UNlVERSITI MALAYSIA PERLIS


Peperiksaan Semester Kedua
Sidang Akademik 201112012
4 Jun2012

EAT 35413 - Steel Building Design


(Rekabentuk Binaan Keluli)
Masa : 3 jam

Please make sure that this question paper has TWELVE (12) printed pages including this
front page before you start the examination.
(Sila pastikan kerlas .oaJan In; mengandungi DUA BEUS (12) muka surat yang bercelak termasuk muka
hadapan .ebelum anda memulakan peperiksaan inf.)

This question paper has TWO (2) sections, SECTION A and SECTION B. Answer ALL
questions from SECTION A and any ONE (1) question from SECITON B.
(Kerlas .oaJan Ini mengandungi DUA (2) bahagian, BAHAGL4N A dan BAHAGL4N B. Jawab SEMUA
soalan daripada BAHA.GL4N A dan mana-mana SATU (1) soa/an dari Bahogian B.)

SULIT

SULIT

-2-

EAT 354

SECTION A: This section has 4 questions. Please answer ALL questions.


BAHAGIAN A.: Bahagian inl menganthmgi 4 soalan. Silajawab SEMUA soalan.

Question 1
(Soa/anI)

a) A flat bar, 300 mm wide and 25 mm thick, is to be used as a tie. Erection conditions
require that the bar be constructed from two lengths connected together with a lap
splice using nine M20 bolts, as shown in Figure I. Calculate the tensile strength of
the bar, assuming grade 8275 steel.
[Satu bar rata, 300 mm lebar dan 25 mm tebal, untuk digunalcan sebagal pengikat. Keadaan
pembinaan memerlukan bar diblna dari dua panjang yang disambungkan bersama tiengan sambat
pusingan menggunalcan sembi/an M20 bolt, seperti yang ditunjulrkan dalam Rajah 1. Kirakan
kekuatan tegangan bar, dengan mengandailcan gred S275 keluli.}

(5 Marks! Markah)

b) If the middle row of the holes is relocate 75 mm in X-direction, calculate the tensile
strength of the bar.
{Jika barisan tengah lubang disusun semula 75 mm dalam arah-X, lcirakan lrekuatan tegangan bar.}

(5 Marks! Markah)

c) Compare your answer in QI(a) and Ql(b). Propose your opinion and state any
assumption you make.
[Bandingkan jawapan anda dalam Q1 (a) dan QI (b). Berikan pendapat anda dan nyatakan sebarang
andaian yang dlbuat.}

(3 Marks! Markah)

d) If the applied tensile load, T is 25% higher than the tensile strength of the bar in
Q 1(b), determine the minimum thickness of the bar.
[fUca beban tegangan yang digunakan, T ialah 25% lebih tinggi daripada kekuatan tegangan bar pada
Q1 (b), tentukan kefebalan minimum bar.}

(4 Marks! Markah)

..3/-

SULIT

SULIT

-3 -

EAT 354

e) Other than increase or decrease the thickness of the bar in Q 1 (d). as a design
engineer what would you do? Give two suggestions and state any assumptionS made.
Sketch a diagram if necessary.
[Selaln daripada menambah aJau mengurangkon kefebalan bar pada Ql (d), sebagai seorangjurulera
rekabentuk apakah yang akon ancla lak:ulcan? Berlkan penclapaJ anda dan nyatakon sebarang andaion
yang dibuat. Lakorkan rajah jiko perlu.]

(3 Marks! Markah)

Lx
T
~

-G- -G-a-e- -a- -a-e- -G- -a0


0

0
0

0
0

]OOmm

0
0

0
0

]00 nun

,.

50mm

SOmm

,I ,I
]50mm ]50mm

Figure!
[Rajah 1]

....4/..

SULIT

-4-

SULIT

EAT3S4

Question 2
(Soalan2)

(a) The part of the floor plan for the internal panel of an office building is shown in
Figure 2. The floor is precast concrete slabs 125 mm thick supported on steel beams.
Assuming that self-weight of main beam may be taken as 1.0 kN/m. The following
loading data may be used:
[&bahag/an pelan lantai unhIk panel dalaman bangunan peJabat dilUnjulckan di Rajah 2. Lantal iIU
adalah papak pra-lUang berketebalon 125 mm disokang pada rasuJc keluJi. Anggap herat sendiri
rasuJc utama sebanyak 1.0 /rN/m. Data behan yang berllwt holeh digunakan.J

125 mm concrete slab

= 3.0 kN/m

[PapaHonkrlt 125 mm]

Finishes

1.0 kN/m2

[Kemasan]
2

= 1.0kN/m

Partition
[Pembahaglan]

Imposed load

=3.0kN/m

[Beban hldup]

If the beam of 457 x 191 x 67 UB of grade S 275 is used in beam B/I-2, check for
the following design capacity; state your assumption [s] if any:
[Jlka rasuk 457 it 191 it 67 UB darl gred S 275 dlgunakan untuk Tasuk BlI-2, periksa kopasiti
rekobentuk berikut; nyatakan ondaion-andaian jika ada:]

(i)

Section classification
[Klaslfikasi seksyen]

(3 Marks! Markah)
(ii)

Maximum bending moment and shear force


[Maksimum moment lentur dan daya ricih]

(3 Marks! Markah)
(iii)

Moment capacity
[Kapasitl momen]

(6 Marks! Markah)
(iv)

Shear capacity
[Kapasili rlclh dan lengkungon]

(6 Marks! Markah)
..5/-

SULIT

-5-

SULIT

EAT 354

(b) As a design engineer of steel structure, if the design capacity at (a) (iii) and (a)(iv) did
not meet the requirement as stated in Eurocode 3: Design of Steel Structures Part I1, gives your comment to solve the problem.
[Sebagai jurutera rekabentuk strulclur hlllIli. jika kopasiti relcabentuJc pada (a)(iii) dan (a)(iv) lidak
memenuhi hlper/uan seperti dinya/akan da/am Eurocode 3: Design of Stee/ Structures Part 1-1,
berikan pendapat anda un/uk menyelesaikan masa/ah i/u]

(2 Marks! Markah)

,
,,
--,-----,,

,,
,,
,

, "'\\--------------\,

________________ J __

r::\
: -r-r-r:
~i~---~-r_-------;-------;-----~-lr_-------~------;-----~-~r_----~~
,,,
,
.. ! ...

--"

6000

f.\
--~
-r~ '~:---~
__-------;-------;--------_lr_-------;-------i-----~-~r_----~x-,,
--,---------------2000

__ .. _____ .1

,,
---------------~--.
,,

, ... \ ___ .... __

"

2000

2000

2000

2000

2000

All Dimension in mm
(Semua dimensi da/am mm)

Figure 2
{Rajah 2J

....6/-

SULIT

SULIT

-6-

EAT 354

Question 3
(Soallln3)

(a) It is proposed to use 686 x 254 x 140UB of grade S275 for a beam spanning 12.0 m
and supporting three secondary beams as shown in Figure 3a. The lateral and
torsional restraint to the compression flange is provided at both end supports and at
positions of secondary beams. The compression flange is unrestrained between
supports and secondary beams.
[Adalah dicadangkan untuk menggunakan 686 " 254 " 140UB gred S275 untuk rasuk yang
panjangnya 12.0 m dan menyakong tiga rasuk kedua sepert; ditunjukkon dalam Rajah 30. Halangan
slsi dan kilasan pada bebibir mampatan rasuk dikenakon pada kedua-dua hujung sokongan dan pada
kedudukan rasuJc..rasuk kedua. Bebibir mamapatan tidak dihalang diamara kedua-dua sokongan dan
rasuJ;,.rasuk kedua]

Design data:
[Data rekabentuk:]

= 3.0kN/m

Characteristic distributed dead load


[Cirt beban mati teragih]

=2.0kN/m

Characteristic distributed imposed load


[Ciri beban htdup teragih]

Characteristic dead load reaction from each secondary beam

= 10kN

[Ciri daya beban mati dari setiap rasuk kedua]

Characteristic imposed load reaction from each secondary beam

= 20 kN

[Ciri daya beban mati dart setiap rasuk kedua]

Young's Modulus,E

= 210kN/mm2

[Modulus Young's, E]

Shear Modulus,G

=81 kN/mm2

[Modulus Ricih, G]

Using the design data given;


[Dengan menggunakon data rekabentuk yang diberi;]

(i)

Draw the shear force and bending moment diagram


[Lukiskan gambarajah daya ricih dan momen lentur]

(3 Marks! Markah)
(ii)

Determine the elastic moment resistance (M.r)


fTentukan momen rintangan /JIifal (M,,)j

(5 Marks! Markah)

....7/-

SULIT

-7-

SULIT

EAT 354

(iii) Check for the buckling moment resistance (Mpb)


[Periksa momen rintangan lengknkan (M,w]

(6 Marks! Markah)
(b) The joint in Figure 3b is subjected to tensile load. The thickness of the plate is 20
mm and the diameter of the bolt holes is 22 mm. All data required for the design are
show in the figure. Check for the minimum and maximum spacing, end and edge
distance.
{Sambungan pada Rajah 3b dikenakan daya tegangan. Ketebalan plat adalah 20 mm dan diameter
lubang bolt adalah 22 mm. Semua data yang diperlukan untuk rekabentuk ditunJukkan didalam rajah.
Semak minimum dan maksimum untuk jara1c, hujung dan Jarak tepi]

(6 Marks/6 Markah)
Secondary beam

1~~t----I~*1~_-----~~1~4-----.-j~1 ~

2000

4000

4000

2000

Figure3a

All Dimension in mm

(Rajah3a)

(Semua dimensi dalam mm)

II

II

II

0
0

0
0
~14

I50

I
I
I
I
I
I
I
I

0
0

~14
80

~I~

80

....

1
0

a..

1 ....
0

~
50

Figure3b

All Dimension in mm

[Rajah3bj

[Semua dimensi dalam mm]

....8/-

SULIT

SULIT

EAT 354

-8-

Question 4
(Soalan4)

A universal column section member (UKC) is to be used as an internal column in a


single-storey building. The column has pinned boundary conditions at each end, and the
storey height is 4 m, as shown in Figure 4. The critical combination of actions results in a
design axial force of 2500 kN. Assess the suitability of 305 x 305 x 158 UKC in grade
8275 steel for this application and check the following design;
(Ketatan rentas tiang (UKC) yang digunakan sebagai salu anggata bahagian ruang dalaman dolam
bangunan bertingkat lIuang yang telah disematkan keadaan .empadan di setiap hujung, dan kstinggian
antara tingkat 4 m. seperti yang ditunju1dcan dalam R/ljah 4. Gabungan Irritikal tindakan hasil dolam reka
bentuk daya paksi 2500 kN. Nilatkan kesesuaian 305 x 305 x 158 UKC dalam gred ksluli 8275 untuk
aplikasi ini dan semak rekabentuk berikut:]

a) Compression resistance if the beam placed on top of the column.


{Rintangan mampatan Jtka ras"k dtleta1dcan di atas tiang.]

(4 Marks! Markah)
b) Buckling resistance in compression if the beam placed on top of the column.
{Rintangan lengko1dcan dalam mampatan jika rasuk di/eta1dcan di atas tiang.]

(6 Marks! Markah)
c) If the axial load, Ned acting 100 mm from column web face, check the
buckling resistance.
{Jzka beban paksi. Nodbertindok 100 mm dari muka web tiang, semak rintangan lengkokan.]

(7 Marks! Markah)
d) Compare your answer in Q4(b) and Q4(c), justify your answer and state any
assumption you made.
(Bandingkan Jawapan anda di Q4(b) dan Q4(c), Justifikasi Jawapan ando dan nyatakan
sebarang andaian yang ando buat.]

(3 Marks! Markah)

Figure 4
{Rajah 4]

....9/SULIT

-9-

SULIT

EAT 354

SECTION B : 'This section has 2 questions. Please answer any ONE of the questions.
BAHAGlAN B: Bahagian inl mengandung/2 .oalan. SiJajawab mana - mana SATU (1) soaIan.

Question 5
[Soalan 5/

a) Select the suitable universal column section (UKC) and design the column shown in
Figure 5 using S275 steel between levels 1 and 2. The following assumptions may be
made:
[Pllih keralan remas liang (UKC) yang sesual dan rekabentuk liang di antora oras I dan 2 yang
elitunjukkan dalam Rajah 6 bagi kelull S275. Andalan-andalan berikut boleh dibuat.]

The column is continuous and fOnDS part of a structure of simple construction.


[nang adalah seJanjor dan membentuk sebahagian darlpadastruktur pembinaan yang mudak}

The column is nominally pinned at the base.


(/'iong secara nominal disemalkan eli pangkal.)

Beams are connected to the column flange by flexible end plates.


[Roauk disambungkan kepoda bebibir lajur oleh plat-akhlr f1eaibel.}

The reactions from the beam are given:


(Diberi tindakbalas dori ramk:)

Reaction from beam 1, Fl,d = 35 kN


(/'indak balas dari ram" I, F'.d = 35 k.N]

Reaction from beam 2, Flod = 200 kN


(/'indak balas dari ramk 2, F~d = 200 k.N]

Reaction from beam 3, F3,d = 35 kN


(/'indak balas dari rasuk 3, FM

35k.N]

(17 MarksJ17 Markah)


b) As an engineer justify the requirement to design for the column between levels 2 and
3. Give your opinion and state any assumptions made.
[Sebagoi seorang jurutera perlutah anda merekabentuk bag/ tiang antara aras 2 dan 3. Berikan
pendapat ando dan nyalakan sebarang undaion yang d/bual.]

(3 MarksJ3 Markah)

....10/-

SULIT

- 10 -

SULIT

EAT3S4

_. :;1; ~-.----.-.---.-.--.-+.-

3750mm

...

._--+._.
I

H P"

45DDmm

Ii

"Zd

F"-"""""'="-"=' ~
Fl.d

FigureS
[RajahS]

....11/-

SULIT

-11-

SULIT

EAT 354

Question 6
ISoalan6/

a) Figure 6a and 6b shows side and front elevations of the connection between column
and beam of the steel building structure. The joint is subjected to tensile load P,
which is 70 kN for dead load and 55 kN for imposed load. The joint dimensions and
loads are shown in the figure. With grade 4.6 and 20 rom diameter bolt used for the
connection, the following data may be used;
[Rajah 60 and 6b menunjukkan pondangan tepi dan hadapan penyambungan di antara tiang dan
rasuk struktur bangunan kelull. Sambungan ini dikenakan dayo tegangan P, iaitu 70 kN untuk beban
mati dan 55 kN untuk beban hidup. Dimensi penyambungan don daya ditunjukkan didalam rajah.
Dengan menggunakan gred 4.6 dan 20 mm diameter bolt untuk sambungan, data yang berikut boleh
digunokan:}

Bolt tension capacity, PI = 47.7 kN


[Keupayaan tegangan bolt, PJ

Bolt shear capacity,P,


{Keupoyaan riaih bolt, PJ

Design strength, Py

=39.2 kN
= 265

N/rom2

[Kekuatan rekobentuk, pJ

(i)

Determine the depth of neutral axis


[Tentukan kedalaman paksi neutral]

(ii)

Calculate for the moment resistance


[Kira untuk penentangan moment]

(iii) Check whether the 20 rom diameter bolt is satisfactory for the combine
shear and tension.
[Perlksa jika bait berd/ameter 20 mm adalah memuaskan untuk gabungan ricth dan
tegangan]

(15Marksl15 Markah)
(b)

The connection between plate and beam is using the fillet weld method. Throat
thickness of the weld is 6 rom and steel grade S 275 are used for the connection.
Thickness of the plate is 15 rom. Determine the design resistance of the weld per
unit length. Assume all the missing data (if any).
[Penyombungan diantora plet dan rasuk menggunakan ldmpalan lambi. Ketebalan tekak
ldmpalan adalah 6 mm dan keluf/ gred S 275 digunokan untuk sambungan inL Ketebalan plet
adalah 15 mm. Tentukan penentangan rekabentuk sambungan untuk satu unit panjang. Buat
andoian untuk data yang tidale lengkap Gika ado))

(5 Marks/5 Markah)

....121-

SULIT

SULIT

EAT 354

- 12 p

200

15 mm thick plate
20 mm thick plate

All Dimension in mm
Figure6a

[Semua dlmensl da/am mm]

[Rajah6a]

Figure6b
[Rajah 6b]

All Dimension in mm
[Semua dimensl da/am mm]

~ooOOOOOOOOOOOOOOOODOOOO-