Académique Documents
Professionnel Documents
Culture Documents
Source: E SOURCE
During damper servicing, moveable surfaces should be cleaned and lubricated. The
cleaning can be done with a power washer or with a bucket of soapy water and a brush.
As long as a service technician is already on the roof, this cleaning and testing should take
about 15 minutes, costing US$10 (at $40 per hour for labor). If this prevents one of the 5ton compressors in a 10-ton unit from running for just 100 hours, it will save 465 kilowattAfter cleaning and lubrication, a damper should be tested. First, it should be run through
its full range of motion. Tools can generate electrical control signals to drive the actuator,
or the economizer setpoint can be manipulated at the control panel. Then the economizer
setpoint should be checked. Although many economizers are set at about 60F, the
setpoint can be as high as the return-air temperature (about 74F) to provide beneficial
ventilation. However, in high-humidity climates (or where outside air is very polluted), it
may not make sense to maximize outside-air flow at low drybulb temperatures.
One of the easiest ways to make a service technician groan is to mention enthalpy
controllers for outside-air economizers, which attempt to account for both the temperature
and humidity of outside air. These devices are notoriously unreliable because of the
difficulty of measuring humidity with inexpensive sensors. Until a reliable, accurate, and
cheap humidity sensor appears, rooftop unit economizers should be controlled by drybulb
temperature sensors. (However, a possible exception to this rule is a building with a goodquality central humidity sensor that sends control commands to rooftop units through an
energy management system.)