Vous êtes sur la page 1sur 4

Phone:+91 9222 666 999

Email:shop@shopelect.com
Website:www.shopelect.com

We touch your electricity everyday!

ACB-B Type

IS: 8828

Air Circuit Breaker

Phone:+91 9222 666 999


Email:shop@shopelect.com
Website:www.shopelect.com

Technical Overview
Salient Features
n

400~1600A in single frame size

Light & compact

High breaking capacity - 45/50kA

Reliable system protection thru:


a) Thermal Magnetic (TOMCR)
b) Microprocessor Release (mIT-100)

Fast acting mechanism (total breaking time less than 30ms including arcing time of less than 10ms) minimizes installation stress
under fault condition

Easy termination - horizontal Bus bar connection.

High mechanical & electrical life.

High dielectric strength due to use of class 'B' and 'F' insulating material ensures reliable performance in tropical conditions

n Comply with utilization category B & pollution degree 3 group 1 of IEC60947-Part1


n Tested for seismic conditions .
n Wide range of accessories offered-Shunt trip, UVT, Auxiliary Switch, Trip indication switches to meet market specifications.

High Breaking & Short Time Withstand Capacity

Contact Pressure by Repulsive Force


Contact Pressure by Contact Spring

Mechanical Retaining Force


Contact Spring
Current

Full utilization of electromagnetic repulsive force

Stationary Contact

Even though it is sound and compact in design, it provides high


breaking capacity and short - time withstand current capacity by fully
utilizing electromagnetic repulsive force.

Moving Contact
Contact Shaft

n The contact spring normally provides an adequate contact


pressure.

Electromagnetic
Repulsive Force

Contact Lead

Current

n A large current flow causes an electromagnetic repulsive force


between the contact lead halves.
n This repulsive force works in a direction to turn the moving contact
clockwise about the contact shaft, giving it more contact pressure.
n Hence this unique
current capacity.

Arc
Stationary Contact
Separating Force Resulting from
Repulsive Force
Separating Force by Trip Spring

n When interrupting a large current, the electromagnetic repulsive force


works in a direction to separate the moving contact from the
stationary contact.

Moving Contact

Trip Spring
Contact Holder Shaft

design ensures a high short-time withstand

Electromagnetic
Repulsive Force

n A separating force resulting from the electromagnetic repulsive force


adds to that by the trip spring, assisting a high-speed interruption.
This is why our design provides a high breaking capacity

Current

Technical Specifications
Amperes Frame (based on IEC / IS)
Type (3 Poles)
Insulation Voltage Ui (V) AC

400
AH-4B

630
AH-6B*

800
AH-8B*

1000
AH-10B

1250
AH-12B

1600
AH-16B

1000

1000

1000

1000

1000

1000

Impulse Voltage Uimp (V) AC (Peak)

Dielectric strength (for a minute) kV

3.5

3.5

3.5

3.5

3.5

3.5

Rated Making Capacity Icm (Peak) kA

105

105

105

105

105

105

Rated Breaking Capacity Icu=Ics (RMS) kA 415V AC

50

50

50

50

50

50

Short time withstand current Icw kA for 1 sec. RMS

50

50

50

50

50

50

30/40

30/40

30/40

30/40

30/40

30/40

40

40

40

42

42

44

Total breaking time/closing time (m.sec.)


Weight (kg)
Overall Dimension (H x W x D) (mm)

483 x 332 x 323

* 630A & 800A ACBs are also available in 45kA breaking capacity at 415V AC operating voltage & 690V insulation voltage.

Phone:+91 9222 666 999


Email:shop@shopelect.com
Website:www.shopelect.com

Protection Release
Microprocessor Release
IT-100 is a true RMS sensing overcurrent trip device, requires no external
supply for its basic function.

Salient Features
n Error free and user friendly setting of current/time.
n Provides highest degree of system protection coordination.
n Self powered by built in current transformer.
n No mal-operation due to external disturbances.
n Built in operation check function.
n Visual fault discrimination by LEDs.
n Three phase and earth fault in one single compact unit.
n Self monitoring of trip unit with blinking indication.
n Function Blocking facility provided.

Tripping Characteristics
Over Load Current (LTD)
LTD Current
Setting range: 0.5, 0.55 ...1.15 In (in steps of 0.05)
LTD Time
Setting range: 2.5, 5 ....... to 35 sec. (in steps of 2.5 sec.)
Short Circuit Current (STD)
STD Current
Setting range: 4, 5 ... 10 In (in steps of 1)
STD Time
Setting Range: 50, 100, ... 550 ms. (in steps of 50 ms)
Instantaneous Current (INS)
Current (INS)
Setting Ranges: 4, 5, ... 11In (in steps of 1)
Ground Fault (GFT)
GFT Current
Setting Range: 15, 20, ... 50% In (in steps of 5%)
GFT Time
Setting Range: 50, 100, ... 550 ms (in steps of 50ms)
Function Blocking In normal running operation of unit, any of the four function
can be blocked by turning the DIP switches to ON position

3
2
80%
100%
120%

minute

Accuracy of Time &


Current Setting 20%
Calibrated at40C:

Balanced (Cold Start)

------

Balanced (Hot Start)

3
2

Operating Time

40ms.

30ms.

50
40
30

MAGNETIC INST. S/C TRIP

Rated Current

20

Current setting of non-adjustable magnetic instantaneous trip

10
8.0
6.0

Applicable Breaker

AH-6B
AH-8B

5.0
4.0
3.0

% Rated Current of Base Current

600

400

500

200

250
300

80

100
120
125
150

2.0

60
70

CT actuated thermal Overload relay offers O/L


Protection along with Shunt trip. Current setting are
60-100% or 80-120%.

20
8

second

A direct acting electromagnetic instantaneous trip


device with fixed current setting for Short Circuit
Protection.

Long Time Delay Trip


Current setting range

50

Thermal Magnetic Release

TIME

hour

1.3

1.05

Tripping Characteristics

Note: Applicable where rated current of


over current trip devices is not less than 250A

AH-10B
AH-12B
AH-16B

Phone:+91 9222 666 999


Email:shop@shopelect.com
Website:www.shopelect.com

www.cselectric.co.in

Air Circuit Breakers - B Series

Overall Dimensions (AH-4B~AH-16B)


Front View

Panel Cutout

15

151.5

151.5

15

166

166
332

Rear View

C&S Electric Ltd.


Corporate Office : 222, Okhla Industrial Estate, New Delhi - 110 020
Tel. : +91-11-3088 7520 - 29, Fax: +91-11-2684 7154, 2682 9063
International Business Division: Tel. : +91-11-4161 3503, 3088 7520-29, Fax: +91-11-2683 8291, 2684 7342
email : exports@cselectric.co.in
Central Marketing Office: Tel. : +91-11-3088 7520-29 , Fax: +91-11-2684 8241, 2684 7342
email : cmo@cselectric.co.in, info@cselectric.co.in

We touch your electricity everyday!

102SGR/B/062011

Side View