PROJECT:
CONSULTANT:
CONTRACTOR:
DOCUMENT TITLE:
ARABIAN BEMCO
CONTRACTING COMPANY
DISTRIBUTION CODE:
PP10CC-0009-6MAL-YR-ABC-001
SHEET NO.
I&C
REV.
1 OF 26
SIZE
SCALE:
A4
N.T.S
FILE NAME:
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 2
/ 26
Rev.: 2
INDEX OF CONTENTS
1. INTRODUCTION............................................................................................................... 3
1.1.OBJECTIVE OF THE DOCUMENT .................................................................................. 3
1.2.SCOPE OF THE DOCUMENT.......................................................................................... 3
1.3.REFERENCE DOCUMENTATION ................................................................................... 3
2. SYSTEM DESCRIPTION .................................................................................................. 5
2.1.MAIN EQUIPMENT, PERMISSIVES AND INTERLOCKS ................................................ 5
2.2.MECHANICAL BATTERY LIMITS .................................................................................... 8
2.3.FUNCTIONALITY.............................................................................................................. 9
2.4.CONTROL INTERFACES WITH OTHER SYSTEMS ....................................................... 9
2.5.SIGNALS MONITORING ................................................................................................ 10
2.5.1. Measuring instrument..................................................................................... 10
2.5.2. Selection logic architecture ........................................................................... 11
2.5.3. Bad quality concept ........................................................................................ 12
2.6.PROCESS ACTUATORS ............................................................................................... 12
2.6.1. Process drivers/actuators .............................................................................. 12
2.6.2. Drivers/Actuators Fault Tolerance ................................................................ 13
2.7.FUNCTIONAL GROUPS................................................................................................. 14
2.7.1. Number of Functional Groups ....................................................................... 14
2.7.2. Functional Groups Operation Modes ............................................................ 14
2.8.SYSTEM CONTROL LOCATION ................................................................................... 15
3. OPERATION MODES..................................................................................................... 16
3.1.POSITION IN THE PLANT GENERAL START-UP SEQUENCE ................................... 16
3.2.CRITERION FOR SYSTEM START-UP ......................................................................... 16
3.3.START-UP SEQUENCE ................................................................................................. 16
3.4.NORMAL OPERATION................................................................................................... 17
3.5.POSITION IN THE PLANT GENERAL SHUTDOWN SEQUENCE ................................ 19
3.6.SHUTDOWN SEQUENCE .............................................................................................. 19
3.7.EMERGENCY SHUTDOWN SEQUENCE ...................................................................... 20
4. LOGIC LOOPS/CONTROL DESCRIPTION ................................................................... 21
4.1.LOGIC LOOPS................................................................................................................ 21
4.2.CONTROL DESCRIPTION ............................................................................................. 26
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 3
/ 26
Rev.: 2
1.
INTRODUCTION
For design information on the system, as well as details and functions of each item, refer to
PP10CC-0009-3MAL-MR-ABC-001 STEAM TURBINE VENTS & DRAINS SYSTEM
DESCRIPTION.
PERMANENT
STANDBY
PREPARATION
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 4
/ 26
Rev.: 2
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 5
/ 26
Rev.: 2
2.
SYSTEM DESCRIPTION
Instrument
Service
A115-MAL10-
CL001
A115-MAL10-
CL002
A115-MAL10-
CP001
Setting
Level
Consequences/Actions
L > 47%
HH
L < 17,5%
LL
L > 47%
HH
L < 17,5%
LL
HH
Alarm
T > 362C
HHH
Alarm
Alarm
A115-MAL10-
T > 357C
HH
Alarm
CT001
T > 356C
Open A115-MAL10-AA081
T < 210C
Close A115-MAL10-AA081
T > 362C
HHH
A115-MAL10-
T > 357C
HH
Alarm
CT002
T > 356C
Open A115-MAL10-AA081
T < 210C
Close A115-MAL10-AA081
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 6
/ 26
Rev.: 2
Instrument
Service
Level
Consequences/Actions
L > 47%
HH
Alarm
L > 35%
Open A115-MA20-AA081/2
L < 20%
Close A115-MA20-AA081/2
L < 17,5%
LL
Alarm
L < 15%
LLL
L > 47%
HH
Alarm
L > 35%
Open A115-MA20-AA081/2
L < 20%
Close A115-MA20-AA081/2
L < 17,5%
LL
Alarm
L < 15%
LLL
HH
Alarm
T > 362C
HHH
T > 357C
HH
Alarm
tank Temperature
T > 356C
Open A115-MAL20-AA083
T < 210C
Close A115-MAL20-AA083
T > 362C
HHH
A115-MAL20-
CL001
tank Level
2
A115-MAL20-
CL002
tank Level
A115-MAL20-
CP001
tank Pressure
A115-MAL20CT001
Setting
A115-MAL20-
T > 357C
HH
Alarm
CT002
tank Temperature
T > 356C
Open A115-MAL20-AA083
T < 210C
Close A115-MAL20-AA083
L > 56%
HHH
Trip ST
L > 46%
HH
A115-MAL30-
CL001
L > 44%
L < 20%
L < 17,5%
LL
Alarm
L < 5%
LLL
L > 56%
HHH
Trip ST
L > 46%
HH
A115-MAL20-AA081/2
A115-MAL30-
CL002
L > 44%
L < 20%
L < 17,5%
LL
Alarm
L < 5%
LLL
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 7
/ 26
Rev.: 2
Instrument
Service
Setting
Level
Consequences/Actions
L > 56%
HHH
Trip ST
L > 46%
HH
A115-MAL30-
CL003
L > 44%
L < 20%
L < 17,5%
LL
Alarm
L < 5%
LLL
HH
Alarm
T > 82C
HHH
T > 77C
HH
Alarm
T = 72C
SP
Control SP A115-MAL30-AA101
T > 82C
HHH
T > 77C
HH
Alarm
T = 72C
SP
Control SP A115-MAL30-AA101
T > 70C
HHH
T > 65C
HH
Alarm
A115-MAL30-
CP001
A115-MAL30-
CT001
2
A115-MAL30CT002
A115-MAL30CT003
2
A115-MAL30CT004
Temperature
T = 60C
SP
Control SP A115-MAL30-AA102
T > 70C
HHH
T > 65C
HH
Alarm
T = 60C
SP
Control SP A115-MAL30-AA102
L > 56%
HHH
L > 46%
HH
Temperature
Trip ST
Alarm
A115-MAL40-
L > 44%
CL001
L < 20%
L < 17,5%
LL
Alarm
L < 5%
LLL
L > 56%
HHH
L > 46%
HH
Trip ST
Alarm
A115-MAL40-
L > 44%
CL002
L < 20%
L < 17,5%
LL
Alarm
L < 5%
LLL
L > 56%
HHH
Trip ST
A115-MAL40-
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 8
/ 26
Rev.: 2
Instrument
Service
CL003
Setting
Level
Consequences/Actions
L > 46%
HH
Alarm
L > 44%
L < 20%
L < 17,5%
LL
L < 5%
LLL
HH
Alarm
Alarm
Trip pumps A115-MAL41/2-AP001
A115-MAL40-
CP001
A115-MAL402
CT001
T > 82C
HHH
T > 77C
HH
Alarm
T = 72C
SP
Control SP A115-MAL40-AA101
T > 82C
HHH
T > 77C
HH
Alarm
T = 72C
SP
Control SP A115-MAL40-AA101
T > 70C
HHH
T > 65C
HH
Alarm
Temperature
T = 60C
SP
Control SP A115-MAL40-AA102
T > 70C
HHH
T > 65C
HH
Alarm
Temperature
T = 60C
SP
Control SP A115-MAL40-AA102
HH
A115-MAL40-
CT002
A115-MAL40CT003
2
A115-MAL40CT004
A115-MAL43CP001
LL
Alarm
Alarm (pump change over
requirement)
Terminal Point
Service
System From /
Ref. Document.
To
-
HP Steam Drains
LP Steam Drains
PP10CC-00-LBA-MDD-ABC-
By-pass System
001
PP10CC-00-LBB-MDD-ABC-
By-pass System
001
To HRSG
-
Blowdown drain
sump
PP10CC-A119-8HAN-MDDABC-001
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 9
/ 26
Rev.: 2
Terminal Point
Service
System From /
Ref. Document.
To
-
Attemperation Water
From Auxiliary
PP10CC-00-LBG-MDD-ABC-
Steam System
001
From SEAL
PP10CC-0009-0MAW-MDD-
STEAM SYSTEM
ABC-001
PP10CC-A119-8GHC-MDD-
System
ABC-001
PP10CC-A119-8GHC-MDD-
System
ABC-001
PP10CC-00-2MAG-GDDRCD-002
PP10CC-00-2MAG-GDDRCD-002
2.3. FUNCTIONALITY
The Steam Turbine Vents & Drains System functionality is described in the system
description. See:
PP10CC-0009-3MAL-MR-ABC-001 STEAM TURBINE VENTS AND DRAINS SYSTEM
DESCRIPTION
Signal Description
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 10
/ 26
Rev.: 2
2.5.1.
Measuring instrument
The measuring instruments which belong to this system are the followings:
Equipment/Line
PP10CC-A115-MAL10BB001
PP10CC-A115-MAL10BB001
PP10CC-A115-MAL102
BB001
PP10CC-A115-MAL20BB001
PP10CC-A115-MAL20BB001
PP10CC-A115-MAL202
BB001
PP10CC-A115-MAL30BR001-600-1A1-PP
PP10CC-A115-MAL30BB001
PP10CC-A115-MAL30BB001
Service
Instrument
HRSG Area
LIT
A115-MAL10-CL001
Level
A115-MAL10-CL002
HRSG Area
Atmospheric drain tank
Pressure
PIT
A115-MAL10-CP001
HRSG Area
TIT
A115-MAL10-CT001
Temperature
A115-MAL10-CT002
ST Area Atmospheric
LIT
drain tank
A115-MAL20-CL001
Level
A115-MAL20-CL002
ST Area Atmospheric
drain tank
Pressure
PIT
A115-MAL20-CP001
ST Area Atmospheric
TIT
drain tank
A115-MAL20-CT001
Temperature
A115-MAL20-CT002
High Energy
TIT
Condensate recovery
A115-MAL30-CT001
tank Temperature
A115-MAL30-CT002
High Energy
Condensate recovery
tank Level
High Energy
Condensate recovery
tank Pressure
Selection
Logic
DUAL
SELECT
DUAL
SELECT
DUAL
SELECT
DUAL
SELECT
DUAL
SELECT
LIT
A115-MAL30-CL001
MEDIAN
A115-MAL30-CL002
SELECT
A115-MAL30-CL003
PIT
A115-MAL30-CP001
Notes
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 11
/ 26
Rev.: 2
Equipment/Line
PP10CC-A115-MAL30BR002-100-1A1-PP
PP10CC-A115-MAL40BR001-250-1A1-PP
PP10CC-A115-MAL40BB001
PP10CC-A115-MAL40BB001
PP10CC-A115-MAL40BR002-100-1A1-PP
PP10CC-A115-MAL43BR001-80-1A1-PP
2.5.2.
Service
Instrument
High Energy
TIT
Condensate recovery
A115-MAL30-CT003
A115-MAL30-CT004
Low Energy
TIT
Condensate recovery
A115-MAL40-CT001
tank Temperature
A115-MAL40-CT002
Low Energy
Condensate recovery
tank Level
Low Energy
Condensate recovery
tank Pressure
SELECT
DUAL
SELECT
MEDIAN
A115-MAL40-CL002
SELECT
A115-MAL40-CL003
PIT
A115-MAL40-CP001
Condensate recovery
A115-MAL40-CT003
A115-MAL40-CT004
Notes
DUAL
A115-MAL40-CL001
TIT
Condensate recovery
Logic
LIT
Low Energy
Low Energy
Selection
PIT
A115-MAL43-CP001
DUAL
SELECT
As a general rule, if a signal is out of configured range, an alarm shall be generated in the
control system.
When two or more measurements are available for the same process value, the value used
for interlocking will depend on the selected logic architecture.
In a DUAL SELECT logic architecture, two measures are available, if both are healthy the
average of the two measurements is used. In case of bad quality of one of the
measurements, automatic change-over to the healthy measurement takes place and an
alarm is generated.
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 12
/ 26
Rev.: 2
In a MEDIAN SELECT logic architecture, three measures are available if all of them are
healthy the average of the three measurements is used. In case of bad quality of one of the
measurements, automatic change-over to the other healthy measurements takes place and
an alarm is generated.
The selected logic architecture of each instrument has been identified in the previous table
(see section 2.5.1).
2.5.3.
2.6.1.
Process drivers/actuators
The process actuators which belong to this system are the followings:
Line/Equipment
Service
Actuator
Fail Safe
Notes
Position
PP10CC-A115-MAL10BR011-40-3A3-PP
2
PP10CC-A115-MAL20BR006-100-1A1-PP
PP10CC-A115-MAL202
BR006-100-1A1-PP
PP10CC-A115-MAL20-
Condensate to
HRSG Atmospheric
A115-MAL10-AA081
FO
A115-MAL20-AA081
FC
A115-MAL20-AA082
FC
A115-MAL20-AA083
FO
drain tank
ST Area Atmospheric
drain tank
Drain
ST Area Atmospheric
drain tank
Drain
Condensate to
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 13
/ 26
Rev.: 2
Line/Equipment
Service
Actuator
Fail Safe
Notes
Position
BR011-40-3A3-PP
HRSG Atmospheric
drain tank
High Energy
PP10CC-A115-MAL30-
Condensate recovery
BR003-80-1E2-NI
tank Attemperation
A115-MAL30-AA101
FO
A115-MAL30-AA102
FO
A115-MAL40-AA101
FO
A115-MAL40-AA102
FO
Water
High Energy
PP10CC-A115-MAL30-
Condensate recovery
BR004-50-3C1-NI
tank Water
temperature
Low Energy
PP10CC-A115-MAL40-
Condensate recovery
BR003-50-3C1-NI
tank Attemperation
Water
Low Energy
PP10CC-A115MAL40-
Condensate recovery
BR004-50-3C1-NI
tank Water
temperature
2.6.2.
When redundant actuators are available, at least one of the followings strategies shall be
configured:
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 14
/ 26
Rev.: 2
The fail safe position of each actuator has been identified in the previous table (see 2.6.1).
2.7.1.
2.7.2.
As a general rule, the system will operate in automatic mode, following not only required
sequences and settings, also taking into account required protections over the operation in
the control system. All functional groups could operate in one of the following modes:
Automatic mode
In auto mode the functional group will follow the control strategies configured in the control
system.
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 15
/ 26
Rev.: 2
Manual mode
In manual mode the functional group will check required sequences, settings and
protections for system operation depending on control strategy, but in this case some
process actuators could be selected to be operated according to operators decision.
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 16
/ 26
Rev.: 2
3.
OPERATION MODES
The system operation modes are the followings:
Cold start-up: cover the initial filling and the initial preparation (system ready to start).
Hot start-up: cover all required sequences up to the moment the system is in operation.
Normal operation.
Shutdown: cover all required sequences up to the moment the system has been
stopped.
Emergency shutdown.
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 17
/ 26
Rev.: 2
Step 01: HRSG Area Atmospheric drain tank attemperation valve (A115-MAL10-AA081)
to AUTO MODE.
Step 02: ST Area Atmospheric drain tank drain valves (A115-MAL20-AA081 & 082) and
2
the valve will open to reduce the temperature inside the tank up to the value of 210C when
the valve will close. In this way, the temperature inside the tank will be controlled. In case
the temperature exceeds the value of 357C an alarm will be generated in DCS but if the
temperature is higher than 362C the valve will be forced to open in order to protect the
tank against high temperatures.
valve will close. In this way, the temperature inside the tank will be controlled. In case the
temperature exceeds the value of 357C an alarm will be generated in DCS but if the
temperature is higher than 362C the valve will be forced to open in order to protect the
tank against high temperatures.
Similarly, the on-off valves A115-MAL20-AA081 and A115-MAL20-AA082 will control the
level inside the ST Area Atmospheric drain. When the level is higher than 35% these
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 18
/ 26
Rev.: 2
2
valves will open to evacuate the water inside the tank up to the value of 20% when they will
close. In this way, the level inside the tank will be controlled. In case the level exceeds the
value of 5% an alarm will be generated in DCS but valves wont be forced to open. On the
contrary, these valves will be forced to close if the level in the high energy vacuum tank is
very high or if the level in the tank is very low.
It is important to note that this tank has an overflow line in order to evacuate the water to
the drain system if the valve doesnt open.
The control valve A115-MAL30-AA102 will control the water temperature in the High
Energy Condensate Recovery drain tank, to avoid pumps cavitation, introducing cool water
from demin water system. In case of exceeding the temperature of 70C the valve will be
forced to open.
At the same time, High Energy Condensate Recovery drain tank level will be controlled by
selected pump (A115-MAL41-AP001 or A115-MAL42-AP001) which will start when the
level is higher than 44% to evacuate the water inside the tank up to the 20% level when the
pump will stop. In this way, the level inside the tank will be controlled. In case the level
exceeds the value of 46% an alarm will be generated in DCS, but if the level exceeds the
value of 56% the DCS will trip the ST.
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 19
/ 26
Rev.: 2
The control valve A115-MAL40-AA102 will control the water temperature in the Low Energy
Condensate Recovery drain tank, to avoid pumps cavitation, introducing cool water from
demin water system. In case of exceeding the temperature of 70C the valve will be forced
to open.
2
At the same time, Low Energy Condensate Recovery drain tank level will be controlled by
selected pump (A115-MAL41-AP001 or A115-MAL42-AP001) which will start when the
level is higher than 44% to evacuate the water inside the tank up to the 20% level when the
pump will stop. In this way, the level inside the tank will be controlled. In case the level
exceeds the value of 46% an alarm will be generated in DCS, but if the level exceeds the
value of 56% the DCS will trip the ST.
Interlock
For process interlocks see section 2.1.
Alarms
For process alarms see section 2.1.
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 20
/ 26
Rev.: 2
Step 02: High Energy Condensate recovery tank attemperation water valve (A115MAL30-AA101) and temperature valve (A115-MAL30-AA102) CLOSE and to MANUAL
2
MODE.
Step 03: ST Area Atmospheric drain tank drain valves (A115-MAL20-AA081 & 082) and
attemperation valve (A115-MAL20-AA083) CLOSE and to MANUAL MODE.
Step 04: HRSG Area Atmospheric drain tank attemperation valve (A115-MAL10-AA081)
CLOSE and to MANUAL MODE.
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 21
/ 26
Rev.: 2
4.
BB001
Temperature Control
Instrument TAG:
PV
Temperature
A115-MAL10-CT001
A115-MAL10-CT002
SP
Permissives
Instrument TAG:
Override
A115-MAL10-CT001
A115-MAL10-CT002
Actuator
A115-MAL10-AA081
Instrument TAG:
PV
Temperature
A115-MAL20-CT001
A115-MAL20-CT002
SP
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 22
/ 26
Rev.: 2
Loop
Permissives
Instrument TAG:
Override
A115-MAL20-CT001
A115-MAL20-CT002
Actuator
Loop
A115-MAL20-AA083
Instrument TAG:
PV
Level
A115-MAL20-CL001
A115-MAL20-CL002
SP
Permissives
Instrument TAG:
Actuator
Loop
PV
A115-MAL30-CL001
A115-MAL30-CL002
A115-MAL30-CL003
A115-MAL20-CL001
A115-MAL20-CL002
A115-MAL20-AA081
Instrument TAG:
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 23
/ 26
Rev.: 2
Loop
Level Control
A115-MAL20-CL001
A115-MAL20-CL002
SP
Permissives
Instrument TAG:
Override
Actuator
A115-MAL30-CL001
A115-MAL30-CL002
A115-MAL30-CL003
A115-MAL20-CL001
A115-MAL20-CL002
A115-MAL20-AA082
MAL30-BB001
Temperature Control
Instrument TAG:
PV
Temperature
A115-MAL30-CT001
A115-MAL30-CT002
SP
Permissives
Override
2
Actuator
T = 72C
A115-MAL30-CT001
A115-MAL30-CT002
A115-MAL30-AA101
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 24
/ 26
Rev.: 2
A115-MAL30-BB001
Temperature
A115-MAL30-CT003
A115-MAL30-CT004
SP
Permissives
Override
2
Actuator
T = 60C
A115-MAL30-CT003
A115-MAL30-CT004
A115-MAL30-AA102
A115-MAL40-BB001
Temperature Control
Instrument TAG:
PV
Temperature
A115-MAL40-CT001
A115-MAL40-CT002
SP
Permissives
Override
2
Actuator
T = 72C
A115-MAL40-CT001
A115-MAL40-CT002
A115-MAL40-AA101
A115-MAL40-BB001
Temperature
Instrument TAG:
A115-MAL40-CT003
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 25
/ 26
Rev.: 2
A115-MAL40-BB001
Override
2
Actuator
T = 60C
A115-MAL40-CT003
A115-MAL40-CT004
A115-MAL40-AA102
Level
A115-MAL30-CL003
OR
A115-MAL40-CL001
A115-MAL40-CL002
A115-MAL40-CL003
SP
Permissives
A115-MAL30-CL001
A115-MAL30-CL002
A115-MAL30-CL003
Interlock
OR
A115-MAL40-CL001
A115-MAL40-CL002
A115-MAL40-CL003
Actuator
Electric Pump
A115-MAL41-AP001
A115-MAL42-AP001
Document Code
Date
PP10CC-0009-6MAL-YR-ABC-001
10/07/13
Page 26
/ 26
Rev.: 2
Once the HRSG System is in operation, the Master Sequence Following Controller
(M.S.F.C) will send an automatic command to Steam Turbine Vents and Drains Functional
Group (STDV GROUP) to set in AUTO MODE this system. The STVD GROUP will send
an automatic command to each pump, to each control valve and to each pneumatic on-off
valve. After being in AUTO MODE, drain pumps will start or stop according to process
conditions. Similarly pneumatic on-off valves will be open or close if required.
In AUTO MODE, on-off valves, control valves and pumps will operate as described in
section 3.4 NORMAL OPERATION.
On the contrary, during the shutdown sequence, the M.S.F.C will set the system in OFF
sending a command to the functional group (STVD GROUP) which will stop the pumps (if
running) and close all valves (if open). After that all devices will be set in MANUAL mode in
2
XV-04
HI_LO_MON
CONDENSATE
LP STEAM DRAIN
HP STEAM DRAIN
TT
DUALSEL
LP STEAM DRAIN
TT
HP STEAM DRAIN
HP STEAM DRAIN
LP STEAM DRAIN
LP STEAM DRAIN
HP STEAM DRAIN
PT
HRSG AREA
ATMOSPHERIC DRAIN
TANK
A115-MAL10-BB001
LT
LP STEAM DRAIN
DUALSEL
LT
HRSG BLOWDOWN
DRAIN SUMP
SH: 1/4
HI_LO_MON
GROUP
STVD
HP STEAM DRAIN
HP STEAM DRAIN
HP STEAM BY-PASS 1
DRAIN
XV-04
CONDENSATE
AUTO / MANUAL
M.S.F.C
START / STOP
AUTO / MANUAL
TO ST VENTS & DRAINS
TT
DUALSEL
SH: 3/4
TT
HP STEAM BY-PASS 2
DRAIN
SH: 4/4
PT
ST AREA
ATMOSPHERIC DRAIN
TANK
A115-MAL20-BB001
LT
DUALSEL
HP STEAM DRAIN
LT
HP STEAM DRAIN
HI_LO_MON
HP STEAM DRAIN
TO ST VENTS & DRAINS
HP STEAM BY-PASS 3
DRAIN
XV-01
HP STEAM BY-PASS 4
DRAIN
HP STEAM BY-PASS 1
DRAIN
SH: 3/4
XV-01
HIGH ENERGY
VACUUM TANK
HP STEAM BY-PASS 2
DRAIN
SH: 3/4
HP STEAM BY-PASS 3
DRAIN
HP STEAM BY-PASS 4
DRAIN
ST MSCV-1 BEFORE
SEAT DRAIN TAP
SH: 2/4
ACC
DUCT
STEAM TURBINE
TRIP
TT
AUTO / MANUAL
CV-01
DUALSEL
SH: 2/4
TT
DEMIN WATER
SUPPLY
PT
ST ATMOSPHERIC
DRAIN TANK
4
SEAL S. HEADER
DRAIN
ST LINE
LOW P. DRAIN
HHH
HH
LT
MEDSEL
HI_LO_MON
SEAT DRAIN
TAP
LT
LLL
SEAL STEAM
HEADER DUMP
HIGH ENERGY
CONDENSATE
RECOVERY DRAIN TANK
MAL30-BB001
SH: 2/4
LT
CV-01
TT
DUALSEL
TO DRAIN
PUMPS
TT
HI_LO_MON
TRIP
START / STOP
SH: 4/4
7
SH: 4/4
SH: 4/4
SH: 3/4
ACC
DUCT
STEAM TURBINE
TRIP
TT
AUTO / MANUAL
CV-01
DUALSEL
SH: 2/4
TT
DEMIN WATER
SUPPLY
PT
SEAL S.
HEADER DRAIN
LOW ENERGY
CONDENSATE
RECOVERY DRAIN TANK
MAL40-BB001
SEAL S.
HEADER DRAIN
SEAL S.
HEADER DRAIN
AFTER ACV
DRAIN
BEFORE ACV
DRAIN
LT
HI_LO_MON
MEDSEL
LLL
HHH
AUTO
CHANGE OVER
START / STOP
CV-01
LT
LL
LT
LVMP-03
HI_LO_MON
PT
TO ST VENTS & DRAINS
5
SH: 3/4
FROM HIGH
ENERGY TANK
7
SH: 4/4
TT
DUALSEL
TT
LVMP-03
CONDENSATE
RECOVERY
TANK
HI_LO_MON
START / STOP
TRIP
SH: 3/4
SH: 4/4