PROJECT:

PP10 CCGT POWER STATION


CONTRACT NO: 31121111/00
CLIENT

CONSULTANT:

CONTRACTOR:

DOCUMENT TITLE:

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION


COMPANY/ORIGINATOR:

PROJECT DOCUMENT NUMBER:

ARABIAN BEMCO
CONTRACTING COMPANY
DISTRIBUTION CODE:

PP10CC-0009-6MAL-YR-ABC-001

SHEET NO.

I&C

REV.

1 OF 26

SIZE

SCALE:

A4

N.T.S

FILE NAME:

PP10CC-0009-6MAL-YR-ABC-001-REV 2 ST VENTS&DRAINS FUNCTIONAL


DESCRIPTION

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 2

/ 26

Rev.: 2

INDEX OF CONTENTS

1. INTRODUCTION............................................................................................................... 3
1.1.OBJECTIVE OF THE DOCUMENT .................................................................................. 3
1.2.SCOPE OF THE DOCUMENT.......................................................................................... 3
1.3.REFERENCE DOCUMENTATION ................................................................................... 3
2. SYSTEM DESCRIPTION .................................................................................................. 5
2.1.MAIN EQUIPMENT, PERMISSIVES AND INTERLOCKS ................................................ 5
2.2.MECHANICAL BATTERY LIMITS .................................................................................... 8
2.3.FUNCTIONALITY.............................................................................................................. 9
2.4.CONTROL INTERFACES WITH OTHER SYSTEMS ....................................................... 9
2.5.SIGNALS MONITORING ................................................................................................ 10
2.5.1. Measuring instrument..................................................................................... 10
2.5.2. Selection logic architecture ........................................................................... 11
2.5.3. Bad quality concept ........................................................................................ 12
2.6.PROCESS ACTUATORS ............................................................................................... 12
2.6.1. Process drivers/actuators .............................................................................. 12
2.6.2. Drivers/Actuators Fault Tolerance ................................................................ 13
2.7.FUNCTIONAL GROUPS................................................................................................. 14
2.7.1. Number of Functional Groups ....................................................................... 14
2.7.2. Functional Groups Operation Modes ............................................................ 14
2.8.SYSTEM CONTROL LOCATION ................................................................................... 15
3. OPERATION MODES..................................................................................................... 16
3.1.POSITION IN THE PLANT GENERAL START-UP SEQUENCE ................................... 16
3.2.CRITERION FOR SYSTEM START-UP ......................................................................... 16
3.3.START-UP SEQUENCE ................................................................................................. 16
3.4.NORMAL OPERATION................................................................................................... 17
3.5.POSITION IN THE PLANT GENERAL SHUTDOWN SEQUENCE ................................ 19
3.6.SHUTDOWN SEQUENCE .............................................................................................. 19
3.7.EMERGENCY SHUTDOWN SEQUENCE ...................................................................... 20
4. LOGIC LOOPS/CONTROL DESCRIPTION ................................................................... 21
4.1.LOGIC LOOPS................................................................................................................ 21
4.2.CONTROL DESCRIPTION ............................................................................................. 26

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13
Page 3

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

/ 26

Rev.: 2

1.

INTRODUCTION

1.1. OBJECTIVE OF THE DOCUMENT


The objective of the document is to provide the functional description of the VENTS &
DRAINS SYSTEM of the project.

For design information on the system, as well as details and functions of each item, refer to
PP10CC-0009-3MAL-MR-ABC-001 STEAM TURBINE VENTS & DRAINS SYSTEM
DESCRIPTION.

1.2. SCOPE OF THE DOCUMENT


The scope of the document is to describe the followings topics:
System description
System operation
Control loops

1.3. REFERENCE DOCUMENTATION


PP10CC-0009-3MAL-MDD-ABC-001 P&ID STEAM TURBINE VENTS & DRAINS
SYSTEM
PP10CC-0009-3MAL-MR-ABC-001 STEAM TURBINE VENTS & DRAINS SYSTEM
DESCRIPTION
PP10CC-0009-6MAL-YDY-ABC-001 STEAM TURBINE VENTS & DRAINS LOGIC
DIAGRAMS
PP10CC-00-6Y-YR-ABC-001 CCPP OPERATION PHILOSOPHY
PP10CC-0009-6Y-YDZ-ABC-001 CONTROL TYPICAL DEVICES
PP10CC-0009-6Y-YLI-ABC-002 DEVICE DEFINITION CONCEPT
PP10CC-0009-6Y-YDY-ABC-001 MASTER LOGIC DIAGRAMS
PP10CC-0009-6Y-YDY-ABC-004
SEQUENCE

PERMANENT

STANDBY

PREPARATION

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 4

/ 26

Rev.: 2

PP10CC-0009-6Y-YDY-ABC-002 CC SIMULTANEOUS START UP SEQUENCE


PP10CC-0009-6Y-YDY-ABC-005 CC SEQUENTIAL START UP SEQUENCE
PP10CC-0009-6Y-YDY-ABC-003 NORMAL SHUT DOWN SEQUENCE

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13
Page 5

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

/ 26

Rev.: 2

2.

SYSTEM DESCRIPTION

2.1. MAIN EQUIPMENT, PERMISSIVES AND INTERLOCKS


The main equipments which belong to this system are four drain tanks and its associated
pumps. The TAGs of these tanks are the followings:
HRSG Area Atmospheric drain tank: PP10CC-A115-MAL10-BB001.
ST Area Atmospheric drain tank: PP10CC-A115-MAL20-BB001.
High Energy Condensate recovery drain tank: PP10CC-A115-MAL30-BB001.
Low Energy Condensate recovery drain tank: PP10CC-A115-MAL40-BB001.

The TAGs of these drain pumps are the followings:


High & Low Energy Condensate recovery drains tank pumps: PP10CC-A115-MAL41AP001 and PP10CC-A115-MAL42-AP001.

For further information see system description PP10CC-0009-3MAL-MR-ABC-001 STEAM


TURBINE VENTS AND DRAINS SYSTEM DESCRIPTION.
The system has the following permissive (start condition) and interlocks:

Instrument

Service

A115-MAL10-

HRSG Area Atmospheric

CL001

drain tank Level

A115-MAL10-

HRSG Area Atmospheric

CL002

drain tank Level

A115-MAL10-

HRSG Area Atmospheric

CP001

drain tank Pressure

Setting

Level

Consequences/Actions

L > 47%

HH

L < 17,5%

LL

L > 47%

HH

L < 17,5%

LL

P > 0,2 barg

HH

Alarm

T > 362C

HHH

Override Open A115-MAL10-AA081

Alarm

Alarm

A115-MAL10-

HRSG Area Atmospheric

T > 357C

HH

Alarm

CT001

drain tank Temperature

T > 356C

Open A115-MAL10-AA081

T < 210C

Close A115-MAL10-AA081

T > 362C

HHH

Override Open A115-MAL10-AA081

A115-MAL10-

HRSG Area Atmospheric

T > 357C

HH

Alarm

CT002

drain tank Temperature

T > 356C

Open A115-MAL10-AA081

T < 210C

Close A115-MAL10-AA081

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 6

/ 26

Rev.: 2

Instrument

Service

Level

Consequences/Actions

L > 47%

HH

Alarm

L > 35%

Open A115-MA20-AA081/2

L < 20%

Close A115-MA20-AA081/2

L < 17,5%

LL

Alarm

L < 15%

LLL

Override close A115-MA20-AA081/2

L > 47%

HH

Alarm

L > 35%

Open A115-MA20-AA081/2

L < 20%

Close A115-MA20-AA081/2

L < 17,5%

LL

Alarm

L < 15%

LLL

Override close A115-MA20-AA081/2

P > 0,2 barg

HH

Alarm

T > 362C

HHH

Override Open A115-MAL20-AA083

ST Area Atmospheric drain

T > 357C

HH

Alarm

tank Temperature

T > 356C

Open A115-MAL20-AA083

T < 210C

Close A115-MAL20-AA083

T > 362C

HHH

Override Open A115-MAL20-AA083

A115-MAL20-

ST Area Atmospheric drain

CL001

tank Level

2
A115-MAL20-

ST Area Atmospheric drain

CL002

tank Level

A115-MAL20-

ST Area Atmospheric drain

CP001

tank Pressure

A115-MAL20CT001

Setting

A115-MAL20-

ST Area Atmospheric drain

T > 357C

HH

Alarm

CT002

tank Temperature

T > 356C

Open A115-MAL20-AA083

T < 210C

Close A115-MAL20-AA083

L > 56%

HHH

Trip ST

L > 46%

HH

Alarm & Override Close


A115-MAL20-AA081/2

A115-MAL30-

High Energy Condensate

CL001

recovery tank Level

L > 44%

L < 20%

Stop pumps A115-MAL41/2-AP001

L < 17,5%

LL

Alarm

L < 5%

LLL

Trip pumps A115-MAL41/2-AP001

L > 56%

HHH

Trip ST

L > 46%

HH

Alarm & Override Close

Start pumps A115-MAL41/2-AP001

A115-MAL20-AA081/2

A115-MAL30-

High Energy Condensate

CL002

recovery tank Level

L > 44%

L < 20%

Stop pumps A115-MAL41/2-AP001

L < 17,5%

LL

Alarm

L < 5%

LLL

Trip pumps A115-MAL41/2-AP001

Start pumps A115-MAL41/2-AP001

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 7

/ 26

Rev.: 2

Instrument

Service

Setting

Level

Consequences/Actions

L > 56%

HHH

Trip ST

L > 46%

HH

Alarm & Override Close


A115-MAL20-AA081

A115-MAL30-

High Energy Condensate

CL003

recovery tank Level

L > 44%

L < 20%

Stop pumps A115-MAL41/2-AP001

L < 17,5%

LL

Alarm

L < 5%

LLL

Trip pumps A115-MAL41/2-AP001

P > 0,8 bara

HH

Alarm

T > 82C

HHH

Override Open A115-MAL30-AA101

T > 77C

HH

Alarm

T = 72C

SP

Control SP A115-MAL30-AA101

High Energy Condensate

T > 82C

HHH

Override Open A115-MAL30-AA101

recovery tank Temperature

T > 77C

HH

Alarm

T = 72C

SP

Control SP A115-MAL30-AA101

High Energy Condensate

T > 70C

HHH

Override Open A115-MAL30-AA102

recovery tank water

T > 65C

HH

Alarm

A115-MAL30-

High Energy Condensate

CP001

recovery tank Pressure

A115-MAL30-

High Energy Condensate

CT001

recovery tank Temperature

2
A115-MAL30CT002

A115-MAL30CT003
2
A115-MAL30CT004

Start pumps A115-MAL41/2-AP001

Temperature

T = 60C

SP

Control SP A115-MAL30-AA102

High Energy Condensate

T > 70C

HHH

Override Open A115-MAL30-AA102

recovery tank water

T > 65C

HH

Alarm

T = 60C

SP

Control SP A115-MAL30-AA102

L > 56%

HHH

L > 46%

HH

Temperature

Trip ST
Alarm

A115-MAL40-

Low Energy Condensate

L > 44%

Start pumps A115-MAL41/2-AP001

CL001

recovery tank Level

L < 20%

Stop pumps A115-MAL41/2-AP001

L < 17,5%

LL

Alarm

L < 5%

LLL

Trip pumps A115-MAL41/2-AP001

L > 56%

HHH

L > 46%

HH

Trip ST
Alarm

A115-MAL40-

Low Energy Condensate

L > 44%

Start pumps A115-MAL41/2-AP001

CL002

recovery tank Level

L < 20%

Stop pumps A115-MAL41/2-AP001

L < 17,5%

LL

Alarm

L < 5%

LLL

Trip pumps A115-MAL41/2-AP001

L > 56%

HHH

Trip ST

A115-MAL40-

Low Energy Condensate

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 8

/ 26

Rev.: 2

Instrument

Service

CL003

recovery tank Level

Setting

Level

Consequences/Actions

L > 46%

HH

Alarm

L > 44%

Start pumps A115-MAL41/2-AP001

L < 20%

Stop pumps A115-MAL41/2-AP001

L < 17,5%

LL

L < 5%

LLL

P > 0,8 bara

HH

Alarm

Alarm
Trip pumps A115-MAL41/2-AP001

A115-MAL40-

Low Energy Condensate

CP001

recovery tank Pressure

A115-MAL402

CT001

Low Energy Condensate

T > 82C

HHH

Override Open A115-MAL40-AA101

recovery tank Temperature

T > 77C

HH

Alarm

T = 72C

SP

Control SP A115-MAL40-AA101

T > 82C

HHH

Override Open A115-MAL40-AA101

T > 77C

HH

Alarm

T = 72C

SP

Control SP A115-MAL40-AA101

Low Energy Condensate

T > 70C

HHH

Override Open A115-MAL40-AA102

recovery tank water

T > 65C

HH

Alarm

Temperature

T = 60C

SP

Control SP A115-MAL40-AA102

Low Energy Condensate

T > 70C

HHH

Override Open A115-MAL40-AA102

recovery tank water

T > 65C

HH

Alarm

Temperature

T = 60C

SP

Control SP A115-MAL40-AA102

P > 2,4 barg

HH

A115-MAL40-

Low Energy Condensate

CT002

recovery tank Temperature

A115-MAL40CT003
2
A115-MAL40CT004

A115-MAL43CP001

Low Energy Condensate


recovery drain pumps
pressure

P < 1,2 barg

LL

Alarm
Alarm (pump change over
requirement)

2.2. MECHANICAL BATTERY LIMITS

Terminal Point

Service

System From /

Ref. Document.

To
-

HP Steam Drains

LP Steam Drains

From HP Steam &

PP10CC-00-LBA-MDD-ABC-

By-pass System

001

From LP Steam &

PP10CC-00-LBB-MDD-ABC-

By-pass System

001

To HRSG
-

HRSG Area tank drains

Blowdown drain
sump

PP10CC-A119-8HAN-MDDABC-001

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13
Page 9

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

/ 26

Rev.: 2

Terminal Point

Service

System From /

Ref. Document.

To
-

Auxiliary Steam Drains

ST header dump drains

Attemperation Water

Exhaust hood Drains

High Energy Condensate

Recovery Tank Steam

Steam Turbine Vacuum Tank


Drains

From Auxiliary

PP10CC-00-LBG-MDD-ABC-

Steam System

001

From SEAL

PP10CC-0009-0MAW-MDD-

STEAM SYSTEM

ABC-001

From Demin Water

PP10CC-A119-8GHC-MDD-

System

ABC-001

From Demin Water

PP10CC-A119-8GHC-MDD-

System

ABC-001

To ACC Steam &


Condensate
System
To ACC Steam &
Condensate
System

PP10CC-00-2MAG-GDDRCD-002

PP10CC-00-2MAG-GDDRCD-002

2.3. FUNCTIONALITY
The Steam Turbine Vents & Drains System functionality is described in the system
description. See:
PP10CC-0009-3MAL-MR-ABC-001 STEAM TURBINE VENTS AND DRAINS SYSTEM
DESCRIPTION

2.4. CONTROL INTERFACES WITH OTHER SYSTEMS


System control interfaces with other systems are:
From (Origin of the signal)

Signal Description

To (Destination of the signal)

Steam Turbine Trip

Steam Turbine Control system

STEAM TURBINE VENTS &


DRAINS SYSTEM
PP10CC-0009-3MAL-MDDABC-001

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13
Page 10

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

/ 26

Rev.: 2

2.5. SIGNALS MONITORING

2.5.1.

Measuring instrument

The measuring instruments which belong to this system are the followings:

Equipment/Line

PP10CC-A115-MAL10BB001

PP10CC-A115-MAL10BB001

PP10CC-A115-MAL102

BB001

PP10CC-A115-MAL20BB001

PP10CC-A115-MAL20BB001

PP10CC-A115-MAL202

BB001

PP10CC-A115-MAL30BR001-600-1A1-PP

PP10CC-A115-MAL30BB001

PP10CC-A115-MAL30BB001

Service

Instrument

HRSG Area

LIT

Atmospheric drain tank

A115-MAL10-CL001

Level

A115-MAL10-CL002

HRSG Area
Atmospheric drain tank
Pressure

PIT
A115-MAL10-CP001

HRSG Area

TIT

Atmospheric drain tank

A115-MAL10-CT001

Temperature

A115-MAL10-CT002

ST Area Atmospheric

LIT

drain tank

A115-MAL20-CL001

Level

A115-MAL20-CL002

ST Area Atmospheric
drain tank
Pressure

PIT
A115-MAL20-CP001

ST Area Atmospheric

TIT

drain tank

A115-MAL20-CT001

Temperature

A115-MAL20-CT002

High Energy

TIT

Condensate recovery

A115-MAL30-CT001

tank Temperature

A115-MAL30-CT002

High Energy
Condensate recovery
tank Level
High Energy
Condensate recovery
tank Pressure

Selection
Logic
DUAL
SELECT

DUAL
SELECT

DUAL
SELECT

DUAL
SELECT

DUAL
SELECT

LIT
A115-MAL30-CL001

MEDIAN

A115-MAL30-CL002

SELECT

A115-MAL30-CL003
PIT
A115-MAL30-CP001

Notes

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13
Page 11

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

/ 26

Rev.: 2

Equipment/Line

PP10CC-A115-MAL30BR002-100-1A1-PP

PP10CC-A115-MAL40BR001-250-1A1-PP

PP10CC-A115-MAL40BB001

PP10CC-A115-MAL40BB001

PP10CC-A115-MAL40BR002-100-1A1-PP

PP10CC-A115-MAL43BR001-80-1A1-PP

2.5.2.

Service

Instrument

High Energy

TIT

Condensate recovery

A115-MAL30-CT003

tank water Temperature

A115-MAL30-CT004

Low Energy

TIT

Condensate recovery

A115-MAL40-CT001

tank Temperature

A115-MAL40-CT002

Low Energy
Condensate recovery
tank Level
Low Energy
Condensate recovery
tank Pressure

SELECT

DUAL
SELECT

MEDIAN

A115-MAL40-CL002

SELECT

A115-MAL40-CL003
PIT
A115-MAL40-CP001

Condensate recovery

A115-MAL40-CT003

tank water Temperature

A115-MAL40-CT004

drain pumps pressure

Notes

DUAL

A115-MAL40-CL001

TIT

Condensate recovery

Logic

LIT

Low Energy

Low Energy

Selection

PIT
A115-MAL43-CP001

DUAL
SELECT

Selection logic architecture

As a general rule, if a signal is out of configured range, an alarm shall be generated in the
control system.

When two or more measurements are available for the same process value, the value used
for interlocking will depend on the selected logic architecture.

In a DUAL SELECT logic architecture, two measures are available, if both are healthy the
average of the two measurements is used. In case of bad quality of one of the
measurements, automatic change-over to the healthy measurement takes place and an
alarm is generated.

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13
Page 12

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

/ 26

Rev.: 2

In a MEDIAN SELECT logic architecture, three measures are available if all of them are
healthy the average of the three measurements is used. In case of bad quality of one of the
measurements, automatic change-over to the other healthy measurements takes place and
an alarm is generated.

The selected logic architecture of each instrument has been identified in the previous table
(see section 2.5.1).

2.5.3.

Bad quality concept

In case of bad quality of one of the redundant measurements, automatic change-over to


the healthy measurement will take place and an alarm will be generated. Bad quality
means that the signal is out of range < 4 or > 20 mA.

2.6. PROCESS ACTUATORS

2.6.1.

Process drivers/actuators

The process actuators which belong to this system are the followings:

Line/Equipment

Service

Actuator

Fail Safe

Notes

Position
PP10CC-A115-MAL10BR011-40-3A3-PP
2
PP10CC-A115-MAL20BR006-100-1A1-PP

PP10CC-A115-MAL202

BR006-100-1A1-PP
PP10CC-A115-MAL20-

Condensate to
HRSG Atmospheric

A115-MAL10-AA081

FO

A115-MAL20-AA081

FC

A115-MAL20-AA082

FC

A115-MAL20-AA083

FO

drain tank
ST Area Atmospheric
drain tank
Drain
ST Area Atmospheric
drain tank
Drain
Condensate to

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13
Page 13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

/ 26

Rev.: 2

Line/Equipment

Service

Actuator

Fail Safe

Notes

Position
BR011-40-3A3-PP

HRSG Atmospheric
drain tank
High Energy

PP10CC-A115-MAL30-

Condensate recovery

BR003-80-1E2-NI

tank Attemperation

A115-MAL30-AA101

FO

A115-MAL30-AA102

FO

A115-MAL40-AA101

FO

A115-MAL40-AA102

FO

Water
High Energy
PP10CC-A115-MAL30-

Condensate recovery

BR004-50-3C1-NI

tank Water
temperature
Low Energy

PP10CC-A115-MAL40-

Condensate recovery

BR003-50-3C1-NI

tank Attemperation
Water
Low Energy

PP10CC-A115MAL40-

Condensate recovery

BR004-50-3C1-NI

tank Water
temperature

1.- Valve pneumatically actuated.

2.6.2.

Drivers/Actuators Fault Tolerance

When redundant actuators are available, at least one of the followings strategies shall be
configured:

Automatic pump selection


If there is a fault in one of the selected pumps which are in operation, the control system
will start automatically another pump in order to keep the required demand of pumps. The
required demand could be one of two pumps running. If it is not possible to keep the
required demand, the control system will generate an alarm.

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 14

/ 26

Rev.: 2

Maximum waiting time


When it is required to start an actuator or to change its position, the control system shall
monitor the maximum admitted time to finish its maneuver. If this time is exceeded, the
control system will generate an alarm.

- Drain pumps expected starting time is 15 seconds (to be confirmed)

Fail safe position


It will be considered the Fail Safe Position the one that the device will go to in case of
control signal or air supply failure.

The fail safe position of each actuator has been identified in the previous table (see 2.6.1).

2.7. FUNCTIONAL GROUPS

2.7.1.

Number of Functional Groups

There will be the following functional groups:


STEAM TURBINE VENTS & DRAINS: STVD

2.7.2.

Functional Groups Operation Modes

As a general rule, the system will operate in automatic mode, following not only required
sequences and settings, also taking into account required protections over the operation in
the control system. All functional groups could operate in one of the following modes:

Automatic mode
In auto mode the functional group will follow the control strategies configured in the control
system.

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 15

/ 26

Rev.: 2

Manual mode
In manual mode the functional group will check required sequences, settings and
protections for system operation depending on control strategy, but in this case some
process actuators could be selected to be operated according to operators decision.

2.8. SYSTEM CONTROL LOCATION


The DCS controller location for this system is the STG Control Compartment.

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 16

/ 26

Rev.: 2

3.

OPERATION MODES
The system operation modes are the followings:
Cold start-up: cover the initial filling and the initial preparation (system ready to start).
Hot start-up: cover all required sequences up to the moment the system is in operation.
Normal operation.
Shutdown: cover all required sequences up to the moment the system has been
stopped.
Emergency shutdown.

3.1. POSITION IN THE PLANT GENERAL START-UP SEQUENCE


This system belongs to operation systems and it will be set in operation following the steps
described in the selected start-up sequence. There are two start-up sequences:
Combined Cycle Simultaneous Start-Up Sequence: PP10CC-0009-6Y-YDY-ABC-002
Combined Cycle Sequential Start-Up Sequence: PP10CC-0009-6Y-YDY-ABC-005

3.2. CRITERION FOR SYSTEM START-UP


From the plant general start-up sequence it will be required to start-up this system under
the following requirements:
Compressed Air System in operation
Condensate System in operation
Demin Water System in operation
ACC System in operation.

3.3. START-UP SEQUENCE


The start-up sequence of the system will follow the following steps:

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 17

/ 26

Rev.: 2

Step 01: HRSG Area Atmospheric drain tank attemperation valve (A115-MAL10-AA081)
to AUTO MODE.
Step 02: ST Area Atmospheric drain tank drain valves (A115-MAL20-AA081 & 082) and
2

attemperation valve (A115-MAL20-AA083) to AUTO MODE.


Step 03: High Energy Condensate recovery tank attemperation water valve (A115MAL30-AA101) and temperature valve (A115-MAL30-AA102) to AUTO MODE.
Step 04: Low Energy Condensate recovery tank attemperation water valve (A115MAL40-AA101), temperature valve (A115-MAL40-AA102) and drain pumps (A115MAL41-AP001 & A115-MAL42-AP001) to AUTO MODE.

3.4. NORMAL OPERATION

HRSG Area Atmospheric drain tank A115-MAL10-BB001


In normal operation, the on-off valve A115-MAL10-AA081 will control the temperature
inside the HRSG Area Atmospheric drain tank. When the temperature is higher than 356C
2

the valve will open to reduce the temperature inside the tank up to the value of 210C when
the valve will close. In this way, the temperature inside the tank will be controlled. In case
the temperature exceeds the value of 357C an alarm will be generated in DCS but if the
temperature is higher than 362C the valve will be forced to open in order to protect the
tank against high temperatures.

ST Area Atmospheric drain tank A115-MAL20-BB001


In normal operation, the on-off valve A115-MAL20-AA083 will control the temperature
inside the ST Area Atmospheric drain tank. When the temperature is higher than 356C the
valve will open to reduce the temperature inside the tank up to the value of 210C when the
2

valve will close. In this way, the temperature inside the tank will be controlled. In case the
temperature exceeds the value of 357C an alarm will be generated in DCS but if the
temperature is higher than 362C the valve will be forced to open in order to protect the
tank against high temperatures.

Similarly, the on-off valves A115-MAL20-AA081 and A115-MAL20-AA082 will control the
level inside the ST Area Atmospheric drain. When the level is higher than 35% these

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 18

/ 26

Rev.: 2
2

valves will open to evacuate the water inside the tank up to the value of 20% when they will
close. In this way, the level inside the tank will be controlled. In case the level exceeds the
value of 5% an alarm will be generated in DCS but valves wont be forced to open. On the
contrary, these valves will be forced to close if the level in the high energy vacuum tank is
very high or if the level in the tank is very low.

It is important to note that this tank has an overflow line in order to evacuate the water to
the drain system if the valve doesnt open.

High Energy Condensate Recovery drain tank A115-MAL30-BB001


In a normal operation, the control valve A115-MAL30-AA101 will control the temperature
inside the High Energy Condensate Recovery drain tank introducing attemperation water
(through diffuser nozzles) from demin water system to reduce the temperature inside the
tank. In case of exceeding the temperature of 82C the valve will be forced to open.
2

The control valve A115-MAL30-AA102 will control the water temperature in the High
Energy Condensate Recovery drain tank, to avoid pumps cavitation, introducing cool water
from demin water system. In case of exceeding the temperature of 70C the valve will be
forced to open.

At the same time, High Energy Condensate Recovery drain tank level will be controlled by
selected pump (A115-MAL41-AP001 or A115-MAL42-AP001) which will start when the
level is higher than 44% to evacuate the water inside the tank up to the 20% level when the
pump will stop. In this way, the level inside the tank will be controlled. In case the level
exceeds the value of 46% an alarm will be generated in DCS, but if the level exceeds the
value of 56% the DCS will trip the ST.

Low Energy Condensate Recovery drain tank A115-MAL40-BB001


In a normal operation, the control valve A115-MAL40-AA101 will control the temperature
inside the Low Energy Condensate Recovery drain tank introducing attemperation water
(through diffuser nozzles) from demin water system to reduce the temperature inside the
tank. In case of exceeding the temperature of 82C the valve will be forced to open.

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 19

/ 26

Rev.: 2

The control valve A115-MAL40-AA102 will control the water temperature in the Low Energy
Condensate Recovery drain tank, to avoid pumps cavitation, introducing cool water from
demin water system. In case of exceeding the temperature of 70C the valve will be forced
to open.
2

At the same time, Low Energy Condensate Recovery drain tank level will be controlled by
selected pump (A115-MAL41-AP001 or A115-MAL42-AP001) which will start when the
level is higher than 44% to evacuate the water inside the tank up to the 20% level when the
pump will stop. In this way, the level inside the tank will be controlled. In case the level
exceeds the value of 46% an alarm will be generated in DCS, but if the level exceeds the
value of 56% the DCS will trip the ST.

Interlock
For process interlocks see section 2.1.

Alarms
For process alarms see section 2.1.

3.5. POSITION IN THE PLANT GENERAL SHUTDOWN SEQUENCE


This system belongs to operation systems and it will be set out of operation following the
steps described in the normal shut down sequence PP10CC-0009-6Y-YDY-ABC-003

3.6. SHUTDOWN SEQUENCE


The shutdown sequence of the system will follow the following steps:
Step 01: Low Energy Condensate recovery tank drain pumps (A115-MAL41-AP001 &
2

A115-MAL42-AP001) STOP (if running) and to MANUAL MODE. Low Energy


Condensate recovery tank attemperation water valve (A115-MAL40-AA101) and
temperature valve (A115-MAL40-AA102) CLOSE and to MANUAL MODE.

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 20

/ 26

Rev.: 2

Step 02: High Energy Condensate recovery tank attemperation water valve (A115MAL30-AA101) and temperature valve (A115-MAL30-AA102) CLOSE and to MANUAL
2

MODE.
Step 03: ST Area Atmospheric drain tank drain valves (A115-MAL20-AA081 & 082) and
attemperation valve (A115-MAL20-AA083) CLOSE and to MANUAL MODE.
Step 04: HRSG Area Atmospheric drain tank attemperation valve (A115-MAL10-AA081)
CLOSE and to MANUAL MODE.

3.7. EMERGENCY SHUTDOWN SEQUENCE


There is not an emergency shutdown sequence for this system.
In case of an emergency shutdown, this system doesnt need to be attended by other
system.

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 21

/ 26

Rev.: 2

4.

LOGIC LOOPS/CONTROL DESCRIPTION

4.1. LOGIC LOOPS


In this system there are the following logic loops:

HRSG Area Atmospheric drain tank A115-MAL10-BB001


2
HRSG Area Atmospheric drain tank A115-MAL10Loop

BB001

Temperature Control
Instrument TAG:
PV

Temperature

A115-MAL10-CT001
A115-MAL10-CT002

SP

Permissives

Open if T > 356C


Close if T < 210C
-

Instrument TAG:

Override

Force to Open if temperature in Tank High High (HHH)

A115-MAL10-CT001
A115-MAL10-CT002

Actuator

Pneumatic On-off valve

A115-MAL10-AA081

ST Area Atmospheric drain tank A115-MAL20-BB001


2
Loop

ST Area Atmospheric drain tank A115-MAL20-BB001


Temperature Control

Instrument TAG:

PV

Temperature

A115-MAL20-CT001
A115-MAL20-CT002

SP

Open if T > 356C


Close if T < 210C

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 22

/ 26

Rev.: 2

Loop

Permissives

ST Area Atmospheric drain tank A115-MAL20-BB001


Temperature Control
-

Instrument TAG:

Override

Force to Open if temperature in Tank High High (HHH)

A115-MAL20-CT001
A115-MAL20-CT002

Actuator

Loop

Pneumatic On-off valve

ST Atmospheric Drain Tank A115-MAL20-BB001


Level Control

A115-MAL20-AA083

Instrument TAG:

PV

Level

A115-MAL20-CL001
A115-MAL20-CL002

SP

Permissives

Open if L > 35%


Close if L < 20%
-

Instrument TAG:

Force to Close if level in High Energy Condensate Tank


Override

High High (HH)

Force to Close if level in ST Atmospheric Drain Tank


Low Low (LLL)

Actuator

Loop
PV

Pneumatic On-off valve

ST Atmospheric Drain Tank A115-MAL20-BB001


Level Control
Level

A115-MAL30-CL001
A115-MAL30-CL002
A115-MAL30-CL003

A115-MAL20-CL001
A115-MAL20-CL002
A115-MAL20-AA081

Instrument TAG:

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13
Page 23

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

/ 26

Rev.: 2

Loop

ST Atmospheric Drain Tank A115-MAL20-BB001

Level Control

A115-MAL20-CL001
A115-MAL20-CL002
SP

Permissives

Open if L > 35%

Close if L < 20%


-

Instrument TAG:

Force to Close if level in High Energy Condensate Tank


2

Override

High High (HH)

Force to Close if level in ST Atmospheric Drain Tank


Low Low (LLL)

Actuator

Pneumatic On-off valve

A115-MAL30-CL001
A115-MAL30-CL002
A115-MAL30-CL003

A115-MAL20-CL001
A115-MAL20-CL002
A115-MAL20-AA082

High Energy Condensate Recovery drain tank A115-MAL30-BB001


High Energy Condensate Recovery drain tank A115Loop

MAL30-BB001

Temperature Control
Instrument TAG:
PV

Temperature

A115-MAL30-CT001
A115-MAL30-CT002

SP
Permissives

Override
2
Actuator

T = 72C

Force to Open if temperature in High Energy

A115-MAL30-CT001

Condensate Tank High High (HHH)

A115-MAL30-CT002

Pneumatic Control Valve

A115-MAL30-AA101

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 24

/ 26

Rev.: 2

High Energy Condensate Recovery drain tank


Loop

A115-MAL30-BB001

Water Temperature Control


Instrument TAG:
PV

Temperature

A115-MAL30-CT003
A115-MAL30-CT004

SP
Permissives

Override
2
Actuator

T = 60C

Force to Open if water temperature in High Energy

A115-MAL30-CT003

Condensate Tank High High (HHH)

A115-MAL30-CT004

Pneumatic Control Valve

A115-MAL30-AA102

Low Energy Condensate Recovery drain tank A115-MAL30-BB001

Low Energy Condensate Recovery drain tank


Loop

A115-MAL40-BB001

Temperature Control
Instrument TAG:
PV

Temperature

A115-MAL40-CT001
A115-MAL40-CT002

SP
Permissives

Override
2
Actuator

T = 72C

Force to Open if temperature in Low Energy

A115-MAL40-CT001

Condensate Tank High High (HHH)

A115-MAL40-CT002

Pneumatic On-off valve

A115-MAL40-AA101

Low Energy Condensate Recovery drain tank


Loop

A115-MAL40-BB001

Water Temperature Control


PV

Temperature

Instrument TAG:
A115-MAL40-CT003

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 25

/ 26

Rev.: 2

Low Energy Condensate Recovery drain tank


Loop

A115-MAL40-BB001

Water Temperature Control


A115-MAL40-CT004
SP
Permissives

Override
2
Actuator

T = 60C

Force to Open if water temperature in Low Energy

A115-MAL40-CT003

Condensate Tank High High (HHH)

A115-MAL40-CT004

Pneumatic On-off valve

A115-MAL40-AA102

High & Low Energy Condensate Recovery drain tanks


Loop

A115-MAL30-BB001 & A115-MAL40-BB001

Drain Pumps Level Control


Instrument TAG:
A115-MAL30-CL001
A115-MAL30-CL002
PV

Level

A115-MAL30-CL003
OR
A115-MAL40-CL001
A115-MAL40-CL002
A115-MAL40-CL003

SP
Permissives

Start if L > 44%


Stop if L < 20%
-

A115-MAL30-CL001
A115-MAL30-CL002
A115-MAL30-CL003

Interlock

Drain Tank Level Low Low (LLL) < 5%

OR
A115-MAL40-CL001
A115-MAL40-CL002
A115-MAL40-CL003

Actuator

Electric Pump

A115-MAL41-AP001
A115-MAL42-AP001

PP10CC Combined Cycle

Document Code

Date

PP10CC-0009-6MAL-YR-ABC-001

10/07/13

ST VENTS & DRAINS FUNCTIONAL DESCRIPTION

Page 26

/ 26

Rev.: 2

4.2. CONTROL DESCRIPTION

Once the HRSG System is in operation, the Master Sequence Following Controller
(M.S.F.C) will send an automatic command to Steam Turbine Vents and Drains Functional
Group (STDV GROUP) to set in AUTO MODE this system. The STVD GROUP will send
an automatic command to each pump, to each control valve and to each pneumatic on-off
valve. After being in AUTO MODE, drain pumps will start or stop according to process
conditions. Similarly pneumatic on-off valves will be open or close if required.

In AUTO MODE, on-off valves, control valves and pumps will operate as described in
section 3.4 NORMAL OPERATION.

On the contrary, during the shutdown sequence, the M.S.F.C will set the system in OFF
sending a command to the functional group (STVD GROUP) which will stop the pumps (if
running) and close all valves (if open). After that all devices will be set in MANUAL mode in
2

order to continue with the shutdown sequence.

See attached sketch for better understanding of above explanation.

XV-04

HI_LO_MON

CONDENSATE

LP STEAM DRAIN

HP STEAM DRAIN
TT
DUALSEL

LP STEAM DRAIN

TT

HP STEAM DRAIN

HP STEAM DRAIN

LP STEAM DRAIN

LP STEAM DRAIN

HP STEAM DRAIN

PT

HRSG AREA
ATMOSPHERIC DRAIN
TANK
A115-MAL10-BB001

LT

LP STEAM DRAIN

DUALSEL

LT

AUX STEAM DRAIN


AUX STEAM DRAIN
AUX STEAM DRAIN

AUX STEAM DRAIN

HRSG BLOWDOWN
DRAIN SUMP

SH: 1/4

STEAM TURBINE VENTS & DRAINS SYSTEM

HI_LO_MON

GROUP
STVD

HP STEAM DRAIN
HP STEAM DRAIN
HP STEAM BY-PASS 1
DRAIN

XV-04

CONDENSATE

AUTO / MANUAL
M.S.F.C

START / STOP

AUTO / MANUAL
TO ST VENTS & DRAINS

TT

DUALSEL

SH: 3/4

TO ST VENTS & DRAINS

TT

HP STEAM BY-PASS 2
DRAIN

SH: 4/4

AUXILIARY STEAM DRAIN


LP STEAM DRAIN

PT

ST AREA
ATMOSPHERIC DRAIN
TANK
A115-MAL20-BB001

LP STEAM BY-PASS DRAIN


LP STEAM BY-PASS DRAIN

LT
DUALSEL

HP STEAM DRAIN
LT

HP STEAM DRAIN
HI_LO_MON

HP STEAM DRAIN
TO ST VENTS & DRAINS

HP STEAM BY-PASS 3
DRAIN

XV-01

HP STEAM BY-PASS 4
DRAIN
HP STEAM BY-PASS 1
DRAIN

SH: 3/4

XV-01

HIGH ENERGY
VACUUM TANK

HP STEAM BY-PASS 2
DRAIN

SH: 3/4

HP STEAM BY-PASS 3
DRAIN
HP STEAM BY-PASS 4
DRAIN
ST MSCV-1 BEFORE
SEAT DRAIN TAP

SH: 2/4

STEAM TURBINE VENTS & DRAINS SYSTEM

ACC
DUCT
STEAM TURBINE
TRIP

TT

AUTO / MANUAL

CV-01

DUALSEL

FROM ST VENTS & DRAINS


1

SH: 2/4

TT

DEMIN WATER
SUPPLY

PT

ST ATMOSPHERIC
DRAIN TANK
4

TO ST VENTS & DRAINS


SH: 2/4

SEAL S. HEADER
DRAIN
ST LINE
LOW P. DRAIN

HHH

HH

LT

MEDSEL

HI_LO_MON

SEAT DRAIN
TAP

LT

LLL

SEAL STEAM
HEADER DUMP

HIGH ENERGY
CONDENSATE
RECOVERY DRAIN TANK
MAL30-BB001

SH: 2/4

LT

CV-01

TT
DUALSEL

TO DRAIN
PUMPS

TT
HI_LO_MON

TRIP

START / STOP

TO ST VENTS & DRAINS


6

SH: 4/4
7

SH: 4/4

TO ST VENTS & DRAINS


5

SH: 4/4

SH: 3/4

STEAM TURBINE VENTS & DRAINS SYSTEM

ACC
DUCT

STEAM TURBINE
TRIP

TT

AUTO / MANUAL

CV-01

DUALSEL

FROM ST VENTS & DRAINS


2

SH: 2/4

TT

DEMIN WATER
SUPPLY

PT

EXHAUST HOOD SHELL


DRAIN
EXHAUST HOOD SHELL
DRAIN
EXHAUST HOOD SHELL
DRAIN
EXHAUST HOOD SHELL
DRAIN
SEAL S. DESUPERHEATER
DRAIN
GLAND CONDENSER
DRAIN
ST GLAND MANIFOLD LOW
POINT DRAIN

SEAL S.
HEADER DRAIN

LOW ENERGY
CONDENSATE
RECOVERY DRAIN TANK
MAL40-BB001

SEAL S.
HEADER DRAIN
SEAL S.
HEADER DRAIN
AFTER ACV
DRAIN
BEFORE ACV
DRAIN

LT

HI_LO_MON

MEDSEL

LLL

HHH

AUTO
CHANGE OVER

START / STOP

CV-01

LT
LL

LT

LVMP-03

HI_LO_MON

PT
TO ST VENTS & DRAINS
5

SH: 3/4

FROM HIGH
ENERGY TANK
7

SH: 4/4

TT
DUALSEL

TT

LVMP-03

CONDENSATE
RECOVERY
TANK

HI_LO_MON

START / STOP
TRIP

TO ST VENTS & DRAINS


5

SH: 3/4

SH: 4/4

STEAM TURBINE VENTS & DRAINS SYSTEM