EN50160 Evaluation
SelecttheappropriateoptiontoenableordisabletheEN50160evaluationfeature.
First Day of Week
SelectSundayorMondaytobethefirstdayoftheweek.
Interruption (% Nominal)
Enterthevaluethatdefineswhatconstitutesavoltageinterruption,expressedas
apercentageofnominalvoltage.Forexample,ifInterruption(% Nominal)isset
to1%,avoltageinterruptionisrecordedifthevoltagedropsbelow99%ofits
nominalvalue.
Max Short Interruption (secs)
Enterthelongesttimeduration,innumberofseconds,thatdefinesashort
interruption.Forexample,ifMaxShortInterruption(secs)issetto270seconds,
avoltageinterruptionlastinglongerthanthattimeisconsideredalong
interruption.
Slow Voltage Variations
Enterthevaluethatdefinestheallowablerangeofslowvoltagevariations,
expressedasapercentageofnominalvoltage(typically+/10%ofnominal).
Voltage for 4-Wire Systems
Selectwhetherthevoltagefora4wiresystemisexpressedasLinetoNeutralor
LinetoLine.
Frequency Configuration
SelectSynchronousforasystemwithasynchronousconnectiontoan
interconnectedsystem,orUnsynchronousforasystemwithoutasynchronous
connectiontoaninterconnectedsystem.
Formoreinformation,refertothePM800seriesReferenceManual.
Page 38
Power Sub-Interval
Enterthedurationofeachsubinterval(fordemandpower),inminutes.
Current Mode
Selectwhichtechniqueisusedtocalculatedemandcurrent.
Current Interval
Enterthedurationofeachdemandinterval(forcalculatingdemandcurrent),in
minutes.
Current Sub-Interval
Enterthetimeperiodforeachsubinterval(fordemandcurrent),inminutes.
I/O Setup
RefertothePM800seriesmeterdocumentationforI/Odescriptionsand
configurationdetails.
Digital Out KY
Label:TypeanameidentifyingtheKYdigitaloutput.
Mode:SelecttheKYdigitaloutputmodeofoperation:
Normal:UsethismodefornormalON/OFFoperationoftheKYdigital
output.
ForTimedorEndofDemandIntervalmode,usetheHoldTimeregister
toenterhowmanysecondstheKYdigitaloutputremainsenergized.
ForAbsolutekWhpulse,AbsolutekVARhpulseorkVAhpulsemode,use
thePulseWeightregistertoenterhowmanyabsolutekWh(intoandout
oftheload),absolutekVARh(intoandoutoftheload)orkVAhare
associatedwitheachpulseoftheKYdigitaloutput.
ForkWhinpulseorkVARhinpulsemode,usethePulseWeightregister
toenterhowmanykWhorkVARhintotheloadareassociatedwitheach
pulseoftheKYdigitaloutput.
Page 39
ForkWhoutpulseorkVARhoutpulsemode,usethePulseWeight
registertoenterhowmanykWhorkVARhoutoftheloadareassociated
witheachpulseoftheKYdigitaloutput.
Ifsettoanyoftheabovepulsemodes,theDigitalKYOutputwillpulsebased
onanenergyperpulsevalue.RefertothePM800seriesreferencemanualfor
detailsondeterminingthevalueofthePulseWeightsetting.
Control:ForNormal,LatchedorTimedmodeofoperation,selecthow
theKYdigitaloutputiscontrolled,i.e.,eitherExternallyControlledor
controlledbypowermeteralarm(PMAlarm).
NOTE
For detailed descriptions on the different Mode and Control options, refer to the Relay Output Operating
Modes section in the PM800 series reference manual.
Digital In SI
Label:TypeanameidentifyingtheSIdigitalinput.
Mode:SelecttheoperationmodefortheSIdigitalinput.Fordetailed
descriptionsonthedifferentmodes,refertotheDigitalInputssectioninthe
PM800seriesreferenceManual.
Normal:UsethismodefornormalON/OFFoperationofthedigitalinput.
DemandIntervalSyncPulse:UsethismodetoconfiguretheSIdigital
inputasthedemandsyncinput(toreceiveademandsyncpulsefroma
utilitydemandmeter,forexample).
ConditionalEnergyControl:UsethismodetoconfiguretheSIdigital
inputforconditionalenergycontrol.
PulseWeight:ForNormalorInputMeteringmodeofoperation,enterthe
pulseweightassociatedwiththechangeofstateoftheinput.
Units:ForNormalorInputMeteringmodeofoperation,selecttheunitof
measurementassociatedwiththeSIdigitalinputpulse(ifapplicable).
Page 40
NOTE
For detailed descriptions on the different modes of operation, refer to the Relay Output Operating
Modes section in the PM800 series reference manual .
ClickOK.Configuretheotherrelaysasrequired.
Digital In A-S1, Digital In A-S2 Digital In A-S6,
Digital In B-S1, Digital In B-S2 Digital In B-S6
Label:Typeanameidentifyingthedigitalinput.
Mode:Selectthedigitalinputmodeofoperation(Normal,DemandInterval
SyncPulse,ConditionalEnergyControl,orInputMetering).
PulseWeight:ForNormalorInputMeteringmode,enterinthePulse
Weightboxhowmanyunitsofameasuredorcalculatedquantityis
associatedwitheachpulse.
Units:ForNormalorInputMeteringmode,selecttheunitsusedforthe
measuredorcalculatedquantity(ifapplicable).
NOTE
For detailed descriptions on the different modes of operation, refer to the Digital Inputs section in the
PM800 series reference manual .
Analog I/O
RefertothePM800seriespowermeterinput/outputmoduleinstallationmanualfor
instructionsonhowtosetuptheanaloginputs(Analog In AAI1,
Analog In AAI2,Analog In BAI1,Analog In BAI2)andanalogoutputs
(Analog Out AAO1,Analog Out AAO2,Analog Out BAO1,
Analog Out BAO2):
AnalogInputs
Label:Thisnameidentifiesthespecificanaloginput.
Units:Definestheunitsofthemonitoredanalogvalue.
Scalefactor:Defineswhatmultiplierisusedonthemeasuredvalue.
ReportRangeLowerLimit:Thisisthevaluethepowermeterreportswhen
theinputreaches(ordropsbelow)thelowestvalidreading.
ReportRangeUpperLimit:Thisisthevaluethepowermeterreportswhen
theinputreaches(orexceeds)thehighestvalidreading.
AnalogOutputs
Label:Thisnameidentifiesthespecificanalogoutput.
Outputregister:Definesthepowermeterregisterassignedtotheanalog
output.
LowerLimit:Thisistheminimumoutputcurrentthatthepowermeter
sendstotheanalogoutputwhentheregistervaluereaches(ordropsbelow)
thelowerlimit.
Page 41
UpperLimit:Thisisthemaximumoutputcurrentthatthepowermeter
sendstotheanalogoutputwhentheregistervaluereaches(orexceeds)the
upperlimit.
Input Metering
Refertothemeterdocumentationfordetaileddescriptionsonmetering
capabilitiesandoptions.
Demand Method
Selectwhichmethodisusedforcalculatingdemand.
Demand Interval
Enterthetimeperiodforeachdemandinterval,inminutes.
Demand Sub-Interval
Enterthetimeperiodforeachdemandsubinterval,inminutes.
Channel 1, Channel 2 Channel 5
Beforeyoucanassociateadigitalinputtoachannel,youneedtosetupthedigital
inputforinputmeteringoperation.RefertoI/OSetuponpage 39fordetails.
1.
FromtheInputMeteringsetupscreen,selectoneoftheavailablechannels.
2.
IntheLabelfield,enteradescriptivenameforthechannel.
3.
Selecttheappropriateunitsandrate.Theunitsyouselectmustmatchtheunits
youselectedforthedigitalinput(whenyouconfigureditforinputmetering).
4.
IntheAvailableInputscolumn,selectthedigitalinput,thenclickthe
buttontomoveittotheAssignedInputscolumn.
(Tounassigntheinput,selectitfromtheAssignedInputscolumn,thenclick
the
button.)
NOTE
Usually, input metering applications also require one input to be set up for Demand Interval Sync Pulse,
to allow customers to synchronize their demand intervals to the utility (typically, the pulse signal is
provided by the utility). To set up an input for demand interval sync pulse, refer to I/O Setup on
page 39.
Meter Resets
Toresetthemeter,doubleclickMeterInitthenselectReinitialize.ClickOK.
ClickSendtoinitializethemeter.Attheprompt,clickYestoproceed,orNoto
aborttheinitialization.
Page 42
NOTE
Initializing a meter will reset or disable certain parameters. Make sure you read the warning prompt
before proceeding.
Metering Standards
Harmonic Distortion
Selecthowtotalharmonicdistortioniscalculated.
PF Sign Convention
SelectwhichstandardsconventiontousefordisplayingPFsign.
Voltage Harmonic Method
Selecthowthemagnitudeofvoltageharmonicisdisplayed.
Current Harmonic Method
Selecthowthemagnitudeofcurrentharmonicisdisplayed.
Onboard Alarms/Events
Standard
Thisallowsyoutoconfigurethestandardalarms.SelectStandardthenclick
Edit.
2
5
6
7
9
11
10
12
13
Thenumberedlabels(onthedrawing)aredescribedbelow:
1.
Theleftcolumnliststhestandardalarms.Selectaniteminthislisttoeditit.
Page 43
2.
Thetwoboxesatthetopliststhestandardalarmconditionandmeasurement
thatdefinesthehighlightediteminalarmslist.Youcanusetheseboxesto
changetheconditionandmeasurementforthisalarm.
3.
SelecttheEnableboxtoenabletheselected(highlighted)alarminthelist,or
cleartheboxtodisablethealarm.
4.
TheLabelboxidentifiesthenameofthestandardalarm.Usethisboxto
renamethealarmasnecessary(e.g.,ifyouchangedtheconditionor
measurementforthestandardalarm).
5.
Enterthesetpointpickupvalue(absoluteorrelative,seeitem#7below)andthe
pickupdelay(inseconds).
6.
Enterthesetpointdropoutvalue(absoluteorrelative,seeitem#7below)andthe
dropoutdelay(inseconds).
7.
Tospecifyabsolutevaluesforthesetpointpickupanddropoutlimits,clear
(uncheck)theRelative(%ofAvg)box.Tospecifysetpointpickupand
dropoutlimitsasapercentageaboveorbelowtheRMSaveragevalue(Avg),
select(check)theRelative(%ofAvg)box.
8.
UsethePriorityboxtosetthealarmpriority.
9.
UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedto
recordtheselectedalarm.
10. SelecttheWaveformCaptureboxtotriggerawaveformcaptureonalarm,or
cleartheboxtodisablewaveformcaptureonalarm.
11. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutput
button,selectoneoftheavailableoutputs,thenclickthe
buttonto
moveittotheSelectedcolumn.ClickOK.
12. Tocreateanewalarm,clickAdd,thenspecifythealarmconditionand
measurement,asdescribedintheprevioussteps.
NOTE
There is a limit to the number of alarms you can create. The Add button is disabled once that limit is
reached. In this case, you must delete an existing alarm before you can create a new one (or you can
select an existing alarm and edit/configure it as necessary).
13. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.
Tosavethechangestothemeter,clickSend.Dependingonthetypeofchanges,a
meterresetmightoccur:
Page 44
NotethatclickingYeswillpowercycle(reset)thedevice.ClickYestoconfirmand
proceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.
Formoreinformationonconfiguringthealarms,refertothePM800seriesReference
Manual.
Disturbance (PM870 only)
Thisallowsyoutoconfigurethedisturbancealarms(i.e.voltagesagsandswells).
SelectDisturbancethenclickEdit.
2
5
6
7
9
11
10
12
13
Thenumberedlabels(onthedrawing)aredescribedbelow:
1.
Theleftcolumnliststhedisturbancealarms.Selectaniteminthislisttoeditit.
2.
Thetwoboxesatthetopliststhedisturbancealarmconditionandmeasurement
thatdefinesthehighlightediteminalarmslist.Youcanusetheseboxesto
changethecondition(sagorswell)andmeasurement(currentorvoltage)fora
selectedalarm.
3.
SelecttheEnableboxtoenabletheselected(highlighted)alarminthelist,or
cleartheboxtodisablethealarm.
4.
TheLabelboxidentifiesthenameofthedisturbancealarm.Usethisboxto
renamethealarmasnecessary(e.g.,ifyouchangedthecondition/measurement
forthedisturbancealarm).
5.
Enterthesetpointpickupvalue(absoluteorrelative,seeitem#7below)andthe
pickupdelay(innumberofcycles).
6.
Enterthesetpointdropoutvalue(absoluteorrelative,seeitem#7below)andthe
dropoutdelay(innumberofcycles).
7.
Tospecifyabsolutevaluesforthesetpointpickupanddropoutlimits,clear
(uncheck)theRelative(%ofAvg)box.Tospecifysetpointpickupand
dropoutlimitsasapercentageaboveorbelowtheRMSaveragevalue,select
(check)theRelative(%ofAvg)box.
Page 45
8.
UsethePriorityboxtosetthealarmpriority.
9.
UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedto
recordtheselectedalarm.
10. SelecttheWaveformCaptureboxtotriggerawaveformcaptureonalarm,or
cleartheboxifyoudonotwanttotriggerawaveformcaptureonalarm.
11. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutput
button,selectoneoftheavailableoutputs,thenclickthe
buttonto
moveittotheSelectedcolumn.ClickOK.
12. Tocreateanewalarm,clickAdd,thenspecifythealarmconditionand
measurement,asdescribedintheprevioussteps.
NOTE
There is a limit to the number of alarms you can create. The Add button is disabled once that limit is
reached. In this case, you must delete an existing alarm before you can create a new one (or you can
select an existing alarm and configure it as necessary).
13. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.
Tosavethechangestothemeter,clickSend.Dependingonthetypeofchanges,a
meterresetmightoccur:
NotethatclickingYeswillpowercycle(reset)thedevice.ClickYestoconfirmand
proceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.
Formoreinformationonconfiguringthealarms,refertothePM800seriesReference
Manual.
Digital
Thisallowsyoutoconfigurethedigitalinputalarms.SelectDigitalthenclick
Edit.
Page 46
1
3
2
4
5
6
7
8
10
11
Thenumberedlabels(onthedrawing)aredescribedbelow:
1.
Theleftcolumnliststhedigitalinputalarms.Selectaniteminthislisttoeditit.
2.
Thisdefinesthealarmcondition.
SelectStatusInputOntosetthealarmwhenthedigitalinputchanges
fromofftoon.
SelectStatusInputOfftosetthealarmwhenthedigitalinputchanges
fromontooff.
TheEndofincrementalenergyinterval(EndIncEnrInt),Endof
demandinterval(EndDmdInt)andPowerup/reset(PwrUp/Reset)
alarmsareunarytypealarmsbecausetheyuseinternalsignalsfromthe
powermeter,andcannotbechangedthroughthissetupscreen.Refertothe
meterdocumentationformoreinformation.
3.
DependingontheI/Omoduleinstalledonyourmeter,thisallowsyoutoselect
oneoftheavailabledigitalinputs.Notethatthisisnotconfigurableforunary
typealarmsseeitem#2above.
4.
SelecttheEnablecheckboxtoenabletheselected(highlighted)alarminthe
list,orcleartheboxtodisablethealarm.
5.
TheLabelboxidentifiesthenameofthedigitalalarm.Typeinthisboxto
renamethealarmasnecessary.
6.
UsethePriorityboxtosetthepriorityfortheselectedalarm.
7.
UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedto
recordtheselectedalarm.
8.
SelecttheWaveformCapturecheckboxtotriggerawaveformcaptureon
alarm,orcleartheboxtoifyoudonotwanttotriggerawaveformcaptureon
alarm.
9.
Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutput
buttonto
button,selectoneoftheavailableoutputs,thenclickthe
moveittotheSelectedcolumn.ClickOK.
Page 47
10. Tocreateanewalarm,clickAdd,thenspecifythealarmtypeandselectthe
digitalinput,asdescribedintheprevioussteps.
11. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.
Tosavethechangestothemeter,clickSend.Dependingonthetypeofchanges,a
meterresetmightoccur:
NotethatclickingYeswillpowercycle(reset)thedevice.ClickYestoconfirmand
proceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.
Formoreinformationonconfiguringthealarms,refertothePM800seriesReference
Manual.
Boolean
ThisallowsyoutoconfiguretheBooleanalarms.SelectBooleanthenclickEdit.
NOTE
If you havent set up any Boolean alarms yet, click Add to create a Boolean alarm.
1
4
6
8
9
11
Page 48
10
12
1.
SelectaBooleanalarmtoeditit.
2.
UsetheLabelboxtorenametheselectedBooleanalarm(e.g.Any
Overcurrent).
3.
Selectthetypeoflogicoperation(e.g.,LogicOR)youwanttousetotestfor
thealarmcondition.
4.
ThisboxliststhealarmparametersusedfortheBooleanlogictest.
5.
ClickEdittoaddorremovealarmparameters.
SelectanalarmparameterunderAvailable,thenclickthe
buttonto
moveittoSelected.Ifyouwanttoremoveaparameter,selectitunder
Selected,thenclickthe
button.
6.
SelecttheEnablecheckboxtoenabletheselected(highlighted)alarminthe
list,orcleartheboxtodisablethealarm.
7.
UsethePriorityboxtosetthepriorityfortheselectedalarm.
8.
UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedto
recordtheselectedalarm.
9.
SelecttheWaveformCaptureboxtotriggerawaveformcaptureonalarm,or
cleartheboxifyoudonotwanttotriggerawaveformcaptureonalarm.
10. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutput
buttontomoveit
button,selectoneoftheavailableoutputs,thenclick
toSelected.ClickOK.
11. TocreateanewBooleanalarm,clickAdd,thenspecifythealarmtypeandselect
thedigitalinput,asdescribedintheprevioussteps.
12. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.
Tosavethechangestothemeter,clickSend.Dependingonthetypeofchanges,a
meterresetmightoccur:
NotethatclickingYeswillpowercycle(reset)thedevice.ClickYestoconfirmand
proceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.
Page 49
Shift Energy
Thisallowsyoutogroupenergyusageandcostaccordingtothreedifferenttime
shiftsinsidea24hourperiod(forexample,three8hourshifts).
First Shift Start, Second Shift Start, Third Shift Start
Usethesesettingstoselectwhattimethefirst,secondorthirdshiftstarts.
Cost Scale Factor
Selectthemultiplierusedwhencalculatingenergycost.
First Shift Cost (per kWh), Second Shift Cost (per kWh), Third Shift Cost (per kWh)
UsethesesettingstoenterthecostperkWhforeachshift.
Billing Cycle Setup
SelectthisthenclickEdittosetupthebillingcycle.
UsetheMonthandDayboxestoselectmeterreadingdates.UsetheTimeof
Dayboxtoselectthehourthemeterreadingisperformed.
Page 50
Waveform Capture
WaveformcaptureissupportedonthePM850andPM870.ThePM870allowsyou
toselectandconfigurethewaveformcapture.
Status
Selecttheappropriateoptiontoenableordisablethisfeature.
File Mode
Selectwhichmethodisusedforstoringwaveforms:
FIFO(firstinfirstout)modediscardstheoldestwaveformcapturewhenthe
waveformstorageisfull.
FillandHoldmodekeepstheoldestwaveformcaptureanddoesnotrecord
newoneswhenthewaveformstoragebecomesfull.
Channels (PM870 only)
Thisallowsyoutoselectwhichinputsyouwanttosetupforwaveformcapture.
SelectChannelsthenclickEdit.
Dependingonyourwiringconfiguration,certaininputsbecomeN/A(not
applicable).Ifthisisthecase,IONSetupdisplaysthisprompt:
1.
Selectthevoltageand/orcurrentinputchannelsyouwanttocapture.Click
Next.
2.
Setthecaptureoptions:
Samples/Cycle
Duration(cycles)
PreEventCycles
MaxCaptureindicatesthemaximumnumberofrecordingsforwaveform
capture,andisshownforinformationalpurposeonly.
Page 51
Page 52
In this chapter
BCPM setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
UsingIONSetup ..................................................... 54
BCPM setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
BasicSetup .......................................................... 55
AuxiliaryCTSizes .................................................... 55
BranchCircuitCTSizes................................................ 55
BreakerSizes ......................................................... 55
DemandSetup ....................................................... 56
InstantaneousCurrentAlarms.......................................... 56
LatchingCurrentAlarms.............................................. 57
VoltageAlarms....................................................... 60
Page 53
BCPM setup
BeforeusingIONSetup,makesureallthecommunicationssettingsfortheBCPM
hasbeenconfigured,asexplainedintheBCPMinstallationguide.
TheBCPMusesModbusRTUprotocoltocommunicatethroughitsRS485serial
communicationsport.
Devicecommunicationssettings:MakesureallthedevicesonthesameRS485
looparesettothesamebaudrate.MakesureParityswitchissettoOFF
(i.e. no parity)foralldevices.
Deviceaddress(unitID)settings:The2stripversionoftheBCPMusesone
Modbusaddress,whilethe4stripversionusestwoModbusaddresses.Panel1
usesthebaseaddressassetontheCommunicationsAddressDIPswitches.
Panel2(forthe4stripversion)isautomaticallyassignedthedeviceaddress
equaltoPanel1sbaseaddressplusone.Forexample,ifyousettheunitIDfor
Panel1to19,theunitIDforPanel2isautomaticallysetto20(i.e.,19+1).
RefertotheBCPMinstallationguidefordetailsonusingtheDIPswitchestoset
thedevicecommunicationsparameters.
NOTE
When setting up the device addresses for multiple BCPMs, make sure each address is unique AND does
not cause address duplication or overlap between the BCPM devices.
Page 54
Basic Setup
Configuration
Selecttheconfigurationoptionthatmatcheshowthecurrentsensorstripsare
arrangedandoriented.RefertotheBCPMinstallationguidefordetails.
NOTE
Make sure Configuration is set to the same value for each half of the BCPM (Panel 1, Panel 2).
Location
Typeanamethatidentifiesthepaneland/ordescribesitsphysicallocation.
Auxiliary CT Sizes
Auxiliary #1 (Amps) to Auxiliary #4 (Amps)
ThesedefinetheAuxiliaryorMainsCTsize(typically200A).Typethe
appropriatenumericvalueforeachauxiliaryCTinstalledinthepanel.Depending
onthemodeloptionordered,aBCPMcanhave4,8ornoinputsforauxiliaryCTs.
IfanyoftheauxiliaryCTsarenotconnected,settheircorrespondingBreakerSize
valuesto0(zero)inIONSetuptodisablealarmsforthoseunusedchannels.
Breaker Sizes
Auxiliary #1 (Amps) to Auxiliary #4 (Amps)
ThesedefinetheAuxiliaryorMainsbreakersize(typically225A).Typethe
appropriatenumericvalueforeachauxiliarybreakerinthepanel.Forunused
breakers,setthevalueto0(zero)todisablealarmsforthosechannels.
Channel #1 (Amps) to Channel #42 (Amps)
ThesedefinetheChannelorBranchbreakersize(typically20A).Typethe
appropriatenumericvalueforeachchannelbreakerinthepanel.Forunused
Page 55
breakers,settheircorrespondingbreakersizevaluesto0(zero)todisablealarms
forthoseunusedchannels.
Demand Setup
Demandistheaveragepowerconsumptionoverafixedtimeinterval(demand
period),typically15 minutes.Demandvaluesarecalculatedforeachsubinterval,
thenaveragedoverthenumberofsubintervalsthatmakeupthedemandperiod.
Number of Sub-intervals
Typethenumberofsubintervalsusedforcalculatingdemand(default=1).
Sub-interval Length (secs)
Typethenumberofsecondsforeachsubinterval(default=900seconds).
Page 56
Page 57
breakeris12A(i.e.,20 x 0.60).Todisablethisalarm(forallchannels)setits
thresholdvalueto0%.
Low Alarm Threshold (%)
TypethelimitfortheLowcurrentalarmstate,expressedasapercentageofthe
breakersize(default = 7.5%).Forexample,theLowalarmthresholdfora20 A
breakeris1.5 A(i.e.,20 x 0.075).Todisablethisalarm(forallchannels)setits
thresholdvalueto0%.
Low-Low Alarm Threshold (%)
TypethelimitfortheLowLowcurrentalarmstate,expressedasapercentageof
thebreakersize(default = 2.5%).Forexample,theLowLowalarmthresholdfor
a20 Abreakeris0.5 A(i.e.,20 x 0.025).Todisablethisalarm(forallchannels)set
itsthresholdvalueto0%.
Page 58
1.
CurrentrisesaboveLL(lowlowalarmthreshold)thisstartsthezero
currentalarmONtimer.
2.
CurrentdropsbelowLLbeforethezerocurrentalarmONtimeperiodends,so
alarmingisnotenabled.ThezerocurrentalarmONtimerisreset.
3.
CurrentrisesaboveLLthisstartsthezerocurrentalarmONtimer.
4.
Currentremainsabovethelowlowalarmthreshold,beyondthetimeperiod
specifiedbythezerocurrentalarmONtimesettingthisenablesthelatching
alarms(alllatchingalarmsarearmed).
5.
CurrentrisesaboveH(highalarmthreshold)thisstartsthehighalarmdelay
timer.
6.
CurrentrisesaboveHH(highhighalarmthreshold)thisstartsthehighhigh
alarmdelaytimer.
7.
CurrentdropsbelowHHbeforethehighhighalarmdelayperiodends,sothe
highhighalarmdelaytimerisreset.
8.
Highalarmislatchedattheendofthehighalarmdelaytimeperiod.
Example 2
1.
CurrentrisesaboveLL(lowlowalarmthreshold)thisstartsthezero
currentalarmONtimer.
2.
Currentremainsabovethelowlowalarmthreshold,beyondthetimeperiod
specifiedbythezerocurrentalarmONtimesettingthisenablesthelatching
alarms(alllatchingalarmsarearmed).
3.
CurrentdropsbelowL(lowalarmthreshold)thisstartsthelowalarmdelay
timer.
4.
CurrentdropsbelowLL(lowlowalarmthreshold)thisstartsthelowlow
alarmdelaytimerandthezerocurrentalarmdelaytimer.
5.
LowalarmislatchedattheendoftheLdelay(lowalarmdelay)timeperiod.
Page 59
6.
LowlowalarmislatchedattheendoftheLLdelay(lowlowalarmdelay)time
period.
7.
Currentremainsbelowthelowlowalarmthreshold,beyondthetimeperiod
specifiedinthezerocurrentalarmdelaytimesetting,thuslatchingthezero
currentalarm.
Voltage Alarms
Thevoltagealarmsetupparametersdefinethealarmdelay(timer)andthreshold
(limit)forvoltageinputsmonitoredbytheBCPM(ifyourBCPMmodeloption
supportsit).
Thealarmdelaysettingdefineshowmanysecondsavoltageinputneedstobein
analarmstate(i.e.exceedstheovervoltagealarmthreshold,orfallsbelowthe
undervoltagealarmthreshold)beforethealarmisactivated.Areturntonormal
(nonalarm)stateisinstantaneous,sothealarmdelaytimerisresetifthevoltage
returnstonormalstatebeforethetimerexpires.
Thealarmthresholdsettingdefinesthelimitforahighvoltageorlowvoltage
alarmstate,expressedasapercentageofthebreakersize.Todisableanalarm,set
itsthresholdvalueto0 (zero) Volts.
Over Voltage Delay (s)
TypethenumberofsecondsthevoltageneedstobecontinuouslyabovetheOver
VoltageThresholdlevelbeforetheOverVoltagealarmisactivated.
Under Voltage Delay (s)
TypethenumberofsecondsthevoltageneedstobecontinuouslybelowtheUnder
VoltageThresholdlevelbeforetheUnderVoltagealarmisactivated.
Over Voltage Threshold (V)
TypethelimitfortheOverVoltagealarmstate,inVolts.Todisablethisalarm(for
allvoltageinputs)setitsthresholdvalueto0 Volts.
Under Voltage Threshold (V)
TypethelimitfortheUnderVoltagealarmstate,inVolts.Todisablethisalarm
(forallvoltageinputs)setitsthresholdvalueto0 Volts.
Voltage Alarm Hysteresis (%)
Typethevalue,expressedasapercentageofthealarmthreshold,thatdefineshow
muchthethevoltagemustfallbelowtheOvervoltagethresholdorriseabovethe
Undervoltagethreshold,todeterminethealarmsOFFstate.
Example:IftheUnderVoltageThresholdissetto270VandtheUnderVoltage
Thresholdissetto200 V,a5% hysteresiswouldresultinanovervoltagealarm
OFFstateat256.5Vandbelow(i.e.270Vminus(270Vx0.05)),andanunder
voltagealarmOFFstateat190Vandabove(i.e., 200 Vminus(200Vx0.05)).
Page 60
Enercept meter
TheEnerceptmeterisacosteffectivesolutionforstandardenergymetering
applications.ItcombineseasytoinstallsplitcoreCTsandhighlyaccuratedigital
meteringandcommunicationselectronicsinthesamepackage.Itsuniquedesign
reducesinstallationcostsbyeliminatingtheneedforaseparatemeterenclosureor
todisconnectconductors.
TherearetwomodelsoftheEnerceptmeter.TheBasicmodelreportspowerand
energy,whiletheEnhancedmodelprovidesmultipleparameters,including
power,demand,energy,amps,volts,powerfactor,andreactivepower.
Formoreinformation,refertothemeterdocumentationavailablefrom
www.powerlogic.com.
In this chapter
Enercept meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
UsingIONSetup ..................................................... 62
Enercept setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
BasicSetup .......................................................... 62
Enercept data screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Resettingenergyanddemandvalues.................................... 63
Page 61
Basic Setup
System Type
SelecttheoptionthatdescribeshowyourEnerceptmeterisconnectedtothe
electricalservice.Refertothemeterdocumentationfortypicalinstallation
examples.
Number of Sub-Intervals
Enterthenumberofsubintervalsusedforcalculatingdemand.Demandisthe
averagepowerconsumptionoverafixedtimeperiod(demandperiod),typically
15 minutes.Demandvaluesarecalculatedforeachsubinterval,thenaveraged
overthenumberofsubintervalsthatmakeupthedemandperiod.
Page 62
Sub-Interval Length
Selectthetimedurationforeachsubinterval(inminutes),orselectSyncto
Commtostartthedemandintervalusingacommandfromthemonitoring
software,suchasPowerLogicSystemManagerSoftware(SMS).
WhiletheEnerceptmeterisselected,clickView>DataScreens(orclickthe
button).
2.
DoubleclicktheRealTimeicontodisplaythedatafromtheEnercept.
Page 63
Page 64
In this chapter
ION6200 meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
ION6200 setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
BasicSetup .......................................................... 67
Communications ..................................................... 68
Demand ............................................................. 68
Display.............................................................. 69
Outputs............................................................. 69
Scaling.............................................................. 70
WiringSetup......................................................... 70
Page 65
NOTE
If the ION6200 is set to Modbus communications protocol (MOD), select the device type Modbus RTU
Device when adding it to the ION Setup network. If the protocol is set to PML, select the device type
ION6200.
Page 66
1.
AddtheION6200toasite(toaModbusgatewaysite,forexample)andselect
ModbusRTUdevicefordevicetype.
2.
ClicktheDisplaytab,selecttheappropriatetemplateoptionfortheION6200,
thenclickOK.
Basic Setup
UsetheBasicSetupscreentoconfigurethesetupregistersothemeterdisplaysthe
correctpowermonitoringvalues.
Volts Mode
SelecttheoptionthatdescribeshowyourION6200meteriswiredtotheelectrical
service.
PT Primary
EnterthevalueforthePT(potentialtransformer)primary,inVolts.
PT Secondary
EnterthevalueforthePTsecondary,inVolts.
NOTE
If a PT is not used, enter the systems nominal voltage for both the PT Primary and PT Secondary settings
(e.g., voltage L-L for Direct Delta connection).
CT Primary
EnterthevaluefortheCT(currenttransformer)primary,inAmps.
CT Secondary
EnterthevaluefortheCTsecondary,inAmps.
Page 67
Communications
WhenIONSetupconnectstotheION6200,themeterscommunicationssettings
aredisplayedontheCommunicationssetupscreen.
NOTE
Altering the settings of a communications channel that is in use can cause a loss of communications with
the meter.
Baud Rate
Displaysthemetersserialcommunicationsbaudratesetting.
Protocol
Displaysthemetersserialcommunicationsprotocolsetting.
NOTE
The Factory protocol is only used by Technical Support for troubleshooting purposes.
Unit ID
DisplaysthemetersunitID.
RTS Delay
DisplaystheRTS(readytosend)delaysettingforthemetersserial
communication.
Demand
Demandistheaveragepowerconsumptionoverafixedtimeperiod(demand
period),typically15 minutes.Demandvaluesarecalculatedforeachsubinterval,
thenaveragedoverthenumberofsubintervalsthatmakeupthedemandperiod.
Period (mins)
Thisisthetimedurationforeachsubinterval,inminutes.
# of Intervals
Thisisthenumberofdemandperiods(subintervals).Enterthenumberof
subintervalsusedforcalculatingdemand.
Page 68
Display
UsetheDisplaysetupscreentoconfigurehowthefrontpanel/remotedisplay
behaves.
Scroll Time
Enterthenumberofsecondsuntilthenextsetofvaluesisdisplayedonthefront
panel.Todisablescrolling,setScrollTimeto0(zero).
Refresh Period
Enterthenumberofsecondsuntilthefrontpaneldisplayrefreshesitsvalues.
Outputs
TheKt(pulseweight,ortimeconstant)valuedefinestheamountofenergy(e.g.,
kWh,kVAh,kVARh)representedbyeachcalibrationpulseofthemetersLEDor
digitaloutput.
Kt Digital Output 1
ThisdefinestheKtvaluefordigitaloutput#1.
Kt Digital Output 2
ThisdefinestheKtvaluefordigitaloutput#2.
Kt IRDA
ThisappliesonlytoION6200meterswithfirmwarev207andearlierversions,and
definestheKtvaluefortheinfrareddataportwhenusedforenergypulsing.
Digital Output 1 Mode
Fordigitaloutput#1,selectenergypulsing(kWh,kVAh,kVARh)orexternal
pulsing(Ext).
Digital Output 2 Mode
Fordigitaloutput#1,selectenergypulsing(kWh,kVAh,kVARh)orexternal
pulsing(Ext).
IRDA Mode
OnlyappliestoION6200meterswithfirmwarev207andearlier.Thisisusedto
settheinfrareddataportforforenergypulsing(kWh,kVAh,kVARh)orexternal
pulsing(Ext).
Page 69
Scaling
ThefollowingModbusscalingregistersshouldnotbechangedfromtheirdefault
settingsunlessModbusprotocolisbeingused.Changestotheseregistersaffect
onlythevaluesdisplayedinsoftware(theyhavenoeffectonvaluesdisplayedon
theION6200frontpanel).Tosetthescaling,selecttheappropriatemultiplier
(x 0.001,x0.01,x0.1,x1,x 10,x100orx1000).
Modbus Scaling Registers
VoltageScale
CurrentScale
NeutralScale
PowerScale
Wiring Setup
Thefollowingparametersallowyoutochangethepolarityoftheindividual
voltageandcurrentinputssothattheymatchhowthePTsandCTsareorientedin
theelectricalsystem.DefaultissettoNormalforallinputs.Youcanchangethe
settingtoInvertedasrequired:
Wiring Setup Registers
V1Polarity,
V2Polarity
V3Polarity
I1Polarity
I2Polarity
I3Polarity
Page 70
Schneider Electric
Power Monitoring and Control
2195 Keating Cross Road
Saanichton, BC
Canada V8M 2A5
Tel: 1-250-652-7100
295 Tech Park Drive, Suite 100
Lavergne, TN 37086
USA
Tel: 1-615-287-3400
70002-0293-00
2009 Schneider Electric. All rights reserved.
04/2009