Vous êtes sur la page 1sur 4

GE Power & Water

Distributed Power

JGS 616 DS
PRELIMINARY DATA, dated 2014-04-08

www.ge-distributedpower.com
616diesel@ge.com

Preliminary, subject to change

GE Power & Water


Distributed Power
JGS 616 DS
GENSET data in continuous operation:

Additional information:

Electrical output at p.f. = 1 (7)

kWe

2,557

Sound pressure level of genset

dB(A)

104

Electrical output at p.f. = 0.8 (7)

kWe

2,541

Sound pressure level of exhaust gas

dB(A)

121
29,220

Mechanical output (1)


Fuel Consumption (3, 4)
Engine jacket water (HT circuit) (2, 3)
Intercooler 1st stage (HT circuit) (2, 3)
Intercooler 2nd stage (LT circuit) (2, 3)
Lube oil (LT circuit) (2, 3)
Surface heat (5)
Emission values:

kW

2,620

Exhaust gas volume at 465 C and nominal power

m/h

g/kWh

188.0

Max. admissible exhaust back pressure

mbar

30

l/h

593.4

Exhaust gas temperature at 100% load

465

kW

1,022

m/h

12,060

kW

461

kW
154
NOx < 1,460 mg/Nm (15% O2)

Engine data:

Combustion air volume at 25 C and nominal power


Max. inlet cooling water temperature (LT- circuit)

54.4

Approx. outlet cooling water temperature (LT- circuit) (8)


Water flow rate (LT- circuit)

62.2

m/h

57.0
73.9

Max. inlet cooling water temperature (HT- circuit)

Approx. outlet cooling water temperature (HT- circuit) (8)


Water flow rate (HT- circuit)

86.1

m/h

79.5

Max. pressure drop of air intake filter

mbar

20

Alternator:

Engine type

616

Configuration

V 60

No. of cylinders

Manufacturer

TD Power Systems (6)


TD125-F2K7 (6)

Type

16

Type rating

190

Efficiency at p.f. = 1,0

kVA

4,500

97.6%

Bore

mm

Stroke

mm

220

97.0%

lit

99.80

Ratings at p.f. = 1,0

kW

2,557

Nominal speed

rpm

1,500

Ratings at p.f. = 0,8

kW

2,541

Mean piston speed

m/s

11.0

Frequency

Hz

50

BMEP at nominal power

bar

21.00

Voltage

kV

10.5

Compression ratio

Epsilon

16.0:1

Protection Class

Continuous power

kW

2,620

Insulation class

Weight dry

kg

13,500

Speed

rpm

1,500

650

Mass

kg

17,400

Piston displacement

Refilling capacity lube oil

1)

Efficiency at p.f. = 0,8

IP 23
F

At standard reference conditions per ISO 3046-1:2002E, ISO 8665 and ISO 8528-5:2010 and continuous operation

2)

Thermal output with tolerance of 8%

3)

New unit, continuous operation (no overload)

4)

Fuel consumption based on EN 590 fuel with assumed LHV 42700 kJ/kg, density 830 g/l and tolerance of +5%

5)

Only valid for engine and generator; Peripheral equipment is not considered (at p. f. = 0,8)

6)

GE Jenbacher reserves the right to change the generator supplier and the generator type

7)

According to VDE 0530 REM / IEC 34.1 with relative tolerances

8)

Based on 30% gylcol

Standard conditions:

Definition of output:

Air pressure:

1000 mbar (14.50 psi) or 100 m (328ft) above sea level

Air temperature:

25 C (77 F) or 298 K

Relative Humidity:

30%

Net break power that the engine manufacturer declares an engine is capable of delivering continuously,
at stated speed, between the normal maintenance intervals and overhauls as required by the manufacturer.
Power determined under the operating conditions of the manufacturers test bench and adjusted to the standard conditions.
Overload: 5% capability according to ICxN 5% (1h in 12h period)

Engine output rating:

Installation at an altitude = 0 m and an air intake temperature 50 C (T1)

Fuel quality:

TA 1000-0001

All data are based on engine full load at specified media temperatures and are subject to change.
The technical instruction TA 1100-0110DS "Boundary Conditions for GE Distributed Power Jenbacher diesel engines" must be strictly observed.

GE Power & Water


Distributed Power
Scope of supply genset JGS 616 DS
Basic engine equipment:

Genset equipment:

- Two exhaust gas turbochargers

- Base frame for diesel engine, alternator and heat exchangers

- Intercooler, two stage


- Lubricating oil pump (gear driven)

- Internal pole alternator with excitation alternator and

- Lubricating oil filters in main circuit

- Flexible coupling, bell housing, anti-vibration mounts

- Lubricating oil heat exchanger

- Air filters

- HP fuel pumps for common rail system


- Fuel-, lubricating oil and jacket water pipe work on engine

- Wiring of components to ECU

- Flywheel for alternator operation

- LP fuel pump with water separator and filter

with automatic voltage regulator; p.f. 0.8 lagging to 1.0

- Crankcase breather

- Exhaust gas manifold


- LT & HT water pumps (mechanical driven)
- LT & HT temperature control valves

Engine accessories:

Control equipment:

- Electric starter motor

- Genset-Management-System DIA.NE XT4 with Touch Display

- Transducers and switches for oil pressure, charge air pressure,


jacket water temperature and pressure
- Jacket water electrical preheating (option)

* Visualisation (industry PC with 15'' color graphics display):


Operation data, controller display, exhaust gas temperature, etc.
* Central genset control:
Speed-, power output and overspeed control,

Documentation:

Generator circuit breaker control, etc.


- Multi-transducer

- Operating and maintenance manual

- Demand switch

- Spare parts manual

- Engine control unit (ECU)


- Remote connection (option)

- Drawings

Assembly, painting and testing in Jenbach / Austria

Preliminary, subject to change


Scope of Supply & Design Subject to Local Regulations and product development

GE Power & Water


Distributed Power
Genset JGS 616 DS

Main dimensions and weights (approximate value)

Connections (at genset)

Length L

mm

8,400

High temperature water inlet and outlet

DN/PN

Width B

mm

2,050

Low temperature water inlet and outlet

DN/PN

65/10

Height H

mm

2,550

Exhaust gas outlet

DN/PN

2x 350/10

Weight empty

kg

37,900

Lube oil

DN/PN

28/10

Weight filled

kg

38,900

Fuel

DN

16

www.ge-distributedpower.com
616diesel@ge.com

Preliminary, subject to change

100/10