Vous êtes sur la page 1sur 36

INDOOR AIR QUALITY ASSESSMENT REPORT

McGill University
Leacock Building
Montreal, Quebec

Assessment performed: November 30th - December 4th 2009

Prepared by:
GESTION ENVIRONNEMENTALE T. HARRIS INC.

___________________________
Brigitte Soucy, M. Sc.
Hygiene Project Manager

___________________________
Jemima Bellemare
Hygiene Technician

Prepared for:
Mr. Louis Boissonneault, Eng.
Project Manager
GENIVAR
1600 Ren-Lvesque Blvd. West, 16th Floor
Montreal, Quebec (H3H 1P9)

RAP 091208-01

EXECUTIVE SUMMARY

OBJECTIVE
Personnel from Gestion Environnementale T. Harris Inc. (GETH) conducted a general Indoor
Air Quality (IAQ) assessment of the selected areas on the 3rd to 9th floors of the Leacock
Building located at 855 Sherbrooke Street West in Montreal, Quebec.
The assessment was performed from November 30th to December 4th 2009 at the request of Mr.
Louis Boissonneault, Project Manager at GENIVAR. This evaluation was conducted in order to
determine the quality of air following the replacement of two ventilation units that serve the 3rd
to 9th floors.
A range of measurements was taken within the areas under study. These included thermal
comfort parameters (temperature and percent relative humidity) and air quality parameters
(carbon dioxide, carbon monoxide and respirable suspended particulates).
METHODS
The indoor air quality assessment was performed in selected rooms throughout the 3rd to 9th
floors. The assessment was performed mainly in offices, but measurements were also taken in at
least one class room on each floor.
Spot testing for IAQ parameters was conducted three times throughout the day for a total of 47
sample locations including one exterior location. Measurements were taken in sufficient numbers
in order to determine if any significant differences in air quality parameters occurred from
location to location and during different periods of the day.
Continuous monitoring for IAQ parameters was conducted over a 24-hour period in three
locations on each floor (3rd to 9th floors) and consisted of recording measured parameters every
minute. Continuous monitoring locations were chosen according to information we received
from the employees in the weeks prior to our assessment.

RESULTS AND DISCUSSION


Results of the continuous monitoring are consistent with the results of the spot testing for IAQ
parameters and the following observations can be made:

Average carbon dioxide (CO2) concentrations are all below the ASHRAE guideline
concentration (950 ppm i.e. 600 ppm (at 17 CFM) above outdoor CO2 concentration) and
show that the rooms are receiving an adequate supply of fresh air.
Average carbon monoxide (CO) concentrations were all below the ASHRAE guideline for an
8-hour period (9 ppm).
Average temperatures measured in some rooms (318, 324, 443C, 539, 608, 718, 732, 812,
923 and 943) are above the ASHRAE maximum temperature guideline for winter months
(24 oC).
Temperatures above the ASHRAE maximum temperature guideline for winter months
(24 oC) were observed in most of the locations tested (see maximum values in Tables I to
VIII in Appendix I).
With the exception of rooms 318 and 324, average relative humidity levels are all above the
minimum relative humidity level of 20% for office spaces established by the RROHS. Most
of the rooms tested over a 24-hour period also meet the ASHRAE recommended range for
relative humidity (30-60%).
Average respirable suspended particulates (RSP) concentrations are all below the ASHRAE
guideline (50 g/m3).

CONCLUSION AND RECOMMENDATIONS


Continuous monitoring results agree well with spot testing results and indicate that during
normal building operation, the quality of air within the locations tested should not represent a
health concern to building occupants and that the complaints may be related to thermal comfort
rather than contaminant levels.
Based on the results of the IAQ assessment performed in Leacock Building from November 30th
to December 4th 2009, GETH makes the following recommendations in order to improve the
comfort of the occupants:

Maintain temperature within ASHRAE guidelines, i.e. between 20 and 24oC for winter
months.
Avoid drifts in temperature exceeding the limits established by ASHRAE.
Maintain relative humidity levels within ASHRAE guidelines, i.e. between 30 and 60%.

TABLE OF CONTENTS

1.

OBJECTIVE ........................................................................................................................ 1

2.

AIR QUALITY STANDARDS AND GUIDELINES ....................................................... 1

3.

METHODS ........................................................................................................................... 5
3.1
3.2

4.

INVESTIGATED AREAS ..................................................................................................... 5


THERMAL COMFORT AND IAQ PARAMETERS .................................................................. 5
RESULTS AND DISCUSSION .......................................................................................... 6

4.1

THERMAL COMFORT AND IAQ PARAMETERS .................................................................. 6

5.

CONCLUSIONS AND RECOMMENDATIONS....................................................... 18

6.

LIMITATIONS .................................................................................................................. 20

APPENDIX I Detailed Results


APPENDIX II Graphical Representation (Continuous Monitoring)
APPENDIX III Sample Location

GENIVAR
1600 Ren-Lvesque Blvd. West, 16th Floor
Montreal, Quebec H3H 1P9
Attention:

Mr. Louis Boissonneault


Project Manager

Re:

Indoor Air Quality Assessment


McGill University - Leacock Building
Montreal, Quebec
______________________________________________________________________________
1.

OBJECTIVE

Personnel from Gestion Environnementale T. Harris Inc. (GETH) conducted a general Indoor
Air Quality (IAQ) assessment of the selected areas on the 3rd to 9th floors of the Leacock
Building located at 855 Sherbrooke Street West in Montreal, Quebec.
The assessment was performed from November 30th to December 4th 2009 at the request of Mr.
Louis Boissonneault, Project Manager at GENIVAR. This evaluation was conducted in order to
determine the quality of air following the replacement of two ventilation units that serve the 3rd
to 9th floors.
A range of measurements was taken within the areas under study. These included thermal
comfort parameters: temperature (T) and percent relative humidity (%RH); air quality
parameters: carbon dioxide (CO2), carbon monoxide (CO) and respirable suspended particulates
(RSP).
2.

AIR QUALITY STANDARDS AND GUIDELINES

Heating, ventilation, and air conditioning (HVAC) systems for buildings are designed to provide
good air quality and thermal comfort at a reasonable energy cost. Good air quality refers to
adequate oxygen levels, removal of CO2 resulting from human respiration, and dilution/removal
of contaminants, including odours. Thermal comfort is typically defined as an environment in
which at least 80% of normally clothed occupants engaged in sedentary or near-sedentary
activities, feel comfortable. Environmental factors contributing to thermal comfort include air
temperature, radiant heat load, relative humidity, and air velocity.
At the present time, there are no legally enforceable standards for indoor air pollutants in
residential and institutional buildings, and non-industrial workplaces in Canada. However,
various organizations have published guidelines for evaluating indoor air quality. These air
quality guidelines specify maximum concentrations and exposure times for specific contaminants
in indoor and outdoor environments.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
The Federal-Provincial Advisory Committee on Environment and Occupational Health, under
the auspices of Health Canada, established acceptable IAQ guidelines for known indoor air
contaminants in two guidelines titled Exposure Guidelines for Residential Indoor Air Quality
(1995) and Indoor Air Quality in Office Buildings: A Technical Guide (1995), setting out
permissible ranges of airborne concentrations for selected substances. The Exposure Guidelines
for Residential Indoor Air Quality includes an acceptable long-term exposure range (ALTER)
that specifies the concentration of a given substance individuals may be exposed to throughout a
lifetime without affecting their health. Similarly, an acceptable short-term exposure range
(ASTER) defines the concentration of a substance to which people can be safely exposed to
within a specified time.
The Indoor Air Quality in Office Buildings: A Technical Guide stipulates that the generally
accepted guidelines for ventilation and indoor air quality are the American Society of Heating,
Refrigerating, and Air Conditioning Engineers (ASHRAE), Standard 55-2004, Thermal
Environmental Conditions for Human Occupancy, and ASHRAE Standard 62.1-2007,
Ventilation for Acceptable Indoor Air Quality. These standards give recommended guidelines for
thermal comfort parameters, and specific chemical contaminants in mechanically ventilated
buildings.
ASHRAE Standard 62.1-2007 also recommends outdoor air mechanical ventilation rates for
typical office buildings. Under this standard, the recommended outdoor air ventilation rate is
17 CFM (cubic feet per minute) per person for a typical office space, based on an estimated
maximum occupancy of five (5) people per 1,000 ft2. At this ventilation rate, a steady-state CO2
concentration of no greater than about 600 ppm above outdoor levels develops in an occupied
space with the assumption that make-up air is of satisfactory quality, and outside CO2
concentrations are in the 300 to 500 ppm range.
For the purpose of the current IAQ assessment, an average outside CO2 concentration of 350
ppm was used. Therefore, a guideline CO2 concentration of 950 ppm (a concentration of 600
ppm above the average outside CO2 concentration) would indicate an adequate supply of fresh
outside air at a ventilation rate of 17 cfm per person occupying a typical office space. Even
though this ventilation rate can be considered acceptable for a typical office environment, certain
airborne contaminants may be relatively higher depending on their content in the fresh outdoor
air introduced. Therefore in some buildings, indoor air quality may not meet all the requirements
of the ASHRAE standard.

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
Quebec Provincial RROHS - Regulation Respecting Occupational Health and Safety
(Rglement sur la sant et la scurit du travail RSST) L.R.Q., c. S-2.1, r.19.01, establishes
requirements regarding ventilation and heating.
Table I summarizes IAQ guidelines, which were used in the interpretation of our sampling data.
For reference, IAQ guidelines published by the World Health Organization (WHO) are also
included. The WHO guidelines do not differentiate between outdoor and indoor air quality, and
are aimed at protecting the health of the general population including sensitive population
subgroups such as the elderly and asthmatics.

TABLE I
Indoor Air Quality Guidelines
Parameter

Units

WHO

RSST
L.R.Q.
TWAEV

20
(Office)

3,500

5,000

35
10 000 (as
total dust)

Health Canada

ASHRAE

ASTER

ALTER

Thermal Comfort
Temperature

20-24 (Winter)
23-25.5 (Summer)

30-80
(Summer)
30-55
(Winter1)
General IAQ

Relative Humidity

30-60

Carbon Dioxide

ppm

600 (at 17 CFM)


above exterior
CO2 concentration

Carbon Monoxide

ppm

9 (8 hr.)
35 (1 hr.)

11 (8 hr.)
25 (1 hr.)

10 (8 hr.)
25 (1 hr.)
50 (30 min.)
90 (15 min.)

Respirable
Particulates

g/m3

50 (annual)2
150 (24 hr.)

100 (1 hr.)3

403

Notes: - None established; 1 unless constrained by window condensation; 2 for particles 10 m or smaller;
3
for particles 2.5 m.

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE II
Limits on Temperature Drifts and Ramps1
Time Period Maximum Temperature Change Allowed (oC)
0.25 hr.
1.1
0.5 hr.
1.7
1 hr.
2.2
2 hr.
2.8
4 hr.
3.3
1
Drift refers to passive temperature changes; Ramp refers to actively controlled temperature changes.

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors

3.

METHODS

3.1

Investigated Areas

The indoor air quality assessment was performed in selected rooms throughout the 3rd to 9th
floors. The assessment was performed mainly in offices, but measurements were also taken in at
least one class room on each floor.
3.2

Thermal Comfort and IAQ Parameters

Measurements of temperature, relative humidity, carbon dioxide (CO2) and carbon monoxide
(CO) were taken using a TSI Q-Trak IAQ Monitor (Models 8551 and 8554). This instrument has
four separate sensors (one for each parameter).
Airborne particulate measurements were taken using a TSI Dust-Trak Aerosol Monitor (Model
8520). This device instantaneously measures average, minimum and maximum particle
concentrations for particles between 0.1 and 10 m in diameter, with a measuring range of 10
g/m3 to 100 mg/m3. Air sampling was conducted at a flow rate of 1.7 litre per minute (lpm). A
10 mm diameter nylon cyclone, attached to the sampling port was employed, in order to measure
the respirable fraction from the total airborne dust sampled. The cyclone, at a flow rate of
1.7 lpm, cuts off particles greater than 4 m in diameter.
The above instruments were calibrated according to manufacturer instructions.
Spot testing for IAQ parameters was conducted three times throughout the day for a total of 47
sample locations including one exterior location. Measurements were taken in sufficient numbers
in order to determine if any significant differences in air quality parameters occurred from
location to location and during different periods of the day.
Continuous monitoring for IAQ parameters was conducted over a 24-hour period in three
locations on each floor (3rd to 9th floors) and consisted of recording measured parameters every
minute. Maximum, minimum and average values for each parameter were calculated.
Continuous monitoring locations were chosen according to information we received from the
employees in the weeks prior to our assessment.

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors

4.

RESULTS AND DISCUSSION

4.1

Thermal Comfort and IAQ Parameters

Spot Testing
The results of IAQ spot testing performed in selected rooms on November 30th 2009 are
summarized in the following charts. The charts show the average results for each IAQ parameter
measured on the 3rd to 9th floors. Detailed results for each room are shown in Tables I to VII in
Appendix I.
Carbon Dioxide (CO2)
1000

ASHRAE
900

800
702
700

656

Concentration (ppm)

633

670

649

627

610

600

500

400

300

200

100

0
3

Floor

Chart No. 1: Spot Testing Results for Carbon Dioxide (CO2)


3rd to 9th Floors, November 30th 2009
ChartrdNo. 1th shows that the average carbon dioxide concentrations (610-702 ppm) measured on
the 3 to 9 floors are below the ASHRAE guideline (950 ppm i.e. 600 ppm (at 17 CFM) above
outdoor CO2 concentration).

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
Overall (with few exceptions), the CO2 levels were noted to be higher in the afternoon than in the
morning.
Carbon Monoxide (CO)
10

ASHRAE
9

Concentration (ppm)

1
0

0,1

0,1

0
Floor

Chart No. 2: Spot Testing Results for Carbon Monoxide (CO)


3rd to 9th Floors, November 30th 2009
Chart No. 2 shows that the average carbon monoxide concentrations (0-0.1 ppm) measured on
the 3rd to 9th floors are below the ASHRAE guideline for an 8-hour period (9 ppm).

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
o

Temperature ( C)
25

24,4

24,5

Temperature (oC)

24

ASHRAE

23,5
23,5
23,3
23,2
23

22,9

22,9

22,5
22,5

22

21,5
3

Floor

Chart No. 3: Spot Testing Results for Temperature


3rd to 9th Floors, November 30th 2009
Chart No. 3 shows that the average temperature measured on the 4th floor (24.4oC) is slightly
higher than the ASHRAE maximum temperature guideline for winter months (24oC). The
average temperatures measured on the remaining floors (22.5-23.5oC) are within ASRAE
recommended temperature range for winter months (20-24 oC).
As can be seen in Tables II to V in Appendix I, temperatures measured in the morning on the 4th,
5th, 6th and 7th floors were all higher than the ASHRAE maximum temperature guideline for
winter months (24oC).
Drifts between morning and afternoon temperatures were observed on the 4th, 5th, 6th and 7th
floors. Temperature drifts should not exceed 3.3oC over a 4-hour period. On the 8th floor,
afternoon measurements that were taken less than one hour from each other show temperature
drifts exceeding 2.2oC (the limit for a 1-hour period).
Temperatures remained relatively constant over the day in most rooms on the 3rd and 9th floors.
Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
Fluctuations in the temperature (that are not under the control of the occupants) may affect the
thermal comfort of occupants (ASHRAE, 2007).

Relative Humidity (%)


80

70

Relative Humidity (%)

60

ASHRAE

50

40

30

26
23

25

26

25

24

24

RROHS

20

10

0
3

Floor

Chart No. 4: Spot Testing Results for Relative Humidity


3rd to 9th Floors, November 30th 2009
Chart No. 4 shows that the average relative humidity levels (23-26%) measured on the 3rd to 9th
floors are below the ASHRAE guidelines (30-60%) for all floors. However, results are above the
minimum relative humidity level of 20% for office spaces established by the RROHS.
Low relative humidity levels may affect the comfort of occupants by causing symptoms such as
irritation of mucus membranes.

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
3

Respirable Suspended Particulates (g/m )


60

50

ASHRAE

Concentration (g/m3)

40

30

20

10
3

0
9

Floor

Chart No. 5: Spot Testing Results for Respirable Suspended Particulates (RSP)
3rd to 9th Floors, November 30th 2009
Chart No. 5 shows that the average concentrations of respirable suspended particulates (RSP)
(2-3 g/m3) measured on the 3rd to 9th floors are below the ASHRAE guideline (50 g/m3).

Gestion Environnementale T. Harris Inc.

10

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
Continuous Monitoring
The results of continuous monitoring for IAQ parameters performed in selected rooms from
November 30th to December 4th 2009 are summarized in the following charts. The charts show
the average results for each IAQ parameter measured in the selected rooms over a 24-hour
period. Detailed results for each room (average, minimum and maximum values) are shown in
Table VIII in Appendix I. Graphical representation of the results for each room is shown in
Appendix II. Sample location is shown in Appendix III.
Carbon Dioxide (CO2)
1000

ASHRAE

950
900
850
800
750

Concentration (ppm)

700
650
600
550
500

482

473
441

450

435

400

453

436

482

471
427

410

445

422
394

370

449

426

398

407
376

350

329

319

732

812

300
250
200
150
100
50
0
307

318

324

422

432 443C 509

534

539

608

621

633

718

723

832

833

919

923

943

Room

Chart No. 6: Continuous monitoring for Carbon Dioxide (CO2)


3rd to 9th Floors, November 30th-December 4th 2009
Note: Average CO2 concentration for room 307 is based on an 11-hour monitoring since the device was unplugged
during sampling.

Chart No. 6 shows that the average carbon dioxide concentrations (319-482 ppm) measured over
a 24-hour period in selected rooms are below the ASHRAE guideline (950 ppm i.e. 600 ppm (at
17 CFM) above outdoor CO2 concentration).

Gestion Environnementale T. Harris Inc.

11

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
Based on the charts shown in Appendix II, CO2 concentrations were noted to be highest around
15:00 in most rooms.

Carbon Monoxide (CO)


10

ASHRAE
9

Concentration (ppm)

2
1
1
0

307

318

324

422

534

539

621

633

718

723

732

812

832

833

919

923

943

0
432 443C 509

608

Room

Chart No. 7: Continuous monitoring for Carbon Monoxide (CO)


3rd to 9th Floors, November 30th-December 4th 2009
Chart No. 7 shows that the average carbon monoxide concentrations (0-1 ppm) measured over a
24-hour period in selected rooms are below the ASHRAE guideline for an 8-hour period
(9 ppm).

Gestion Environnementale T. Harris Inc.

12

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
o

Temperature ( C)
35

29,3

30

27,7
26,3

26,5

25,6

25

25,4

25,3

22,8

24,7

24,1

23,9 23,9
23

22,5

ASHRAE
20,9 21,2

21,3
Temperature (oC)

26,1

21,3

20,4 20,6

20

15

10

0
307

318

324

422

432 443C 509

534

539

608

621

633

718

723

732

812

832

833

919

923

943

Room

Chart No. 8: Continuous Monitoring for Temperature


3rd to 9th Floors, November 30th-December 4th 2009
Chart No. 8 shows that the average temperatures measured over a 24-hour period in rooms 318,
324, 443C, 539, 608, 718, 732, 812, 923 and 943 (24.1-29.3oC) are above the ASHRAE
maximum temperature guideline for winter months (24 oC). The average temperatures measured
in the remaining rooms (20.4-23.9oC) are within ASHRAE recommended temperature range for
winter months (20-24 oC).
Based on the charts shown in Appendix II, temperatures were noted to be relatively constant
during office hours with changes of 2oC or less over the day in most rooms.
Drops in temperatures, with a rise in relative humidity have been observed in some rooms (e.g.
432, 443C, 509, 621 and 718). All these rooms have opening windows. The sudden changes may
be related to the opening of the windows.
In room 633, high temperatures (25-30oC) were noted around 13:00 and a drop in relative
humidity was also noted around the same time (see chart No 23 in Appendix II).
Gestion Environnementale T. Harris Inc.

13

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
In room 832, temperature went from 21oC to 26oC in less then 3 hours (between 9:00 and 12:00).
A drop in relative humidity was noted at the same time (see chart No. 33 in Appendix II). This
drift exceeds the limit for a 4-hour period (3.3oC).
Relative Humidity (%)
80

70

Relative Humidity (%)

60

ASHRAE

50
45

46
42

40

37

38

37

36

34

39

44
40

39
37

33

31

30
30

25
22

22
RROHS

20

11

10

318

324

10

0
307

422

432 443C 509

534

539

608

621

633

718

723

732

812

832

833

919

923

943

Room

Chart No. 9: Continuous Monitoring for Relative Humidity


3rd to 9th Floors, November 30th-December 4th 2009
Chart No. 9 shows that the average relative humidity levels measured over a 24-hour period in
rooms 307, 318, 324, 443C and 923 (10-25%) are below the ASHRAE recommended range (3060%). However, relative humidity levels measured in rooms 307, 443C and 923 (22-25%) are
above the minimum relative humidity level of 20% for office spaces established by the RROHS.
Humidity levels measured in rooms 318 and 324 are below the minimum relative humidity level
of 20% for office spaces established by the RROHS. Relative humidity levels measured in the
remaining rooms (30-46%) are within ASHRAE recommended range (30-60%).

Gestion Environnementale T. Harris Inc.

14

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
3

Respirable Suspended Particulates (g/m )


60

ASHRAE
50
44

Concentration (g/m3)

40

30

21
20
13

13

12

11
9

10

7
3

8
6

5
3

0
307

318

324

422

432 443C 509

534

539

608

621

633

718

723

732

812

832

833

919

923

943

Room

Chart No. 10: Continuous Monitoring for Respirable Suspended Particulates (RSP)
3rd to 9th Floors, November 30th-December 4th 2009
Note: Average RSP concentration for room 307 is based on a 20-hour monitoring since the device was unplugged
during sampling.

Chart No. 10 shows that the average concentrations of respirable suspended particulates (RSP)
(2-44 g/m3) measured over a 24-hour period are below the ASHRAE guideline (50 g/m3) in
all rooms. The average concentration for room 422 is unavailable due to a malfunction of the
device. The maximum concentration recorded for this room is 23 g/m3.

Gestion Environnementale T. Harris Inc.

15

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
Results of the continuous monitoring are consistent with the results of the spot testing for IAQ
parameters and the following observations can be made:

Average carbon dioxide (CO2) concentrations are all below the ASHRAE guideline
concentration (950 ppm i.e. 600 ppm (at 17 CFM) above outdoor CO2 concentration) and
show that the rooms are receiving an adequate supply of fresh air.
Average carbon monoxide (CO) concentrations were all below the ASHRAE guideline for an
8-hour period (9 ppm).
Average temperatures measured in some rooms (318, 324, 443C, 539, 608, 718, 732, 812,
923 and 943) are above the ASHRAE maximum temperature guideline for winter months
(24 oC).
Temperatures above the ASHRAE maximum temperature guideline for winter months
(24 oC) were observed in most of the locations tested (see maximum values in Tables I to
VIII in Appendix I).
With the exception of rooms 318 and 324, average relative humidity levels are all above the
minimum relative humidity level of 20% for office spaces established by the RROHS. Most
of the rooms tested over a 24-hour period also meet the ASHRAE recommended range for
relative humidity (30-60%).
Average respirable suspended particulates (RSP) concentrations are all below the ASHRAE
guideline (50 g/m3).

The following information was gathered during the assessment:

Some rooms (located on the corners of the building) have opening windows, but the majority
has non-opening windows.
Room 324 (computer laboratory) was originally a larger room and no change in the
ventilation system has been made since the room changed layout.

Gestion Environnementale T. Harris Inc.

16

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
Outdoor Conditions
Table III shows the average temperature and relative humidity based on hourly data from
Environment Canada (between 12:00 and 12:00) during the IAQ assessment performed from
November 30th to December 4th 2009.
TABLE III
Outdoor Temperature and Relative Humidity
November 30th December 4th 2009
Date
th
Nov. 30 Dec. 1st
Dec. 1st Dec. 2nd
Dec. 2nd Dec. 3rd
Dec. 3rd Dec. 4th

Temp. (oC)
-0.3
1.4
5.7
4.7

RH (%)
75
84
84
81

Table IV shows the respirable suspended particulates (RSP) concentrations measured on the days
the assessment was performed.
TABLE IV
Outdoor Concentrations for Respirable Suspended Particulates (RSP)
November 30th December 4th 2009
Date
November 30th
December 1st
December 2nd
December 3rd
December 4th
1

RSP (g/m3)1
11
16
22
6
9

Measured around 12:00

Gestion Environnementale T. Harris Inc.

17

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
5.

CONCLUSIONS AND RECOMMENDATIONS

While the quantity of air supplied to a work area is vital for diluting odours and other
contaminants, indoor air quality complaints may be related to thermal comfort rather than
contaminant levels. Temperature and relative humidity can play a role in how people perceive
their indoor environment. Thermal comfort is a function of temperature, relative humidity and air
motion.
The level of carbon dioxide (CO2) present in an occupied space is a good indicator of adequate
ventilation rates. Under the ASHRAE guideline, the recommended maximum carbon dioxide
(CO2) concentrations are 600 ppm above the outside concentrations for ventilation rate of 17
CFM of outside air.
Average carbon dioxide (CO2) concentrations measured in the Leacock Building are below the
ASHRAE guideline concentration (950 ppm) in all the locations tested. These results indicate
that all the locations are receiving adequate quantities of fresh air to control the build-up of
contaminants. Under these conditions, contaminants generated in the space under normal
conditions should not build up to concentrations expected to impact on occupant comfort or
health.
Average carbon monoxide (CO) concentrations remained below the ASHRAE guideline for an
8-hour period (9 ppm) in all locations tested. Therefore, this should not represent a health
concern to the building occupants.
The average temperatures recorded in rooms 318, 324, 443C, 539, 608, 718, 732, 812, 923 and
943 (24.1-29.3oC) are higher than the thermal comfort range of 20 to 24C as derived for winter
season from the ASHRAE recommended temperature ranges. Spot testing, along with maximum
temperature values recorded during continuous monitoring, show that temperatures above the
ASHRAE maximum temperature guideline for winter months (24 oC) were observed in most of
the locations tested.
Drifts in temperatures were observed mainly from the 4th to the 8th floors (notably in room 832).
Temperature drifts should not exceed the limits established by ASHRAE (see Table II).
Temperatures higher than the thermal comfort range, along with fluctuations in the temperature
(that are not under the control of the occupants) can play a role in how people perceive their
indoor environment. Temperatures should be maintained within the thermal comfort range of
20 to 24C as derived for winter season from the ASHRAE recommended temperature ranges.
With the exception of rooms 318 and 324, average relative humidity levels are all above the
minimum relative humidity level of 20% for office spaces established by the RROHS. Most of
the rooms tested over a 24-hour period also meet the ASHRAE recommended range for relative
Gestion Environnementale T. Harris Inc.

18

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
humidity (30-60%). The majority of building occupants should feel comfortable under these
conditions.
At low humidity conditions, some occupants may experience discomfort due to drying of the
skin and mucous membranes. Low relative humidity can cause other particles in the air to
become more irritating. Additional humidification may be necessary in order to increase relative
humidity levels within recommended comfort ranges in rooms 318 and 324.
Average respirable suspended particulates (RSP) concentrations are below the ASHRAE
guideline (50 g/m3) in all locations tested. Therefore, individuals working in these areas should
not experience discomfort at the RSP concentrations measured.
Continuous monitoring results agree well with spot testing results and indicate that during
normal building operation, the quality of air within the locations tested should not represent a
health concern to building occupants and that the complaints may be related to thermal comfort
rather than contaminant levels.
RECOMMENDATIONS
Based on the results of the IAQ assessment performed in Leacock Building from November 30th
to December 4th 2009, GETH makes the following recommendations in order to improve the
comfort of the occupants:

Maintain temperature within ASHRAE guidelines, i.e. between 20 and 24oC for winter
months.
Avoid drifts in temperature exceeding the limits established by ASHRAE (see Table II).
Maintain relative humidity levels within ASHRAE guidelines, i.e. between 30 and 60%.

Gestion Environnementale T. Harris Inc.

19

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors

6.

LIMITATIONS

The investigations, assessments and recommendations detailed in this report were carried out in a
manner consistent with the level of care and skill normally exercised by reasonable members of
the environmental and industrial hygiene consulting profession currently practicing under similar
conditions in the area. There are no warranties, expressed or implied, that apply to the
professional services provided under the terms of our assignment and included in this report.
In preparing this report, Gestion Environnementale T. Harris Inc. relied on information supplied
by independent laboratories and testing services. Except as expressly set out in this report, we
have not made any independent verification of such information.
The investigation, assessments and recommendations in this report have been made in the
context of existing industry accepted guidelines that were in place at the date of this report. The
investigation did not take account of any government regulations not in effect or not generally
promulgated at the date of this report.
The collection of samples at the Site was consistent with the scope of work agreed upon with the
person or entity to whom this report is addressed and the information obtained concerning prior
site investigations. As conditions between samples may vary, the potential remains for the
presence of unknown additional contaminants for which there were no known indicators.
This report is for the sole use of the person or entity to whom it is addressed. No other person or
entity is entitled to use or rely upon this report.

Gestion Environnementale T. Harris Inc.

20

APPENDIX I
Detailed Results

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE I
Spot Testing Results for IAQ Parameters - 3rd Floor
McGill University Leacock Building
November 30th 2009

No.

Sample location

Time

CO2
(ppm)

CO
(ppm)

Temp.
(C)

R.H.
(%)

RSP
3
(g/m )

rd

3 Floor

313
(N)

10:41

551

23.1

23.7

13:44

603

24.3

21.8

588

23.4

22.2

522

22.6

22.4

14:51
10:43
2

314
(NE corner)

321E
(S)

13:47

586

23.2

21.3

14:56

545

22.9

20.3

10:13

642

23.1

28.6

665

24.4

20.4

10:32

654

23.4

22.6

13:40

755

23.7

23.0

730

21.7

25.6

592

21.4

24.3

13:38
-

328
(W)

14:45
10:35
5

331
(corner)

Hall

13:51

580

21.4

23.0

14:41

557

21.0

22.2

10:19

638

22.9

26.4

760

24.5

22.5

13:25

798

22.2

26.4

Average

633

22.9

23.3

Minimum

522

21.0

20.3

Maximum

798

24.5

26.4

14:48

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE II
Spot Testing Results for IAQ Parameters 4th Floor
McGill University Leacock Building
November 30th 2009
No.

Sample
Location

Time

CO2
(ppm)

CO
(ppm)

Temp.
(C)

R.H.
(%)

RSP
3
(g/m )

th

4 Floor

414
(NE corner)

420

427
(SE corner)

429
(S)

439
(W)

443B
(NW corner)

Hall

10:14

817

26.3

27.7

13:14

799

23.5

27.4

14:15

737

23.0

26.5

10:28

602

27.0

23.3

13:16

791

23.7

27.9

14:18

761

0.2

23.5

26.4

10:16

823

24.9

25.3

13:18

717

0.1

23.4

26.5

14:20

704

23.5

26.6

10:19

601

25.7

24.6

10:22

514

26.4

23.0

13:21

801

0.1

23.2

26.6

14:22

661

23.4

25.8

10:24

589

26.7

23.3

13:11

626

23.2

27.3

14:14

715

22.8

26.9

10:26

595

26.9

23.3

13:13

621

23.3

27.1

14:16

869

23.3

26.4

Average

702

24.4

25.9

Minimum

514

22.8

23.0

Maximum

869

0.2

27.0

27.9

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE III
Spot Testing Results for IAQ Parameters 5th Floor
McGill University Leacock Building
November 30th 2009

No.

Sample
Location

Time

CO2
(ppm)

CO
(ppm)

Temp.
(C)

R.H.
(%)

RSP
3
(g/m )

th

5 Floor

514
(E)

520

521
(E)

525
(S)

528
(SW corner)

10:42

529

25.6

22.7

13:30

633

0.3

22.4

25.6

14:32

673

22.7

25.0

10:46

578

26.1

23.3

13:32

827

0.1

22.2

28.0

14:33

1011

22.8

30.8

10:39

595

25.6

23.4

13:33

609

0.2

21.9

26.4

14:35

690

22.6

26.0

10:38

676

25.4

23.2

13:36

592

21.9

26.3

14:37

660

22.0

26.1

10:35

522

24.8

21.0

13:37

556

18.7

26.4

14:39

571

19.3

24.6

10:33

589

26.8

22.1

13:25

664

23.0

26.3

14:29

712

0.1

22.2

25.1

10:26

595

26.9

23.3

13:13

621

23.3

27.1

14:16

869

23.3

26.4

Average

656

23.3

25.2

Minimum

522

18.7

21.0

Maximum

1011

0.3

26.9

30.8

543
(N)

Hall

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE IV
Spot Testing Results for IAQ Parameters 6th Floor
McGill University Leacock Building
November 30th 2009
No.

Sample
Location

Time

CO2
(ppm)

CO
(ppm)

Temp.
(C)

R.H.
(%)

RSP
3
(g/m )

th

6 Floor

609
(NE corner)

614

615
(E)

623
(S)

626
(SW corner)

638
(NW corner)

Hall

10:51

608

26.3

23.0

13:41

731

21.7

29.1

14:41

660

21.8

26.0

10:57

651

26.7

23.5

13:46

730

0.1

22.4

28.1

14:46

681

22.5

26.6

10:52

545

26.5

22.6

13:44

663

0.2

22.2

28.1

14:44

651

22.2

26.3

11:00

556

26.0

21.9

13:49

644

0.4

21.9

28.0

14:48

606

22.0

25.4

11:01

589

26.3

22.0

13:55

629

0.3

21.9

27.2

14:50

648

21.4

26.1

10:49

595

26.1

22.7

13:43

613

21.9

27.8

14:43

621

22.1

25.8

10:58

627

26.6

22.7

13:47

1307

0.4

22.2

28.2

14:47

706

22.5

26.4

Average

670

0.1

23.5

25.6

Minimum

545

21.4

21.9

Maximum

1307

0.4

26.7

28.2

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE V
Spot Testing Results for IAQ Parameters 7th Floor
McGill University Leacock Building
November 30th 2009
No.

Sample
Location

Time

CO2
(ppm)

CO
(ppm)

Temp.
(C)

R.H.
(%)

RSP
3
(g/m )

th

7 Floor

704

710
(NE corner)

714
(E)

725
(SW corner)

737
(NW corner)

738
(N)

Hall

11:21

721

26.7

24.4

14:10

730

0.1

21.5

28.7

15:08

674

22.4

26.5

11:05

624

25.8

22.7

13:57

655

0.1

20.2

28.5

14:51

654

20.6

26.0

11:17

602

26.4

22.9

14:09

663

0.4

21.0

27.9

15:03

760

22.6

25.7

11:14

537

25.4

22.1

14:07

540

20.4

25.9

15:01

625

21.4

24.3

11:09

559

25.8

23.1

14:02

630

0.1

22.4

27.1

14:57

575

22.3

25.5

11:07

621

24.9

22.5

13:59

590

0.1

20.2

26.3

14:54

574

20.0

26.1

11:12

723

26.2

23.4

14:05

832

0.1

22.8

26.6

15:00

733

22.3

26.1

Average

649

0.1

22.9

25.3

Minimum

537

20.0

22.1

Maximum

832

26.7

28.7

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE VI
Spot Testing Results for IAQ Parameters 8th Floor
McGill University Leacock Building
November 30th 2009
No.

Sample
Location

Time

CO2
(ppm)

CO
(ppm)

Temp.
(C)

R.H.
(%)

RSP
3
(g/m )

th

8 Floor

818
(E)

824
(SE corner)

828
(SW corner)

836

11:29

561

23.1

22.9

14:22

586

23.4

21.4

15:15

566

21.0

24.4

11:33

590

22.7

23.2

14:24

565

22.8

21.0

15:18

607

20.7

25.7

11:36

598

22.9

23.1

14:28

569

22.9

21.6

15:19

540

20.7

24.4

11:39

757

23.7

25.6

14:29

646

23.6

24.0

15:22

609

21.4

26.8

11:43

574

22.5

22.9

14:32

577

22.7

21.3

15:12

606

21.0

23.4

11:47

692

24.5

24.5

14:34

767

23.4

24.2

15:13

883

21.1

26.0

Average

627

22.5

23.7

Minimum

540

20.7

21.0

Maximum

883

24.5

26.8

841
(NW corner)

Hall

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE VII
Spot Testing Results for IAQ Parameters 9th Floor
McGill University Leacock Building
November 30th 2009
No.

Sample
Location

Time

CO2
(ppm)

CO
(ppm)

Temp.
(C)

R.H.
(%)

RSP
3
(g/m )

th

9 Floor

11:24

623

22.9

25.4

14:17

656

23.6

23.5

15:24

646

23.9

21.6

10:47

545

23.7

22.9

14:01

577

24.6

22.1

15:08

641

22.3

26.9

11:05

532

21.0

28.9

14:08

577

23.8

21.5

11:10

543

22.5

25.9

14:11

565

23.6

21.2

15:16

551

23.3

20.9

11:15

544

21.6

25.4

14:14

573

23.4

21.6

15:21

543

23.6

21.0

10:50

684

23.8

25.3

14:05

750

24.3

23.0

15:12

815

23.1

27.3

Average

610

23.2

23.8

Minimum

532

21.0

20.9

Maximum

815

24.6

28.9

908
(N)

912
(NE corner)

925
(SE corner)

929
(SW corner)

940
(W)

Hall

Gestion Environnementale T. Harris Inc.

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE VIII
Continuous Monitoring Results for IAQ Parameters
McGill University Leacock Building
November 30th - December 4th 2009
Sample
Location

CO2 (ppm)
Avg.
Min.
Max.

307
318
324

473
441
482

340
359
306

776
746
808

422
432
443C

435
410
436

372
352
365

873
670
720

509
534
539

370
453
471

300
380
399

737
698
681

608
621
633

427
422
394

366
364
355

770
595
516

718
723
732

398
445
329

316
368
286

652
798
467

Gestion Environnementale T. Harris Inc.

Results
CO (ppm)
Temp. (C)
Avg.
Min.
Max.
Avg.
Min.
Max.
3rd Floor November 30th - December 1st 2009
0
0
0
21.3
19.6
22.5
0
0
0.4
26.3
23.5
27.2
0
0
0.1
29.3
24.4
29.9
4th Floor December 1st - December 2nd 2009
0
0
0
22.8
21.4
24.3
0
0
0.1
23.0
22.6
23.7
0
0
0.4
25.6
25.1
26.1
5th Floor December 1st - December 2nd 2009
0
0
0
23.9
21.3
26.1
0
0
1
23.9
23.4
25.9
0
0
0
25.4
24.2
27.1
6th Floor December 2nd - December 3rd 2009
1
0
1
26.5
25.8
27.7
0
0
0
20.9
20.3
22.5
0
0
0.3
21.2
20.3
29.5
7th Floor December 2nd - December 3rd 2009
0
0
0
25.3
24.8
26.4
0
0
0
22.5
22.2
23.8
0
0
0
24.1
23.7
25.4

RSP (g/m3)
Avg.
Min.
Max.

Avg.

R.H. (%)
Min.

Max.

22.0
10.5
10.1

18.7
8.1
7.4

42.5
32.8
33.7

3
9
2

2
5
1

10
35
9

36.9
35.8
22.4

33.5
21.7
19.5

39.0
38.7
26.0

7
21

2
11

23
21
59

34.2
32.8
30.4

14.3
21.4
19.6

38.0
34.8
33.2

6
6
5

2
3
2

51
15
15

37.3
45.2
46.2

33.4
39.8
23.1

41.1
49.2
52.2

13
13
44

3
2
7

22
23
74

38.0
38.5
36.8

34.1
34.6
32.7

43.2
43.3
40.1

11
8
12

1
1
2

21
19
21

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors
TABLE VIII (continued)
Continuous Monitoring Results for IAQ Parameters
McGill University Leacock Building
November 30th - December 4th 2009
Sample
Location

CO2 (ppm)
Avg.
Min.
Max.

812
832
833

319
426
376

279
353
332

659
1 066
797

919
923
943

482
449
407

355
348
359

1 009
755
622

Gestion Environnementale T. Harris Inc.

Results
CO (ppm)
Temp. (C)
Avg.
Min.
Max.
Avg.
Min.
Max.
8th Floor December 3rd - December 4th 2009
0
0
0
26.1
25.7
26.6
0
0
0
21.3
20.7
26.0
0
0
0
20.4
19.8
24.2
9th Floor December 3rd - December 4th 2009
0
0
0
20.6
20.0
22.1
0
0
0.5
27.7
25.8
27.9
0
0
0
24.7
24.1
26.6

RSP (g/m3)
Avg.
Min.
Max.

Avg.

R.H. (%)
Min.

Max.

31.2
39.4
41.5

25.7
24.3
32.7

40.4
46.3
46.6

4
3
5

2
1
3

10
10
10

43.5
24.7
39.8

39.6
21.6
32.5

47.5
40.5
44.4

4
9
5

2
5
2

11
23
13

McGill University
Leacock Building

December 2009

INDOOR AIR QUALITY ASSESSMENT


3rd to 9th Floors

Gestion Environnementale T. Harris Inc.

Vous aimerez peut-être aussi