Vous êtes sur la page 1sur 54

New Era University

College of Engineering and Technology


Department of Electrical Engineering

EE 581D
Industrial Power Systems Design

Part 1, Chapter 1:
Load and Power System Design

Submitted by:
Arvin Joseph K. Torrente
BS EE 5

Submitted to:
Engr. Timoteo Limsiaco P.E.E.

Professor

1.1: Summary of Loads

No.
1
2
3
4
5
6
7
8

No.
1
2
3
4
5
6

Table 1.1.1: Low Voltage Load for Diesel


Power
HP
Power Rated
Load Description
Qty.
Rating
Rating
Factor
KVA
(KW)
Feed Pump
1
500
380
0.9
422.22
Heater/Boiler
1
600
450
0.9
500
Gas Separator Pump
1
200
150
0.9
166.67
Vapor Pump
1
250
190
0.9
211.11
Reboiler
1
450
350
0.9
388.89
Air Cooled Condenser
1
200
150
0.9
166.67
Reflux Pump
1
150
110
0.9
122.22
Product Output Pump
1
50
40
0.9
44.44
Total 2022.22
Table 1.1.2: Low Voltage Load for Kerosene
Power
HP
Power Rated
Load Description
Qty.
Rating
Rating
Factor
KVA
(KW)
Feed Pump
1
500
380
0.9
422.22
Caustic Circulation Pump
1
500
380
0.9
422.22
Caustic Settler Pump
1
350
260
0.9
288.89
Water Wash Output Pump
1
200
150
0.9
166.67
Salt-Bed Output Pump
1
200
150
0.9
166.67
Product Output Pump
1
50
40
0.9
44.44
Total 1511.11

Table 1.1.3: Low Voltage Load for LPG/Butane


No.

Load Description

Qty.

1
2
3
4
5
6
7
8

Feed Pump
Caustic Pre-wash Output Pump
Mercapton Extractor Pump
Water Wash Output Pump
Steam Heater
Salt-Bed Output Pump
Lean Merox Caustic Pump
Product Output Pump

1
1
1
1
1
1
1
1

Total Load:

Power
HP
Power Rated
Rating
Rating
Factor
KVA
(KW)
500
380
0.9
422.22
450
340
0.9
377.78
400
300
0.9
333.33
200
150
0.9
166.67
500
380
0.9
422.22
200
150
0.9
166.67
300
230
0.9
255.56
50
40
0.9
44.44
Total 2188.89
.

1.2: Schedule of Loads


Table 1.2.1: MCC01
Fdr

Connected Load

1
2
3
4
5
6
7
8

Feed Pump
Heater/Boiler
Gas Separator Pump
Vapor Pump
Reboiler
Air Cooled Condenser
Reflux Pump
Product Output Pump
Total

Volt
Rtg.

KVA
Rtg.

480
480
480
480
480
480
480
480

422.22
500
166.67
211.11
388.89
166.67
122.22
44.44
2022.22

PF
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9

FLA
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95

619.80
734.00
244.67
309.91
570.89
244.67
179.42
65.24
2968.6

Current Ratings
CB
OC
Conductor
Rating
Relay
1549.5 712.77
774.75
1835.0 844.10
917.50
611.68 281.37
305.84
774.78 356.40
387.39
1427.2 656.53
713.62
611.68 281.37
305.84
448.55 206.33
224.27
163.10
75.02
81.55

MC
465.0
562.5
187.5
237.5
437.5
187.5
137.5
50

Calculation for Feeders:


=

For feeder 1:
=

422220
3 480 0.9 0.95

250% = 619.80 250% = 1549.5


=
115% = 619.80 115% = 712.80
125% = 619.80 125% = 774.78
=
125% = 380 125% = 475

See Table for conductor and circuit protection ratings.

Table 1.2.2: MCC02


Fdr

Connected Load

Feed Pump
Caustic Circulation
Pump
Caustic Settler Pump
Water Wash Output
Pump
Salt-Bed Output Pump
Product Output Pump
Total

2
3
4
5
6

619.80

Current Ratings
CB
OC
Conductor
Rating
Relay
1549.5 712.77
774.75

465.0

0.95

619.80

1549.5

712.77

774.75

465.0

0.9

0.95

424.09

1060.2

487.71

530.12

325.0

166.67

0.9

0.95

244.67

611.68

281.37

305.84

187.5

166.67
44.44
1511.11

0.9
0.9

0.95
0.95

244.67
65.24
2218.27

611.68
163.10

281.37
75.02

305.84
81.55

187l5
50.00

Volt
Rtg.

KVA
Rtg.

PF

480

422.22

0.9

0.95

480

422.22

0.9

480

288.89

480
480
480

FLA

MC

Table 1.2.3: MCC03


Fdr

Connected Load

Feed Pump
Caustic Pre-wash
Output Pump
Mercapton Extractor
Pump
Water Wash Output
Pump
Steam Heater
Salt-Bed Output Pump
Lean Merox Caustic
Pump
Product Output Pump
Total

2
3
4
5
6
7
8

619.80

Current Ratings
CB
OC
Conductor
Rating
Relay
1549.5 712.77
774.75

465.0

0.95

554.58

1386.5

637.77

693.23

425.0

0.9

0.95

489.33

1223.3

562.73

611.66

375.0

166.67

0.9

0.95

244.67

611.68

281.37

305.84

187.5

480
480

422.22
166.67

0.9
0.9

0.95
0.95

619.80
244.67

1549.5
611.68

712.77
281.37

774.75
305.84

465.0
187.5

480

255.56

0.9

0.95

375.16

937.91

431.44

468.95

287.5

480

44.44
2188.89

0.9

0.95

65.24
3213.25

163.10

75.02

81.55

50

Volt
Rtg.

KVA
Rtg.

PF

480

422.22

0.9

0.95

480

377.78

0.9

480

333.33

480

FLA

MC

Fdr
1
2
3

Table 1.2.4: Main Distribution Panel / Main Station


Current Ratings
Volt
Connected Load
CB
Rtg.
FLA
Conductor
Rating
MCC01
480 2968.60 4007.61
3710.75
MCC02
480 2218.27 2994.66
2772.84
MCC03
480 3213.25 4337.89
4016.56
Total
8400.12 11340.16
10500.15
For Main Distribution Panel / Main Station

Use; 3PST, 480V, 12000A, 133KAIC Circuit Breaker


As per NEC 430-52 for motor fuse:
Table 1.2.5: Maximum Size of Motor Fuse from Full Load Line Current
Type of Motor
Time Delay Fuse
Non-Time Delay Fuse
Single Phase
300%
175%
Three Phase
300%
175%
Synchronous
300%
175%
Wound Rotor
150%
150%
Direct Current
150%
15%
For feeder 1 of MCC01:
(

= 300%
1) = 300% 619.80 =
= 175%
= 175% 619.80 =

Feeder
No.

Table 1.2.6: Maximum Motor Fuse Rating


Full Load
Fuse Rating (Amp)
Current (FLA)
Time Delay Fuse
Non-Time Delay Fuse

MCC01
1
2
3
4
5
6
7
8

619.80
734.00
244.67
309.91
570.89
244.67
179.42
65.24

1859.40
2202.00
734.00
929.73
1712.67
734.00
538.26
195.72

1084.65
1284.50
428.17
542.34
999.06
428.17
313.99
114.17
5

MCC02
1
2
3
4
5
6

619.80
619.80
424.09
244.67
244.67
65.24

1859.40
1859.40
1272.27
734.00
734.00
195.72

1084.65
1084.65
742.16
428.17
428.17
114.17

MCC03
1
2
3
4
5
6
7
8

619.80
554.58
489.33
244.67
619.80
244.67
375.16
65.24

1859.40
1663.74
1467.99
734.00
1859.40
734.00
1125.48
195.72

1084.65
970.52
856.33
428.17
1084.65
428.17
656.53
114.17

*See Part 2 Chapter 3.5 For Generator Sizing and Protection

New Era University


College of Engineering and Technology
Department of Electrical Engineering

EE 581D
Industrial Power Systems Design

Part 1, Chapter 2:
Voltage Drop

Submitted by:
Arvin Joseph K. Torrente
BS EE 5

Submitted to:
Engr. Timoteo Limsiaco P.E.E.

Professor

2.1 Transformer and Transient Voltage Drop Due to Motor


Starting
Transformer Specs:
6.3MVA, 13.5kV/460V, 7.15% impedance, 10% allowable voltage drop
Transformer Full Load Current (FLCT):
=

(1.732 )
5722.22
1.732 460

=
=

Short Circuit Current at Secondary Side (ISC):


=

7182.22
7.15
100

Maximum KVA of Transformer at Rated Short Circuit Current (Q1)


1=
1=
=

1.732)
1000

460 100450.63 1.732


1000
,

Motor In-Rush KVA at Starting


=

1.732
1000

7182.22 460 100% 1.732


1000
=
8

Voltage Drop at Transformer Secondary Due to Motor In-Rush

100%

5722
100%
80031
= .

(100% 7.15%)
= 460 92.85%
=
.

For verification:
65%? 4668.3 < 7182
=
Therefore,
Size of Transformer is Adequate

2.2: Determination of Cable and its Distance


*Initial values

Feeder Conductor
No.
Current
Rating
(Amp)
MDP
10500.18
Main
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8

3710.76
774.75
917.50
305.84
387.39
713.62
305.84
224.27
81.55

Table 2.2.1: Conductor Sizing


Conductor Size
mm2
21 3 400
MCC01
8 3 400
2 3 250
2 3 400
3 175
3 250
2 3 250
3 175
3 100
3 22

@ 90
@ 90
@ 90
@ 90
@ 90
@ 90
@ 90
@ 90
@ 90
@ 90

Equivalent
MCM/AWG
750MCM
750MCM
500MCM
750MCM
350MCM
500MCM
500MCM
350MCM
4/0 AWG
4 AWG
9

Table 2.2.1 (Cont.)


Conductor Size

Feeder Conductor
No.
Current
Rating
(Amp)

Main
2-1
2-2
2-3
2-4
2-5
2-6

2772.85
774.75
774.75
530.12
305.84
305.84
81.55

Main
3-1
3-2
3-3
3-4
3-5
3-6
3-7
3-8

4016.57
774.75
693.23
611.66
305.84
774.75
305.84
468.95
81.55

mm2

Equivalent
MCM/AWG

MCC02
6 3 400
2 3 250
2 3 250
2 3 150
3 175
3 175
3 22
MCC03
8 3 400
2 3 250
2 3 200
2 3 175
3 175
2 3 250
3 175
3 400
3 22

@ 90
@ 90
@ 90
@ 90
@ 90
@ 90
@ 90

750MCM
500MCM
500MCM
300MCM
350MCM
350MCM
4 AWG

@ 90
@ 90
@ 90
@ 90
@ 90
@ 90
@ 90
@ 90
@ 90

750MCM
500MCM
400MCM
350MCM
350MCM
500MCM
350MCM
750MCM
4 AWG

2.3: Calculation of Voltage Drop on the Conductors


=(

1
305

While,
IL = Line Current
RC = Conductor Resistance
L = Length of conductor
C = No. of parallel runs
Computing for MDP Conductor line drop:
= (0.031 8400.12)
% =

100 =

480

72
1
= .
305 21
(480 2.9272)
100 = .
480

10

FEEDER NO.
MDP

Table 2.3.1: Voltage Drop of Conductors


DISTANCE
VDROP (V)
VDROP (%)
(M)
72
2.92
0.6098

REMARKS
Vdrop<5%

MCC01
MAIN
1
2
3
4
5
6
7
8

30
45
25
50
35
38
28
30
40

1.1315
2.0575
0.9325
2.5269
1.6004
1.6004
1.4151
1.7648
4.3636

0.8441
1.2724
1.0380
1.3702
1.1772
1.1772
1.1386
1.2114
1.7528

Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%

0.8432
1.2724
1.1009
1.1566
1.3175
1.3070
1.7528

Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%

1.0989
1.3102
1.1438
1.1784
1.3363
1.2816
1.2837
1.0770
1.8170

Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%
Vdrop<2%

MCC02
MAIN
1
2
3
4
5
6

30
47
27
30
45
44
40

1.1273
2.0575
1.2345
1.5017
2.2742
2.2237
4.3636
MCC03

MAIN
1
2
3
4
5
6
7
8

30
47
27
30
45
44
40
27
42

1.2247
2.1490
1.3501
1.5161
2.2742
2.0118
2.0215
1.0295
4.5818

11

New Era University


College of Engineering and Technology
Department of Electrical Engineering

EE 581D
Industrial Power Systems Design

Part 1, Chapter 3:
Power System Design

Submitted by:
Arvin Joseph K. Torrente
BS EE 5

Submitted to:
Engr. Timoteo Limsiaco P.E.E.

Professor

12

13.8KV
FROM UTILITY

T1 6.3MVA, 13.4/0.48KV, %Z = 7.15%


72M 11 x 3 x 800MM2 XLPE
UNARMOURED IN PVC CONDUIT

FROM AUX
SUPPLY

MAIN
STATION
ATS

3PST 480V
12KA 133KAIC

30M 3 x 3 x 800MM2 XLPE


UNARMOURED IN PVC CONDUIT

MCC01 (DIESEL PROCESSING)


CF

LOAD DESCRIPTION

30M 2 x 3 x 800MM2 XLPE


UNARMOURED IN PVC CONDUIT

30M 3 x 3 x 800MM2 XLPE


UNARMOURED IN PVC CONDUIT

MCC02

MCC01

MCC03

MCC03 (BUTANE PROCESSING)

RATING

CF

LOAD DESCRIPTION

RATING

FEED PUMP

422.22KVA

FEED PUMP

HEATER/BOILER

500.00KVA

CAUSTIC PRE-WASH OUTPUT PUMP 377.78KVA

GAS SEPARATOR PUMP

166.67KVA

MERCAPTON EXTRACTOR PUMP

333.33KVA

VAPOR PUMP

211.11KVA

WATER WASH OUTPUT PUMP

166.67KVA

REBOILER

388.89KVA

STEAM HEATER

422.22KVA

AIR COOLED CONDENSER

166.67KVA

SALT BED OUTPUT PUMP

166.67KVA

REFLUX PUMP

122.22KVA

LEAN MEROX CAUSTIC PUMP

255.56KVA

PRODUCT OUTPUT PUMP

44.44KVA

PRODUCT OUTPUT PUMP

3PST 480V
3000A 108KAIC

SEE LOAD SCHEDULE FOR


RATINGS

SEE LOAD SCHEDULE FOR RATINGS

3PST 480V
2500A 101KAIC

3PST 480V
3300KA 109KAIC
SEE LOAD SCHEDULE FOR RATINGS

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

422.22KVA

44.44KVA

MCC02 (KEROSENE PROCESSING)


CF

LOAD DESCRIPTION

RATING

FEED PUMP

422.22KVA

CAUSTIC CIRCULATION PUMP

422.22KVA

CAUSTIC SETTLER PUMP

288.89KVA

WATER WASH OUTPUT PUMP

166.67KVA

SALT BET OUTPUT PUMP

166.67KVA

PRODUCT OUTPUT PUMP

44.44KVA

HAYDAR ALIEV REFINERY PLANT

E-1

CF

LOAD

MCC01

MCC02

MCC03

MV FROM GRID

FROM AUX
SUPPLY
MDP
ATS

HAYDAR ALIEV REFINERY PLANT

E-2

LV FROM
MAIN STATION

Circuit Breaker
Magnetic Contactor
Relay Fuse

FROM AUX
SUPPLY
MCC01

MCC01 (DIESEL PROCESSING)

ATS

CF

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

HAYDAR ALIEV REFINERY PLANT

LOAD

FEED PUMP

HEATER/BOILER

GAS SEPARATOR PUMP

VAPOR PUMP

REBOILER

AIR COOLED CONDENSER

REFLUX PUMP

PRODUCT OUTPUT PUMP

E-3

LV FROM
MAIN STATION
FROM AUX
SUPPLY
MCC02
ATS

M
3

M
3

M
3

M
3

M
3

M
3

MCC02 (KEROSENE PROCESSING)


CF

LOAD

FEED PUMP

CAUSTIC CIRCULATION PUMP

CAUSTIC SETTLER PUMP

WATER WASH OUTPUT PUMP

SALT BET OUTPUT PUMP

PRODUCT OUTPUT PUMP

HAYDAR ALIEV REFINERY PLANT

E-4

LV FROM
MAIN STATION
FROM AUX
SUPPLY
MCC03
ATS
MCC05 (BUTANE PROCESSING)
CF

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

HAYDAR ALIEV REFINERY PLANT

LOAD

FEED PUMP

CAUSTIC PRE-WASH OUTPUT PUMP

MERCAPTON EXTRACTOR PUMP

WATER WASH OUTPUT PUMP

STEAM HEATER

SALT BED OUTPUT PUMP

LEAN MEROX CAUSTIC PUMP

PRODUCT OUTPUT PUMP

E-5

New Era University


College of Engineering and Technology
Department of Electrical Engineering

EE 581D
Industrial Power Systems Design

Part 1, Chapter 4:
Short Circuit Calculations

Submitted by:
Arvin Joseph K. Torrente
BS EE 5

Submitted to:
Engr. Timoteo Limsiaco P.E.E.

Professor

18

13.8KV
FROM UTILITY

FP1
T1 6.3MVA, 13.4/0.48KV, %Z = 7.15%
11 x 3 x 800MM2 XLPE UNARMOURED
IN PVC CONDUIT

FROM AUX
SUPPLY

MAIN
STATION
ATS

3PST 480V
12KA 133KAIC

FP2

3 x 3 x 800MM2 XLPE UNARMOURED


IN PVC CONDUIT

MCC01 (DIESEL PROCESSING)


CF

LOAD DESCRIPTION

2 x 3 x 800MM2 XLPE UNARMOURED


IN PVC CONDUIT

3 x 3 x 800MM2 XLPE UNARMOURED


IN PVC CONDUIT

MCC02

MCC01

MCC03

MCC03 (BUTANE PROCESSING)

RATING

CF

LOAD DESCRIPTION

RATING

FEED PUMP

422.22KVA

FEED PUMP

HEATER/BOILER

500.00KVA

CAUSTIC PRE-WASH OUTPUT PUMP 377.78KVA

GAS SEPARATOR PUMP

166.67KVA

MERCAPTON EXTRACTOR PUMP

333.33KVA

VAPOR PUMP

211.11KVA

WATER WASH OUTPUT PUMP

166.67KVA

REBOILER

388.89KVA

STEAM HEATER

422.22KVA

AIR COOLED CONDENSER

166.67KVA

SALT BED OUTPUT PUMP

166.67KVA

REFLUX PUMP

122.22KVA

LEAN MEROX CAUSTIC PUMP

255.56KVA

PRODUCT OUTPUT PUMP

44.44KVA

PRODUCT OUTPUT PUMP

3PST 480V
3000A 108KAIC

SEE LOAD SCHEDULE FOR


RATINGS

FP3

SEE LOAD SCHEDULE FOR RATINGS

FP4

3PST 480V
2500A 101KAIC

3PST 480V
3300KA 109KAIC

FP5

FP7

SEE LOAD SCHEDULE FOR RATINGS

FP6

422.22KVA

44.44KVA

FP8

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

M
3

MCC02 (KEROSENE PROCESSING)


CF

LOAD DESCRIPTION

RATING

FEED PUMP

422.22KVA

CAUSTIC CIRCULATION PUMP

422.22KVA

CAUSTIC SETTLER PUMP

288.89KVA

WATER WASH OUTPUT PUMP

166.67KVA

SALT BET OUTPUT PUMP

166.67KVA

PRODUCT OUTPUT PUMP

44.44KVA

HAYDAR ALIEV REFINERY PLANT

E-6

4.2: Percent Impedance Calculation


4.2.1: Per Unit Method
Procedure in using the Per Unit Method
1. Draw the system diagram.
2. Draw the impedance diagram
3. Obtain the source short circuit level
4. Select KVA base.
5. Compute the Per Unit (PU) value of utility source.
6. Compute the PU value of transformer.
7. Compute the PU value for feeder lines.
8. Compute the PU value for motor contribution.
9. Compute the short circuit currents at designated points.
Given: Available S.C. MVA @ 13.8KV, 3 is 1000MVA with X/R = 11.
Computing for Per Unit (PU) Impedance Value of Utility Source ZS
=
. .

MVAbase = 5.7MVA
=

5.7
1000

= .
=

. .

cos

= 0.0057 cos(tan

11) =

sin

= 0.0057 sin(tan

11) = .

= .

= .

. .
. .
.

Computing for PU Impedance Value of Main Feeder Cable ZMC


=
=

305

0.031 72
5.7

305 21
13.5

= .

. .

20

Computing for PU Impedance Value of Transformer ZT


Transformer Specs:
6.3MVA, 13.5/0.48KV, %Z=7.15%, %R=1.13%, %X=6.72%, X/R=5.95
= 480
=

%
100

6.72 0.480
= .
100 0.480

. .

%
100

1.13 0.480
= .
100 0.480

. .

= 0.0672 + 0.0113 = .

Computing for PU Impedance Value of Feeder Cable ZC-1

=
=

305

0.031 30
5.7

305 8
0.48

= .

. .

Computing for PU Impedance Value of Motor ZM1-1


Motor Specs:
500HP, 422.22KVA, Xd=3%, X/R=11
=
=

"

100

+
=

3
480

100
480

0.405
= .
11

= 0.0368 + 0.405 = .

5.7
= .
0.422

. .

. .

21

FP1

ZT

ZMC

ZC3

ZC2

ZC1

ZC1-1

ZC1-2

ZC1-3

ZC1-4

ZC1-5

ZC1-6

ZC1-7

ZC1-8

ZC2-1

ZC2-2

ZC2-3

ZC2-4

ZC2-5

ZC2-6

ZC3-1

ZC3-2

ZC3-3

ZC3-4

ZC3-5

ZC3-6

ZC3-7

ZC3-8

ZM1-1

ZM1-2

ZM1-3

ZM1-4

ZM1-5

ZM1-6

ZM1-7

ZM1-8

ZM2-1

ZM2-2

ZM2-3

ZM2-4

ZM2-5

ZM2-6

ZM3-1

ZM3-2

ZM3-3

ZM3-4

ZM3-5

ZM3-6

ZM3-7

ZM3-8

HAYDAR ALIEV REFINERY PLANT

E-7

FP2

ZMC

ZC3

ZC2

ZC1

ZT

ZC1-1

ZC1-2

ZC1-3

ZC1-4

ZC1-5

ZC1-6

ZC1-7

ZC1-8

ZC2-1

ZC2-2

ZC2-3

ZC2-4

ZC2-5

ZC2-6

ZC3-1

ZC3-2

ZC3-3

ZC3-4

ZC3-5

ZC3-6

ZC3-7

ZC3-8

ZM1-1

ZM1-2

ZM1-3

ZM1-4

ZM1-5

ZM1-6

ZM1-7

ZM1-8

ZM2-1

ZM2-2

ZM2-3

ZM2-4

ZM2-5

ZM2-6

ZM3-1

ZM3-2

ZM3-3

ZM3-4

ZM3-5

ZM3-6

ZM3-7

ZM3-8

HAYDAR ALIEV REFINERY PLANT

E-8

ZC1-1

ZC1-2

ZC1-3

ZC1-4

ZC1-5

ZC1-6

ZC1-7

ZC1-8

ZC2-1

ZC2-2

ZC2-3

ZC2-4

ZC2-5

ZC2-6

ZC3-1

ZC3-2

ZC3-3

ZC3-4

ZC3-5

ZC3-6

ZC3-7

ZC3-8

ZM1-1

ZM1-2

ZM1-3

ZM1-4

ZM1-5

ZM1-6

ZM1-7

ZM1-8

ZM2-1

ZM2-2

ZM2-3

ZM2-4

ZM2-5

ZM2-6

ZM3-1

ZM3-2

ZM3-3

ZM3-4

ZM3-5

ZM3-6

ZM3-7

ZM3-8

ZT

ZMC

ZC2

ZC3

ZC1

FP3

HAYDAR ALIEV REFINERY PLANT

E-9

ZT

ZMC

ZC3

ZC2

ZC1

ZC1-2

ZC1-3

ZC1-4

ZC1-5

ZC1-6

ZC1-7

ZC1-8

ZC2-1

ZC2-2

ZC2-3

ZC2-4

ZC2-5

ZC2-6

ZC3-1

ZC3-2

ZC3-3

ZC3-4

ZC3-5

ZC3-6

ZC3-7

ZC3-8

ZM1-2

ZM1-3

ZM1-4

ZM1-5

ZM1-6

ZM1-7

ZM1-8

ZM2-1

ZM2-2

ZM2-3

ZM2-4

ZM2-5

ZM2-6

ZM3-1

ZM3-2

ZM3-3

ZM3-4

ZM3-5

ZM3-6

ZM3-7

ZM3-8

ZC1-1

ZM1-1

FP4

HAYDAR ALIEV REFINERY PLANT

E-10

ZC1-1

ZC1-2

ZC1-3

ZC1-4

ZC1-5

ZC1-6

ZC1-7

ZC1-8

ZC2-1

ZC2-2

ZC2-3

ZC2-4

ZC2-5

ZC2-6

ZC3-1

ZC3-2

ZC3-3

ZC3-4

ZC3-5

ZC3-6

ZC3-7

ZC3-8

ZM1-1

ZM1-2

ZM1-3

ZM1-4

ZM1-5

ZM1-6

ZM1-7

ZM1-8

ZM2-1

ZM2-2

ZM2-3

ZM2-4

ZM2-5

ZM2-6

ZM3-1

ZM3-2

ZM3-3

ZM3-4

ZM3-5

ZM3-6

ZM3-7

ZM3-8

ZT

ZMC

ZC1

ZC3

ZC2

FP5

HAYDAR ALIEV REFINERY PLANT

E-11

ZT

ZMC

ZC3

ZC2

ZC1

ZC1-1

ZC1-2

ZC1-3

ZC1-4

ZC1-5

ZC1-6

ZC1-7

ZC1-8

ZC2-2

ZC2-3

ZC2-4

ZC2-5

ZC2-6

ZC3-1

ZC3-2

ZC3-3

ZC3-4

ZC3-5

ZC3-6

ZC3-7

ZC3-8

ZM1-1

ZM1-2

ZM1-3

ZM1-4

ZM1-5

ZM1-6

ZM1-7

ZM1-8

ZM2-2

ZM2-3

ZM2-4

ZM2-5

ZM2-6

ZM3-1

ZM3-2

ZM3-3

ZM3-4

ZM3-5

ZM3-6

ZM3-7

ZM3-8

ZC2-1

ZM2-1

FP6

HAYDAR ALIEV REFINERY PLANT

E-12

ZC1-1

ZC1-2

ZC1-3

ZC1-4

ZC1-5

ZC1-6

ZC1-7

ZC1-8

ZC2-1

ZC2-2

ZC2-3

ZC2-4

ZC2-5

ZC2-6

ZC3-1

ZC3-2

ZC3-3

ZC3-4

ZC3-5

ZC3-6

ZC3-7

ZC3-8

ZM1-1

ZM1-2

ZM1-3

ZM1-4

ZM1-5

ZM1-6

ZM1-7

ZM1-8

ZM2-1

ZM2-2

ZM2-3

ZM2-4

ZM2-5

ZM2-6

ZM3-1

ZM3-2

ZM3-3

ZM3-4

ZM3-5

ZM3-6

ZM3-7

ZM3-8

ZT

ZMC

ZC1

ZC2

ZC3

FP7

HAYDAR ALIEV REFINERY PLANT

E-13

ZT

ZMC

ZC3

ZC2

ZC1

ZC1-1

ZC1-2

ZC1-3

ZC1-4

ZC1-5

ZC1-6

ZC1-7

ZC1-8

ZC2-1

ZC2-2

ZC2-3

ZC2-4

ZC2-5

ZC2-6

ZC3-2

ZC3-3

ZC3-4

ZC3-5

ZC3-6

ZC3-7

ZC3-8

ZM1-1

ZM1-2

ZM1-3

ZM1-4

ZM1-5

ZM1-6

ZM1-7

ZM1-8

ZM2-1

ZM2-2

ZM2-3

ZM2-4

ZM2-5

ZM2-6

ZM3-2

ZM3-3

ZM3-4

ZM3-5

ZM3-6

ZM3-7

ZM3-8

ZC3-1

ZM3-1

FP8

HAYDAR ALIEV REFINERY PLANT

E-14

ZT

FP1

FP2

ZMC
ZT

ZC1-1 to 1-8

ZMC

ZC2-1 to 2-6

ZC3-1 to C3-8

ZC1

ZC2

ZC3

ZC1-2 to C1-8

ZC2-1 to C2-6

ZC3-1 to C3-8

ZM1-2 to 1-8

ZM2-1 to M2-6

ZM3-1 to 3-8

ZMC

ZM1-1 to 1-8

ZM2-1 to 2-6

ZM3-1 to 3-8

ZT

ZC1

ZC2

ZC3

ZC1

ZC2

ZC3

ZT

ZC1-1 to C1-8

ZC2-1 to C2-6

ZC3-1 to C3-8

ZC2

ZMC

ZC1-1 to C1-8

ZC2-1 to C2-6

ZC3

ZC3-1 to C3-8

ZC1

ZM1-1 to M1-8

ZM2-1 to M2-6

ZM3-1 to M3-8

ZM1-1 to M1-8

ZM2-1 to M2-6

ZM3-1 to M3-8

ZC1-1
FP3

ZM1-1

FP4

HAYDAR ALIEV REFINERY PLANT

E-15

ZC1-1 to 1-8

ZC2-1 to 2-6

ZT

ZT

ZMC

ZMC

ZC3-1 to C3-8

ZC1-1 to 1-8

ZC2

ZC1

ZM1-1 to 1-8

ZM2-1 to 2-6

ZC2-1 to 2-6

ZC3-1 to C3-8

ZC3

ZM1-1 to 1-8

ZM3-1 to 3-8

ZT

ZM2-1 to 2-6

ZC1

ZC2

ZC3

ZC1-1 to C1-8

ZC2-1 to C2-6

ZC3-2 to C3-8

ZM1-1 to 1-8

ZM2-1 to M2-6

ZM3-2 to 3-8

ZM3-1 to 3-8

ZT

ZC1-1 to C1-8

ZC1

ZMC

ZC2-2 to C2-6

ZC3-1 to C3-8

ZC3

ZC1

ZMC

ZM1-1 to 1-8

ZM2-2 to M2-6

ZM3-1 to 3-8

ZC2

ZC3

ZC3

ZC2-1
FP5

ZC3-1
FP7

ZM2-1

ZM3-1

FP6

FP8

HAYDAR ALIEV REFINERY PLANT

E-16

4.3: Calculation of Short Circuit Currents


Based from IEEE 141-1993 P. 125
Procedures for calculating industrial system short-circuit:
A. Prepare system diagrams
B. Collect and convert impedance data
C. Combine impedances
D. Calculate short-circuit current
A. System Diagrams
A full-detail one-line diagram can be found on the next page.
B. Impedance Data
Impedance data, including both reactance and resistance,
should be collected for important elements and converted to
per-unit on bases selected for the study.
Since resistance is not constant but varies with temperature,
consideration should be given to the choice of resistance values for
study purposes.
For calculations of maximum short-circuit currents to select
electric power system equipment, a fully loaded industrial power
system is recommended because it has the largest number of
motors connected and contributing to short-circuit current.
Consequently, hot or rated load resistance values are usually
accepted for these calculations.
Fault Duty Calculation at Fault Point 1 (High Side 13.5kV)
Given data: 1000MVA Short Circuit Utility, X/R is 11%,
MVAbase = 5.7;

kVbase = 0.480
. .

. .

. .

. . cos

=
. .

= 0.0057 cos(

. . sin

. .

5.7
= .
1000

= 0.0057 cos(tan
. .

. .

11) = .

. .

11) = .

= 0.000516 + 0.005677 = .

. .

.
32

5.7

3 13.5 0.0057

Transformer
Transformer Data:
5.7MVA, 13.5/0.48KV, %Z=7.15%, X/R=13.3

. .

Fig. 4.3.1: X/R Ratio of Transformers


(From IIEE Standard 141, p.184)
%
5.7 7.15
=

= .
100
5.7 100
= tan

. .

. .

. .

= .

. . cos

tan

. . sin

= tan

13.3 =

= .

= 0.0715 cos(
= 0.0715 sin(tan

13.3 ) = .
13.3) = .

. .

. .
. .

33

For Feeder Cable from Transformer to Main Distribution Panel


Size of cable is 21sets x 3 x 400mm2 THHN XLPI, Unarmored Cable
Length of cable is 72m connected in parallel. Refer to PEC 2009 Ed. Table
9.1.1.9 on page 1506 or NEC 2015 Ed. Table 9 on page 767 for values of X
and R.
=

0.031
305

0.038
305

. .

305

0.031 72
5.7

= .
305 21
0.48

. .

. .

305

0.038 72
5.7

= .
305 21
0.48

. .

. .

. .

. .

= .

= .

For Feeder Cables from Main Distribution Panel to MCC01


Size of cable is 8sets x 3x 400mm2 THHN XLPI, Unarmored Cable
Length of cable is 30m connected in parallel. Refer to PEC 2009 Ed. Table
9.1.1.9 on page 1506 or NEC 2015 Ed. Table 9 on page 767 for values of X
and R.
=

. .

. .

0.031
305

0.038
305

305

0.031 30
5.7

= .
305 8
0.48

305

0.038 30
5.7

=
305 8
0.48

. .

. .

. .

= .

= .

. .
.

. .
.

34

For Feeder Cables from MCC01 to Individual Motors


For 1st motor in MCC01 with specs:
500HP, 422.22KVA, Xd=3%, X/R=11

Fig. 4.3.2: X/R range for


three-phase induction motors
(From IIEE Standard 141, p.184)
For Motors:
"

. .

"

100
. .

. .

. .

"

=
. .

=
. .

= .

3
5.7

= .
100 0.422

0.405
= .
11
+

. .

. .
= .

35

Table 4.3.1: List of Impedance Values


= .
= .

+
+

.
.
Cable

Motors
MCC01

MAIN
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8

0.0094 +
0.8213 +
0.0314 +
0.2555 +
0.1278 +
0.0694 +
0.1431 +
0.2433 +
1.6547 +

0.0146
0.0876
0.0487
0.2028
0.1363
0.0740
0.1136
0.1241
0.1947

MAIN
2-1
2-2
2-3
2-4
2-5
2-6

0.0126 +
0.0858 +
0.0456 +
0.1460 +
0.1789 +
0.1533 +
1.6547 +

0.0195
0.0915
0.0487
0.1034
0.1419
0.1217
0.1947

MAIN
3-1
3-2
3-3
3-4
3-5
3-6
3-7
3-8

0.0094 + 0.0146
0.0858 + 0.0915
0.0602 + 0.0537
0.0767 + 0.0608
0.2300 + 0.1825
0.0803 + 0.0857
0.2044 + 0.1622
0.0679+j0.1051
1.6547 + 0.1947

0.4052 +
0.5700 +
0.3277 +
1.6209 +
0.4835 +
0.3277 +
0.4672 +
1.2955 +

0.0436
0.0570
0.0712
0.3242
0.0504
0.0712
0.1552
1.2955

0.4052 +
0.4052 +
1.3806 +
0.7509 +
0.7509 +
1.2955 +

0.0436
0.0436
0.1972
0.1632
0.1632
1.2955

0.4052 +
1.2063 +
0.1712 +
0.7509 +
0.4052 +
0.7509 +
0.1648 +
1.2955 +

0.0436
0.1257
0.0180
0.1632
0.0436
0.1632
0.0253
1.2955

MCC02

MCC03

C. Combine Impedances
The third step is to combine reactances or vector
impedances, and resistances where applicable, to the point of fault
into a single equivalent impedance, reactance, or resistance. The
equivalent impedance of separate impedances in series is the sum
of the separate impedances. The equivalent impedance of separate
impedances in parallel is the reciprocal of the sum of
the reciprocals of the separate impedances.
Impedances will be combined depending on the layout of the
impedance on the location of the fault.

36

D. Calculate Short-Circuit Current


Low-voltage duties. The standards for interrupting
equipment allows a modified sub-transient reactance for a group of
low-voltage induction and synchronous motors fed from a low
voltage substation. If the total of motor horsepower ratings at 480
or 600 V is approximately equal to (or less than) the transformer
self-cooled rating in kilovolt-amperes, a reactance of 0.25 per unit
based on the transformer self-cooled rating may be used as a single
impedance to represent the group of motors.
Once the first-cycle network has been established and its
impedances are converted and reduced to a single equivalent
per-unit impedance ZPU (or reactance XPU) for each fault point
of interest, the symmetrical short-circuit current duty is calculated
by dividing the per-unit pre-fault operating voltage EPU by ZPU (or XPU)
and multiplying by base current:
=

ZT
ZMC
ZMCC01
ZMCC02
ZMCC03

Table 4.3.2: System Impedances at Fault Point 1


Z
1/Z
Z
Rectangular
Polar
0.0054 + 0.0713
0.071585.67
13.99 85.67
1.0560
0.0086 + 0.0105
0.013650.68
73.52 50.68
46.59
0.1065 + 0.0415
0.114321.29
87.72 21.29
8.15
0.1352 + 0.0363
0.139915.03
7.15 15.03
6.90
0.0649 + 0.0234
0.069019.83
14.49 19.83
13.64

(1.0560

=
+
+(

13.95) + (46.59
56.88) + (2.9414
= .
=

5700
=
92.67 1.732 0.48

)=

0.9710 ) = .
.

13.95
56.88
3.18
1.85
4.92

37

Table 4.3.3: Short Circuit Current for Each Fault Point


Fault
ZTH
ISCsym
Point
Rectangular
Polar
58.5874
71.80
92.67 50.79
FP1
74kA
2.0431
11.96
12.12 80.30 565.70kA
FP2
43.1676
52.04
67.61 50.32 101.41kA
FP3
51.3988
71.76
88.27 54.39
FP4
77.67kA
24.3762
36.18
43.63 56.03 157.15kA
FP5
50.3274
71.61
87.53 54.90
FP6
78.33kA
43.1676
52.04
67.61 50.32 101.41kA
FP7
50.5689
71.73
87.76 54.82
FP8
78.13kA

Fault
Point
No.

Table 4.3.4: Short Circuit Value and Assessment


Existing
Calculated
Fault
Equivalent Per
MCB
3 Phase
Location
Unit Impedance
KAIC
Fault (kA)
Rating

Remarks

Source

58.5874

71.80

74kA

80

Adequate

Xformer/MDP

2.0431

11.96

565.70kA

600

Adequate

MCC01 Main

43.1676

52.04

101.41kA

120

Adequate

MCC01
Motor1-1

51.3988

71.76

77.67kA

80

Adequate

MCC02 Main

24.3762

36.18

157.15kA

175

Adequate

MCC02
Motor2-1

50.3274

71.61

78.33kA

80

Adequate

MCC03 Main

43.1676

52.04

101.41kA

120

Adequate

MCC03
Motor3-1

50.5689

71.73

78.13kA

80

Adequate

38

New Era University


College of Engineering and Technology
Department of Electrical Engineering

EE 581D
Industrial Power Systems Design

Part 1, Chapter 5:
Arc Flash Design

Submitted by:
Arvin Joseph K. Torrente
BS EE 5

Submitted to:
Engr. Timoteo Limsiaco P.E.E.

Professor

39

5.1 Determination of Maximum Arcing Current


In order to demonstrate the worst-case arc-flash scenario across a
given range of arcing fault currents, constant-energy lines can be plotted
on the TCC plot in conjunction with tripping characteristics of various
devices.
For voltage levels less than 15kV, the IEEE 1584 2002 presents
the equation for incident energy as shown in Equation (1). The values
for the variables shown in this equation are presented in Table 5.1.1. In
equation (1), the units of energy are Joules/cm2. Equation (2) shows
Equation (1) algebraically rearranged in order to calculate values for time
with respect to a given set of parameters. The conversion factor between
Joules and calories has also been included so that the units of Energy (E)
in Equation (2) are cal/cm2.
Equation 1:
= (4.184)

10[

( )

0.20

610

Where:
E
Cf
K1
K2
Ia
G
t
x
D

=
=
=
=
=
=
=

energy in
calculation factor (1 for 1kV above and 1.5 for below 1kV)
-0.792 for open configurations (no enclosure) or
-0.555 for close configurations (enclosed)
0 for ungrounded and HRG systems and
-0.133 for grounded systems
magnitude of the arcing fault current (kA) that may be
determined according to IEEE 1584TM 2002, equation (1)
= gap between conductors (mm)
= duration of arc (seconds)
= distance component
= distance from the arc to the worker

40

Equation 2:
0.20 4.1667

=
4.184

10[

( )

610

Where:
t
=
E
=
Cf
=
K1
=
=
Ia
=
G
t
x
D

duration of the arc (seconds)


energy in
calculation factor
-0.792 for open configurations (no enclosure) and
-0.555 for close configurations (enclosed)
magnitude of the arcing fault current (kA) that may be
determined according to IEEE 1584TM 2002, equation (1)
= gap between conductors (mm)
= duration of arc (seconds)
= distance component
= distance from the arc to the worker

Equation (3) shows the linear relationship between time and arcing
current with respect to a given energy and specific system parameters
shown in Table 1. With the aid of curve-fitting software, this relationship
was found consistent for all system configurations considered.
= ( )
Where:
t
= time in seconds
k
= unique constant based on specific system parameters
(see table 5.1.1 for a summary)
Ia
= magnitude of arcing fault current
B
= a constant value of -1.081
Computing for maximum 3 phase short circuit current available
log ( ) =

+ 0.662 log
0.00304

Where:
Ia
=
K
=
Ibf
=
V
=
G
=
=

+ 0.0966
log

+ 0.000526

+ 0.5588

log

arcing current (kA)


-0.097 for box configurations
symmetrical RMS current for 3 phase Faults (kA)
system voltage (kV)
gap between conductors
25mm/1in.
41

Table 5.1.1
Grounded
Enclosure
or
Configuration
Ungrounded
(K1)
(K2)
-0.113
10
0
Open Air*
2.000
455
-0.792
-0.113
40
0
-0.113
0.208 - 1
1.5
Switchgear
32
1.473
610
0
-0.555
-0.113
MCC and
25
1.641
Panels
0
455
-0.113
Cable
13
2.000
-0.792
0
-0.113
Open Air
102
2.000
455
-0.792
0
-0.113
13
0
>1-5
1.0
Switchgear*
0.973
910
-0.555
-0.113
102
0
-0.113
Cable
13
2.000
455
-0.792
0
-0.113
13
0
Open Air*
2.000
455
-0.792
-0.113
153
0
> 5 - 15
1.0
-0.113
Switchgear
153
0.973
910
-0.555
0
-0.113
Cable
13
2.000
455
-0.792
0
*Minimum and maximum values are shown for a range of typical bus gaps (G)
System Parameter values are based on IEEE Standard 1584TM 2002, Tables 2,3, and 4
System
Voltage
(kV)

Calculation
Factor (CT)

Equipment
Type

Gap (G)
(mm)

Distance
factor (x)

Working
Distance
(D) (mm)

Unique
Constant
(k)
0.6945
0.5354
0.6437
0.4962
0.6841
0.5274
0.4304
0.3318
0.6893
0.5314
0.8252
0.6362
1.5890
1.2250
1.2683
0.9778
1.0339
0.7970
1.0339
0.7970
0.7252
0.5591
1.1146
0.8593
1.0339
0.7970

42

Computing for Maximum 3 Phase Short Circuit Current @FP2


= 0.4304 (565.70)
= .
log

0.097 + (0.662 log 565.70) + 0.0966 0.48 + 0.000526 25 + 0.5588


0.48 (log 565.70) 0.00304 25 log 565.70
= .
=
.

log

0.097 + (1.2531) + 0.0966 0.48 + 0.000526 25 + 0.5588 0.48


(1.8928) 0.00304 25 (1.8928)

Table 5.1.2: Summary of Arcing Current in Different Fault Points


Arcing
Fault
Current (Ia)
Point
(kA)
1
31.65
2
204.17
3
47.45
4
36.32
5
69.12
6
36.51
7
47.45
8
11.62

5.2: Determination of Arc Flash Protection (PPE)


Fire resistant clothing is necessary due to the following reasons:
Most severe burn energies and fatalities are caused by non-flame
resistant clothing igniting and continuing to burn.
Flame resistant clothing will self-extinguish, thus limiting the injury.
Body area under non-FR clothing is often burned more severely than
exposed skin.
National Fire Protection Association uses a three-step process to identify what
type of PPE needs to be worn at certain conditions.

43

Step 1: Determine the Hazard/Risk Category Classification based in NFPA 70E,


Table 130.7(C)(9)(a)

TASK

CB OR FUSE
SWITCH
OPERATION
WITH COVERS
ON
CB OR FUSE
SWITCH
OPERATION
WITH COVERS
OFF
WORK ON
ENERGIZED
PARTS,
INCLUDING
VOLTAGE
TESTING

Table 5.2.1: NFPA 70E, Table 130.7(C)(9)(a)


HAZARD/RISK
V-RATED
V-RATED TOOLS
CATEGORY
GLOVES
PANEL BOARDS AND SWITCHBOARDS
BETWEEN 240V AND 600V

No

No

No

No

Yes

Yes

Step 2: Select Protective Clothing and PPE based on NFPA 70E,


Table 130.7(C)(10).
Table 5.2.2: NFPA 70E, Table 130.7(C)(10)
Personal Protective Clothing
Hazard/Risk Category Number
FR Clothing:
-1 0
1
2
3
4
Long-Sleeved Shirt
X
X
X
X
Pants
X
X
X
X
Coverall
(note5) (note 7)
X
(note 5)
Jacket, Parka, Rainwear
AN
AN
AN
AN
Hard Hat
X
X
X
X
Safety Classes
X X
X
Flash Suit Hood
X
X
Hearing Protection
X
X
X

44

Step 3: Identify ATPV and System based on HRC from Table 130.7(C)(11)

Hazard/Risk
0
1
2

Table 5.2.3: NFPA 70E, Table 130.7(C)(11)


Typical Protective Clothing Systems
Category
Clothing Description
Minimum ATPV
Non-Melting Flammable
N/A
Materials (1)
Fire Retardant Shirt and
4
Pants or Coverall (1)
Cotton Underwear PLUS
Fire Retardant Shirt and
8
Pants or Overall (1-2)
Cotton Underwear PLUS
Fire Retardant Shirt and
25
Pants or Overall (2-3)
Cotton Underwear PLUS
Fire Retardant Shirt and
Pants PLUS Double Layer
40
Switching Coat and
Plants (3 or more)

Arc Thermal Protection Value (ATPV) is defined by ASTM 1959-00 as:


the incident energy on a fabric or material that results in sufficient heat
transfer through the fabric or material to cause the onset of a second degree
burn based on the Stoll Curve
Typical Protective Clothing:

45

46

Safety Gloves

Employees shall wear rubber insulating gloves where there is a danger of


arm and hand injury from electrical shock and burns due to contact with live
parts. Gloves used shall be of the appropriate voltage class.

Glove Selection

Glove size is important to ensure a proper fit and dexterity. Size is inches
around the palm of your hand.
Leather Protectors:
- Required for penetration protection
- If gloves used without, then must be re-tested prior to next use.

47

Table 5.2.4: NFPA 70E Approach Boundaries


Alternating Current (AC) and Direct Current (DC)
Shock Protection Boundaries
Voltage Range
Limited
Restricted
Movable
AC
DC
Fixed
Not
0 - 50 VAC
0 100 VDC
Not Specified
Specified
Avoid
51 - 300 VAC
101 300VDC
10 0
3 6
Contact
301 750 VAC 301 1000VDC
10 0
3 6
12

Prohibited
Not
Specified
Avoid
Contact
1

48

New Era University


College of Engineering and Technology
Department of Electrical Engineering

EE 581D
Industrial Power Systems Design

Part 1, Chapter 6:
Power Factor Correction

Submitted by:
Arvin Joseph K. Torrente
BS EE 5

Submitted to:
Engr. Timoteo Limsiaco P.E.E.

Professor

49

6.1: Power Factor Correction


Power factor is the ratio of working power to apparent power.
It measures how effectively electrical power is being used. A high
power factor signals efficient utilization of electrical power, while
a low power factor indicates poor utilization of electrical power.
To determine power factor (PF), divide working power (kW) by
apparent power (kVA) In a linear or sinusoidal system, the result
is also referred to as the cosine .
=

= cos

Low power factor means youre not fully utilizing the electrical
power youre paying for. As the triangle relationships in Figure 6.1.1
demonstrate, kVA decreases as power factor increases. At 70% power
factor, it requires 142 kVA to produce 100 kW. At 95% power factor, it
requires only 105 kVA to produce 100 kW Another way to look at it is
that at 70% power factor, it takes 35% more current to do the same work.

Fig. 6.1.1: Example of Power Factor Correction

50

Table 6.1.1: (IEEE Std 141-1993 Table 8)


Typical Unimproved Power Factor Values

By Industry
Auto parts
Brewery
Cement
Chemical
Coal Mine
Clothing

Percent
Power
Factor
75 80
76 80
80 85
65 75
65 80
35 60

Electroplating
Foundry
Forge
Hospital
Machine Manufacturing
Metalworking
Office Building
Oil-field pumping
Paint manufacturing
Plastic
Stamping
Steelworks
Textile
Tool, die, jig

65
75
70
75
60
65
80
40
55
75
60
65
65
60

70
80
80
80
65
70
90
60
65
80
70
80
75
65

By Operation
Air Compressor:
External Motors
Hermetic Motors
Metal Working:
Arc Welding
Arc Welding with
standard capacitors
Resistance Welding
Machining
Melting:
Arc furnace
Inductance furnace 60Hz
Stamping:
Standard speed
High Speed
Spraying
Weaving:
Individual drive
Multiple drive
Brine

Percent
Power
Factor
75 80
50 - 80
35 60
70 80
40 60
40 - 65
75 90
100
60 70
45 60
60 65
60
70
70 75

6.1.1: Determination of Capacitance


Data:
5700KVA Demand, 480V, three-phase, @0.60 PF, 18-hour Plant Operation
Improve to 0.95 PF
(Plant Power factor is based on Table 6.1.1)
=

= 5700 0.60 =
= cos (
)
= cos(
)

= tan
0.60 = cos(
(
0.95 =
53.13 = tan

3420

)=
)=

=
=
=

.
.
.

51

Determining the size of capacitor:


(tan(
) tan(
))
=
= (3420)(tan(53.13) tan(18.19))
=
.
=

30
3436.21
=
=
30 18

18
= .

, .

From Meralco, the cost per kVA for Generators (Wheeling) with
primary voltage of 34.5kV and below is Php 184.37.
Connection of Capacitor Bank
In a three-phase system, to supply the same reactive power, the
star connection requires a capacitor with a capacitance three times higher
than the delta connected capacitor. In addition, the capacitor with the
star connection results to be subjected to a voltage 3 lower and flows
through by a current 3 higher than a capacitor inserted and delta
connected.
6.1.2: kVA Billing, and Savings Forecast
= 5700
=

Uncorrected Original Billing:


5700

184.37 =

3436.21
=
0.95

Corrected new Billing:


3617.06

184.37 =
Annual Savings:
1,050,909.00

666,877.35 = 384,031.65 12
=

52

6.2: Protective Equipment


Line Current:
=

7500

4803

= .

6.2.1: Wire Size


From Article 460.8(A) in NFPA70 (NEC2014):
The ampacity of capacitor circuit conductors
shall not be less than 135 percent of the
rated current of the capacitor.
= 135%

= 135% 9 =
.

6.2.2: Fuse and Circuit Breakers


From Articles 460.8(B), 460.8(C), and 460.8(C)(3) in NFPA70 (NEC 2014):
An overcurrent device shall be provided in each
ungrounded conductor for each capacitor bank.
The rating or setting of the overcurrent device
shall be as low as practicable.
Exception: A separate overcurrent device shall not be required
for a capacitor connected on the load side of a
motor overload protective device.
A disconnecting means shall
be provided in each ungrounded conductor for each capacitor bank
(3) The rating of the disconnecting means shall not be less
than 135 percent of the rated current of the capacitor.
= 135%

= 135% 9 =

53

CAPACITOR
BANK
G
MDP

UTILITY

MCC01

HAYDAR ALIEV REFINERY PLANT

MCC02

MCC03

E-17

Vous aimerez peut-être aussi