Académique Documents
Professionnel Documents
Culture Documents
www.elsevier.com/locate/solener
Abstract
The paper presents and discusses internal pressure and discharge coecients for a building with wind-driven cross-ventilation caused
by sliding window openings on two adjacent walls. The study found that both coecients vary considerably with the opening area
(porosity of wall(s)) and the inlet to outlet ratio. Comparisons with previous work were also carried out. Experimental results verify
the unsteady pressure and velocity eld, particularly in the case of cross-ventilation with large opening areas. For such cases, a simulation
sensitivity analysis of wind-induced building ventilation conrms that airow rates vary considerably when dierent discharge coecient
values are used.
2006 Elsevier Ltd. All rights reserved.
Keywords: Wind-driven ow; Cross-ventilation; Windward wall porosity; Inlet to outlet ratio; Internal pressure coecient; Inlet discharge coecient
1. Introduction
In a recent survey carried out by Canada Mortgage and
Housing Corporation (CMHC, 2004) to verify the use and
utility of ventilation systems in new Ontario houses it was
found that Over 90% of new homeowners in Ontario do
open windows, with over 40% opening windows for periods
of the winter. In mid-summer, almost 10% do not open
windows at all, which may indicate continuous use of air
conditioning systems. These houses would benet from
mid-summer ventilation to provide fresh air. The window
opening data collected (CMHC, 2004) are summarized in
Fig. 1. Many complaints reported from the occupants are
due to noise and drafts from mechanical systems. Field
experiments carried out in an urban canyon have shown
that appreciable ventilation rates can be obtained with natural ventilation in residential buildings, especially when
*
Corresponding author. Tel.: +1 514 848 2424 (7080); fax: +1 514 848
7965.
E-mail address: p_karava@alcor.concordia.ca (P. Karava).
0038-092X/$ - see front matter 2006 Elsevier Ltd. All rights reserved.
doi:10.1016/j.solener.2006.06.013
cross-ventilation with two or more windows is used (Niachou et al., 2005). Chang et al. (2004) investigated the eects
of outdoor air conditions on hybrid air conditioning with
natural and mechanical ventilation in oce buildings.
The study found that natural ventilation at temperatures
lower than the indoor temperature eectively covered the
lower indoor task zone through negative buoyancy, which
enabled energy-saving air conditioning in the task zone.
Natural ventilation a traditional method to eectively
remove solar heat gains and improve the indoor thermal
environment appears as a cost-eective and attractive
alternative to mechanical ventilation. Cross-ventilation,
which is the design type of choice, is now attracting considerable attention again as a measure for sustainable design
of a building; recent developments involve integration of
cross-ventilation with HVAC and solar technologies such
as double facades or Building Integrated Photovoltaic Systems (BIPV). However, while natural ventilation is conceptually simple, its detailed design can be a challenge; the
ventilation performance involves the buildings form, its
surroundings and climate. This complexity, particularly
21
Nomenclature
A
A1
A2
a
Aopening
Awall
Ac
b
Cc
CD
CD,inlet
Cp1
opening area
inlet opening area
outlet opening area
A1/A2 = inlet to outlet ratio
area of the opening
area of the wall
cross section area of the vena contracta
1/4 for uniform distribution of cracks
contraction coecient
discharge coecient
inlet discharge coecient
external pressure coecient in opening 1
for wind-driven ventilation, can make dicult the development of a successful design. Mochida et al. (2005) and Lee
et al. (2005) pointed out that careful consideration of wind
ow around a building when deciding the placement of
window openings is very important to fully utilize the
potential of cross-ventilation and improve thermal comfort. However, dierent window congurations result in
dierent ventilation eectiveness, indoor air quality (IAQ)
and impact on comfort conditions in the occupied zone
(Heiselberg et al., 2001, 2002). Currently, codes of practice
or ventilation standards do not provide any selection criteria for dierent window types (e.g., sliding, top, side and
bottom hung windows, windows with louvers) or their
placement on the facade for adequate ventilation.
Formulating guidelines for the design of ventilation
systems is indeed signicant. This includes selection of
appropriate window type and its location on the facade
aiming to enhance ventilation or summer cooling
performance. This paper investigates the main parameters
aecting natural ventilation design, i.e., number/type of
windows or openings, size and location on facade for
wind-driven cross-ventilation and determines appropriate
discharge coecient values. The unsteady pressure and
velocity eld in the vicinity of the openings are investigated
80
Never
Percent of season
70
Monthly
60
Weekly
Daily < 1 h
40
3*Weekly
50
Cp2
Cpin
Cpw
Cv
DP
Q
u
V
Vc
Vth
q
Daily extended
30
20
CD Cc Cv
10
where
0
Spring or Fall
Summer
Winter
22
A = opening area;
Cc = contraction coecient (61);
Cv = velocity coecient depending on the friction conditions (61);
DP = pressure dierence across the opening;
q = air density.
For low-rise buildings, the airow through ventilation
openings (i.e., openable windows) is mainly wind-driven,
especially during summer. For wind-driven ventilation,
the discharge coecient for an inlet can be determined by:
C D;inlet
AV
Q
u
p
p
C pw C pin V C pw C pin
in which
Q = airow through the opening;
u = local velocity in the opening;
V = reference wind speed at the buildings height;
Cpw = pressure coecient on windward facade;
Cpin = internal pressure coecient, determined for a building with two openings by:
C p2 a2 C p1
large openings
5
1 a2
e:g:; windows; doors turbulent flow
C 2 b C p1
small openings
6
C pin
1b
e:g:; cracks laminar flow
C pin
Aopening
Awall
23
Fig. 2. Exploded view of building model with pressure tap locations and opening congurations.
Table 1
Study considerations and range of variables
Ventilation strategy
Building dimensions
61 39 12 (eave height) m
15.3 9.8 3 (eave height) cm
1:12 (gabled)
1:400
Open (a = 0.15, T.I. = 22% at
the eave height)
0 (perpendicular to long wall)
Sliding
0160 m2
010 cm2
022%
08
0% and 0.5%
Roof slope
Scaling
Upstream terrain
Wind direction
Window type
Opening area
Windward wall porosity
Ainlet/Aoutlet
Building envelope leakage
0.8
0.6
0.4
The measured mean values of the external pressure coefcients (reference height = building height) are 0.67 for the
windward wall, 0.36 for the side wall, 0.25 for the leeward wall and 0.4 and 0.74 on taps 7 and 9 of the roof
(see Fig. 2). The measured mean internal pressure coecient for 0.5% background leakage (without openings) is
0.36 which is slightly dierent from the theoretical value,
0.23, obtained by Eq. (6) using Cp1 as the representative
of the positive external pressure and Cp2 as the area-averaged pressure on the rest of the building envelope.
Cpin
0.2
0
0
10
15
20
25
-0.2
-0.4
BLWT, 0% leakage
BLWT, 0.5% leakage
Theoretical, 0% leakage
30
-0.6
24
0.8
Present study
Previous studies
0.6
0.4
Cpin
0.2
0
0
-0.2
-0.4
10
15
20
25
30
-0.6
Cpin
0.2
0
0.1
10
A1/A2
-0.2
BLWT, 5% leakage, 10% windward wall porosity
Theoretical, 0% leakage
Murakami et al. (1991), side wall outlet
Murakami et al. (1991), leeward wall outlet
-0.4
-0.6
25
1.4
0.2
Windward wall porosity = 5%
Windward wall porosity = 10%
1.2
0.16
Cp
0.12
Cp
0.8
STDEV
0.6
0.08
0.4
0.04
0.2
0
0.1
1
A1/A2
10
10
20
30
Windward wall porosity (Ainlet/Awall) (%)
40
26
BLWT, outlet
Theoretical, outlet
Sandberg (2004), outlet
1.8
Previous studies
Present study
1.5
1.2
Cp
0.9
0.6
0.3
0
0.01
0.1
A1/A2
10
100
-0.3
Fig. 8. Pressure dierence across the inlet and outlet as a function of inlet
to outlet ratio (A1 = 2.6 cm2 or 5% windward wall porosity Ainlet/Awall).
u/V
Vref (m/s)
Present study
Hu et al. (2005)
Etheridge (2004)
Sawachi et al. (2004)
Murakami et al. (1991)
0.50.63
0.45
0.60
0.50
0.641.0
7.2
7.0
4.0
3.0
Not reported
Inlet CD
0.8
0.6
0.4
0.2
0
0
5
10
15
20
25
Windward wall porosity (Ainlet/Awall) (%)
30
CD = 1
1
0.8
Inlet CD
1.2
27
CD = 0.65
0.6
0.4
0.2
0
0.1
1
A1/A2
10
Fig. 10. Inlet CD as a function of inlet to outlet ratio for A1 = 2.6 cm2 or
5% windward wall porosity (Ainlet/Awall).
28
Table 3
Mean and STDEV air change rate for dierent opening congurations
(July 1213, 2002)
A1 (m2)
A2 (m2)
A1/A2
Inlet CD
Outlet CD
STDEV
0.02
0.02
0.1
0.1
0.1
0.1
0.02
0.02
0.02
0.02
0.1
0.1
1
1
5
5
1
1
0.5
1
0.5
1
0.5
1
0.5
0.5
0.5
0.5
0.5
1
0.38
0.54
0.60
0.62
1.99
3.76
0.18
0.26
0.29
0.30
1.02
2.03
decrease of pressure drop is not taken into account. Therefore, opening area, discharge coecient, airow and pressure drop are coupled and these interactions may have
important implications on control of openings. Although
these are data for a test building, and results cannot be generalized, it is clear that signicant dierences stem from
inaccurate determination of discharge coecients. A sensitivity analysis in terms of internal pressure coecient is
partially covered since the latter aects the evaluation of
CD. However, this work should be extended to validate
(using experimental results) predictions in airow modeling
with respect to Cpin since experimental results show that the
internal pressure coecient variation is not predicted accurately by the theory particularly for A1 = A2.
5. Concluding remarks
The paper presents and compares with other literature
sources the results of a series of experiments carried out
in a Boundary Layer Wind Tunnel (BLWT) for the evaluation of the internal pressure coecient and the discharge
coecient in a building with cross-ventilation caused by
29
ESRU, 2002. The ESP-r system for building energy simulationUser Guide
Version 10 Series. University of Strathclyde, Glasgow, UK.
Etheridge, D.W., 2004. Natural ventilation through large openings
measurements at model scale and envelope theory. International
Journal of Ventilation 2 (4), 325342.
Etheridge, D., Sandberg, M., 1996. Building ventilation: Theory and
measurement. John Willey & Sons, London.
Furbringer, J.M., Roulet, C.A., Borchiellini, R., 1999. An overview of the
evaluation activities of IEA ECBCS Annex 23. Energy and Buildings
30, 1933.
Heiselberg, P. 2004a. Building integrated ventilation systems-modelling
and design challenges. In: Proceedings of CIB World Congress,
Toronto, Canada.
Heiselberg, P., 2004b. Natural ventilation design. International Journal of
Ventilation 2 (4), 295312.
Heiselberg, P., Svidt, K., Nielsen, P.V., 2001. Characteristics of airow
from open windows. Building and Environment 36, 859869.
Heiselberg, P., Bjorn, E., Nielsen, P.V., 2002. Impact of open windows on
room air ow and thermal comfort. International Journal of Ventilation 1 (2), 91100.
Hiyama, K., Kato, S. 2005. Study on new prediction procedure of crossventilation performance based on power balance. In: Choi, C.K., Kim,
Y.D., Kwak, H.G. (Eds.), Proceedings of 6th Asian-Pacic Conference
on Wind Engineering (APCWE VI), Seoul, Korea, September 1214,
pp. 14851495.
Hu, H.C., Kurabuchi, T., Ohba, M. 2005. Numerical study of windinduced ventilation with the local dynamic similarity model. In:
Naprstek, J., Fischer, C. (Eds.), Proceedings of 4th European &
African Wind Engineering Conference (EACWE4), Prague, July 11
15.
Jensen, J.T., Sandberg, M., Heiselberg, P., Nielsen, P.V., 2002. Wind
driven cross-ow analyzed as a catchment problem and as a pressure
driven ow. International Journal of Ventilation, HybVent-Hybrid
Ventilation Special Edition 1, 88101.
Karava, P., Stathopoulos, T., Athienitis, A.K., 2004. Wind-driven ow
through openings: A Review of discharge coecients. International
Journal of Ventilation 3 (3), 255266.
Karava, P. Athienitis, A.K., Stathopoulos, T. Reardon, J.T. 2006.
Modelling of indoor-outdoor air-exchange in a multi-unit residential
building. Submitted. In: Proceedings of International Building Physics
Conference, Montreal, August 2731.
Katayama, T., Tsutsumi, J., Ishii, A., 1992. Full-scale measurements and
wind tunnel tests on cross-ventilation. Journal of Wind Engineering
and Industrial Aerodynamics 4144, 25532562.
Kato, S., 2004. Flow network model based on power balance as applied to
cross ventilation. International Journal of Ventilation 2 (4), 395408.
Kato, S., Murakami, S., Mochida, A., Akabashi, S., Tominaga, Y., 1992.
Velocity-pressure eld of cross ventilation with open windows
analyzed by wind tunnel and numerical simulation. Journal of Wind
Engineering and Industrial Aerodynamics 4144, 25752586.
Kurabuchi, T., Ohba, M., Endo, T., Akamine, Y., Nakayama, F., 2004.
Local dynamic similarity model of cross ventilation: Part 1
theoretical framework. International Journal of Ventilation 2 (4),
371382.
Kurabuchi, T., Endo, T., Ohba, M., Goto, T., Akamine, Y. 2005. Local
dynamic similarity concept as applied to evaluation of discharge
coecients of cross-ventilated buildings. Part 1: Basic idea and
underlying wind tunnel tests. In: Santamouris, M. (Ed.), Proceedings
of PALENC, Santorini, Greece, May 1921, pp. 409414.
Lee, J.Y., Kang, J.H., Jang, Y.G., Zhang, W., Lee, S.J. 2005. PIV analysis
of the ventilation ow inside a large-scale factory building. In: Choi,
C.K., Kim, Y.D., Kwak, H.G. (Eds.), Proceedings of 6th AsianPacic
Conference on Wind Engineering (APCWE VI), Seoul, Korea,
September 1214, pp. 427436.
Liu, H., 1991. Wind engineering A handbook for structural engineers.
Prentice-Hall, New Jersey.
Mochida, A., Yoshimo, H., Takeda, T., Kakegawa, T., Miyauchi, S.,
2005. Methods for controlling airow in and around a building under
30