Description
General
Cable Size
Voltage grade
Ref. standard
Number of cores
Max.operating temp.
Max.short circuit temp.
CONDUCTOR
Material
Nominal area
Minimum no. of wires
Shape
Compaction
Conductor diameter - Approx.
CONDUCTOR SCREEN
Unit
1C x 240mm
kV
kV
Nos.
C
C
1C x 240mm
12/20 (24)
IEC 60502-2
1
90
250
mm
Nos.
mm
0.3
Yes
mm
0.3
mm
mm
XLPE
5.50
4.85
Yes
mm
0.3
Semiconductive Water Blocking Tape
mm
mm
0.3
Copper Tape
1
0.1
(NOTE : * No. of Copper Tape & Thickness may change but shall be suitable to carry Fault Current Rating of 1.1kA for 1Sec.)
INNER SHEATH
Material
Thickness of inner sheath - Nominal
Thickness of inner sheath - Minimum
Dia over inner sheath - Approximate
Colour of inner sheath
mm
mm
mm
ARMOUR
Material of Armour
Diameter of armour wire- Nominal
Number of wires- Approximate
Dia over armour- Approximate
mm
Nos.
mm
PVC ST 2
1.20
0.76
37.80
Black
Yes (Nonconductive Water Blocking
Tape)
AWA
2.00
52
42.40
Yes (Nonconductive Water Blocking
Tape)
PP Tape or Polyester Tape
TECHNICAL PARTICULARS
Date : 13th Mar. 2016
Rev. No. : 00
Description
TAPE
Material
Approx. Tape Thickness
Application
OUTER SHEATH
Material
Thickness of outer sheath - Nominal
Thickness of outer sheath - Minimum
Overall dia - Approximate
Colour of sheath
PACKAGING
Standard Drum length ( 5%)
Unit
1C x 240mm
mm
mm
mm
mm
HDPE (ST 7)
2.30
1.64
46.5
Black
mtr
1000
Wooden / Steel drums with Wooden
10.02 Packing material
Lagging
10.03 Approx. Size of drum (H x W)*
mm
2000 x 1140
* Drum dimensions is for guidance only & may change due to non-availability of drum of specified size.
11.00 WEIGHTS (Approx.)
11.01 Finished cable
kg / km
2445
11.02 Net weight
kg
2445
11.03 Gross weight of drum
kg
2705
12.00 ELECTRICAL PARAMETERS
12.01 DC resistance of conductor at 20 C - Maximum
/km
0.125
12.02 AC resistance of conductor at 90 C - Approximate
/km
0.162
12.03 Reactance at 50 Hz - Approximate
/km
0.113
12.04 Impedance at 50 Hz - Approximate
/km
0.198
12.05 Capacitance at 50 Hz - Approximate
F/km
0.313
12.06 Short circuit current rating of conductor for 1 Sec.
kA
22.56
12.07 Current Rating (considering 1C cables laid in trefoil
12.08 formation):
12.08.01 Current rating- in ground at 20 C
A
367
Current rating- in duct at 20 C
12.08.02 (In case of Single core cables, considering 3 Single core cables
A
351
in trefoil formation in One common duct)
12.08.03 Current rating- in air at 30C (Flat Spaced)
A
593
12.08.04 Basic Assumptions
Ambient temp. - 30 C
Ground temp. 20 C
Depth of laying in ground - 0.8 Mtr.
Thermal resistivity of soil -1.5 K. m/W
Thermal resistivity of Earthenware duct = 1.2 K m/W
12.09 Fault current rating of copper screen for 1 sec.
kA
0.256
12.10 Fault current rating of armour for 1 second (Approx.)
kA
12.27
12.11 Charging Current at U0 = 12kV, 50Hz.
A/km
1.180
12.12 Dielectric Loss (at U0 = 12kV)
W/km/ph
56.64
13.00 MISC
13.01 Max pulling tension when pulled by pulling eye
kg
720
13.02 Min. Bending radius
mm
15 x OD of cable
NOTE : Embossing on outer sheath of cable shall be as per the examples given below :
"ELECTRIC CABLE 12/20 KV OMAN CABLES 1 X 240 YEAR"
Sequential length marking shall also be provided on outer sheath of cable at every 1m by printing/indenting/embossing.