Multilin
Agenda
AGENDA
Introduction
Product overview
Installation
Percent Current Differential
Lab: setting up 87L
Grouped elements
Control elements
Monitoring & Metering
Introduction
Introduction
Transmission Line Protection Considerations
1) Reliability: has two aspects:
Dependability: the degree of certainty that the relay will operate
correctly.
Security: the relay will not operate incorrectly
2) Speed: Very high power during fault conditions: delays translate into
increased damage: faster protection tends to compromise relay system
security and selectivity.
3) Sensitivity: The minimum operating quantities allows the relay to detect
an abnormal condition. High-impedance ground faults,voltage unbalance
and high source- to- line impedance ratio affect the sensitivity
4) Selectivity: or coordination: ability of the relay system to minimize
outages as a result of a fault by operating as fast as possible within their
primary zone.
5) Simplicity and ergonomics: simple to apply and to obtain maximum
protection for the minimum cost in one box
Terms: Coordination, Unit Protection/None Unit Protection, Primary/Back up
Introduction
Transmission Line Protection Considerations
High voltage transmission lines have extremely high level of fault current and
low impedance characteristics. Over current protection can not be as fast as its
needed.
Solutions:
Current Differential:
Unit Protection
Measure the current phasors at both ends of the line. If you have a line fault
there will be a difference in the current magnitude at each end and/or a change
in current phase angle with respect to applied voltage.
Distance or (Impedance):
None Unit Protection
Impedance known as Distance: The distance relay operates by using both
voltage and current to determine if a fault is in a relays zone of protection. At
time of fault Current increases and voltage decreases which translates into a
change in impedance.
Introduction
Current differential highlights
Communication link
Product overview
52
79
M onitoring
50DD
50P(2)
3V_0
CLOSE
50_2(2)
51P(2)
51_2(2)
TRIP
50BF(2)
87L
21P
67P(2)
68
FlexElement
TM
50N(2)
78
M etering
51N(2)
Transducer
Inputs
67N/ G
21G
59P
27P(2)
50G(2)
51G(2)
59N
59X
27X
25(2)
OR
- G.703
- RS422
FSC
(SONET)
Installation
10
11
12
Octet Timing
Disabled
Rad Modem
Rad Modem
Loop Timing
Loop Timing
mode
mode
Loop Timing
Octet Timing
Disabled
Internal
mode
13
Octet Timing
enabled
Multiplexer
Multiplexer
Octet Timing
enabled
Loop Timing
Loop Timing
mode
mode
The multiplexer provides the clock for all relays: again, one clock per
system:
14
Tx Clock
Tx Data
15
Connected directly to
MUX
Connected to MUX
via converter
16
Transmitted
data blocked
Local relay
G7R
17
Received data
echoed back.
G7R
G7X
G7X
G7R
Local relay
Remote
relay
18
CHANNEL ID FAIL
1. Each packet carries relay
ID number per channel
2. Each received packet is
compared with ID
programmed L90 Power
System menu.
3. 0 means NO Channel ID
check is required (for
direct fibers).
Protection against:
1.
Inadvertent loopback
2.
Inadvertent connection to a
wrong L90 relay.
19
SETTING
VAG
To Remote Relays
channel 1 & 2
VBG
VCG
Compute Charging
Current
SETTING
DATA FROM
LOCAL END
CURRENT DIFF
SOURCE:
IA
Charging Current
IA 2 @Timestamp
IB
IB @Timestamp
IC
IC @Timestamp
RUN
OR
RUN
Compute
Phasors
& Variance
(Local)
IA
Process
Phasors
IB
Computations IC
IA
FLEXLOGIC OPERANDS
87L DIFF OP
IB
87L DIFF OP A
IC
87L DIFF OP B
SETTING
L90 POWER SYSTEM
NUM. OF TERMINALS:
87L DIFF OP C
SETTINGS
AND
3 = 1
OR
CURRENT DIFF
PICKUP:
CURRENT DIFF
RESTRAINT 1:
CURRENT DIFF
RESTRAINT 2:
SETTING
AND
OR
2 = 1
SETTING
AND
CURRENT DIFF
TAP 1:
DATA FROM
REMOTE 1
Channel 1 OK=1
OR
AND
Channel 1 ID Fail
IA 2 @Timestamp
Compute
Phasors
& Variance
(Remote 1)
IB 2 @Timestamp
IC2 @Timestamp
DTT PHASE A
AND
DTT PHASE B
AND
DTT PHASE C
AND
Compute
Phasors
& Variance
(Remote 2)
IB 2 @Timestamp
IC @Timestamp
2
AND
AND
IB
IA Restraint
IB Operate
IB Restraint
IC Operate
IC Restraint
IC
OR
>1
RUN
Channel 2 ID Fail
IA 2 @Timestamp
AND
>1
OR
DTT PHASE C
IA Operate
>1
CURRENT DIFF
TAP 2:
AND
DTT PHASE A
IA
SETTING
DATA FROM
REMOTE 2
Channel 2 OK=1
DTT PHASE B
CURRENT DIFF
BREAK PT:
RUN
IA
AND
IB
RUN
IC
87L BLOCKED
AND
OR
AND
OR
AND
AND
OR
OR
FLEXLOGIC OPERAND
AND
STUB BUS OP
AND
SETTING
CURRENT DIFF
DTT:
Enabled=1
AND
To Remote Relays
channel 1 & 2
OR
OR
SETTING
CURRENT DIFF
KEY DTT:
AND
OR
827056A9.CDR
Off
20
Operate Current
K2
K1
Restraint Current
21
32 samples for
Transmission of
next phaselet
present
time
windo
w
time
waveform
time
magnitude
22
32 samples for
Transmission of
next phaselet
windo
w
time
present
time
time
waveform
magnitude
window
time
23
OPERATE
OPERATE
RESTRAINT
Real (ILOC/IREM)
OPERATE
OPERATE
24
OPERATE
REST.
Error factor is low
25
Time of
energization
0
-50
-100
-150
-200
0.04
0.06
0.08
0.1
0.12
0.14
0.16
0.18
time, sec
26
Current, A
0.3
0.25
Theoretical compensated
current
0.2
0.15
0.1
0.05
Time of
energization
0
-0.05
-0.1
-0.15
-0.2
0.04
0.06
0.08
0.1
0.12
0.14
0.16
0.18
time, sec
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
0.04
0.06
0.08
0.1
0.12
0.14
0.16
0.18
time, sec
27
Forward t0
travel
time
Return
travel
t3
time
RELAY 2
tf
t1 Relay
turn-around
t2 time
ping-pong
tr
t f tr
t3 t0 t2 t1
2
Relay 2
Communication path
0
8.33 ms
Capture T2i-2=2.3
5.1
Capture T1i-2=5.1
2.3
8.33 ms
Send T1i-2=5.1
8.33
8.33
Store T1i-2=5.1
8.33 ms
13.43
Store T2i-2=2.3
Send T2i-2=2.3
10.53
8.33 ms
Send T1i-1=16.66
16.66
16.66
Send T2i-1=16.66
8.33 ms
21.76
Store T2i-1=16.66
Capture T1i=21.76
T1i-3=0
T2i-2=2.3
T2i-1=16.66
T1i=21.76
Store T1i-1=8.33
Capture T2i=18.96
18.96
T2i-3=0
T1i-2=5.1
T1i-1=16.66
T2i=18.96
a1=2.3-0=2.3
b1=21.76-16.66=5.1
1=(2.3-5.1)/2=
= -1.4ms (ahead)
a2=5.1-0=5.1
b2=18.96-16.66=2.3
2=(5.1-2.3)/2=
= +1.4ms (behind)
Speed up
Slow down
30
t1
t2
28
Relay 2
33.32
Store T1i-3=33.32
33.32
Store T2i-3=33.32
8.52 ms
38.28
Capture T1i-2=38.28
Capture T2i-2=35.62
35.62
8.14 ms
41.55
Send T1i-2=38.28
41.55
Send T2i-2=35.62
8.52 ms
Store T1i-2=38.28
Store T2i-2=35.62
8.14 ms
Send T1i-1=50.00
50.00
8.52 ms
54.03
49.93
Send T2i-1=49.93
53.16
Store T1i-1=50.00
Capture T2i=53.16
Store T2i-1=49.93
Capture T1i=54.03
8.14 ms
T1i-3=33.32
T2i-2=35.62
T2i-1=49.93
T1i=54.03
T2i-3=33.32
T1i-2=38.28
T1i-1=50.00
T2i=53.16
a1=35.62-33.32=2.3
b1=54.03-49.93=4.1
1=(2.3-4.1)/2=
= -0.9ms (ahead)
a2=38.28-33.32=4.96
b2=53.16-50.00=3.16
2=(4.96-3.16)/2=
= +0.9ms (behind)
Speed up
Slow down
0
19.5
30
t1
t2
Virtual Shaft
clock 1
clock 2
29
L90-3
L90-1
L90-3
Data (currents)
Transfer Trip
30
L90-1
L90-2
I_0
31
32
ADM-2
ADM-3
RELAY 2
RELAY 1
Rx
Tx
ADM-1
Tx
ADM-4
Rx
33
ADM-2
ADM-3
GPS clock
GPS clock
Rx
Tx
ADM-1
Tx
RELAY 1
ADM-4
Rx
RELAY 2
34
SETTINGS
OR
GPS COMPENSATION
Off = 0
RUN
Use Calculated
Correction, Establish and
Update Memory
FLEXLOGIC OPERAND
87L DIFF GPS FAIL
SETTINGS
AND
Use Memorized
Correction
OR
OR
AND
OR
FLEXLOGIC OPERAND
87L DIFF GPS 1 FAIL
RUN
FLEXLOGIC OPERAND
87L DIFF 1 MAX ASYM
ACTUAL VALUES
Ch1 Assymtery
RUN
FLEXLOGIC OPERAND
ACTUAL VALUES
ACTUAL VALUES
AND
GPS function
RUN
FLEXLOGIC OPERAND
| Ch2 Assymetry | > MAX
Ch2 Assymtery
RUN
ACTUAL VALUES
Ch2 Round Trip Time
FLEXLOGIC OPERAND
|Ch2 T-Time New Ch2 T-TIME Old| > CHANGE
35
Asymmetry-disabled
(about 3 ms of
asymmetry present)
Diff. Current
high
Asymmetry-enabled
(about 3 ms of
asymmetry present)
Diff. Current
low
36
Compute
Frequency
Deviation
f f1
+
+
+
System
Frequency
_
f1
RELAY 2
_
f2
Compute
Frequency
Deviation
f f2
Phase Frequency
Loop Filter
Phase Frequency
Loop Filter
1
+
+
+
(2 1)/2
Ping-Pong
Phase
Deviation
time stamps
Ping-Pong
Phase
Deviation
(2 1)/2
(2 1)/2
GPS
Phase
Deviation
time stamps
GPS
Phase
Deviation
(2 1)/2
GPS
Clock
GPS
Clock
37
38
Test Set 2
Tx
(64Kbps)
Tx
Rx
39
L90 system is
chosen
Charging current
enabled/disabled
Channel ID
enabled/disabled
Channel ID
enabled/disabled
87L enabled
Source chosen
Pickup
CT Tap
40
Slope 1
Slope 2
DTT
External DTT
2000/5
Rx
Tx
(64Kbps)
Tx
Rx
41
Restraint 2
Disturbance Detector-logic
diagram
42
43
87L should
operate at the
current
Rx
Tx
(64Kbps)
Tx
Rx
Test Set
Rx
87L should
NOT operate
Tx
(64Kbps)
Tx
Rx
Test Set 1
Tx
(64Kbps)
Tx
Rx
Operate /
Restraint
Characteristics
44
Relays response
Injected currents
SETTING
87L TRIP FUNCTION:
Disable=0
Enable=1
SETTING
SETTING
IA
IA > PICKUP
IB
IB > PICKUP
IC
IC > PICKUP
SETTING
87L TRIP SEAL-IN:
Enable=1
AND
FLEXLOGIC OPERAND
87L DIFF OP A
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR
AND
87L TRIP OP A
OR
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR
AND
87L DIFF OP B
87L TRIP OP B
OR
Mode is hosen:
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
1P or 3P
FLEXLOGIC OPERAND
OR
AND
87L DIFF OP C
87L TRIP OP C
FLEXLOGIC OPERAND
OR
OR
87L TRIP OP
OR
SETTING
87L TRIP M ODE:
1-Pole=0
3-Pole=1
AND
SETTING
AND
87L TRIP SUPV:
50DD SV
Supervising
element 50DD
AND
OR
OR
50
AND
OR
SETTING
87L TRIP FORCE 3- :
OR
Off=0
FLEXLOGIC OPERAND
AND
OR
OPEN POLE OP
45
SETTING
87L TRIP FUNCTION:
Disable=0
Seal-in outputs if
Enable=1
SETTING
SETTING
IA
IB > PICKUP
IC
IC > PICKUP
Outputs per
phase or 3-phase
desirable
IA > PICKUP
IB
SETTING
87L TRIP SEAL-IN:
Enable=1
AND
FLEXLOGIC OPERAND
87L DIFF OP A
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR
AND
87L TRIP OP A
OR
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR
AND
87L DIFF OP B
87L TRIP OP B
OR
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
OR
AND
87L DIFF OP C
87L TRIP OP C
FLEXLOGIC OPERAND
OR
OR
87L TRIP OP
OR
SETTING
Logic to detect
multi-phase
evolving and
sequential faults
Open Pole
forces 3P trip
if another
fault occurs
during open
pole
conditions
AND
87L TRIP SUPV:
50DD SV
AND
OR
OR
50
AND
OR
SETTING
87L TRIP FORCE 3- :
OR
Off=0
FLEXLOGIC OPERAND
AND
OR
OPEN POLE OP
Grouped elements
46
Line disconnect
switch 52b contact
IOC trigger
47
Breaker
Line
Breaker
IOC
48
49
50
51
52
Control elements
53
Control elements
available in L90
Synchrocheck
Logic
54
3-phase
line VT
1-phase
bus VT
AutoReclose sequence
55
SETTING
AR FUNCTION:
Enable=1
Disable=0
D60 Relay Only
FLEXLOGIC OPERAND
LINE PICKUP OP
AND
FLEXLOGIC OPERANDS
AR ENABLED
SETTING
AR DISABLED
OR
AR INITIATE
AR BLOCK:
Off = 0
FLEXLOGIC OPERAND
SETTING
AR RIP
0.5 cycle
AND
SETTING
Off = 0
OR
(Evolving fault)
(From sheet 3)
FLEXLOGIC OPERAND
AND
SETTING
AR 1-P RIP
LO
AR 1P INIT:
Off = 0
TRIP 1-POLE
OR
OR
FLEXLOGIC OPERAND
D60 Relay Only From Trip Output
SETTING
SETTING
Off = 0
AND
OR
0
SETTING
SETTING
AR 3P INIT:
AR 3-P/1 RIP
Off = 0
SETTING
OR
OR
FLEXLOGIC OPERAND
OR
AR DEAD TIME 1
EXTENSION:
FLEXLOGIC OPERAND
AND
OR
AND
OR
SETTING
AR 3P TD INIT:
Off = 0
SETTING
CLOSE (to page 2)
OR
From sheet 3
Off = 0
OR
BKR ONE POLE OPEN
SETTING
BKR 3 POLE OPEN:
FLEXLOGIC OPERAND
AR 3-P/2 RIP
Off = 0
OR
SETTING
OR
AND
RESET
CLOSE BKR1 OR BKR2
From Sheet 2
OR
FLEXLOGIC OPERAND
0
AND
OR
AR SHOT COUNT>0
SETTING
FLEXLOGIC OPERAND
AR INCOM PLETE SEQ
AR PAUSE
827089AD.CDR
Off = 0
SHOT COUNT = MAX
AND
SETTING
AND
FLEXLOGIC OPERAND
AR M0DE:
AR LO
AND
1 Pole
SETTING
3 Pole - A
3 Pole -B
AR INCOMPLETE SEQ.
TIMER:
OR
OR
1 & 3 Pole
AND
AND
OR
OR
0
5ms
SETTING
AND
OR
AR MULTI-P FAULT:
OR
AR FORCE 3P TRIP
OR
AR ZONE 1 EXTENT
AutoReclose
logic
Evolving fault
OR
Off = 0
AR DISABLED
FLEXLOGIC OPERAND
AND
OR
OR
AND
AND
LO
AND
To sheet 3
AND
OR
AND
2ms
LO
OR
AND
AND
OR
OR
AND
S
Latch
OR
R
RESET
LO
AND
LO
AND
2ms
OR
AND
827090A9.CDR
AND
OR
AutoReclose
logic
56
AutoReclose
logic
Breaker Function
Breakers are set in
System Setup\
Breakers
LEDs
57
58
C60 3
Ethernet
Ethernet
B1
B3
Line 2
L90 2
L90 1
Substation 1
B2
B4
Substation
59
Direct
Outputs are
assigned with
Flexlogic
operands
This is active
in 3-terminal
only
Channel status
controls either
Direct Input is read
from the received
data or set to
default
60
Remote Relay
Breaker Fail is
assigned to Direct
Output 1-1
61
62
63
Thank you.