Vous êtes sur la page 1sur 10

474 Journal of Electrical Engineering & Technology Vol. 6, No. 4, pp.

474~483, 2011
DOI: 10.5370/JEET.2011.6.4. 474

Enhancement of Power System Transient Stability and Power


Quality Using a Novel Solid-state Fault Current Limiter
A. R. Fereidouni*, B. Vahidi, T. Hoseini Mehr** and M. Garmroodi Doiran*
Abstract Solid-state fault current limiters (SSFCL) in power systems are alternative devices to limit
prospective short circuit currents from reaching lower levels. Fault current limiters (FCL) can be
classified into two categories: R-type (resistive) FCLs and L-type (inductive) FCLs. L-type FCL uses
an inductor to limit fault level and is more efficient in suppressing voltage drop during a fault. In
contrast, R-type FCL is constructed with a resistance and is more effective in consuming the
acceleration energy of generators during a fault. Both functions enhance the transient stability of the
power system. In the present paper, a novel SSFCL is proposed to enhance power system transient
stability and power quality. The proposed SSFCL uses both functions of an L-type and R-type FCL.
SSFCL consists of four diodes, one self-turn-off IGCT, a current-limiting by-pass inductor (L), and a
variable resistance parallel with an inductor for improvement of power system stability and prevention
of over-voltage across SSFCL. The main advantages of the proposed SSFCL are the simplicity of its
structure and control, low steady-state impedance, fast response, and the existence of R-type and Ltype impedances during the fault, all of which improve power system stability and power quality.
Simulations are accomplished in PSCAD/EMTDC.
Keywords: Solid-state fault current limiter, Transient stability, Power system, Fault current

1. Introduction
As electric power systems have become more
complicated, fault levels are becoming larger due to
increasing electric power demand. To increase the
reliability of power supply, electric power systems are
interconnected to one another to share electric power.
However, once a fault occurs, the fault current also comes
from the interconnected grids. The interconnection of the
power system is restricted to a certain extent such that the
fault current will not exceed the capacity of the circuit
breaker (CB). Furthermore, the interconnection allows the
rejection of the fault point from the power system by the
CB to avoid the expansion of the influence of the fault
when it occurs [1].
With the increasing demand for electric power, power
systems are becoming larger and more interconnected. As a
consequence, fault current increases and transient stability
problems become more serious. Hence, to maintain the
stability of the power system, replacing the substation
equipment, changing the system configuration, or installing
a fault current limiter become necessary at a certain point
[2]. To overcome the high fault current, traditional methods

Corresponding Author: Dept. of Electrical Engineering, Amirkabir


University of Technology, Tehran, Iran. (vahidi@aut.ac.ir)
*
Dept. of Electrical Engineering, Amirkabir University of Technology,
Tehran, Iran. (fereidouni_aut@aut.ac.ir, mehdi_ garmrudi @yahoo.com)
** Dept. of Electrical Engineering, Isfahan University of Technology,
Isfahan, Iran (hoseini.mehr124@gmail.com)
Received: November 24, 2010; Accepted: April 28, 2011

have been used in the last decades. Current-limiting fuses,


series reactors, or high-impedance transformers replace or
modify the parameterization of existing equipment (such as
transformers, CBs, etc.) and adjust the system for new fault
duty and FCL. However, some of these alternatives may
create other problems, such as loss of power system
stability, high cost, and increase in power losses, which
may ultimately lead to decreased operational flexibility and
lower reliability [3][6].
FCL is a good option for limiting fault current and
maintaining the stability of a power system [6],[7] because
the application of FCL in electric power systems can
suppress the amplitudes of short-circuit fault currents and
enhance power system stability and voltage quality [8].
FCLs can be classified into R-types (resistive) and Ltypes (inductive) by current-limiting impedance. An L-type
FCL is more effective in suppressing voltage drop during a
fault, and limits the AC component of fault current better
than the other type. In contrast, an R-type FCL is more
effective in consuming the acceleration energy of
generators at the fault [1].
In the past few years, many kinds of fault currentlimiting devices have been developed in accordance with
the development of power electronics, magnet technology,
and superconducting materials [9][12].
Superconducting FCL has emerged as an alternative to
limit prospective short-circuit currents to lower levels and
improve power system reliability and stability by reducing
the fault current. Three configurations of superconductor-

A. R. Fereidouni, B. Vahidi, T. Hoseini Mehr and M. Garmroodi Doiran

based fault current-limiting devices are available. This type


of FCL is useful for bringing the superconductor into its
off-state; however, it has several disadvantages that
manifest either in the external sources or magnetic fields.
The superconducting device takes a long time to cover
from its fault current-limiting properties because the
coolant must be cooled back to its pre-fault temperature.
These materials ensure the cost-efficiency and reliability of
the cooling system for the superconductor, which needs to
be cooled to the temperature of helium. The cooling system
requires maintenance from time to time because it can
sometimes produce poisonous gases when overheated [13].
Because cooling technologies are still in their infancy
stage, they often succumb to frequent breakdowns.
Moreover, the commercial deployment of these
technologies has not yet been accomplished; thus, only a
few countries have this type of technology [14].
The present paper proposes to use SSFCL to limit
prospective short-circuit currents to lower levels and
improve the reliability and stability of power systems. We
propose and investigate a solid-state FCL (SSFCL) that has
excellent features of both the L-type and R-type FCL. The
proposed SSFCL consists of four diodes, one self-turn-off
IGCT, a current-limiting bypass reactor (L), and a variable
resistance parallel with current limitting reactor. The most
beneficial quality of the proposed configuration is the
simplicity of its structure and control, low steady-state
impedance, fast response, and high impedance fault.
Furthermore, the configuration takes a very short time to
cover, from its fault current limiting to its pre-fault, is both
economical, and is readily available. In the present paper,
we mainly provide a theoretical analysis on improving
power system transient stability using the proposed SSFCL,
which is capable of consuming excessive acceleration
generator power, increasing stability limit of the system,
and enlarging the stability region after the short circuit.
A simulation study on one-machine infinite bus system,
including the proposed SSFCL, is performed in accordance
with the laboratory scale test system [15]. The effects of
the SSFCL unit on the transient stability of the power
system and power quality is investigated and evaluated.

2. Configuration of the New SSFCL


The configuration of the new single-phase SSFCL is
shown in Fig. 1. The configuration comprises a self-turnoff device IGCT (T); four diodes D1, D2, D3, and D4; a
current-limiting impedance L; and a variable resistance
Rvar iable . SSFCL improves the operation of the SCR bridgetype FCL with bypass reactor in Fig. 2 [16] by substituting
power switches T1, T2, T3 and T4 with four diodes D1, D2,
D3, and D4. The aim of this process is to simplify the
circuit and DC reactor (L1) with a self-turn-off device
IGCT (T). Attaching variable resistance Rvar iable in parallel
with the current-limiting impedance and removing the

475

voltage-limiting element (Zno) are also part of the process.


The self-turn-off device IGCT is used as a fast solid-state
switch to discontinue a current instantly upon receiving a
turn-off signal. Current-limiting bypass reactor (L) and
variable resistance ( Rvar iable ) are used to pass the fault
current when the solid-state switch interrupts and decreases
a fault current, enhancing power system stability and
power quality. Variable resistance prevents over-voltage,
which can probably be caused by a sudden interruption of
current.

Fig. 1. Configuration of the proposed single-phase SSFCL

Fig. 2. SCR bridge-type FCL with bypass reactor [16]


Fig. 3 shows the three-phase SSFCL scheme that can be
acquired after being set up using one single-phase SSFCL
in every phase line. The benefits of this scheme are a
simple control method, independence of operation, and
convenience of selected location, among others. However,
12 diodes and 3 IGCT devices are needed for this particular
scheme, which is not economical.

Fig. 3. Three-phase SSFCL composed of a single-phase


unit

476

Enhancement of Power System Transient Stability and Power Quality Using a Novel Solid-state Fault Current Limiter

To simplify the system and decrease the volume, the


weight and cost of the SSFCL and compact structure of the
three-phase SSFCL shown in Fig. 4 are recommended.

works as an L-type FCL. Although IFCL-LR is lower than the


varistor current (variable resistance: ON), the current also
flows through the variable resistance; thus, the resistor
consumes the energy. The SSFCL works as an R+L-type
FCL. Consequently, the proposed SSFCL has the currentlimiting characteristics of both L-type and R-type FCLs.

(a)

Fig. 4. Configuration of the proposed three-phase SSFCL


The proposed three-phase SSFCL consists of 8 diodes
D1D8, 3 bypass reactors L1L3, and 3 variable
resistances Rvar1Rvar3, which are parallel with bypass
reactors L1L3, respectively, and one IGCT device T.

3. Concept of Proposed SSFCL


In the steady state, the self-turn-off device IGCT (T) is
turned on and all current flows through the diodes. When a
fault occurs, the self-turn-off device IGCT (T) is switched
off, thereby forcing most of the current to flow through the
inductor and variable resistance branch. As shown in Figs.
5(a) and 5(b), variable resistance has high impedance,
whereas IFCL-LR is more than a certain value (varistor
current) and has low resistance while the IFCL-LR is less than
the varistor current; these states are called OFF and ON
modes in the present paper. When a fault occurs, the
SSFCL is in the waiting mode, and the current of the
SSFCL is lower than the varistor current. Therefore, the
variable resistance is in ON mode and the current passes
via the variable resistance and reactor. The SSFCL is in the
current-limiting mode [Fig. 5(b)] while the current of the
SSFCL is more than the varistor current. Therefore, the
variable resistance is in OFF mode and the current passes
via a reactor. The absolute value alternately varies more
and less during a cycle. During one cycle, although current
is more than the varistor current (variable resistance: OFF),
the current does not flow through the variable resistance.
Because the peak of the line current [i.e., IFCL-LR] is
restricted by the inductance of the SSFCL, the SSFCL

(b)
Fig. 5. Schema of (a) the proposed SSFCL and (b) operation principle in current-limiting mode

3.1. Sequence of Operation of Variable Resistance


The sequence of operation of this variable resistance is
shown in Fig. 6. A description is also provided.
Before beginning the simulation, the variable resistance
is initialized with an initial impedance value Rinitialize =
High. The simulation is then begun to monitor the current
magnitude and rate of current change during the entire
simulation time. After achieving a steady-state operating
point, a three-phase-to-ground fault is inserted into the
system, which is external to the SSFCL. As soon as the
fault is inserted, the magnitude of the line current jumps
instantaneously and achieves a new steady-state value
while the fault is present. However, to ensure that there is a
fault in the transmission system and that the impedance is
not falsely triggered, the rate of current change is also
monitored. A fault changes the rate instantaneously. After
setting the necessary flags, variable resistance is ramped
down to low resistance. While the fault current is present in
the varistor current (-VC < I < +VC), the SSFCL works as
an L+R-type FCL. As soon as the fault current becomes
more than +VC and lower than VC, variable resistance is
ramped up to high resistance, and SSFCL begins to work as

A. R. Fereidouni, B. Vahidi, T. Hoseini Mehr and M. Garmroodi Doiran

477

Fig. 7. Proposed SSFCL activation-timing diagram

4. Modeling and Simulation


4.1. Model Power System

Fig. 6. Sequence of activation for variable resistance


an L-type FCL. After the fault is cleared, the variable
resistance is ramped up to the initial resistance; this cycle
occurs whenever there is a fault.

3.2. Proposed SSFCL Activation Timing


Timing the operation of the FCL trigger is of paramount
importance when modeling any devices. The activation
time of an FCL can be a function of its physical properties
or user settable parameters via a relay or built-in timers.
Fig. 7 shows the proposed SSFCL activation-timing
diagram.
As Fig. 7 shows, a fault is inserted at the time of fault.
The magnitude of the line current immediately increases
and the magnitude flag is raised. The rate of change
flag is also asserted because the rate at which the line
current changes is non-zero. While fault current is in
between VC < I < +VC, the variable resistance of the
SSFCL is ramped down to low resistance such that the
limiting current and variable resistance can proceed (L+Rtype SSFCL). As soon as the fault current becomes more
than +VC and lower than VC, the variable resistance is
ramped up to high resistance such that the limiting current
proceeds (L-type SSFCL). Once the fault is cleared, the
variable resistance is ramped up to initial resistance.

A simulation model of the proposed SSFCL based on


experimental results is performed by PSCAD (power system
computer-aided design). Using the SSFCL model, power
system simulation studies are carried out in one-machine
infinite bus system with parallel transmission lines that
correspond to a laboratory scale experimental system (Fig.
8). The rating capacity is 120 MVA, rating voltage is 13.8 kV,
and frequency is 60 Hz. The three-phase, four-pole
synchronous generator is expressed by a 7-order model
based on Parks equation. The CB1 and CB2 that simulate
CB are closed in the initial location. A three-line grounded
fault (3LG) is simulated at the terminal of the lower line
(fault line) by closing the SW. After a while, the fault line is
rejected by opening CB1 and CB2, and this time interval is
called clearing time. Meanwhile, the reclosing time
occurs when CB1 and CB2 are reclosed to become the initial
condition. During reclosing time, the SW is opened to clear
the fault. The SSFCL is installed at the generator side bus in
both lines. Simulation studies are performed under the
Transmission Line
Vb

Va

Pg

CB1

Vg

(1)

SSFCL

Isafe-line
CB2

Ifault-line

SSFCL
SW

Synchrounos Generator
120 MVA, 13.8 kV, 60 HZ, 3-phase
Xd=1.04 (pu), X'd=0.314 (pu), X''d=0.28
Xq=0.77, T'do=6.55, T''do=0.039

L1
2 mH

CB3

L2
2 mH

CB4

Infinite Bus
13.8 kV

Fault
(2)

3LG

Fig. 8. Simulation model system including the proposed


SSFCL

478

Enhancement of Power System Transient Stability and Power Quality Using a Novel Solid-state Fault Current Limiter

conditions of 3LG fault with reclosing time of 900 ms and


fault-clearing time of approximately 100 ms.
Transient stability analysis is performed by combining the
solution of algebraic equations. This solution describes the
network with a numerical solution of differential equations,
which in turn describe the motion of the machine rotor. In
these studies, the synchronous generator is represented by a
voltage source behind a transient reactance X'd. During
transient conditions, the generator internal voltage remains
constant in magnitude but changes its angle (). This angle
corresponds to the angle between the generator internal
voltage and infinite bus voltage. The mechanical power, PM,
which is supplied by the turbine, also remains constant.
These simplified assumptions, which correspond to neglect,
excitation, and speed governor systems, are considered valid
if transient simulation time is under 1 s. The two lines are
equal and are characterized by reactance XL (XL1 = XL2).
When the system operates in normal conditions, the SSFCL
presents zero impedance. During fault conditions, the
SSFCL is represented by impedance Zsc, which
characterizes the final resistance or inductance presented by
SSFCL device. The non-linear differential equation, also
called swing equation, describes the motion of the
synchronous machine rotor:
2 H 
+ D + PG ( ) = PM
0
 = r 0

(1)
(2)

where H is the inertia constant, 0 is the rated synchronous


speed, D is the damping factor, and PG is the electrical
machine power. The electrical machine power is a function
of angle and depends on network topology. These
functions must be characterized for the three stages that
constitute the executed transient stability studies.
4.1.1. Before Fault

PG ( ) =0

(4)

However, in the case of a resistive SSFCL design, the


generator power is
pG ( ) = RSC .

E2
RSC + X d 2

(5)

Considering the power system circuit represented in Fig.


9, the equivalent circuit during the fault is demonstrated,
where Zsc characterizes the final SSFCL resistance or
reactance.

Fig. 9. Equivalent circuit during fault condition considering


the SSFCL located in the feeder position of line L2
Applying the delta-wye transformation to the
impedances occurring among Buses 1 and 2 and the fault
point 3 lead to
X L .Z
( X L )2
SC
Z =Z =
;
=
Z
3
1 Z
2 Z
+ 2X L
+ 2X L
SC
SC

(6)

The equivalent circuit of Fig. 4 can be reduced to the


one represented in Fig. 10 because Zth and Vth denote
Thvenins impedance and voltage source equivalents,
respectively.

Before the fault, the system operates in a steady state or


equilibrium state characterized by voltage V , with power
supplied S to the infinite bus. Generator internal voltage
j ) is determined by the instant generator
E ( E = Ee
power given by
P ( ) =
G

E.V
sin( )
XL
X +
d
2

(3)

4.1.2. During Fault


The fault is a three-phase symmetrical fault placed at
power line L2 after the CB, which is near Bus 1, and occurs
at t = T1. Considering the power system circuit represented
in Fig. 8, the use of an inductive SSFCL design leads to the
following generator power:

Fig. 10. Equivalent circuit reduced.


Thvenins impedance and voltage
determined using the following relations:

Z .Z
3 2
th Z + Z
3
2

j
V
= V e th
V = Z .
3 Z + Z
th
th
3 2
Z

source

are

(7)
(8)

A. R. Fereidouni, B. Vahidi, T. Hoseini Mehr and M. Garmroodi Doiran

4.2. Simulation

The generator power is given by


E .V
E 2
th cos( + )
P ( ) =
cos( a )
G
th
th
Za
Za

(9)

where
j
Z a = Z + Z + jX = Z a e a
1
th
d

(10)

4.1.3. After Fault

The fault is cleared at t = T2 by opening CB2 and CB4.


The instant generator power is given by
E.V
P ( ) =
sin( )
G
X + X
L1
d

479

(11)

Stable operation of the power system network is


dependent on the balance of mechanical and electromagnetic forces that keep the generators synchronized.
When a power system is in normal condition, there is
equilibrium between the consumed and produced power in
this power system. When a large disturbance such as a
short circuit or line tripping appears, this situation of
synchronous equilibrium may momentarily or permanently
damp oscillations, depending on the case. Thus, the power
system transient stability problem is then determined to
assess whether the power angle of the generator is able to
keep or reach a new satisfactory steady-state operating
point following the fault [17].
If the proposed SSFCL is used in the power system
during a fault, theory and simulation results show that the
transient stability of the system can be enhanced. Fig. 11

(a)

(b)

(c)

(d)

(e)

(f)

Fig. 11. Simulation result of (a) fault-line current, (b) safe-line current, (c) generator voltage, (d) output power, (e) rotor
angle, and (f) rotor angle velocity of the generator of model SSFCL at the current-limiting operation (PG = 50 MW,
clearing time = 100 ms, 3LG fault)

480

Enhancement of Power System Transient Stability and Power Quality Using a Novel Solid-state Fault Current Limiter

(a)

(c)

(b)

(d)

Fig. 12. The simulation results of (a) the voltage across the SSFCL, (b) current through the SSFCL, (c) current through the
current-limiting reactor (L), and (d) current through the variable resistance (PG = 50 MW, clearing time = 100 ms,
3LG fault)

shows a typical simulation result throughout the procedure:


(from top to bottom) (a) fault-line current (kA), (b) safeline current (kA), (c) generator voltage (kV), (d) output
power of generator (MW), (e) rotor angle (deg), and (f)
rotor angle velocity of the generator (rad/s). The operating
conditions for the simulation are as follows: output power
is 50 MW and clearing time is set at 100 ms. The fault
occurs at 3 s and is cleared at 3.1 s. The fault line is
reclosed at 4 s (Fig. 8). The SSFCL in the fault line works
to restrict the current. In this case, the generator returns to
the initial condition stably after the switching procedure.
When the clearing time is longer, the generator steps out of
and loses the synchronism.
Fig. 12 shows the A-phase voltage and currents of the
proposed SSFCL in the simulation results shown in Fig. 11:
(from top to bottom) (a) Voltage across the SSFCL (kV),
(b) current through the SSFCL (kA), (c) current through
the current-limiting reactor (L) (kA), and (d) current
through the variable resistance (kA). Although all currents
contain DC components, the SSFCL model operates
according to the principle. Each time the current becomes
less than the varistor current, the variable resistance goes
into ON mode and the current sees through the variable
resistance.

5. Results and Discussion


5.1. Current-limiting Performance
Fig. 13 shows the fault current of A phase with the
SSFCL (I Fault-Line with SFCL) and without the SSFCL (I Fault-Line
without SFCL) (Fig. 4). Although the RMS value of the fault
current reaches nearly 30 kA without any SSFCL, the value
is restricted less than 16 kA with the SSFCL. The
capability of the SSFCL to restrict the fault current is not
reduced by adding variable resistance.

Fig. 13. Current through the A-phase line during the fault
with SSFCL and without SSFCL (kA).

A. R. Fereidouni, B. Vahidi, T. Hoseini Mehr and M. Garmroodi Doiran

5.2. Voltage Drop Suppression During the Fault


The RMS value of Va in Fig. 8 with the SSFCL is
approximately 0.7 PU during the fault (Fig. 14), whereas it
is only 0.1 PU without any SSFCL. The ability of the
SSFCL to suppress voltage drop is not degraded by
attaching the variable resistance in parallel. Moreover, the
surge voltages observed at the beginning of the currentlimiting performance with SSFCL without variable
resistance are eliminated with the SSFCL with variable
resistance.

481

Fig. 16 shows the relation of the load angle and angular


velocity. After initial operation, the system becomes stable
at approximately 16.6 (deg) load angle and 120 angular
velocity. In steady-state normal operation, the three-phase
fault breaks the synchronism of the load angle to over 90
(deg), which is the maximum load angle that the machine
can sustain. After the fault, the machine goes out of
control; however, is able to find a stable point at 98 (deg)
through a hypothetical controller. The SSFCL is installed
after the initial operation; thus, the system becomes stable
at about 16.6 (deg) load angle and 120 angular velocity.
In the steady-state normal operation, when a fault occurs in
three phases, the load angle maintains synchronism at 32
(deg), which is under the maximum load angle.

Fig. 14. RMS value of terminal voltage of generator (PU)

5.3. Effect of Energy Absorbed in Variable Resistance


on Power System Stability, Load Angle, and
Angular Velocity
Critical clearing time depends on the acceleration energy,
which is the difference between the mechanical input
energy and output electric energy of the generator at the
fault. Fig. 15 shows the generator power during the fault.
The electric energy transferred to the infinite bus is small
without SSFCL because the generator voltage is low.
However, the SSFCL suppresses the voltage drop; thus, the
electric power can be transferred to a certain extent through
the abovementioned transmission line. Moreover, the
electric energy is consumed in the variable resistance of the
SSFCL, and the acceleration energy is greatly diminished.
Hence, critical clearing time with SSFCL is longer than
that without the SSFCL or the SSFCL without variable
resistance.

Fig. 16. Angular velocity vs. power angle graph in case of


a three-phase fault in the model power system
where (a) the SSFCL is not installed and (b) the
SSFCL is installed

The rotor angular velocity of the generator at critical


clearing time is shown in Fig. 17 in two cases: with SSFCL
and without SSFCL. The generator accelerates most during
the fault without the SSFCL and accelerates least with the
SSFCL. Therefore, the proposed SSFCL enhances the
stability of the power system by restraining the change of
angular velocity.

Fig. 17. The rotor angular velocity in two cases (rad/s)


Fig. 15. The generator output change during the fault with
100 ms clearing time for the two cases (MW)

The proposed SSFCL characterizes both the L-type and


R-type FCLs.

482

Enhancement of Power System Transient Stability and Power Quality Using a Novel Solid-state Fault Current Limiter

6. Conclusion
A novel SSFCL is proposed in the present paper. The
studies conducted in the present paper show the effect of a
proposed SSFCL on power transient stability and power
quality. Through the present study, the proposed SSFCL is
demonstrated to restrict fault current and to protect the
synchronization of generators. The capability of this
SSFCL to diminish fault currents has an effect on
synchronism. The SSFCL more efficiently protects
synchronization, with three lines to a ground fault,
compared with a system with any SSFCL. The first
objective of an FCL is to protect devices such as CBs.
However, if SSFCLs are installed in systems, other side
effects are produced, as shown in the present study. We
have considered a simple power system in the perspective
of stability. The simulation study was performed to
investigate power system characteristics of the proposed
SSFCL, which consists of four diodes, one self-turn-off
IGCT, a current-limiting by-pass reactor (L), and a variable
resistance in parallel L. The present study had two goals:
improve power system stability and prevent over-voltage
across the SSFCL. The SSFCL consumes excessive energy
in the variable resistance during the fault. The SSFCL has
current-limiting characteristics of both the L-type and Rtype FCLs. To determine how the voltage drop suppression
and energy consumption feature of the proposed SSFCL
influence power system stability, various parameters of
power system were investigated. The proposed SSFCL has
excellent characteristics in improving power system
stability once the effects of voltage drop suppression and
excessive energy consumption during the fault have
manifested.

[4]
[5]

[6]

[7]

[8]

[9]

[10]

[11]
[12]

References
[13]
[1] Y. Shirai, K. Furushiba, Y. Shouno, M. Shiotsu, and T.
Nitta, Improvement of Power System Stability by
Use of Superconducting Fault Current Limiter with
ZnO Device and Resistor in Parallel, IEEE
Transaction on Applied Superconductivity, Vol. 18,
No. 2, June 2008.
[2] Masaki Yagami, Junji Tamura, Enhancement of
Transient Stability Using Fault Current Limiter and
Thyristor Controlled Braking Resistor, Power Tech,
2007 IEEE Lausanne.
[3] Lin Ye, LiangZhen Lin and Klaus-Peter Juengst,
Application Studies of Superconducting Fault
Current Limiters in Electric Power System, IEEE
Trans. on Applied Superconductivity, Vol. 12, No1,
pp. 900903, March 2002.

[14]
[15]

[16]

[17]

Thomas P.Sheahen, Introduction to HighTemperature Superconductivity, Plenum Press, New


York and London.
W. Paul, M. Chen, M. Lakner, J. Rhyner, D. Braun, W.
Lanz, M. Kleimaier, Superconducting Fault Current
Limiter Applications, technical and economical
benefits, simulations and test results, CIGR session
2000, no 13201.
M.E. Almeida, C.S. Rocha, J.A. Dente, P.J. Costa
Branco, Enhancement of Power System Transient
Stability and Power Quality using Superconducting
Fault Current Limiters, Lisbon, Portugal,
March1820, 2009.
A. J. Power, An Overview of Transmission Fault
Current limiters, Fault Current Limiters - A look at
Tomorrow, IEE Colloquium on June 1995, pp
1/11/5.
Takahiro Nomura, Mitsugi Yamaguchi and Satoshi
Fukui et al, Single DC reactor Type Fault Current
Limiter for 6.6KV Power System, IEEE Trans. On
Applied Superconductivity, Vol.11, No.1, March
2001:20902093.
R. F. Giese et al., Assessment study of
superconducting fault current limiters operation at
77K, IEEE Trans. Power Delivery, vol. 8, no. 3,pp.
11381147, July 1993.
R. K. Smith et al., Solid state distribution current
limiter and circuit breaker application requirements
and control strategies, IEEE Trans. PWRD, vol. 8,
no. 3, pp. 11551164, July 1993.
E. Thuries et al., Toward the superconducting fault
current limiter, IEEE Trans. Power Delivery, vol. 6,
pp. 801808, Apr. 1991.
M. Chen et al., Fabrication and characterization of
superconducting rings for fault current limiter
application, vol. 282287, 1997.
Gurjeet singh malhi, Studies of fault current
limiters for power systems protection", August, 2007.
Manish Verma, "A comprehensive overview,
behavioral model and Simulation of a Fault Current
Limiter ", June 29, 2009.
K. Furushiba and Y. Shirai et al., Power system
characteristics of the SCFCL in parallel with a
resistor and a ZnO device, IEEE Trans. Applied
Superconductivity, vol. 17, no. 2, pp. 19151918,
June 2007.
Zhengyu Lu, Daozhuo Jiang and Zhaolin Wu, A
New Topology of Fault-Current Limiter and Its
Parameters Optimization. IEEE Power Electronics
Specialists Conference, PESC03.
J. Machowski, Power System Dynamic and Stability:
John Willey & sons press, 1997.

A. R. Fereidouni, B. Vahidi, T. Hoseini Mehr and M. Garmroodi Doiran

483

Alireza Fereidouni was born in


Behshahr, Iran, in 1987. He received his
B.Sc. degree in Electrical Engineering
from Babol University of Technology,
Babol, Iran, in 2009. He is currently an
M.Sc. student in the Department of
Electrical Engineering at Amikabir
University of Technology, Tehran, Iran.
His research interests are power system stability and
protection, power electronics, and high voltage.

Tahoura Hoseini Mehr was born in


Babol, Iran, in 1987. She received her
B.Sc. degree in Electrical Engineering
from Babol University of Technology,
Babol, Iran, in 2009. She is currently
an M.Sc. student in the Department of
Electrical Engineering at Isfahan
University of Technology, Isfahan, Iran.
Her research interests are power electronics, electrical
machines, and power system control and protection.

Behrooz Vahidi, was born in Abadan,


Iran, in 1953. He received his B.S.
degree in Electrical Engineering from
Sharif University of Technology, Tehran,
Iran, in 1980, his M.S. degree in
Electrical Engineering from Amirkabir
University of Technology, Tehran in
1989, and his Ph.D. degree in Electrical
Engineering from the University of Manchester Institute of
Science and Technology, Manchester, UK in 1997. From
1980 to 1986, he worked in the field of high voltage as a
Chief Engineer. Since 1989, he has been with the
Department of Electrical Engineering of Amirkabir
University of Technology where he is currently a Professor.
Prof. Vahidi is a senior member of IEEE. His main research
interests are high voltage, electrical insulation, power
system transient, lightning protection, and pulse-power
technology. He has authored and co-authored more than
220 papers and 5 books on high-voltage engineering and
power systems.

Mehdi Garmroodi Doiran was born


in Tehran, Iran in 1986. He received his
B.Sc. degree in Electrical Engineering
from Sharif University of Technology,
Tehran, Iran, in 2009. He is currently
an M.Sc. student in the Department of
Electrical Engineering at Amirkabir
University of Technology, Tehran, Iran.
His research interests are power system control and
protection, power electronics, and power system transient
stability.

Vous aimerez peut-être aussi