Académique Documents
Professionnel Documents
Culture Documents
Instrument transformers (ITs) are designed to transform voltage or current from the high
values in the transmission and distribution systems to the low values that can be utilized by
low voltage metering devices.
There are three primary applications for which ITs are used:
metering (for energy billing and transaction purposes)
protection control (for system protection and protective relaying purposes)
and load survey (for economic management of industrial loads)
Instrument transformer used in conjunction with ammeters and over current relays are called
current transformers.
adapting the MV current value at the primary to the characteristics of the metering or
protection devices by supplying a secondary current with a reduced, but proportional
current value
CTs are connected on the MV network primary circuit, they supply a reduced current value to
the secondary circuit, proportional to the network current on which they are installed.
The current transformer is designed to connect in series with the line to transform the line
current to the standard 5 amperes suitable for the meter or relay.
The primary is series-mounted on the MV network and subject to the same over-currents as
the latter and withstands the MV voltage.
The secondary generally has one of its terminals connected to earth. The secondary must
never be in an open circuit to avoid lethal shock as high voltage induced in secondary open
terminal in this case.
Types of CTS
wound: when the primary and the secondary have a coil wound on the magnetic circuit
slip-over: primary made up of a conductor that is not insulated from the installation
core: primary made up of an insulated cable.
Why secondary circuit of current transformer should not open:
To open the secondary circuit of current transformer while it is energized is a dangerous act.
If the secondary circuit open circuited then there will be zero current in the secondary circuit,
hence reduced back emf. This back emf restrains the primary flux to exceed. Without back
emf the primary flux increases and core get saturated. This increased flux develops high
voltage across secondary that is dangerous enough to catch a lethal shock.
Voltage transformers
Potential Transformer (PT) or Voltage Transforner (VT) is a device which transforms the
voltage on the power system from primary values to safe secondary values, in a ratio
proportional to the primary value. It is designed to give the secondary a voltage which is
proportional to that applied to its primary.
VTs or PTs make a low voltage from the high voltage of a certain ratio, so that the large
voltage can be easily measurable or sensed by using this low voltage by low voltage capacity
costly equipment like relay, PLC.
VTs or PTs are connected to the MV network primary, they supply the secondary circuit with
a reduced voltage value, proportional to the network voltage on which they are installed.
The voltage transformer is designed to connect in parallel with the line to transform the line
voltage to 115 or 120 volts suitable for the meter or relay. To keep the voltage at the meters
and relays at a safe value, the secondary circuit must be grounded.
A voltage transformer is connected across the line or lineground, and is loaded to a greater or
lesser degree depending on the number of devices connected in parallel at the secondary
terminals (Figure 20). As the load is increased, the curves for ratio error and phase angle will
show how the accuracy is affected. If accuracy is not important, the load can be increased to
the thermal volt-ampere rating, the maximum which can be carried without overheating.
Voltage transformers must be able to withstand an accidental short circuit for one second
Consists of a primary winding, a magnetic core, one or several secondary windings, with
everything encapsulated in an insulating resin.
Voltage transformers have the following two functions:
Adapting the value of MV voltage on the primary to the characteristics of metering or
protection devices by supplying a secondary voltage that is proportional and lower in
value.
Isolating power circuits from the metering and/or protection circuit.
.
Generator Protection
Protection
A. Stator Winding Problems A. Differential Protection (what goes in must come out)
1. Winding-winding short
2. Stator ground
B. Rotor Problems
1. Loss of Field
1. Loss of field
a. Impedance
2. Field ground
2. Field ground
a. First ground
b. Second ground
C. Abnormal Conditions
1. Over/Under Frequency
2. Over Excitation
3. Reverse Power
4. Out of Step
5. Unbalance Current
Protection relays
Protective relays monitor the current and/or voltage of the power system to detect problems
with the power system. Currents and voltages to relays are supplied via CTs and PTs
As Generators and transformers are major components of a power system, so it is quite
necessary to take all the preventive measures for the protection of transformers and
generators.
These are the following ways (ANSI codes) we use to protect transformers and generators
from faults:
ANSI
code
87/G1
Description
Generator differential protection (87/G1): the protection is provided with high
speed, high stability circulating current relays. The relays has a pick up range of
10 to 40% of 5A and shall have suitable stabilizing for ensuring stability against
external faults. The relays shall be tuned to fundamental frequency to reject
harmonics produced by CT saturation.
87/GT1
87T1A
64GI
Generator stator earth fault protection (64GI): the stator earth fault protection
shall consist of a zero sequence voltage relay connected to the broken delta
winding of generator voltage transformer. The protection shall act to initiate a
time-delayed signal only and hence the relay shall be continuously rated for
110V.
The relay shall incorporate arrangements to make it insensitive to third
harmonic voltages.
87TG
64-1,64-
Generator rotor earth fault protection(64-1,64-2): the first rotor earth fault of
40G
Generator loss of field protection(40G): this protection shall be single phase off
set impedance type. The relays shall have impedance settings to cover the usual
range of impedance of large turbo generators.
21G
46G
67-1G,
67-2G
characteristics. One of the two relays shall be set with higher time dial setting to
provide second stage of protection.
51G
initiate an overload alarm. The relay shall have high reset ratio and adequate
continuous thermal rating.
59G
50T1A
95G
86G and Lockout relays(86G and 86GT): lockout relays shall be provided for each
86GT
generator unit which will be multi contact , hand reset type. The latching
mechanism shall be positive and insensitive to vibration and shock
Excitation
Excitation systems have a powerful impact on generator dynamic performance and
availability, it ensures quality of generator voltage and reactive power, i.e. quality of
delivered energy to consumers
The main purpose of excitation system for generator is to supply the power source to the rotor
field coil. Excitation system produce the field current and it controlled by the automatic
voltage regulator (AVR).
This field current controller is important to ensure the generator running in the suitable
voltage. It also controls the value of current when generator connected to a large load. It
receives or delivers the required level for reactive power ( kVAr).
Following types are common:
Brushless excitation systems, with rotating exciter machines and Automatic Voltage
Regulator (AVR), or
Static excitation systems (SES), feeding rotor directly from thyristor bridges via
brushes.
Main functions of excitation system are to provide variable DC current with short time
overload capability, controlling terminal voltage with suitable accuracy, ensure stable
operation with network and/ or other machines, contribution to transient stability subsequent
to a fault, communicate with the power plant control system and to keep machine within
permissible operating range.
The functions of an excitation system are
to provide direct current to the synchronous generator field winding, and
to perform control and protective functions essential to the satisfactory operation of
the power system
Types of Excitation Systems
1. DC excitation systems
2. AC excitation systems
3. Static excitation systems
1. DC Excitation Systems:
utilize
dc
generators
driven
by
motor
as
or
the
source
shaft
of
of
power;
main
generator;
AC Excitation Systems:
use ac machines (alternators) as source of power
usually, the exciter is on the same shaft as the turbine-generator
the ac output of exciter is rectified by either controlled or non-controlled rectifiers
rectifiers may be stationary or rotating
early systems used a combination of magnetic and rotating amplifiers as regulators;
most new systems use electronic amplifier regulators
the power supply to the rectifiers is from the main generator or the station auxiliary
bus
An exciter is part of the generator package supplying direct current to the alternator field
windings to magnetize the rotating poles. The exciter output may be controlled by a voltage
regulator. Types of exciters include brush type with rotating commutator, static excitation or
brush less generator and exciter.
DC Exciter
This invoves a small DC generator coupled to the same shaft as the rotor. Therefore, when the
rotor rotates this exciter produces the power for the electromagnet. Control of the exciter
output is done by varying the field current of the exciter. This output from the exciter then
controls the magnetic field of the rotor to produce a constant voltage output by the generator.
This DC current feeds to the rotor through slip rings.
Static Exciter
In modern generators the exciters are static. The DC power for the electromagnet is from the
main generator output itself. A number of high power thyristors rectify the AC current to
produce a DC current which feeds to the rotor through slip rings. This eliminates the
operation and maintenance problems associated with having another rotating machine. Static
exciters offer a better control of the output than an electromechanical control.
During start up, when there is no output from the generator, a large battery bank provides the
necessary power for excitation.
Brushless Exciter
In this system the armature of the exciter is on the rotor shaft itself. The DC output of this
armature, after rectification by solid-state devices, goes to the rotor coils. Since the armature
and rotor are on the same rotating shaft, this eliminates the need for slip rings. Hence it
reduces maintenance and operational requirements and thus improving reliability.
hundreds of megawatts.
Synchronous generator converts mechanical power to ac electric power. The source of
mechanical power, the prime mover, may be a diesel engine, a steam turbine, a water
generation.
Smaller synchronous machines are sometimes used for private generation and as
standby units, with diesel engines or gas turbines as prime movers
Fig.1 Two methods to produce electricity: Rotating coil and Rotating magnetic field concept
In the case of alternators the latter approach is used.
Main Parts and Working
Rotor and Armature coils are the 2 main parts of an alternator. Rotor produces a rotating
magnetic field. Armature coils are stationary and rotating magnetic flux associated with the
rotor induces electricity in the armature coils.
The rotor is made to rotate by a prime mover. This makes the rotor flux also rotate along with
it, at the same speed.
Such revolving magnetic flux now intersects the armature coils, which is fitted around the
rotor. This will generate an alternating E.M.F across the winding.