Vous êtes sur la page 1sur 4

TECHNICAL SPECIFICATION

ELECTRICAL AND INSTRUMENTATION


REQUIREMENTS FOR SIMPLE PACKAGED
EQUIPMENT
DATE: 03 APR 2003

ENGINEERING SERVICES BY KBR TECHNICAL SERVICES, INC.

IS110E BASE
PAGE 1 OF 4

TABLE OF CONTENTS
Section
1.
1.1
1.2
1.3
1.4
2.
3.
4.

Title
Page No.
GENERAL ......................................................................................................................................1
Scope..............................................................................................................................................1
Codes and Industry Standards .......................................................................................................1
Government Regulations ................................................................................................................1
General Requirements....................................................................................................................1
INSTRUMENT SPECIFICATIONS .................................................................................................2
ELECTRICAL REQUIREMENTS ...................................................................................................3
ADDITIONAL REQUIREMENTS....................................................................................................4

1. GENERAL
1.1 Scope
This specification defines minimum technical requirements for instrumentation and controls incorporated on
simple general purpose skid package units.
1.2 Codes and Industry Standards
Applicable requirements in the latest edition, revision, or addendum of the following codes, standards, and
references shall be considered an integral part of this Specification. Requirements modified by this
Specification, Purchasers referenced drawings, or a purchase order shall take precedence over published
specifications.
FLUID CONTROLS INSTITUTE (FCI)
FCI 70-2, "Control Valve Seat Leakage"
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70, "National Electrical Code" (NEC)
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ICS 6, "Industrial Control and Systems Enclosures"
UNDERWRITERS LABORATORIES (UL)
UL 98,
"Safety Enclosed and Dead-Front Switches"
UL 198E, "Safety Class R Fuses"
1.3 Government Regulations
Federal Standards and Instructions of the Occupational Safety and Health Administration (OSHA), including any
requirements by state or local agencies that have jurisdiction where the equipment will be installed, shall apply.
1.4 General Requirements
1.4.1 Neither mercury nor asbestos shall be permitted.
1.4.2 Instruments and electrical components and materials shall be listed by a recognized national testing
laboratory.
1.4.3 All pre-wired assemblies shall be UL listed or approved by a testing organization acceptable to the
authority having jurisdiction.
1.4.4 Design, material, equipment, and installation shall meet the specified electrical area classification. If
purging is required to meet the area classification, then Purchaser acceptance is required.

TECHNICAL SPECIFICATION
ELECTRICAL AND INSTRUMENTATION
REQUIREMENTS FOR SIMPLE PACKAGED
EQUIPMENT
DATE: 03 APR 2003

ENGINEERING SERVICES BY KBR TECHNICAL SERVICES, INC.

IS110E BASE
PAGE 2 OF 4

2. INSTRUMENT SPECIFICATIONS
2.1 The entire instrumentation system shall be fully assembled and piped.
2.2 Instruments that are connected to the process shall have a 3/4 inch block and bleed valve.
2.3 Instruments shall be located and installed such that accuracy and reliability are not impaired by vibration,
pulsation, temperature, or contamination. Length of impulse lines connected to process pipelines or equipment
shall be minimized. Instruments must be accessible.
2.4 Process transmitters shall be used instead of process switches (e.g., level, flow, pressure temperature,
etc.). Use of switches requires purchaser approval. Nominal operations shall be between 30% and 70% of
scale range.
2.5 Instruments in steam, liquid, liquid-sealed, or condensing service shall be located below the process
connection, and impulse tubing/piping shall slope continuously down to instruments. Instruments in gas or
vapor service shall be located above their process connection point, and impulse tubing/piping shall slope
continuously up to instrument.
2.6 Instrument support shall be designed and installed in such a way to avoid strain on equipment, piping
connections, and instruments and shall allow for flexibility required for thermal expansion of equipment and
piping. Dips and/or sags where vapor/liquid can collect in piping and tubing runs shall be avoided.
2.7 Piping from level gauges and external displacer type level instruments shall be self-draining into a vessel or
standpipe. Displacer chambers shall have a maximum allowable working pressure (MAWP) equal to or greater
than that of the vessel. Level instrument chambers shall not have cast iron bodies. Tubular glass shall not be
used in process applications.
2.8 Magnetic level gauges are preferred for hazardous liquid applications. Flat glass reflex type shall be used
for all other applications. Pad type reflex welded-in gauge glass is acceptable for lube and hydraulic reservoir
applications.
2.9 Automated valves installed in lines smaller than 1 inch shall be line sized. Valves in line sizes 1 inch and
larger shall have a minimum valve body size of 1 inch but not less than half the pipe size. Body sizes shall not
be 1-1/4 inch, 2-1/2 inch, 3-1/2 inch, or 5 inch.
2.10 Automated valve bodies or regulators shall not be cast iron, ductile iron, brass, or bronze, except in water
or air services in non-hazardous classified areas.
2.11 Integral flanged type globe valves are preferred for modulating services. Rotary style valves may be
considered. Seat leakage shall comply with FCI 70-2 standards. Face-to-face dimensions shall comply with
ISA standards.
2.12 Ball or rotary valves shall be used for automated on-off service and shall be rated ANSI Class IV shutoff
minimum.
2.13 Valve actuators, including springs, shall be designed to fully stroke the valve against unbalanced forces,
which can result from a pressure drop across the valve equal to the maximum upstream pressure specified.
Control valves shall have electro-pneumatic positioners.
2.14 Packing for automated valves shall be Teflon or glass-filled PTFE for services up to 450F (232C )or shall
be graphite-based for services with operating temperatures above 450F (232C).

TECHNICAL SPECIFICATION
ELECTRICAL AND INSTRUMENTATION
REQUIREMENTS FOR SIMPLE PACKAGED
EQUIPMENT
DATE: 03 APR 2003

ENGINEERING SERVICES BY KBR TECHNICAL SERVICES, INC.

IS110E BASE
PAGE 3 OF 4

2.15 Sizing of control valves shall be based on ISA valve sizing equations or on sizing programs of approved
valve manufacturers. In general, valves shall be sized so that the normal flow rate is from 50% to 80% of
maximum opening of the valve.
2.16 Pneumatic instruments shall normally operate with 3 to 15 psig (21-103 kPa) input and output signals.
Each pneumatic instrument shall have an air supply complete with shutoff valve and air set (air filter/regulator
with output gauge).
2.17 Instrument transmitters shall be HART smart with 4-20 mA output.
2.18 Temperature elements shall be type K thermocouples or 3-wire 100 ohm Pt RTD, unless otherwise
specified.
2.19 Where multiple alarm conditions may exist, the Supplier shall provide a set of voltage free contacts for an
external common trouble alarm, rated for 120 V AC.
2.20 Temperature-sensing devices shall be mounted in thermowells where exposed to process streams.
Preferred installation of the thermowell shall be in a piping elbow pointed toward the flow.
2.21 Unless otherwise specified, purge systems shall be in accordance with NFPA 496 Type Z Classification.
3. ELECTRICAL REQUIREMENTS
3.1 Design, materials, equipment, and installation shall meet the specified electrical area classification.
3.2 The electrical items of the packaged equipment shall be mounted and wired by the supplier. Packaged
equipment wiring shall be brought out to identified terminal blocks in skid-mounted junction boxes or control
panel. Wiring shall be appropriately labeled to identify the device to which it is associated. Junction boxes shall
be located for easy access.
3.3 Wiring shall be separated by voltage level and application as follows: AC power and control; DC power and
control; Electronic signal wiring, intrinsically safe and non-intrinsically safe (e.g., separate conduit, separate
terminal strips). Design and use of AC power greater than 120 V AC for instrumentation shall require approval
of Purchaser. AC and DC power wiring shall be a minimum of 12 AWG copper THHN/THWN 600-volt rated.
Wiring shall be permanently labeled at both ends. If DC power distribution is provided within a local panel,
fused terminals shall be used for individual circuit protection unless the terminals are current limited.
3.4 Single conductor panel wiring used for AC and DC signals shall be 18 AWG minimum size, 7-strand copper
construction, Type ITC, and shall have 90C insulation suitable for DC circuits in wet or dry locations. Wiring
from junction boxes to individual instruments shall be shielded twisted pair or triad 16 AWG minimum in conduit.
3.5 Use of AC receptacles shall be minimized but where required shall be the 3-wire type: hot (black), neutral
(white), and ground (green), with the ground wire connected to ground per NEC.
3.6 Terminal strips in junction boxes and local panels shall have field external connections on one side and
internal panel connections on the other side.
3.7 Unless otherwise specified, the local panel shall be weatherproofed to NEMA 4X, with all stainless steel
construction, and suitable for operation in the environmental conditions specified.
3.8 Unless otherwise specified, the junction boxes shall be weatherproofed to NEMA 4X and suitable for
operation in the environmental conditions specified.

TECHNICAL SPECIFICATION
ELECTRICAL AND INSTRUMENTATION
REQUIREMENTS FOR SIMPLE PACKAGED
EQUIPMENT
DATE: 03 APR 2003

ENGINEERING SERVICES BY KBR TECHNICAL SERVICES, INC.

IS110E BASE
PAGE 4 OF 4

3.9 Supplier shall provide opening(s) and designated space for wire and tubing that will be installed after
package arrives at site. Field installation shall not require cutting holes in panel or installing hardware inside the
panel to secure Owner-installed wire and tubing. Conduit and cable entries shall be bottom or side. All panel
openings shall be plugged for shipment to prevent water or dirt from entering during shipment or storage prior to
installation.
3.10 Mechanical protection of wire and cables shall be provided by use of conduit or raceways.
3.11 Rigid conduit and piping shall not be routed over cases of rotating machinery (or other equipment), over or
in front of removable heads on vessels and exchangers, nor where such routings would impair the functionality
of inspection openings or panel doors. Drains shall be installed at low points, or a drip loop with a low-point
drain shall be used to prevent water from draining down conduit system into an instrument or enclosure.
3.12 Liquid-tight, flexible metallic conduit with accepted fittings shall be used in all areas at connections where
vibration, movement or adjustments are likely to occur; this type of conduit shall not be used in Class I, Division
1 hazardous (classified) locations.
3.13 Flexible metallic conduits shall be specified and installed to meet the NEC Article 348.
3.14 Conduit seals shall not be poured by Supplier. Supplier shall provide the seals for pouring by others at
site.
3.15 Purchaser will provide an electrical power supply of the voltage; phase and frequency specified. All
equipment and components on the package shall be designed and rated for operation at this voltage.
3.16 Two grounding pads of suitable ampacity shall be provided at diagonally opposite corners of each skid.
4. ADDITIONAL REQUIREMENTS
Instruments, equipment, and enclosures shall be identified before shipment by permanently affixing a name tag,
or affixing a stainless steel tag with stainless steel fasteners.

Vous aimerez peut-être aussi