Académique Documents
Professionnel Documents
Culture Documents
Introduction
High voltage power transformers are one of the most
expensive elements in a power system and their failure
is a very costly event. The monitoring and diagnostic
techniques, which can evaluate the integrity of
transformer, are essential to evolve optimum and better
reliability of the equipment. In this regard several
techniques such as thermal monitoring, oil analysis,
partial discharge measurement, capacitance & tan delta
measurements, recovery voltage measurements etc. are
applied for transformer wherein each one is applied for
a specific type of problem and have their own merits.
These methods are not found to be suitable to monitor
and diagnose winding deformations. When a
transformer is subjected to high through fault currents,
the mechanical stmcture and windings are subjected to
severe mechanical stresses causing winding movement
and deformations. It may also result in insulation
damage and turn-to-turn faults are most likely. The
deformation can also be due to ageing of paper. As a
transformer ages the insulation shrink and the clamping
pressure may be lost which reduces its withstand
strength. Winding deformations in transformers are
difficult to establish by conventional methods of
diagnostic tests like ratio, impedancdinductance,
magnetizing current etc. Deformation results in relative
changes to the internal inductance and capacitance of
the winding. These changes can be detected externally
by low voltage impulse method or FRA method.
B. P. Singh'
Experimental results
Figure 3a and 3h shows the per-phase measurement (U,
V and W) of magnitude and phase plot respectively of
HV winding. For a threelegged core-type unit, the
1 X6
Test
Test transformer
Signal and
Reference
Shield
Figure 2 Experimental test set-up
IM J
Rgwe 3a: Magnitude plM of three phases.
187
Theoretical aspects
The design data of the transformer is used to compute
the inductances [SI and capacitances [9]. A 40 number
HV disc winding is sub-divided in 20 sections with each
~~
188
Acknowledgment
Authors wish to thank the management of CPRI and
BHEL to publish this paper. Thanks are also due to M/s
Vijai Electricals Limited, Hyderahad, India, to provide
the transformer to carry out the research work.
I
Figure 6 Magnitude plot for variation of inductances for the changes
insection I.
References
FrrnmVfW,
[7]
Conclusions
Experimental and theoretical investigations were carried
out on HV disc winding of a 11 kV/433 V, 1 MVA
transformer. Sweep frequency responses of the
transformer were obtained experimentally. It was
189