Académique Documents
Professionnel Documents
Culture Documents
2013
All maintenance hvac technicians must know how to perform pump down on an air
conditioning system.
Manifold gauge.
Ratchet Offset Wrench.
Two jaws jumper cable.
Adjustable wrench.
Safety glass.
Gloves.
Digital Multimeter.
Workshop Cleaning wipe.
.
F.
G.
H.
I.
J.
K.
L.
M.
Check the disconnecting switch to ensure the air conditioning unit is shut down by the
main switch. Check the thermostat and switch it to fan and cool modes.
Be sure the king and suction valves are back seated.
Remove the service port cap and valve stem cap. Open the end cap of the service valves
for suction and king valve using an adjustable wrench.
Verify the closed position in the manifold gauge valves.
Install the manifold gauge. Use the blue hose (Low pressure meter in the left side) and
connect it to the suction service valve on the compressor (This is the big tubing coming
from the evaporator) do not tight the blue hose. Use the red hose (high pressure meter
in the right side and connect it to the king valve in the liquid line. (This is the small
tubing coming from the condenser).
Mid seat the king service valve (located downstream from the condenser in the liquid
line. The small tubing) using a Ratchet Offset Wrench. Turn it around four times with
clockwise rotation, to ensure we have refrigerant in the hoses. Open the high side gauge
manifold with two turns counterclockwise (the red in the right side).
Open the low side gauge manifold with two turns clockwise. (the blue in the left side)
and purge the suction line hose to evacuate the air in the gauge hoses.
Front seat the king valve. Using a Ratchet Offset Wrench. Turn it around with clockwise
rotation until it reaches the end. (by turning the stem valve outwards as far as it will go.
Mid seat the suction service valve in the compressor.
Jump the low pressure control automatic reset switch that open on Pressure Fall to
prevent compressor shut down at 30 psi when is in operation. Remove the wire nuts to
the low pressure control automatic reset switch. Use an alligator clips wire to jump it.
Turn on the unit by the main switch and check the process until the low side gauge
reading should drop to a lower suction pressure on the gauge. This indicates the low
pressure gauge readings reaches between 0 psi to -10 inches of Hg vacuum. All of
refrigerant in the system goes through the compressor and we have stored it
temporarily between the compressor, the condenser and the king valve.
Back seat the suction service valve, turn it around with counterclockwise rotation until
it reaches the end. (by turning the valve stem inwards as far as it will go)
Turn off main switch of the unit. Close both (the low and high side gauge manifold);
check your gauges readings to ensure you have MANUAL PUMP DOWN in the system.
The low pressure gauge readings should be between 0 psi to -10 inches of Hg vacuum.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
Be sure that you have closed both (the low and high side gauge manifold)
Back seat the king service valve.
Mid seat the suction service valve.
Start the unit by the main switch.
Open the high side gauge manifold and slowly open the low side to ensure we are
equalizing the pressure between the two hose and the system. When done back seat the
suction service valve in the compressor and close both valves on the manifold gauge .
Remove the manifold gauge and attach the hoses in the dummy ports on back side.
Replace the service port cap and the valve stem caps.
Turn off the unit by the main switch.
Clean the manifold gauge, the hoses and the service port valves with workshop cleaning
wipe.
Remove the jumper from the low pressure control automatic reset switch. Replace the
wire nuts to the low pressure control automatic reset switch.
When opening and closing compressor service valves, make sure to use the right tools, such as
an appropriately sized service wrench. Do not attempt to open a service valve with an
adjustable wrench. You can easily round the valve stem edges, rendering the valve useless.
If the valve stem is difficult to open and appears to be stuck, lightly tap the end of the valve
stem with a hammer. This should open the valve. (Remember to loosen that packing gland nut
before attempting to open the valve stem!)
Remember to replace the service port cap and valve stem cap after closing the valve port and
removing your refrigeration gauges. These caps serve two purposes:
1. They help prevent a refrigerant leak; and
2. They prevent the threads on the service valve from being rusted over or otherwise
damaged.
When brazing either a suction or discharge service valve, make sure the valve is mid-seated
before brazing. If left in either the front-seated or back seated position, heat from brazing
can cause the inside plunger to weld to the seating area on the inside of the valve body.
When brazing, its best to wrap the service valve in a wet rag. This prevents the valve from
being overheated and damaged. Be sure not to allow water to enter the system.
Working with these valves is very simple. Just remember some basic rules for trouble-free
operation.