Fault level shall be for 60kA for 3sec for Noted. The same has been incorporated
1. and attached herewith for your reference.
Main and Neutral side SPBD.
Rated Voltage level for PT sizing Noted. The same has been incorporated
2. and attached herewith for your reference.
calculations to be checked.
Enclosures:
a. PT sizing calculations//Rev- A – For information only.
b. CT sizing calculations//Rev- A – For information only.
c. Single Line Diagram//Rev-B – 1CYJ318002A387
SINGLE LINE DIAGRAM
SIEMENS LTD.
SIEMENS
SIEMENS LTD.
62OP-40874
WBS No.:-
SIEMENS LTD.
1CYJ318002A387
50 0 100
132 KV BUS
6.6 KV BUS
SIEMENS
Scope
(T1, T2, T3) TO GEN. TRANSFORMER DIFF. PROTECTION PANEL (CUSTOMERS SCOPE) Customer's Scope
P2
FOR PROTECTION CTR. : 3600/1A,
3
CORE-1 S2 CLASS : PS
S1
FOR SPARE (FOR FUTURE USE) SIEMENS
Scope
CTR. : 3600/1A,
3
CLASS : PS T19, T20, T21
CORE-2 S2
S1 Core-1
A A A Core-2 A T22, T23, T24
CLASS : PS
P1 CTR. : 500/1A, For Spare CLASS : PS
FOR CUSTOMER'S CLASS : PS CTR. : 500/1A,
UAT DIFF. PROTECTION CTR. : 500/1A, FOR OVERALL DIFF.
P1 3 3 P2 P1 3 P2
S1 S2 S1 S2 S1 S2
3 Ph, 11 kV, 630 Amp Tee - off SPBD of Aluminium SC level: 60kA for 3 Seconds
P1
P1
P1
Tee-Off LA, SC, & PT Panel
IPT GENERATOR PROTECTION RELAY PANEL METERING SECTION SYNCH. SECTION AVR PANEL
110V 110V Cl: 6P, 7.5VA (2A+1M)
PROT.-1 (SEC.-1) UNITROL
CLASS : 3P / 30VA 3 3
PT FUSE 3 1 6080
3A, 11kV FOR STATOR V F A MW MVA MVAR PF TVM
E/F PROTECTION
MCB AVR CH#1 (SEC.-2)
Tee - off connection of 630 Amp TP for LAVT from Main SPBD
A
3 3 3
25 S DV DF
PROT.-2 (SEC.-1) 86A1 86B1 86C1 86A2 86B2 86C2
PT FUSE
3A, 11kV
3 CLASS : 3P / 30VA
AVR
SYNCH. & MET
0.25µF/12kV
25A - DIGITAL AUTO SYNCH.
MCB (SEC.-2)
SC level: 60kA for 3 Seconds
MW-TDR
MVAR
Spare
MVA
MW
Vyb
Vbr
Vry
PF
B
Ib
Iy
F
Ir
MCB AVR CH#2 (SEC.-2)
PT-3 SP, 6Amps CLASS: 0.2 / 30VA
11kV 110V 110V
A
3 3 3
P1
TO OVERALL DIFF. PROTECTION RELAY (CUSTOMER'S SCOPE)
(T16, T17, T18) P2
CTR. : 3600/1A,
3
FOR PROTECTION S2 CLASS : PS
CORE-1 S1
Spare
60 kA for 3 Seconds
A A
BUS DUCT 3500 A
3
CTR. : 3600/1A,
CORE-2 S2 CLASS : PS
S1
P1
B
BUS DUCT N
630 Amp SP connection for NGT
NEUTRAL GROUNDING
L
TRANSFORMER WITH RESISTOR
S1 S2 S1 S2 S1 S2
SINGLE LINE DIAGRAM
P1 P2 P1 P2 P1 P2
1 1 1
11kV/ 3 / 240V CTR.: 300/1A, CTR.: 300/1A, CTR. : 400/5A, M/s BLA POWER PVT.LTD. 1X43 MW
CL.5P10,15VA CL.5P10,15VA MINIATURE CT FOR 100% STATOR
65 KVA for 60 sec
A A
FOR 100% E/F PROTECTION M/s BLA POWER PVT.LTD.
A STATOR E/F 0.90 omhs, 65KW for 60Sec. A
NOTES:
SIEMENS LTD.
Document No. Rev.No.
______________________________________________________________________________________________________________________________________
We reserve the rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly
forbidden. © SIEMENS Ltd.
-2- Information#1 A
Rated Power 45 MW
Rated Voltage 11 kV
______________________________________________________________________________________________________________________________________
Format No.: DDIT3009
REV./Date : B/22.07.2009
Page: Document No. Rev.No.
-3- Information#1 A
As PS class CT is selected for protection purpose, there is no need for burden calculation at rated condition; however
it should be ensured that at plant fault level, CTs do not saturate. Hence the knee-point voltage of CTs shall be
designed as follows:
Vk > 2 * If (Rct + 2RL)
Where:
Vk = KNEE POINT VOLTAGE OF CT
If = FAULT CURRENT IN CT SECONDARY
= [SYSTEM FAULT CURRENT / CT RATIO] * SAFETY FACTOR
The Rct value is subject to change and shall be confirmed by the CT manufacturer and hence the value of Vk shall be
accordingly governed by the above formula. In any case, the CT shall be designed to have Vk such that it does not
saturate at system fault level of 60 kA for 3 Seconds.
• The sizing for the CT used for Generator Transformer Protection is kept as same as line side CT’s as looking into the
plant SLD the current in GT would not be more than the Full Load Current of Generator.
______________________________________________________________________________________________________________________________________
Format No.: DDIT3009
REV./Date : B/22.07.2009
Page: Document No. Rev.No.
-4- Information#1 A
[C] For UAT CT’s in Tap-off Busduct.
• CT RATIO SELECTION CALCULATION
As PS class CT is selected for protection purpose, there is no need for burden calculation at rated condition; however
it should be ensured that at plant fault level, CTs do not saturate. Hence the knee-point voltage of CTs shall be
designed as follows:
Vk > 2 * If (Rct + 2RL)
Where:
Vk = KNEE POINT VOLTAGE OF CT
If = FAULT CURRENT IN CT SECONDARY
= [SYSTEM FAULT CURRENT / CT RATIO] * SAFETY FACTOR
-5- Information#1 A
Protection
Burden(VA) TOTAL
Description UNIT
per UNIT (VA)
Cable of 2.5 mm2 of 60 meters length. 0.86 1 0.86
7UM622 burden 0.05 1 0.05
Total 0.91 VA
20 % Margin 1.092 VA
Hence 15 VA is sufficient for Metering CT.
______________________________________________________________________________________________________________________________________
Format No.: DDIT3009
REV./Date : B/22.07.2009
Document No. Rev.No.
______________________________________________________________________________________________________________________________________
We reserve the rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly
forbidden. © SIEMENS Ltd.
-2- Information#2 0
PT CALCULATIONS:
v PT RATIO SELECTION
______________________________________________________________________________________________________________________________________
Format No.: DDIT3009
REV./Date : B/22.07.2009