Vous êtes sur la page 1sur 320

beta

BETA Low-Voltage Circuit Protection

Catalog ET B1 2007

Seite 3

Electrical Installation from A to Z

ET_B1_2007_en.FH10 Wed Nov 29 11:37:27 2006

Catalogs for the division:


Electrical Installation Technology
ALPHA Distribution Boards and Terminal Blocks
ALPHA Small Distribution Boards, ET A1
Distribution Boards, Terminal Blocks
Order No.:
pdf only: (E86060-K8210-A101-A7-7600)
ALPHA 400-ZS Meter Cabinets

ET A2

Regional catalogs available on request


(available in German only)
BETA Low-Voltage Circuit Protection
ET B1
Order No.:
pdf only: (E86060-K8220-A101-A8-7600)
Technical Information

ET B1 T

Order No.:
pdf only: (E86060-K8229-A101-A8-7600)
GAMMA Building Controls
ET G1
Order No.:
E86060-K8230-A101-A6-7600
DELTA Switches and Socket Outlets
ET D1
Order No.:
pdf only: (E86060-K8240-A101-A7-7600)

Identification codes for fast orientation


New products not contained in the
previous catalogs

Ordering
Order nos., prices and weights generally apply
to the same quantity:
Units
Set or
Package
The package size (abbreviated as PS) specifies
the minimum quantity of a product to be ordered.
You can order this quantity or a multiple thereof.
The packing unit (abbreviated as P.unit) specifies the number of units, sets or packages in a
master carton.
Export regulations

The products listed in this catalog/price list may


be subject to European/German and/or US export regulations.
Therefore, any export requiring a license is subject to approval by the competent authorities.
According to current provisions, the following
export regulations must be observed with respect to the products featured in this catalog/
price list:
AL

Number of the German Export List


Products marked other than N require an
export license.
In the case of software products, the export
designations of the relevant data medium
must also be generally adhered to.
Goods labeled with an AL not equal to N
are subject to a European or German export
authorization when being exported outside
the EU.

ECCNNumber of the US Export List


(Export Control Classification Number).

The A&D Offline Mall

Products marked other than N are subject


to a reexport license in specific countries.

CA 01
Order No.:
E86060-D4001-A110-C5-7600 (CD-ROM)
E86060-D4001-A510-C5-7600 (DVD)

In the case of software products, the export


designations of the relevant data medium
must also be generally adhered to.

Internet
Visit our Automation and Drives Web site on the
Internet. You will find us at the following addresses
Automation and Drives:
http://www.siemens.com/automation
Electrical Installation Technology:
http://www.siemens.com/e-installation
for the A&D Mall:
http://www.siemens.com/automation/mall

Goods labeled ECCN not equal to N are


subject to US re-export authorization.

Even without a label, or with an AL: N or


ECCN: N authorization may be required due to
the final destination and purpose for which the
goods are to be used.
The deciding factors are the AL or ECCN export
authorization indicated on order confirmations,
delivery notes and invoices.
Errors excepted and subject to change without
prior notice.

BETA Protecting

Low-Voltage Fuse Systems

Semiconductor Fuses

Miniature Circuit-Breakers

BETA

Residual Current
Protective Devices

Low-Voltage
Circuit Protection

Lightning and
Overvoltage Protection Devices
BETA Switching

Switches and Light Indicators

Catalog ET B1 2007
4

Switching Devices
Supersedes: Catalog ET B1 2006
Timers

Transformers and
Socket Outlets

The products contained in this catalog are


also included in the Offline Mall CA 01
Order No.:
E86060-D4001-A110-C5-7600 (CD-ROM)
E86060-D4001-A510-C5-7600 (DVD)

BETA Measuring

Measuring Devices

BETA Monitoring

Monitoring Devices

Distribution
with Busbars

SR60 Busbar Systems

Busbars for Modular Installation


Devices
Modular Installation
Devices, Mounting Depth
55 mm >N<
Notes on Product
Changeover

The products and systems listed in this catalog


are manufactured using a quality management
system certified by BVQI and according to
EN ISO 9001:2000-12 (Certificate No. 117779)
Siemens AG 2006

Appendix

Siemens Automation and Drives.


Welcome

More than 60,000 people aiming for the same goal:


increasing your competitiveness. That's Siemens
Automation and Drives.
We offer you a comprehensive portfolio for sustained
success in your sector, whether you're talking automation engineering, drives or electrical installation systems. Totally Integrated Automation (TIA) and Totally
Integrated Power (TIP) form the core of our offering.
TIA and TIP are the basis of our integrated range of
products and systems for the manufacturing and process
industries as well as building automation. This portfolio
is rounded off by innovative services over the entire life
cycle of your plants.
Learn for yourself the potential our products and
systems offer. And discover how you can permanently
increase your productivity with us.
Your regional Siemens contact can provide more information. He or she will be glad to help.

Siemens ET B1 2007

Siemens ET B1 2007

Siemens Automation and Drives.


Welcome

More than 60,000 people aiming for the same goal:


increasing your competitiveness. That's Siemens
Automation and Drives.
We offer you a comprehensive portfolio for sustained
success in your sector, whether you're talking automation engineering, drives or electrical installation systems. Totally Integrated Automation (TIA) and Totally
Integrated Power (TIP) form the core of our offering.
TIA and TIP are the basis of our integrated range of
products and systems for the manufacturing and process
industries as well as building automation. This portfolio
is rounded off by innovative services over the entire life
cycle of your plants.
Learn for yourself the potential our products and
systems offer. And discover how you can permanently
increase your productivity with us.
Your regional Siemens contact can provide more information. He or she will be glad to help.

Siemens ET B1 2007

Siemens ET B1 2007

Sharpen your competitive edge.


Totally Integrated Automation

With Totally Integrated Automation (TIA), Siemens is the only


manufacturer to offer an integrated range of products and systems for automation in all sectors - from incoming goods to outgoing goods, from the field level through the production control
level to connection with the corporate management level.

It goes without saying that you profit from Totally Integrated


Automation during the entire life cycle of your plants - from the
first planning steps, through operation, right up to modernization. Consistent integration in the further development of our
products and systems guarantees a high degree of investment
security here.

On the basis of TIA, we implement solutions that are perfectly


tailored to your specific requirements and are characterized by a
unique level of integration. This integration not only ensures significant reductions in interface costs but also guarantees the
highest level of transparency across all levels.

ERP
Enterprise
Resource
Planning

MES
Manufacturing
Execution
Systems

Control

SIMATIC NET
Industrial
Communication

Totally Integrated Automation makes a crucial contribution


towards optimizing everything that happens in the plant and
thus creates the conditions for a significant increase in productivity.

Ethernet

Production
Order
Management

Material
Management

SINAUT Telecontrol
System

Production
Operations
Recording

SIMATIC
Software

Equipment
Management

Production Modeler

Detailed
Production
Scheduling

Laboratory Information
Management System

SIMATIC Controllers/
Automation System
SENTRON
Circuit
Breakers

SIMATIC PCS 7
Process Control System

SIMATIC HMI
Human Machine
Interface

PROFINET

SIMOTION
Motion Control
System

SINUMERIK
Computer
Numeric Control

Safety Integrated

PROFIBUS

Field Instrumentation /
Analytics

PC-based Automation

AS-Interface

KNX/EIB
GAMMA instabus

Product Specification
Management System

SIMATIC IT Framework

Ethernet

SIMATIC
Sensors

Industrial
Ethernet

Plant
Information
Management

Siemens ET B1 2007

HART

Building
Technology

Micro-Automation and
Aktor-Sensor Interface Level

ECOFAST IP65
Distributed
Automation System

SIMOCODE pro
Motor Management System

SIRIUS
Soft Starter

SIWAREX
Weighing
Technology

SIMATIC
Distributed
I/O

PROFIBUS PA

Drive Systems/
SINAMICS

SINAMICS

SIMODRIVE

Siemens ET B1 2007

SINAMICS

Sharpen your competitive edge.


Totally Integrated Automation

With Totally Integrated Automation (TIA), Siemens is the only


manufacturer to offer an integrated range of products and systems for automation in all sectors - from incoming goods to outgoing goods, from the field level through the production control
level to connection with the corporate management level.

It goes without saying that you profit from Totally Integrated


Automation during the entire life cycle of your plants - from the
first planning steps, through operation, right up to modernization. Consistent integration in the further development of our
products and systems guarantees a high degree of investment
security here.

On the basis of TIA, we implement solutions that are perfectly


tailored to your specific requirements and are characterized by a
unique level of integration. This integration not only ensures significant reductions in interface costs but also guarantees the
highest level of transparency across all levels.

ERP
Enterprise
Resource
Planning

MES
Manufacturing
Execution
Systems

Control

SIMATIC NET
Industrial
Communication

Totally Integrated Automation makes a crucial contribution


towards optimizing everything that happens in the plant and
thus creates the conditions for a significant increase in productivity.

Ethernet

Production
Order
Management

Material
Management

SINAUT Telecontrol
System

Production
Operations
Recording

SIMATIC
Software

Equipment
Management

Production Modeler

Detailed
Production
Scheduling

Laboratory Information
Management System

SIMATIC Controllers/
Automation System
SENTRON
Circuit
Breakers

SIMATIC PCS 7
Process Control System

SIMATIC HMI
Human Machine
Interface

PROFINET

SIMOTION
Motion Control
System

SINUMERIK
Computer
Numeric Control

Safety Integrated

PROFIBUS

Field Instrumentation /
Analytics

PC-based Automation

AS-Interface

KNX/EIB
GAMMA instabus

Product Specification
Management System

SIMATIC IT Framework

Ethernet

SIMATIC
Sensors

Industrial
Ethernet

Plant
Information
Management

Siemens ET B1 2007

HART

Building
Technology

Micro-Automation and
Aktor-Sensor Interface Level

ECOFAST IP65
Distributed
Automation System

SIMOCODE pro
Motor Management System

SIRIUS
Soft Starter

SIWAREX
Weighing
Technology

SIMATIC
Distributed
I/O

PROFIBUS PA

Drive Systems/
SINAMICS

SINAMICS

SIMODRIVE

Siemens ET B1 2007

SINAMICS

Integrated energy distribution from a single source.


Totally Integrated Power

Totally Integrated Power offers communication


and software modules for connecting the energy
distribution systems to industrial automation and
building automation. This enables the implementation of significant savings potential.

Totally Integrated Power (TIP) brings together all the components


of electrical energy distribution into an integrated whole. Thus TIP
provides the answer to growing market demands in the planning,
construction and use of utility buildings and industrial buildings.
On the basis of TIP, we offer integrated solutions for energy distribution, from medium voltage to the power outlet. Totally Integrated Power is based here on integration in planning and configuring as well as on perfectly matched products and systems.

Communication

Load
management

HMI

Graphs

Prognoses

Maintenance
Substation
Distribution
Maintenance
task

Message/
error
management

Selective
protection

Protocols

Power
quality

DATE:
EMPLOYEE

Cost center

Building
automation

COST CENTER
PAY PERIOD BEGINNING
PAY PERIOD ENDING

DATE
SUN

MON

TUE

WED

THUR

FRI

SUN

MON

TUE

WED

THUR

FRI

SUN

MON

TUE

WED

THUR

FRI

SAT

SUN

TOTAL

IN
OUT
IN
OUT
OVERTIME

TOTAL HOURS
DATE
SAT

SUN

TOTAL

IN

Process/production
automation

OUT

UI
I cos o
P o
cos
PW
W

IN

Hall 1
Distribution 3
Infeed II

Air conditioning system


checkup
Replacing circuit
breaker contacts
Replacing meters

OUT
OVERTIME

TOTAL HOURS

central ON
OFF
local ON
OFF
tripped

DATE
SAT

SUN

TOTAL

IN
OUT
IN
OUT
OVERTIME

TOTAL HOURS
CODES
V=VACATION
H=HOLIDAY
S=SICK

REGULAR

HOLIDAY

OTHER

OVER THE HOURS


TIME & ONE-HALF

SICK

VACATION

PROCESS FIELD BUS

instabus EIB

Products and systems

110 kV

Planning
and configuration

Siemens ET B1 2007

Siemens ET B1 2007

Integrated energy distribution from a single source.


Totally Integrated Power

Totally Integrated Power offers communication


and software modules for connecting the energy
distribution systems to industrial automation and
building automation. This enables the implementation of significant savings potential.

Totally Integrated Power (TIP) brings together all the components


of electrical energy distribution into an integrated whole. Thus TIP
provides the answer to growing market demands in the planning,
construction and use of utility buildings and industrial buildings.
On the basis of TIP, we offer integrated solutions for energy distribution, from medium voltage to the power outlet. Totally Integrated Power is based here on integration in planning and configuring as well as on perfectly matched products and systems.

Communication

Load
management

HMI

Graphs

Prognoses

Maintenance
Substation
Distribution
Maintenance
task

Message/
error
management

Selective
protection

Protocols

Power
quality

DATE:
EMPLOYEE

Cost center

Building
automation

COST CENTER
PAY PERIOD BEGINNING
PAY PERIOD ENDING

DATE
SUN

MON

TUE

WED

THUR

FRI

SUN

MON

TUE

WED

THUR

FRI

SUN

MON

TUE

WED

THUR

FRI

SAT

SUN

TOTAL

IN
OUT
IN
OUT
OVERTIME

TOTAL HOURS
DATE
SAT

SUN

TOTAL

IN

Process/production
automation

OUT

UI
I cos o
P o
cos
PW
W

IN

Hall 1
Distribution 3
Infeed II

Air conditioning system


checkup
Replacing circuit
breaker contacts
Replacing meters

OUT
OVERTIME

TOTAL HOURS

central ON
OFF
local ON
OFF
tripped

DATE
SAT

SUN

TOTAL

IN
OUT
IN
OUT
OVERTIME

TOTAL HOURS
CODES
V=VACATION
H=HOLIDAY
S=SICK

REGULAR

HOLIDAY

OTHER

OVER THE HOURS


TIME & ONE-HALF

SICK

VACATION

PROCESS FIELD BUS

instabus EIB

Products and systems

110 kV

Planning
and configuration

Siemens ET B1 2007

Siemens ET B1 2007

Totally Integrated Power


BETA Low-Voltage Circuit-Protection Devices
in this Catalog

You can totally rely on the BETA low-voltage circuit-protection devices.


Siemens offers a broad range of mutually compatible devices for line protection, personnel and fire protection, lightning current and overvoltage protection and device and plant protection. This provides an absolute maximum of
flexibility, convenience and safety for building installations and industrial
systems.
Our device range comprises all the protective devices required for an all round
protection concept, such as fuses, miniature circuit-breakers, residual current
protection equipment and overvoltage protection devices, as well as switching devices, measuring and monitoring devices. We are renowned leaders in
technology for residual current protection equipment and have the broadest
device spectrum of fuses.

BETA Low-Voltage Circuit Protection


BETA protecting

< 4 kV

Selective
line protection

Personnel and
fire protection

< 1,5 kV < 1,3 kV

Overvoltage
protection

Fuses

TYPE 1 surge arresters

BETA protecting

BETA switching

BETA measuring
Measuring devices

Distribution
boards

BETA monitoring

I201_13504

Fuse monitors

Siemens ET B1 2007

The remote monitoring of electric measured values for the capacity utilization
of a distribution board are essential for the safe and reliable supply of electrical power. Monitoring and switching options on the move from a cell phone
using the GSM alarm module further increase the availability of plants. And
the monitoring of voltage and switchover to an emergency supply for lighting
systems ensures the safety of all those in the building.
This catalog contains all the devices currently available for mounting in distribution boards or similar options for mounting on 35 mm standard mounting
rails in switchgear cabinets.

BETA switching

Residual-current
operated
circuit-breakers

BETA measuring

TYPE 2 surge
arresters

BETA monitoring

Miniature
circuitbreakers

TYPE 3 surge
arresters

LAN
GSM
Residual current
components

Line protection
components

Switching
devices
Socket outlets

Communication

Line protection
components

Monitoring
devices
I201_13505

Residual current
components

Siemens ET B1 2007

ALPHA distribution boards and terminal blocks


The ALPHA range comprises small distribution boards, meter cabinets,
wall and floor-mounted distribution boards and molded-plastic distribution boards. The ALPHA FIX terminal blocks meet all your needs for clear
and manageable wiring using a full range of connection methods.

BETA low-voltage circuit protection


Siemens offers an optimally coordinated device range for line protection,
personnel and fire protection, lightning and overvoltage protection,
device and plant protection.
Based on an allround protection concept, our device range offers a complete spectrum of protection devices, such as fuses, miniature circuitbreakers, residual current-operated circuit-breakers and surge suppressors, as well as switching devices, measuring instruments and monitoring devices.
GAMMA building controls
The innovative GAMMA instabus building controls lets you increase
safety and convenience and maximize efficiency. GAMMA instabus
controls lighting, shading and room temperature. All the electrical
functions of a building can be intelligently integrated into the system.
Connection to other systems of a building, such as LAN, opens up a
whole new world of applications. A key feature of GAMMA instabus is its
great flexibility.
DELTA switches and socket outlets
The DELTA switch and socket outlet range combines a wide range of different design interfaces with more innovative and safe technology. And
because the operator interfaces are simple to interchange, you can enjoy complete safety even when your taste or the environment changes.

10

Siemens ET B1 2007

Siemens electrical installation:


the world of electrical installation technology
These days, it's hard to imagine daily life without electricity.
Modern electrical switching and installation technology is an essential requirement for ensuring that our use of electricity is safe and user-friendly.
Innovative from the outset
The Siemens electrical installation technology group has been working in
this sector for more than 110 years and we are constantly developing new
products innovations, which make the use of electricity increasingly safer
and more cost effective. Ideal for residential, non-residential or industrial
buildings. According to all internationally valid regulations and standards.
Using new technologies, such as instabus EIB we have opened up new horizons in the area of private housing. In addition, we are also building bridges
between factory automation and building management in the industrial and
non-residential building sector.
Quality you can rely on
All our products are subject to the most rigorous quality specifications during
production and testing. And we ensure strict compliance with these specifications in order to offer our customers nothing but the very best. Our numerous certificates are further confirmation of our endeavors in this respect.
The quality of a product is largely determined in its development phase.
From the very outset, reliability demands and the accompanying quality
assurance measures are defined and incorporated in the design.
The first quality inspections are already run on the pilot and test series.

BETA low-voltage circuit protection provides solutions in all areas:

Industrial buildings

Non-residential buildings

Residential buildings

Siemens ET B1 2007

11

Electrical Installations from


Regensburg and Across the Globe
Our factory in Regensburg
The Regensburg device factory is now one of the world's leading
manufacturers of installation devices and systems. Since it was
founded in 1948 it has become one of the largest employers of the
region and currently boasts a staff of around 1,500 employees.
Development is carried out using cutting-edge tools such as CAD, simulation and automated laboratory equipment. It goes without saying
that our devices offer complete electromagnetic compatibility as
the proportion of electronic devices in electrical installationt technology is constantly on the increase. This is particularly noticeable in building control systems.
Our products are subject to the harshest conditions: the technology
used is tried and tested and ensures complete functional reliability.
Circuit-breakers must comply with national and international regulations. During testing, our devices are subjected to considerably higher
demands than those defined in the regulations. For our customers,
this means rugged and long-lasting devices that provide maximum reliability and ease of operation.
Environmentally-friendly products and production methods
We make every endeavor to ensure that our production methods are
environmentally friendly. This has already been rewarded with several environment awards for outstanding services rendered to environment protection and nature conservation. We do not use substances
that are harmful to the environment, such as lead, mercury, cadmium,
hexavalent chromium compounds, PBB or PBDE Our switches and
socket outlets have been cadmium-free for more than a decade. Once
again, Siemens is a pioneer in its field.

12

Siemens ET B1 2007

El Paso (USA)
Juarez (USA)
I201_13388

Wythenshawe (UK)
Drummondville (Canada)

regrund (Sweden)

Regensburg (Germany)
Cham (Germany)
Sibiu (Romania)
Kartal (Turkey)
Vassilikon Eube (Greece)

Chase Road
(UK)

Spartanburg (USA)

Shanghai (China)
Aurangabad (India)

Manaus (Brazil)

Canoas (Brazil)
I201_13389a

Branches worldwide
The products developed here are
manufactured not just in Regensburg
but worldwide in our factories.
These products (and systems) prove
their high performance, quality and
reliability on a daily basis.

Siemens ET B1 2007

13

Services

Always up-to-date high quality training


Knowledge is the key to success:
our seminars help you create the basis
for a successful business.
In our modern training center in Regensburg the first one to be certified by EIBA
or at a range of other locations, our expert
training staff will help you acquire the necessary theoretical and practical know-how
to succeed. Clearly structured and with
multimedia teaching tools. Available in
German and English.
Step-by-step, you will be familiarized with
Siemens instabus applications from configuration, commissioning and assembly,
through to the implementation of sophisticated customer solutions.
Please note: our seminars cover all levels
and are designed to meet all requirements.
From PC beginner courses through to special courses for instabus experts. Our individual support guarantees a successful
seminar: the courses are for a limited number of participants and optimum attention is
paid to your individual requirements for
maximum success and a minimum investment of your valuable time. If required, we
can also hold in-house courses at your
company's premises.
Please do not hesitate to contact us.

Tel.: +49 (0)941 790 2950


E-Mail: cscet.aud@siemens.com

Training and sales advice

14

Siemens ET B1 2007

Save time with planning aids

Comprehensive service and


support

Information material and


contacts

Whether you are an installation en-

You can rely on Siemens technology

If you require any further information,

gineer, planner or switchgear engi-

as well as on our services and sup-

we have a wide range of information

neer we have tools that help you

port. We offer assistance in all mat-

material for you and your customers:

plan the layout of your distribution

ters: from the planning of your electri-

an overview of our versatile switches

boards and meter cabinets. And that

cal installation technology, to training,

and outlets, our building control sys-

gives you more time to spend on

to marketing, advertising and public

tems and our modular installation

other projects.

relations.

devices and distribution boards. If


you have any queries, requirements

Tel.: +49 (0)180 50 50 222

or suggestions: just call.

Fax: +49 (0)180 50 50 223

Tel.: +49 (0)911 895 5900

E-Mail:
technical-assistance@siemens.com

Fax: +49 (0)911 895 5907


E-Mail:
technical-assistance@siemens.com
http://www.siemens.com/
e-installation

ALPHA configuration software

Personal support

Comprehensive information material for you and


your customers
Siemens ET B1 2007

15

Simple Labeling

A new software tool means it has never been


easier to label your switches, distribution boards
and modular installation devices.
The new PC-based inscription tool serves the
inscription of label inserts, forms and other documentation of the relevant products from the following segments: ALPHA (distribution boards and

interface, users can change the layout and format of


the required text. You can even upload and edit
preprepared texts. The tool also allows users to insertsymbols, special characters and even images to
improve the clarity of the inscription.

terminal blocks), BETA (low-voltage circuit pro-

Once the required number of labels has been set, the

tection), GAMMA (building controls) and DELTA

pages can be printed out on a standard printer onto a

(switches and socket outlets).

prepunched adhesive film or simply on DIN A4 paper

The inscription tool is a software that supports users


when labeling meter cabinets, wall-mounted and floormounted distribution boards, modular installation de-

and used immediately. So it couldn't be easier to label


any number of distribution boards, socket outlets or
switches.

vices or the relevant components from the switch and

This inscription tool is available free of charge and can

socket outlet systems and socket outlets segment. A

be downloaded on the Internet in either English or

key feature of this tool is its extremely simple and user-

German. The software runs on all the more recent

friendly operator guidance. A single operator interface

versions of the Microsoft operating system. The oper-

gives users access to all the relevant products of the

ator guidance helps users to install the inscription tool

ALPHA, BETA, GAMMA and DELTA ranges. The

without any problems. For easy application, an icon is

relevant forms and products are integrated in the tool

automatically placed on the desktop.

complete with images and can be called up as

You can download the inscription tool at:

needed.

http://www.automation.siemens.com/et/html_00/

Load, label, print

support/label_tool.htm

The catalog search facility lets you call up the products

For further practical tips:

of the desired product range as and when required. In


this way, for example, you can display the user interfaces of the DELTA i-system. A simple mouse click
imports the image of the selected switch to be labeled
to the editing area. The surfaces that can be labeled
are highlighted. So users can see immediately where

16

the text will be. On the right-hand side of the user

Siemens ET B1 2007

http://www.automation.siemens.com/et/html_00/
support/praxistipps.htm

A single operator interface gives users access to all the relevant products of the ALPHA, BETA, GAMMA and
DELTA ranges. The relevant catalogs with images of the devices and systems are integrated in the tool and can
be called up as needed.

Siemens ET B1 2007

17

I2_13442

Four ways to success:


BETA Low-Voltage Circuit Protection

Low-Voltage
Fuse Systems
Miniature CircuitBreakers
Residual Current
Protective Devices

Switches and
Light Indicators
Switching Devices

protecting

Monitoring of:

Multimeters

Voltage,

Multicounters

Timers

Power Supply Units

E-counters

Current, Fuses,
Insulation, Faults,

Current Transformers

Lightning and Surge


Arresters

BETA

Measuring
Devices

BETA

BETA

switching

measuring

Phases, Direction of Rotation


Temperature, Light

Four routes to

18

Siemens ET B1 2007

BETA
monitoring

S uccess.

BETA low-voltage circuit-protection devices


for any

B uilding.

Siemens ET B1 2007

19

New Developments

Miniature circuit-breakers with plug-in terminals


Quick-fit in double-quick time: 3-pole version now available.
This device is aimed especially at the residential sector.
These plug-in terminals offer easy front connection for
manual insertion of conductors.
Further details can be found in the
chapter "Miniature circuit-breakers"

Miniature circuit-breakers according to UL 489


Off to new horizons: Miniature circuit-breakers for applications in IEC and NEMA applications. Suitable for universal
use for branch circuit protection in 240/120 V AC systems
Further details can be found in the
chapter "Miniature circuit-breakers"

SIQUENCE, UC sensitive
RCBO, type B, up to 125 A
We have a handle on all types of residual current:
UC sensitive residual current operated
circuit-breakers with integral overcurrent protection (RCBOs) for maximum
plant availability thanks to our complete all round protection. Selective
version now also available for use as
an upstream group switch.
Further details can be found in the
chapter "Residual current protective
devices".
Lightning and overvoltage protection devices
Damage and consequential costs can be prevented:
our devices for inner lightning current and overvoltage
protection provide reliable
protection for plants,
high-quality products and
industrial goods.
Further details can be
found in the chapter
"Lightning and overvoltage protection devices"

20

Siemens ET B1 2007

Remote control switches with ZA and ZE function


Safety at work: Our remote control range has been
expanded with new functions, such as central ON,
central OFF and series connections. Auxiliary
switches can also be mounted.
Further details can be found in the chapter
"Switching devices"

Switching relays
Safety at work: switching relays are used for contact
multiplication. They can be used with safe isolation
between coil voltage and contact. Busbar
mounting also with remote control switches
facilitates installation.

Insta contactors with AC magnetic system


The right device for every application: with an extremely
long service life of 3 million switching cycles. Particularly
suitable for switching heating, lighting
and motors. Auxiliary switches can be
mounted on all models.

Further details can be found in the chapter


"Switching devices"

Further details can be found in the


chapter "Switching devices"

Insta contactors with manual switching


Manual intervention possible at any time: same features
as Insta contactors with AC magnetic system, enhanced
with manual switching option.
With switching position indicator for
fast recognition of operating state.

Digital time switches


So much more than a time switch: save time with these
time switches thanks to their extremely intuitive menudriven handling, text-assisted programming
with logical 4 pushbutton system and easy
user guidance. User-friendly programming
at the PC.

Further details can be found in the


chapter "Switching devices"

Mechanical time switches


So much more than a time switch: easy commissioning
thanks to automatic makeready system even after a
power failure and automatic daylight
savings. High clock accuracy thanks to
precision quartz clock mechanism.
Further details can be found in the
chapter "Timers"

Further details can be found in the chapter


"Timers"

GSM alarm module


Mobile monitoring and control: global, mobile monitoring
and operation of plants for greater safety, reliability and
convenience. Simplest installation and operation per SMS.
Plants can be remotely switched
and messages received.
Further details can be found in
the chapter "Monitoring devices".

Siemens ET B1 2007

21

BETA
Protecting
Line
protection

Line
protection

Personnel and
fire protection

Lightning and
overvoltage
device protection

Time
switching

Power supply

BETA
Switching
Manual and
electrical
switching

BETA
Measuring
Measuring

BETA
Monitoring
Monitoring

BETA Low-Voltage Circuit Protection


This is a range you can truly rely on: the BETA low-voltage cir-

And we have expanded this range even further to include

cuit protection range. It offers a uniquely consistent product

new components with expanded functionality and an even

range of control, switching and circuit-protection devices.

greater selection of types.

Whether for fuse systems, miniature circuit-breakers, residual

7 This supports an absolute maximum of flexibility,

current protective devices or overvoltage protection every-

convenience and safety for building management and

thing is complete, compatible and clearly arranged.

industrial applications.

22

Siemens ET B1 2007

Low-Voltage
Fuse Systems

NEOZED Fuse Systems

1/2
1/3
1/7
1/8

NEOZED fuse links


NEOZED fuse bases
NEOZED fuse disconnectors
MINIZED switch disconnectors

DIAZED Fuse Systems

1/10
1/12

DIAZED fuse links


DIAZED fuse bases

LV HRC Fuse Systems

1/16
1/22
1/26
1/27

LV HRC fuse links gG


LV HRC fuse bases
LV HRC signal detectors
LV HRC fuse switch disconnectors

Cylindrical Fuse Systems

1/46
1/47

Cylindrical fuse links gG


Bases for cylindrical fuses

Fuse Links
for Motor Circuits

1/48
1/49

LV HRC fuse links aM


Cylindrical fuse links aM

American/Canadian
Class CC Fuses

1/50

Class CC fuse links and


fuse holders

1/1

Low-Voltage Fuse Systems


NEOZED Fuse Systems
NEOZED fuse links

Selection and ordering data


Size

In

Identification
color

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

Rated voltage 400 V AC/250 V DC, gG operational class


Consumer packings, pack of 10
D01

2
4
6
10
13
16

pink
brown
green
red
black
gray

5SE2 302
5SE2 304
5SE2 306
5SE2 310
5SE2 013-2A
5SE2 316

016
016
016
016
016
016

0.006
0.006
0.006
0.007
0.007
0.007

10
10
10
10
10
10

D02

20
25
32
35
40
50

blue
yellow
black
black
black
white

5SE2 320
5SE2 325
5SE2 332
5SE2 335
5SE2 340
5SE2 350

016
016
016
016
016
016

0.012
0.013
0.014
0.014
0.014
0.015

10
10
10
10
10
10

copper

5SE2 363

016

0.016

10

D03

80
100

silver
red

5SE2 280
5SE2 300

016
016

0.039
0.042

10
10

20
25

blue
yellow

5SE2 820
5SE2 825

016
016

0.011
0.012

10
10

63

Versions for Italy only (no approvals)


D01

1/2

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


NEOZED Fuse Systems
NEOZED fuse bases

Selection and ordering data


Size

In

Matching
cover

Terminals1)

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit

0.123
0.120

1
1

Units

Fuse bases, molded plastic, with touch protection acc. to BGV A3 (VBG4)
1-pole
with combined terminal, can be busbar mounted
D01
D02

16
63

FR2

1.5

5SG1 301
5SG1 701

016
016

1
2
3
4
5

3-pole
with combined terminal, can be busbar mounted
D01
16

FR2
D02
63

4.5

5SG5 301
5SG5 701

016
016

0.371
0.360

1
1

6
7

1-pole
with cover
D01
D02

16
63

(A1)
(A1)

FR0/R
FR0/R

1.5
1.5

5SG1 330
5SG1 730

016
016

0.068
0.087

6
6

D01
D02

16
63

A1
A1

FR0/R
FR0/R

1.5
1.5

5SG1 331
5SG1 731

016
016

0.056
0.080

6
6

without cover

9
10

3-pole
with cover
D01
D02

16
63

(A2)
(A2)

FR0/R
FR0/R

4.5
4.5

5SG5 330
5SG5 730

016
016

0.216
0.252

2
2

11

(A1) means that the fuse base is supplied with cover as standard.
A1 means that the fuse base is supplied without cover,
The cover can be ordered separately as a spare part.

12

For busbars for NEOZED fuse bases, see chapter "Busbars for
modular installation devices".
1)

For terminal versions, see Catalog ET B1 T.

13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/3

17

Low-Voltage Fuse Systems


NEOZED Fuse Systems
NEOZED fuse bases
Size

In

Matching
cover

Terminals1)

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

Fuse bases made of ceramic


1-pole
with cover
D01
D02
D02

16
63
63

(A4)
(A10)
(A10)

BB
SS
KS

1.5
1.5
1.5

5SG1 553
5SG1 653
5SG1 693

016
016
016

0.083
0.093
0.090

6
6
6

D01
D02
D02
D03

16
63
63
100

A4
A10
A10
A6, A9

BB
SS
KS
KS

1.5
1.5
1.5
2.5

5SG1 595
5SG1 655
5SG1 695
5SG1 812

016
016
016
016

0.071
0.081
0.078
0.176

6
6
6
10

without cover

for screw connection only, without cover


D01
D02
D03

16
63
100

A4
A10
A6, A9

BB
SS
KS

1.5
1.5
2.5

5SG1 590
5SG1 650
5SG1 810

016
016
016

0.061
0.078
0.176

6
6
10

D01
D02
D03

16
63
100

(A8)
(A8)
(A9)

BB
SS
KS

1.5
1.5
2.5

5SG1 594
5SG1 694
5SG1 813

016
016
016

0.105
0.115
0.242

6
6
10

D01
D02
D02

16
63
63

(A5)
(A11)
(A11)

BB
SS
KS

4.5
4.5
4.5

5SG5 553
5SG5 653
5SG5 693

016
016
016

0.263
0.240
0.290

2
2
2

D01
D02
D02

16
63
63

A5
A11
A11

BB
SS
KS

4.5
4.5
4.5

5SG5 555
5SG5 655
5SG5 695

016
016
016

0.228
0.265
0.255

2
2
2

for screw connection only, without cover


D01
16
A5
D02
63
A11
D02
63
A11

BB
SS
KS

4.5
4.5
4.5

5SG5 550
5SG5 650
5SG5 690

016
016
016

0.228
0.260
0.250

2
2
2

with cap

3-pole
with cover

without cover

(A4) means that


the fuse base is supplied with cover as standard.
A4 means
that the fuse base is supplied without cover, the cover can be ordered
separately as a spare part.

For busbars for NEOZED fuse bases, see chapter "Busbars for
modular installation devices".
1)

For terminal version, see Catalog ET B1 T.

1/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


NEOZED Fuse Systems
NEOZED fuse bases

Accessories
MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

NEOZED covers made of molded plastic


for fuse bases made of molded plastic
cover A1 (for sizes D01, D02), clip-on

1.5

5SH5 244

016

0.008

cover A2 (for sizes D01, D02), clip-on

4.5

5SH5 245

016

0.017

1
2
3
4
5
6
7

for fuse bases made of ceramic


cover A4 (for size D01), clip-on
cover A10 (for size D02), clip-on

1.5
1.5

5SH5 251
5SH5 253

016
016

0.012
0.020

15
15

cover A5 (for size D01), clip-on


cover A11 (for size D02), clip-on

4.5
4.5

5SH5 252
5SH5 254

016
016

0.035
0.045

5
5

cover A6 (for size D03), screw-on

2.5

5SH5 233

016

0.021

20

5SH5 235
5SH5 234

016
016

0.034
0.066

5
10

PG

Weight
1 unit
approx.

PS*
P. unit

8
9

NEOZED caps made of molded plastic


cover A8 (for sizes D01, D02), clip-on
cover A9 (for size D03), screw-on

Version/size

Order No.

Busbar adapters
for clipping onto busbars
12 mm 5 mm, with 40 mm center clearance,
device width 4.5 MW,
with connecting cables, 3 mm 16 mm2 for rated current 63 A,
for mounting of modular installation devices

5SH5 503

Price

1 unit
016

10

kg

Units

0.280

11
12
13

busbar adapter for clipping onto busbars with 60 mm center


clearance, see SR60 busbar system
NEOZED screw caps
molded plastic, with inspection hole
D01
D02
ceramic

5SH4 116
5SH4 163

016
016

0.007
0.008

10/1000
10/1000

D01, sealable
D02, sealable
D03
ceramic, with inspection hole

5SH4 316
5SH4 363
5SH4 100

016
016
016

0.014
0.015
0.070

10
10
3

D01
D02

5SH4 317
5SH4 362

016
016

0.014
0.017

20
20

14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/5

17

Low-Voltage Fuse Systems


NEOZED Fuse Systems
NEOZED fuse bases
Size

For fuse

Identification
color

Order No.

up to A

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

NEOZED adapter sleeves


D01

2
4
6
10/13

pink
brown
green
red

5SH5 002
5SH5 004
5SH5 006
5SH5 010

016
016
016
016

0.001
0.001
0.001
0.001

10
10
10
10

D02

20
25
32/35/40

blue
yellow
black

5SH5 020
5SH5 025
5SH5 035

016
016
016

0.001
0.001
0.001

10
10
10

50

white

5SH5 050

016

0.001

10

80

silver

5SH5 080

016

0.001

10

5SH5 402
5SH5 404
5SH5 406
5SH5 410
5SH5 416

016
016
016
016
016

0.001
0.001
0.001
0.001
0.001

10
10
10
10
10

5SH5 100

016

0.016

1/10

5SH5 400

016

0.001

25

5SH5 417

016

0.001

25

D03

for adaptation of NEOZED D01 fuse links from 2 A ... 16 A for insertion in
NEOZED bases D02
D02

2
4
6
10/13
16

pink
brown
green
red
gray

NEOZED adapter sleeve fitters

NEOZED retaining springs


for adaptation of NEOZED screw caps D02
for insertion of NEOZED fuse links D01
D02

2 ... 16

for application in the five new German Laender, for adaptation


of DL screw caps to insert NEOZED fuse links D01 in DL bases.
DL
2 ... 16

For busbars for NEOZED fuse bases, see chapter "Busbars for modular installation devices".

1/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


NEOZED Fuse Systems
NEOZED fuse disconnectors

Selection and ordering data


Number of
poles

In

Terminals

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

D01, draw-out technology


1

16

FR1

5SG7 610

016

0.070

1+N

16

FR1

5SG7 650

016

0.150

16

FR1

5SG7 620

016

0.150

16

FR1

5SG7 630

016

0.220

3+N

16

FR1

5SG7 660

016

0.300

2
1 N

6
7

2 4
1 3 5

2 4 6
1 3 5 N

3
4
5

2 N
1 3

1
2

2 4 6 N

For busbars for NEOZED fuse disconnectors, see chapter "Busbars for
modular installation devices".

9
10
11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/7

17

Low-Voltage Fuse Systems


NEOZED Fuse Systems
MINIZED switch disconnectors

Selection and ordering data


Number of
poles

In

Terminals

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

D01, draw-out technology, mounting depth 55 mm


for rail mounting
Anti-slip terminal at incoming and outgoing feeder
1
2

16

Version for Italy only (no approvals)


25

5SG7 713

016

0.080

5SG7 713-1B

016

0.080

5SG7 753

016

0.150

5SG7 753-1B

016

0.150

5SG7 723

016

0.160

5SG7 723-1B

016

0.160

5SG7 733

016

0.254

5SG7 733-1B

016

0.254

5SG7 763

016

0.310

5SG7 763-1B

016

0.310

1
2 N

1+N
16
R
Version for Italy only (no approvals)
25

1 N
2 4

16

Version for Italy only (no approvals)


25
1 3
2 4 6

3
16
R
Version for Italy only (no approvals)
25

3+N

1 3 5
2 4 6 N

16

Version for Italy only (no approvals)


25
1 3 5 N

D02, draw-out technology, mounting depth 70 mm


for rail mounting
N-conductor is leading for switch-on and delayed for switch-off
Anti-slip terminal at incoming and outgoing feeder
Enclosure, knob
Silicone-free, chlorine-free
Heat-resistant up to 140 C
Self-extinguishing acc. to UL 94
Creep resistance CTI 200
Fuse-carrier

Silicone-free, halogen-free
Heat-resistant up to 150 C
Self-extinguishing acc. to UL 94
1

63

FR2

1.5

5SG7 113

016

0.145

1+N

63

FR2

5SG7 153

016

0.267

63

FR2

5SG7 123

016

0.283

63

FR2

4.5

5SG7 133

016

0.421

25
35

5SG7 133-8BA25
5SG7 133-8BA35

016
016

0.420
0.420

1
1

50

5SG7 133-8BA50

016

0.420

5SG7 163

016

0.540

2
1 N

2 N
1 3

2 4
1 3 5

Versions for Austria only (with permanently fitted


adapter sleeves, incl. fuse link)
2 4 6

1 3 5 N

3+N

63

FR2

2 4 6 N

For busbars for MINIMIZED switch disconnectors, see chapter


"Busbars for modular installation devices".

1/8

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


NEOZED Fuse Systems
MINIZED switch disconnectors

Accessories
Size

Contact load

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit

0.050

Units

For MINIZED D02, draw-out technology, mounting depth 70 mm


Auxiliary switches
For indication of switching state of the switch disconnector
Can be retrofitted individually using factory-fitted brackets
1 NO + 1 NC
Mounting width 0.5 MW
Min. contact load
Max. contact load
NO contacts

AC-14, 2 A, 400 V AC
AC-14, 6 A, 230 V AC
DC-13, 1 A, 220 V DC
DC-13, 1 A, 110 V DC
DC-13, 3 A, 60 V DC
DC-13, 6 A, 24 V DC
AC-13, 2 A, 400 V AC
AC-13, 6 A, 230 V AC
DC-13, 1 A, 220 V DC
DC-13, 1 A, 110 V DC
DC-13, 3 A, 60 V DC
DC-13, 6 A, 24 V DC

Size

For fuse

Identification
color

6
7
Order No.

PG

Weight
1 unit
approx.
kg

PS*
P. unit

5SH5 527

016

0.003

10/100

up to A

NEOZED adapter sleeve fitters

Price

1 unit

Reducers
for insertion of NEOZED fuse links, size D01 in
MINIZED switch disconnectors, size D02

D02

3
4

50 mA, 24 V

NC contacts

NEOZED adapter sleeves


D01

027

5ST3 010

1
2

Units

8
9

2
4
6

pink
brown
green

5SH5 402
5SH5 404
5SH5 406

016
016
016

0.001
0.001
0.001

10
10
10

10/13
16

red
gray

5SH5 410
5SH5 416

016
016

0.001
0.001

10
10

20
25
32/35/40
50

blue
yellow
black
white

5SH5 020
5SH5 025
5SH5 035
5SH5 050

016
016
016
016

0.001
0.001
0.001
0.001

10
10
10
10

5SH5 100

016

0.016

1/10

10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/9

17

Low-Voltage Fuse Systems


DIAZED Fuse Systems
DIAZED fuse links

Selection and ordering data


Size

Identification
color

In

Thread

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

Rated voltage 500 V AC/500 V DC


DIN VDE 0635
Characteristic: slow
TNDz

Characteristic: quick
NDz

2
4
6

pink
brown
green

10
16
20
25

red
gray
blue
yellow

2
4
6

pink
brown
green

10
16
20
25

red
gray
blue
yellow

2
4
6

pink
brown
green

E16

E16

5SA2 11
5SA2 21
5SA2 31

016
016
016

0.013
0.013
0.013

10
10
10

5SA2 51
5SA2 61
5SA2 71
5SA2 81

016
016
016
016

0.013
0.013
0.015
0.016

10
10
10
10

5SA1 11
5SA1 21
5SA1 31

016
016
016

0.013
0.013
0.013

10
10
10

5SA1 51
5SA1 61
5SA1 71
5SA1 81

016
016
016
016

0.013
0.013
0.015
0.016

10
10
10
10

5SB2 11
5SB2 21
5SB2 31

016
016
016

0.026
0.026
0.026

5
5
5

DIN VDE 0636-301, IEC 60269-3-1


Operational class gG
DII

DIII

DIV1)

E27

10

red

5SB2 51

016

0.027

16
20
25
32
35
50
63

gray
blue
yellow
black
black
white
copper

5SB2 61
5SB2 71
5SB2 81
5SB4 010
5SB4 11
5SB4 21
5SB4 31

016
016
016
016
016
016
016

0.028
0.029
0.031
0.048
0.050
0.051
0.054

5
5
5
5
5
5
5

80
100

E33

silver
red

R1"

5SC2 11
5SC2 21

016
016

0.110
0.110

3
3

2
4
6
10
10

pink
brown
green
red
red

E27

5SB1 11
5SB1 21
5SB1 31
5SB1 41
5SB1 51

016
016
016
016
016

0.026
0.026
0.026
0.026
0.027

5
5
5
5
5

16
20
25

gray
blue
yellow

5SB1 61
5SB1 71
5SB1 81

016
016
016

0.028
0.029
0.031

5
5
5

35
50
63
80
100

black
white
copper
silver
red

5SB3 11
5SB3 21
5SB3 31
5SC1 11
5SC1 21

016
016
016
016
016

0.050
0.051
0.054
0.110
0.110

5
5
5
3
3

DIN VDE 0635


quick
for 5SB1 41 a DIAZED screw adapter
for 6 A is used
DII

DIII

DIV
1)

E33

R1"

Rated voltage 500 V AC/400 V DC.

1/10

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


DIAZED Fuse Systems
DIAZED fuse links
Size

Identification
color

In

Thread

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

Rated voltage 690 V AC/600 V DC


DIN VDE 0636-301, IEC 60269-3-1
Operational class gG,
for fuse links 2 A ... 25 A,
DIAZED screw adapters DII are used
DIII
2
pink
4
brown
6
green

E33

5SD8 002
5SD8 004
5SD8 006

016
016
016

0.068
0.068
0.068

5
5
5

10
16

red
gray

5SD8 010
5SD8 016

016
016

0.068
0.069

5
5

20
25
35
50
63

blue
yellow
black
white
copper

5SD8 020
5SD8 025
5SD8 035
5SD8 050
5SD8 063

016
016
016
016
016

0.071
0.072
0.078
0.080
0.082

5
5
5
5
5

5SD6 01
5SD6 02
5SD6 03

016
016
016

0.068
0.068
0.068

5
5
5

5SD6 04
5SD6 05
5SD6 06
5SD6 07
5SD6 08
5SD6 10
5SD6 11

016
016
016
016
016
016
016

0.068
0.069
0.071
0.072
0.078
0.080
0.082

5
5
5
5
5
5
5

6
7

DIN VDE 0635


for direct current railway facilities,
quick
for fuse links 2 A ... 25 A,
DIAZED screw adapters DII are used
2
4
6

pink
brown
green

10
16
20
25
35
50
63

red
gray
blue
yellow
black
white
copper

E33

3
4
5

Rated voltage 750 V AC/750 V DC

DIII

1
2

8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/11

17

Low-Voltage Fuse Systems


DIAZED Fuse Systems
DIAZED fuse bases

Selection and ordering data


Size

In

Thread

Terminals1) Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Fuse bases made of ceramic


Rated voltage 500 V AC/500 V DC
(for 690 VAC/600 V DC, size DIII bases are to be used together with
DIAZED 5SH1 170 screw caps and DIAZED 5SD8 fuse links)
1-pole
NDz
DII

25
25

E16
E27

KK
BB

5SF1 012
5SF1 005

016
016

0.060
0.093

5
5

DIII
DIII

63
63

E33
E33

BS
SS

5SF1 205
5SF1 215

016
016

0.191
0.154

5
5

for screw connection only


NDz

25

E16

KK

5SF1 01

016

0.055

DII

25

E27

BB

5SF1 024

016

0.093

DIII
DIII

63
63

E33
E33

BS
SS

5SF1 224
5SF1 214

016
016

0.137
0.141

5
5

DIV

100

R1"

5SF1 401
flat
connection

016

0.380

E33S

KK

5SF4 230

016

0.460

Rated voltage 750 V AC/750 V DC


only for DIAZED 5SH1 161 screw caps,
only for DIAZED screw adapters DII and DIII,
only for DIAZED 5SD6 fuse links
with fine thread, with cap.
1-pole
DIII

63

Rated voltage 500 V AC/500 V DC


(for 690 VAC/600 V DC, size DIII bases are to be used together with
DIAZED 5SH1 170 screw caps and DIAZED 5SD8 fuse links)
3-pole
with cap and N-type fixpoint terminal
DII
3 25
DIII

3 63

E27

BB

5SF5 067

016

0.400

E33

BB

5SF5 237

016

0.580

for screw connection only, with cap and N-type fixpoint terminal
DII

3 25

E27

KB

5SF5 066

016

0.410

DIII

3 63

E33

KB

5SF5 236

016

0.590

For busbars for DIAZED fuse bases, see chapter "Busbars for
modular installation devices".
1)

For terminal markings, see Catalog ET B1 T.

1/12

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


DIAZED Fuse Systems
DIAZED fuse bases
Size

In

Thread

Terminals1) Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

Fuse bases made of molded plastic


Touch-protection acc. to BGV A3 (VGB4)
Rated voltage 500 V AC/ 500 V DC
for rail mounting or screw fixing
anti-slip terminal at the incoming and outgoing feeders
Enclosure: silicone-free,
halogen-free
heat-resistant up to 150 C
tracking resistance CTI 225
self-extinguishing acc. to UL 94
1-pole

3-pole

DII

25

E27

RR

5SF1 060

016

0.152

3/108

DIII

63

E33

RR

5SF1 260

016

0.186

3/108

DII
DIII

3 25
3 63

E27
E33

RR
RR

5SF5 068
5SF5 268

016
016

0.457
0.538

1/36
1/36

1
2
3
4
5
6
7
8

DIAZED bus-mounting bases, EZR


for clipping onto 5SH3 5 busbar
only for screw connection
1-pole
DII
DIII

25
63

E27
E33

B
B

5SF6 005
5SF6 205

016
016

0.072
0.135

5
5

E27

5SF2 07

016

0.351

1/5

3-pole
DII

3 25

11

For busbars for DIAZED fuse bases, see chapter "Busbars for
modular installation devices".
1)

10

For terminal markings, see Catalog ET B1 T.

12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/13

17

Low-Voltage Fuse Systems


DIAZED Fuse Systems
DIAZED fuse bases

Accessories
Size

Thread

for fuse links

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

DIAZED covers
DIAZED covers
made of molded plastic
not for SILIZED fuse links
1-pole
(5 DIAZED bases = 12 MW)
DII
(4 DIAZED bases = 12 MW)
DIII
Caps
Molded plastic
1-pole
NDz
DII
DIII

E27

5SH2 032

016

0.017

10/620

E33

5SH2 232

016

0.020

10/620

E16
E27
E33

5SH2 01
5SH2 02
5SH2 22

016
016
016

0.028
0.038
0.048

5
5
5

E27
E33

5SH3 401
5SH3 411

016
016

0.013
0.014

5/60
5/60

5SH3 30
5SH3 32
5SH3 34

016
016
016

0.020
0.029
0.035

5
10
10

2
4
6
10
16

5SH3 28
5SH3 31
5SH3 05
5SH3 06
5SH3 07

016
016
016
016
016

0.002
0.002
0.002
0.002
0.002

10
10
10
10
10

2
4
6
10
16
20

5SH3 10
5SH3 11
5SH3 12
5SH3 13
5SH3 14
5SH3 15

016
016
016
016
016
016

0.015
0.015
0.015
0.015
0.014
0.012

10/5000
10/5000
10/10000
10/10000
10/10000
10/5000

25
35
50
63

5SH3 16
5SH3 17
5SH3 18
5SH3 20

016
016
016
016

0.012
0.019
0.018
0.017

10/10000
10/10000
10/5000
10/6000

80
100

5SH3 21
5SH3 22

016
016

0.006
0.005

10/1000
10/1000

Cover rings
1-pole
molded plastic
also for bus-mounting base EZR
DII
DIII

ceramic
DII and DIII also for bus-mounting base EZR
NDz
E16
DII
E27
DIII
E33

DIAZED screw adapters


DIAZED screw adapters
NDz

E16

also for mounting in DIAZED base DIII


DII1)
E27

DIII1)

E33

DIAZED gauge rings


for DIV bases
DIV
1)

R1"

Suitable for a rated voltage of up to 750 V.

1/14

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


DIAZED Fuse Systems
DIAZED fuse bases
Size

In

Thread

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

DIAZED adapter sleeves


DIAZED adapter sleeves
for snapping onto DIAZED screw caps,
if E16 DIAZED fuse links
are inserted in DII DIAZED bases

5SH3 01

016

0.012

10

if DII DIAZED fuse links


are inserted in DIII DIAZED bases

5SH3 02

016

0.023

10

DIAZED adapter sleeve fitters for DII/DIII

5SH3 703

016

0.025

Rated voltage 500 V AC/500 V DC


ceramic
25

E16

5SH1 11

016

0.016

5/5000

molded plastic, with inspection hole, black,


not for SILIZED fuse links
DII

25

E27

5SH1 221

016

0.026

5/5000

DIII

63

E33

5SH1 231

016

0.042

5/5000

narrow version, ceramic


DII

25

E27

5SH1 12

016

0.034

5/30000

DIII

63

E33

5SH1 13

016

0.059

5/20000

mushroom shape, ceramic, with inspection hole, sealable


DII
25

E27

5SH1 22

016

0.050

5/5000

DIII

E33

5SH1 23

016

0.076

5/5000

R1"

5SH1 141

016

0.181

63

3
4
5

DIAZED screw caps

NDz

1
2

6
7
8
9
10
11

ceramic
DIV

100

12
13

Rated voltage 750 V AC/750 V DC


only for 5SD6 DIAZED fuse links
and 5SF4 230 DIAZED fuse bases
made of ceramic, with fine thread
DIII

63

E33S

5SH1 161

016

0.084

63

E33

5SH1 170

016

0.086

14

Rated voltage 690 V AC/600 V DC

15

only for 5SD8 DIAZED fuse links


made of ceramic, prolonged version
DIII

16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/15

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse links gG

Selection and ordering data


Sizes

Mounting width

In

Un

mm

PG

Insulated grip lugs

Order No.

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

LV HRC fuse links with combination alarm, gG operational class


0001)

21

10
16
20
25
32
35

400 V AC

3NA6 803-4
3NA6 805-4
3NA6 807-4
3NA6 810-4
3NA6 812-4
3NA6 814-4

013
013
013
013
013
013

0.135
0.135
0.135
0.135
0.135
0.135

3
3
3
3
3
3

3NA6 817-4
3NA6 820-4
3NA6 822-4
3NA6 824-4
3NA6 830-4

013
013
013
013
013

0.135
0.135
0.135
0.135
0.135

3
3
3
3
3

3NA6 824-4KK
3NA6 830-4KK
3NA6 832-4

013
013
013

0.200
0.200
0.200

3
3
3

3NA6 836-4

013

0.200

3NA6 114-4
3NA6 117-4
3NA6 120-4
3NA6 122-4
3NA6 124-4
3NA6 130-4

013
013
013
013
013
013

0.290
0.290
0.290
0.290
0.290
0.290

3
3
3
3
3
3

3NA6 132-4
3NA6 136-4
3NA6 140-4
3NA6 142-4
3NA6 144-4

013
013
013
013
013

0.290
0.290
0.430
0.430
0.430

3
3
3
3
3

3NA6 220-4
3NA6 222-4
3NA6 224-4

013
013
013

0.450
0.450
0.450

3
3
3

100
125
160
200
224

3NA6 230-4
3NA6 232-4
3NA6 236-4
3NA6 240-4
3NA6 242-4

013
013
013
013
013

0.450
0.450
0.450
0.450
0.450

3
3
3
3
3

250
300

3NA6 244-4
3NA6 250-4

013
013

0.450
0.650

3
3

315
355
400

3NA6 252-4
3NA6 254-4
3NA6 260-4

013
013
013

0.650
0.650
0.650

3
3
3

40
50
63
80
100
00

30

80
100
125

400 V AC

160

30

47.2

47.2

57.8

1)

35
40
50
63
80
100

400 V AC

125
160
200
224
250
50
63
80

400 V AC

LV HRC fuse links of size 000 can also be used in LV HRC fuse bases,
LV HRC fuse switch disconnectors, LV HRC fuse strips as well as in
LV HRC in-line fuse switch disconnectors of size 00

1/16

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse links gG
Sizes

Mount- In
ing
width

Un

mm

Non-insulated grip lugs

Insulated grip lugs

Order No.

Order No.

Price
1 unit

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

LV HRC fuse links with combination alarm,


operational class gG
0001)

00

21

30

2
4

3NA7 802
3NA7 804

3NA6 802
3NA6 804

013
013

0.135
0.135

3
3

6
10
16
20

3NA7 801
3NA7 803
3NA7 805
3NA7 807

3NA6 801
3NA6 803
3NA6 805
3NA6 807

013
013
013
013

0.135
0.136
0.136
0.136

3
3
3
3

25
32
35
40
50
63

3NA7 810
3NA7 812
3NA7 814
3NA7 817
3NA7 820
3NA7 822

3NA6 810
3NA6 812
3NA6 814
3NA6 817
3NA6 820
3NA6 822

013
013
013
013
013
013

0.600
0.136
0.440
0.136
0.128
0.120

3
3
3
3
3
3

80
100

3NA7 824
3NA7 830

3NA6 824
3NA6 830

013
013

0.128
0.120

3
3

3NA7 824-7
3NA7 830-7

3NA6 824-7
3NA6 830-7

013
013

0.211
0.211

3
3

3NA7 832
3NA7 836

3NA6 832
3NA6 836

013
013

0.200
0.200

3
3

3NA7 105
3NA7 107

3NA6 105
3NA6 107

013
013

0.290
0.290

3
3

25

3NA7 110

3NA6 110

013

0.290

35
40
50
63
80
100

3NA7 114
3NA7 117
3NA7 120
3NA7 122
3NA7 124
3NA7 130

3NA6 114
3NA6 117
3NA6 120
3NA6 122
3NA6 124
3NA6 130

013
013
013
013
013
013

0.290
0.290
0.290
0.290
0.290
0.290

3
3
3
3
3
3

125
160

3NA7 132
3NA7 136

3NA6 132
3NA6 136

013
013

0.290
0.290

3
3

200
224
250
35
50

3NA7 140
3NA7 142
3NA7 144
3NA7 214
3NA7 220

3NA6 140
3NA6 142
3NA6 144
3NA6 214
3NA6 220

013
013
013
013
013

0.440
0.440
0.400
0.450
0.450

3
3
3
3
3

63

3NA7 222

3NA6 222

013

0.450

80
100
125
160
200
224
250

3NA7 224
3NA7 230
3NA7 232
3NA7 236
3NA7 240
3NA7 242
3NA7 244

3NA6 224
3NA6 230
3NA6 232
3NA6 236
3NA6 240
3NA6 242
3NA6 244

013
013
013
013
013
013
013

0.450
0.450
0.450
0.450
0.450
0.450
0.450

3
3
3
3
3
3
3

3002)
315
3552)
400

3NA7 252

3NA7 260

3NA6 250
3NA6 252
3NA6 254
3NA6 260

013
013
013
013

0.641
0.660
0.641
0.660

3
3
3
3

80
100

500 V
AC/250 V
DC

500 V
AC/250 V
DC

125
160
1

30

47.2

47.2

57.8

16
20

500 V
AC/440 V
DC

500 V
AC/440 V
DC

1)

LV HRC fuse links of size 000 can also be used in LV HRC fuse bases,
LV HRC fuse switch disconnectors, LV HRC fuse strips as well as in
LV HRC in-line fuse switch disconnectors of size 00

2)

The 300 A and 355 A fuse links do not conform to a VDE mark.
They correspond to the standard, but are not permissible.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/17

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse links gG
Sizes

Mount- In
ing
width

Un

mm

Non-insulated grip lugs

Insulated grip lugs

Order No.

Order No.

Price

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price

1 unit

1 unit

LV HRC fuse links with combination alarm,


operational class gG
0001)

00

21

30

30

2
4

3NA7 802-6
3NA7 804-6

3NA6 802-6
3NA6 804-6

013
013

0.136
0.136

3
3

6
10
16
20

3NA7 801-6
3NA7 803-6
3NA7 805-6
3NA7 807-6

3NA6 801-6
3NA6 803-6
3NA6 805-6
3NA6 807-6

013
013
013
013

0.136
0.136
0.136
0.136

3
3
3
3

25
32
35
40
50

3NA7 810-6
3NA7 812-6
3NA7 814-6
3NA7 817-6
3NA7 820-6

3NA6 810-6
3NA6 812-6
3NA6 814-6
3NA6 817-6
3NA6 820-6

013
013
013
013
013

0.136
0.136
0.136
0.211
0.211

3
3
3
3
3

63

3NA7 822-6

3NA6 822-6

013

0.211

80
100

3NA7 824-6
3NA7 830-6

3NA6 824-6
3NA6 830-6

013
013

0.211
0.211

3
3

3NA7 120-6
3NA7 122-6

3NA6 120-6
3NA6 122-6

013
013

0.290
0.290

3
3

3NA7 124-6
3NA7 130-6
3NA7 132-6
3NA7 136-6
3NA7 140-6

3NA6 124-6
3NA6 130-6
3NA6 132-6
3NA6 136-6

013
013
013
013

0.290
0.290
0.290
0.290

3
3
3
3

3NA6 140-6

013

0.440

3NA7 224-6
3NA7 230-6

3NA6 224-6
3NA6 230-6

013
013

0.450
0.450

3
3

125
160
200

3NA7 232-6
3NA7 236-6
3NA7 240-6

3NA6 232-6
3NA6 236-6
3NA6 240-6

013
013
013

0.450
0.450
0.450

3
3
3

224
250

3NA7 242-6
3NA7 244-6

3NA6 242-6
3NA6 244-6

013
013

0.660
0.660

3
3

3002)
315

3NA7 250-6
3NA7 252-6

3NA6 250-6
3NA6 252-6

013
013

0.660
0.660

3
3

50
63

690 V
AC/250 V
DC

690 V
AC/250 V
DC

690 V
AC/440 V
DC

80
100
125
160

47.2

200

47.2

80
100

57.8

690 V
AC/440 V
DC

Further versions on request.


1)

LV HRC fuse links of size 000 can also be used in LV HRC fuse bases,
LV HRC fuse switch disconnectors, LV HRC fuse strips as well as in
LV HRC in-line fuse switch disconnectors of size 00.

2)

The 300 A fuse links do not conform to a VDE mark.


They correspond to the standard, but are not permissible.

1/18

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse links gG
Sizes

Mounting width

In

Un

mm

Non-insulated grip lugs

Order No.

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

LV HRC fuse links with front indicator, operational class gG


000

00

1)

21

30

2
4
6
10
16
20

3NA3 802
3NA3 804
3NA3 801
3NA3 803
3NA3 805
3NA3 807

013
013
013
013
013
013

0.133
0.133
0.133
0.133
0.133
0.133

3
3
3
3
3
3

25
32
35

3NA3 810
3NA3 812
3NA3 814

013
013
013

0.133
0.133
0.133

3
3
3/90

40
50
63
80
100
125
160

3NA3 817
3NA3 820
3NA3 822
3NA3 824
3NA3 830
3NY1 822
3NY1 824

013
013
013
013
013
013
013

0.133
0.133
0.133
0.133
0.133
0.130
0.129

3
3/90
3/90
3/90
3/90
1
1

3NA3 814-7
3NA3 820-7
3NA3 822-7

013
013
013

0.200
0.200
0.200

3
3
3

3NA3 824-7
3NA3 830-7
3NA3 832
3NA3 836

013
013
013
013

0.200
0.200
0.217
0.217

3
3
3
3

3NA3 001
3NA3 003
3NA3 005

013
013
013

0.340
0.340
0.340

3
3
3

20
25
32

3NA3 007
3NA3 010
3NA3 012

013
013
013

0.340
0.340
0.340

3
3
3

35
40
50
63
80
100

3NA3 014
3NA3 017
3NA3 020
3NA3 022
3NA3 024
3NA3 030

013
013
013
013
013
013

0.340
0.340
0.340
0.340
0.340
0.340

3
3
3
3
3
3

125
160

3NA3 032
3NA3 036

013
013

0.340
0.340

3
3

3NA3 105
3NA3 107
3NA3 110
3NA3 114
3NA3 117
3NA3 120

013
013
013
013
013
013

0.290
0.290
0.290
0.300
0.300
0.300

3
3
3
3
3
3

63
80
100

3NA3 122
3NA3 124
3NA3 130

013
013
013

0.300
0.300
0.300

3
3
3

125
160
200
224
250

3NA3 132
3NA3 136
3NA3 140
3NA3 142
3NA3 144

013
013
013
013
013

0.300
0.300
0.440
0.440
0.440

3
3
3
3
3

35
50
63

500 V AC/
250 V DC

400 V AC
500 V AC/
250 V DC

80
100
125
160
0

30

30

47.2

1)

6
10
16

16
20
25
35
40
50

500 V AC/
440 V DC

500 V AC/
440 V DC

1
2
3
4
5
6
7
8
9
10
11
12
13

LV HRC fuse links of size 000 can also be used in LV HRC fuse bases,
LV HRC fuse switch disconnectors, LV HRC fuse strips as well as in
LV HRC in-line fuse switch disconnectors of size 00

14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/19

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse links gG
Sizes

Mounting width

In

Un

mm

Non-insulated grip lugs

Order No.

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

LV HRC fuse links with front indicator, gG operational class


2

47.2

57.8

57.8

71.2

35
50
63
80
100
125

3NA3 214
3NA3 220
3NA3 222
3NA3 224
3NA3 230
3NA3 232

013
013
013
013
013
013

0.453
0.453
0.453
0.453
0.453
0.453

3
3
3
3
3
3

160
200

3NA3 236
3NA3 240

013
013

0.453
0.453

3
3

224
250
3001)
315

3NA3 242
3NA3 244
3NA3 250
3NA3 252

013
013
013
013

0.453
0.453
0.647
0.647

3
3
3
3

3551)
400
200
224
250

3NA3 254
3NA3 260
3NA3 340
3NA3 342
3NA3 344

013
013
013
013
013

0.647
0.647
0.647
0.640
0.647

3
3
3
3
3

3001)
315

3NA3 350
3NA3 352

013
013

0.647
0.647

3
3

3551)
400
4251)
500
630

3NA3 354
3NA3 360
3NA3 362
3NA3 365
3NA3 372

013
013
013
013
013

0.647
0.647
1.000
1.000
1.000

3
3
3
3
3

500 V AC/
440 V DC

4
(IEC design)

101.8

630
800
1000
1250

500 V AC/
440 V DC

3NA3 472
3NA3 475
3NA3 480
3NA3 482

013
013
013
013

2.500
2.500
2.500
2.500

1
1
1
1

4a2)

101.8

500
630
800
1000
1250

500 V AC/
440 V DC

3NA3 665
3NA3 672
3NA3 675
3NA3 680
3NA3 682

013
013
013
013
013

2.700
2.700
2.700
2.840
2.840

1
1
1
1
1

1)

The 300 A, 355 A and 425 A fuse links do not conform to a VDE mark.
They correspond to the standard, but are not permissible.

2)

Fuse links, size 4a can only be installed in 3NH7 520 LV HRC fuse base,
size 4a.

1/20

500 V AC/
440 V DC

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse links gG
Sizes

Mounting width

In

Un

mm

Non-insulated grip lugs

Order No.

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

LV HRC fuse links with front indicator, gG operational class


000

00

21

3NA3 802-6
3NA3 804-6
3NA3 801-6

013
013
013

0.135
0.135
0.135

3
3
3

10
16
20

3NA3 803-6
3NA3 805-6
3NA3 807-6

013
013
013

0.135
0.135
0.135

3
3
3

25
32
35
40
50
63

3NA3 810-6
3NA3 812-6
3NA3 814-6
3NA3 817-6
3NA3 820-6
3NA3 822-6

013
013
013
013
013
013

0.135
0.135
0.135
0.200
0.200
0.200

3
3
3
3
3
3

3NA3 824-6
3NA3 830-6

013
013

0.200
0.200

3
3

3NA3 120-6
3NA3 122-6
3NA3 124-6

013
013
013

0.290
0.290
0.290

3
3
3

100
125
160

3NA3 130-6
3NA3 132-6
3NA3 136-6

013
013
013

0.290
0.290
0.290

3
3
3

47.2

200

3NA3 140-6

013

0.426

47.2

80
100
125

3NA3 224-6
3NA3 230-6
3NA3 232-6

013
013
013

0.426
0.426
0.426

3
3
3

160
200

3NA3 236-6
3NA3 240-6

013
013

0.426
0.426

3
3

57.8

224
250
3001)
315

3NA3 242-6
3NA3 244-6
3NA3 250-6
3NA3 252-6

013
013
013
013

0.660
0.680
0.660
0.680

3
3
3
3

57.8

250
315

3NA3 344-6
3NA3 352-6

013
013

0.660
0.660

3
3

71.2

355
400
4251)
500

3NA3 354-6
3NA3 360-6
3NA3 362-6
3NA3 365-6

013
013
013
013

1.000
1.000
1.000
1.000

3
3
3
3

30

2
4
6

690 V AC/
250 V DC

690 V AC/
250 V DC

80
100

30

50
63
80

690 V AC/
440 V DC

690 V AC/
440 V DC

690 V AC/
440 V DC

1
2
3
4
5
6
7
8
9
10
11
12

1)

The 300 A and 425 A fuse links do not conform to a VDE mark.
They correspond to the standard, but are not permissible.

13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/21

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse bases

Selection and ordering data


Sizes

In

Version

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

LV HRC fuse bases


000/00

160

160

160
125
160

160

250

250

4
(IEC design)

1/22

Siemens ET B1 2007

400

630

1250

1-pole
with flat connections, screw
with clamp-type terminal connections
with saddle-type terminal connections
with flat connections and terminal strip
with flat connections, nut
with flat and saddle-type terminal connection

3NH3 030
3NH3 031
3NH3 032
3NH3 035
3NH3 038
3NH3 050

014
014
014
014
014
014

0.235
0.230
0.266
0.230
0.207
0.227

3
3
3
3
3
3

made of molded plastic, for mounting rail


and screw fixing
with flat connections, screw
with saddle-type terminal connections
with box terminal, up to 50 mm2

3NH3 051
3NH3 052
3NH3 053

014
014
014

0.119
0.114
0.109

1/10
1/10
1/10

3-pole, with phase barriers


with flat connections
with clamp-type terminal connections
with saddle-type terminal connections

3NH4 030
3NH4 031
3NH4 032

014
014
014

0.700
0.800
0.800

1
1
1

with flat connections and terminal strip

3NH4 035

014

0.750

1-pole
with screw-type terminal connections
with clamp-type terminal connections

3NH3 120
3NH3 122

014
014

0.460
0.460

3
3

1-pole
with flat connections
with double busbar connections

3NH3 230
3NH3 220

014
014

0.789
0.789

3
3

3-pole
with screw-type terminal connections

3NH4 230

014

2.100

1-pole
with screw-type terminal connections
with double busbar connections

3NH3 330
3NH3 320

014
014

0.843
1.000

1
1

1-pole
with screw-type terminal connections
with double busbar connections

3NH3 430
3NH3 420

014
014

1.100
1.100

1
1

1-pole
with screw-type terminal connections

3NH3 530

014

3.000

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse bases
Sizes

In

Version

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit

0.150
0.150
0.150

1
1
1

Units

LV HRC bus-mounting bases for busbars


for busbars 12 mm x 5 mm to 12 mm x 10 mm
busbar clearance 40 mm
000/00

000/00

160

80

1-pole
with top saddle-type terminal connection
with bottom saddle-type terminal connection
terminal strip, top

3-pole, tandem design


3 outgoing feeders, top and bottom with
saddle-type terminal connection
with 4 phase barriers
with 2 non-interrupted phase barriers

3NH3 036
3NH3 037
3NH3 048

014
014
014

3NH4 037
3NH4 045

014
014

0.800
0.800

1
1

supplied with additional saddle-type terminal


connections
with screw connection for mounting plate
with claw fixing for non-perforated busbar
with screw connection for perforated busbar

3NH7 030
3NH7 031
3NH7 032

014
014
014

1.000
1.000
1.000

1
1/3
1/3

with screw connection for mounting plate


with claw fixing for non-perforated busbar
with screw connection for perforated busbar

3NH7 230
3NH7 231
3NH7 232

014
014
014

2.500
2.500
2.500

1
1
1

with screw connection for mounting plate


with claw fixing for non-perforated busbar

3NH7 330
3NH7 331

014
014

4.800
4.800

1
1

with screw connection for perforated


busbar, can be used as disconnector

3NH7 332

014

4.800

with screw connection for mounting plate

3NH7 520

6
7

Degree of pollution 3
Degree of protection: open IP10, closed IP20
1-pole, with flat connection

2/3

4a

160

250

400
and
630

1250

3
4
5

LV HRC fuse bases with slewing equipment

000/00

1
2

8
9
10
11
12
014

5.200

13

14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/23

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse bases

Accessories
Sizes

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

Mounting parts for LV HRC fuse bases


LV HRC contact covers
Touch protection for contact pieces

000/00
0
1
2
3

3NX3 105
3NX3 114
3NX3 106
3NX3 107
3NX3 108

014
014
014
014
014

0.013
0.010
0.027
0.031
0.038

2/20
2/40
2/20
2/12
2/10

3NH3 0/3NH4 0
3NH3 1
3NH3 2

000/00
0
1

3NX2 023
3NX2 030
3NX2 024

014
014
014

0.025
0.050
0.053

2/40
2/30
2/20

3NH3 3
3NH3 4
LV HRC protective covers IP2X
for LV HRC fuse bases, size 000/00
1 and 3-pole

2
3

3NX2 025
3NX2 026

014
014

0.066
0.101

2/10
2/8

3NX3 115

014

0.039

10

3NX3 116

014

0.014

10

LV HRC contact covers


for mounting onto contacts to ensure touch protection
outgoing terminal
incoming terminal

3NX3 105
3NX3 113

014
014

0.013
0.006

2/20
2/50

LV HRC partitions
for 3NH3 0 LV HRC bus-mounting bases
Phase barriers

3NX2 027

014

0.017

2/50

End barrier

3NX2 028

014

0.020

2/50

for 3NH4 0 LV HRC bus-mounting base in tandem design


non-interrupted barrier

3NX2 031

014

0.050

2/30

LV HRC partitions
for side-by-side mounting of LV HRC fuse bases
and as end barrier for side-by-side arrangement
Type

LV HRC covers IP2X


for LV HRC protective cover IP2X

Mounting parts for LV HRC bus-mounting bases

1/24

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse bases
Sizes

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

Mounting parts for LV HRC fuses


Fuse pullers
for LV HRC fuse links

000 ... 4

without sleeve

3NX1 013

014

0.280

with sleeve

3NX1 014

014

0.480

1
2
3
4
5

Isolating links
for LV HRC fuse bases and fuse switch disconnectors
with insulated grip lugs
silver-plated

000/00
0
1
2
3

3NG1 002
3NG1 102
3NG1 202
3NG1 302
3NG1 402

014
014
014
014
014

0.080
0.110
0.170
0.240
0.290

3
1/10
1/10
1/5
1/5

4
4a

3NG1 503
3NG1 505

014
014

0.708
0.730

1/5
1/5

with non-insulated grip lugs


tinned
nickel-plated

Fuse-base covers
for LV HRC fuse bases
acc. to DIN 43620
red with yellow information label
"power supply isolating point"

6
7

000/00
1, 2, 3

3NX1 003
3NX1 004

014
014

0.050
0.100

3
3

9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/25

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC signal detectors

Selection and ordering data


Sizes

Order No.

000 to 4

Price

PG

Weight
1 unit
approx.
kg

PS*
P. unit

3NX1 021

014

0.036

1/4

3NX1 022
3NX1 023

014
014

0.015
0.015

1/12
1/12

000, 00, 1, 2 3NX1 024

014

0.010

1 unit
LV HRC signal detectors
Only for SIEMENS 3NA3, 3NA7 and 3ND LV HRC fuse
links with non-insulated grip lugs
Rated voltage: 690 V AC/600 V DC
Contact: microswitch 250 V AC, 6 A
Connection: flat termination 2.3 mm ... 0.5 mm
1
N

Units

4 2
NO NC

Signal detector links


Rated voltage: 690 V AC/600 V DC
Response value > 9 V; 2.5 A; for standard applications
Response value > 2 V; 7 A; only for meshed systems
Signal detector tops

000 ... 4

Only for SIEMENS 3NA3, 3NA7 and 3ND LV HRC fuse


links with non-insulated grip lugs
Rated voltage: 690 V AC/600 V DC
Contact: microswitch 230 V AC, 5 A, 1 CO contact
Connection: flat termination 2.3 mm
1
N

1/26

4 2
NO NC

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors

Selection and ordering data

1
2

Surface mounting and installation


Rated
Connection type
uninter- (double-ended)
rupted
current Iu
Connec- for conductor
tion
cross-section
A
mm2

For LV HRC
For isolatfuse links acc. ing links2)
to
DIN 436201)

Size

up to 160 A, also clip-on for standard mounting rails


1603)
Box
1.5 ... 50
0004)
terminals

Degree of protection IP00,


without fuse links,
without isolating links,
with connection screws
Order No.
Price

Size
00

PG

1 unit
3NP40 10-0CH01

103

Weight
1 unit
approx.

PS*
P. unit

kg

Units

0.512

3
4
5
6
7

3NP40 10
160

Flat termi- up to 2 70 (M8)


00 a. 000
nation
Box ter- 2.5 ... 70 or 2 2.5 ... 16
minals

00

Flat termi- up to 150 (M10)


1 and 0
nation
Flat termi- up to 240 (M10)
2 and 1
nation
Flat termi- up to 2 240 (M12) 3 and 2
nation

3NP40 70-0CA01

103

0.749

3NP40 70-0CH01

103

0.800

1 and 0

3NP42 70-0CA01

103

2.436

2 and 1

3NP43 70-0CA01

103

3.614

3 and 2

3NP44 70-0CA01

103

4.984

3NP40 70
250
400
630

9
10

3NP42 70

For all fuse switch disconnectors with flat connections, use the relevant cable lug covers (3NY7 101 to 3NY7 141) in order to ensure protection
against finger touch according to BGV A3, see "Accessories".
1)
2)

See LV HRC Fuse Links.


Use silver-plated isolating links.

3)
4)

125/160 A only possible with 3NY1 822 (125 A) and 3NY1 824 (160 A)
21 mm LV HRC fuse links, see "Accessories".
Corresponds to LV HRC fuse link size 00 with maximum width 21 mm
(according to IEC 60269-2-1 and DIN 43620).

11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/27

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution
for 40 mm busbar systems
Rated
Connection type
uninter- (double-ended)
rupted
current Iu
Connec- for conductor
tion
cross-section
A
mm2

For LV HRC
For isolatfuse links acc. ing links2)
to
DIN 436201)

Size

Degree of protection IP00,


without fuse links,
without isolating links,
with terminal screws
Order No.
Price

Size

PG

1 unit

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Rails of width 12 mm or 15 mm and thickness 5 mm or 10 mm3)


with adapter, deep, e.g. for installation in ALPHA meter cabinets
(ALPHA 400-ZS) and ALPHA distribution boards (STAB/SIKUS)
1604)
Box ter- 1.5 ... 50
minals
connection top
0005)
00
connection bottom
160

Flat termi- up to 2 70 (M8)


nation
connection top
00 a. 000
connection bottom
Box terminals

3NP40 15-0CK01
3NP40 15-0CJ01

103
103

0.952
0.970

1
1

00

3NP40 75-0CE01
3NP40 75-0CF01

103
103

1.210
1.244

1
1

00

3NP40 75-0CK01
3NP40 75-0CJ01

103
103

1.290
1.274

1
1

3NP40 15-1CK01
3NP40 15-1CJ01

103
103

0.892
0.888

1
1

00 a. 000

3NP40 75-1CE01
3NP40 75-1CF01

103
103

1.186
1.189

1
1

00 a. 000

3NP40 75-1CK01
3NP40 75-1CJ01

103
103

1.261
1.213

1
1

1 and 0

3NP42 75-1CG01

103

3.719

2.5 ... 70 or 2 2.5 ... 16

3NP40 15-0CK01
connection top
00 a. 000
connection bottom

with adapter, deep, acc. to DIN 43620 Teil 6, for general applications and ALPHA distribution boards (STAB/SIKUS)
1604)
Box ter- 1.5 ... 50
minals
connection top
0005)
00
connection bottom
160

Flat termi- up to 2 70 (M8)


nation
connection top
00 a. 000
connection bottom
Box terminals

2.5 ... 70 or 2 2.5 ... 16


connection top
00 a. 000
connection bottom

250

Flat termi- up to 240 (M10)


nation
connection
top or bottom

1 and 0

For all fuse switch disconnectors with flat connections, use the relevant cable lug covers (3NY7 101 to 3NY7 141) in order to ensure protection
against finger touch according to BGV A3, see "Accessories".
1)
2)
3)

See LV HRC Fuse Links.


Use silver-plated isolating links.
For mounting on 5 mm thick busbars, a bar thickness compensation is
required for 3NP42 and 3NP43, see "Accessories". 3NP44 can only be
mounted on 10 mm thick busbars!

1/28

Siemens ET B1 2007

4)
5)

125/160 A only possible with 3NY1 822 (125 A) and 3NY1 824 (160 A)
21 mm LV HRC fuse links, see "Accessories".
Corresponds to LV HRC fuse link size 00 with maximum width 21 mm
(according to IEC 60269-2-1 and DIN 43620).

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution
for 60 mm busbar systems
Rated
uninterrupted
current
Iu

Connection type
(double-ended)

Connection
A

for conductor
cross-section
mm2

For LV HRC
For isolatfuse links acc. ing links2)
to
DIN 436201)

Degree of protection IP00,


without fuse links,
without isolating links,
with terminal screws
Order No.

Size

Size

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

0.916
0.950

1
1

Price
1 unit

Rails of width 12 mm to 30 mm and thickness 5 mm or 10 mm3)


flat, T and I profiles, as well as on Rittal PLS systems.
1604)

Box
1.5 ... 50
terminal5)
connection, top
0004)
connection, bottom

00

3NP40 16-1CK01
3NP40 16-1CJ01

103
103

Flat termi- up to 2 70 (M8)


nation
connection, top
00 a. 000
connection, bottom

00

3NP40 76-1CE01
3NP40 76-1CF01

103
103

1.203
1.201

1
1

00

3NP40 76-1CK01
3NP40 76-1CJ01

103
103

1.295
1.249

1
1

1 and 0

1 and 0

3NP42 76-1CG01

103

3.713

2 and 1

2 and 1

3NP43 76-1CG01

103

5.440

3 and 2

3NP44 76-1CG01

103

7.688

2.5 ... 70 or 2 2.5 ... 16


Box
terminal5)
connection, top
00 a. 000
connection, bottom
250
3NP42 76
400

630

Flat termi- up to 150 (M10)


nation
connection, top or
bottom
Flat termi- up to 240 (M10)
nation
connection, top or
bottom

Flat termi- up to 2 240 (M12)


nation
connection, top or 3 and 2
bottom

6
7
8
9

For all fuse switch disconnectors with flat connections, use the relevant cable lug covers (3NY7 101 to 3NY7 141) in order to ensure protection
against finger touch according to BGV A3, see "Accessories".
1)
2)
3)

See LV HRC Fuse Links.


Use silver-plated isolating links.
For mounting on 5 mm thick busbars, a bar thickness compensation is
required for 3NP42 and 3NP43, see "Accessories". 3NP44 can only be
mounted on 10 mm thick busbars!

4)
5)

3
4
5

3NP40 16
160

1
2

125/160 A only possible with 21 mm 3NY1 822 (125 A) and 3NY1 824
(160 A) LV HRC fuse links, see "Accessories".
No further cover required for 3NP40 with box terminal.

10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/29

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution
with fuse monitoring by SIRIUS circuit-breaker1)2)

Surface mounting and installation


Rated
uninterrupted
current
Iu

Connection type
(double-ended)

Connection
A

for conductor
cross-section
mm2

For LV HRC
For isolatfuse links acc. ing links4)
to
DIN 436203)

Degree of protection IP00,


without fuse links,
without isolating links,
with connection screws
Order No.

Size

Size

up to 160 A, also clip-on for standard mounting rails


160
Flat termi- up to 2 70 (M8)
00 a. 000
nation
Box ter- 2.5 ... 70 or
minals
2 2.5 ... 16
250
Flat termi- up to 150 (M10)
1 and 0
nation
400
Flat termi- up to 240 (M10)
2 and 1
nation
630
Flat termi- up to 2 240 (M12) 3 and 2
nation

00

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

3NP40 70-0FA01

103

1.276

3NP40 70-0FH01

103

1.350

1 and 0

3NP42 70-0FA01

103

2.940

2 and 1

3NP43 70-0FA01

103

4.174

3 and 2

3NP44 70-0FA01

103

5.495

For all fuse switch disconnectors with flat connections, use the relevant cable lug covers (3NY7 101 to 3NY7 141) in order to ensure protection
against finger touch according to BGV A3, see "Accessories".
1)
2)

SIRIUS circuit-breaker with auxiliary switch 1 NO + 1 NC as standard.


3NP40 7 also available with auxiliary switch 2 NO or 2 NC on request.

3)

See LV HRC Fuse Links.

4)

Use silver-plated isolating links.

For 3NP40 7 with output socket for auxiliary switch, the signal lead must be
ordered separately, see "Accessories". In the case of 3NP41 to 3NP44, the
auxiliary switch must be connected over a 2.8 mm 0.5 mm flat connection according to DIN 46244-A.

1/30

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution
with fuse monitoring by SIRIUS circuit-breaker1)2)

1
2

for 40 mm busbar systems


Rated
uninterrupted
current
Iu

Connection type
(double-ended)

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

103
103

1.812
1.780

1
1

3NP40 75-0FK01
3NP40 75-0FJ01

103
103

1.820
1.831

1
1

with adapter, deep, acc. to DIN 43620 part 6, for general applications and ALPHA distribution boards (STAB/SIKUS)
160
Flat termi- up to 2 70 (M8)
nation
connection top
00 a. 000
00 a. 000
3NP40 75-1FE01
connection bottom
3NP40 75-1FF01

103
103

1.616
1.620

1
1

Connection
A

for conductor
cross-section
mm2

For LV HRC
For isolatfuse links acc. ing links4)
to
DIN 436203)

Degree of protection IP00,


without fuse links,
without isolating links,
with terminal screws
Order No.

Size

Size

Price
1 unit

Rails of width 12 mm or 15 mm and thickness 5 mm or 10 mm5)


with adapter, deep, e.g. for installation in ALPHA meter cabinets
(ALPHA 400-ZS) and ALPHA distribution boards (STAB/SIKUS)
160
Flat termi- up to 2 70 (M8)
nation
connection top
00 a. 000
00
3NP40 75-0FE01
3NP40 75-0FF01
connection bottom
Box terminals

2.5 ... 70 or
2 2.5 ... 16
connection top
00 a. 000
connection bottom

00

3
4
5
6
7
8

Box terminals

250

2.5 ... 70 or
2 2.5 ... 16
connection top
00 a. 000
connection bottom

Flat termi- up to 240 (M10)


nation
connection
top or bottom

1 and 0

00 a. 000

3NP40 75-1FK01
3NP40 75-1FJ01

103
103

1.717
1.630

1
1

1 and 0

3NP42 75-1FG01

103

4.210

9
10

For all fuse switch disconnectors with flat connections, use the relevant cable lug covers (3NY7 101 to 3NY7 141) in order to ensure protection
against finger touch according to BGV A3, see "Accessories".
1)
2)

SIRIUS circuit-breaker with auxiliary switch 1 NO + 1 NC as standard.


3NP40 7 also available with auxiliary switch 2 NO or 2 NC on request.
For 3NP40 7 with output socket for auxiliary switch, the signal lead must be
ordered separately, see "Accessories". In the case of 3NP41 to 3NP44, the
auxiliary switch must be connected over a 2.8 mm 0.5 mm flat connection according to DIN 46244-A.

3)
4)
5)

See LV HRC Fuse Links.


Use silver-plated isolating links.
For mounting on 5 mm thick busbars, a bar thickness compensation is
required for 3NP42 and 3NP43, see "Accessories". 3NP44 can only be
mounted on 10 mm thick busbars!

11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/31

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution
with fuse monitoring by SIRIUS circuit-breaker1)2)

for 60 mm busbar systems


Rated uninterrupted
current Iu

Connection type
(double-ended)

Connection

For LV HRC
For isolatfuse links acc. ing links4)
to
DIN 436203)

for conductor crosssection


Size
mm2

Degree of protection IP00,


without fuse links,
without isolating links,
with terminal screws
Order No.
Price

Size

PG

1 unit

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Rails of width 12 mm to 30 mm and thickness 5 mm or 10 mm5) Flat,


T and I profiles, as well as on Rittal PLS systems
160

Flat termina- up to 2 70
tion
(M8)
connection 00 a. 000
top
connection
bottom
Box terminals 2.5 ... 70 or
2 2.5 ... 16
connection 00 a. 000
top
connection
bottom

250

400

630

00

00

3NP40 76-1FE01

103

1.670

3NP40 76-1FF01

103

1.890

3NP40 76-1FK01

103

1.755

3NP40 76-1FJ01

103

1.915

Flat termina- up to 150


tion
(M10)
connection
top or
bottom

1 and 0

1 and 0

3NP42 76-1FG01

103

4.171

Flat termina- up to 240


tion
(M10)
connection
top or
bottom

2 and 1

2 and 1

3NP43 76-1FG01

103

5.845

Flat termina- up to 2
tion
240 (M12)
connection, 3 and 2
top or
bottom

3 and 2

3NP44 76-1FG01

103

8.235

For all fuse switch disconnectors with flat connections, use the relevant cable lug covers (3NY7 101 to 3NY7 141) in order to ensure protection
against finger touch according to BGV A3, see "Accessories".
1)
2)

SIRIUS circuit-breaker with auxiliary switch 1 NO + 1 NC as standard.


3NP40 7 also available with auxiliary switch 2 NO or 2 NC on request.

3)

See LV HRC Fuse Links.

4)

For 3NP40 7 with output socket for auxiliary switch, the signal lead must be
ordered separately, see "Accessories". In the case of 3NP41 to 3NP44, the
auxiliary switch must be connected over a 2.8 mm 0.5 mm flat connection according to DIN 46244-A.

5)

Use silver-plated isolating links.


For mounting on 5 mm thick busbars, a bar thickness compensation is
required for 3NP42 and 3NP43, see "Accessories". 3NP44 can only be
mounted on 10 mm thick busbars!

1/32

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution

Accessories

1
2

with fuse monitoring


For fuse
switch disconnectors

Version

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Quick retaining plates


between two rails
DIN EN 60715
Busbar center-to-center
clearance 125 mm
Busbar center-to-center
clearance 125 mm

3NP40 10,
3NP40 70
3NP42 70

3NY1 995

103

0.135

1/200

3NY7 322

103

0.249

3NP40 7 with flat connection1)


3NP42 7
3NP43
3NP44

3NY7 101
3NY7 121
3NY7 131
3NY7 141

103
103
103
103

0.065
0.220
0.221
0.319

3NY7 120
3NY7 130
3NY7 140

103
103
103

0.333
0.583
0.725

3
4
5

3NY1 995
1 set

Cable lug covers


and finger-safe cover acc. to
BGV A3 (1 set = 2 units) for
1 single mounting or 2 adapter
devices
Terminals
(1 set = 3 units)

3NP42 7
3NP43
3NP44

1 set
1 set
1 set
1 set

1 set

Triple terminals
(1 set = 3 units)
for mounting on box terminals

Conductor
cross-section
70 mm2 ... 150 mm2
120 mm2 ... 240 mm2
150 mm2 ... 300 mm2

1 set
1 set
1 set
1 set

Conductor
cross-section
3NP40 1,
3NP40 7

solid/stranded:
2.5 mm2 ... 16 mm2

3NY7 102

103

0.131

1 set

for mounting on flat terminations 3NP40 7

Finely stranded with


end sleeve:
2.5 mm2 ... 10 mm2
for Iu max = 225 A
for 2 switch disconnectors

3NY7 105

103

0.113

1 set

3NY1 237

103

0.265

for 3 switch
disconnectors

3NY1 238

103

0.434

for 4 switch
disconnectors
Link rails

3NY1 438

103

0.650

3NY1 263

103

0.267

3NY1 265

103

0.012

3NY1 236

103

0.262

1 set

3NY7 102

3-phase busbars
Modular width 90 mm
= 5 MW
3NY1 237

3NP40 1

Permissible connection 25 mm2


or supply terminal

Feeder terminals
(1 set = 3 units)
for Iu max = 225 A

12

1 set
3NP40 1

3NY1 236

Conductor
cross-section
solid/stranded:
25 mm2 ... 95 mm2
Finely stranded with
end sleeve:
16 mm2 ... 70 mm2

3NY7 481

103

0.021

Sealing pins
(1 set = 10 units)

3NP42 7,
3NP43,
3NP44

3NY7 482

103

0.056

10

3NY7 381

103

0.064

NSE00172

3NP42 7,
3NP43,
3NP44

Bar thickness compensations


(1 Assembly kit = 5 units) for
3NP42 7,
only 5 mm thick busbars
3NP43

15

1 set
1 set

The fuse switch disconnector with mounted cable lug covers,


together with molded-plastic masking frame for distributor/device field/incoming
feeder unit, is easy to install in the meter cabinet.

* You can order this quantity or a multiple thereof.

13
14

Overreaching protections

3NY7 481

1)

9
11

3NY1 263
3NP40 1

8
10

3NY1 238

Caps
for 1 blank space in 3NY1 238

6
7

Siemens ET B1 2007

1/33

16
17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution
For fuse
switch disconnectors

Version

Order No.

Price

PG

1 unit
Fuse carrier
gray with inscription label with
voltage inspection holes
Auxiliary switches 1 CO

3NY3 035

PS*
P. unit

kg

Units

3NP40 1
3NP40 7

3NY7 003
3NY7 001

103
103

0.160
0.220

1
1

3NP40 1 up
to 3NP44

3NY3 035

103

0.004

3NY3 030

103

0.004

3NY1 822
3NY1 824

013
013

0.130
0.129

1
1

3NY1 910
3NY1 911

103
103

0.097
0.261

1
1

for sizes 000 and 00 with


self-tapping screws for sizes
1 to 3 to clip on
Electronically optimized
Fuse links sizes 000
3NP40 1
with non-insulated grip lugs,
operational class gL/gG for
cable and line protection, overall
width 21 mm acc. to IEC 602692-1 and DIN 43620
Signal leads
for connection to output socket
of fuse monitoring size 00
1-m cable with connector
3-m cable with connector

1/34

Weight
1 unit
approx.

Siemens ET B1 2007

3NP40 7
3NP40 7

400 V/125 A
400 V/160 A

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution
Covers
Fuse switch
disconnectors

Height Width

Order No.

mm

Price

PG

1 unit

Weight
1 unit
approx.
kg

Units

PS*
P. unit

For installation in 40 mm and 60 mm busbar systems


1)

Touch-protection covers
3NP40 75, 3NP40 76

3NY7 601

103

0.125

For installation in any distribution boards2)


Molded-plastic covers

3NY1 251

3NP40 1
3NP40 7 with
box terminals
3NP40 7 with
flat connection

215 130
215 130

3NY1 251
3NY7 200

103
103

0.052
0.037

1
1

215 130

3NY7 201

103

0.046

3NP42 7
3NP43
3NP44

375 220
375 245
375 290

3NY7 220
3NY7 230
3NY7 240

103
103
103

0.112
0.117
0.125

1
1
1

2 x 3NP40 1
1 x 3NP40 1 left
1 x 3NP40 1 right

197 215.5
197 215.5
197 215.5

3NY1 258
3NY1 262
3NY1 264

103
103
103

0.063
0.093
0.091

1
1
1

1 x 3NP40 7 left
1 x 3NP40 7 right
2 x 3NP40 7

208 229
208 229
208 229

3NY7 500
3NY7 501
3NY7 502

103
103
103

0.120
0.120
0.054

1
1
1

3NP42 7
3NP43
3NP44

309 216
375 245
375 290

3NY7 220
3NY7 230
3NY7 240

103
103
103

0.112
0.117
0.125

1
1
1

6
7

3NY7 600

103

0.095

For installation in ALPHA 160- and ALPHA 400 wall-mounted distribution


boards (STAB 160/STAB 400), and ALPHA 630 floor-mounted distribution
boards (SIKUS 630)
Touch-protection covers1)3)
3NP40 76
Molded-plastic covers
for mounting on mounting plates or busbars.
For further information,
see Catalog ET A1
"ALPHA Distribution
Boards"

1)
2)

1 3NP40 1 right
1 3NP40 1 left
2 3NP40 1

166 199
166 199
166 199

3NY1 260
3NY1 261
3NY1 248

103
103
103

0.082
0.086
0.036

1
1
1

1 3NP40 7 left
1 3NP40 7 right
2 3NP40 7

208 229
208 229
208 236

3NY7 500
3NY7 501
3NY7 502

103
103
103

0.120
0.120
0.054

1
1
1

3NP42 7
3NP43
3NP44

309 2164)
375 245
375 290

3NY7 820
3NY7 230
3NY7 240

103
103
103

0.113
0.117
0.125

1
1
1

When using LV HRC fuse links, size 00 (160 A), the permissible load
current is 0.9 x In.
Special covers may be required for installation in ALPHA wall-mounted and
floor-mounted distribution boards (STAB, SIKUS) and ALPHA 400-ZS meter
cabinets, see "Accessories".

3)
4)

3
4
5

For installation in ALPHA 400-ZS meter cabinets, see publication


"Installation and mounting", Order No. E20001-P285-A526-V1
Molded-plastic covers
Suitable for distribution
board/
device panel or for
incoming feeder panel
in the meter cabinet
(busbar mounted)

1
2

9
10

In 60 mm busbar systems, the conductor cross-section is limited to


16 mm2 if the outgoing feeder is at the bottom.
If 8GE3 818-0 mounting plates are used, 3NY7 220 molded-plastic covers
can also be used (for installation in any distribution boards).

11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/35

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution
Fuse switch
disconnectors

8HP
enclosures

Order No.

Size

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

For installation in 8HP molded-plastic distribution systems


Molded-plastic covers
1 3NP40 10
for installation in
8HP complete
1 3NP40 70
enclosures with fuse 2 3NP40 10
switch disconnec3 3NP40 10
tors
1 3NP40 70

8HP6 431
8HP6 422

046
046

0.221
0.224

1
1

2 3NP40 70

2
2
2
2

8HP6 432
8HP6 432
8HP6 423
8HP6 424

046
046
046
046

0.465
0.465
0.230
0.203

1
1
1
1

1 3NP40 70
2 3NP40 70
1 3NP42 70

2.5
2.5
2.5

8HP6 423
8HP6 424
8HP6 427

046
046
046

0.230
0.203
0.250

1
1
1

Fuse switch
disconnectors

Height
Width

Order No.

PG

Weight
1 unit
approx.
kg

PS*
P. unit
Units

NSE00173a

1
1

mm

Price

1 unit

For installation in STAB-/SIKUS 8GD/8GA "classic" distribution boards,


see publication "Installation and mounting", Order No. E20001-P285-A526-V1
Molded-plastic covers
1 3NP40 10 right
for mounting
between 2 standard with and without
mounting rails with auxiliary switch
3NY1 995 quick
1 3NP40 10 left
retaining plate
with and without
auxiliary switch
in a field of width B1 2 3NP40 10 with
and without auxiliary switch
in a field of width
2 3NP40 10 with
B2/2
and without
auxiliary switch

197 215.5

3NY1 256

103

0.116

197 215.5

3NY1 257

103

0.118

197 215.5

3NY1 258

103

0.063

197 235

3NY1 250

103

0.075

197 485
in a field of width B2 3 x 3NP40 10 with
and without auxiliary switch (supports
included in delivery)

3NY1 253

103

0.225

197 485
4 x 3NP40 10 with
and without auxiliary switch (supports
included in delivery)
197 485
5 3NP40 10 with
and without auxiliary switch

3NY1 254

103

0.188

3NY1 255

103

0.125

3NP40 1

3NY1 271

103

1 set
0.100

1 set

3NY1 250

3NY1 253

3NY1 255
Supports
(1 set = 10 units)
for 3NY1 253 and
3NY1 254 moldedplastic covers

1/36

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for power distribution
Fuse switch
disconnectors

Height
Width

Order No.

mm
Molded-plastic
covers
for mounting on
3NP40 1 switch
disconnectors

Price

PG

1 unit

Weight
1 unit
approx.

PS*
P. unit

kg

Units

166 199

3NY1 260

103

0.082

1 3NP40 1 left with 166 199


and without auxiliary switch

3NY1 261

103

0.086

166 199

3NY1 248

103

0.036

166 469

3NY1 247

103

0.072

Width 90

3NY1 270

103

0.040

1 set

208 219
208 219

3NY7 800
3NY7 801

103
103

0.100
0.120

1
1

208 222

3NY7 802

103

0.120

309 216

3NY7 820

103

0.113

1 3NP40 1 right
with and without
auxiliary switch

2 3NP40 1 with
and without
auxiliary switch
in a field of width B2 5 3NP40 1 with
and without
auxiliary switch

6
7

3NY1 247
Blanking covers
(1 set = 10 units)
for covering blank
spaces in the
3NY1 2 moldedplastic covers

1 set
3NP40 1

Molded-plastic covers
1 x 3NP40 7 left
for mounting
between two stan1 x 3NP40 7 right
dard mounting rails
with 3NY1 995 quick 2 3NP40 7
retaining plate
with 3NY1 322 quick 1 3NP42 7
retaining plate
Molded-plastic covers
for attachment
to 8GD9 100 mount- 1 x 3NP40 7 left
ing plate
1 x 3NP40 7 right
2 3NP40 7
1 3NP42 70

208 229

3NY7 500

103

0.120

208 229
208 236
309 2161)

3NY7 501
3NY7 502
3NY7 820

103
103
103

0.120
0.054
0.113

1
1
1

1 3NP43 70

375 245

3NY7 230

103

0.117

1 3NP44 70

375 290

3NY7 240

103

0.125

1)

8
9
10
11

Molded-plastic covers
for attachment
to 8GD9 591
mounting plate
to 8GD9 592
mounting plate

3
4
5

3NY1 260
on standard mounting rails with special
8GD9 equipment
rack and for mounting on busbars
(except 3NY1 247)
in a field of width B1

1
2

12
13

For mounting on 8GD9 590 mounting plate, the 3NY7 220 molded-plastic
cover can also be used.

14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/37

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for increased technical requirements

Selection and ordering data


Surface mounting and installation
Rated
Connection type
uninter- (double-ended)
rupted
current Iu
Connection

For LV HRC For isofuse links


lating
acc. to
links
DIN 436201)

Size
For
conductor
cross-section
mm2

Size

Auxiliary
switches at
the switch
disconnectors
Version

Degree of protection IP00,


without fuse links,
without isolating links,
with connection screws
Order No.

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price

1 unit

Completely compartmentalized, with high speed closing feature


00 a. 000

00

without4)
1 NO +
1 NC

3NP50 60-0CA00
3NP50 60-0CA10

103
103

1.608
1.650

1
1

Clamp
connection

1-wire
00 a. 000
2.5 ... 50
or
2 conductors
1 2.5 ... 50
1 2.5 ... 35

00

without4)
1 NO +
1 NC

3NP50 60-0CB00
3NP50 60-0CB10

103
103

1.739
1.748

1
1

Flat
connection

6 ... 1505)

1 and 0

without
1 NO +
1 NC

3NP52 60-0CA00
3NP52 60-0CA10

103
103

5.475
5.491

1
1

Clamp
connection

35 ... 120

1 and 0

without
1 NO +
1 NC

3NP52 60-0CB00
3NP52 60-0CB10

103
103

5.605
5.814

1
1

400

Flat
connection

6 ... 2405)

2 and 1

without
1 NO +
1 NC

3NP53 60-0CA00
3NP53 60-0CA10

103
103

6.532
6.551

1
1

630

Flat
connection

6 ... 2 2405) 3 and 2

without
1 NO +
1 NC

3NP54 60-0CA00
3NP54 60-0CA10

103
103

7.945
7.958

1
1

160

250

Flat
2.5 ... 1503)
connection2)

1)

See LV HRC Fuse Links.

2)

For 3NP50 60 with flat connections, the relevant 3NY1 106 cable lug
covers must be used (see "Accessories") for the purpose of protection
against accidental contact according to DIN VDE 0106 Part 100
(see "Accessories").

3)

4)

If auxiliary switch is retrofitted, additional drill holes are required on


the switch.

5)

According to DIN 46234 or DIN 46235; with cable lug according to


DIN 46235: min. conductor cross-section 16 mm2 (use M12 cable lugs if
required).

According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235


(use M10 cable lugs if required).

1/38

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for increased technical requirements
for 40 mm busbar system
Rated uninterrupted
current Iu

Connection type
(double-ended)

For isolating
links

Connection

Size

For LV HRC
fuse links
acc. to
DIN 436201)
For conductor Size
cross-section
mm2

Auxiliary
switches at
the switch
disconnectors
Version

Degree of protection IP00,


without fuse links, without
isolating links, with
terminal screws
Order No.
Price

PG

1 unit

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Completely compartmentalized, with high speed closing feature2)


Rail width: 12 mm and 5 mm or 10 mm thickness
160
Flat
2.5 ... 1503)
00 a. 000
connection
Connection,
bottom
Clamp
connection

1-wire
00 a. 000
2.5 ... 50 or
2 conductors
1 2.5 ... 50
1 2.5 ... 35,
bottom
connection

1)

See LV HRC Fuse Links.

2)

For accessories and further devices on busbar systems,


see "Accessories".

without
1 NO +
1 NC

3NP50 65-1CF00
3NP50 65-1CF10

103
103

2.380
2.370

1
1

without
1 NO +
1 NC

3NP50 65-1CG00
3NP50 65-1CG10

103
103

2.433
2.437

1
1

3)

Connection type
(double-ended)

For isolating
links

Connection

Size

For LV HRC
fuse links
acc. to
DIN 436201)
For conductor Size
cross-section
mm2

According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235


(use M cable lugs if required).

Auxiliary
switches at
the switch
disconnectors
Version

Degree of protection IP00,


without fuse links,
without isolating links,
with terminal screws
Order No.
Price
1 unit

PG

3
4
5

for 60 mm busbar system


Rated uninterrupted
current Iu

1
2

Weight
1 unit
approx.

PS*
P. unit

kg

Units

6
7
8

Completely compartmentalized, with high speed closing feature2)

Use switch version "Surface mounting and installation" and busbar adapter,
see "Accessories".
1)

See LV HRC Fuse Links.

2)

For accessories and further devices on busbar systems,


see "Accessories".

10
11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/39

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for increased technical requirements
with fuse monitoring by SIRIUS circuit-breakers

Surface mounting and installation


Rated unin- Connection type
terrupted
(double-ended)
current Iu

Connection for conductor crosssection


mm2

For LV HRC Auxiliary switches


fuse links
acc. to
DIN 436201)
at switch
at the
disconcircuitnectors
breakers
Size
Version
Version

Degree of protection IP00, PG


without fuse links, without
isolating links, with
terminal screws
Order No.
Price

1 unit

Weight PS*
1 unit
P. unit
approx.

kg

Units

103
103

2.484
2.550

1
1

Completely compartmentalized, with high speed closing feature with fuse


monitoring by SIRIUS circuit-breakers2)
with plug-in connection of the auxiliary switch connecting cable
(length approx. 1 m) to the circuit-breaker
160
Flat
2.5 ... 1504) 00 a. 000
1 NO + 1 NC 1 NO + 1 NC 3NP50 60-0EA86
connection3
1 NO + 1 NC 2 NO
3NP50 60-0EA26
)

1 conductor
2.5 ... 50
2 conductor
1 2.5 ... 50
1 2.5 ... 35
6 ... 1505)

00 a. 000

1 NO + 1 NC 1 NO + 1 NC 3NP50 60-0EB86
1 NO + 1 NC 2 NO
3NP50 60-0EB26

103
103

2.616
2.650

1
1

1 and 0

1 NO + 1 NC 1 NO + 1 NC 3NP52 60-0EA86
1 NO + 1 NC 2 NO
3NP52 60-0EA26

103
103

6.014
6.867

1
1

Clamp
connection

35 ... 120

1 and 0

1 NO + 1 NC 1 NO + 1 NC 3NP52 60-0EB86
1 NO + 1 NC 2 NO
3NP52 60-0EB26

103
103

7.095
6.659

1
1

400

Flat
connection

6 ... 2405)

2 and 1

1 NO + 1 NC 1 NO + 1 NC 3NP53 60-0EA86
1 NO + 1 NC 2 NO
3NP53 60-0EA26

103
103

7.083
5.410

1
1

630

Flat
connection

6 ... 2 2405) 3 and 2

1 NO + 1 NC 1 NO + 1 NC 3NP54 60-0EA86
1 NO + 1 NC 2 NO
3NP54 60-0EA26

103
103

8.462
9.233

1
1

Clamp
connection

250

Flat
connection

1)

See LV HRC Fuse Links.

2)

SIRIUS circuit-breakers: auxiliary switches, 2 NC also available on request.

3)

For 3NP50 60 with flat connections, the relevant 3NY1 106 cable lug
covers must be used (see "Accessories") for the purpose of protection
against accidental contact according to DIN VDE 0106 Part 100
(see "Accessories").

1/40

Siemens ET B1 2007

4)

According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235


(use M10 cable lugs if required).

5)

According to DIN 46234 or DIN 46235, with cable lug according to


DIN 46235: min. conductor cross-section 16 mm2 (use M12 cable lugs if
required).

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for increased technical requirements
for 40 mm busbar system
Rated uninterrupted
current Iu

Connection type
(double-ended)

Connection

for conductor crosssection


mm2

For LV HRC Auxiliary switches


fuse links
acc. to
DIN 436201)
at switch at the circuitdisconbreakers
nectors
Size
Version
Version

Degree of protection IP00, PG


without fuse links,
without isolating links,
with terminal screws
Order No.
Price

1 unit

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Completely compartmentalized, with high speed closing feature with


fuse monitoring by SIRIUS circuit-breakers2)3)
Rail width: 12 mm and 5 mm or 10 mm thickness
160
Flat connec- 2.5 ... 1504) 00 a. 000
tion
Connection,
bottom
Clamp connection

1)
2)

1-wire
00 a. 000
2.5 ... 50
2 conductor
1 2.5 ... 50
1 2.5 ... 35,
bottom connection

See LV HRC Fuse Links.


SIRIUS circuit-breaker on request, also auxiliary switch 2 NC.

1 NO + 1 NC 1 NO + 1 NC
1 NO + 1 NC 2 NO

3NP50 65-1EF86
3NP50 65-1EF26

103
103

2.908
2.950

1
1

1 NO + 1 NC 1 NO + 1 NC
1 NO + 1 NC 2 NO

3NP50 65-1EG86
3NP50 65-1EG26

103
103

3.020
2.973

1
1

3)

For accessories and further devices on busbar systems, see "Accessories"


and switchgear, SIVACON distribution boards and cabinet systems, >
components for 8US, 8UC, 4NC distribution board systems -> 8US busbar
systems.

4)

According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235


(use M10 cable lugs if required).

for 60 mm busbar system

1
2
3
4
5
6
7
8

Note:
For switch versions "For mounting and installation" and busbar adapters, see "Accessories".

9
10
11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/41

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for increased technical requirements
with fuse monitoring by electronic fuse monitoring

Surface mounting and installation


Rated
uninterrupted
current Iu

Connection type
(double-ended)

Connection

For LV HRC Auxiliary switches


fuse links
acc. to
DIN 436201)
for conducat switch at fuse
tor crossdiscon- monitoring
section
nectors
2
Size
Version Version
mm

Degree of protection IP00,


without fuse links,
without isolating links,
with terminal screws
Order No.
Price

PG

1 unit

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Completely comparmentalized, with high-speed closing feature with electronic


fuse monitoring EF (self-powered), open-circuit principle
for rated operational voltages Ue of 400 V to 500 V AC,
infeed must be from the top!
with plug-in connection of auxiliary switch connecting cable
(length approx. 1 m) for fuse monitoring, status display: green LED
illuminated, fault indication: green LED flashing, fuse failure: red LED
(display per phase)
160
Flat
2.5 ... 1203) 00 a. 000
1 NO + 2 NO +
connection2)
1 NC
1 NC
00 a. 000
1 NO + 2 NO +
Clamp
1-wire:
1 NC
1 NC
connection
2.5 ... 50
2-wire:
1 2.5 ... 50
1 2.5 ... 35

103

2.375

3NP50 60-0HB13

103

2.500

250

Flat
connection

6 ... 1504)

1 and 0

1 NO +
1 NC

2 NO +
1 NC

3NP52 60-0HA13

103

5.865

400

Flat
connection

6 ... 2404)

2 and 1

1 NO +
1 NC

2 NO +
1 NC

3NP53 60-0HA13

103

6.951

630

Flat
connection

6 ...2404)

3 and 2

1 NO +
1 NC

2 NO +
1 NC

3NP54 60-0HA13

103

8.513

1)

See LV HRC Fuse Links.

2)

For 3NP50 60 with flat connections, the relevant 3NY1 106 cable lug
covers must be used (see "Accessories") for the purpose of protection
against accidental contact according to DIN VDE 0106 Part 100
(see "Accessories").

1/42

3NP50 60-0HA13

Siemens ET B1 2007

3)

According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235


(use M10 cable lugs if required).

4)

According to DIN 46234 or DIN 46235; with cable lug according to


DIN 46235: min. conductor cross-section 16 mm2 (use M12 cable lugs if
required).

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for increased technical requirements
for 40 mm busbar system
Rated
uninterrupted
current Iu

Connection type
(double-ended)

For LV HRC Auxiliary switches


fuse links
acc. to
DIN 436201)
Connection for conducat switch at fuse
tor crossdiscon- monitoring
section
nectors
mm2
Size
Version Version

Degree of protection IP00,


without fuse links,
without isolating links,
with connection screws
Order No.
Price

PG

1 unit

Weight
1 unit
approx.

PS*
P. unit

kg

Units

2.776

Completely comparmentalized, with high-speed closing feature with electronic


fuse monitoring EF (self-powered), open-circuit principle
for rated operational voltages Ue of 400 V to 500 V AC,
infeed must be from the top!
for rail width: 12 mm and 5 mm or 10 mm thickness
1 NO +
160
Flat con2.5 ... 1202) 00 a. 000
1 NC
nection
bottom
connection

1)

See LV HRC Fuse Links.

2 NO +
1 NC

2)

3NP50 65-1HF13

103

According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235


(use M10 cable lugs if required).

1
2
3
4
5
6
7

for 60 mm busbar system


Note:
For switch versions "For mounting and installation" and busbar
adapters, see "Accessories".

8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/43

17

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
for increased technical requirements

Accessories
For fuse switch
disconnectors

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

Fuse carriers
3NP50 6.-.C..0
3NP52 60-.C..0
3NP53 60-.C..0
3NP54 60-.C..0

3NY1 074
3NY1 371
3NY1 372
3NY1 373

103
103
103
103

0.620
0.263
1.510
1.690

1
1
1
1

with fuse monitoring by 3RV1 motor


starter protectors
(with auxiliary switches, 1 NO + 1 NC), with plug-in
connection, without connector and connecting cable

3NP50 6.-.E..6
3NP52 60-.E..6
3NP53 60-.E..6
3NP54 60-.E..6

3NY1 420
3NY1 421
3NY1 422
3NY1 423

103
103
103
103

1.405
1.900
1.980
2.600

1
1
1
1

Connector and connecting cable


1 m long
3 m long

3NP5 with 3RV1

3NY1 910
3NY1 911

103
103

0.097
0.261

1
1

with electronic fuse monitoring


for 400 V ... 500 V
(with auxiliary switches, 2 NO + 1 NC), with plug-in
connection, without connector and connecting cable

3NP50 6.-.H.13
3NP52 60-.H.13
3NP53 60-.H.13
3NP54 60-.H.13

3NY1 513-0
3NY1 513-2
3NY1 513-3
3NY1 513-4

103
103
103
103

1.235
2.130
2.146
0.325

1
1
1
1

Connector and connecting cable (6-pole)


3 m long

3NP5 with EF

3NY1 915

103

0.372

3NP501)

3NY3 033

103

0.015

3NP52 ... 3NP54

3NY3 034

103

0.015

3NP50
3NP52
3NP53, 3NP54

3NY4 031
3NY4 011
3NY4 012

103
103
103

0.218
0.215
0.240

1
1
1

3NY1 210
3NY1 211
3NY1 212

3NY1 102
3NY1 103
3NY1 104

103
103
103

0.071
0.075
0.084

1
1
1

3NY1 074

3NY1 513-3

3NY1 915
Auxiliary switches 1 NO + 1 NC
with actuating cams, screws and
washers (mounting kit)

3NY3 033
with fixing bracket and screws
(mounting kit)

3NY3 034
Electric arc chambers
(for 3NP52, 3NP53 and 3NP54, 3
units each are required)

3NY4 031

3NY4 011
Molded-plastic covers
300 220 mm
as replacement for covers from
assembly kits for installation (without 300 245 mm
mounting brackets and small com- 300 290 mm
ponents)
1)

If retrofitted, drill holes required.

1/44

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


LV HRC Fuse Systems
LV HRC fuse switch disconnectors
For fuse switch Dimensions
disconnectors

Order No.

mm

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

For installation in any distribution board


Height Width
215 135

3NY1 105

103

0.045

1/400

215 135

3NY1 115

103

0.044

1/400

with and without auxiliary


switches
3NP50 with
and without
auxiliary
switches

220 160

3NY1 125

103

0.062

265 135

3NY1 107

103

0.073

for covering cable lug connections

3NP50 with
and without
auxiliary
switches

290 135

3NY1 106

103

0.071

1/225

for separate covering of top and


bottom cable lug connections

with auxiliary
switch
3NP50 with
and without
auxiliary
switches

290 135

3NY1 116

103

0.071

1/225

290 135

3NY1 108

103

0.048

1/200

3NP50 60
3NP52 60
3NP53 60
3NP54 60

250 149
300 220
300 245
300 290

3NY1 208
3NY1 210
3NY1 211
3NY1 212

103
103
103
103

0.531
0.287
0.298
0.313

1
1
1
1

Molded-plastic covers
for installation in cabinet

for installation in metal front panels

for covering connection terminals

3NP50 with
and without
auxiliary
switches
with auxiliary
switch

3NY1 106

(1 set = 6 units) screw-on to free


screw end for protection against
unintentional contact

3NP52
3NP53/
3NP54 60

99
95

3NY1 241
3TX6 546-3B

103
101

0.205
0.260

1 set
1 set

120

3NY1 245

103

0.336

1 set

11
12

3TX6 546-3B
Clamp connections
(1 set = 3 units)
3NP50
3NP52

8
10

1 set

Cover length

6
7
9

3NY1 212
Covers for cable lug connection

3
4
5

3NY1 107

Assembly kits for installation


with molded-plastic cover, mounting
brackets and small components. for
switches with and without auxiliary
switches

1
2

Conductor
cross-section
2.5 ... 50 mm2
1)

35 ... 120 mm

1 set
3NY1 903

103

0.108

1 set

3NY1 907

103

0.225

1 set

8US12 91-4SB00
8US12 10-4AG00

103
103

0.551
3.060

1
1

3NY1 907
Busbar adapters
for 60 mm busbar system

Rail width
3NP50
108
3NP52, 3NP53, 250 (length
3NP542)
320 mm,
M10 terminal
screws, connecting cables
must be made)

13
14

8US12 10-4AG00
Sealing eyes
can be retrofitted (1 set = 10 units)
1)

3NP50

Also available in 2-wire version: 1 2.5 mm2 ... 50 mm2 and


1 2.5 mm2 ... 35 mm2.

* You can order this quantity or a multiple thereof.

3NY1 940
2)

103

1 set
0.010

1 set

Switch is wider than adapter; however, this can be expanded to 276 mm


using two 8US19 982BM00 lateral modules.

Siemens ET B1 2007

1/45

15
16
17

Low-Voltage Fuse Systems


Cylindrical Fuse Systems
Cylindrical fuse links gG

Selection and ordering data


Sizes

In

Un

mm mm

V AC

PG

gG operational class

Order No.

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

Cylindrical fuse links


8 32

2
4
6
10
16
20

400

3NW6 302-1
3NW6 304-1
3NW6 301-1
3NW6 303-1
3NW6 305-1
3NW6 307-1

018
018
018
018
018
018

0.004
0.004
0.004
0.004
0.004
0.004

10
10
10
10
10
10

10 38

2
4
6
8
10
12

500

3NW6 002-1
3NW6 004-1
3NW6 001-1
3NW6 008-1
3NW6 003-1
3NW6 006-1

018
018
018
018
018
018

0.008
0.008
0.008
0.008
0.008
0.008

10
10
10
10
10
10/100

3NW6 005-1
3NW6 007-1
3NW6 010-1

018
018
018

0.008
0.008
0.008

10
10
10

3NW6 012-1
3NW6 104-1
3NW6 101-1

018
018
018

0.008
0.019
0.019

10
10
10

3NW6 108-1
3NW6 103-1
3NW6 106-1
3NW6 105-1
3NW6 107-1
3NW6 110-1
3NW6 112-1
3NW6 117-1
3NW6 120-1

018
018
018
018
018
018
018
018
018

0.019
0.019
0.019
0.019
0.019
0.019
0.019
0.019
0.019

10/100
10
10/100
10
10
10
10
10
10

3NW6 208-1
3NW6 203-1
3NW6 206-1
3NW6 205-1
3NW6 207-1
3NW6 210-1

018
018
018
018
018
018

0.051
0.051
0.051
0.051
0.051
0.051

10/100
10/100
10/100
10
10
10

32
40
50

3NW6 212-1
3NW6 217-1
3NW6 220-1

018
018
018

0.051
0.051
0.051

10
10
10

63
80
100

3NW6 222-1
3NW6 224-1
3NW6 230-1

018
018
018

0.051
0.051
0.051

10
10
10

16
20
25
14 51

32
4
6
8
10
12
16
20
25
32
40
50

22 58

1/46

Siemens ET B1 2007

8
10
12
16
20
25

400
500

400
500

400

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


Cylindrical Fuse Systems
Bases for cylindrical fuses

Selection and ordering data


In

For fuse links of


size

mm x mm

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*
P. unit
Units

Draw-out technology
without signal detectors
1-pole
20
2
32
50
100
1

8 x 32
10 x 38
14 x 51
22 x 58

1
1
1.5
2

3NW7 313
3NW7 013
3NW7 111
3NW7 211

018
018
018
018

0.056
0.056
0.095
0.145

1
1/12
1
1

1-pole + N
20
32
50

8 x 32
10 x 38
14 x 51

1
1
3

3NW7 353
3NW7 053
3NW7 151

018
018
018

0.069
0.069
0.215

1
1
1

1 N

100

22 x 58

3NW7 251

018

0.330

20
32
50
100

8 x 32
10 x 38
14 x 51
22 x 58

2
2
3
4

3NW7 323
3NW7 023
3NW7 121
3NW7 221

018
018
018
018

0.118
0.118
0.195
0.300

1
1/6
1
1

2 4 6

20
32
50

8 x 32
10 x 38
14 x 51

3
3
4.5

3NW7 333
3NW7 033
3NW7 131

018
018
018

0.172
0.172
0.295

1
1/4
1

1 3 5

100

22 x 58

3NW7 231

018

0.691

2 4 6 N

20
32
50

8 x 32
10 x 38
14 x 51

3
3
6

3NW7 363
3NW7 063
3NW7 161

018
018
018

0.185
0.185
0.315

1
1
1

1 3 5 N

100

22 x 58

3NW7 261

018

0.475

20
32
50
100

8 x 32
10 x 38
14 x 51
22 x 58

1
1
1.5
2

3NW7 312
3NW7 012
3NW7 112
3NW7 212

018
018
018
018

0.058
0.080
0.095
0.145

1
1
1
1

2 N

20
32
50

8 x 32
10 x 38
14 x 51

2
2
3

3NW7 352
3NW7 052
3NW7 152

018
018
018

0.120
0.167
0.215

1
1
1

1 N

100

22 x 58

3NW7 252

018

0.330

2 4

20
32
50

8 x 32
10 x 38
14 x 51

2
2
3

3NW7 322
3NW7 022
3NW7 122

018
018
018

0.112
0.162
0.195

1
1
1

1 3

100

22 x 58

3NW7 222

018

0.300

20
32
50
100

8 x 32
10 x 38
14 x 51
22 x 58

3
3
4.5
6

3NW7 332
3NW7 032
3NW7 132
3NW7 232

018
018
018
018

0.167
0.243
0.295
0.480

1
1
1
1

2 4 6 N

20
32
50

8 x 32
10 x 38
14 x 51

4
4
6

3NW7 362
3NW7 062
3NW7 162

018
018
018

0.227
0.327
0.315

1
1
1

1 3 5 N

100

22 x 58

3NW7 262

018

0.475

2-pole

1 3

3
4
5

2 N

2 4

1
2

3-pole

6
7

3-pole + N

8
9

with signal detectors


1-pole
2

10

1-pole + N

11

2-pole

12

3-pole
2 4 6

1 3 5

13

3-pole + N

14

Auxiliary switches
for indicating disconnection of the fuse link
solely for application of Striker fuse links
(not currently included in the Siemens product range).
For retrofitting using the factory-fitted brackets, 0.5 MW.
Contact: 250 V AC, 5 A,
Minimum contact load: 12 V, 25 mA
for fuse bases
for fuse bases

14 x 51
22 x 58

0.5

3NW7 901
3NW7 902

018
018

0.050
0.050

15

1
1

16

Busbars for bases for cylindrical fuses, see chapter "Busbars for
modular installation devices".

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/47

17

Low-Voltage Fuse Systems


Fuse Links for Motor Circuits
LV HRC fuse links aM

Selection and ordering data


Sizes

Mounting width

In

Un

mm

Non-insulated grip lugs

Order No.

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

LV HRC fuse links with front indicator, aM operational class


000

21

6
10
16
20
25
32

500 V AC

35
40
50
63
80

014
014
014
014
014
014

0.130
0.130
0.130
0.130
0.130
0.130

3
3
3
3
3
3

3ND1 814
3ND1 817
3ND1 820
3ND1 822
3ND1 824

014
014
014
014
014

0.130
0.130
0.130
0.130
0.130

3
3
3
3
3

00

30

100
125
160

500 V AC

3ND1 830
3ND1 832
3ND1 836

014
014
014

0.192
0.192
0.192

3
3
3

30

63
80
100

690 V AC

3ND2 122
3ND2 124
3ND2 130

014
014
014

0.290
0.290
0.440

3
3
3

47.2

125
160
200
250

3ND2 132
3ND2 136
3ND2 140
3ND2 144

014
014
014
014

0.440
0.440
0.440
0.440

3
3
3
3

47.2

125
160

3ND2 232
3ND2 236

014
014

0.440
0.440

3
3

3ND2 240
3ND2 244
3ND2 252
3ND2 254
3ND2 260

014
014
014
014
014

0.440
0.440
0.650
0.650
0.650

3
3
3
3
3

3ND2 352
3ND2 354
3ND2 360

014
014
014

0.650
0.650
0.650

3
3
3

3ND1 365
3ND1 372

014
014

1.030
1.000

3
3

57.8

1/48

3ND1 801
3ND1 803
3ND1 805
3ND1 807
3ND1 810
3ND1 812

Siemens ET B1 2007

690 V AC

200
250
315
355
400

57.8

315
355
400

71.2

500
630

690 V AC

* You can order this quantity or a multiple thereof.

Low-Voltage Fuse Systems


Fuse Links for Motor Circuits
Cylindrical fuse links aM

Selection and ordering data


Sizes

In

Un

mm mm

V AC

PG

Operational class aM

Order No.

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

Cylindrical fuse links


10 38

0.5
1

3NW8 000-1
3NW8 011-1

018
018

0.003
0.008

10
10

2
4
6

3NW8 002-1
3NW8 004-1
3NW8 001-1

018
018
018

0.008
0.008
0.008

10
10
10

8
10
12
16
20
25

3NW8 008-1
3NW8 003-1
3NW8 006-1
3NW8 005-1
3NW8 007-1
3NW8 010-1

018
018
018
018
018
018

0.003
0.008
0.008
0.008
0.008
0.008

10
10
10/100
10
10
10

3NW8 102-1
3NW8 104-1
3NW8 101-1

018
018
018

0.019
0.019
0.019

10/50
10
10/50

8
10
12
16
20
25

3NW8 108-1
3NW8 103-1
3NW8 106-1
3NW8 105-1
3NW8 107-1
3NW8 110-1

018
018
018
018
018
018

0.019
0.019
0.019
0.019
0.019
0.019

10/50
10
10/50
10
10
10

32
40
50

3NW8 112-1
3NW8 117-1
3NW8 120-1

018
018
018

0.019
0.019
0.019

10
10
10

3NW8 203-1
3NW8 206-1
3NW8 205-1
3NW8 207-1
3NW8 210-1

018
018
018
018
018

0.051
0.051
0.051
0.051
0.051

10/50
10/50
10/50
10
10

32
40
50

3NW8 212-1
3NW8 217-1
3NW8 220-1

018
018
018

0.051
0.051
0.051

10
10
10

63
80
100

3NW8 222-1
3NW8 224-1
3NW8 230-1

018
018
018

0.051
0.051
0.051

10
10
10

14 51

22 58

2
4
6

10
12
16
20
25

500

400
500

400
500

400

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

1/49

17

Low-Voltage Fuse Systems


American/Canadian Class CC Fuses
Class CC fuse links
and fuse holders

Selection and ordering data


Rated
current

Characteristic
slow
Order No.

Characteristic
quick
Price

Order No.

1 unit

Characteristic
slow, current limited
Price

Order No.

1 unit

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

Price
1 unit

Class CC fuses
0.6 (6/10)
0.8 (8/10)
1
1.5 (1 )

3NW1 006-0HG
3NW1 008-0HG
3NW1 010-0HG
3NW1 015-0HG

--3NW2 010-0HG
--

--3NW3 010-0HG
--

018
018
018
018

0.008
0.008
0.008
0.008

10
10
10
10

2
3
4
5

3NW1 020-0HG
3NW1 030-0HG
3NW1 040-0HG
3NW1 050-0HG

3NW2 020-0HG
3NW2 030-0HG
3NW2 040-0HG
3NW2 050-0HG

3NW3 020-0HG
3NW3 030-0HG
3NW3 040-0HG
3NW3 050-0HG

018
018
018
018

0.008
0.008
0.008
0.008

10
10
10
10

6
8
10
12
15
20
25
30

3NW1 060-0HG
3NW1 080-0HG
3NW1 100-0HG
-3NW1 150-0HG
3NW1 200-0HG
3NW1 250-0HG
3NW1 300-0HG

3NW2 060-0HG
3NW2 080-0HG
3NW2 100-0HG
3NW2 120-0HG
3NW2 150-0HG
3NW2 200-0HG
3NW2 250-0HG
--

3NW3 060-0HG
3NW3 080-0HG
3NW3 100-0HG
3NW3 120-0HG
3NW3 150-0HG
3NW3 200-0HG
3NW3 250-0HG
3NW3 300-0HG

018
018
018
018
018
018
018
018

0.008
0.008
0.008
0.008
0.008
0.008
0.008
0.008

10
10
10
10
10
10
10
10

PG

Weight
1 unit
approx.

PS*
P. unit

kg

Units

0.056
0.118
0.172

12
6
4

Version

Rated voltage

Rated current

600
600
600

30
30
30

MW

Order No.

Price

1 unit

Class CC fuse holders


1-pole
2-pole
3-pole

1/50

Siemens ET B1 2007

1
2
3

3NW7 513-0HG
3NW7 523-0HG
3NW7 533-0HG

018
018
018

* You can order this quantity or a multiple thereof.

Semiconductor Fuses

2/6
2/6
2/7
2/7
2/8

Rated voltage 500 V AC


Rated voltage 600 V AC
Rated voltage 660 V AC
Rated voltage: 690 V AC/ 700 V DC
Rated voltage 690 V AC,
operational class gS
Rated voltage 690 V AC,
operational class gR
Rated voltage 800 V AC
Rated voltage 1000 V AC
Rated voltage 1500 V AC
Rated voltage 2000 V AC
Rated voltage 2500 V AC

SITOR Fuse Links for


Special Applications

2/9
2/10
2/10

For rectifiers in electrolysis systems


For SITOR thyristor sets
For railway supply rectifiers

SITOR Cylindrical
Fuse Links

2/11

SITOR cylindrical fuse links

SILIZED Fuse Links

2/13
2/13

NEOZED fuse links SILIZED


DIAZED fuse links SILIZED

LV HRC SITOR
Fuse Links

2/2
2/2
2/3
2/3
2/4
2/5

2/1

Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 500 V AC

Selection and ordering data


Size

In

Operational Order No.


class

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Rated voltage 500 V AC


with bolt-on links
Mounting dimensions: 110 mm
31)

150
200
250
300
350
400

gR
gR
gR
gR
aR
aR

3NC2 423-3
3NC2 425-3
3NC2 427-3
3NC2 428-3
3NC2 431-3
3NC2 432-3

047
047
047
047
047
047

1.063
1.057
1.066
1.078
1.056
1.062

3
3
3
3
3
3

150
200
250
300
350
400

gR
gR
gR
gR
aR
aR

3NC2 423
3NC2 425
3NC2 427
3NC2 428
3NC2 431
3NC2 432

047
047
047
047
047
047

1.055
1.070
1.056
1.056
1.061
1.056

3
3
3
3
3
1/3

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

1.120
1.113

3
3

Special design with 2 oblong slots


3

1)

Cladding dimensions and grip lugs according to IEC 60269-2-1;


but blade slotted according to IEC 60269-4-1.

Rated voltage 600 V AC

Selection and ordering data


Size

In

Operational Order No.


class

Price

1 unit

Unit(s)

Rated voltage 600 V AC


for mounting in LV HRC fuse bases
3

2/2

Siemens ET B1 2007

710
800

gR
gR

3NE1 437-1
3NE1 438-1

047
047

* You can order this quantity or a multiple thereof.

Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 660 V AC

Selection and ordering data


Size

OperaOrder No.
tional class

In

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Rated voltage 660 V AC


with bolt-on links
Mounting dimensions: 110 mm
31)

150
200
250
350
500
1000

gR
gR
gR
gR
gR
aR

3NC8 423-3
3NC8 425-3
3NC8 427-3
3NC8 431-3
3NC8 434-3
3NC8 444-3

047
047
047
047
047
047

1.062
1.063
1.069
1.072
1.069
1.085

3
3
3
3
3
3

150
200
250
350
500

gR
gR
gR
gR
gR

3NC8 423
3NC8 425
3NC8 427
3NC8 431
3NC8 434

047
047
047
047
047

1.044
1.060
1.074
1.065
1.095

3
3
3
3
3

1)

Cladding dimensions and grip lugs according to IEC 60269-2-1;


but blade slotted according to IEC 602269-4-1.

Rated voltage 690 V AC/700 V DC

Selection and ordering data


Size

Operational Order No.


class

In

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Rated voltage 690 V AC/700 V DC


with bolt-on links
Mounting dimensions: 80 mm
000

3
4
5

Special design with 2 oblong slots


3

1
2

6
7
8
9

20
25
32

gR
gR
gR

3NE8 714-1
3NE8 715-1
3NE8 701-1

047
047
047

0.130
0.130
0.131

10
10
10

40
50
63

gR
gR
aR

3NE8 702-1
3NE8 717-1
3NE8 718-1

047
047
047

0.131
0.132
0.132

10
10
10

80
100
125
160
200
250

aR
aR
aR
aR
aR
aR

3NE8 720-1
3NE8 721-1
3NE8 722-1
3NE8 724-1
3NE8 725-1
3NE8 727-1

047
047
047
047
047
047

0.131
0.130
0.131
0.132
0.130
0.133

10
10
10
10
10
10

11

315

aR

3NE8 731-1

047

0.134

10

12

10

13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

2/3

17

Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gS

Selection and ordering data


Size

In

Operational Order No.


class

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Rated voltage 690 V AC


for mounting in LV HRC fuse bases
000

2/4

16
20
25

gS
gS
gS

3NE1 813-0
3NE1 814-0
3NE1 815-0

047
047
047

0.127
0.128
0.127

3
3
3

35
40
50
63
80

gS
gS
gS
gS
gS

3NE1 803-0
3NE1 802-0
3NE1 817-0
3NE1 818-0
3NE1 820-0

047
047
047
047
047

0.128
0.127
0.128
0.128
0.129

3
3
3
3
3

00

100
125

gS
gS

3NE1 021-0
3NE1 022-0

047
047

0.202
0.202

3
3

160
200
250
315

gS
gS
gS
gS

3NE1 224-0
3NE1 225-0
3NE1 227-0
3NE1 230-0

047
047
047
047

0.580
0.582
0.580
0.581

3
3
3
3

350
400
450
500

gS
gS
gS
gS

3NE1 331-0
3NE1 332-0
3NE1 333-0
3NE1 334-0

047
047
047
047

0.766
0.743
0.760
0.766

3
3
3
3

560
630
710
800

gS
gS
gS
gS

3NE1 435-0
3NE1 436-0
3NE1 437-0
3NE1 438-0

047
047
047
047

1.111
1.114
1.117
1.124

3
3
3
3

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gR

Selection and ordering data


Size

In

Operational Order No.


class

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

0.203
0.203
0.203

3
3
3

Unit(s)

Rated voltage 690 V AC


for mounting in LV HRC fuse bases
00

80
100
125

gR
gR
gR

3NE1 020-2
3NE1 021-2
3NE1 022-2

047
047
047

1
2
3
4
5

00

160
200
250
315

gR
gR
gR
gR

3NE1 224-2
3NE1 225-2
3NE1 227-2
3NE1 230-2

047
047
047
047

0.613
0.612
0.626
0.615

3
3
3
3

350
450
500

gR
gR
gR

3NE1 331-2
3NE1 333-2
3NE1 334-2

047
047
047

0.754
0.768
0.768

3
3
3

560
630
670
710
800
850

gR
gR
gR
gR
gR
gR

3NE1 435-2
3NE1 436-2
3NE1 447-2
3NE1 437-2
3NE1 438-2
3NE1 448-2

047
047
047
047
047
047

1.149
1.179
1.170
1.153
1.184
1.207

3
3
3
3
3/1
3

25
35
50

gR
gR
gR

3NE8 015-1
3NE8 003-1
3NE8 017-1

047
047
047

0.205
0.204
0.203

3
3
3

63
80
100

gR
aR
aR

3NE8 018-1
3NE8 020-1
3NE8 021-1

047
047
047

0.205
0.203
0.205

3
3
3

125
160

aR
aR

3NE8 022-1
3NE8 024-1

047
047

0.213
0.207

3
3

6
7
8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

2/5

17

Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 800 V AC

Selection and ordering data


Size

In

Operational Order No.


class

Price

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

047
047
047
047
047

0.753
0.760
0.760
0.754
0.771

3
3
3
3
3

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

1 unit

Unit(s)

Rated voltage 800 V AC


with bolt-on links
Mounting dimensions: 110 mm
21)

1)

250
315
450
500
710

aR
aR
aR
aR
aR

3NE4 327-0B
3NE4 330-0B
3NE4 333-0B
3NE4 334-0B
3NE4 337

Cladding dimensions and grip lugs according to IEC 60269-2-1;


but blade slotted according to IEC 60269-4-1.

Rated voltage 1000 V AC

Selection and ordering data


Size

In

Operational Order No.


class

Price

1 unit

Rated voltage 1000 V AC


for mounting in LV HRC fuse bases
0

32
40
50

gR

3NE4 101
3NE4 102
3NE4 117

047
047
047

0.278
0.277
0.276

3
3
3

63
80
100

aR

3NE4 118
3NE4 120
3NE4 121

047
047
047

0.279
0.276
0.278

3
3
3

3NE4 122
3NE4 124

047
047

0.279
0.279

3
3

3NE3 221
3NE3 222
3NE3 224
3NE3 225
3NE3 227
3NE3 230-0B

047
047
047
047
047
047

0.580
0.568
0.573
0.570
0.580
0.585

3
3
3
3
3
3

3NE3 231
3NE3 232-0B
3NE3 233

047
047
047

0.590
0.576
0.720

3
3
3

3NE3 332-0B
3NE3 333
3NE3 334-0B
3NE3 335
3NE3 336

047
047
047
047
047

0.759
0.748
0.753
0.756
0.760

3
3
3
3
3

3NE3 337-8
3NE3 338-8
3NE3 340-8

047
047
047

0.762
0.764
0.753

3
3
3

3NE3 421
3NE3 626
3NE3 430
3NE3 432
3NE3 635
3NE3 635-6

047
047
047
047
047
047

1.200
1.300
1.241
1.247
1.179
1.184

3
3
3
3
3
3

3NE3 434
3NE3 636
3NE3 637

047
047
047

1.490
1.213
1.190

3
3
3

3NE3 637-1

047

1.246

125
160
with bolt-on links
Mounting dimensions: 110 mm
11)

100
125
160
200
250
315

aR

350
400
450
21)

400
450
500
560
630

aR

7102)
8003)
9004)

Mounting dimensions: 130 mm


3

100
224
315
400
450
4505)

aR

500
630
710
Mounting dimensions: 140 mm, M12 screw connection
3
710
1)
2)
3)

Cladding dimensions and grip lugs according to IEC 60269-2-1;


but blade slotted according to IEC 60269-4-1.
Rated voltage 900 V AC.

aR
4)
5)

Rated voltage 690 V AC.


Design according to 3NE6 4.. and 3NE9 4...

Rated voltage 800 V AC.

2/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1500 V AC

Selection and ordering data


Size

In

Operational Order No.


class

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Rated voltage 1500 V AC


with bolt-on links
Mounting dimensions: 210 mm
3

Mounting dimensions: 170 mm


3

1)

160
224
315
350
450
4501)

aR

250
450
600

3NE5 424
3NE5 426
3NE5 430
3NE5 431
3NE5 433
3NE5 433-1

047
047
047
047
047
047

1.900
1.968
2.000
1.959
2.100
1.961

2
2
2
2
2
2

3NE5 627
3NE5 633
3NE5 643

047
047
047

1.562
1.585
1.587

3
3
3

6
7

Rated voltage 2000 V AC

Selection and ordering data


In

Operational Order No.


class

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Rated voltage 2000 V AC


with bolt-on links
Mounting dimensions: 210 mm
3

200
250
350
400
450
4501)
5251)
630
6301)
7101)

1)

aR

3NE7 425
3NE7 427
3NE7 431
3NE7 432
3NE7 633
3NE7 633-1
3NE7 648-1

047
047
047
047
047
047
047

2.100
1.970
1.980
1.973
1.968
1.983
1.975

2
2
2
2
2
2
2

3NE7 636
3NE7 636-1
3NE7 637-1

047
047
047

1.997
2.024
1.997

2
2
2

3
4
5

M12 screw connection

Size

1
2

8
9
10
11
12

M12 screw connection

13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

2/7

17

Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 2500 V AC

Selection and ordering data


Size

In

Operational Order No.


class

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

2.542
2.550
2.557

1
1
1

Unit(s)

Rated voltage 2500 V AC


with bolt-on links
Mounting dimensions: 260 mm
3

1)

4001)
5001)
6301)

aR

3NE9 632-1
3NE9 634-1
3NE9 636-1A

047
047
047

M12 screw connection

2/8

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Semiconductor Fuses
SITOR Fuse Links for Special Applications
For rectifiers in electrolysis systems

Selection and ordering data


In

Un

V AC

Operational
class

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

For rectifiers in electrolysis systems


for screwing onto water-cooled busbars
350
600
630
800

800
1000
800
1000

710
1250

900
600

aR

3NC5 531
3NC5 840
3NC5 841
3NC5 838

047
047
047
047

0.671
1.408
1.185
1.196

1/3
3
3
3

3NE6 437-7
3NE9 450-7

047
047

1.168
1.245

3
3

800
1000
1000
800

gR

3NE6 437
3NE9 440-6
3NE6 444
3NE9 450

047
047
047
047

1.093
1.082
1.175
1.114

3
3
3
3

aR

3
4
5
6
7

For air-cooled rectifiers in electrolysis systems


710
850
900
1250

1
2

8
9
10
11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

2/9

17

Semiconductor Fuses
SITOR Fuse Links for Special Applications
For SITOR thyristor sets

Selection and ordering data


In

Un

Operational
class

Order No.

V AC

200
450

1000

aR

3NE3 525-5
3NE3 535-5

50
100
170

1000

gR
aR

250
315
450

800

aR

Price

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

047
047

0.744
0.746

3
3

3NE4 117-5
3NE4 121-5
3NE4 146-5

047
047
047

0.303
0.309
0.311

1/3
1/3
1/3

3NE4 327-6B
3NE4 330-6B
3NE4 333-6B

047
047
047

0.692
0.688
0.690

3
3
3

3NE4 334-6B
3NE4 337-6

047
047

0.688
0.689

3
3

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.725
0.740

3
3

1 unit

Unit(s)

For SITOR 6QG10 thyristor sets

For SITOR 6QG11 thyristor sets


800

For SITOR 6QG12 thyristor sets

500
710

For railway supply rectifiers

Selection and ordering data


In

Un

V AC

250
350

680

Operational
class

Order No.

Price

1 unit

For railway supply rectifiers

2/10

Siemens ET B1 2007

aR

3NC7 327-2
3NC7 331-2

047
047

* You can order this quantity or a multiple thereof.

Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links

Selection and ordering data


Size

In

Un

mm mm

V AC/V DC

Operational
class

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Cylindrical fuse links


10 38

3
6
8

600/

aR

10
12
16
20
25
32
14 51

22 58

1
2
3
4

660/700

5
6
10
15
20

690/700

aR

1
2
3
4

3NC1 003
3NC1 006
3NC1 008

047
047
047

0.009
0.009
0.009

10
10
10

3NC1 010
3NC1 012
3NC1 016
3NC1 020
3NC1 025
3NC1 032

047
047
047
047
047
047

0.009
0.009
0.009
0.009
0.009
0.009

10
10
10
10
10
10

3NC1 401
3NC1 402
3NC1 403
3NC1 404

047
047
047
047

0.020
0.020
0.020
0.020

10
10
10
10

3NC1 405
3NC1 406
3NC1 410
3NC1 415
3NC1 420

047
047
047
047
047
047

0.020
0.020
0.020
0.020
0.020

10
10
10
10
10

047
047

0.020
0.020
0.021

10
10
10

6
7

25
30
32

3NC1 425
3NC1 430
3NC1 432

40
50
20
25
32

3NC1 440
3NC1 450
3NC2 220
3NC2 225
3NC2 232

047
047
047
047
047

0.021
0.021
0.056
0.056
0.056

10
10
5
5
5

3NC2 240
3NC2 250
3NC2 263
3NC2 280
3NC2 200

047
047
047
047
047

0.056
0.056
0.056
0.057
0.057

5
5
5
5
5

3NC1 410-5
3NC1 415-5
3NC1 420-5

047
047
047

0.020
0.020
0.020

10
10
10

3NC1 425-5
3NC1 430-5
3NC1 432-5
3NC1 440-5
3NC1 450-5

047
047
047
047
047

0.020
0.020
0.020
0.020
0.020

10
10
10
10
10

3NC2 220-5
3NC2 225-5
3NC2 232-5

047
047
047

0.056
0.056
0.056

10
10
10

3NC2 240-5
3NC2 250-5
3NC2 263-5
3NC2 280-5
3NC2 200-5

047
047
047
047
047

0.056
0.056
0.056
0.057
0.057

10
10
10
10
10

40
50
63
80
100

690/700

aR

600/700

Cylindrical fuse links with striking pin


14 51

10
15
20

690/700

aR

25
30
32
40
50
22 58

20
25
32
40
50
63
80
100

690/700

600/700

aR

10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

2/11

17

Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links

Accessories
Size

Version

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Cylindrical fuse holders/cylindrical fuse switch disconnectors/


cylindrical fuse disconnectors1)
10 x 38

1-pole
2-pole
3-pole
1-pole
2-pole
3-pole

3NC1 091
3NC1 092
3NC1 093
3NC1 491
3NC1 492
3NC1 493

047
047
047
047
047
047

0.065
0.131
0.197
0.125
0.233
0.350

12
6
4
6
3
2

1-pole
2-pole
3-pole

3NC2 291
3NC2 292
3NC2 293

047
047
047

0.193
0.381
0.584

6
3
2

for fuse links with striking pin


14 x 51

1-pole

3NC1 491-5

047

0.125

22 x 58

1-pole

3NC2 291-5

047

0.193

10 x 38

1-pole
2-pole
3-pole

3NC1 038-1
3NC1 038-2
3NC1 038-3

047
047
047

0.042
0.077
0.113

10
8
6

14 x 51

1-pole2)

3NC1 451-1

047

0.120

22 x 58

1-pole2)

3NC2 258-1

047

0.238

for fuses 10 x 38
for fuses 14 x 51

3NC1 038
3NC1 451

047
047

0.002
0.005

20
20

10 x 38,
14 x 51,
22 x 58

3NC1 000

047

0.069

14 x 51

22 x 58

3NC1 491-5

Cylindrical fuse bases

Cylindrical fuse clips

Fuse tongs

For busbars, see chapter "Busbars for modular installation devices".


1)

2)

Fuse holders according to IEC 60269-3, UL 512,


fuse switch disconnectors (10 x 38, 14 x 51) according to IEC 60947-3,
fuse disconnectors (22 x 58) according to IEC 60947-3
The cylindrical fuse bases can be modularly expanded to make multi-pole
bases.

2/12

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Semiconductor Fuses
SILIZED Fuse Links
NEOZED fuse links SILIZED

Selection and ordering data


Size

Order No.

In

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Rated voltage 400 V AC/250 V DC, gR operational class


Consumer packings, pack of 10
D01

10
16

5SE1 310
5SE1 316

016
016

0.006
0.007

10
10

D02

20
25
35
50
63

5SE1 320
5SE1 325
5SE1 335
5SE1 350
5SE1 363

016
016
016
016
016

0.012
0.012
0.012
0.013
0.014

10
10
10
10
10

DIAZED fuse links SILIZED

Selection and ordering data


Size

In

Identification
color

Thread

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Rated voltage 500 V AC/500 V DC

1
2
3
4
5
6
7
8

DIN VDE 0636-301


for semiconductor protection, designation, yellow ring
Operational class gR, characteristic super quick
DII DIAZED screw adapter for 25 A
is used for the 30 A fuse links
DII
16
gray
E27
20
blue
25
yellow
30
DIII

DIV

35
50
63
80
100

black
white
copper
silver
red

E33

R1"

9
5SD4 20
5SD4 30
5SD4 40

016
016
016

0.028
0.029
0.031

5
5
5

5SD4 80

016

0.031

5SD4 50
5SD4 60
5SD4 70
5SD5 10
5SD5 20

016
016
016
016
016

0.050
0.051
0.054
0.110
0.110

5
5
5
3
3

10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

2/13

17

Semiconductor Fuses
Notes

7
2/14

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers

General Data

3/2

Product overview

Standard Product Range

3/3
3/4
3/5

5SJ6 ...-.KS, 6 kA
5SY6 ...-.KV, 6 kA
Auxiliary switches/fault signal
contacts for 5SY6 ...-.KV

High-Capacity Product
Range

3/6
3/10
3/11
3/12
3/16
3/19

5SY6, 6 kA
5SJ4 ...-.HG40, 14 kA
5SJ4 ...-.HG41, 14 kA
5SY4, 10 kA
5SY7, 15 kA
5SY8, 25 kA

UC Product Range

3/21

5SY5, 10 kA

High-Current Product
Range

3/22

5SP4, 10 kA

Additional Components

3/23
3/24
3/25

RC units for 5SY.


RC units for 5SP4
Auxiliary switches/fault signal
contacts for 5SY. and 5SP4
Remote-controlled mechanisms for
5SY. and 5SP4
Shunt trips/undervoltage releases
for 5SY. and 5SP4

3/26
3/27

Accessories

3/28

For 5SJ6, 5SY. and 5SP4

Power Supply Company


Product Range

3/29

5SP3, 25 kA
mounting depth 92 mm
Accessories
for 5SP3, 25 kA

3/30
Special Range

3/31

Circuit-breaker terminals for


auxiliary circuits

3/1

Miniature Circuit-Breakers
General Data
Product overview

Overview
Rated currents In

5SJ6 ...-.KS

70

10

5SY6 ...-.KV

Standards

Rated switching capacity

Usage

Industry

Device
mounting
depth
[mm]

Res. buildings

Tripping
characteristic

Non-res. buildings

Version

--

----

--

---

--

--

10 000
3

--

--

--

--

10 000

---

--

--

--

Energy limitation class

Standard product range

... 20 A

6
2

... 40 A
... 40 A

... 63 A

6 000
3

EN 60898-1

High-capacity product range


5SY6

5SJ4

5SY4

5SY7

5SY8

70

0.3 ... 63 A

0.3 ... 63 A

0.3 ... 63 A

0.3 ... 63 A

... 63 A

... 80 A

0.3 ... 80 A

0.3 ... 63 A

0.3 ... 63 A

0.3 ... 63 A

0.3 ... 63 A

0.3 ... 63 A

10 000
3

EN 60898-1

... 63 A

UL 489
14/10 kA
CSA 22.2 No. 502

10 000
3

EN 60898-1

15 000
3

... 63 A

EN 60947-2

25 kA

UC product range
5SY5

70

2 ... 63 A

EN 60898-2

0.3 ... 63 A

High-current product range


5SP4

70

80 ... 125 A

80 ... 125 A

80 ... 100 A

EN 60898-1

--

Power supply company product range


5SP3

92

16 ... 100 A

8WA1

--

12.5/22.5 0.5 ... 10 A

Approvals

VDE

DIN VDE 0645

25 000

Special range
EN 60947-2

--

IMQ

UL

BV

DNV

GL

LRS

CCC

5SJ6 ...-.KS

High-capacity product range


5SY6

--

--

--

--

--

--

--

--

5SY6 ...-.KV

--

--

5SJ4

--

--

--

--

--

--

--

--

5SY4

--

5SY8

--

--

--

5SY7

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

Standard product range

UC product range
5SY5

High-current product range


5SP4

Power supply company product range


5SP3

3/2

Siemens ET B1 2007

Miniature Circuit-Breakers

6 000
3

Standard Product Range


5SJ6 ...-.KS, 6 kA

Benefits

Application

Quicker and safer connection of load circuits using screwless


terminal pairs on the outgoing terminals.
If using flexible conductors, no end sleeve necessary
Outstanding touch protection according to VBG4/BGV A3
Simple voltage test thanks to test point on side of outgoing terminal
Complete compatibility with all other 5SJ and 5SY miniature circuitbreakers

Un: 230/400 V, 50 to 60 Hz, can be used in systems up to


250/440 V AC, 60 V DC per pole
Standards: IEC/EN 60898, DIN VDE 0641 Part 11
Particularly suitable for use in lighting and socket circuits in
residential buildings.

Functions
Double, screwless outgoing terminal for rigid and flexible conductors from 1.5 to 4 mm2
Tool-free disconnection and manual removal

Selection and ordering data


In

MW

PG

Characteristic B
Order No.

Preis

Order No.

1 Stck

Preis

PG

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

Characteristic C

10
13
16

20

3
4
5

5SJ6 110-6KS
5SJ6 113-6KS
5SJ6 116-6KS

002
002
002

5SJ6 110-7KS
5SJ6 113-7KS
5SJ6 116-7KS

003
003
003

0.111
0.111
0.111

1/12
1/12
1/12

5SJ6 120-6KS

002

5SJ6 120-7KS

003

0.111

1/12

6
7
8

1-pole
1

1
2

1-pole + N
1 N

2 N

10
13
16
20

5SJ6 510-6KS
5SJ6 513-6KS
5SJ6 516-6KS
5SJ6 520-6KS

002
002
002
002

5SJ6 510-7KS
5SJ6 513-7KS
5SJ6 516-7KS
5SJ6 520-7KS

003
003
003
003

0.185
0.185
0.185
0.185

1/12
1/12
1/12
1/12

10
13
16

5SJ6 210-6KS
5SJ6 213-6KS
5SJ6 216-6KS

002
002
002

5SJ6 210-7KS
5SJ6 213-7KS
5SJ6 216-7KS

003
003
003

0.225
0.225
0.225

1/12
1/12
1/12

5SJ6 220-6KS

002

5SJ6 220-7KS

003

0.225

1/12

5SJ6 310-6KS
5SJ6 313-6KS
5SJ6 316-6KS
5SJ6 320-6KS

002
002
002
002

5SJ6 310-7KS
5SJ6 313-7KS
5SJ6 316-7KS
5SJ6 320-7KS

003
003
003
003

0.345
0.345
0.345
0.345

1/12
1/12
1/12
1/12

2-pole
1 3

2 4

3-pole

20

1 3 5

2 4 6

10
13
16
20

9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/3

17

Miniature Circuit-Breakers

6 000
3

Standard Product Range


5SY6 ...-.KV, 6 kA

Application
Un: 230 V AC, 50 to 60 Hz
Standards: IEC/EN 60898, DIN VDE 0641 Part 11
1+N in 1 MW for distribution applications with little available space
Additional components can be retrofitted

Selection and ordering data


In

MW

Characteristic B
Order No.

PG
Preis

Characteristic C
Order No.

1 Stck

PG
Preis
1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

1-pole + N
2 N

1 N

2
4
6
8
10
13
16
20
25
32
40

3/4

Siemens ET B1 2007

5SY6 006-6KV

5SY6 010-6KV
5SY6 013-6KV
5SY6 016-6KV
5SY6 020-6KV
5SY6 025-6KV
5SY6 032-6KV
5SY6 040-6KV

002
002

5SY6 002-7KV
5SY6 004-7KV
5SY6 006-7KV
5SY6 008-7KV
5SY6 010-7KV
5SY6 013-7KV

003
003
003
003
003
003

0.132
0.132
0.132
0.132
0.132
0.132

1/12
1/12
1/12
1/12
1/12
1/12

002
002
002
002
002

5SY6 016-7KV
5SY6 020-7KV
5SY6 025-7KV
5SY6 032-7KV
5SY6 040-7KV

003
003
003
003
003

0.132
0.132
0.132
0.132
0.132

1/12
1/12
1/12
1/12
1/12

002

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers
Standard Product Range
Auxiliary switches/fault signal contacts
for 5SY6 ...-.KV

Benefits

Application

An auxiliary switch or fault signal contact can be retrofitted to the


left-hand side of the circuit-breaker housing
Mounting with factory-fitted screws
Can be connected to instabus KNX EIB and AS-Interface bus or
PROFIBUS via binary inputs.

Auxiliary switches: indications of the circuit state of the miniature


circuit-breaker: ON/OFF
Fault signal contacts: signaling of electrical triggering, no signaling
of mechanical shut-down
Short-circuit protection ensured by miniature circuit-breakers of
characteristic B or C with In = 4 A or fuse gL 4 A
Product standards: IEC/EN 62019 (VDE 0640)

AS/FC RCBO

1
2
3
4
5

input

in s ta b u s K N X E IB
I2_08258d

6
7

Technical specifications
5ST3 018-0KV, 5ST3 028-0KV
Terminals
Conductor cross-section

mm2

0.5 ... 2.5

Recommended tightening torque

Nm

0.6 ... 0.8


50 mA/24 V

Min. contact load

Max. contact load


230 V AC, AC-15

230 V AC, AC-13


110 V DC, DC-12

A
A

3
0.5

Selection and ordering data


Version

MW

Order No.

Preis

PG

1 Stck

Weight
1 unit
approx.

PS*
P. unit

kg

Unit(s)

0.037

Auxiliary switches (AS) for 5SY6 ...-.KV


1 NO + 1 NC

1 4

0.5

5ST3 018-0KV

027

9
10

1 3

11

2 1
2 2

12

Fault signal contacts (FC) for 5SY6 ...-.KV


1 1
1 2

2W

9 5
1 4 9 6

0.5

5ST3 028-0KV

027

0.050

9 8

13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/5

17

Miniature Circuit-Breakers

6 000
3

High-Capacity Product Range


5SY6, 6 kA

Application
Un: 230/400 V, 50 to 60 Hz, can be used in systems up to
250/440 V AC, 60 V DC per pole

Standards: IEC/EN 60898, DIN VDE 0641 Part 11


Additional components can be retrofitted

Selection and ordering data


In

MW

Preis

PG

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

Characteristic B
Order No.

A
1-pole1)
1

2
4

5SY6 102-6
5SY6 104-6

002
002

0.165
0.165

1/12
1/12

6
10
13
16
20
25

5SY6 106-6
5SY6 110-6
5SY6 113-6
5SY6 116-6
5SY6 120-6
5SY6 125-6

002
002
002
002
002
002

0.165
0.165
0.165
0.165
0.165
0.165

1/12
1/12
1/12
1/12
1/12
1/12

321)
40
50
63

5SY6 132-6
5SY6 140-6
5SY6 150-6
5SY6 163-6

002
002
002
002

0.165
0.165
0.165
0.165

1/12
1
1
1

5SY6 506-6
5SY6 510-6
5SY6 513-6

002
002
002

0.330
0.330
0.330

1
1
1/6

16
20
25

5SY6 516-6
5SY6 520-6
5SY6 525-6

002
002
002

0.330
0.330
0.330

1/6
1
1

32
40
50
63

5SY6 532-6
5SY6 540-6
5SY6 550-6
5SY6 563-6

002
002
002
002

0.330
0.330
0.330
0.330

1
1
1
1

1-pole + N
1 N

2 N

6
10
13

2-pole
1 3

2 4

6
10
13
16
20
25
32
40
50
63

5SY6 206-6
5SY6 210-6
5SY6 213-6
5SY6 216-6
5SY6 220-6
5SY6 225-6
5SY6 232-6
5SY6 240-6
5SY6 250-6
5SY6 263-6

002
002
002
002
002
002
002
002
002
002

0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330

1/6
1/6
1
1/6
1
1
1
1
1
1

6
10
13

5SY6 306-6
5SY6 310-6
5SY6 313-6

002
002
002

0.495
0.495
0.495

1
1/4
1

16
20
25

5SY6 316-6
5SY6 320-6
5SY6 325-6

002
002
002

0.495
0.495
0.495

1/4
1
1

321)
40
50
63

5SY6 332-6
5SY6 340-6
5SY6 350-6
5SY6 363-6

002
002
002
002

0.495
0.495
0.495
0.495

1/4
1
1
1

3-pole
1 3 5

2 4 6

The 5SY6 versions are certified acc. to UL 1077 and CSA 22.2
No. 235-M 89 and can be installed as "supplementary protectors"
up to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole, 3-pole,
3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories,
see page 3/28.
1)

Also suitable for 21-kW active power with three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of
miniature circuit-breakers of characteristic B or C and In = 40 A is
recommended for continuous load applications.

3/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers

6 000
3

High-Capacity Product Range


5SY6, 6 kA
In

MW

Characteristic B
Order No.

PG
Preis
1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

3-pole + N
1 3 5 N

2 4 6 N

6
10
13
16
20
25

5SY6 606-6
5SY6 610-6
5SY6 613-6
5SY6 616-6
5SY6 620-6
5SY6 625-6

002
002
002
002
002
002

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

5SY6 632-6
5SY6 640-6
5SY6 650-6
5SY6 663-6

002
002
002
002

0.660
0.660
0.660
0.660

1
1
1
1

5SY6 406-6
5SY6 410-6
5SY6 413-6

002
002
002

0.660
0.660
0.660

1
1
1

16
20
25

5SY6 416-6
5SY6 420-6
5SY6 425-6

002
002
002

0.660
0.660
0.660

1
1
1

32
40
50
63

5SY6 432-6
5SY6 440-6
5SY6 450-6
5SY6 463-6

002
002
002
002

0.660
0.660
0.660
0.660

1
1
1
1

32
40
50
63

2 4 6 8

6
10
13

3
4
5

4-pole
1 3 5 7

1
2

6
7

The 5SY6 versions are certified acc. to UL 1077 and CSA 22.2
No. 235-M 89 and can be installed as "supplementary protectors"
up to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole, 3-pole,
3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories,
see page 3/28.

8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/7

17

Miniature Circuit-Breakers

6 000
3

High-Capacity Product Range


5SY6, 6 kA

Application
Un: 230/400 V, 50 to 60 Hz, can be used in systems up to
250/440 V AC, 60 V DC per pole

Standards: IEC/EN 60898, DIN VDE 0641 Part 11


Additional components can be retrofitted

Selection and ordering data


In

MW

PG

Characteristic C
Order No.

Preis

Order No.

1 Stck

Preis

PG

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

Characteristic D

1-pole
0.3
0.5
1

5SY6 114-7
5SY6 105-7
5SY6 101-7

003
003
003

5SY6 114-8
5SY6 105-8
5SY6 101-8

004
004
004

0.165
0.165
0.165

1
1
1

5SY6 115-7
5SY6 102-7
5SY6 103-7
5SY6 104-7
5SY6 106-7
5SY6 108-7

003
003
003
003
003
003

5SY6 115-8
5SY6 102-8
5SY6 103-8
5SY6 104-8
5SY6 106-8
5SY6 108-8

004
004
004
004
004
004

0.147
0.165
0.165
0.165
0.165
0.165

1
1/12
1
1
1/12
1

10
13
16

5SY6 110-7
5SY6 113-7
5SY6 116-7

003
003
003

5SY6 110-8
5SY6 113-8
5SY6 116-8

004
004
004

0.165
0.165
0.165

1
1
1

20
25
32 1)
40
50
63

5SY6 120-7
5SY6 125-7
5SY6 132-7
5SY6 140-7
5SY6 150-7
5SY6 163-7

003
003
003
003
003
003

5SY6 120-8
5SY6 125-8
5SY6 132-8
5SY6 140-8
5SY6 150-8
5SY6 163-8

004
004
004
004
004
004

0.165
0.165
0.165
0.165
0.165
0.165

1
1
1
1
1
1

5SY6 514-7
5SY6 505-7
5SY6 501-7
5SY6 515-7
5SY6 502-7
5SY6 503-7

003
003
003
003
003
003

5SY6 514-8
5SY6 505-8
5SY6 501-8
5SY6 515-8
5SY6 502-8
5SY6 503-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

4
6
8
10
13
16
20
25
32

5SY6 504-7
5SY6 506-7
5SY6 508-7
5SY6 510-7
5SY6 513-7
5SY6 516-7
5SY6 520-7
5SY6 525-7
5SY6 532-7

003
003
003
003
003
003
003
003
003

5SY6 504-8
5SY6 506-8
5SY6 508-8
5SY6 510-8
5SY6 513-8
5SY6 516-8
5SY6 520-8
5SY6 525-8
5SY6 532-8

004
004
004
004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1
1
1
1

40
50
63

5SY6 540-7
5SY6 550-7
5SY6 563-7

003
003
003

5SY6 540-8
5SY6 550-8
5SY6 563-8

004
004
004

0.330
0.330
0.330

1
1
1

5SY6 214-7
5SY6 205-7
5SY6 201-7

003
003
003

5SY6 214-8
5SY6 205-8
5SY6 201-8

004
004
004

0.330
0.330
0.330

1
1
1

5SY6 215-7
5SY6 202-7
5SY6 203-7
5SY6 204-7
5SY6 206-7
5SY6 208-7

003
003
003
003
003
003

5SY6 215-8
5SY6 202-8
5SY6 203-8
5SY6 204-8
5SY6 206-8
5SY6 208-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1/6
1
1/6
1/6
1

10
13
16

5SY6 210-7
5SY6 213-7
5SY6 216-7

003
003
003

5SY6 210-8
5SY6 213-8
5SY6 216-8

004
004
004

0.330
0.330
0.330

1/6
1
1

20
25
32
40
50
63

5SY6 220-7
5SY6 225-7
5SY6 232-7
5SY6 240-7
5SY6 250-7
5SY6 263-7

003
003
003
003
003
003

5SY6 220-8
5SY6 225-8
5SY6 232-8
5SY6 240-8
5SY6 250-8
5SY6 263-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

1.6
2
3
4
6
8

1-pole + N
0.3
0.5
1
1.6
2
3

1 N

2 N

2-pole
0.3
0.5
1

1 3

2 4

1.6
2
3
4
6
8

The 5SY6 versions are certified acc. to UL 1077 and CSA 22.2
No. 235-M 89 and can be installed as "supplementary protectors"
up to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole, 3-pole,
3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories,
see page 3/28.

3/8

Siemens ET B1 2007

1)

Also suitable for 21-kW active power with three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of
miniature circuit-breakers of characteristic B or C and In = 40 A is
recommended for continuous load applications.

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers

6 000
3

High-Capacity Product Range


5SY6, 6 kA
In

MW

Characteristic C
Order No.

PG
Preis

Characteristic D
Order No.

1 Stck

PG
Preis
1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

3-pole
1 3 5

2 4 6

0.3
0.5
1
1.6
2
3

5SY6 314-7
5SY6 305-7
5SY6 301-7
5SY6 315-7
5SY6 302-7
5SY6 303-7

003
003
003
003
003
003

5SY6 314-8
5SY6 305-8
5SY6 301-8
5SY6 315-8
5SY6 302-8
5SY6 303-8

004
004
004
004
004
004

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1
1
1
1

4
6
8

5SY6 304-7
5SY6 306-7
5SY6 308-7

003
003
003

5SY6 304-8
5SY6 306-8
5SY6 308-8

004
004
004

0.495
0.495
0.495

1
1
1

10
13
16
20
25
321)

5SY6 310-7
5SY6 313-7
5SY6 316-7
5SY6 320-7
5SY6 325-7
5SY6 332-7

003
003
003
003
003
003

5SY6 310-8
5SY6 313-8
5SY6 316-8
5SY6 320-8
5SY6 325-8
5SY6 332-8

004
004
004
004
004
004

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1
1
1
1

40
50
63

5SY6 340-7
5SY6 350-7
5SY6 363-7

003
003
003

5SY6 340-8
5SY6 350-8
5SY6 363-8

004
004
004

0.495
0.495
0.495

1
1
1

5SY6 614-7
5SY6 605-7
5SY6 601-7

003
003
003

5SY6 614-8
5SY6 605-8
5SY6 601-8

004
004
004

0.660
0.660
0.660

1
1
1

2 4 6 N

1.6
2
3
4
6
8
10
13
16

5SY6 615-7
5SY6 602-7
5SY6 603-7
5SY6 604-7
5SY6 606-7
5SY6 608-7
5SY6 610-7
5SY6 613-7
5SY6 616-7

003
003
003
003
003
003
003
003
003

5SY6 615-8
5SY6 602-8
5SY6 603-8
5SY6 604-8
5SY6 606-8
5SY6 608-8
5SY6 610-8
5SY6 613-8
5SY6 616-8

004
004
004
004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1
1
1
1

20
25
32
40
50
63

5SY6 620-7
5SY6 625-7
5SY6 632-7
5SY6 640-7
5SY6 650-7
5SY6 663-7

003
003
003
003
003
003

5SY6 620-8
5SY6 625-8
5SY6 632-8
5SY6 640-8
5SY6 650-8
5SY6 663-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

5SY6 414-7
5SY6 405-7
5SY6 401-7
5SY6 415-7
5SY6 402-7
5SY6 403-7

003
003
003
003
003
003

5SY6 414-8
5SY6 405-8
5SY6 401-8
5SY6 415-8
5SY6 402-8
5SY6 403-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

4
6
8

5SY6 404-7
5SY6 406-7
5SY6 408-7

003
003
003

5SY6 404-8
5SY6 406-8
5SY6 408-8

004
004
004

0.660
0.660
0.660

1
1
1

10
13
16
20
25
32

5SY6 410-7
5SY6 413-7
5SY6 416-7
5SY6 420-7
5SY6 425-7
5SY6 432-7

003
003
003
003
003
003

5SY6 410-8
5SY6 413-8
5SY6 416-8
5SY6 420-8
5SY6 425-8
5SY6 432-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

40
50
63

5SY6 440-7
5SY6 450-7
5SY6 463-7

003
003
003

5SY6 440-8
5SY6 450-8
5SY6 463-8

004
004
004

0.660
0.660
0.660

1
1
1

0.3
0.5
1

6
7
8
9
10

4-pole
1 3 5 7

2 4 6 8

0.3
0.5
1
1.6
2
3

11
12
13
14

The 5SY6 versions are certified acc. to UL 1077 and CSA 22.2
No. 235-M 89 and can be installed as "supplementary protectors" up
to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole, 3-pole,
3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories,
see page 3/28.
1)

15

Also suitable for 21-kW active power with three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of
miniature circuit-breakers of characteristic B or C and In = 40 A is recommended for continuous load applications.

* You can order this quantity or a multiple thereof.

3
4
5

3-pole + N
1 3 5 N

1
2

16
Siemens ET B1 2007

3/9

17

Miniature Circuit-Breakers
High-Capacity Product Range
5SJ4 ...-.HG40, 14 kA

Benefits

Application

Can be used for all NEMA applications according to UL 489 or


CSA C22.2 No. 5-02 "Branch Circuit Protection", no restrictions
with regard to backup protection
Can be used for "field wiring, same polarity" applications, AWG 14
to AWG 4, Cu only
For all applications in residential, non-residential and industrial
buildings

Un: 240 V, 50 to 60 Hz
According to IEC/EN 60898, can be used in systems up to
250/440 V AC, 60 V AC per pole
Acc. to UL 489, CSA C22.2 No. 5-02, can be used in systems up to
- 240 V AC, switching capacity 14 kA (10 kA for devices of
characteristic C with In 45 A and characteristic D with In 25 A).
- 60 V AC, switching capacity 10 kA

Selection and ordering data


MW

In

Preis

PG

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

Characteristic B
Order No.

A
1-pole
6
10
13

In

5SJ4 106-6HG40
5SJ4 110-6HG40
5SJ4 113-6HG40

002
002
002

0.120
0.120
0.120

1/12
1/12
1/12

15
16
20

5SJ4 118-6HG40
5SJ4 116-6HG40
5SJ4 120-6HG40

002
002
002

0.120
0.120
0.120

1/12
1/12
1/12

25
30
32
35
40
45

5SJ4 125-6HG40
5SJ4 130-6HG40
5SJ4 132-6HG40
5SJ4 135-6HG40
5SJ4 140-6HG40
5SJ4 145-6HG40

002
002
002
002
002
002

0.120
0.120
0.120
0.120
0.120
0.120

1/12
1/12
1/12
1/12
1/12
1/12

50
60
63

5SJ4 150-6HG40
5SJ4 160-6HG40
5SJ4 163-6HG40

002
002
002

0.120
0.120
0.120

1/12
1/12
1/12

PG
Preis

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

MW

PG

Characteristic C
Order No.

Preis

Characteristic D
Order No.

1 Stck

A
1-pole
0.3
0.5
1

5SJ4 114-7HG40
5SJ4 105-7HG40
5SJ4 101-7HG40

003
003
003

5SJ4 114-8HG40
5SJ4 105-8HG40
5SJ4 101-8HG40

004
004
004

0.120
0.120
0.120

1/12
1/12
1/12

5SJ4 115-7HG40
5SJ4 102-7HG40
5SJ4 103-7HG40

003
003
003

5SJ4 115-8HG40
5SJ4 102-8HG40
5SJ4 103-8HG40

004
004
004

0.120
0.120
0.120

1/12
1/12
1/12

4
5
6
8
10
13

5SJ4 104-7HG40
5SJ4 111-7HG40
5SJ4 106-7HG40
5SJ4 108-7HG40
5SJ4 110-7HG40
5SJ4 113-7HG40

003
003
003
003
003
003

5SJ4 104-8HG40
5SJ4 111-8HG40
5SJ4 106-8HG40
5SJ4 108-8HG40
5SJ4 110-8HG40
5SJ4 113-8HG40

004
004
004
004
004
004

0.120
0.120
0.120
0.120
0.120
0.120

1/12
1/12
1/12
1/12
1/12
1/12

15
16
20

5SJ4 118-7HG40
5SJ4 116-7HG40
5SJ4 120-7HG40

003
003
003

5SJ4 118-8HG40
5SJ4 116-8HG40
5SJ4 120-8HG40

004
004
004

0.120
0.120
0.120

1/12
1/12
1/12

25
30
32
35
40
45

5SJ4 125-7HG40
5SJ4 130-7HG40
5SJ4 132-7HG40
5SJ4 135-7HG40
5SJ4 140-7HG40
5SJ4 145-7HG40

003
003
003
003
003
003

5SJ4 125-8HG40
5SJ4 130-8HG40
5SJ4 132-8HG40
5SJ4 135-8HG40
5SJ4 140-8HG40
5SJ4 145-8HG40

004
004
004
004
004
004

0.120
0.120
0.120
0.120
0.120
0.120

1/12
1/12
1/12
1/12
1/12
1/12

50
60
63

5SJ4 150-7HG40
5SJ4 160-7HG40
5SJ4 163-7HG40

003
003
003

5SJ4 150-8HG40
5SJ4 160-8HG40
5SJ4 163-8HG40

004
004
004

0.120
0.120
0.120

1/12
1/12
1/12

3/10

1.6
2
3

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers
High-Capacity Product Range

N
Benefits

5SJ4 ...-.HG41, 14 kA

Application

Can be used for all NEMA applications according to UL 489 or


CSA C22.2 No. 5-02 "Branch Circuit Protection", no restrictions
with regard to backup protection
Can be used for "field wiring, opposite polarity" applications,
AWG 14 to AWG 4, Cu only
For all applications in residential, non-residential and industrial
buildings

Un: 240 V, 50 to 60 Hz
Acc. to IEC/EN 60898, can be used in systems up to 250/440 V
AC, 60 V AC per pole
Acc. to UL 489, CSA C22.2 No. 5-02, can be used in systems up to
- 240 V AC, switching capacity 14 kA (10 kA for devices of
characteristic C with In 45 A and characteristic D with In 25 A).
60 V AC, switching capacity 10 kA

Selection and ordering data


In

MW

PG

Characteristic C
Order No.

Preis

Order No.

1 Stck

Preis

PG

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

Characteristic D

1-pole
1

13

5SJ4 113-7HG41

003

5SJ4 113-8HG41

004

0.155

15
16
20

5SJ4 118-7HG41
5SJ4 116-7HG41
5SJ4 120-7HG41

003
003
003

5SJ4 118-8HG41
5SJ4 116-8HG41
5SJ4 120-8HG41

004
004
004

0.155
0.155
0.155

1
1
1

25
30
32
35
40
45

5SJ4 125-7HG41
5SJ4 130-7HG41
5SJ4 132-7HG41
5SJ4 135-7HG41
5SJ4 140-7HG41
5SJ4 145-7HG41

003
003
003
003
003
003

5SJ4 125-8HG41
5SJ4 130-8HG41
5SJ4 132-8HG41
5SJ4 135-8HG41
5SJ4 140-8HG41
5SJ4 145-8HG41

004
004
004
004
004
004

0.155
0.155
0.155
0.155
0.155
0.155

1
1
1
1
1
1

13

5SJ4 213-7HG41

003

5SJ4 213-8HG41

004

0.310

15
16
20

5SJ4 218-7HG41
5SJ4 216-7HG41
5SJ4 220-7HG41

003
003
003

5SJ4 218-8HG41
5SJ4 216-8HG41
5SJ4 220-8HG41

004
004
004

0.310
0.310
0.310

1
1
1

25
30
32
35
40
45

5SJ4 225-7HG41
5SJ4 230-7HG41
5SJ4 232-7HG41
5SJ4 235-7HG41
5SJ4 240-7HG41
5SJ4 245-7HG41

003
003
003
003
003
003

5SJ4 225-8HG41
5SJ4 230-8HG41
5SJ4 232-8HG41
5SJ4 235-8HG41
5SJ4 240-8HG41
5SJ4 245-8HG41

004
004
004
004
004
004

0.310
0.310
0.310
0.310
0.310
0.310

1
1
1
1
1
1

5SJ4 313-7HG41
5SJ4 318-7HG41
5SJ4 316-7HG41
5SJ4 320-7HG41

003
003
003
003

5SJ4 313-8HG41
5SJ4 318-8HG41
5SJ4 316-8HG41
5SJ4 320-8HG41

004
004
004
004

0.465
0.465
0.465
0.465

1
1
1
1

25
30
32

5SJ4 325-7HG41
5SJ4 330-7HG41
5SJ4 332-7HG41

003
003
003

5SJ4 325-8HG41
5SJ4 330-8HG41
5SJ4 332-8HG41

004
004
004

0.465
0.465
0.465

1
1
1

35
40
45

5SJ4 335-7HG41
5SJ4 340-7HG41
5SJ4 345-7HG41

003
003
003

5SJ4 335-8HG41
5SJ4 340-8HG41
5SJ4 345-8HG41

004
004
004

0.465
0.465
0.465

1
1
1

3
4
5
6
7

2-pole
1

1
2

8
9

3-pole
1

13
15
16
20

10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/11

17

Miniature Circuit-Breakers

10 000
3

High-Capacity Product Range


5SY4, 10 kA

Application
Un: 230/400 V, 50 to 60 Hz, can be used in systems up to
250/440 V AC, 60 V DC per pole

Standards: IEC/EN 60898, DIN VDE 0641 Part 11


Additional components can be retrofitted

Selection and ordering data


v

In

MW

PG

Characteristic A
Order No.

Preis

Order No.

1 Stck

Preis

PG

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

0.165
0.165
0.165

1
1
1

Characteristic B

1-pole
1
1.6
2

5SY4 101-5
5SY4 115-5
5SY4 102-5

001
001
001

----

3
4
6

5SY4 103-5
5SY4 104-5
5SY4 106-5

001
001
001

--5SY4 106-6

002

0.165
0.165
0.165

1
1/12
1/12

8
10
13
16
20
25

5SY4 108-5
5SY4 110-5
5SY4 113-5
5SY4 116-5
5SY4 120-5
5SY4 125-5

001
001
001
001
001
001

-5SY4 110-6
5SY4 113-6
5SY4 116-6
5SY4 120-6
5SY4 125-6

002
002
002
002
002

0.165
0.165
0.165
0.165
0.165
0.165

1
1/12
1
1/12
1
1

321)
40
50

5SY4 132-5
5SY4 140-5
5SY4 150-5

001
001
001

5SY4 132-6
5SY4 140-6
5SY4 150-6

002
002
002

0.165
0.165
0.165

1
1
1

63
802)

5SY4 163-5
--

001

5SY4 163-6
5SY4 180-6

002
002

0.165
0.162

1
1/12

5SY4 501-5
5SY4 515-5
5SY4 502-5

001
001
001

----

0.330
0.330
0.330

1
1
1

3
4
6
8
10
13

5SY4 503-5
5SY4 504-5
5SY4 506-5
5SY4 508-5
5SY4 510-5
5SY4 513-5

001
001
001
001
001
001

--5SY4 506-6
-5SY4 510-6
5SY4 513-6

002
002

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1/6

16
20
25

5SY4 516-5
5SY4 520-5
5SY4 525-5

001
001
001

5SY4 516-6
5SY4 520-6
5SY4 525-6

002
002
002

0.330
0.330
0.330

1/6
1
1

32
40
50
63

5SY4 532-5
5SY4 540-5
5SY4 550-5
5SY4 563-5

001
001
001
001

5SY4 532-6
5SY4 540-6
5SY4 550-6
5SY4 563-6

002
002
002
002

0.330
0.330
0.330
0.330

1
1
1
1

5SY4 201-5
5SY4 215-5
5SY4 202-5
5SY4 203-5
5SY4 204-5
5SY4 206-5

001
001
001
001
001
001

-----5SY4 206-6

002

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

8
10
13

5SY4 208-5
5SY4 210-5
5SY4 213-5

001
001
001

-5SY4 210-6
5SY4 213-6

002
002

0.330
0.330
0.330

1
1/6
1

16
20
25
32
40
50

5SY4 216-5
5SY4 220-5
5SY4 225-5
5SY4 232-5
5SY4 240-5
5SY4 250-5

001
001
001
001
001
001

5SY4 216-6
5SY4 220-6
5SY4 225-6
5SY4 232-6
5SY4 240-6
5SY4 250-6

002
002
002
002
002
002

0.330
0.330
0.330
0.330
0.330
0.330

1/6
1
1
1
1
1

63
802)

5SY4 263-5
--

001

5SY4 263-6
5SY4 280-6

002
002

0.330
0.324

1
1/6

1-pole + N
1
1.6
2

1 N

2 N

002

2-pole
1
1.6
2
3
4
6

1 3

2 4

The 5SY4 versions are certified acc. to UL 1077 and CSA 22.2
No. 235-M 89 and can be installed as "supplementary protectors" up
to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole, 3-pole,
3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories,
see page 3/28.
1)

Only applies to 5SY4 132-6:


Also suitable for 21-kW active power at three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of
miniature circuit-breakers of characteristic B or C and In = 40 A is recommended for continuous load applications.

2)

No

V.

3/12

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers

10 000
3

High-Capacity Product Range


5SY4, 10 kA
In

MW

Characteristic A
Order No.

PG
Preis

Characteristic B
Order No.

1 Stck

PG
Preis
1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

3-pole
1 3 5

2 4 6

1
1.6
2

5SY4 301-5
5SY4 315-5
5SY4 302-5

001
001
001

----

0.495
0.495
0.495

1
1
1

3
4
6
8
10
13

5SY4 303-5
5SY4 304-5
5SY4 306-5
5SY4 308-5
5SY4 310-5
5SY4 313-5

001
001
001
001
001
001

--5SY4 306-6
-5SY4 310-6
5SY4 313-6

002
002

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1
1
1
1

16
20
25

5SY4 316-5
5SY4 320-5
5SY4 325-5

001
001
001

5SY4 316-6
5SY4 320-6
5SY4 325-6

002
002
002

0.495
0.495
0.495

1/4
1
1

321)
40
50
63
802)

5SY4 332-5
5SY4 340-5
5SY4 350-5
5SY4 363-5

001
001
001
001

5SY4 332-6
5SY4 340-6
5SY4 350-6
5SY4 363-6
5SY4 380-6

002
002
002
002
002

0.495
0.495
0.495
0.495
0.486

1/4
1
1
1
1/4

5SY4 601-5
5SY4 615-5
5SY4 602-5
5SY4 603-5
5SY4 604-5
5SY4 606-5

001
001
001
001
001
001

-----5SY4 606-6

002

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

8
10
13

5SY4 608-5
5SY4 610-5
5SY4 613-5

001
001
001

-5SY4 610-6
5SY4 613-6

002
002

0.660
0.660
0.660

1
1
1

16
20
25
32
40
50

5SY4 616-5
5SY4 620-5
5SY4 625-5
5SY4 632-5
5SY4 640-5
5SY4 650-5

001
001
001
001
001
001

5SY4 616-6
5SY4 620-6
5SY4 625-6
5SY4 632-6
5SY4 640-6
5SY4 650-6

002
002
002
002
002
002

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

63

5SY4 663-5

001

5SY4 663-6

002

0.660

5SY4 401-5
5SY4 415-5
5SY4 402-5

001
001
001

----

0.660
0.660
0.660

1
1
1

3
4
6

5SY4 403-5
5SY4 404-5
5SY4 406-5

001
001
001

--5SY4 406-6

002

0.660
0.660
0.660

1
1
1

8
10
13
16
20
25

5SY4 408-5
5SY4 410-5
5SY4 413-5
5SY4 416-5
5SY4 420-5
5SY4 425-5

001
001
001
001
001
001

-5SY4 410-6
5SY4 413-6
5SY4 416-6
5SY4 420-6
5SY4 425-6

002
002
002
002
002

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

32
40
50

5SY4 432-5
5SY4 440-5
5SY4 450-5

001
001
001

5SY4 432-6
5SY4 440-6
5SY4 450-6

002
002
002

0.660
0.660
0.660

1
1
1

63
802)

5SY4 463-5

001

5SY4 463-6
5SY4 480-6

002
002

0.660
0.648

1
1/3

002

3-pole + N
1 3 5 N

2 4 6 N

1
1.6
2
3
4
6

1
2
3
4
5
6
7
8
9

4-pole
1 3 5 7

2 4 6 8

1
1.6
2

10
11
12

The 5SY4 versions are certified acc. to UL 1077 and CSA 22.2
No. 235-M 89 and can be installed as "supplementary protectors" up
to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole, 3-pole,
3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories, see
page 3/28.
1)

2)

14

Only applies to 5SY4 332-6:


Also suitable for 21-kW active power at three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of
miniature circuit-breakers of characteristic B or C and In = 40 A is recommended for continuous load applications.
No

13
15

V.

16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/13

17

Miniature Circuit-Breakers

10 000
3

High-Capacity Product Range


5SY4, 10 kA
In

MW

Characteristic C
Order No.

PG
Preis

Characteristic D
Order No.

1 Stck

PG
Preis
1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

1-pole
0.3
0.5
1
1.6
2
3

5SY4 114-7
5SY4 105-7
5SY4 101-7
5SY4 115-7
5SY4 102-7
5SY4 103-7

003
003
003
003
003
003

5SY4 114-8
5SY4 105-8
5SY4 101-8
5SY4 115-8
5SY4 102-8
5SY4 103-8

004
004
004
004
004
004

0.165
0.165
0.165
0.165
0.165
0.165

1
1
1
1
1/12
1

4
6
8

5SY4 104-7
5SY4 106-7
5SY4 108-7

003
003
003

5SY4 104-8
5SY4 106-8
5SY4 108-8

004
004
004

0.165
0.165
0.165

1/12
1
1

10
13
16
20
25
321)

5SY4 110-7
5SY4 113-7
5SY4 116-7
5SY4 120-7
5SY4 125-7
5SY4 132-7

003
003
003
003
003
003

5SY4 110-8
5SY4 113-8
5SY4 116-8
5SY4 120-8
5SY4 125-8
5SY4 132-8

004
004
004
004
004
004

0.165
0.165
0.165
0.165
0.165
0.165

1/12
1
1
1
1
1

40
50
63
802)

5SY4 140-7
5SY4 150-7
5SY4 163-7
5SY4 180-7

003
003
003
003

5SY4 140-8
5SY4 150-8
5SY4 163-8
--

004
004
004

0.165
0.165
0.165
0.161

1
1
1
1/12

0.3
0.5
1
1.6
2
3

5SY4 514-7
5SY4 505-7
5SY4 501-7
5SY4 515-7
5SY4 502-7
5SY4 503-7

003
003
003
003
003
003

5SY4 514-8
5SY4 505-8
5SY4 501-8
5SY4 515-8
5SY4 502-8
5SY4 503-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

4
6
8

5SY4 504-7
5SY4 506-7
5SY4 508-7

003
003
003

5SY4 504-8
5SY4 506-8
5SY4 508-8

004
004
004

0.330
0.330
0.330

1
1
1

10
13
16
20
25
32

5SY4 510-7
5SY4 513-7
5SY4 516-7
5SY4 520-7
5SY4 525-7
5SY4 532-7

003
003
003
003
003
003

5SY4 510-8
5SY4 513-8
5SY4 516-8
5SY4 520-8
5SY4 525-8
5SY4 532-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

40
50
63
802)

5SY4 540-7
5SY4 550-7
5SY4 563-7
5SY4 580-7

003
003
003
003

5SY4 540-8
5SY4 550-8
5SY4 563-8
--

004
004
004

0.330
0.330
0.330
0.323

1
1
1
1/6

0.3
0.5
1

5SY4 214-7
5SY4 205-7
5SY4 201-7

003
003
003

5SY4 214-8
5SY4 205-8
5SY4 201-8

004
004
004

0.330
0.330
0.330

1
1
1

1.6
2
3
4
6
8

5SY4 215-7
5SY4 202-7
5SY4 203-7
5SY4 204-7
5SY4 206-7
5SY4 208-7

003
003
003
003
003
003

5SY4 215-8
5SY4 202-8
5SY4 203-8
5SY4 204-8
5SY4 206-8
5SY4 208-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

10
13
16

5SY4 210-7
5SY4 213-7
5SY4 216-7

003
003
003

5SY4 210-8
5SY4 213-8
5SY4 216-8

004
004
004

0.330
0.330
0.330

1
1
1

20
25
32
40
50
63
802)

5SY4 220-7
5SY4 225-7
5SY4 232-7
5SY4 240-7
5SY4 250-7
5SY4 263-7
5SY4 280-7

003
003
003
003
003
003
003

5SY4 220-8
5SY4 225-8
5SY4 232-8
5SY4 240-8
5SY4 250-8
5SY4 263-8
--

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330
0.323

1
1
1
1
1
1
1

1-pole + N
1 N

2 N

2-pole
1 3

2 4

The 5SY4 versions are certified acc. to UL 1077 and CSA 22.2
No. 235-M 89 and can be installed as "supplementary protectors" up
to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole, 3-pole,
3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories,
see page 3/28.

3/14

Siemens ET B1 2007

1) Only applies to 5SY4 132-7:


Also suitable for 21-kW active power at three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of
miniature circuit-breakers of characteristic B or C and In = 40 A is
recommended for continuous load applications.
2)

No

V.

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers

10 000
3

High-Capacity Product Range


5SY4, 10 kA
In

MW

Characteristic C
Order No.

PG
Preis

Characteristic D
Order No.

1 Stck

PG
Preis
1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

3-pole
1 3 5

2 4 6

0.3
0.5
1
1.6
2
3

5SY4 314-7
5SY4 305-7
5SY4 301-7
5SY4 315-7
5SY4 302-7
5SY4 303-7

003
003
003
003
003
003

5SY4 314-8
5SY4 305-8
5SY4 301-8
5SY4 315-8
5SY4 302-8
5SY4 303-8

004
004
004
004
004
004

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1
1
1
1

4
6
8

5SY4 304-7
5SY4 306-7
5SY4 308-7

003
003
003

5SY4 304-8
5SY4 306-8
5SY4 308-8

004
004
004

0.495
0.495
0.495

1
1
1

10
13
16
20
25
321)

5SY4 310-7
5SY4 313-7
5SY4 316-7
5SY4 320-7
5SY4 325-7
5SY4 332-7

003
003
003
003
003
003

5SY4 310-8
5SY4 313-8
5SY4 316-8
5SY4 320-8
5SY4 325-8
5SY4 332-8

004
004
004
004
004
004

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1/4
1
1
1

40
50
63
802)

5SY4 340-7
5SY4 350-7
5SY4 363-7
5SY4 380-7

003
003
003
003

5SY4 340-8
5SY4 350-8
5SY4 363-8
--

004
004
004

0.495
0.495
0.495
0.482

1
1
1
1

5SY4 614-7
5SY4 605-7
5SY4 601-7
5SY4 615-7
5SY4 602-7
5SY4 603-7

003
003
003
003
003
003

5SY4 614-8
5SY4 605-8
5SY4 601-8
5SY4 615-8
5SY4 602-8
5SY4 603-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

4
6
8

5SY4 604-7
5SY4 606-7
5SY4 608-7

003
003
003

5SY4 604-8
5SY4 606-8
5SY4 608-8

004
004
004

0.660
0.660
0.660

1
1
1

10
13
16
20
25
32

5SY4 610-7
5SY4 613-7
5SY4 616-7
5SY4 620-7
5SY4 625-7
5SY4 632-7

003
003
003
003
003
003

5SY4 610-8
5SY4 613-8
5SY4 616-8
5SY4 620-8
5SY4 625-8
5SY4 632-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

40
50
63
802)

5SY4 640-7
5SY4 650-7
5SY4 663-7
5SY4 680-7

003
003
003
003

5SY4 640-8
5SY4 650-8
5SY4 663-8
--

004
004
004

0.660
0.660
0.660
0.647

1
1
1
1/3

5SY4 414-7
5SY4 405-7
5SY4 401-7

003
003
003

5SY4 414-8
5SY4 405-8
5SY4 401-8

004
004
004

0.660
0.660
0.660

1
1
1

5SY4 415-7
5SY4 402-7
5SY4 403-7
5SY4 404-7
5SY4 406-7
5SY4 408-7

003
003
003
003
003
003

5SY4 415-8
5SY4 402-8
5SY4 403-8
5SY4 404-8
5SY4 406-8
5SY4 408-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

10
13
16

5SY4 410-7
5SY4 413-7
5SY4 416-7

003
003
003

5SY4 410-8
5SY4 413-8
5SY4 416-8

004
004
004

0.660
0.660
0.660

1
1
1

20
25
32
40
50
63
802)

5SY4 420-7
5SY4 425-7
5SY4 432-7
5SY4 440-7
5SY4 450-7
5SY4 463-7
5SY4 480-7

003
003
003
003
003
003
003

5SY4 420-8
5SY4 425-8
5SY4 432-8
5SY4 440-8
5SY4 450-8
5SY4 463-8
--

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660
0.647

1
1
1
1
1
1
1/3

3-pole + N
1 3 5 N

2 4 6 N

0.3
0.5
1
1.6
2
3

2 4 6 8

0.3
0.5
1

1.6
2
3
4
6
8

The 5SY4 and 5SY7 versions are certified acc. to UL 1077 and
CSA 22.2 No. 235-M 89 and can be installed as "supplementary protectors" up to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole,
3-pole, 3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories,
see page 3/28.

* You can order this quantity or a multiple thereof.

No

5
6
7
9
10
11
12

1) Only applies to 5SY4 332-7 and 5SY7 132-6:


Also suitable for 21-kW active power at three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of
miniature circuit-breakers of characteristic B or C and In = 40 A is recommended for continuous load applications.
2)

3
4

4-pole
1 3 5 7

1
2

V.

13
14
15
16

Siemens ET B1 2007

3/15

17

Miniature Circuit-Breakers

15 000
3

High-Capacity Product Range


5SY7, 15 kA

Application
Un: 230/400 V, 50 to 60 Hz, can be used in systems up to
250/440 V AC, 60 V DC per pole

Standards: IEC/EN 60898, DIN VDE 0641 Part 11


Additional components can be retrofitted

Selection and ordering data


In

MW

Preis

PG

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

Characteristic B
Order No.

A
1-pole
1

6
10
13

5SY7 106-6
5SY7 110-6
5SY7 113-6

002
002
002

0.165
0.165
0.165

1
1
1

5SY7 116-6
5SY7 120-6
5SY7 125-6
5SY7 132-6
5SY7 140-6
5SY7 150-6
5SY7 163-6

002
002
002
002
002
002
002

0.165
0.165
0.165
0.165
0.165
0.165
0.165

1
1
1
1
1
1
1

5SY7 506-6
5SY7 510-6
5SY7 513-6
5SY7 516-6
5SY7 520-6
5SY7 525-6

002
002
002
002
002
002

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

5SY7 532-6
5SY7 540-6
5SY7 550-6
5SY7 563-6

002
002
002
002

0.330
0.330
0.330
0.330

1
1
1
1

5SY7 206-6
5SY7 210-6
5SY7 213-6

002
002
002

0.330
0.330
0.330

1
1
1

5SY7 216-6
5SY7 220-6
5SY7 225-6
5SY7 232-6
5SY7 240-6
5SY7 250-6
5SY7 263-6

002
002
002
002
002
002
002

0.330
0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1
1

5SY7 306-6
5SY7 310-6
5SY7 313-6
5SY7 316-6
5SY7 320-6
5SY7 325-6

002
002
002
002
002
002

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1
1
1
1

5SY7 332-6
5SY7 340-6
5SY7 350-6
5SY7 363-6

002
002
002
002

0.495
0.495
0.495
0.495

1
1
1
1

5SY7 606-6
5SY7 610-6
5SY7 613-6

002
002
002

0.660
0.660
0.660

1
1
1

16
20
25

5SY7 616-6
5SY7 620-6
5SY7 625-6

002
002
002

0.660
0.660
0.660

1
1
1

32
40
50
63

5SY7 632-6
5SY7 640-6
5SY7 650-6
5SY7 663-6

002
002
002
002

0.660
0.660
0.660
0.660

1
1
1
1

5SY7 406-6
5SY7 410-6
5SY7 413-6

002
002
002

0.660
0.660
0.660

1
1
1

5SY7 416-6
5SY7 420-6
5SY7 425-6
5SY7 432-6
5SY7 440-6
5SY7 450-6
5SY7 463-6

002
002
002
002
002
002
002

0.660
0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1
1

16
20
25
321)
40
50
63

1-pole + N
1 N

2 N

6
10
13
16
20
25

32
40
50
63
2-pole
1 3

2 4

6
10
13

16
20
25
32
40
50
63

3-pole
1 3 5

2 4 6

6
10
13
16
20
25

32
40
50
63
3-pole + N
1 3 5 N

2 4 6 N

6
10
13

4-pole
1 3 5 7

2 4 6 8

6
10
13
16
20
25
32
40
50
63

For information and footnote, see page 3/17.

3/16

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers

15 000
3

High-Capacity Product Range


5SY7, 15 kA
In

MW

Characteristic C
Order No.

PG
Preis

Characteristic D
Order No.

1 Stck

PG
Preis
1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

1-pole
1

0.3
0.5
1
1.6
2
3

5SY7 114-7
5SY7 105-7
5SY7 101-7
5SY7 115-7
5SY7 102-7
5SY7 103-7

003
003
003
003
003
003

5SY7 114-8
5SY7 105-8
5SY7 101-8
5SY7 115-8
5SY7 102-8
5SY7 103-8

004
004
004
004
004
004

0.165
0.165
0.165
0.165
0.165
0.165

1
1
1
1
1
1

4
6
8

5SY7 104-7
5SY7 106-7
5SY7 108-7

003
003
003

5SY7 104-8
5SY7 106-8
5SY7 108-8

004
004
004

0.165
0.165
0.165

1
1
1

10
13
16
20
25
321)

5SY7 110-7
5SY7 113-7
5SY7 116-7
5SY7 120-7
5SY7 125-7
5SY7 132-7

003
003
003
003
003
003

5SY7 110-8
5SY7 113-8
5SY7 116-8
5SY7 120-8
5SY7 125-8
5SY7 132-8

004
004
004
004
004
004

0.165
0.165
0.165
0.165
0.165
0.165

1
1
1
1
1
1

40
50
63

5SY7 140-7
5SY7 150-7
5SY7 163-7

003
003
003

5SY7 140-8
5SY7 150-8
5SY7 163-8

004
004
004

0.165
0.165
0.165

1
1
1

5SY7 514-7
5SY7 505-7
5SY7 501-7

003
003
003

5SY7 514-8
5SY7 505-8
5SY7 501-8

004
004
004

0.330
0.330
0.330

1
1
1

2 N

1.6
2
3
4
6
8
10
13
16

5SY7 515-7
5SY7 502-7
5SY7 503-7
5SY7 504-7
5SY7 506-7
5SY7 508-7
5SY7 510-7
5SY7 513-7
5SY7 516-7

003
003
003
003
003
003
003
003
003

5SY7 515-8
5SY7 502-8
5SY7 503-8
5SY7 504-8
5SY7 506-8
5SY7 508-8
5SY7 510-8
5SY7 513-8
5SY7 516-8

004
004
004
004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1
1
1
1

20
25
32
40
50
63

5SY7 520-7
5SY7 525-7
5SY7 532-7
5SY7 540-7
5SY7 550-7
5SY7 563-7

003
003
003
003
003
003

5SY7 520-8
5SY7 525-8
5SY7 532-8
5SY7 540-8
5SY7 550-8
5SY7 563-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

5SY7 214-7
5SY7 205-7
5SY7 201-7
5SY7 215-7
5SY7 202-7
5SY7 203-7

003
003
003
003
003
003

5SY7 214-8
5SY7 205-8
5SY7 201-8
5SY7 215-8
5SY7 202-8
5SY7 203-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

4
6
8

5SY7 204-7
5SY7 206-7
5SY7 208-7

003
003
003

5SY7 204-8
5SY7 206-8
5SY7 208-8

004
004
004

0.330
0.330
0.330

1
1
1

10
13
16
20
25
32

5SY7 210-7
5SY7 213-7
5SY7 216-7
5SY7 220-7
5SY7 225-7
5SY7 232-7

003
003
003
003
003
003

5SY7 210-8
5SY7 213-8
5SY7 216-8
5SY7 220-8
5SY7 225-8
5SY7 232-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

40
50
63

5SY7 240-7
5SY7 250-7
5SY7 263-7

003
003
003

5SY7 240-8
5SY7 250-8
5SY7 263-8

004
004
004

0.330
0.330
0.330

1
1
1

0.3
0.5
1

6
7
8
9
10

2-pole
1 3

2 4

0.3
0.5
1
1.6
2
3

11
12
13
14

Information and footnote to pages 3/16 and 3/17:


The 5SY7 versions are certified acc. to UL 1077 and CSA 22.2
No. 235-M 89 and can be installed as "supplementary protectors" up
to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole, 3-pole,
3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories,
see page 3/28.
1)

15

Only applies to 5SY7 132-6 and 5SY7 132-7:


Also suitable for 21-kW active power at three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of
miniature circuit-breakers of characteristic B or C and In = 40 A is recommended for continuous load applications.

* You can order this quantity or a multiple thereof.

3
4
5

1-pole + N
1 N

1
2

16
Siemens ET B1 2007

3/17

17

Miniature Circuit-Breakers

15 000
3

High-Capacity Product Range


5SY7, 15 kA
In

MW

Characteristic C
Order No.

PG
Preis

Characteristic D
Order No.

1 Stck

PG
Preis
1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

3-pole
0.3
0.5
1
1.6
2
3

5SY7 314-7
5SY7 305-7
5SY7 301-7
5SY7 315-7
5SY7 302-7
5SY7 303-7

003
003
003
003
003
003

5SY7 314-8
5SY7 305-8
5SY7 301-8
5SY7 315-8
5SY7 302-8
5SY7 303-8

004
004
004
004
004
004

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1
1
1
1

4
6
8

5SY7 304-7
5SY7 306-7
5SY7 308-7

003
003
003

5SY7 304-8
5SY7 306-8
5SY7 308-8

004
004
004

0.495
0.495
0.495

1
1
1

10
13
16
20
25
321)

5SY7 310-7
5SY7 313-7
5SY7 316-7
5SY7 320-7
5SY7 325-7
5SY7 332-7

003
003
003
003
003
003

5SY7 310-8
5SY7 313-8
5SY7 316-8
5SY7 320-8
5SY7 325-8
5SY7 332-8

004
004
004
004
004
004

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1
1
1
1

40
50
63

5SY7 340-7
5SY7 350-7
5SY7 363-7

003
003
003

5SY7 340-8
5SY7 350-8
5SY7 363-8

004
004
004

0.495
0.495
0.495

1
1
1

5SY7 614-7
5SY7 605-7
5SY7 601-7

003
003
003

5SY7 614-8
5SY7 605-8
5SY7 601-8

004
004
004

0.660
0.660
0.660

1
1
1

1.6
2
3
4
6
8
10
13
16

5SY7 615-7
5SY7 602-7
5SY7 603-7
5SY7 604-7
5SY7 606-7
5SY7 608-7
5SY7 610-7
5SY7 613-7
5SY7 616-7

003
003
003
003
003
003
003
003
003

5SY7 615-8
5SY7 602-8
5SY7 603-8
5SY7 604-8
5SY7 606-8
5SY7 608-8
5SY7 610-8
5SY7 613-8
5SY7 616-8

004
004
004
004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1
1
1
1

20
25
32
40
50
63

5SY7 620-7
5SY7 625-7
5SY7 632-7
5SY7 640-7
5SY7 650-7
5SY7 663-7

003
003
003
003
003
003

5SY7 620-8
5SY7 625-8
5SY7 632-8
5SY7 640-8
5SY7 650-8
5SY7 663-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

5SY7 414-7
5SY7 405-7
5SY7 401-7
5SY7 415-7
5SY7 402-7
5SY7 403-7

003
003
003
003
003
003

5SY7 414-8
5SY7 405-8
5SY7 401-8
5SY7 415-8
5SY7 402-8
5SY7 403-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

4
6
8

5SY7 404-7
5SY7 406-7
5SY7 408-7

003
003
003

5SY7 404-8
5SY7 406-8
5SY7 408-8

004
004
004

0.660
0.660
0.660

1
1
1

10
13
16
20
25
32

5SY7 410-7
5SY7 413-7
5SY7 416-7
5SY7 420-7
5SY7 425-7
5SY7 432-7

003
003
003
003
003
003

5SY7 410-8
5SY7 413-8
5SY7 416-8
5SY7 420-8
5SY7 425-8
5SY7 432-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

40
50
63

5SY7 440-7
5SY7 450-7
5SY7 463-7

003
003
003

5SY7 440-8
5SY7 450-8
5SY7 463-8

004
004
004

0.660
0.660
0.660

1
1
1

1 3 5

2 4 6

3-pole + N
0.3
0.5
1

1 3 5 N

2 4 6 N

4-pole
0.3
0.5
1
1.6
2
3

1 3 5 7

2 4 6 8

The 5SY7 versions are certified acc. to UL 1077 and CSA 22.2
No. 235-M 89 and can be installed as "supplementary protectors" up
to 277 V AC (1-pole, 1-pole + N) and 480 V AC (2-pole, 3-pole,
3-pole + N, 4-pole).
For additional components, see page 3/23; for accessories,
see page 3/28.
1)

Only applies to 5SY7 332-7:


Also suitable for 21-kW active power at three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of
miniature circuit-breakers of characteristic B or C and In = 40 A is recommended for continuous load applications.

3/18

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers
High-Capacity Product Range
5SY8, 25 kA

Application
Un: 230/400 V, 50 to 60 Hz, can be used in systems up to
250/440 V AC, 60 V DC per pole

Standards: IEC/EN 60947-2


Additional components can be retrofitted

Selection and ordering data


In

MW

PG

Characteristic C
Order No.

Preis

Order No.

1 Stck

PG
Preis

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

Characteristic D

1-pole
1

0.3
0.5
1

5SY8 114-7
5SY8 105-7
5SY8 101-7

003
003
003

5SY8 114-8
5SY8 105-8
5SY8 101-8

004
004
004

0.165
0.165
0.165

1
1
1

5SY8 115-7
5SY8 102-7
5SY8 103-7
5SY8 104-7
5SY8 106-7
5SY8 108-7

003
003
003
003
003
003

5SY8 115-8
5SY8 102-8
5SY8 103-8
5SY8 104-8
5SY8 106-8
5SY8 108-8

004
004
004
004
004
004

0.165
0.165
0.165
0.165
0.165
0.165

1
1
1
1
1
1

10
13
16

5SY8 110-7
5SY8 113-7
5SY8 116-7

003
003
003

5SY8 110-8
5SY8 113-8
5SY8 116-8

004
004
004

0.165
0.165
0.165

1
1
1

20
25
321)
40
50
63

5SY8 120-7
5SY8 125-7
5SY8 132-7
5SY8 140-7
5SY8 150-7
5SY8 163-7

003
003
003
003
003
003

5SY8 120-8
5SY8 125-8
5SY8 132-8
5SY8 140-8
5SY8 150-8
5SY8 163-8

004
004
004
004
004
004

0.165
0.165
0.165
0.165
0.165
0.165

1
1
1
1
1
1

5SY8 514-7
5SY8 505-7
5SY8 501-7
5SY8 515-7
5SY8 502-7
5SY8 503-7

003
003
003
003
003
003

5SY8 514-8
5SY8 505-8
5SY8 501-8
5SY8 515-8
5SY8 502-8
5SY8 503-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

4
6
8
10
13
16
20
25
32

5SY8 504-7
5SY8 506-7
5SY8 508-7
5SY8 510-7
5SY8 513-7
5SY8 516-7
5SY8 520-7
5SY8 525-7
5SY8 532-7

003
003
003
003
003
003
003
003
003

5SY8 504-8
5SY8 506-8
5SY8 508-8
5SY8 510-8
5SY8 513-8
5SY8 516-8
5SY8 520-8
5SY8 525-8
5SY8 532-8

004
004
004
004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1
1
1
1

40
50
63

5SY8 540-7
5SY8 550-7
5SY8 563-7

003
003
003

5SY8 540-8
5SY8 550-8
5SY8 563-8

004
004
004

0.330
0.330
0.330

1
1
1

5SY8 214-7
5SY8 205-7
5SY8 201-7

003
003
003

5SY8 214-8
5SY8 205-8
5SY8 201-8

004
004
004

0.330
0.330
0.330

1
1
1

5SY8 215-7
5SY8 202-7
5SY8 203-7
5SY8 204-7
5SY8 206-7
5SY8 208-7

003
003
003
003
003
003

5SY8 215-8
5SY8 202-8
5SY8 203-8
5SY8 204-8
5SY8 206-8
5SY8 208-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

10
13
16

5SY8 210-7
5SY8 213-7
5SY8 216-7

003
003
003

5SY8 210-8
5SY8 213-8
5SY8 216-8

004
004
004

0.330
0.330
0.330

1
1
1

20
25
32
40
50
63

5SY8 220-7
5SY8 225-7
5SY8 232-7
5SY8 240-7
5SY8 250-7
5SY8 263-7

003
003
003
003
003
003

5SY8 220-8
5SY8 225-8
5SY8 232-8
5SY8 240-8
5SY8 250-8
5SY8 263-8

004
004
004
004
004
004

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

1.6
2
3
4
6
8

2 N

0.3
0.5
1
1.6
2
3

6
7
8
9
10
11

2-pole
1 3

2 4

0.3
0.5
1

1.6
2
3
4
6
8

12
13
14
15

For additional components, see page 3/23; for accessories,


see page 3/28.
1)

Only applies to 5SY8 132-7:


Also suitable for 21-kW active power at three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of miniature circuit-breakers of characteristic C and In = 40 A is recommended for
continuous load applications.

* You can order this quantity or a multiple thereof.

3
4
5

1-pole + N
1 N

1
2

16
Siemens ET B1 2007

3/19

17

Miniature Circuit-Breakers
High-Capacity Product Range
5SY8, 25 kA
In

MW

Characteristic C
Order No.

PG
Preis

Characteristic D
Order No.

1 Stck

PG
Preis
1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

3-pole
0.3
0.5
1
1.6
2
3

5SY8 314-7
5SY8 305-7
5SY8 301-7
5SY8 315-7
5SY8 302-7
5SY8 303-7

003
003
003
003
003
003

5SY8 314-8
5SY8 305-8
5SY8 301-8
5SY8 315-8
5SY8 302-8
5SY8 303-8

004
004
004
004
004
004

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1
1
1
1

4
6
8

5SY8 304-7
5SY8 306-7
5SY8 308-7

003
003
003

5SY8 304-8
5SY8 306-8
5SY8 308-8

004
004
004

0.495
0.495
0.495

1
1
1

10
13
16
20
25
321)

5SY8 310-7
5SY8 313-7
5SY8 316-7
5SY8 320-7
5SY8 325-7
5SY8 332-7

003
003
003
003
003
003

5SY8 310-8
5SY8 313-8
5SY8 316-8
5SY8 320-8
5SY8 325-8
5SY8 332-8

004
004
004
004
004
004

0.495
0.495
0.495
0.495
0.495
0.495

1
1
1
1
1
1

40
50
63

5SY8 340-7
5SY8 350-7
5SY8 363-7

003
003
003

5SY8 340-8
5SY8 350-8
5SY8 363-8

004
004
004

0.495
0.495
0.495

1
1
1

5SY8 614-7
5SY8 605-7
5SY8 601-7

003
003
003

5SY8 614-8
5SY8 605-8
5SY8 601-8

004
004
004

0.660
0.660
0.660

1
1
1

1.6
2
3
4
6
8
10
13
16

5SY8 615-7
5SY8 602-7
5SY8 603-7
5SY8 604-7
5SY8 606-7
5SY8 608-7
5SY8 610-7
5SY8 613-7
5SY8 616-7

003
003
003
003
003
003
003
003
003

5SY8 615-8
5SY8 602-8
5SY8 603-8
5SY8 604-8
5SY8 606-8
5SY8 608-8
5SY8 610-8
5SY8 613-8
5SY8 616-8

004
004
004
004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1
1
1
1

20
25
32
40
50
63

5SY8 620-7
5SY8 625-7
5SY8 632-7
5SY8 640-7
5SY8 650-7
5SY8 663-7

003
003
003
003
003
003

5SY8 620-8
5SY8 625-8
5SY8 632-8
5SY8 640-8
5SY8 650-8
5SY8 663-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

5SY8 414-7
5SY8 405-7
5SY8 401-7
5SY8 415-7
5SY8 402-7
5SY8 403-7

003
003
003
003
003
003

5SY8 414-8
5SY8 405-8
5SY8 401-8
5SY8 415-8
5SY8 402-8
5SY8 403-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

4
6
8

5SY8 404-7
5SY8 406-7
5SY8 408-7

003
003
003

5SY8 404-8
5SY8 406-8
5SY8 408-8

004
004
004

0.660
0.660
0.660

1
1
1

10
13
16
20
25
32

5SY8 410-7
5SY8 413-7
5SY8 416-7
5SY8 420-7
5SY8 425-7
5SY8 432-7

003
003
003
003
003
003

5SY8 410-8
5SY8 413-8
5SY8 416-8
5SY8 420-8
5SY8 425-8
5SY8 432-8

004
004
004
004
004
004

0.660
0.660
0.660
0.660
0.660
0.660

1
1
1
1
1
1

40
50
63

5SY8 440-7
5SY8 450-7
5SY8 463-7

003
003
003

5SY8 440-8
5SY8 450-8
5SY8 463-8

004
004
004

0.660
0.660
0.660

1
1
1

1 3 5

2 4 6

3-pole + N
0.3
0.5
1

1 3 5 N

2 4 6 N

4-pole
0.3
0.5
1
1.6
2
3

1 3 5 7

2 4 6 8

For additional components, see page 3/23; for accessories,


see page 3/28.
1)

Only applies to 5SY8 332-7:


Also suitable for 21-kW active power at three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). The use of miniature circuit-breakers of characteristic C and In = 40 A is recommended for
continuous load applications.

3/20

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers

10 000
3

UC Product Range
5SY5, 10 kA

Application
Un: 230/400 V, 50 to 60 Hz, 220 V DC per pole, can be used in
systems up to 250/440 V AC
- 220 V DC: 1-pole
- 440 V DC: 2-pole

Standards: IEC/EN 60898, DIN VDE 0641 Part 11


Additional components can be retrofitted

Selection and ordering data


In

MW

PG

Characteristic B
Order No.

Preis

Order No.

1 Stck

Preis

PG

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

Characteristic C

1
2
3
4

1-pole
0.3
0.5
1
1.6
2
3
1

2
+

5SY5 102-6

002

5SY5 114-7
5SY5 105-7
5SY5 101-7
5SY5 115-7
5SY5 102-7
5SY5 103-7

003
003
003
003
003
003

0.165
0.165
0.147
0.165
0.165
0.165

1
1
1
1
1
1

5
6
7

4
6
8

5SY5 104-6
5SY5 106-6

002
002

5SY5 104-7
5SY5 106-7
5SY5 108-7

003
003
003

0.165
0.165
0.165

1
1
1

10
13
16
20
25
321)

5SY5 110-6
5SY5 113-6
5SY5 116-6
5SY5 120-6
5SY5 125-6
5SY5 132-6

002
002
002
002
002
002

5SY5 110-7
5SY5 113-7
5SY5 116-7
5SY5 120-7
5SY5 125-7
5SY5 132-7

003
003
003
003
003
003

0.165
0.165
0.165
0.165
0.165
0.165

1
1
1
1
1
1

40
50
63

5SY5 140-6
5SY5 150-6
5SY5 163-6

002
002
002

5SY5 140-7
5SY5 150-7
5SY5 163-7

003
003
003

0.165
0.165
0.165

1
1
1

5SY5 214-7
5SY5 205-7
5SY5 201-7

003
003
003

0.330
0.330
0.330

1
1
1

1.6
2
3
4
6
8
10
13
16

5SY5 206-6

5SY5 210-6
5SY5 213-6
5SY5 216-6

002
002
002
002

5SY5 215-7
5SY5 202-7
5SY5 203-7
5SY5 204-7
5SY5 206-7
5SY5 208-7
5SY5 210-7
5SY5 213-7
5SY5 216-7

003
003
003
003
003
003
003
003
003

0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1/6
1
1
1
1

20
25
32
40
50
63

5SY5 220-6
5SY5 225-6
5SY5 232-6
5SY5 240-6
5SY5 250-6
5SY5 263-6

002
002
002
002
002
002

5SY5 220-7
5SY5 225-7
5SY5 232-7
5SY5 240-7
5SY5 250-7
5SY5 263-7

003
003
003
003
003
003

0.330
0.330
0.330
0.330
0.330
0.330

1
1
1
1
1
1

2-pole
1

0.3
0.5
1

10
11
12

The terminal section indicates the DC polarity value which it is


essential to observe when connecting.
For additional components, see page 3/23; for accessories,
see page 3/28.
1)

Also suitable for 21-kW active power with three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). For continuous
load applications, we recommend using 5SY. ...-6/-7 with In = 40 A.

13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/21

17

Miniature Circuit-Breakers

10 000

High-Current Product Range


5SP4, 10 kA

Application
Un: 230/400 V, 50 to 60 Hz, can be used in systems up to
250/440 V AC, 60 V DC per pole
Standards: IEC/EN 60898, EN 60204-1, DIN VDE 0641 Part 11
Additional components can be retrofitted individually
Main switch characteristics according to EN 60204-1

Can be snapped onto standard mounting rail acc. to EN 60715


Can be screwed onto bases
As main and miniature circuit-breakers in non-residential and
industrial buildings

Selection and ordering data


In

MW Characteristic B
Order No. Preis

PG

Characteristic C
Order No. Preis

1 Stck

PG

Characteristic D
Order No. Preis

1 Stck

PG

1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

1-pole
1

80
100
125

1.5 5SP4 180-6


5SP4 191-6
5SP4 192-6

002
002
002

5SP4 180-7
5SP4 191-7
5SP4 192-7

003
003
003

5SP4 180-8
5SP4 191-8
--

004
004

0.258
0.258
0.258

1
1
1

80
100
125

5SP4 280-6
5SP4 291-6
5SP4 292-6

002
002
002

5SP4 280-7
5SP4 291-7
5SP4 292-7

003
003
003

5SP4 280-8
5SP4 291-8
--

004
004

0.516
0.516
0.516

1
1
1

80
100
125

4.5 5SP4 380-6


5SP4 391-6
5SP4 392-6

002
002
002

5SP4 380-7
5SP4 391-7
5SP4 392-7

003
003
003

5SP4 380-8
5SP4 391-8
--

004
004

0.762
0.762
0.762

1
1
1

80
100
125

002
002
002

5SP4 480-7
5SP4 491-7
5SP4 492-7

003
003
003

5SP4 480-8
5SP4 491-8
--

004
004

1.032
1.032
1.032

1
1
1

2-pole
1 3

2 4

3-pole
1 3 5

2 4 6

4-pole
1 3 5 7

5SP4 480-6
5SP4 491-6
5SP4 492-6

2 4 6 8

For additional components, see page 3/23; for accessories,


see page 3/28.

3/22

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers

-25

Additional Components

(Type A)

RC units for 5SY.

Benefits

Product standards: IEC/EN 61009-1 (VDE 0664 Part 20);


IEC/EN 61009-2-1 (VDE 0664 Part 21); IEC/EN 61543 (VDE 0664
Part 30)
Rated voltage for 2, 3 and 4-pole version: 230 to 400 V AC; 50 to
60 Hz; applicable in systems up to: 250/440 V AC
Can be combined with miniature circuit-breakers of characteristic
A, B, C and D
Definition of surge current withstand capability with current waveform 8/20 s according to DIN VDE 0432, Part 2
S-Type: can be used as upstream group switch for selective
tripping contrary to a downstream standard RCCB or RC unit. Very
high surge current withstand capability: > 5 kA
K-type: super resistant: Short-time delayed tripping in the case
of transient leakage currents. High surge current withstand capability: > 3 kA.

High application flexibility


Customers can combine the device characteristics of RC units and
miniature circuit-breakers
Used together with miniature circuit-breakers achieves a
combined personnel and line protection.

Application
Personnel and fire protection
- In 30 mA: additional protection in the case of direct contact
- In 300 mA: preventative fire protection in the case of ground
fault currents

Selection and ordering data


Rated
Rated
residual current
current
I n
mA

MW Version

Order No.

In
A

Instantaneous tripping, surge current withstand capability > 1 kA

Preis

PG

1 Stck

Weight
1 unit
approx.

PS*
P. unit

kg

Unit(s)

1)

230 ... 400 V AC; 50 ... 60 Hz; 2-pole


1 3 (N )

2 4 (N )

I2 _ 0 7 8 2 0 a

2 /1

4 /3

6
7

0.3 ... 16 2

5SM2 121-6

007

0.180

0.3 ... 40 2

5SM2 322-6
5SM2 622-6

007
007

0.170
0.170

1
1

30
100
300
500

0.3 ... 63

5SM2 325-6
5SM2 425-6
5SM2 625-6
5SM2 725-6

007
007
007
007

0.170
0.170
0.170
0.170

1
1
1
1

30
300

0.3 ... 40 3

5SM2 332-6
5SM2 632-6

007
007

0.260
0.260

1
1

30
100
300
500

0.3 ... 63

5SM2 335-6
5SM2 435-6
5SM2 635-6
5SM2 735-6

007
007
007
007

0.260
0.260
0.260
0.260

1
1
1
1

30
300

0.3 ... 40 3

5SM2 342-6
5SM2 642-6

007
007

0.290
0.290

1
1

30
100
300
500

0.3 ... 63

5SM2 345-6
5SM2 445-6
5SM2 645-6
5SM2 745-6

007
007
007
007

0.290
0.290
0.290
0.290

1
1
1
1

2 4 6
2 /1

10

230 ... 400 V AC; 50 ... 60 Hz; 3-pole

I2 _ 0 8 4 1 1 a

3
4

30
300

4 /3 (N )

1 3 5 (N )

1
2

6 /5

10

230 ... 400 V AC; 50 ... 60 Hz; 4-pole


1 3 5 7 (N )

2 4 6 8 (N )

I2 _ 0 7 8 1 9 a

2 /1
4 /3

6 /5
8 /7 (N )

11
12

short-time delayed; super resistant; surge current withstand capability > 3 kA1)
0.3 ... 40 3
0.3 ... 63

5SM2 342-6KK01
5SM2 345-6KK01

007
007

0.290
0.290

1
1

300
300

0.3 ... 40 2
0.3 ... 63

5SM2 622-8
5SM2 625-8

007
007

0.170
0.170

1
1

300
500
1 000

0.3 ... 63 3

5SM2 635-8
5SM2 735-8
5SM2 835-8

007
007
007

0.260
0.400
0.260

1
1
1

300
500
1 000

0.3 ... 63 3

5SM2 645-8
5SM2 745-8
5SM2 845-8

007
007
007

0.290
0.400
0.290

1
1
1

30

230 ... 400 V AC; 50 ... 60 Hz; 4-pole

selective; surge current withstand capability > 5 kA1)

13

230 ... 400 V AC; 50 ... 60 Hz; 2-pole

230 ... 400 V AC; 50 ... 60 Hz; 3-pole

230 ... 400 V AC; 50 ... 60 Hz; 4-pole

1)

15
16

Not for 5SY6 ...-.KV and 5SY5.

* You can order this quantity or a multiple thereof.

14

Siemens ET B1 2007

3/23

17

Miniature Circuit-Breakers

-25

Additional Components

(Type A)

RC units for 5SP4

Benefits

Product standards: IEC/EN 61009-1 (VDE 0664, Part 20);


IEC/EN 61009-2-1 (VDE 0664, Part 21); IEC/EN 61543 (VDE 0664,
Part 30)
Rated voltage
- 2-pole: 125 to 230 V AC; 50 to 60 Hz; can be used in systems
up to 125/240 V AC
- 4-pole: 230 to 400 V AC; 50 to 60 Hz; can be used in systems
up to 230/400 V AC
Can be combined with miniature circuit-breakers, characteristic B
and C
Definition of surge current withstand capability with current
waveform 8/20 s according to DIN VDE 0432, Part 2
S-Type: Can be used as upstream group switch for selective
tripping against downstream standard RCCBs. Very high surge
current withstand capability: > 5 kA.

High application flexibility


Customers can combine the device characteristics of RC units and
miniature circuit-breakers
Used together with miniature circuit-breakers achieves a
combined personnel and line protection
External remote tripping over Y1/Y2 terminals

Application
Personnel and fire protection
- In 30 mA: additional protection in the case of direct contact
- In 300 mA: preventative fire protection in the case of ground
fault currents

Selection and ordering data


Rated
Rated
residual current
current
I n
In
mA

MW Version

Order No.

Preis

PG

1 Stck

Weight
1 unit
approx.

PS*
P. unit

kg

Unit(s)

Instantaneous tripping, surge current withstand capability > 1 kA


230 ... 400 V AC; 50 ... 60 Hz; 2-pole
Y1 Y2

1 3 (N)

I2_06662c

30
300

80 ... 100 3.5

5SM2 327-6
5SM2 627-6

007
007

0.410
0.410

1
1

30
300

80 ... 100 5

5SM2 347-6
5SM2 647-6

007
007

0.630
0.630

1
1

300

80 ... 100

5SM2 627-8

007

0.410

300
1 000

80 ... 100

5SM2 647-8
5SM2 847-8

007
007

0.630
0.630

1
1

2 4 (N)
2/1

4/3(N)

230 ... 400 V AC; 50 ... 60 Hz; 4-pole


Y 1

Y 2

1 3 5 7 (N )

I2 _ 0 6 6 6 1 c

2 4 6 8 (N )
2 /1
4 /3

6 /5
8 /7 (N )

selective; surge current withstand capability > 5 kA


230 ... 400 V AC; 50 ... 60 Hz; 2-pole
230 ... 400 V AC; 50 ... 60 Hz; 4-pole

3/24

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers
Additional Components
Auxiliary switches/fault signal contacts
for 5SY. and 5SP4

Benefits
Can be retrofitted individually (for mounting concept,
see page 3/26)
Mounting with factory-fitted clips
Short-circuit protection by means of miniature circuit-breakers
of B or C characteristic and In = 6 A or gL 6 A fuses.
Wide range of applications due to additional version for controlling
programmable control system (PLCs) according to EN 61131-2
Can be connected to instabus KNX EIB and AS-Interface bus over
binary inputs.

Application
Indication of the miniature circuit-breakers switching state:
AS: ON/OFF
FC: tripped
Auxiliary switches (AS)
5ST3 013
5ST3 014
5ST3 015
Area of application 1 mA/5 V DC to 50 mA/30 V DC.

Auxiliary switches (AS) and fault signal contacts (FC)


5ST3 0.0
5ST3 0.1
5ST3 0.2
Min. contact load:
50 mA, 24 V
Max. contact load:
NO contact:
2 A, 400 V AC, AC-14
6 A, 230 V AC, AC-14
1 A, DC 220 V, DC-13
1 A, 110 V DC, DC-13
3 A, 60 V DC, DC-13
6 A, 24 V DC, DC-13
NC contact:
2 A, 400 V AC, AC-13
6 A, 230 V AC, AC-13
1 A, 220 V DC, DC-13
1 A, 110 V DC, DC-13
3 A, 60 V DC, DC-13
6 A, 24 V DC, DC-13

3
4
5

Selection and ordering data


Version

MW

Order No.

Preis

PG

1 Stck
Auxiliary circuit switches (AS) for 5SY miniature circuit-breakers1)
1 NO + 1 NC 0.5
13
21
for small output

1
2

Weight
1 unit
approx.

PS*
P. unit

kg

Unit(s)

6
7
8

5ST3 010
5ST3 013

027
027

0.050
0.050

1
1

2 NO

5ST3 011
5ST3 014

027
027

0.050
0.050

1
1

2 NC

5ST3 012
5ST3 015

027
027

0.050
0.050

1
1

10

1 NO + 1 NC 0.5

5ST3 020

027

0.050

11

2 NO

5ST3 021

027

0.050

2 NC

5ST3 022

027

0.050

22
14
13
23

for small output

24
14
11
21

for small output

22
12

1)

Fault signal contacts (FC) for 5SY miniature circuit-breakers


13
21
22
14
13
23

12

24
14
11
21

13

22
12
1)

Not for 5SY6 ...-KV.

14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/25

17

Miniature Circuit-Breakers
Additional Components
Remote-controlled mechanisms for 5SY. and 5SP4

Benefits
Can be retrofitted individually (for mounting concept, see below)
Mounting with factory-fitted brackets
Can be mechanically latched and locked
Further additional components can be attached
Function switch on the front
Can be connected over binary inputs and outputs to
instabus KNX EIB and AS-Interface
UN = 230 V, 50 to 60 Hz

Mounting concept
Using this mounting concept, all additional 5ST3 components can
be combined with miniature circuit-breaker of the 5SY1) and 5SP4
series:

5ST3

AS

5SM2

5SY

RC

RC unit

ST

MCB

or

UR

AS

AS
FC

FC
AS

AS
FC

FC
AS

AS
FC

FC
AS

or

or

FC

AS
FC

or
AS
FC

AS
FC

AS
FC

input

output

instabus KNX EIB

I2_07795d

1)

AS
FC

or
FC

AS

or
AS
FC

FC

or

1)

5SM2

or

or

5SP4

5SY5: without RC unit; not for 5SY6 ...-KV

Functions
ON/OFF remote control switch of miniature circuit-breaker and ON
remote control switch of RC unit
Remote ON switching possible following acknowledgment of fault
occurrence

Manual switching on-site possible


Remote display of switching status of remote-controlled mechanism and miniature circuit-breakers.

Selection and ordering data


Rated voltage MW
Un

Order No.

V AC
Remote controlled mechanism (RC) for
5SY and 5SP4 miniature circuit-breakers1)

Preis

PG

1 Stck

230

3.5

5ST3 050

027

Weight
1 unit
approx.

PS*
P. unit

kg

Unit(s)

0.395

M
P N 1 2 3
I2_10741

ON OFF

For detailed application information, see operator guide.

3/26

Siemens ET B1 2007

1)

Not for 5SY6 ...-.KV.

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers
Additional Components
Shunt trips/undervoltage releases
for 5SY. and 5SP4

Benefits

Application

Shunt trips
Can be retrofitted individually (for mounting concept,
see page 3/26)
Response limits according to EN 60947-1, 7.2.1.4
Can be connected to instabus KNX EIB and AS-Interface bus over
binary outputs.
Undervoltage releases
Can be retrofitted individually (for mounting concept, see
page 3/26)
Response limits according to EN 60947-1, 7.2.1.3
Can be connected to instabus KNX EIB and AS-Interface bus over
binary outputs.

Shunt trips
Remote tripping of miniature circuit-breakers
For voltages:
110 to 415 V AC, 110 V DC
24 to 48 V AC/DC
Undervoltage releases
Can be used as remote trip in an EMERGENCY-OFF loop
Ensures disconnection of the control circuit according to EN 60204
In cases of interrupted or insufficient voltage, the undervoltage
release trips the miniature circuit-breaker or prevents it from
switching on
For voltages:
230 V AC
110 V DC
24 V DC.

Selection and ordering data


Rated voltage
Un

MW

Order No.

Preis

PG

1 Stck

Weight
1 unit
approx.

PS*
P. unit

kg

Unit(s)

Shunt trips (ST) for miniature circuit-breakers


5SY4, 5SY6, 5SY7, 5SY8, 5SY5, 5SP41)
C2

110 ... 415 V AC

5ST3 030

027

0.098

24 ... 48 V AC/DC

5ST3 031

027

0.098

Undervoltage releases (UR) for miniature circuit-breakers


5SY4, 5SY6, 5SY7, 5SY8, 5SY5, 5SP41)
D1

13 23

D2

14 24

D1
v

D2
1)

3
4
5
6
7
8

C1

U<

1
2

230 V AC
110 V DC
24 V DC

5ST3 040
5ST3 041
5ST3 042

027
027
027

0.115
0.115
0.115

1
1
1

230 V AC
110 V DC
24 V DC

5ST3 043
5ST3 044
5ST3 045

027
027
027

0.115
0.115
0.115

1
1
1

9
10

Not for 5SY6 ...-.KV.

11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/27

17

Miniature Circuit-Breakers
Accessories
For 5J6, 5SY. and 5SP4

Selection and ordering data


MW

Order No.

Preis

PG

1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

Accessories for miniature circuit-breakers 5SJ6, 5SY6, 5SY4, 5SY7, 5SY8, 5SY5, 5SP4
Terminal covers
applicable for all types of poles;
as an additional cover for screw openings;
prevents removal of the device from the
standard mounting rail; sealable

5ST3 800

027

0.001

5/10

5ST3 801

027

0.008

5ST3 802

027

0.027

5ST3 803

027

0.035

1 set

contour for modular devices with a mounting depth of 70 mm;


can be snapped onto either side of the busbar, so that two spacers
allow for convenient cable routing
0.5

5TG8 240

027

0.010

Snap-on terminals
for 35 mm standard mounting rail, for conductors up to 16 mm2 solid
or conductors up to 10 mm2 stranded
Width: 0.5 MW

5ST2 112

027

0.008

1/50

5ST2 201

027

0.012

1/20

5ST2 173

027

1 set
0.038

1 set

Handle locking devices


applicable for all types of poles;
sealable against unintended on and off-switching;
padlock with a shackle of max. 3 mm

Padlocks
for 5ST3 801 handle locking device

1 set

Locking devices
consisting of
5ST3 801 handle locking device and
5ST3 802 padlock
Spacers

Fixing parts
4 MW (plastic)

Inscription labels (white)


15 mm x 9 mm, 3 frames 44 labels,
can be mounted on lower casing collar
Self-adhesive
Inscription options

Labeling systems
to download the labeling program free of charge,
please visit our Web site at:
www.siemens.com/beta
Recommended labels; ELAT-3-747
can be ordered at:
Brady GmbH
Otto-Hahn-Str. 5-7
D-63222 Langen
Tel: +49 (0)6103/7598-660

For busbars for miniature circuit-breakers, see chapter "Busbars for


modular installation devices".

3/28

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers
Power Supply Company Product Range
5SP3, 25 kA
mounting depth 92 mm

Application
Un: 230/400 V, 50-60 Hz, can be used in systems up to:
50/440 V AC
Standards: DIN VDE 0645
As main miniature circuit-breakers at the meter panel
As group miniature circuit-breakers in distribution board applications
Characteristic E:
Adapted to the special application requirements for cascade
circuits between melting fuses and miniature circuit-breakers.

At a glance
Protection of insulated cables against overcurrents
Disconnection of loads
Assurance of network-compatible power consumption
Can be switched on again after failures even by non-specialists
Complies with defined selectivity requirements for upstream and
downstream overcurrent protection devices
Can be screwed onto mounting plates
Can be clipped onto busbars using adapters
Can be snapped onto standard mounting rails using mounting
plates according to EN 60715

Selection and ordering data


In

MW

Preis

PG

Weight
1 unit
approx.

PS*
P. unit

1 Stck

kg

Unit(s)

Characteristic E
Order No.

A
Selective main miniature circuit-breakers
16
20

5SP3 716
5SP3 720

005
005

0.550
0.550

1/3
1/3

25
32
35
40
50
63

5SP3 725
5SP3 732
5SP3 735
5SP3 740
5SP3 750
5SP3 763

005
005
005
005
005
005

0.550
0.550
0.550
0.550
0.550
0.550

1/3
1/3
1/3
1/3
1/3
1/3

80
100

5SP3 780
5SP3 791

005
005

0.550
0.550

1/3
1/3

1 set

Selective main miniature circuit-breakers


3 x 1-pole, premounted to 5ST1 324 busbar adapter; can be
clipped onto busbars (spacing: 40 mm); including three 5ST1 323
transparent operating protective covers

1
2
3
4
5
6
7
8

5SP3 716-1
5SP3 720-1
5SP3 725-1
5SP3 732-1
5SP3 735-1

005
005
005
005
005

1.700
1.700
1.700
1.700
1.700

1 set
1 set
1 set
1 set
1 set

40
50
63

5SP3 740-1
5SP3 750-1
5SP3 763-1

005
005
005

1.700
1.700
1.700

1 set
1 set
1 set

80
100

5SP3 780-1
5SP3 791-1

005
005

1.700
1.700

1 set
1 set

10

16
20
25
32
35

11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/29

17

Miniature Circuit-Breakers
Power Supply Company Product Range
Accessories
for 5SP3, 25 kA

Selection and ordering data


Order No.

Preis

PG

1 Stck

Weight
1 unit
approx.
kg

PS*
P. unit
Unit(s)

Accessories for main miniature circuit-breakers (SHU)


Busbar adapters
suitable for a busbar spacing of 40 mm;
can be equipped with 3 main miniature circuit-breakers;
for clip-on assembly

5ST1 328

005

0.234

5ST1 318

005

0.001

3/10

5ST1 323

005

0.012

1/3

5ST1 316

005

0.001

Breaker blocking covers


to prevent manual off-switching

Transparent operating protective covers


multiple locking options against accidental and
deliberate operation
Padlocks
Phillips screwdrivers
Special wrenches (Antilux)
These can be installed by the operator or the power supply
company
Terminal covers
2 units required per device;
for covering terminals within the overall dimensions
according to DIN 43880

3/30

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Miniature Circuit-Breakers
Special Range

N
Application

Circuit-breaker terminals
for auxiliary circuits

Benefits

Circuit-breaker terminals are used for short-circuit protection


or for protection against overloading and short-circuiting in
auxiliary and control circuits after control transformers.
Standards: DIN VDE 0660 Part 101 and IEC/EN 60947-2,
insofar as they relate to circuit-breaker terminals. Finger-safe
according to EN 50274.

Space-saving construction in terminal block design


Clear arrangement on 35 mm standard mounting rail (TH 35
according to EN 60715)
Unambiguous indication of switching position or "released"
status
No fuses
Switch/isolating point function
Signals through built-in auxiliary switches
Floating through-type connection parallel to the switching
contacts
Double connection option at all terminal points
Inscription with terminal block labeling accessories

1
2
3
4
5

Selection and ordering data


Version

Order No.

IN

Preis

PG

1 Stck

Weight PS*
1 unit
P. unit
approx.
kg

Unit(s)

Circuit-breaker terminals
Terminal size 1.5 mm
with short-circuit release
1
2
4
6
10

8WA1 011-1SF24
8WA1 011-1SF25
8WA1 011-1SF26
8WA1 011-1SF27
8WA1 011-1SF28

041
041
041
041
041

0.053
0.052
0.053
0.053
0.050

10
10
10
10
10

1
2
4
6
10

8WA1 011-2SF24
8WA1 011-2SF25
8WA1 011-2SF26
8WA1 011-2SF27
8WA1 011-2SF28

041
041
041
041
041

0.052
0.051
0.051
0.051
0.053

10
10
10
10
10

1
2
4
6
10

8WA1 011-6SF24
8WA1 011-6SF25
8WA1 011-6SF26
8WA1 011-6SF27
8WA1 011-6SF28

041
041
041
041
041

0.096
0.093
0.092
0.093
0.090

5
5
5
5
5

1
2
4
6
10

8WA1 011-4SF24
8WA1 011-4SF25
8WA1 011-4SF26
8WA1 011-4SF27
8WA1 011-4SF28

041
041
041
041
041

0.089
0.092
0.091
0.105
0.088

5
5
5
5
5

0.5
1
2
4
6
10

8WA1 011-8SF23
8WA1 011-8SF24
8WA1 011-8SF25
8WA1 011-8SF26
8WA1 011-8SF27
8WA1 011-8SF28

041
041
041
041
041
041

with overload and short-circuit release


8WA1 011-1SF24

Terminal size 2.5 mm


with short-circuit release, auxiliary switch
with 1 NO contact and 1 NC contact

with overload and short-circuit release,


auxiliary switch and through-type connection

with overload and short-circuit release, auxiliary


switch with 1 NO contact and 1 NC contact
0.093
0.092
0.097
0.092
0.090
0.090

5
5
5
5
5
5

6
7
8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

3/31

17

Miniature Circuit-Breakers
Special Range
Circuit-breaker terminals
for auxiliary circuits

Version

Order No.

IN

Preis

PG

1 Stck

Weight PS*
1 unit
P. unit
approx.
kg

Unit(s)

Accessories

8WA1 822-7VD01

8WA1 822-7VD02

8WA1 822-7VD03

8WA1 822-7VD04

3/32

Feeder terminals
Rated uninterrupted current 76 A
Connection up to 16 mm
Link rails, single-pole
Rated uninterrupted current 65 A

8WA1 822-7VD00

041

0.012

10

5 connections
Length 104 mm
For terminals: 8WA1 011-4SF2., 8WA1 011-6SF2.,
8WA1 011-8SF2.

8WA1 822-7VD02

041

0.015

20

9 connections
Length 104 mm
For terminals: 8WA1 011-1SF2., 8WA1 011-2SF2.
10 connections
Length 206 mm
For terminals: 8WA1 011-4SF2., 8WA1 011-6SF2.
8WA1 011-8SF2.

8WA1 822-7VD07

041

0.017

20

8WA1 822-7VD01

041

0.031

20

18 connections
Length 206 mm
For terminals: 8WA1 011-1SF2., 8WA1 011-2SF2.

8WA1 822-7VD06

041

0.036

20

8WA1 822-7VD04

041

0.031

10

8WA1 822-7VD03

041

0.061

10

Link rails, two-pole


Rated uninterrupted current 120 A
for terminal 8WA1 011-4SF2
5 connections/pole
Length 104 mm
9 connections/pole
Length 206 mm

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current
Protective Devices

General Data

4/2

Product overview

Residual Current
Operated Circuit-Breakers
(RCCBs)

4/3
4/4
4/6
4/7
4/7
4/8

5SM3, type A, product overview


5SM3, type A, 16 ... 125 A
5SM3, type A, SIGRES, for severe
environmental conditions , 25 ... 80 A
5SM3, type A, 500 V, 25 ... 63 A
5SM3, type A, 50 ... 400 Hz, 25 ... 40 A
5SM3, type A, 24 V, 16 A

SIQUENCE RCCBs,
UC sensitive

4/9

5SM3, type B, 25 ... 80 A

Additional Components/
Accessories for RCCBs

4/10
4/11
4/12
4/13

Remote controlled mechanisms for 5SM3


Auxiliary switches for 5SM3
Accessories for 5SM3
5SM1 930 leakage current
measuring devices

SIQUENCE RCCBs with


Integral Overcurrent
Protection (RCBOs),
UC Sensitive

4/14

5SU1, type B, 100 ... 125 A

RCCBs with Integral


Overcurrent Protection
(RCBOs)

4/15

5SU1, type A, 6 ... 40 A

Additional Components/
Accessories for RCBOs

4/17
4/18

Remote controlled mechanisms for 5SU1


Auxiliary switches/fault signal contacts
for 5SU1
Shunt trips/undervoltage releases for 5SU1
Accessories for 5SU1

4/19
4/20
RC Units for Miniature
Circuit-Breakers

4/21
4/22
4/23

5SM2, product overview


5SM2, 0.3 ... 63 A,
for 5SY4, 5SY6, 5SY7, 5SY8
5SM2, 80 ... 100 A, for 5SP4

RCCB Socket Outlets


(SRCDs)

4/24

5SM1 and 5SZ9 RCCB


protective socket outlets

Accessories

4/26

For all product ranges

4/1

Residual Current Protective Devices


General Data
Product overview

Overview
Residual current operated circuit-breakers (RCCBs)
5SM3
Type A
In = 16 ... 125 A
In =10 mA ... 1 A
2-pole (1-pole + N) and 4-pole (3-pole + N)
N-connection, right and left
Versions and
SIGRES for severe environmental conditions
Version for 500 V
Version 50 ... 400 Hz

SIQUENCE RCCBs, UC sensitive


5SM3
Type B
In = 25 ... 80 A
In = 30, 300 mA
4-pole (3+ N)
Versions and
Leakage current measurement device

SIQUENCE RCBOs, UC sensitive


5SU1
Combined person and line protection
Type B
In = 100 ... 125 A
In = 30, 300 mA
MCB characteristic C, D
Rated short-circuit capacity 10 kA
4-pole
Versions and

RCCBs with integral overcurrent protection (RCBOs)


5SU1
Combined personnel and line protection
Type A
In = 6 ... 40 A
In = 10 ... 300 mA
Type B
Circuit-breaker characteristics B and C
Rated short-circuit capacity 6 kA and 10 kA
2 (1 + N) and 2-pole

RC units for miniature circuit-breakers


5SM2
For mounting on miniature circuit-breakers
Combined person and line protection
Type A
In = 0.3 ... 100 A
In =10 mA ... 1 A
2, 3 and 4-pole
Versions and

RCCB socket outlets (SRCDs)


5SM1 and 5SZ9
Can be retrofitted in existing installations
Increased protection level
Type AC and type A
In = 16 A
In= 10 and 30 mA

Accessories
Locking devices
Covers
Wall enclosures

Definitions
1 MW = 18 mm modular width

4/2

Siemens ET B1 2007

Residual Current Protective Devices

(Type A)

Residual Current Operated Circuit-Breakers (RCCBs)


5SM3, type A, product overview

Overview
Number of
poles

Rated
current In

Rated residual
current In

mA

16

10, 30

25
40
63
80

30, 100, 300

MW

Mountable auxiliary N-connection


switches
Right

Left

--

3
4

Residual current operated circuit-breakers, type A1),


16 ...125 A
Instantaneous tripping,
surge current withstand capability > 1 kA

30, 100, 300

2.5

-----

100
125

30, 300

---

---

25

30, 300
500
30, 300
100, 500

-
--

40

short-time delayed, super resistant,


surge current withstand capability > 3 kA

selective,

surge current withstand capability > 5 kA

63

30, 300
100, 500

--

80
125

30, 300
30, 100, 300, 500

--

25
40

30

---

63
63

30, 100
100, 300

2.5

---

40
63

100, 300
100, 1 000
300
300, 500

--
--

25
40
63
80

30

30

2.5

-----

25
40
63
80

30
30, 300

-----

63

300

--

25
40
63

30, 300

----

25
40

30

---

16

30

--

125

5
6
7
8

SIGRES residual current operated circuit-breakers,


type A1), for severe environmental conditions
Instantaneous tripping,
surge current withstand capability > 1 kA

selective,
surge current withstand capability > 5 kA

30

9
10
11

Residual current operated circuit-breakers, type A1),


500 V
Instantaneous tripping,
surge current withstand capability > 1 kA

12

Residual current operated circuit-breakers, type A1),


50 ... 400 Hz
Instantaneous tripping,
surge current withstand capability > 1 kA

Residual current operated circuit-breakers, type A1),


24 ... 125 V
Instantaneous tripping,
surge current withstand capability > 1 kA
1)

1
2

13

= Type A for AC and pulsating DC residual currents

14
15
16
Siemens ET B1 2007

4/3

17

Residual Current Protective Devices

-25

(Type A)

Residual Current Operated Circuit-Breakers (RCCB)


5SM3, type A, 16 ... 125 A

Benefits

Application

Terminals with wire protection can be directly busbar-mounted


with devices with terminals in the modular width, e.g. with 5SY
miniature circuit-breakers.
An auxiliary switch can be retrofitted on the right side of the
enclosure by the customer (except 5SM3 .1.-.KK)
Operating handle and test button can be locked by means of a
handle locking device (for devices up to In = 80 A)
N-connection on the left allows simply busbar-mounting with pin
busbars if the miniature circuit-breakers are fitted on the right.

Personnel and fire protection


- In 30 mA: additional protection in the case of direct contact
- In 300 mA: preventative fire protection in the case of ground
fault currents
Product standards: IEC/EN 61008-1 (VDE 0664, Part 10);
IEC/EN 61008-2-1 (VDE 0664, Part 11); IEC/EN 61543
(VDE 0664, Part 30)
Un 230/400 V; 50 to 60 Hz; used in systems up to: 240/415 V AC
Definition of surge current withstand capability with current waveform 8/20 s acc. to DIN VDE 0432, Part 2
K-type, super resistant: short-time delayed tripping in the case
of transient leakage currents. High surge current withstand capability: > 3 kA.
S-type: can be used as upstream group switch for selective
tripping contrary to a downstream standard RCCB or RC unit.
Very high surge current withstand capability: > 5 kA.

Selection and ordering data


Rated
Circuit diagram/
residual
max. permissible
short-circuit series fuse current
In
mA

Rated MW N-connection, right


current
Order No.
Price
In
A

N-connection, left
Order No.
Price

1 unit

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Instantaneous tripping, surge current withstand capability > 1 kA


125 ... 230 V AC; 50 ... 60 Hz; 2-pole
1 N

I2_05982c

2 NT

63 A

10
30

16
16
25
40

100

25
40
25
40

300

10 000

30

1 N

100
I2_05982c

2 NT

63
80
63
80

300

63
80

30

100
125

100

100
125
100
125

2.5

5SM3 111-6
5SM3 311-6
5SM3 312-6
5SM3 314-6

-----

007
007
007
007

0.230
0.230
0.230
0.230

1
1
1
1

5SM3 412-6
5SM3 414-6
5SM3 612-6
5SM3 614-6

-----

007
007
007
007

0.230
0.230
0.210
0.210

1
1
1
1

5SM3 316-6
5SM3 317-6
5SM3 416-6
5SM3 417-6

-----

007
007
007
007

0.320
0.320
0.300
0.300

1
1
1
1

5SM3 616-6
5SM3 617-6

---

007
007

0.280
0.280

1
1

5SM3 318-6KK
5SM3 315-6KK

---

007
007

0.245
0.245

1
1

5SM3 418-6KK
5SM3 415-6KK
5SM3 618-6KK
5SM3 615-6KK

-----

007
007
007
007

0.245
0.245
0.245
0.245

1
1
1
1

5SM3 342-6
5SM3 344-6
5SM3 346-6
5SM3 347-6

5SM3 342-6KL
5SM3 344-6KL
5SM3 346-6KL
5SM3 347-6KL

007
007
007
007

0.500
0.500
0.500
0.500

1
1
1
1

100 A
10 000

1 N

I2_05982c

300

2 NT

125 A
10 000

230 ... 400 V AC; 50 ... 60 Hz; 4-pole


30
25
1 3 5 N
40
63
80
I2 _ 0 5 9 7 7 d

N-connection, right

100

40
63

5SM3 444-6
5SM3 446-6

---

007
007

0.460
0.460

1
1

300

25
40
63
80
25
40
63

5SM3 642-6
5SM3 644-6
5SM3 646-6
5SM3 647-6
5SM3 742-6
5SM3 744-6
5SM3 746-6

5SM3 642-6KL
5SM3 644-6KL
5SM3 646-6KL
5SM3 647-6KL
----

007
007
007
007
007
007
007

0.440
0.440
0.440
0.440
0.440
0.440
0.440

1
1
1
1
1
1
1

100 A

N-connection, right

10 000

500
N 1 3 5

I2_10730

N 2 4 6 T

N-connection, left
N-connection, left

100 A
10 000

For additional components see page 4/10.

4/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices

-25

(Type A)

Residual Current Operated Circuit-Breakers (RCCB)


5SM3, type A, 16 ... 125 A
Rated
Circuit diagram/
max. permissible short- residual
current
circuit series fuse
In
mA

Rated MW N-connection, right


current
Order No.
Price

N-connection, left
Order No.
Price

In
A

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.500
0.480
0.480
0.480

1
1
1
1

Instantaneous tripping, surge current withstand capability


> 1 kA
230 ... 400 V AC; 50 ... 60 Hz; 4-pole
30
125
1 3 5 N
100
300
500

5SM3 345-6
5SM3 445-6
5SM3 645-6
5SM3 745-6

-----

007
007
007
007

1
2
3
4

I2 _ 0 6 2 3 2 c

125 A
10 000

short-time delayed, super resistant,


surge current withstand capability > 3 kA
230 ... 400 V AC; 50 ... 60 Hz; 4-pole
1

30
N

30
100

25
40
63

5SM3 342-6KK01
5SM3 344-6KK01
5SM3 346-6KK01
5SM3 446-6KK01

-----

007
007
007
007

0.500
0.500
0.500
0.460

1
1
1
1

5SM3 416-8
5SM3 616-8

---

007
007

0.300
0.280

1
1

I2 _ 0 5 9 7 7 d

6
7

100 A
10 000

selective; surge current withstand capability > 5 kA


125 ... 230 V AC; 50 ... 60 Hz; 2-pole
100
300

1 N

I2_05982c

63

2.5

2 NT

100 A
10 000

230 ... 400 V AC; 50 ... 60 Hz; 4-pole


100
40
1 3 5 N
63

I2 _ 0 5 9 7 7 d

5SM3 444-8
5SM3 446-8

---

007
007

0.460
0.460

1
1

300

40
63

5SM3 644-8
5SM3 646-8

-5SM3 646-8KL

007
007

0.440
0.440

1
1

1 000

63

5SM3 846-8

--

007

0.515

N-connection, right

10
11

100 A

N-connection, right

10 000

12

N 1 3 5

13

I2_10730

N 2 4 6 T

N-connection, left
100 A
10 000

N-connection, left
1

300
500
N

125

5SM3 645-8
5SM3 745-8

---

007
007

0.480
0.480

1
1

15

I2 _ 0 6 2 3 2 c

14

125 A
10 000

16

For additional components see page 4/10.

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

4/5

17

Residual Current Protective Devices

-25

(Type A)

Residual Current Operated Circuit-Breakers (RCCBs)


5SM3, type A, SIGRES,
for severe environmental conditions , 25 ... 80 A

Benefits

Application

Our patented active condensation protection significantly increases service life under harsh ambient conditions
Terminals with wire protection can be directly busbar-mounted
from underneath with devices with terminals in the respective
modular width, e.g. 5SY miniature circuit-breakers.
An auxiliary switch can be fitted to the right-hand side of the enclosure by the customer
Operating handle and test button can be locked by means of a
handle locking device.

For use in areas with high levels of pollution gas and humidity, such
as indoor swimming pools, in agriculture, construction distribution
boards or in the chemical industry
Personnel and fire protection
- In 30 mA: additional protection in the case of direct contact
- In 300 mA: preventative fire protection in the case of ground
fault currents
Product standards: IEC [EN 61008-1 (VDE 0664, Part 10);
61008-2-1 (VDE 0664, Part 11); EN 61543 (VDE 0664, Part 30)]
Un 230/400 V; 50 to 60 Hz; can be used in systems up to:
240/415 V AC
Definition of surge current withstand capability with current waveform 8/20 s according to DIN VDE 0432, Part 2
S-type: can be used as upstream group switch for selective
tripping contrary to a downstream standard RCCB or RC unit. Very
high surge current withstand capability: > 5 kA.

Function
Function of condensation protection with switched off
RCCBs through infeed from below

Selection and ordering data


Circuit diagram

Maximum
permissible
short-circuit
series fuse

Rated
Rated MW Verresidual current
sion
current
I n
mA

Order No.

In
A

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Instantaneous tripping, surge current withstand capability > 1 kA


125 ... 230 V AC; 50 ... 60 Hz; 2-pole
1 N

25
40

10 000

5SM3 312-6KK12
5SM3 314-6KK12

007
007

0.230
0.230

1
1

63
80

2.5

10 000

5SM3 316-6KK12
5SM3 317-6KK12

007
007

0.320
0.320

1
1

30

25
40
63
80

5SM3 342-6KK12
5SM3 344-6KK12
5SM3 346-6KK12
5SM3 347-6KK12

007
007
007
007

0.500
0.500
0.500
0.500

1
1
1
1

300

40
63

5SM3 644-6KK12
5SM3 646-6KK12

007
007

0.440
0.440

1
1

5SM3 646-8KK12

007

0.440

30

63 A

100 A

I2_05982c

2 NT
Incoming
direction

230 ... 400 V AC; 50 ... 60 Hz; 4-pole


1

100 A

10 000

I2 _ 0 5 9 7 7 d

Incoming
direction

, selective; surge current withstand capability > 5 kA


230 ... 400 V AC; 50 ... 60 Hz; 4-pole
300

63

For additional components see page 4/10.

4/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices

-25

(Type A)

Residual Current Operated Circuit-Breakers (RCCBs)


5SM3, type A, 500 V, 25 ... 63 A

Benefits

Application

Terminals with wire protection can be directly busbar-mounted


from underneath with devices with terminals in the respective
modular width, e.g. 5SY miniature circuit-breakers.
An auxiliary switch can be fitted to the right-hand side of the enclosure by the customer
Operating handle and test button can be locked by means of a
handle locking device

Personnel and fire protection


- In 30 mA: additional protection in the case of direct contact
- In 300 mA: preventative fire protection in the case of ground
fault currents
Product standards: IEC/EN 61008-1 (VDE 0664, Part 10);
IEC 61008-2-1 (VDE 0664, Part 11); IEC/EN 61543 (VDE 0664,
Part 30); VDE 0664 Part 101
Un 500 V; 50 to 60 Hz; can be used in systems up to: 500 V AC
Definition of surge current withstand capability with current
waveform 8/20 s according to DIN VDE 0432, Part 2

Selection and ordering data


Circuit diagram

Maximum
permissible
short-circuit
series fuse

Rated
residual
current

Rated
current

I n

In

mA

MW Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Instantaneous tripping, surge current withstand capability > 1 kA


500 V AC; 50 ... 60 Hz; 4-pole
1

30

25
40
63

300

25
40
63

63 A
10 000

I2 _ 0 5 9 7 7 d

5SM3 352-6
5SM3 354-6
5SM3 356-6

007
007
007

0.500
0.500
0.500

1
1
1

5SM3 652-6
5SM3 654-6
5SM3 656-6

007
007
007

0.440
0.440
0.440

1
1
1

1
2
3
4
5
6
7
8

For additional components see page 4/10.

-25

5SM3, type A, 50 ... 400 Hz, 25 ... 40 A

(Type A)

Benefits

Application

Terminals with wire protection can be directly busbar-mounted


from underneath with devices with terminals in the respective
modular width, e.g. 5SY miniature circuit-breakers.
An auxiliary switch can be fitted to the right-hand side of the enclosure by the customer
Operating handle and test button can be locked by means of a
handle locking device.

For use with power supply frequencies between 50 and 400 Hz


Personnel and fire protection
- In 30 mA: additional protection in the case of direct contact
Product standards: IEC/EN 61008-1 (VDE 0664, Part 10);
IEC 61008-2-1 (VDE 0664, Part 11); IEC/EN 61543 (VDE 0664,
Part 30)
Un 230/400 V; 50 to 400 Hz; can be used in systems up to:
240/415 V AC
Definition of surge current withstand capability with current
waveform 8/20 s according to DIN VDE 0432, Part 2

10
11
12

Selection and ordering data


Circuit diagram

Maximum
permissible
short-circuit
series fuse

Rated
residual
current

Rated
current

I n

In

mA

MW Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

13

kg

Unit(s)

14

0.500
0.500

1
1

Instantaneous tripping, surge current withstand capability > 1 kA


230 ... 400 V AC; 50 ... 400 Hz; 4-pole
1

30

80 A

10 000

25
40

5SM3 342-6KK03
5SM3 344-6KK03

007
007

15

I2 _ 0 5 9 7 7 d

16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

4/7

17

Residual Current Protective Devices

-25

(Type A)

Residual Current Operated Circuit-Breakers (RCCBs)


5SM3, type A, 24 V, 16 A

Benefits

Application

Terminals with wire protection can be directly busbar-mounted


with devices with terminals in the modular width, e.g. with 5SY
miniature circuit-breakers.
An auxiliary switch can be fitted to the right-hand side of the enclosure by the customer
Operating handle and test button can be locked by means of a
handle locking device.

For special applications (e.g. laboratories)


Personnel and fire protection
- In = 30 mA: additional protection in the case of direct contact
Product standards: IEC/EN 61008-1 (VDE 0664, Part 10);
IEC 61008-2-1 (VDE 0664, Part 11); IEC/EN 61543 (VDE 0664,
Part 30)
Un 24 to 125 V; 50 to 60 Hz; can be used in systems: 125 V AC
Definition of surge current withstand capability with current waveform 8/20 s according to DIN VDE 0432, Part 2

Selection and ordering data


Circuit diagram

Maximum
permissible
short-circuit
series fuse

Rated
residual
current

Rated
current

I n

In

mA

MW Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.280

Instantaneous tripping, surge current withstand capability > 1 kA


24 ... 125 V AC; 50 ... 60 Hz; 2-pole
1 N

30

63 A

16

5SM3 311-6KK13

007

10 000

I2_05982c

2 NT

For additional components see page 4/10.

4/8

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices

-25

SIQUENCE RCCBs, UC sensitive

(Type B)

5SM3, type B, 25 ... 80 A

Overview
Number of
poles

Rated
current In
A

Rated residual
current In
mA

MW

30, 300

300

Mountable auxiliary N-connection


switches
Right

SIQUENCE residual current operated circuit-breakers, type B1),


25 ... 80 A
short-time delayed, super resistant,
surge current withstand capability > 3 kA

selective,
surge current withstand capability > 5 kA

1)

25
40
63
80
63
80

3
4
5

= type B for AC fault currents,


pulsating and smooth residual currents.

Benefits

Application

UC sensitive: for detection of AC fault currents, pulsating and


smooth DC residual currents
Terminals with wire protection can be directly busbar-mounted
from underneath with devices with terminals in the respective
modular width, e.g. 5SY miniature circuit-breakers.
Increased operating safety in systems with capacitive impedances
due to adapted tripping characteristic
An auxiliary switch can be fitted to the right-hand side of the enclosure by the customer
Operating handle and test button can be locked by means of a
handle locking device.

Systems with equipment in which smooth residual currents can


also arise (e.g. with B6 bridge circuit on frequency converters and
medical equipment)
Product standards: IEC/EN 61008-1 (VDE 0664, Part 10);
VDE 0664 Part 100; IEC/EN 61543 (VDE 0664, Part 30)
For use in three-phase current systems
Un 230/400 V; 50 to 60 Hz; can be used in systems up to:
240/415 V AC
Definition of surge current withstand capability with current waveform 8/20 s according to DIN VDE 0432, Part 2
K-type, super resistant: short-time delayed tripping in the case
of transient leakage currents. High surge current withstand capability: > 3 kA.
S-type: can be used as upstream group switch for selective
tripping contrary to a downstream standard RCCB or RC unit. Very
high surge current withstand capability: > 5 kA.

Selection and ordering data


Maximum per- Rated
residual
missible
current
short-circuit
series fuse
I n
mA

Circuit diagram

Rated MW Vercurrent
sion

Order No.

In
A

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

short-time delayed; super resistant; surge current withstand capability


> 3 kA1)
1

30

100 A
10 000

300
2

I2 _ 0 5 9 7 6 c

25
40
63
80
25
40
63
80

5SM3 342-4
5SM3 344-4
5SM3 346-4
5SM3 347-4
5SM3 642-4
5SM3 644-4
5SM3 646-4
5SM3 647-4

008
008
008
008
008
008
008
008

0.600
0.600
0.600
0.600
0.520
0.520
0.520
0.520

1
1
1
1
1
1
1
1

5SM3 646-5
5SM3 647-5

008
008

0.520
0.520

1
1

300

100 A
10 000

I2 _ 0 5 9 7 6 c

63
80

9
10

13

230 ... 400 V AC; 50 ... 60 Hz; 4-pole


3

12

selective, surge current withstand capability > 5 kA1)


1

6
7

11

230 ... 400 V AC; 50 ... 60 Hz; 4-pole

1)

1
2

14
T

15

For rated currents In > 80 A, see SIQUENCE RCBOs, page 4/14.

16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

4/9

17

Residual Current Protective Devices


Additional Components/Accessories for RCCBs
Remote controlled mechanisms for 5SM3

Benefits

Function

Can be retrofitted individually


Mounting with factory-fitted brackets
Can be mechanically latched and locked
A 5ST3 01. auxiliary switch can also be mounted on the remote
control (see page 4/18)
Function switch on the front
Can be connected over binary inputs and outputs to
instabus KNX EIB and AS-Interface
Un = 230 V, 50 to 60 Hz.

Remote ON/OFF switching of 5SM3 RCCBs ( 80 A)


Remote ON switching possible following acknowledgment of fault
occurrence
Manual switching on-site possible
Remote display of switching status of remote controls and RCCBs.

Selection and ordering data


Circuit diagram

Rated voltage MW
Un

Order No.

V AC

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.395

Remote control (RC) for


5SM3 RCCBs ( 80 A)
230
M
P

3.5

5ST3 051

027

3
I2 _ 1 2 3 3 7

O N

O F F

For detailed application information, see Operatore guide.


For auxiliary switches for mounting on the remote control,
see "Additional components/accessories for RCBOs".

4/10

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices


Additional Components/Accessories for RCCBs
Auxiliary switches for 5SM3

Benefits

Application

An auxiliary switch can be fitted to the right-hand side of the RCCB


enclosure by the customer
Mounting with factory-fitted brackets
Can be connected to instabus KNX EIB and AS-Interface bus or
PROFIBUS through binary inputs.

Indications of the circuit state of the RCCB: ON/OFF


Short-circuit protection ensured by miniature circuit-breakers of
characteristic B or C with In = 6 A or fuse gL 6 A
Product standards: IEC/EN 62019 (VDE 0640)

FI
AS
input
in s ta b u s K N X E IB

Technical specifications
5SW3 30.
mm2
Nm

5SW3 330

6
7

0.75 ... 2.5


0.6 ... 0.8
50 mA/24 V

Min. contact load


Max. contact load
230 V AC, AC-12
230 V AC, AC-14
220 V DC, DC-12

3
4
5

I2_07849b

Terminals
Conductor cross-section
Recommended tightening torque

1
2

A
A
A

6
3.6
1

0.5

Selection and ordering data


Circuit diagram

Version

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Auxiliary switches (AS) on RCCB for 5SM3 up to 80 A


Auxiliary switches (AS)
21 13

1 NO + 1 NC

0.5

5SW3 300

008

0.042

1/10

2 NC

0.5

5SW3 301

008

0.042

1/10

2 NO

0.5

5SW3 302

008

0.042

1/10

8
9

22 14
21 11
22 12
23 13
24 14

11

Auxiliary switches (AS) on RCCBs for 5SM3, 125 A


Auxiliary switches (AS)
23 11

10

1 NO + 1 NC

0.5

5SW3 330

008

0.040

12

24 12

13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

4/11

17

Residual Current Protective Devices


Additional Components/Accessories for RCCBs
Accessories for 5SM3

Accessories
Version

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Covers for connection terminals


for residual current operated circuit-breakers up to 80 A,
sealable (2 units in plastic bag)
5SW3 010
5SW3 011
5SW3 008

008
008
008

0.003
0.004
0.006

1/50
1/50
1/50

5SW3 303

008

0.008

5ST3 802

027

0.027

I2_11431

2 MW
2.5 MW
4 MW

Locking devices
for RCCBs up to 80 A,
sealable and lockable
4.5 mm lock hasp diameter

Padlocks
for 5SW3 303 locking device

1 set

Locking devices with padlock


comprising 5SW3 303 locking device and
5ST3 802 padlock

5SW3 312

008

0.035

1 set

Busbars for residual current protective devices


see chapter "Busbars for modular installation devices".

4/12

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices


Additional Components/Accessories for RCCBs
5SM1 930 leakage current measuring devices

Benefits

Application

The leakage current measuring device enables systematic selection of the rated residual current for the RCCB, thus preventing
accidental tripping. The measured leakage current should be a
maximum of 1/3 of the rated residual current of the RCCBs. If this
condition is not met due to the rated current required to protect the
RCCB, remedial action must be taken at the equipment that generates the leakage current.
This makes it considerably easier to determine the cause when
RCCBs are accidentally tripped, particularly in extended systems
Matching of measuring curve, particularly on residual current
operated circuit-breakers, universal current sensitive (Type B)
Mounting depth 55 mm

Rated voltage: up to 500 V AC; 50 to 60 Hz


For measuring leakage currents of up to 300 mA in electrical
systems
Using the enclosed calibration curve, a voltmeter with an internal
resistance of > 1 M/V can determine the leakage current.
Measuring range for AC voltage: Urms: 1 mV to 2 V.

Function
Leakage currents are currents which, during uninterrupted operation, leak from the PE conductor or other ground connections.
As a result, the difference of the currents flowing to and from the
device will be higher than zero due to the RCBO. If the tripping current of the RCBO is reached, it then trips as leakage currents are
recorded and evaluated in the same way as fault currents.
The leakage current measuring device lets you determine the
static leakage currents flowing during plant runtime. The device
records and evaluates the currents like the RCCB, thus providing
a direct statement on how much the RCCB has already been
pre-loaded.

Selection and ordering data


Circuit diagram

Rated residual Rated current MW Order No.


current
I n

In

mA

0 ... 300

63

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.430

5SM1 930 leakage current measurement devices


500 V AC; 50 ... 60 Hz; 4-pole
1 3 5 N

5SM1 930-0

008

1
2
3
4
5
6
7
8

V 1 M/V
2 4 6 N

I2_07078a

Gossen-Metrawatt offers suitable test devices for RCCB function


tests and for testing protective measures.

10

Information is available at:


Gossen-Metrawatt GmbH
Thomas-Mann-Str. 16-20
D-90 471 Nuremberg
Tel. +49 (0)911/8602 111
Fax +49 (0)911/8602 777
http://www.gmc-instruments.com
e-mail:
info@gmc-instruments.com

11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

4/13

17

Residual Current Protective Devices


SIQUENCE RCCBs with Integral Overcurrent Protection RCBOs, UC Sensitive
-25

5SU1, type B, 100 ... 125 A

(Type B)

Overview
Number of
poles

Rated current In Rated residual


current In
A
mA

MW

Additional components can be


retrofitted

100
125

30, 300

11

SIQUENCE RCBOs, type B1), 100 ... 125 A


Rated short-circuit capacity 10 kA
short-time delayed tripping, super resistant,
surge current withstand capability >3 kA
Rated voltage 400 V AC;
10 000
Characteristic C
Rated voltage 400 V AC;
Characteristic D

10 000

100

30, 300

11

Rated voltage 480 V AC;


Characteristic C
selective version

10 000

100
125

300

11

Rated voltage 400 V AC;


Characteristic C
Rated voltage 400 V AC;
Characteristic D

10 000

125

300

11

10 000

100

300

11

1)

= type B for AC fault currents, pulsating and smooth residual


currents.

Benefits

Application

UC sensitive: for detection of AC fault currents, pulsating and


smooth DC residual currents
Time-saving wiring and simplified device co-ordination thanks to
RCBO for combined personnel and line protection in a single
device
Increased operating safety in systems with capacitive impedances
due to adapted tripping characteristic
Additional components can be retrofitted by the customer
External remote tripping over Y1/Y2 terminals

Systems with equipment in which smooth residual currents can


also arise (e.g. with B6 bridge circuit on frequency converters and
medical equipment)
Product standards: IEC/EN 61009-1 (VDE 0664, Part 10);
VDE 0664 Part 200; IEC/EN 61543 (VDE 0664, Part 30)
For use in three-phase current systems
Un = 400 V or Un = 480 V; 50 ... 60 Hz
Definition of surge current withstand capability with current waveform 8/20 s according to DIN VDE 0432 Part 2
K-type, super resistant: short-time delayed tripping in the case
of transient leakage currents. High surge current withstand capability: > 3kA.

Selection and ordering data


Version

Rated Rated MW MCB characteristic C


residual current
Order No.
Price
current
In
In
mA

Price

Weight
1 unit
approx.

PS*/
P. unit

1 unit

kg

Unit(s)

MCB characteristic D
Order No.

1 unit

PG

short-time delayed tripping; super resistant;


surge current withstand capability > 3 kA1)
400 V AC; 50 ... 60 Hz; 4-pole
30
100
125
10 000

300

100
125

11

5SU1 374-7AK81
5SU1 374-7AK82

5SU1 374-8AK81
--

011
011

1.950
1.950

1
1

11

5SU1 674-7AK81
5SU1 674-7AK82

5SU1 674-8AK81
--

011
011

1.950
1.950

1
1

11

5SU1 674-7CK81
5SU1 674-7CK82

---

011
011

1.950
1.950

1
1

-5SU1 674-7BK82

5SU1 674-8BK81
--

011
011

1.950
1.950

1
1

480 V AC; 50 ... 60 Hz; 4-pole


10 000

300

100
125

selective; surge current withstand capability > 5 kA


400 V AC; 50 ... 60 Hz; 4-pole

300

100
125

11

10 000

4/14

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices


RCCBs with Integral Overcurrent Protection, (RCBOs)
-25

(Type A)

5SU1, type A, 6 ... 40 A

Overview
Number of
poles

Rated current In Rated residual


current In
A
mA

MW

Additional
components can be
retrofitted

6
8
10
13
16

30, 300
30
30, 300

20
25
32
40

30, 300

6
8
10
13
16

10, 30, 300


30
10, 30, 300

20
25
32
40

30, 300

6
10
13
16
20
25
32
40

30

RCBOs, type A1), 6 ... 40 A 2-(1 + N) pole


Instantaneous tripping,
surge current withstand capability > 1 kA 6 000
Rated short-circuit capacity 6 kA
3
Characteristic B and C

Rated short-circuit capacity 10 kA


Characteristic B and C

10 000
3

3
4
5

1
2

6
7

RCBOs, type A1), 6 ... 40 A, 2-pole

Instantaneous tripping,
surge current withstand capability > 1 kA
Rated short-circuit capacity 10 kA
Characteristic B and C

1)

10 000
3

9
10

= Type A for AC and pulsating DC residual currents.

Benefits
Compact device version for personnel and line protection
Simplified device coordination thanks to unit comprising residual
current operated circuit-breaker RCCB and miniature circuitbreaker
Saves time with wiring
Maximum plant availability thanks to assignment of a device to a
specific electrical circuit
Excellent current limitation and selectivity characteristics
Combined terminal for simultaneous connection of pin busbars
and feeder cables
Simple connection of feeder cables due to rear relocation of
busbar connection
Identical terminals at both sides for optional infeed from the top or
the bottom
Operating handle and test button can be locked by means of a
handle locking device
Customers can retrofit additional components to the miniature
circuit-breakers for additional uses
Additional features of the 10 kA version:
Reach-round protection exceeds requirements
according to BGV A3
No tools required for rail mounting or dismounting
Separate switching position indicator

Application
Personnel and fire protection
- In 30 mA: additional protection in the case of direct contact
- In 300 mA: preventative fire protection in the case of ground
fault currents
Cable and line protection against overload and short-circuits
Product standards: IEC/EN 61008-1 (VDE 0664, Part 10);
IEC/EN 61008-2-1 (VDE 0664, Part 11); IEC/EN 61543
(VDE 0664, Part 30)
Un = 230 V; 50 ... 60 Hz
Miniature circuit-breaker characteristic B or C
Definition of surge current withstand capability with current
waveform 8/20 s acc. to DIN VDE 0432, Part 2

11
12
13
14
15
16

Siemens ET B1 2007

4/15

17

Residual Current Protective Devices

-25

(Type A)

RCCBs with Integral Overcurrent Protection, (RCBOs)


5SU1, type A, 6 ... 40 A

Selection and ordering data


Circuit diagram

Rated Rated MW
residual current
current
In
In
mA

MCB characteristic B
Order No.
Price

MCB characteristic C
Order No.
Price

1 unit

1 unit

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Instantaneous tripping,
surge current withstand capability > 1 kA
230 V AC; 50 ... 60 Hz; 2- (1 + N)-pole
1

30
N

I2 _ 0 6 0 0 1 b

6 000
3
300

6
8
10
13
16
20
25
32
40
6
10
13
16

20
25
32
40
230 V AC; 50 ... 60 Hz; 2- (1 + N)-pole
1
N
10
6
2
10
13
16
I2 _ 0 6 0 0 1 b

30

10 000
3

300

6
8
10
13
16
20
25
32
40
6
10
13
16

20
25
32
40

I2 _ 0 6 0 0 1 b

10 000
3

4/16

Siemens ET B1 2007

20
25
32
40

5SU1 356-7KK06
5SU1 356-7KK08
5SU1 356-7KK10
5SU1 356-7KK13
5SU1 356-7KK16

011
011
011
011
011

0.260
0.260
0.260
0.260
0.260

1
1
1
1
1

5SU1 356-6KK20
5SU1 356-6KK25
5SU1 356-6KK32
5SU1 356-6KK40
5SU1 656-6KK06
5SU1 656-6KK10
5SU1 656-6KK13
5SU1 656-6KK16

5SU1 356-7KK20
5SU1 356-7KK25
5SU1 356-7KK32
5SU1 356-7KK40
5SU1 656-7KK06
5SU1 656-7KK10
5SU1 656-7KK13
5SU1 656-7KK16

011
011
011
011
011
011
011
011

0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260

1
1
1
1
1
1
1
1

5SU1 656-6KK20
5SU1 656-6KK25
5SU1 656-6KK32
5SU1 656-6KK40

5SU1 656-7KK20
5SU1 656-7KK25
5SU1 656-7KK32
5SU1 656-7KK40

011
011
011
011

0.260
0.260
0.260
0.260

1
1
1
1

5SU1 154-6KK06
5SU1 154-6KK10
5SU1 154-6KK13
5SU1 154-6KK16

5SU1 154-7KK06
5SU1 154-7KK10
5SU1 154-7KK13
5SU1 154-7KK16

011
011
011
011

0.260
0.260
0.260
0.260

1
1
1
1

5SU1 354-6KK06
-5SU1 354-6KK10
5SU1 354-6KK13
5SU1 354-6KK16

5SU1 354-7KK06
5SU1 354-7KK08
5SU1 354-7KK10
5SU1 354-7KK13
5SU1 354-7KK16

011
011
011
011
011

0.260
0.260
0.260
0.260
0.260

1
1
1
1
1

5SU1 354-6KK20
5SU1 354-6KK25
5SU1 354-6KK32
5SU1 354-6KK40
5SU1 654-6KK06
5SU1 654-6KK10
5SU1 654-6KK13
5SU1 654-6KK16

5SU1 354-7KK20
5SU1 354-7KK25
5SU1 354-7KK32
5SU1 354-7KK40
5SU1 654-7KK06
5SU1 654-7KK10
5SU1 654-7KK13
5SU1 654-7KK16

011
011
011
011
011
011
011
011

0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260

1
1
1
1
1
1
1
1

5SU1 654-6KK20
5SU1 654-6KK25
5SU1 654-6KK32
5SU1 654-6KK40

5SU1 654-7KK20
5SU1 654-7KK25
5SU1 654-7KK32
5SU1 654-7KK40

011
011
011
011

0.260
0.260
0.260
0.260

1
1
1
1

5SU1 324-6FA06
5SU1 324-6FA10
5SU1 324-6FA13
5SU1 324-6FA16

5SU1 324-7FA06
5SU1 324-7FA10
5SU1 324-7FA13
5SU1 324-7FA16

011
011
011
011

0.403
0.403
0.403
0.403

1
1
1
1

5SU1 324-6FA20
5SU1 324-6FA25
5SU1 324-6FA32
5SU1 324-6FA40

5SU1 324-7FA20
5SU1 324-7FA25
5SU1 324-7FA32
5SU1 324-7FA40

011
011
011
011

0.403
0.403
0.403
0.403

1
1
1
1

Instantaneous tripping,
surge current withstand capability > 1 kA
230 V AC; 50 ... 60 Hz; 2-pole
30
6
1
N
10
13
16

5SU1 356-6KK06
-5SU1 356-6KK10
5SU1 356-6KK13
5SU1 356-6KK16

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices


Additional Components/Accessories for RCBOs
Remote controlled mechanisms for 5SU1

Benefits
Can be retrofitted individually (see below)
Mounting with factory-fitted brackets
Can be mechanically latched and locked
Further additional components can be attached
Function switch on the front
UN = 230 V, 50 to 60 Hz
Additional components are identical to those for 5SY miniature
circuit-breakers.

Mounting concept
Using this mounting concept, all additional 5ST3 components can
be combined with miniature circuit-breakers of the 5SY1) and 5SP4
series and the 5SU1 RCBO series:

5ST3

or

or

5SU1

AS

5ST3 805-1
Handle
couplers
5ST3 050

or
ST

RCBOs

or
UR

AS

FC
AS

6
7

or
AS
FC

AS
FC

AS
FC

FC
AS

AS
FC

FC
AS

or

or
AS
FC

FC

AS
FC

input

output

instabus KNX/EIB

I2_12130

1)

AS
FC

AS
FC

or
FC

AS

RC

AS
FC

3
4
5

or

FC

1
2

Not for 5SY6 ...-.KV.

Function
Remote ON/OFF switching of the RCBO.
Remote ON switching possible following acknowledgment of fault
occurrence

Manual switching on-site possible


Remote display of switching status of remote control and RCBOs.

10
11

Selection and ordering data


Circuit diagram

Rated voltage MW
Un

Order No.

Price

PG

V AC

Weight
1 unit
approx.
kg

PS*/
P. unit

0.395

Unit(s)

Remote controlled mechanisms (RC) for 5SU1 RCBOs


230

3.5

5ST3 050

027

12
13

M
P N 1 2 3
I2_10741

14

ON OFF

For detailed application information, see operator guide.

15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

4/17

17

Residual Current Protective Devices


Additional Components/Accessories for RCBOs
Auxiliary switches/fault signal contacts for 5SU1

Benefits
Can be retrofitted individually (see page 4/17)
Mounting with factory-fitted brackets
Short-circuit protection by means of miniature circuit-breakers
of B or C characteristic and In = 6 A or gL 6 A fuses.
Wide range of applications due to additional version for controlling
programmable control systems (PLCs) according to EN 61131-2
Can be connected to instabus KNX EIB and AS-Interface bus over
binary inputs.

Application
Indication of the switching state of the RCBO
AS: ON/OFF
FC: triggered
Auxiliary switches (AS)
5ST3 013
5ST3 014
5ST3 015
Area of application 1 mA/5 V DC to 50 mA/30 V DC.

Auxiliary switches (AS) and fault signal contacts (FC)


5ST3 0.0
5ST3 0.1
5ST3 0.2
Min. contact load:
50 mA, 24 V
Max. contact load:
NO contact:
2 A, 400 V AC, AC-14
6 A, 230 V AC, AC-14
1 A, 220 V DC, DC-13
1 A, 110 V DC, DC-13
3 A, 60 V DC, DC-13
6 A, 24 V DC, DC-13
NC contact:
2 A, 400 V AC, AC-13
6 A, 230 V AC, AC-13
1 A, 220 V DC, DC-13
1 A, 110 V DC, DC-13
3 A, 60 V DC, DC-13
6 A, 24 V DC, DC-13

Selection and ordering data


Circuit diagram

Version

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Auxiliary switches (AS) for 5SU1 RCBO1) 2)


13
21

1 NO + 1 NC 0.5

5ST3 010
5ST3 013

027
027

0.050
0.050

1
1

2 NO

5ST3 011
5ST3 014

027
027

0.050
0.050

1
1

2 NC

5ST3 012
5ST3 015

027
027

0.050
0.050

1
1

1 NO + 1 NC 0.5

5ST3 020

027

0.050

2 NO

5ST3 021

027

0.050

2 NC

5ST3 022

027

0.050

5ST3 805-1

027

0.008

for small output

22
14
13
23

for small output

24
14
11
21

for small output

22
12

Fault signal contacts (FC) for 5SU1 RCBOs1)


13
21
22
14
13
23
24
14
11
21
22
12

1 set

Handle couplers for additional components


For mounting the additional components: auxiliary switches,
fault signal contacts, shunt trips and undervoltage releases
onto 5SU1 RCBOs, you require a handle coupler.
1 set = 5 units
1)

Also needed for mounting onto 5SU1...-.KK. RCBOs 5ST3 805-1 handle
coupler.

2)

Also suitable for mounting on 5ST3 051 remote controlled mechanism.

4/18

Siemens ET B1 2007

1 set

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices


Additional Components/Accessories for RCBOs
Shunt trips/undervoltage releases for 5SU1

Benefits

Application

Shunt trips
Can be retrofitted individually (see page 4/17)
Response limits according to EN 60947-1, 7.2.1.4
Can be connected to instabus KNX EIB and AS-Interface bus over
binary outputs.
Undervoltage releases
Can be retrofitted individually (see page 4/17)
Response limits according to EN 60947-1, 7.2.1.3
Can be connected to instabus KNX EIB and AS-Interface bus over
binary outputs.

Shunt trips
Remote tripping of the RCBO.
For voltages:
110 to 415 V AC,
110 V DC
24 to 48 V AC/DC
Undervoltage releases
Can be used as remote trip in an EMERGENCY-OFF loop
Ensures disconnection of the control circuit according to EN 60204
In cases of interrupted or insufficient voltage, the undervoltage
release trips the miniature circuit-breaker or prevents it from
switching on
For voltages:
230 V AC
110 V DC
24 V DC

Selection and ordering data


Circuit diagram

Rated voltage

MW

Order No.

Un
Shunt trips (ST) for 5SU1 RCBOs1)
C2

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

D2

6
7

5ST3 030

027

0.098

5ST3 031

027

0.098

5ST3 040
5ST3 041
5ST3 042

027
027
027

0.115
0.115
0.115

1
1
1

5ST3 043
5ST3 044
5ST3 045

027
027
027

0.115
0.115
0.115

1
1
1

10

5ST3 805-1

027

0.008

1 set

11

230 V AC
110 V DC
24 V DC

8
9

1 set

Handle couplers for additional components


For mounting the additional components: auxiliary
switches, fault signal contacts, shunt trips and undervoltage releases onto 5SU1 RCBOs, you require a handle
coupler.
1 set = 5 units
1)

110 ... 415 V AC

Undervoltage releases (UR) for 5SU1 RCBOs1)


230 V AC
D1 13 23
110 V DC
U<
24 V DC
D2 14 24
D1

3
4

24 ... 48 V AC/DC

C1

1
2

Also needed for mounting onto 5SU1...-.KK. RCBOs 5ST3 805-1 handle
coupler.

12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

4/19

17

Residual Current Protective Devices


Additional Components/Accessories for RCBOs
Accessories for 5SU1

Accessories
Version

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Locking devices
for 5SU1 ...-.KK.. RCBOs
sealable and lockable
lock hasp diameter, 4.5 mm

5ST3 801-1

027

0.010

5ST3 802

027

0.027

Padlocks
for 5ST3 801-1 locking device

For busbars for RCBOs, see chapter


"Busbars for modular installation devices".

4/20

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices

(Type A)

RC Units for Miniature Circuit-Breakers


5SM2, product overview

Overview
Number of
poles

Rated
current In

Rated residual
current In

mA

MW

Additional components
can be retrofitted
(Type A)1)

RC units for 5SY4, 5SY6, 5SY7, 5SY8 miniature


circuit-breakers2)
2

0.3 ... 16

10

at the MCB

0.3 ... 40
0.3 ... 63

30, 300
30, 100, 300, 500

at the MCB
at the MCB

0.3 ... 40
0.3 ... 63

30, 300
30, 100, 300, 500

at the MCB
at the MCB

0.3 ... 40
0.3 ... 63

30, 300
30, 100, 300, 500

at the MCB
at the MCB

short-time delayed, super resistant


surge current withstand capability > 3 kA

0.3 ... 40
0.3 ... 63

30

at the MCB
at the MCB

selective
surge current withstand capability > 5 kA

0.3 ... 40
0.3 ... 63

300

at the MCB
at the MCB

3
4

0.3 ... 63
0.3 ... 63

300, 500, 1000


300, 500, 1000

3
3

at the MCB
at the MCB

Instantaneous tripping,
surge current withstand capability > 1 kA

2
4

80 ... 100
80 ... 100

30, 300
30, 300

3.5
5

at the MCB
at the MCB

selective
surge current withstand capability > 5 kA

2
4

80 ... 100
80 ... 100

300
300, 1000

3.5
5

at the MCB
at the MCB

1)
2)

3
4
5
6
7

RC units for 5SP4 miniature circuit-breakers2)


Instantaneous tripping,
surge current withstand capability > 1 kA

1
2

= Type A for AC and pulsating DC residual currents

RC unit, additional components for 5SY. and 5SP4 miniature circuit-breakers, see also section, "Miniature circuit-breakers/Additional components".

9
10
11
12
13
14
15
16
Siemens ET B1 2007

4/21

17

Residual Current Protective Devices

-25

(Type A)

RC Units for Miniature Circuit-Breakers


5SM2, 0.3 ... 63 A,
for 5SY4, 5SY6, 5SY7, 5SY8

Benefits

Product standards: IEC/EN 61009-1 (VDE 0664, Part 20);


IEC/EN 61009-2-1 (VDE 0664, Part 21); IEC/EN 61543 (VDE 0664,
Part 30)
Rated voltage for 2, 3 and 4-pole version: 230 to 400 V AC; 50 to
60 Hz; applicable in systems up to: 250/440 V AC
Can be combined with miniature circuit-breakers of characteristic
A, B, C and D
Definition of surge current withstand capability with current
waveform 8/20 s acc. to DIN VDE 0432, Part 2
S-Type: can be used as upstream group switch for selective
tripping contrary to a downstream standard RCCB. Very high
surge current withstand capability: > 5 kA
K-type: super resistant: Short-time delayed tripping in the case
of transient leakage currents. High surge current withstand capability: > 3 kA.

High application flexibility


Customers can combine the device characteristics of RC units and
miniature circuit-breakers
Used together with miniature circuit-breakers achieves a
combined personnel and line protection.

Application
Personnel and fire protection
- In 30 mA: additional protection in the case of direct contact
- In 300 mA: preventative fire protection in the case of ground
fault currents

Selection and ordering data


Circuit diagram

Rated
Rated
residual current
current
In
I n
mA

MW Version

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Instantaneous tripping, surge current withstand capability > 1 kA1)


230 ... 400 V AC, 50 ... 60 Hz, 2-pole
1 3 (N )

2 4 (N )

I2 _ 0 7 8 2 0 a

2 /1

10

0.3 ... 16 2

5SM2 121-6

007

0.180

30
300

0.3 ... 40 2

5SM2 322-6
5SM2 622-6

007
007

0.170
0.170

1
1

30
100
300
500

0.3 ... 63

5SM2 325-6
5SM2 425-6
5SM2 625-6
5SM2 725-6

007
007
007
007

0.170
0.170
0.170
0.170

1
1
1
1

30
300
30
100
300
500

0.3 ... 40 3

5SM2 332-6
5SM2 632-6
5SM2 335-6
5SM2 435-6
5SM2 635-6
5SM2 735-6

007
007
007
007
007
007

0.260
0.260
0.260
0.260
0.260
0.260

1
1
1
1
1
1

4 /3 (N )

230 ... 400 V AC, 50 ... 60 Hz, 3-pole


1 3 5 (N )

0.3 ... 63

2 4 6

I2 _ 0 8 4 1 1 a

2 /1

4 /3

6 /5

230 ... 400 V AC, 50 ... 60 Hz, 4-pole


1 3 5 7 (N )

30
300

0.3 ... 40 3

5SM2 342-6
5SM2 642-6

007
007

0.290
0.290

1
1

30
100
300
500

0.3 ... 63

5SM2 345-6
5SM2 445-6
5SM2 645-6
5SM2 745-6

007
007
007
007

0.290
0.290
0.290
0.290

1
1
1
1

2 4 6 8 (N )

I2 _ 0 7 8 1 9 a

2 /1
4 /3

6 /5
8 /7 (N )

short-time delayed; super resistant; surge current withstand capability > 3 kA1)
0.3 ... 40 3
0.3 ... 63

5SM2 342-6KK01
5SM2 345-6KK01

007
007

0.290
0.290

1
1

300
300

0.3 ... 40 2
0.3 ... 63

5SM2 622-8
5SM2 625-8

007
007

0.170
0.170

1
1

300
500
1 000

0.3 ... 63 3

5SM2 635-8
5SM2 735-8
5SM2 835-8

007
007
007

0.260
0.400
0.260

1
1
1

300
500
1 000

0.3 ... 63 3

5SM2 645-8
5SM2 745-8
5SM2 845-8

007
007
007

0.290
0.400
0.290

1
1
1

30

230 ... 400 V AC, 50 ... 60 Hz, 4-pole

selective; surge current withstand capability > 5 kA1)


230 ... 400 V AC, 50 ... 60 Hz, 2-pole

230 ... 400 V AC, 50 ... 60 Hz, 3-pole

230 ... 400 V AC, 50 ... 60 Hz, 4-pole

1)

Not for 5SY6 ...-.KV.

For miniature circuit-breakers, see Chapter


"Miniature circuit-breakers".

4/22

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices

-25

(Type A)

RC Units for Miniature Circuit-Breakers


5SM2, 80 ... 100 A,
for 5SP4

Benefits

Product standards: IEC/EN 61009-1 (VDE 0664, Part 20);


IEC/EN 61009-2-1 (VDE 0664, Part 21); IEC/EN 61543 (VDE 0664,
Part 30)
Rated voltage
- 2-pole: 125 to 230 V AC; 50 to 60 Hz; can be used in systems up
to 125/240 V AC
- 4-pole: 230 to 400 V AC; 50 to 60 Hz; can be used in systems up
to 230/400 V AC
Can be combined with miniature circuit-breakers, characteristic B
and C
Definition of surge current withstand capability with current waveform 8/20 s acc. to DIN VDE 0432, Part 2
S-Type: can be used as upstream group switch for selective
tripping against downstream standard RCCBs. Very high surge
current withstand capability: > 5 kA.

High application flexibility


Customers can combine the device characteristics of RC units and
miniature circuit-breakers
Used together with miniature circuit-breakers achieves a
combined personnel and line protection
External remote tripping over Y1/Y2 terminals

Application
Personnel and fire protection
- In 30 mA: additional protection in the case of direct contact
- In 300 mA: preventative fire protection in the case of ground
fault currents

Selection and ordering data


Circuit diagram

Rated
Rated
residual current
current
In
I n
mA

MW Version

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.410
0.410

1
1

Instantaneous tripping, surge current withstand capability > 1 kA


125 ... 230 V AC, 50 ... 60 Hz, 2-pole
Y1 Y2

30
300

1 3 (N)

I2_06662c

80 ... 100 3.5

5SM2 327-6
5SM2 627-6

007
007

4/3(N)

230 ... 400 V AC, 50 ... 60 Hz, 4-pole


Y 1

Y 2

30
300

1 3 5 7 (N )

I2 _ 0 6 6 6 1 c

80 ... 100 5

5SM2 347-6
5SM2 647-6

007
007

0.630
0.630

1
1

5
6
7
9
10

2 4 6 8 (N )
2 /1
4 /3

3
4

2 4 (N)
2/1

1
2

6 /5
8 /7 (N )

11

selective; surge current withstand capability > 5 kA


125 ... 230 V AC, 50 ... 60 Hz, 2-pole
300

80 ... 100

5SM2 627-8

007

0.410

300
1 000

80 ... 100

5SM2 647-8
5SM2 847-8

007
007

0.630
0.630

1
1

230 ... 400 V AC, 50 ... 60 Hz, 4-pole

12
13

For miniature circuit-breakers, see Chapter "Miniature circuit-breakers".

14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

4/23

17

Residual Current Protective Devices

-25

(Type A)

RCCB Socket Outlets (SRCDs)


5SM1 and 5SZ9 RCCB protective socket outlets

Overview
Number of poles Rated
current In

Rated residual
current In

mA

(Type A)

16

10, 30

16

10, 30

16

10, 30

RCCB protective socket outlets


For mounting onto switch and socket box, equipped with RCCB and
2 5 socket outlets
Molded-plastic enclosures, equipped with RCCB and 5 socket outlet

RCCB protective socket outlets for a higher level of protection


5 DELTA profil socket outlets, titanium white

= Type A for AC and pulsating DC residual currents

Application
RCCB protective socket outlets
Molded-plastic enclosure equipped with residual current operated
circuit-breaker and flush-mounting 5 socket outlet or flushmounting 5 double socket outlet
Rated voltage: 230 V AC, 50 to 60 Hz
For electric devices, where in the event of damage, there is a risk
of accidental contact with live parts
For outdoor connection of gardening equipment and socket outlets
in workshops or for agricultural purposes
Degree of protection IP54 (5SZ9 2.6)

RCCB protective socket outlets for a higher level of protection


RCCB protective socket outlets according to VDE 0662,
DELTA profil
Rated voltage: 230 V AC, 50 to 60 Hz
Childproof 5 socket outlets with integrated RCCB
For retrofitting in existing installations or for additional protection in
children's rooms, bathroom, garage, workshop, kindergarten,
schools etc.
With VDE mark of conformity acc. to the DIN VDE 0662 (stationary
protective socket outlet for a higher level of protection, SRCD) draft
The mode of operation is not dependent on the supply voltage
The protective conductor is monitored but not switched
Degree of protection, IP21
With screwless terminals 1.5 to 2.5 mm2, for Cu and Al conductors
For installation in conventional switch and socket boxes, 60 mm,
for screw connection
Can be used in TN-S systems, TN-C systems and TT systems
Including frame, single frame, with cutout 48 mm 48 mm.
Note:
The protective measures according to DIN VDE 0100 must also be
observed when RCCB protective socket outlets are used.

Selection and ordering data


Rated
residual
current
In
mA

Rated
current

Order No.

In
A

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

RCCB protective socket outlets


RCCB protective socket outlet according to VDE 0664
for mounting on switch and socket box, equipped with
residual current operated circuit-breaker and
2 childproof 5 socket outlets
10
30

16

5SM1 920-5
5SM1 920-8

008
008

0.500
0.500

1
1

16

5SZ9 206
5SZ9 216

008
008

0.760
0.760

1
1

RCCB protective socket outlet according to


VDE 0664 in molded-plastic enclosure, equipped
with residual current operated circuit-breaker
and flush-mounting 5 socket outlet
10
30

4/24

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Residual Current Protective Devices

-25

(Type A)

RCCB Socket Outlets (SRCDs)


5SM1 and 5SZ9 RCCB protective socket outlets
Rated
residual
current
I n
mA

Rated
current

Order No.

In
A

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.160
0.160

1
1

RCCB protective socket outlets for a higher level of protection


RCCB protective socket outlets acc. to VDE 0662
for increased protection level 5 DELTA
profil socket outlets, childproof, titanium white
L
N
PE

10
30
PE

16

5SZ9 211
5SZ9 212

008
008

1
2
3
4

I2_06874

6
7

Suitable for mounting on 5TG1 825 surface-mounting enclosures.

For further cutout frames for multiple combinations,


see the catalog ET D1, "DELTA switches and socket outlets".

8
9
10
11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

4/25

17

Residual Current Protective Devices


Accessories
For all product ranges

Accessories
Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Terminal covers, gray


for surface mounting, degree of protection IP40,
sealable, with 35 mm standard mounting rail
up to 2.5 MW
up to 4.5 MW

5SW3 004
5SW3 005

008
008

0.084
0.114

1/10
1

Wall enclosures, gray


for flush mounting, degree of protection IP40
with 35 mm standard mounting rail
up to 2.5 MW
up to 4.5 MW

5SW3 006
5SW3 007

008
008

0.126
0.147

1/4
1/5

5SW1 200

008

0.450

can be assembled as mini distribution board, suitable for all devices,


cover parts prepared for rail mounting of conventional label caps,
comprising:
End plates (for snapping onto standard mounting rail)

5ST2 134

027

0.022

1/10

Angled profile (approx. 1 m long) or, alternatively,

5ST2 135

027

0.330

1/5

Flat profile
(as a cover between the rows of devices length approx. 1 m)

5ST2 136

027

0.260

1/5

5ST2 112

027

0.008

1/50

5ST2 201

027

0.012

1/20

5ST2 173

027

0.038

Molded-plastic enclosures, gray


surface mounting, IP54, with 35 mm standard mounting rail, sealable,
with transparent hinged lid,
for 4.5 MW

Covers

Snap-on terminals
for 35 mm standard mounting rail,
for conductors up to 16 mm2 solid
or conductors up to 10 mm2 stranded
width 0.5 MW
Fixing parts
4 MW (plastic)

1 set

Inscription labels (white)


15 mm 9 mm, 3 frames with 44 labels each
any attachment and inscription, self-adhesive
Labeling system

1 set

To download the labeling program free of charge,


please visit our Web site at:
http://www.siemens.de/beta
Recommended labels ELAT-3-747
can be ordered at: Brady GmbH
Otto-Hahn-Str. 5-7
D-63222 Langen
Tel: +49 (0)6103/7598-660

4/26

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Lightning and Overvoltage


Protection Devices

General Data

5/2

Product overview

Lightning Arresters

5/3

Requirement category B,
type 1, class I

Arrester Combinations

5/4

Requirement category B and C,


type 1 and 2, class I and II

Surge Arresters

5/5

Narrow version, requirement


category C, type 2, class II
Wide version, requirement
category C, type 2, class II
Multipole, requirement category D,
type 3, class III

5/6
5/8

Surge Protection
Adapters

5/9

Requirement category D,
type 3, class III

Accessories

5/10

For lightning and overvoltage


protection devices

5/1

Lightning and Overvoltage Protection Devices


General Data
Product overview

Overview
Lightning arresters requirement category B, type 1, class I
Plug-in protective blocks
TN-C, TN-S and TT systems
Rated arrester voltage Uc 350 V AC
Lightning current 50 ... 100 kA
All versions with remote indication contact
Installation location: Main distribution board, upstream or
downstream from the counter

Arrester Combinations requirement category B and C, type 1 and 2, class I and II


Plug-in protective blocks
TN-C, TN-S and TT systems
Rated arrester voltage Uc 350 V AC
Lightning current 50 ... 100 kA
All versions with remote indication contact
Installation location: Main distribution board

Surge arresters, narrow version requirement category C, type 2, class II


Plug-in protective blocks
2, 3 and 4-pole (TN-C, TN-S and TT systems)
Rated arrester voltage Uc 350 V AC
Rated discharge current 20 kA
Discharge surge current 40 kA
Version without or with remote indication contact
Installation location: Sub-distribution board
Mounting width 12 mm/pole

Surge arresters, wide version requirement category C, type 2, class II


Plug-in protective blocks or compact version
1, 2, 3 and 4-pole (TN-C, TN-S and TT systems)
Rated arrester voltage Uc 350 V AC
Rated discharge current 20 kA
Discharge surge current 40 kA
Version without or with remote indication contact
Installation location: Sub-distribution board
Mounting width 18 mm/pole (1 MW/pole)

Surge arresters requirement category D, type 3, class III


Plug-in protective blocks
For 1-phase and 3-phase systems
Rated voltage
- 1-phase AC/DC 24 V, 60 V, 120 V, 230 V
- 3-phase system AC 230/400 V
Monitoring device
Installation location: As close as possible upstream from
the terminal equipment

Surge protection adapters socket outlets, socket outlet adapters and combination protective devices
Can be plugged into 5 socket outlets
Status display
Permanent thermal monitoring of the protection circuit

Accessories
Male connectors for lightning and surge arresters
Through-type terminals
Busbars

1 MW modular width 18 mm

5/2

Siemens ET B1 2007

Lightning and Overvoltage Protection Devices


Lightning Arresters
Requirement category B, type 1, class I

Benefits
Type 1 lightning arresters do not require decoupling reactors
to be fitted in the plant. This simplifies plant configuration and
reduces space requirements. No time is wasted on planning
the installation of decoupling reactors. This also considerably
cuts costs.
The rated arrester voltage is a uniform 350 V AC. This increases safety in systems with extended voltage overshoots.
All lightning arresters are fitted with a mechanical fault indication, which does not require an extra power supply. This
means they can be installed in the precounter area, where
electrical plants can be protected particularly effectively.
The protective modules are plug-in versions. No mounting
work required when replacing the protective modules. When
taking insulation measurements, the protective modules are
simply removed, no need to disconnect the power supply.

All type 1 lightning arresters are fitted with a remote indication


contact, which is inserted in the device and does not require
any further space. A remote signaling is always possible, even
in the event of a power failure.

Application
Type 1 lightning arresters include the system cables in the
equipotential bonding, which protects the low-voltage
systems against the overvoltages and high surge currents that
can be triggered by direct or indirect lightning strikes.
The protection level is lowered to 1.5 kV by the lightning arrester, which reduces the load on the plant if a lightning strike
is discharged.
The lightning arresters are enclosed and are suitable for
installation in the precounter area.
Tested by wave-shaped lightning impulse, 25/100 kA with
waveform 10/350 s.

Selection and ordering data


Discharge
capacity
kA

MW

100

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

0.732

Lightning arresters
2-pole
for TT and TN-S systems

5SD7 412-1

008

1
2
3
4
5
6
7
8
9

3-pole
for TN-C systems

75

5SD7 413-1

008

0.909

10
11

4-pole
for TT and TN-S systems

100

5SD7 414-1

008

1.310

12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

5/3

17

Lightning and Overvoltage Protection Devices


Arrester Combinations
Requirement category B and C,
type 1 and 2, class I and II

Benefits
Type 1 and 2 arrester combinations do not require decoupling
reactors to be fitted in the plant. This simplifies plant configuration and reduces space requirements. No time is wasted on
planning the installation of decoupling reactors. This also considerably cuts costs.
The rated arrester voltage is a uniform 350 V AC. This
increases safety in systems with longer voltage overshoots.
All arrester combinations are fitted with a mechanical fault indication, which does not require an extra power supply.
The protective modules are plug-in versions. No mounting
work required when replacing the protective modules. When
taking insulation measurements, the protective modules are
simply removed, no need to disconnect the combination
arrester from the power supply.
The same type 2, class II overvoltage protective modules are
used as for the slim version of the surge arresters (5SD7 42.).
This simplifies stock-keeping.

All arrester combinations are fitted with a remote indication


contact, which is inserted in the device and does not require
any further space. A remote signaling is always possible, even
in the event of a power failure.

Application
Type 1 and 2 arrester combinations include the system cables
in the equipotential bonding, which protects the low-voltage
systems against the overvoltages and high currents that can
be triggered by direct lightning strikes.
The protection level is lowered to 1.5 kV by the arrester combinations, which reduces the load on the plant if a lightning
strike is discharged.
Tested by wave-shaped lightning impulse, 25/100 kA with
waveform 10/350 s.
A thermal isolating arrester disconnector offers a high degree
of protection against overload during runtime.

Selection and ordering data


Discharge
capacity
kA

MW

2-pole
for TT and TN-S systems

100

5SD7 442-1

3-pole
for TN-C systems

75

4-pole
for TT and TN-S systems

100

Order No.

Weight
1 unit
approx.
kg

Unit(s)

008

0.770

5SD7 443-1

008

1.040

5SD7 444-1

008

1.430

Price

PG

1 unit

PS*/
P. unit

Arrester combinations

5/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Lightning and Overvoltage Protection Devices


Surge Arresters
Narrow version,
requirement category C, type 2, class II

Benefits
Type 2 surge arresters do not require decoupling reactors to
be fitted in the system. This simplifies plant configuration and
reduces space requirements. No time is wasted on planning
the installation of decoupling reactors. This considerably cuts
costs.
The rated arrester voltage is a uniform 350 V AC. This
increases safety in systems with extended voltage overshoots.
All type 2 surge arresters are fitted with a mechanical fault
indication, which does not require an extra power supply.
The protective modules are plug-in versions. No mounting
work required when replacing the protective modules. When
taking insulation measurements, the protective modules are
simply removed, no need to disconnect the surge arrester
from the power supply.
The same protective modules are used as for combination
arresters. This simplifies stock-keeping.

All type 2 surge arresters are available with a remote signaling


contact, which is inserted in the device and does not require
any further space. A remote signaling is always possible, even
in the event of a power failure. The remote signaling signals a
fault even if the protective module is not plugged in.
The protective module is only 12 mm wide and is an outstanding space-saving solution.

Application
Type 2 surge arresters are used after type 1 lightning arresters
in main distribution boards or sub-distribution boards and protect low-voltage systems against overvoltages.
The type 2 surge arrester lowers the level of protection to
1.5 kV.
A thermal isolating arrester disconnector offers a high degree
of protection against overload during runtime.

Selection and ordering data


Mounting
width

Discharge
capacity rated
value/max.
kA

mm (MW)

20/40
20/40

24 (1 1/3)
24 (1 1/3)

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

0.220
0.227

1
1

Surge arresters
2-pole
for TT and TN-S systems
Without remote signaling
With remote signaling

5SD7 422-0
5SD7 422-1

008
008

1
2
3
4
5
6
7
8
9

5SD7 422-0
3-pole
for TN-C systems
Without remote signaling
With remote signaling

20/40
20/40

36 (2)
36 (2)

5SD7 423-0
5SD7 423-1

008
008

0.320
0.330

1
1

10
11

5SD7 423-0
4-pole
for TT and TN-S systems
Without remote signaling
With remote signaling

20/40
20/40

48 (2 2/3)
48 (2 2/3)

5SD7 424-0
5SD7 424-1

008
008

0.408
0.416

1
1

12
13
14

5SD7 424-1

15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

5/5

17

Lightning and Overvoltage Protection Devices


Surge Arresters
Wide version,
requirement category C, type 2, class II

Benefits
Type 2 surge arresters do not require decoupling reactors to
be fitted in the system. This simplifies plant configuration and
reduces space requirements. No time is wasted on planning
the installation of decoupling reactors. This considerably cuts
costs.
The rated arrester voltage is a uniform 350 V AC. This
increases safety in systems with extended voltage overshoots.
All type 2 surge arresters are fitted with a mechanical fault
indication, which does not require an extra power supply.
The protective modules are plug-in versions. No mounting
work required when replacing the protective modules. When
taking insulation measurements, the protective modules are
simply removed, no need to disconnect the surge arrester
from the power supply.

Type 2 surge arresters are available with a remote signaling


contact, which is inserted in the device and does not require
any further space. A remote signaling is always possible, even
in the event of a power failure. The remote signaling signals a
fault even if the protective module is not plugged in.
The width of a protective module is 1 MW. This means that it
can also be rail-mounted with a miniature circuit-breaker or
RCCB.

Application
Type 2 surge arresters are used after type 1 lightning arresters
in main distribution boards or sub-distribution boards and protect low-voltage systems against overvoltages.
The type 2 surge arrester lowers the level of protection to
1.5 kV.
A thermal isolating arrester disconnector offers a high degree
of protection against overload during runtime.

Selection and ordering data


Discharge capacity MW
rated value/max.

Order No.

kA

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

0.114
0.120

1
1

Surge arresters, wide version


1-pole, compact (non plug-in)
Without remote signaling
With remote signaling

20/40
20/40

1
1

5SD7 466-0
5SD7 466-1

008

1-pole, plug-in
Without remote signaling
With remote signaling

20/40
20/40

1
1

5SD7 461-0
5SD7 461-1

008
008

0.130
0.134

1
1

N/PE, 1-pole, plug-in


Without remote signaling

20/40

5SD7 481-0

008

0.131

008

5SD7 466-1

5SD7 461-1

5/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Lightning and Overvoltage Protection Devices


Surge Arresters
Wide version,
requirement category C, type 2, class II
Discharge capacity MW
rated value/max.

Order No.

kA

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

0.393
0.403

1
1

Surge arresters, wide version


3-pole, plug-in, 3+0 circuit
for TN-C systems
Without remote signaling
With remote signaling

20/40
20/40

3
3

5SD7 463-0
5SD7 463-1

008
008

1
2
3
4
5

5SD7 463-1
4-pole, plug-in, 3+1 circuit
for TN-C and TN-S systems
Without remote signaling
With remote signaling

20/40
20/40

4
4

5SD7 464-0
5SD7 464-1

008
008

0.433
0.443

1
1

6
7

5SD7 464-0

8
9
10
11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

5/7

17

Lightning and Overvoltage Protection Devices


Surge Arresters
Multipole,
requirement category D, type 3, class III

Benefits

Application

The protective modules are plug-in versions. No mounting


work required when replacing the protective modules.
All type 3 surge arresters are fitted with a mechanical fault indication, which does not require an extra power supply.
In the event of a power failure, a remote signaling is output
over an optocoupler with open collector output.

Type 3 surge arresters are installed after the type 2 surge


arresters in sub-distribution boards close to the loads in single
or multiphase systems and further limit the overvoltage in
order to protect the connected loads.
Type 3 surge arresters in voltage versions 24, 60, 120 and
240 V can be used in AC and DC systems.

Selection and ordering data


Rated
voltage Un

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

1
1
1
1

Surge arresters, plug-in


2-pole
with remote signaling

V AC, V DC
24
60
120
230

1
1
1
1

5SD7 432-4
5SD7 432-3
5SD7 432-2
5SD7 432-1

008
008
008
008

0.027
0.026
0.081
0.071

V AC
230/400

5SD7 434-1

008

0.056

5SD7 432-1
4-pole
with remote signaling

5/8

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Lightning and Overvoltage Protection Devices


Surge Protection Adapters
Requirement category D, type 3, class III

Benefits

Application

All type 3 surge protection adapters are fitted with an LED as


a visual status and fault indication.
The protection circuit is continuously thermally monitored. This
ensures constant safe operation for the operator.
The attractive design fits well into residential living spaces.

Type 3 surge protection adapters for insertion in a 5


socket outlet protect electronic loads against overvoltages
from main power supplies.
However, overvoltages do not just reach loads over power
cables. Telecommunication devices for TAE, ISDN/RDS and
RJ12 connection, televisions or radios with aerial connection
or satellite radio connection are all connected to a further
power supply system which may also pass overvoltages on to
devices.

Selection and ordering data


Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Surge protection adapters


for line contactor

5SD7 435-0

008

0.115

for telecommunication devices/TAE

5SD7 435-2

008

0.156

1
2
3
4
5
6
7
8
9

for ISDN/RDSI

5SD7 435-3

008

0.156

10
11
for TV/radio

5SD7 435-5

008

0.156

12
13
for telecommunication devices/RJ12

5SD7 435-6

008

0.144

14
for SAT installations

5SD7 435-7

008

0.156

15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

5/9

17

Lightning and Overvoltage Protection Devices


Accessories
For lightning and overvoltage protection devices

Selection and ordering data


Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Through-type terminals
5SD7 490-1

008

0.191

5SD7 418-1

008

0.240

5SD7 418-0

008

0.240

5SD7 448-1
5SD7 418-0

008
008

0.129
0.240

1/100
1

5SD7 428-1

008

0.052

5SD7 428-0

008

0.049

for 5SD7 46. surge arresters, requirement category C,


type 2, class II
Surge arresters L/N
Surge arresters N/PE

5SD7 468-1
5SD7 488-0

008
008

0.051
0.040

1
1

for surge arresters, wide version, 2-pole, 5SD7 432-.,


requirement category D, type 3, class III
Rated voltage Un = 230 V
Rated voltage Un = 120 V
Rated voltage Un = 60 V
Rated voltage Un = 24 V

5SD7 437-1
5SD7 437-2
5SD7 437-3
5SD7 437-4

008

008

0.028
0.027
0.026
0.027

1
1
1
1

5SD7 438-1

008

0.162

for simple wiring in various wiring versions

Connectors

5SD7 418-0

for 5SD7 41. lightning arresters,


requirement category B, type 1, class I
Lightning arresters L/N Ifi 50 kAeff
for 5SD7 41 lightning arresters.
Lightning arresters N/PE
for 5SD7 41. lightning arresters and
5SD7 44. arrester combinations.
for 5SD7 44. arrester combinations, requirement
category B, type 1, class I
Lightning arresters L/N Ifi 25 kAeff
Lightning arresters N/PE
for 5SD7 41. lightning arresters and
5SD7 44. arrester combinations.

5SD7 448-1
for 5SD7 42. surge arresters and 5SD7 44. arrester combinations, requirement category C, type 2, class II
Surge arresters L/N
for 5SD7 42. surge arresters and
5SD7 44. arrester combinations.
Surge arresters N/PE
5SD7 428-1

5SD7 468-1

5SD7 437-1

for surge arresters, wide version, 4-pole, 5SD7 434-1,


requirement category D, type 3, class III

008
008

For busbars for lightning and overvoltage protection devices,


see chapter "Busbars for modular installation devices"

5/10

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Switches and
Light Indicators

6/2

Introduction

6/3

5TE8 control switches

6/5

5TE4 8 pushbuttons

6/7

5TE5 8 light indicators

6/8

5TE8 ON/OFF switches

6/11

5TE1 switch disconnectors

6/1

Switches and Light Indicators


Introduction

Overview
Usage

Industry

Standards

Res. buildings

Application

Non-res. buildings

Devices

IEC 60947-3, EN 60947-3


(VDE 0660 Part 107)
IEC 60669-1, EN 60669-1
(VDE 0632 Part 1)
GB14048.3-2002 CCC

To be used as pushbuttons in
control systems, e.g. to switch on
seal-in circuits or as pushbuttons
with maintained-contact function
for manual use, as control
switches or for the switching of
loads

IEC 60947-3, EN 60947-3


(VDE 0660 Part 107)
IEC 60669-1, EN 60669-1
(VDE 0632 Part 1)
GB14048.3-2002 CCC

--

Optical signaling in installations


and control circuits to indicate
switching states or faults

DIN VDE 0710-1

--

--

5TE8 control switches


5TE8 two-way switches
For the switching of lighting,
20 A
motors and other electrical
5TE8 group switches with center position, devices
20 A
5TE8 control switches
20 A

For the application of logical links


in control cabinets

5TE4 8 pushbuttons
5TE4 8 pushbuttons
with/without maintained-contact function

Light indicators
5TE5 8 light indicators

5TE8 ON/OFF switches


5TE8 On/Off switches
20 A ... 125 A

For the application of logical links 16 A ... 25 A and 40 A ... 100 A:


in control cabinets
IEC 60947-3, EN 60947-3
(VDE 0660 Part 107)
IEC 60669-1, EN 60669-1
(VDE 0632 Part 1)
32 A and 125 A:
IEC 60947-3, EN 60947-3
(VDE 0660 Part 107)
GB14048.3-2002 CCC

5TE1 switch disconnectors


5TE1 switch disconnectors
100 A ... 200 A

Definitions
Ie = Rated operational current
Ue = Rated operational voltage
Ic = Rated control current
Uc = Rated control voltage
Ps = Rated operational power
1 MW =Modular width 18 mm

6/2

Siemens ET B1 2007

For the switching of system com- IEC 60947-3, EN 60947-3,


ponents
KEMA certified,
UL 508

Switches and Light Indicators


5TE8 control switches

Overview
Two-way switches ON/OFF switches
Group switches
with center
position
Control switches
20 A

20 A and 32 A

32 ... 63 A

80 ... 125 A

Sealable switch position


Mountable auxiliary switch

5TE8 151
5TE8 161

Position indication red/green

--

--

Optional: red handle (instead of gray)

--

--

Order No.

Price

Separate handle locking device

Ue

Ie

Conductor
crosssections

V AC

up to mm2

MW

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Two-way switches (20 A)


with separate handle locking device, sealable switch position,
mountable auxiliary switch
1 NO contact, 1 NC contact

5TE8 151

3
4
5

Selection and ordering data


Version

1
2

400

20

5TE8 151

027

0.062

1/12

2 NO contacts, 2 NC contacts
auxiliary switch cannot be mounted
400

20

5TE8 152

027

0.081

1/12

3 NO contacts, 1 NC contact
auxiliary switch cannot be mounted
400

20

5TE8 153

027

0.082

1/120

230

20

5TE8 161

027

0.060

1/12

2 CO contacts
auxiliary switch cannot be mounted
400

20

5TE8 162

027

0.076

1 CO contact

6
7
8
9
10

5TE8 162
Group switches with center position (20 A)

11

max. mounting depth of 73.5 mm in center position,


with separate handle locking device, sealable switch position,
auxiliary switch cannot be mounted
1 CO contact
230

20

5TE8 141

027

0.060

1/12

400

20

5TE8 142

027

0.077

1/12

2 CO contacts

12

5TE8 141

13

Control switches (20 A)


with fixed mounted 230 V glow lamp or 48 V diode,
replaceable, white luminescent cap,
separate handle locking device, sealable switch position,
auxiliary switch cannot be mounted
1 NO contact
230
48

20
20

6
6

1
1

5TE8 101
5TE8 101-3

027
027

0.057
0.057

1/12
1/120

230

20

5TE8 105

027

0.057

400

20

5TE8 102

027

0.066

1/12

400

20

5TE8 103

027

0.078

1/12

1.5

5TE8 108

027

0.128

1/80

1 NO contact
for max. 150 m cable length
5TE8 101
2 NO contacts
3 NO contacts
3 NO contacts with mounted auxiliary switch
(1 NO contact, 1 NC contact)
400
20

5TE8 108

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

6/3

14
15
16
17

Switches and Light Indicators


5TE8 control switches

Accessories
Version

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Auxiliary switches (AS)


for all 5TE8 switches,
for right-side retrofitting with factory-fitted brackets,
for further technical specifications, see also Section,
"Miniature circuit-breakers"
1 NO contact + 1 NC contact

0.5

5ST3 010

027

0.050

2 NO contacts
2 NC contact

0.5
0.5

5ST3 011
5ST3 012

027
027

0.050
0.050

1
1

5ST3 801

027

0.008

5TG8 240

027

0.010

5ST3 010
Handle locking devices
for all 5TE8 switches,
can be sealed against unwanted manual ON/OFF switching,
for padlock with max. 3 mm shackle

Spacers
Contour for modular devices with a mounting depth of 70 mm;
can be snapped onto either side of the busbar, so that two
spacers allow for convenient cable routing
0.5

1 set

Cap sets
for manual changing of the luminous plates for 5TE8 10
control switches
Cap set comprising 1 red, green, and yellow plate each

5TG8 068

027

0.006

1 set/
30 units

For busbars for control switches, see chapter "Busbars for modular
installation devices".

6/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Switches and Light Indicators


5TE4 8 pushbuttons

Selection and ordering data


Version

Ue

Ie

V AC

Conductor
crosssections
up to mm2

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Pushbuttons without maintained-contact function


1 NO contact, 1 NC contact
1 gray pushbutton

230

20

5TE4 800

027

0.061

230

20

5TE4 804

027

0.053

1 NO contact, 1 NC contact
1 red pushbutton

230

20

5TE4 805

027

0.061

1 NO contact, 1 NC contact
1 green pushbutton

230

20

5TE4 806

027

0.061

1 NO contact, 1 NC contact
1 yellow pushbutton

230

20

5TE4 807

027

0.061

1 NO contact, 1 NC contact
1 blue pushbutton

230

20

5TE4 808

027

0.061

1 NO contact, 1 NC contact
1 green pushbutton,
1 blue pushbutton

5TE4 800

Pushbuttons with maintained-contact function


1 NO contact, 1 NC contact
1 gray pushbutton

230

20

5TE4 810

027

0.060

2 NO contacts
1 gray pushbutton

400

20

5TE4 811

027

0.061

3 NO contacts + N
1 gray pushbutton

400

20

5TE4 812

027

0.080

4 NC contacts
1 gray pushbutton

400

20

5TE4 813

027

0.080

2 CO contacts
1 gray pushbutton

400

20

5TE4 814

027

0.075

Control pushbuttons with maintained-contact function


or momentary-contact function and lamp, 230 V
for max. 5 m cable length

5TE4 820

1 NO contact, 1 NC contact
1 red pushbutton

400

20

5TE4 820

027

0.071

1 NO contact
1 red pushbutton

230

20

5TE4 821

027

0.078

2 NO contacts
1 red pushbutton

400

20

5TE4 823

027

0.080

2 NC contacts
1 red pushbutton

400

20

5TE4 824

027

0.080

5TE4 822

027

0.078

5TE4 830

027

0.065

5TE4 831

027

0.084

Control pushbuttons with maintained-contact function


or momentary-contact function and lamp, 230 V
for max. 150 m cable length
1 NO contact
1 red pushbutton

400

20

Double pushbuttons with maintained-contact function and/or


momentary-contact function
1 NO contact and 1 NC contact
1 red pushbutton,
400
20
6
1
1 green pushbutton
1 NO contact, 1 NC contact and 1 NO contact, 1 NC contact
1 red pushbutton,
400
20
6
1 green pushbutton

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

5TE4 830

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

6/5

17

Switches and Light Indicators


5TE4 8 pushbuttons
Version

Ue

Ie

V AC

Conductor
cross-sections
up to mm2

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Double pushbuttons with maintained-contact function


and/or momentary-contact function and two lamps, 230 V
for max. 5 m cable length
1 NO contact and 1 NO contact
1 red pushbutton,
400
1 green pushbutton

20

5TE4 840

027

0.080

1 NO contact and 1 NC contact


1 red pushbutton,
400
1 green pushbutton

20

5TE4 841

027

0.080

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

5TE4 840

Accessories
Version

Ue

Order No.

1 unit

Unit(s)

Lamps, manually removable for voltages other than 230 V or


as spare lamps with inscription label
LED
12 AC/DC

5TG8 050

027

0.001

1/10

LED
LED

24 AC/DC
48 AC/DC

5TG8 051
5TG8 052

027
027

0.001
0.001

1/10
1/10

LED

60 AC/DC

5TG8 053

027

0.001

1/10

glow lamp

115 AC
110 DC
230 AC
220 DC

5TG8 054

027

0.001

1/10

5TG8 055

027

0.001

1/10

5TG8 050
glow lamp

5TG8 060

Price

1 set

Cap sets, manually replaceable with colored caps


with or without lamps
gray, non-transparent (1 set = 5 units)

5TG8 060

027

0.002

red, transparent (1 set = 5 units)

5TG8 061

027

0.002

green, transparent (1 set = 5 units)

5TG8 062

027

0.002

yellow, transparent (1 set = 5 units)

5TG8 063

027

0.002

blue, transparent (1 set = 5 units)

5TG8 064

027

0.002

black, non-transparent (1 set = 5 units)

5TG8 065

027

0.002

1 set/
10 sets

white, transparent (1 set = 5 units)

5TG8 066

027

0.002

red and green (1 set contains 10 lamps per color),


yellow, blue and white (1 set contains 5 lamps per color)

5TG8 067

027

0.012

1 set/
10 sets
1 set/
10 sets

red, green, yellow (1 set = 3 units)

5TG8 070

027

0.002

1 set/
10 sets
1 set/
10 sets
1 set/
10 sets
1 set/
10 sets
1 set/
10 sets

1 set/
10 sets

5TG8 061

6/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Switches and Light Indicators


5TE5 8 light indicators

Selection and ordering data


Ue

Conductor
MW Order No.
cross-sections

Price

V AC

up to mm2

1 unit

PG

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Light indicators for a max. cable length of up to 5 m


with 1 red lamp
with 2 lamps, red and green
with 3 green lamps

230

5TE5 800
5TE5 801
5TE5 802

027
027
027

0.060
0.056
0.063

1/12
1
1

5TE5 804

027

0.060

230

3
4
5

Light indicators for a max. cable length of up to 250 m


with 1 red lamp

1
2

6
7
Accessories
Ie

Ue

Order No.

mA

0.4

12 AC/DC
24 AC/DC

5TG8 050
5TG8 051

LED
LED

48 AC/DC
60 AC/DC

Glow lamp
Glow lamp

Price

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

027
027

0.001
0.001

1/10
1/10

5TG8 052
5TG8 053

027
027

0.001
0.001

1/10
1/10

115 AC
110 DC

5TG8 054

027

0.001

1/10

230 AC
220 DC

5TG8 055

027

0.001

1/10

red, transparent (1 set = 5 units)

5TG8 061

027

0.002

1 set/
10 sets

green, transparent (1 set = 5 units)

5TG8 062

027

0.002

yellow, transparent (1 set = 5 units)

5TG8 063

027

0.002

1 set/
10 sets
1 set/
10 sets

blue, transparent (1 set = 5 units)

5TG8 064

027

0.002

white, transparent (1 set = 5 units)

5TG8 066

027

0.002

red and green (1 set = 10 lamps per color),


yellow, blue and white (1 set = 5 lamps per color)

5TG8 067

027

0.012

1 set/
10 sets

red, green, yellow (1 set = 3 units)

5TG8 070

027

0.002

1 set/
10 sets

1 unit

Lamps, manually removable for voltages other


than 230 V or as spare lamps with inscription
label
LED
LED

5TG8 050

1 set

Cap sets for manual changing of colored caps

5TG8 061

Unit(s)

1 set/
10 sets
1 set/
10 sets

9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

6/7

17

Switches and Light Indicators


5TE8 ON/OFF switches

Selection and ordering data


Version

Ue

Ie

V AC

Conductor
crosssections
up to mm2

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

ON/OFF switches (20 A and 32 A)


with separate handle locking device, sealable switch position,
auxiliary switch can be mounted
1 NO contact
230
20
6
32

5TE8 111
5TE8 211

027
027

0.053
0.053

1/12
1

2 NO contacts

5TE8 111

400

20
32

5TE8 112
5TE8 212

027
027

0.062
0.062

1/12
1/12

400

20
32

5TE8 113
5TE8 213

027
027

0.072
0.072

1/12
1/12

20
32

5TE8 114
5TE8 214

027
027

0.082
0.081

1/120
1/120

20
32

1.5

5TE8 118
5TE8 218

027
027

0.128
0.128

1/80
1/80

5TE8 521
5TE8 721
5TE8 311
5TE8 411
5TE8 511

027
027
027
027
027

0.100
0.112
0.100
0.100
0.100

1/120
1/120
1/12
1/12
1/120

5TE8 611
5TE8 711
5TE8 811

027
027
027

0.112
0.112
0.112

1/12
1/120
1/120

5TE8 522
5TE8 722

027
027

0.204
0.225

1/6
1/60

5TE8 312
5TE8 412
5TE8 512
5TE8 612
5TE8 712
5TE8 812

027
027
027
027
027
027

0.204
0.204
0.204
0.225
0.225
0.225

1/6
1/6
1/60
1/6
1/6
1/60

5TE8 523
5TE8 723

027
027

0.307
0.338

1/40
1/40

3 NO contacts

3 NO contacts + N
auxiliary switch cannot be mounted
400
3 NO contacts + N
with mounted auxiliary switch
400

5TE8 218
ON/OFF switches (32 A to 125 A)
can be used as switch disconnector acc. to EN 60947-1
with separate handle locking device, sealable switch position,
auxiliary switch, can be mounted, position indication red/green
1 NO contact, red handle

230

1 NO contact

5TE8 511
2 NO contacts, red handle

400

2 NO contacts

5TE8 514

3 NO contacts, red handle

400

3 NO contacts

3 NO contacts + N,
red handle
3 NO contacts + N

4 NO contacts

6/8

Siemens ET B1 2007

400

63
100
32
40
63

35
50
35

80
100
125

50

63
100

35
50

32
40
63
80
100
125

35

50

63
100

35
50

32
40
63

35

5TE8 313
5TE8 413
5TE8 513

027
027
027

0.307
0.307
0.307

1/40
1/40
1/40

80
100
125

50

5TE8 613
5TE8 713
5TE8 813

027
027
027

0.340
0.338
0.338

1/4
1/4
1/40

63

35

5TE8 524

027

0.413

1/30

100
32
40
63

50
35

5TE8 724
5TE8 314
5TE8 414
5TE8 514

027
027
027
027

0.445
0.410
0.410
0.413

1/30
1/30
1/3
1/3

80
100
125

50

5TE8 614
5TE8 714
5TE8 814

027
027
027

0.455
0.445
0.455

1/30
1/3
1/30

32
40
63
80
100
125

35

5TE8 315
5TE8 415
5TE8 515
5TE8 615
5TE8 715
5TE8 815

027
027
027
027
027
027

0.413
0.413
0.413
0.455
0.455
0.455

1
1
1
1
1
1

50

* You can order this quantity or a multiple thereof.

Switches and Light Indicators


5TE8 ON/OFF switches
Version

Ue

Ie

V AC

Conductor
crosssections
up to mm2

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

0.263

1/40

Unit(s)

ON/OFF switches 63 A
can be used as switch disconnector acc. to EN 60947-1
Terminal access from the bottom and off-position lockable with
special key (exclusive power supply company tool). Reduced lower terminal entry for conductors with approx. 7 mm diameter
3 NO contacts
400
63
35
3
5TE8 533

027

1
2
3
4
5

5TE8 533

Accessories
Version

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Auxiliary switches (AS)


for all 5TE8 switches,
for right-side retrofitting with factory-fitted brackets,
for further technical specifications, see also Section
"Miniature circuit-breakers"
1 NO contact + 1 NC contact

0.5

5ST3 010

027

0.050

2 NO contacts

0.5

5ST3 011

027

0.050

2 NC contacts

0.5

5ST3 012

027

0.050

5ST3 801

027

0.008

5ST3 010
Handle locking devices
for all 5TE8 switches,
can be sealed against unwanted manual ON/OFF switching,
padlock with max. 3 mm shackle

6
7
8
9
10

Terminal covers
for all 5TE8 5 to 5TE8 8 switches,
in 1 MW per pole version,
for covering screw openings,
sealable

5ST3 800

027

0.001

5/10

5TG8 240

027

0.010

11

Spacers

12

contour for modular devices with a mounting depth of 70 mm;


can be snapped onto either side of the busbar, so that two
spacers allow for convenient cable routing
0.5

13
Fixpoint terminals
with snap-on mounting for mounting on standard mounting rail and
lateral cable entry,
can also be used as RCCB terminal,
with 3 terminals for cables of 1.5 mm2 to 10 mm2 and
1 terminal for cables of 1.5 mm2 to 25 mm

8GB4 576

032

0.026

5ST2 112

027

0.008

1/50

Snap-on terminals
with snap-on mounting for mounting on the standard mounting
rail with terminals for conductors up to 16 mm2 solid and
10 mm2 stranded

* You can order this quantity or a multiple thereof.

14
15
16

Siemens ET B1 2007

6/9

17

Switches and Light Indicators


5TE8 ON/OFF switches
Version

Ue

Ie

V AC

Conductor
crosssections
up to mm2

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Phase connectors
for easier wiring in various wiring versions
and busbar mountings or as a fixpoint terminal for conductors from
2.5 mm2 to 50 mm2
1-pole
230
125
50
1

5TE9 112

027

0.111

5TE9 113

027

0.111

N-conductor connectors
for easier wiring in various wiring versions
and busbar mountings or as a fixpoint terminal for N-conductors from
2.5 mm2 to 50 mm2
1-pole

6/10

Siemens ET B1 2007

230

125

50

* You can order this quantity or a multiple thereof.

Switches and Light Indicators


5TE1 switch disconnectors

Overview
From 160 A: supplied with one terminal cover
160 A and 200 A: version for connection with cable lug

Installation on standard mounting rail according to EN 60715,


which is raised at least 5 mm from the base plate
Screw connection on base plate.

Selection and ordering data


Version

Ue

Ie

MW

Order No.

V AC
A
Switch disconnectors, lockable,
with gray knob and transparent enclosure,
mounting depth 92 mm

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

2 NO contacts
690

100
125

5TE1 210
5TE1 220

027
027

0.480
0.480

1
1

160
200

5TE1 230
5TE1 240

027
027

0.620
0.620

1
1

100
125

5TE1 310
5TE1 320

027
027

0.540
0.540

1
1

160
200

5TE1 330
5TE1 340

027
027

0.730
0.730

1
1

100
125
160
200

5TE1 410
5TE1 420
5TE1 430
5TE1 440

027
027
027
027

0.590
0.590
0.770
0.770

1
1
1
1

3 NO contacts with N-conductor through-type terminal


690
100
5
125
160
8
200

5TE1 610
5TE1 620
5TE1 630
5TE1 640

027
027
027
027

0.590
0.590
0.770
0.770

1
1
1
1

Switch disconnectors with red knob and yellow cap,


can be used as emergency system interrupter according
to IEC 60204-1, EN 60204-1 (VDE 0113 Part 1)
if switch is easily accessible, mounting depth 92 mm
3 NO contacts
690
100
5
125

5TE1 315
5TE1 325

027
027

0.540
0.540

1
1

3 NO contacts
690
5TE1 210

4 NO contacts
690

160
200

5TE1 335
5TE1 345

027
027

0.730
0.730

1
1

100
125
160
200

5TE1 415
5TE1 425
5TE1 435
5TE1 445

027
027
027
027

0.590
0.590
0.770
0.770

1
1
1
1

4 NO contacts
690
5TE1 315

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

6/11

17

Switches and Light Indicators


5TE1 switch disconnectors

Accessories
Version

Ue

Ie

V AC

A AC

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Terminal covers
for 100 A and 125 A switch disconnectors; sealable

5TE9 000

027

0.060

for 160 A and 200 A switch disconnectors; sealable

5TE9 001

027

0.050

5TE9 000

5TE9 001
1 set

Cage Clamp terminals


for switch disconnectors 160 A and 200 A
terminal diameter 14.5 mm for 92 mm2 cables
5 mm Allen screw
5TE9 003
Set comprising three Cage Clamp terminals

5TE9 003

027

0.080

1 set

Set comprising four Cage Clamp terminals

5TE9 004

027

0.080

1 set

Auxiliary switches
Auxiliary switches optionally mountable left or
right or both sides (2 units)
minimum contact load 24 V, 50 mA
1-pole CO contact

230

5TE9 005

027

0.080

2-pole CO contact

230

5TE9 006

027

0.080

5TE9 014

027

0.230

200 mm
400 mm

5TE9 010
5TE9 011

027
027

0.550
0.550

1
1

200 mm
400 mm

5TE9 012
5TE9 013

027
027

0.550
0.550

1
1

5TE9 005
Locking units
for up to three padlocks with max. 8 mm

Rotary actuators with extension axes for mounting


on hinged doors or enclosure lids, lockable, IP65
Black knob
Shaft length
5TE9 01.

6/12

Red knob
Shaft length

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Switching Devices

7/2

Product overview

7/3

5TT4 1 remote control switches

7/4

5TT4 2 switching relays

7/5

5TT5 7 Insta contactors

7/6

5TT5 8 Insta contactors

7/8

5TT3 4 soft-starting devices

7/9

5TT5 2 EMERGENCY-STOP modules

7/1

Switching Devices
Product overview

Application

Standards

Res. buildings

Industry

Devices

Non-res. buildings

Overview
Usage

Switching of lighting by pushbutton

EN 60669 (VDE 0632),


EN 60669-2-2 and
EN 60669-2-2/A1

--

---

--

Switching of small loads or application


in control systems

EN 60947-4-1
(VDE 0660 Part 102)

--

Switching of motors, heating or lighting,


such as fluorescent lamps or incandescent lamps, and resistive and inductive loads

IEC 60947-4-1,
IEC 60947-5-1, IEC 61095,
EN 60947-4-1,
EN 60947-5-1,
EN 61095,
VDE 0660,
UL 508

Protection of machines with transmission, belt or chain drives, conveyor


belts, fans, pumps, compressors,
packing machines, door operating
mechanisms

EN 60947-4-2,
(VDE 0660 Part 117)

--

--

--

--

--

5TT4 1 remote control switches


Without central switching
With central switching
Shutter/blind and series remote control
switches

5TT4 2 switching relays


For PLCs

Insta contactors
5TT5 7
5TT5 8 without manual switching option
5TT5 8 with manual switching option

Soft-starting devices
5TT3 441, 230 V AC
5TT3 440, 400 V AC

>N-type< EMERGENCY-STOP modules


5TT5 200, 10 A

Definitions
Ie
= Rated operational current
Ue = Rated operational voltage
= Rated control current
Ic
Uc = Rated control voltage
Ps = Rated operational power
1 MW= Modular width 18 mm

7/2

Siemens ET B1 2007

EMERGENCY-STOP switching of
Acc. to the EC Machine
machines in industrial, commercial and directive for machines
private economic applications
98/37/EG, EN 954-1

Switching Devices
5TT4 1 remote control switches

Selection and ordering data


Contacts

Ue

Ie

Uc

MW

V AC

A AC

V AC

1 NO contact

250

16

2 NO contacts

400

16

230
115
24
12
8
230
115
24
12
8

3 NO contacts

400

16

230
24

4 NO contacts

400

16

230
24
230
115
24
12
8

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Remote control switches

1 NO contact + 1 NC contact

250

16

5TT4 101-0
5TT4 101-1
5TT4 101-2
5TT4 101-3
5TT4 101-4
5TT4 102-0
5TT4 102-1
5TT4 102-2
5TT4 102-3
5TT4 102-4

027
027
027
027
027
027
027
027
027
027

0.126
0.120
0.121
0.118
0.124
0.132
0.132
0.132
0.130
0.136

1/12
1
1
1
1
1
1
1
1
1

5TT4 103-0
5TT4 103-2

0.200
0.195

1
1

5TT4 104-0
5TT4 104-2
5TT4 105-0
5TT4 105-1
5TT4 105-2
5TT4 105-3
5TT4 105-4

027
027
027

0.211
0.206
0.137
0.131
0.132
0.129
0.135

1
1
1
1
1
1
1

027
027
027
027
027
027

Remote control switches with central switching


2 NO contacts
400
16

230

1.5

5TT4 122-0

400

16

230

2.5

5TT4 123-0

027
027

0.181

3 NO contacts

0.194

1 NO contact + 1 NC contact

250

16

230

1.5

5TT4 125-0

027

0.182

250

16

230

5TT4 132-0

027

0.130

3
4
5
6
7
8

Series remote control switches


Contact sequence 1 + 2 2 1 0
2 NO contacts

1
2

9
10

Shutter/blind remote control switches


Contact sequence 1 0 2 0
2 NO contacts

250

16

230
24
12

5TT4 142-0
5TT4 142-2
5TT4 142-3

027
027
027

0.138
0.132
0.130

1
1
1

250
30

5
0.1

--

0.5

5TT4 900
5TT4 901

027
027

0.032
0.054

1
1

11
12

Auxiliary switches
1 CO contact
1 CO contact
for small output

13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

7/3

17

Switching Devices
5TT4 2 switching relays

Selection and ordering data


Version

Ue

Ie

Uc

MW

Order No.

V AC

A AC

V AC

1 NO contact

250

16

230
115
24
12
8

5TT4 201-0
5TT4 201-1
5TT4 201-2
5TT4 201-3
5TT4 201-4

2 NO contacts

400

16

230
115
24
12
8

4 NO contacts

400

16

230
115

Price

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

027
027
027
027
027

0.126
0.120
0.120
0.118
0.124

1/12
1
1
1
1

5TT4 202-0
5TT4 202-1
5TT4 202-2
5TT4 202-3
5TT4 202-4

027
027
027
027
027

0.137
0.131
0.131
0.129
0.135

1
1
1
1
1

5TT4 204-0
5TT4 204-1

027
027

0.250
0.257

1
1

5TT4 204-2
5TT4 204-3
5TT4 204-4

027
027
027

0.253
0.250
0.245

1
1
1

5TT4 205-0
5TT4 205-1

027
027

0.137
0.131

1
1

5TT4 205-2
5TT4 205-3
5TT4 205-4

027
027
027

0.131
0.129
0.135

1
1
1

5TT4 206-0
5TT4 206-1

027
027

0.127
0.121

1
1

5TT4 206-2
5TT4 206-3
5TT4 206-4

027
027
027

0.122
0.120
0.125

1
1
1

5TT4 207-0
5TT4 207-1
5TT4 207-2

027
027
027

0.140
0.134
0.135

1
1
1

5TT4 207-3
5TT4 207-4

027
027

0.133
0.138

1
1

1 unit

Unit(s)

Switching relays

5TT4 201-0

24
12
8
1 NO contact +
1 NC contact

400

16

230
115

24
12
8
1 CO contact

250

16

230
115

24
12
8
2 CO contacts

400

16

230
115
24
12
8

7/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Switching Devices
5TT5 7 Insta contactors

Selection and ordering data


Version

Ue

Ie

Uc

MW

V AC

A AC

V AC

V DC

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Insta contactors
for AC or DC continuous operation,
with switch position indication,
with DC magnetic system

5TT5 730-0

5TT5 740-0

4 NO contacts

440

24

230
115
24

220
110
24

5TT5 730-0
5TT5 730-1
5TT5 730-2

027
027
027

0.247
0.247
0.247

1
1
1

3 NO contacts,
1 NC contact

440

24

230

220

5TT5 731-0

027

0.247

2 NO contacts,
2 NC contacts

440

24

24
230

24
220

5TT5 731-2
5TT5 732-0

027
027

0.247
0.247

1
1

24

24

5TT5 732-2

027

0.247

4 NC contacts

440

24

230
24

220
24

5TT5 733-0
5TT5 733-2

027
027

0.247
0.247

1
1

4 NO contacts

440

40

440

401)

220
24
220

3 NO contacts,
1 NC contact

230
24
230

5TT5 740-0
5TT5 740-2
5TT5 741-0

027
027
027

0.410
0.410
0.410

1
1
1

24

24

2 NO contacts,
2 NC contacts

440

401)

230

220

5TT5 741-2

027

0.410

5TT5 742-0

027

0.410

24
220
24

5TT5 742-2
5TT5 750-0
5TT5 750-2

027
027
027

0.410
0.410
0.410

1
1
1

5TT5 751-0

027

0.410

5TT5 751-2

027

0.410

5TT5 752-0

027

0.410

5TT5 752-2

027

0.410

5TT5 900
5TT5 901

027
027

0.039
0.039

1
1

4 NO contacts

440

63

24
230
24

3 NO contacts,
1 NC contact

440

631)

230

220

24

24

230

220

24

24

2 NO contacts,
2 NC contacts

440

631)

Auxiliary switches
for left-sided mounting on the 24 A, 40 A and 63 A Insta contactors
max. one auxiliary switch per Insta contactor.
minimum contact load 24 V AC; 5 mA
2 NO contacts
1 NO contact,
1 NC contact

230, AC-15
230, AC-15

4
4

0.5
0.5

1
2
3
4
5
6
7
8
9
10
11

5TT5 900
Spacers
for heat dissipation between the Insta contactors. We
recommend placing a spacer between each second Insta
contactor.
Can be mounted reciprocally, so that two spacers enable
greater cable penetration

0.5

5TG8 240

027

0.010

13

5TG8 240

5TT5 903
1)

12

Sealable terminal covers


for Insta contactors 24 A, (1 set = 2 units)

5TT5 902

027

1 set
0.010

for Insta contactors 40 A and 63 A, (1 set = 2 units)

5TT5 903

027

0.010

1 set/
25 sets
1 set/
25 sets

For NC contacts 30 A.

14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

7/5

17

Switching Devices

5TT5 8 Insta contactors

Selection and ordering data


Version

Ue

Ie

Uc

V AC

A AC

V AC

MW

Order No.

Price

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

0.130
0.130

1
1

027
027
027

0.130
0.130
0.130
0.130

1
1
1
1

5TT5 830-0
5TT5 830-1
5TT5 830-2

027
027
027

0.230
0.230
0.230

1
1
1

1 unit

Unit(s)

Insta contactors without manual switching


for alternating current continuous operation, with switch position
indication, with alternating current magnetic system
2 NO contacts
250
20
230
24
1 NO contact, 1 NC contact

250

20

230
24
230
24

5TT5 800-0
5TT5 800-2
5TT5 801-0
5TT5 801-2
5TT5 802-0
5TT5 802-2

027
027
027

2 NC contacts

250

20

4 NO contacts

440

25

230
115
24

3 NO contacts, 1 NC contact

440

25

230
115
24

5TT5 831-0
5TT5 831-1
5TT5 831-2

027
027
027

0.230
0.230
0.230

1
1
1

2 NO contacts, 2 NC contacts

440

25

4 NC contacts

440

25

230
24
230
24

5TT5 832-0
5TT5 832-2
5TT5 833-0
5TT5 833-2

027
027
027
027

0.230
0.230
0.230
0.230

1
1
1
1

4 NO contacts

440

40

3 NO contacts, 1 NC contact

440

40

5TT5 840-0
5TT5 840-2
5TT5 841-0
5TT5 841-2

027
027
027
027

0.380
0.380
0.380
0.380

1
1
1
1

2 NO contacts, 2 NC contacts

440

40

230
24

5TT5 842-0
5TT5 842-2

0.380
0.380

1
1

4 NC contacts

440

40

230
24
230
24

5TT5 843-0
5TT5 843-2
5TT5 850-0
5TT5 850-2

027
027
027
027
027
027

0.380
0.380
0.380
0.380

1
1
1
1

5TT5 800-0

5TT5 830-0

5TT5 840-0

230
24
230
24

4 NO contacts

440

63

3 NO contacts, 1 NC contact

440

63

230
24

5TT5 851-0
5TT5 851-2

027
027

0.380
0.380

1
1

2 NO contacts, 2 NC contacts

440

63

4 NC contacts

440

63

230
24
230
24

5TT5 852-0
5TT5 852-2
5TT5 853-0
5TT5 853-2

027
027
027
027

0.380
0.380
0.380
0.380

1
1
1
1

5TT5 910-0

027

0.030

5TT5 910-1

027

0.030

5TT5 910-5
5TT5 910-6
5TT5 910-7

027
027
027

0.002
0.003
0.004

2
2
2

Auxiliary switches
for mounting on right-hand side
max. one auxiliary switch per Insta contactor.
2 NO contacts
230,
AC-15
1 NO contact, 1 NC contact

230,
AC-15

--

--

0.5

5TT5 910-0
Sealable terminal covers
for Insta contactor 20 A
for Insta contactor 24 A
for Insta contactors 40 A and 63 A

7/6

Siemens ET B1 2007

1
2
3

* You can order this quantity or a multiple thereof.

Switching Devices

N
Version

Ue

Ie

Uc

V AC

A AC

V AC

5TT5 8 Insta contactors


MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Insta contactors with manual switching 0/I/Automatic


for alternating current continuous operation, with switch position
indication, with alternating current magnetic system
2 NO contacts
250
20
230
24
1 NO contact,
1 NC contact

250

20

5TT5 800-6
5TT5 800-8

027
027

0.135
0.135

1
1

230

5TT5 801-6

027

0.135

24

5TT5 801-8

027

0.135

5TT5 830-6
5TT5 830-8
5TT5 831-6

072
027
027

0.235
0.235
0.235

1
1
1

5TT5 831-8

027

0.235

5TT5 800-6
4 NO contacts

440

25

3 NO contacts,
1 NC contact

440

25

230
24
230

24

5TT5 830-6
4 NO contacts

440

40

3 NO contacts,
1 NC contact

440

40

4 NO contacts

440

63

5TT5 840-6
5TT5 840-8
5TT5 841-6

027
027
027

0.390
0.390
0.390

1
1
1

24

5TT5 841-8

027

0.390

230

5TT5 850-6

027

0.390

5TT5 910-0

027

0.030

5TT5 910-1

027

0.030

230
24
230

5TT5 840-6
Auxiliary switches
for mounting on right-hand side
max. one auxiliary switch per Insta contactor.
2 NO contacts

230, AC-15 6

--

1 NO contact,
1 NC contact

230, AC-15 6

--

0.5

1
2
3
4
5
6
7
8
9
10

5TT5 910-0
Sealable terminal covers
for Insta contactor 20 A
for Insta contactor 25 A
for Insta contactors 40 A
and 63 A

1
2
3

5TT5 910-5
5TT5 910-6
5TT5 910-7

027
027
027

0.002
0.003
0.004

2
2
2

11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

7/7

17

Switching Devices
5TT3 4 soft-starting devices

Overview
1-phase 1.5 kW
3-phase 5.5 kW
Increases the service life of one-phase asynchronous motors and
mechanical drive equipment
Can also be retrofitted in existing systems

Separate setting of acceleration time and starting torque


With LED display for startup or continuous operation
The power semiconductors are bridged after completion of
start-up.

Selection and ordering data


Version

Ue

Pc

MW

Order No.

V AC W

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Soft-starting devices with transparent caps


1-phase

230
L1

T1

T2

100 ... 1 500

5TT3 441

027

0.135

300 ... 5 500

5TT3 440

027

0.430

AI2_07513

5TT3 441

tacc

Mst

tacc: Acceleration time


Mst: Starting torque

Soft-starting devices mounting depth 55 mm


3-phase, 2-phase motor actuation

400

L3

L2

T3

T2

AI2_07514

5TT3 440

tacc

Mst

tacc: Acceleration time

7/8

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Switching Devices
5TT5 2 EMERGENCY-STOP modules

Overview
Scope
The scope of the EC Directive Machines is no longer restricted to
industrial machinery, but now covers virtually all machines used in all
areas of commercial and private trade and industry and applies to all
Stationary
Movable
Hand-held
Mobile
Machine tools and processing machines
Prime movers and production machines
Compressors
Risk analysis and selection of a suitable category
Engineers and operators assume responsibility for the correct risk
assessment.
It is difficult to make a quantitative assessment of the risk, so that
when selecting the category, the reasonable risk can be determined
within a broad band width.

Risk parameter S:

Risk parameter F:
frequency and
duration

seriousness of injury

Operating and packaging machines


Machines in underground mining
Earthmoving machines and harvesters
Hoisting equipment
Floor conveyors
Machines for lifting persons
Plants
Interchangeable equipment, such as snow ploughs and mountable sweeping devices

This becomes clear if you select "F2 frequently to continuous"


instead of "F1 rarely to frequently", for the risk parameters "F
Frequency and duration" when drawing up a risk graph (see image).
The whole band width of safety categories may lie between the
assessment of "often" and "frequently".

Categories

Risk parameter P:
possibility of
avoiding injuries

minor injury
serious and irreversible
injury of one or several
persons or death of a
person

preferred categories for


reference points

possible under certain


circumstances
rarely to frequently

possible category which requires


additional measures with regard
to the risk

hardly possible
possible under certain
circumstances

1
2
3
4
5
6
7
8

I2_08404a

frequently to constantly
hardly possible

overdimensioned measures with


regard to the risk

Benefits
According to the 98/37/EC EC Machine Directive
Safety category 4 according to EN 954-1
According to the 98/37/EC EC Machine Directive

Safety category 4 according to EN 954-1


Electrical isolation between electric circuit and control
LED display for operation and circuit state

9
10

Selection and ordering data


Version

Ue

Ie

Uc

V AC

V AC

EMERGENCY-STOP modules, mounting depth 55 mm


400
5
230

MW

Order No.

Price

PG

1 unit
4

5TT5 200

027

Weight
1 unit
approx.
kg

PS*/
P. unit

0.250

Unit(s)

11
12
13

5TT5 200

14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

7/9

17

Switching Devices
Notes

7/10

Siemens ET B1 2007

Timers

General Data

8/2

Introduction

Timers for Buildings

8/3

7LF6 1, 5TT1 3 timers

Timers for Industrial


Applications

8/4

5TT3 1 timers

Time Switches

8/5
8/8

7LF4 4 digital time switches


7LF5 3 mechanical time switches

8/1

Timers
General Data
Introduction

Overview

Energy saving in stairwell lighting

Usage

Industry

Standards

Res. buildings

Application

Non-res. buildings

Devices

EN 60669, IEC 60699

--

7LF6 113 stairwell lighting timers with advance


warning

With warning through flashing prior to EN 60669, IEC 60699,


switching off the stairwell lighting in DIN 18015
apartment houses

--

5TT1 303 stairwell lighting timers ECG

For controlling electronic primary


switching devices for fluorescent
lamps and warning by dimming prior
to switching off the stairwell lighting
in stairwells with multiple apartments
For saving energy in little or variously
used rooms, with warning by flashing
Prior to switching off the stairwell
lighting in stairwells with apartment
houses

EN 60669, IEC 60699,


DIN 18015

--

EN 60669, IEC 60699,


DIN 18015

--

--

Energy saving in bathrooms

EN 60699, IEC 60699

--

For influencing time sequences in


control systems

EN 60255, IEC 60255

--

--

---

---

5TT3 183 flashing timers

--

--

5TT3 184 off-delay timers

--

--

VDE 0631 Part 1 and Part 2-7,


IEC 60730-1 and 60730-2-7,

EN 60730-1 and EN 60730-2-7,

UL 60730

VDE 0631 Part 1 and Part 2-7,


IEC 60730-1 and 60730-2-7,
EN 60730-1 and EN 60730-2-7,
UL 60730

Timers for buildings


7LF6 110, 7LF6 111 stairwell lighting timers

7LF6 114 lighting timers with advance warning


7LF6 115 energy-saving timers with advance
warning
7LF6 112 timers for fan
Timers for industrial applications
5TT3 185 multifunction timers
5TT3 181 delay timers
5TT3 182 wiper timers

7LF4 4 digital time switches


7LF4 40 Mini time switches
7LF4 41 Top time switches
7LF4 42 Profi time switches

Minute-precise switching of
devices and system components in
daily, weekly and yearly programs

7LF4 43 Astro time switches


7LF4 44 Expert time switches

7LF5 3 mechanical time switches


7LF5 300-1, 300-5, 300-6, 300-7, 301-0
synchronous time switches without
power reserve
7LF5 301-1, 301-4, 301-5, 301-6, 301-7, 305-0
quartz-clock time switches with power reserve

Definitions
Ie
= Rated operational current
Ue = Rated operational voltage
= Rated control current
Ic
Uc = Rated control voltage
= Rated operational power
Ps
1 MW = Modular width 18 mm

8/2

Siemens ET B1 2007

Switching of day and week


program, accurate to 30 minutes

Timers
Timers for Buildings
7LF6 1, 5TT1 3 timers

Overview
Stairwell lighting timers

Lighting timers EnergyTimers for


saving timers fans

7LF6 110

7LF6 111

7LF6 113

5TT1 303

7LF6 114

7LF6 115

7LF6 112

Setting range in minutes


Manual switch, steady light

0.5 ... 10

0.5 ... 10

0.5 ... 10

1 ... 10

0.5 ... 10

3 ... 60

0.5 ... 10
continuous
operation

Resettable
Switch off warning

---

--

flashing

dimming

flashing

flashing

--

ECG control

--

--

--

--

--

--

-Quadruple runtime extension by


extended pressing of pushbutton
Switch off by pressing pushbutton twice --

--

--

--

--

--

--

--

--

--

--

4-wire circuit, L-momentary contact

--

--

--

3-wire circuit, L-momentary contact


3-wire circuit, N-momentary contact

--

---

---

Ie

Uc

V AC

V AC

MW

Order No.

Price

PG

1 unit

3
4
5

Selection and ordering data


Ue

1
2

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

6
7

Stairwell lighting timers

with switch for steady light and latch setting,


setting range 0.5 ... 10 minutes
for 3-wire circuit, L-momentary contact, not resettable
250
16
230
for 4-wire circuit, L-momentary contact, resettable,
or 3-wire circuit, N-momentary contact, resettable

7LF6 110

027

0.085

230

7LF6 111

027

0.085

with warning by flashing prior to switching off,


for 4-wire circuit, L-momentary contact, resettable,
or 3-wire circuit, N-momentary contact, resettable
250
-230

7LF6 113

027

0.085

7LF6 114

027

0.085

250

16

9
10

Lighting timers
with switch for steady light and latch setting,
with switch for steady light and latch setting,
setting range 0.5 ... 10 minutes, quadruple extension of runtime
by pressing pushbutton for 1 second,
or 4-wire circuit, L-momentary contact,
or 3-wire circuit, N-momentary contact
250
-230
1

11

Energy-saving timers
with switch for steady light and latch setting,
with switch for steady light and latch setting,
setting range 3 ... 60 minutes,
switch off by pressing pushbutton second time as with remote
control switch, for 4-wire circuit, L-momentary contact, resettable, or 3-wire circuit, N-momentary contact, resettable
250

--

12

230

7LF6 115

027

0.085

13

230

7LF6 112

027

0.085

14

Timers for fans up to 200 VA


with switch for steady light and latch setting,
setting range 0.5 ... 10 minutes,
for delayed switch-on of fan
250
-ECG control switches with transparent cap,
for ECG dynamic

with transparent cap, with switch for steady light and position
indication, setting range 1 ... 10 minutes,
with warning prior to switch-off by dimming,
direct current output 1 to 10 V for control
of 20 ECG dynamic
mounting depth 55 mm
250

* You can order this quantity or a multiple thereof.

10

230

15
2

5TT1 303

027

0.130

Siemens ET B1 2007

16
8/3

17

Timers
Timers for Industrial Applications
5TT3 1 timers

Overview
Multifunction
timers

Delay
timers

Wiper
timers

Flashing timers

Off-delay
timers

5TT3 185

5TT3 181

5TT3 182

5TT3 183

5TT3 184

0.02 s ... 300 h


8

0.25 ... 640 s


4

1 ... 10 s
1

1 ... 10 s
1

0.5 ... 10 s
1

Programmable

Repeat accuracy 1 %

Setting ranges
Number
LED for switch position indication
LED for status display
Large voltage range

Selection and ordering data


Ue

Ie

Uc

V AC

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Multifunction timers with transparent cap


programmable for:
response delay; passing make contact function; delayed pulse generator; clock generator starting with impulse; off-delay; pulse converter;
passing break contact function; response/off-delay
1 CO contact
250
4
12 ... 240 AC
1
12 ... 240 DC

5TT3 185

027

0.065

Delay timers with transparent cap


1 CO contact
250
8

220 ... 240

5TT3 181

027

0.100

Wiper timers with transparent cap


1 CO contact
250
8

220 ... 240

5TT3 182

027

0.100

220 ... 240

5TT3 183

027

0.100

110 ... 240 AC


110 ... 240 DC

5TT3 184

027

0.100

Flashing timers with transparent cap


Pulse time is equal to idle time
1 CO contact

250

Off-delay timers with transparent cap


1 CO contact

8/4

Siemens ET B1 2007

250

* You can order this quantity or a multiple thereof.

Timers
Time Switches
7LF4 4 digital time switches

Overview

Mini

Top

Profi

Astro

Expert

7LF4 401

7LF4 411
7LF4 412

7LF4 421
7LF4 422

7LF4 431
7LF4 432

7LF4 444

Text-assisted programming concept


Display

-LCD

DOT matrix

DOT matrix

DOT matrix

DOT matrix

Background lighting

--

Setting the contrast


Operating mode

-digital

digital

digital

digital

digital

Switching channels
Automatic daylight savings

1/2

1/2

1/2

Manual switching

-1

Special voltages
Modular width MW

-2

Programming
Data keys, software

--

--

Day program
Week program

Year program

--

--

--

--

Exception program
Calendar function (public holidays)

---

---

---

---

Astro program
Operating hours meter

---

---

--

Pulse function

--

--

--

--1)

Random function
Vacation period function

---

---

--

--

Cycle function
Control inputs

---

---

---

1 h-test

--

--

--

PIN code
Sealable cover

--

--

--

EEPROM memory for backup of


switch programs

--

Hour program

1)

--

1
2
3
4
5
6
7

8
9
10
11

A pulse function can be programmed through the second-precise input of


start and end times in the year program.

12
13
14
15
16
Siemens ET B1 2007

8/5

17

Timers
Time Switches
7LF4 4 digital time switches

Selection and ordering data


Contacts

Ue

Ie

Uc

MW

V AC

V AC

V DC

250

16

230

--

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Mini digital time switches


Programming
- week program
1 channel
1 CO contact

7LF4 401-0

027

0.185

7LF4 401-0

Top digital time switches


Programming
- week program
With text-assisted programming concept in German, English, French,
Italian, Dutch and Spanish
1 channel
56 programs
1 CO contact
7LF4 411-0

250

16

2 channels
56 programs (28 per channel)
2 CO contacts
250
16

230
120

---

7LF4 411-0
7LF4 411-1

027
027

0.230
0.230

1
1

230

--

7LF4 412-0

027

0.230

120

--

7LF4 412-1

027

0.230

7LF4 421-0
7LF4 421-1

027
027

0.235
0.235

1
1

7LF4 421-2

027

0.235

7LF4 422-0

027

0.270

7LF4 422-1
7LF4 422-2

027
027

0.270
0.270

1
1

Profi digital time switches

7LF4 421-0

Programming
- week program
- operating hours meter, counting range: 65535 h
- random function
- vacation period function
With text-assisted programming concept in German, English, French,
Italian, Dutch and Spanish
Simple program creation by means of PC using the software included
with the 7LF4 940-0 USB adapter
1 channel
56 programs
Pulse function, 84 start times
1 CO contact

250

16

230
120

---

24

24

2 channels
56 programs (28 per channel)
2 CO contacts

250

16

230

--

120
24

-24

Astro digital time switches

7LF4 431-0

8/6

Programming
- astro function
- week program
- operating hours meter, counting range: 65535 h
- vacation period function
- 1h-Test
- input disable over PIN code
With text-assisted programming concept in German, English, French,
Italian, Dutch and Spanish
Simple program creation by means of PC using the software included
with the USB adapter 7LF4 940-0
1 channel
28 programs
With control input, delay time 0 min. ... 23 h 59 min.
1 CO contact
250
16
2 channels
28 programs (14 per channel)

230

--

7LF4 431-0

027

0.235

2 CO contacts

230

--

7LF4 432-0

027

0.270

Siemens ET B1 2007

250

16

* You can order this quantity or a multiple thereof.

Timers
Time Switches
7LF4 4 digital time switches
Contacts

Ue

Ie

Uc

V AC

V AC

MW

Order No.

V DC

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Expert digital time switches

7LF4 444

Programming
- year program
- astro function
- week program
- exception program (priority program)
- operating hours meter, counting range: 65535 h
- vacation period function
- 1h-Test
- input disable over PIN code
With text-assisted programming concept in German, English, French,
Italian, Dutch and Spanish
Incl. a 7LF4 940-2 data key Expert
Simple program creation by means of PC using the software included
with the 7LF4 940-0 USB adapter
4 channels
84 programs per channel
Cycle function for channel 1
With control input, delay time 0 min. ... 23 h 59 min.
4 CO contacts
250
16
120/230
--

24

7LF4 444-0

027

0.455

7LF4 444-2

027

0.451

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.003

Accessories
Version

Order No.

Price

1 unit

Data keys
for digital time switches: Profi and Astro
Programming at the PC (7LF4 940-0 USB adapter and software
required)
Transfer of programs to the time switch
Readout of programs from the time switch
Transfer of programs
- from PC to time switch and vice versa
- from time switch to time switch

7LF4 940-1

for digital time switches: Expert


Programming at the PC
(7LF4 940-0 USB adapter and software required)
Read-in of programs to the time switch
Writing programs from the time switch
Transfer of programs
- from PC to time switch and vice versa
- from time switch to time switch

7LF4 940-2

027

6
7
8
9

7LF4 940-1

3
4
5

24

1
2

027

0.003

10
11

7LF4 940-2

USB adapter and software

7LF4 940-0

for digital time switches: Profi, Astro and Expert


For the reading and writing of data keys at the PC
Incl. programming software
Incl. a 7LF4 940-1 data key for digital time switches; Profi and Astro
Can be connected over USB interface
System requirements:
- Windows 2000, Windows ME, Windows XP,
or Windows 98 Second Edition
- USB connection
- 40 MB free disk space

7LF4 940-0

027

0.125

12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

8/7

17

Timers
Time Switches
7LF5 3 mechanical time switches

Overview
Synchronous time switches without power
reserve

Quartz-clock time switch with power reserve

7LF5
300-1

7LF5
301-1

7LF5
300-5

7LF5
300-6

7LF5
300-7

7LF5
301-0

7LF5
301-4

7LF5
301-5

7LF5
301-6

7LF5
301-7

7LF5
305-0

Display
Switching channels

index disk
1

index disk
1

Operating mode
Automatic daylight savings

synchronous
--

quartz
--

--

--

--

Modular widths

--1)

--1)

Programming
Hour program

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

---

--

--

--

--

--

ON/Automatic
ON/Automatic/OFF

--

--

--

--

--

--

--

--

--

--

--

Sealable cover

Day program
Week program
Manual switching

1)

Time switches for wall mounting

Selection and ordering data


Contacts

Ue

Ie

Uc

V AC

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Synchronous time switches without power reserve


Synchronous time switches
Day disk
1 NO contact
Hour disk

250

16

230

7LF5 300-1

027

0.850

1 NO contact

250

16

230

7LF5 300-7

027

0.850

7LF5 300-7
Synchronous time switches
Day disk
1 CO contact

250

16

230

7LF5 300-5

027

0.155

Week disk
1 CO contact

250

16

230

7LF5 300-6

027

0.155

230

--

7LF5 301-0

027

0.220

7LF5 300-5
Synchronous time switches for wall mounting
Day disk
1 CO contact

250

16

7LF5 301-0

8/8

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Timers
Time Switches
7LF5 3 mechanical time switches
Contacts

Ue

Ie

Uc

V AC

V AC

16

230

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.900

Quartz-clock time switches with power reserve


Quartz-clock time switches
Day disk
1 NO contact

250

7LF5 301-1

027

Quartz-clock time switches


Time set automatically during commissioning
Automatic daylight savings
With quartz clock mechanism
Clock accuracy 0.2 s/day
Power reserve (time buffer in the event of a power failure) 5 years
Day disk

7LF5 301-4

250

16

230

7LF5 301-4

027

0.165

16

230

7LF5 301-5

027

0.165

250

16

230

7LF5 301-6

027

0.165

250

16

230

7LF5 301-7

027

0.165

1 CO
250
Quartz-clock time switches

3
4
5

7LF5 301-1

1 CO contact
Week disk

1
2

6
7

clock accuracy 2.5 s/day


Day disk
1 CO contact
Week disk
1 CO contact

7LF5 301-7
Quartz-clock time switches for wall mounting
Day disk
1 CO contact

250

16

230

--

7LF5 305-0

027

0.230

10
11

7LF5 305-0

12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

8/9

17

Timers
Notes

8/10

Siemens ET B1 2007

Transformers and Socket


Outlets

9/2

Introduction

9/3

4AC3 0, 4AC3 1 bell transformers

9/3

4AC3 4, 4AC3 5, 4AC3 6


transformers

9/3

4AC2 4 power supply units

9/4

5TE6 8 socket outlets

9/1

Transformers and Socket Outlets


Introduction

Application

Standards

Res. buildings

Industry

Devices

Non-res. buildings

Overview
Usage

AC voltage/current supply up to 40 VA as
safety extra-low voltage for the supply of
gongs, buzzers, bells, door openers, intercoms, remote control switches and AC
power supplies for safety e.l.v. systems for
short-time operation.

EN 61558-2-8

--

AC voltage/current supply up to 63 VA as
EN 61558-2-2
safety extra-low voltage for the supply of
calibration circuits, switching relays, Insta
contactors and AC power supplies for safety
e.l.v. systems for continuous operation.

--

Direct voltage/current supply up to 24 V DC, EN 61558-2-6


2.0 A as safety extra-low voltage for the supply of gongs, buzzers, bells, door openers,
switching relays, Insta contactors and DC
power supplies for safety e.l.v. systems for
continuous operation.

For power supply during maintenance in


distribution boards

Bell transformers
4AC3 0, 4AC3 1

Transformers
for permanent load
4AC3 4, 4AC3 5, 4AC3 6

Power supply units


for direct voltages
4AC2 4

Socket outlets
5TE6 8

Definitions
Ie
=
=
Ue
=
Ic
=
Uc
=
Ps
1 MW =

9/2

Rated operational current


Rated operational voltage
Rated control current
Rated control voltage
Rated operational power
Modular width 18 mm

Siemens ET B1 2007

DIN VDE 0620-1,


CEE 7 standard sheet V,
CEI 23-50,
UL 498

Transformers and Socket Outlets


4AC3 0, 4AC3 1 bell transformers

Selection and ordering data


Ue

Usec

Isec

Ps

V AC

V AC

A AC

VA

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Bell transformers
with PTC protection for AC voltage/current supply as safety
extra-low voltage for short-time operation, for the supply of
gongs, buzzers, bells, door openers, intercoms and remote
control switches
with two secondary voltages, optionally for
series or parallel switching
230
2x4/8
2x1/1
8
2x2/2
16
2x12/24

2x0.33/0.33
2x0.67/0.67
2x1.67/1.67

8
16
40

2
2

4AC3 008
4AC3 016

027
027

0.290
0.370

1
1

2
2
3

4AC3 108
4AC3 116
4AC3 140

027
027
027

0.260
0.320
0.490

1
1
1

4AC3 4, 4AC3 5, 4AC3 6 transformers

Selection and ordering data


Ue

Usec

Isec

Ps

V AC

V AC

A AC

VA

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Transformers for permanent loads


with PTC protection for AC voltage/current supply as safety
extra-low voltage for continuous operation for the supply of
calibration circuits, switching relays and Insta contactors,
with one secondary voltage
230
8

1
3
5

with two secondary voltages, optionally for


series or parallel switching
230
2x4/8
2x2/2
2x12/24
2x0.67/0.67
2x1.0/1.0
2x1.67/1.67
2x2.62/2.62

1
2
3
4
5
6
7
8

8
24
40

3
4
4

4AC3 408
4AC3 524
4AC3 540

027
027
027

0.320
0.940
0.870

1
1
1

16
16
24
40
63

3
3
4
4
5

4AC3 516
4AC3 616
4AC3 624
4AC3 640
4AC3 663

027
027
027
027
027

0.600
0.600
0.910
0.840
1.170

1
1
1
1
1

10
11

4AC2 4 power supply units

Selection and ordering data


Ue

Usec

Isec

Ps

V AC

V DC

A DC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

0.830
1.160

1
1

Unit(s)

Power supply units


with transformer for safety extra-low voltage,
with rectifier in center tap connection
230
12
2.0
24
2.0

24
48

4
5

4AC2 400
4AC2 401

027
027

12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

9/3

17

Transformers and Socket Outlets


5TE6 8 socket outlets

Selection and ordering data


Ue

Ie

Conductor
MW
cross-section

V AC

mm2

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

VDE socket outlets according to DIN VDE 0620-1


Without cover
250

16

2.5

5TE6 800

027

0.089

2.5

5TE6 801

027

0.094

2.5

5TE6 802

027

0.094

2.5

5TE6 803

027

0.090

2.5

5TE6 804

027

0.088

2.5

5TE9 120

027

0.020

VDE socket outlets according to DIN VDE 0620-1


With hinged lid
250

16

Socket outlets according to CEI 23-50


With hinged lid
250

16

Socket outlets according to CEE 7 Standard sheet V


Without cover, with grounding pin
250
16

UL 498 socket outlets


Without cover
125

15

Hinged lids for 5TE6 80. socket outlets

9/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Measuring Devices

10/2

Introduction

10/4

7KT5 8 time and pulse counters

10/4

7KT5 5 and 7KT5 6


time counters for front-panel
mounting

10/5

7KT1 0 analog measuring


devices

10/5

7KT1 1 digital measuring devices

10/6

7KT1 30 multimeters

10/7

7KT1 3 multicounters

10/8

7KT1 14 E-counters,
single-phase

10/8

7KT1 5 E-counters, three-phase

10/9

7KT1 16 E-counters, three-phase,


instabus KNX EIB

10/9

7KT1 390 LAN couplers

10/10

7KT9 0 measuring selector


switches

10/10

7KT1 2 current transformers

10

10/1

Measuring Devices
Introduction

Overview

Monitoring of operating hours and


starting operations of devices or plants

IEC 60255-6,
EN 60255-6
(VDE 0435 T 301)
UL 94

Usage

Industry

Standards

Res. buildings

Application

Non-res. buildings

Devices

Time and pulse counters


7KT5 80 and 7KT5 82 time counters
7KT5 81 and 7KT5 83 pulse counters

Time counters for front-panel mounting


7KT5 5 and 7KT5 6

Monitoring of operating hours of devices IEC 60255-6, EN 60255-6


or plants
(VDE 0435 T 301)

For measuring voltages and currents,


IEC 60051-2, EN 60051-2
for monitoring input and output currents
or device currents

--

For measuring voltages and currents,


DIN 43751-1,
for monitoring input and output currents DIN 43751-2
or device currents

--

For the display and assessment of


IEC 60051-2, EN 60051-2
23 electrical measured values in
IEC 61010-1, EN 61010-1
switchgear, infeed and outgoing feeders (VDE 0411 T 1)

--

For the display and assessment of


35 electrical measured values and
consumption values in switchgear,
infeed and outgoing feeders

--

Analog measuring devices


7KT1 0

Digital measuring devices


7KT1 1

Multimeters
7KT1 30

Multicounters
7KT1 31, 7KT1 34, 7KT1 35

10/2

Siemens ET B1 2007

IEC 60051-2, EN 60051-2


IEC 61010-1, EN 61010-1
(VDE 0411 T 1)
IEC 62053-21, EN 62053-21
(VDE 0418 T 3-21)

Measuring Devices
Introduction
Usage

Industry

Standards

Res. buildings

Application

Non-res. buildings

Devices

E-counters, single-phase
7KT1 14

E-counters, three-phase
7KT1 50, 7KT1 51, 7KT1 52

For the measurement of kWh in 1-phase IEC 62053-11, EN 62053-11


systems, e.g. in industrial plants, offices (VDE 0418 T 3-11)
and apartments in apartment houses
IEC 62053-21, EN 62053-21
(VDE 0418 T 3-21)

--

For the measurement of kWh in single


and three-phase systems, e.g. in industrial plants, offices and apartments in
apartment houses

IEC 61010-1, EN 61010-1


(VDE 0411 T 1)

IEC 62053-11, EN 62053-11


(VDE 0418 T 3-11)

E-counters, three-phase,
instabus KNX EIB
With instabus KNX EIB interface,
for the measurement of kWh in single
and three-phase systems, e.g. in industrial plants, offices and apartments in
apartment houses

IEC 61036
EN 61036
(VDE 0418 T7)

Worldwide data communication with


measuring devices using LAN/Internet

IEEE 802

3
4
5

IEC 62053-21, EN 62053-21


(VDE 0418 T 3-21)

7KT1 16

1
2

6
7
8
9

LAN couplers
7KT1 390

--

10
11

Measuring selector switches


7KT9 0

For switching over the phases for voltmeters and ammeters

--

12

Current transformers
7KT1 2

For non-contact measuring of primary


currents of a 3-phase system

IEC 60044-1, EN 60044-1


(VDE 0414 T 44-1)

--

13
14

Definitions
= Rated operational current
Ie
= Rated operational voltage
Ue
= Rated control supply current
Ic
= Rated control supply voltage
Uc
= Rated operational power
Ps
1 MW = Modular width 18 mm

15
16
Siemens ET B1 2007

10/3

17

Measuring Devices
7KT5 8
time and pulse counters

Selection and ordering data


Uc

Frequency

Hz

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Time counters
Mechanical counting mechanism,
display 00000.00 h without resetting
12 ... 24 DC

24 AC
115 AC
230 AC
115 AC
230 AC
7KT5 801

50

60

7KT5 801

027

0.095

7KT5 802
7KT5 803
7KT5 804
7KT5 806
7KT5 807

027
027
027
027
027

0.095
0.095
0.095
0.095
0.095

1
1
1
1
1

7KT5 811

027

0.095

7KT5 812
7KT5 814

027
027

0.095
0.095

1
1

7KT5 821

027

0.080

Pulse counters
Mechanical counting mechanism,
display 0000000
without resetting
10 ... 24 DC

24 AC
230 AC

50/60

Electronic time counters


LCD 000000.0 h without resetting
12 ... 150 DC, 24 ... 240 AC
with electrical resetting

50/60

12 ... 150 DC, 24 ... 240 AC

50/60

7KT5 822

027

0.080

with electrical and mechanical resetting


12 ... 150 DC, 24 ... 240 AC

50/60

7KT5 823

027

0.080

7KT5 833

027

0.080

MW

Order No.

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

Electronic pulse counters


7KT5 823

LCD display 0000000


with electrical and mechanical resetting
10 ... 150 DC, 24 ... 240 AC

50/60

7KT5 5 and 7KT5 6


time counters for front-panel mounting

Selection and ordering data


Uc

Frequency

Hz

Price

1 unit

Unit(s)

Time counters
mechanical counting mechanism, display 00000.00 h,
for front-panel mounting, front frame 48 mm x 48 mm
10 ... 80 DC

7KT5 500

027

0.045

24 AC
115 AC
230 AC

50

7KT5 505
7KT5 501
7KT5 502

027
027
027

0.045
0.045
0.045

1
1
1

115 AC
230 AC

60

7KT5 503
7KT5 504

027
027

0.045
0.045

1
1

7KT5 600
7KT5 601
7KT5 602

027
027
027

0.120
0.120
0.120

1
1
1

7KT5 603
7KT5 604

027
027

0.120
0.120

1
1

55 mm 55 mm
Sealing rings for 7KT9 020 covers

7KT9 020

027

0.015
1 set

5/1

IP 43-installation in switchboards with smooth surfaces


(1 set = 5 units)

7KT9 000

027

0.020

1 set

7KT9 021

027

0.010

7KT5 500
for front-panel mounting, front frame 72 mm x 72 mm
with narrow frame according to DIN 43700
10 ... 50 DC
115 AC
230 AC

50

115 AC
230 AC

60

7KT5 600
Covers for 7KT5 5 time counters

Terminal covers for 7KT5 6 time counters


Degree of protection IP20

10/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Measuring Devices
7KT1 0
analog measuring devices

Selection and ordering data


Umeas

Imeas

V AC

A AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Analog voltmeters

7KT1 000

500
Analog ammeters for direct connection

7KT1 000

027

0.105

25
40
60
Analog ammeters for transformer connection
with 3 different interchangeable scales

7KT1 010
7KT1 011
7KT1 012

027
027
027

0.110
0.125
0.135

1
1
1

7KT1 020

027

0.105

0 ... 60/5
0 ... 150/5
0 ... 400/5

0 ... 60 A,
0 ... 150 A and
0 ... 400 A

Selection and ordering data


Umeas

Imeas

V AC

V AC

A AC

230

600

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.190

Digital voltmeters
2

7KT1 110

027

3
4
5

7KT1 1
digital measuring devices

Uc

1
2

6
7
8
9

Digital ammeters for direct and transformer connection


230
0 ... 20
transformer/5

7KT1 120

027

0.200

10

11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

10/5

17

Measuring Devices
7KT1 30
multimeters

Overview
All required measured values of an installation clearly visible at a
glance
5 display fields with setting options for the measured quantities to
be displayed
Device version for direct connection up to 63 A or for
transformers /5 A.
Transformer ratio, primary side, adjustable from 5 to 5000 A in
5 A increments

11 mm high, green 7-segment display for measured values


Orange display of measured units per display field
2 display fields (D4, D5) can also be combined for the display of
count values
Display of connection errors
Measuring accuracy class 2
Display of 25 measured values

Selection and ordering data


Uc

Ie

Ue

V AC

A AC

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Multimeters
for the display of 23 electrical values,
of which 5 values can be continuously displayed
for 3-phase, 3/4-wire connection
for direct connection

7KT1 300

230
63
3 x 230/400 6
for transformer connection of 10 ... 5000 A, adjustable in 5 A
increments
secondary current, optionally 1 A or 5 A

7KT1 300

027

0.400

230
/1 or /5
for front-panel mounting 96 mm 96 mm
for transformer connection of 10 to 5000 A,
adjustable in 5 A increments
secondary current, optionally 1 A or 5 A
230
/1 or /5

3 x 230/400 6

7KT1 301

027

0.380

3 x 230/400

7KT1 302

027

0.378

7KT1 302

10/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Measuring Devices
7KT1 3
multicounters

Overview
6 display fields with setting options for the measured quantities to
be displayed
Device version for direct connection up to 63 A or for
transformers /5 A
Transformer ratio, primary side, adjustable from 5 to 5000 A.
2 display fields (D4, D5) can also be combined for the display of
count values.

Display of connection errors


Display of 35 measured values
Measuring accuracy class 1
All devices with S0 output
Devices available with PROFIBUS, Modbus or LAN
communication interfaces (over 7KT1 390 LAN server).

3
4

Selection and ordering data


Uc

Ie

Ue

V AC

A AC

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Multicounters
for the display of 35 electrical values, of which
5 or 6 values can be continuously displayed.
for 3-phase, 3/4-wire connection, with S0 interface

230

7KT1 310

63

3 230/400 6

7KT1 310

027

0.420

/5

3 230/400 6

7KT1 311

027

0.410

3 230/400

7KT1 312

027

0.410

3 230/400 6

7KT1 340

027

0.470

230
/5
for transformer connection
for front-panel mounting 96 mm 96 mm

3 230/400 6

7KT1 341

027

0.423

230
/5
with PROFIBUS DP V0 interface

3 230/400

7KT1 342

027

0.397

63

3 230/400 6

7KT1 350

027

0.415

/5

3 230/400 6

7KT1 351

027

0.415

3 230/400

7KT1 352

027

0.460

for transformer connection


for front-panel mounting 96 mm 96 mm
230
/5

with RS485 interface and RTU Modbus protocol or


for connection to LAN networks with 7KT1 390 LAN coupler
for direct connection
230

63

for transformer connection

7KT1 312

10

for direct connection


230
for transformer connection
230

for transformer connection


for front-panel mounting 96 mm 96 mm
230
/5

5
6
7

without communication interface


for direct connection
for transformer connection
230

1
2

11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

10/7

17

Measuring Devices
7KT1 14
E-counters,single-phase

Selection and ordering data


Uc

Ie

Ue

V AC

A AC

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

E-counters for active energy


with drum-type register 4 12 mm,
with S0 interface, for 1-phase operation
direct connection, single rate
230
63
direct connection, double rate

230

7KT1 140

027

0.400

230

230

7KT1 141

027

0.400

MW

Order No.

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

63

7KT1 140

7KT1 5
E-counters, three-phase

Selection and ordering data


Uc

Ie

V AC
A AC
E-counters for active energy

Ue

V AC

Price

1 unit

with S0 interface,
for 3-phase, 4-wire connection
for direct connection, single rate
230
63

3 230/400

7KT1 500

027

0.396

for transformer connection, single rate


230
transformer /5
3 230/400

7KT1 501

027

0.396

230
63
3 230/400
for transformer connection, double rate

7KT1 510

027

0.396

230

7KT1 511

027

0.396

3 230/400

7KT1 502

027

0.396

230
transformer /5
for direct connection, double rate

3 230/400

7KT1 503

027

0.396

230

3 230/400

7KT1 512

027

0.396

for transformer connection, double rate


230
transformer /5
3 230/400

7KT1 513

027

0.396

230
63
3 230/400
for transformer connection, double rate

7KT1 520

027

0.450

230

7KT1 521

027

0.388

for direct connection, double rate

transformer /5

3 230/400

E-counters for active and reactive energy


with S0 interface,
for 3-phase, 4-wire connection
for direct connection, single rate
230
63
for transformer connection, single rate

63

E-counters for active and reactive energy


with LAN interface for connection to LAN coupler,
for 3 phase, 4-wire connection
for direct connection, double rate

10/8

Siemens ET B1 2007

transformer /5

3 230/400

* You can order this quantity or a multiple thereof.

Measuring Devices
7KT1 16
E-counters, three-phase, instabus KNX EIB

Selection and ordering data


Display

Ie

Ue

MW

A AC

V AC

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

E-counters for 3/4 wire connection, with LCD,


with IR interface for double rate
Direct connection, with 2 S0 pulse outputs and
instabus KNX EIB interface
Active and reactive
energy
7KT1 162

10(63)

3 230/400

7KT1 162

027

0.450

7KT1 165

027

0.390

PG

Weight
1 unit
approx.

PS*/
P. unit

Transformer connection, with 2 S0 pulse outputs


and instabus KNX EIB interface
Active and reactive
energy

transformers/5(6) 3 230/400

Accessories
Order No.

Price

1 unit
027

7KT9 030

IR measuring heads for 7KT1 16.


for reading out data according to IEC 61107
with 9-pin COM connector and read-out software

kg

Unit(s)

0.170

1
2
3
4
5
6
7
8

7KT1 390
LAN couplers

Overview

Application

Worldwide communication with measuring devices


TCP/IP data protocol
One LAN coupler for 10 devices
Microsoft Excel user interface (MS Excel)
Limit value signals can be set for all measured values
Limit violations are signaled with time information
Analysis of 35 measured values with the 7KT1 340 or 7KT1 341
multicounters

LAN couplers are the data communication link between a PC and a


group of up to 10 measuring devices (7KT1 34. multicounters or
E-counters). The LAN coupler can be linked either directly to a PC or
be integrated in a company-specific LAN.
Multicounters and E-counters are switched in parallel with a shielded
2-wire line.

Selection and ordering data


Uc

MW

Order No.

V AC

Price

PG

1 unit

7KT1 390

027

10
11

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

12

0.232

13

LAN couplers
for connection of 10 devices with LAN interface, with software for
installation and startup routines and Microsoft Excel and tables for
operating, setting limit values and monitoring
230

14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

10/9

17

Measuring Devices
7KT9 0
measuring selector switches

Selection and ordering data


MW

Conductor
crosssections
up to mm2

12

7KT9 010

7KT9 011

Ue

Ie

V AC
400

Order No.

Price

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

027

0.110

1/48

027

0.110

PG

Weight
1 unit
approx.

PS*/
P. unit

kg
0.460
0.460
0.465

Unit(s)
1
1
1

1 unit

Unit(s)

Voltmeter selector switches

7KT9 010
Ammeter selector switches for transformer operation
400
12
6

7KT9 011

7KT1 2
current transformers

Selection and ordering data

Current transformers

Ue

Isec

MeasuMW
ring range

V AC
720

A
5

A AC
3 60
3 100
3 150

Order No.

Price

1 unit
6

7KT1 200
7KT1 201
7KT1 202

027
027
027

7KT1 200

10/10

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Monitoring Devices

11/2

Introduction

11/5

5TT3 46 fault signaling units

11/6

7LQ2 1, 5TT3 3 dusk switches

11/7

7LQ2 0 temperature controllers

11/7

5TT3 170 fuse monitors

11/8

5TT3 171 line circuit relays

11/8

5TT3 42 phase/phase sequence


monitors

11/9

5TT3 1 and 5TT3 4 voltage relays

11/11

5TT6 1 current relays

11/12

5TT6 10 priority switches

11/12

5TT3 47 insulation monitors


for industrial applications

11/13

7LQ3 35 insulation monitors


for medical premises

11/14

5TT3 472 p.f. monitors

11/14

5TT3 435 level relays

11/15

5TT3 43 thermistor motor


protection relays

11/16

5TT7 1 GSM alarm modules

11

11/1

Monitoring Devices
Introduction

Application

Standards
Non-res. buildings

Res. buildings

Industry

Overview
Devices

Usage

5TT3 460 centralized fault signaling units


5TT3 461 expansion fault signaling units

Evaluation and display of fault alarms


and alarm signals for monitoring industrial plants and control systems

IEC 60255,
DIN VDE 0435-303

--

--

Dusk switches
7LQ2 1, 5TT3 3

For demand-oriented switching of lighting installations for shop windows or


paths in order to cut costs

EN 60730

--

Temperature controllers
7LQ2 0

Controlling and limiting of


temperatures

EN 60730

Fuse monitors
5TT3 170

Monitoring of all types of melting fuses

IEC 60255,
DIN VDE 0435

--

Main isolating relays


5TT3 171

Shutdown of unused lines

IEC 60255,
DIN VDE 0435

--

--

Phase/phase sequence monitors


5TT3 421/5TT3 423

Monitoring of the phase sequence of a


system and the power supply

IEC 60255,
DIN VDE 0435

--

--

Fault signaling units

11/2

Siemens ET B1 2007

Monitoring Devices
Introduction

Monitoring of the power supply of


emergency lighting in public buildings

Undervoltage relays
5TT3 404 to 5TT3 406

Usage

Industry

Voltage relays
Undervoltage relays
5TT3 400 to 5TT3 403

Standards

Res. buildings

Application

Non-res. buildings

Devices

IEC 60255,
DIN VDE 0435-303,
DIN VDE 0108

--

--

--

--

Short-time voltage relays


5TT3 407
Under/overvoltage relays
5TT3 408

Monitoring of the power supply for


short-time failures of 20 ms
Monitoring of the power supply for
ensuring operational parameters for
devices or system components

--

--

IEC 60255,
DIN VDE 0435

--

--

Under/overvoltage relays
5TT3 410

Monitoring of the neutral conductor for


breaks

DIN VDE 0633

--

Overvoltage relays
5TT3 19

Monitoring of the power supply for


ensuring operational parameters for
devices or system components
Monitoring of emergency and signal
lighting and motors

IEC 60255,
DIN VDE 0435

--

--

IEC 60255,
DIN VDE 0435-303

--

Current relays
5TT6 1

1
2
3
4
5
6
7
8

Priority switches
5TT6 10

Switching of system loads in


residential buildings

IEC 60669 (VDE 0632),


BTO 6 Clause 4

--

--

Insulation monitors for industrial


applications 5TT3 4

Monitoring of the insulation resistance


in non-grounded systems

IEC 60255,
IEC 61557

--

--

Insulation monitors for medical


premises
7LQ3 350

For monitoring the insulation resistance


in non-grounded systems on medical
premises

EN 61557-8 (VDE 0413 Part 8)


IEC 61557-8:1997-02
EN 61557-8:1997-03
DIN VDE 0100-710 (VDE 0100,
Part 710):2002-11
VE-EN 7-1991
ASTMF12071996-00
IEC 60364-7-710:2002-11

--

--

Signaling and test combinations


7LQ3 351

For displaying operation and fault


signals of the insulation monitor

IEC 60364-7-710:2002-11
DIN VDE 0100-710 (VDE 0100,
Part 710):2002-11

--

--

Power supply units


7LQ3 352

For powering a max. of 3x 7LQ3 351


signaling and test combinations

IEC 60742:1983 + A1:1992,


modified, EN 60742:
1995-09 EN 61558-1:1997-07
IEC 61558-1:1997, modified

--

--

9
10
11
12
13

Measuring current transformers


7LQ3 353

7LQ3 353 measuring current transformers for monitoring power supplies on


medical premises. They record the load
current and convert it into a usable
signal for evaluation devices

EN 60044-1:2001-11
Measuring transformers
Part 1: Current transformers
(IEC 60044-1:1999 + A1:2000),
German version
EN 60044-1:2001-11

--

--

P.f. monitors
5TT3 472

For monitoring of the underload of


motors up to approx. 5 A AC by
making p.f. measurements

IEC 60255
IEC 61557

--

--

14
15
16

Siemens ET B1 2007

11/3

17

Monitoring Devices

Application

Standards
Non-res. buildings

Res. buildings

Industry

Introduction
Devices

Level relays
5TT3 430/5TT3 435

Control of liquid levels in containers

IEC 60255,
DIN VDE 0435

--

Thermistor motor protection relays


5TT3 43

Thermal protection of motor


windings

IEC 60255,
DIN VDE 0435

--

--

GSM alarm modules

Mobile monitoring and switching of


system components

Definitions
Ie
= Rated operational current
= Rated operational voltage
Ue
= Rated control current
Ic
= Rated control voltage
Uc
= Rated operational power
Ps
1 MW = 18 mm modular width

Usage

Transparent caps

Adding a transparent cap extends the 55 mm mounting depth of a


device to 70 mm. This is a useful option for improving the appearance of a distribution board.
.

11/4

Siemens ET B1 2007

Monitoring Devices
5TT3 46 fault signaling units

Overview

Function

4 fault signal inputs with LED


1 LED as centralized fault indicator
One unit each for centralized fault indication and acoustic
signaling
With acknowledgment for acoustic indicators
Open-/closed-circuit principle to the 4 inputs can be set via
jumpers X1-X2
A maximum of 39 5TT3 461 expansion fault signaling units can be
connected to the 5TT3 460 centralized fault signaling unit
The maximum possible cable length between 5TT3 460 centralized fault signaling units and 5TT3 461 expansion fault signaling
units is approx. 100 m with a conductor cross-section of 1.5 mm2.

A fault is indicated as a centralized fault at the LED, and a centralized fault indication is initiated. The assigned LED remains lit until the
fault is eliminated. Until the acknowledgment, momentary faults can
be identified by the remaining centralized fault.

1
2
3
4
5

Selection and ordering data


Ue

Ie

Uc

V AC

V AC

Centralized fault signaling units with transparent cap


230
5
230

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

5TT3 460

027

0.130

5TT3 461

027

0.110

Expansion fault signaling units with transparent cap


230

6
7
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

11/5

17

Monitoring Devices
7LQ2 1, 5TT3 3 dusk switches

Overview
7LQ2 100

7LQ2 101

7LQ2 102

7LQ2 103

5TT3 303

Setting ranges in lux

2 ... 500

2 x 2 ... 500

2 ... 500

2 x 2 ... 500

2 ... 2000

Adjustable time delay

--

--

--

Switching status indication


Light sensor, max. cable length

50 m

50 m

50 m

50 m

--

Switching channels
Incandescent lamp load

1
2000 W

2
2 x 2000 W

1
2000 W

2
2 x 2000 W

1
1200 W

Selection and ordering data


Ue

Ie

Uc

V AC

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Dusk switches
Setting range 2 ... 500 lux

7LQ2 100

1-channel version,
with 7LQ2 910 light sensor for surface mounting, IP55
250
16
230

7LQ2 100

027

0.210

2-channel version,
with 7LQ2 910 light sensor, for surface mounting, IP55
expandable to 24 channels through parallel switching of
12 devices, which can be mutually controlled through a light
sensor.
250
16
230

7LQ2 101

027

0.210

1-channel version,
with 7LQ2 911 light sensor for flush wall mounting, IP65
250
16
230

7LQ2 102

027

0.210

2-channel version,
with 7LQ2 911 light sensor, for flush wall mounting, IP65
expandable to 24 channels through parallel switching of
12 devices, which can be mutually controlled through a light
sensor.
250
16
230

7LQ2 103

027

0.210

5TT3 303

027

0.190

7LQ2 910

027

0.060

7LQ2 911

027

0.060

7LQ2 103
Setting range 2 ... 2000 lux
1-channel version,
for surface mounting, IP55, with integrated light sensor
250
10
230

5TT3 303
Replacement light sensors
with watertight/resistant resin molding material,
heat-resistant to 70 C
Degree of protection IP55, for 7LQ2 100 and 7LQ2 101,
for surface mounting, 2 ... 500 lux
Degree of protection IP65, for 7LQ2 102 and 7LQ2 103,
for flush wall mounting, 2 ....0 500 lux

11/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Monitoring Devices
7LQ2 0 temperature controllers

Overview
7LQ2 001

7LQ2 002

7LQ2 003

7LQ2 005

Setting ranges in C

-30 ... +30

0 ... +60

+40 ... +100

+2 ... +400

Switching status indication

Adjustable switching hysteresis in C


Temperature sensor, measuring element

1 ... 5
KTY 11-6

1 ... 5
KTY 11-6

1 ... 5
KTY 11-6

1 ... 20
for PT100

Max. cable length

100 m

100 m

100 m

100 m

3
4

Selection and ordering data


Ue

Ie

Uc

V AC

V AC

MW

Order No.

Price

PG

1 unit

1
2

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Temperature controllers
With KTY 11-6 temperature sensor
Setting range -30 ... +30 C, 1 CO contact
250
16

230

7LQ2 001

027

0.210

Setting range 0 ... +60 C, 1 CO contact


250

230

7LQ2 002

027

0.210

250
16
230
Temperature controllers without temperature sensor

7LQ2 003

027

0.210

7LQ2 005

027

0.210

16

6
7

Setting range +40 ... +100 C, 1 CO contact

7LQ2 001

For PT 100 measuring element (not included in delivery)


Setting range +2 ... +400 C, 1 CO contact
250
16

230

KTY 11-6 replacement temperature sensors


Safety class IP65, for 7LQ2 001, 7LQ2 002 and
7LQ2 003, encapsulated,
with watertight/resistant resin material,
with 1 m silicone line,
heat-resistant up to 105 C,
can be extended up to 100 m

9
230

027

7LQ2 900

0.040

10
5TT3 170 fuse monitors

Overview

Application

For all fuse systems


Signal is output even when load is shut off
Also suitable for asymmetrical networks, networks with harmonics
or motors with feedback
With two display LEDs, 1 for "Fuse OK" and 1 for "Fuse Failed"

For the fuse monitoring of all kinds of melting fuses, in particular for
the automatic shutdown and closing lockout of 3-phase AC
motors in the event of the failure of one or more phase fuses.
Note:
The internal resistance of the measuring paths of the fuse monitor is
in the M range so that the VDE regulations with regard to touch
voltage are met in the event of faulty fuses (>1000 /V).
To isolate, the main switch must be switched off. The enclosed label
should be affixed to the switchgear as a reminder.

Selection and ordering data


Ue

Ie

Uc

V AC

MW

Fuse monitors with transparent cap


for all low-voltage fuse systems.
Can be used in asymmetric systems afflicted with harmonics and
regenerative feedback motors. Alarm also for disconnected loads.
230
4
3x 380 ... 415
2

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

11
12
13
14

Unit(s)

15
5TT3 170

027

0.150

16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

11/7

17

Monitoring Devices
5TT3 171 line circuit relays

Overview

Application

Adjustable from 2 to 20 VA
With status display for contact position
With switch continuously ON
With safety information on stickers for socket outlets and distribution boards

For disconnecting the voltage or field circuit of electrical systems


even when loads are disabled.
The line circuit relay switches off the system component, but is not a
device for ensuring isolation in the sense of safe disconnection.

Selection and ordering data


Ue

V AC
Line circuit relay with transparent cap

Ie

Uc

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

for disconnecting the voltage or field circuit of electrical systems


even when loads are disabled.
1 NC contact
250
16
Base load resistor for electronic devices

230

with 15-cm connection wires, end sleeves and shrink sleeving

5TT3 171

027

0.072

5TG8 222

027

0.010

5TT3 171

5TT3 42 phase/phase sequence monitors

Overview

Application

Phase monitors with 3-fold LED display


Phase sequence monitors with single LED display

For visual detection/signaling of phase failures in a 3-phase system.


The phase sequence is arbitrary. The device is also suitable for 1, 2
or 3-phase operation.
Indication of phase sequence in 3-phase system.

Selection and ordering data


Ue

V AC
Phase monitors with transparent cap

Ie

Uc

V AC

230/400

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

with 3 green LEDs for 3 phases


1 CO

250

5TT3 421

027

0.060

5TT3 423

027

0.050

Phase sequence monitors with transparent cap


with one green LED, which lights up for right-rotating field
1 CO

11/8

Siemens ET B1 2007

250

400

* You can order this quantity or a multiple thereof.

Monitoring Devices
5TT3 1 and 5TT3 4 voltage relays

Overview
5TT3
194

5TT3
195

5TT3
400

5TT3
401

5TT3
402

5TT3
403

5TT3
404

5TT3
405

5TT3
406

5TT3
407

5TT3
408

5TT3
410

General monitoring
Monitoring of safety light devices

--

--

--

--

--

---

---

---

---

Monitoring of medical facilities

--

--

--

--

--

--

--

--

--

--

--

Monitoring of N-conductor
Monitoring of short-time interruptions

---

---

---

---

---

---

---

---

---

---

--

Overvoltage
Undervoltage

--

--

---

1, 2, 3-phase against N

--

--

--

--

--

--

3 phases against N
Asymmetry detection

---

---

---

---

---

---

N-conductor monitoring

--

--

--

--

Reverse voltage detection


Short-time failure detection

---

--

---

---

---

---

--

--

--

--

--

---

Phase failure detection


Switching thresholds:

--

--

--

--

--

--

--

--

--

--

--

---

0.7 / 0.9 x Uc, not adjustable

--

--

--

--

--

--

--

--

--

0.8 / 0.85 x Uc, not adjustable


0.85 / 0.95 x Uc, not adjustable

---

---

---

---

---

---

--

---

---

0.7 ... 0.95 x Uc, 5 % hysteresis, adjustable

--

--

--

--

--

--

--

--

--

--

--

0.7 ... 1.1 x Uc, 4 % hysteresis, adjustable


0.9 ... 1.3 x Uc, 4 % hysteresis, adjustable

---

---

---

---

---

---

---

---

---

Adjustable time delay


Contact: 1 CO contact

---

---

---

---

---

---

---

---

--

---

Contact: 2 CO contacts

--

--

Selection and ordering data


Ue

V AC
Voltage relays with transparent cap

Ie

Uc

V AC

MW

Order No.

Price

PG

1 unit

11

Contact, 2 CO contacts

5TT3 195

027

0.150

5TT3 400

027

0.065

for undervoltage monitoring of safety light devices of 1, 2 or 3 phases


against N, with phase failure detection, switching
thresholds: 0.85/0.95 x Uc, not adjustable
Contact, 1 CO contact
230
4
230/400
1

5TT3 401

027

0.065

5TT3 400

12

for general undervoltage monitoring of 1, 2 or 3 phases against N,


with phase failure detection, switching
thresholds: 0.7/0.9 x Uc, not adjustable
230

230/400

9
10

0.150

Contact, 1 CO contact

Unit(s)

027

230/400

6
7

kg

5TT3 194

PS*/
P. unit

Contact, 2 CO contacts
230
4
230/400
2
for general overvoltage monitoring of 3 phases against N, with asymmetry, reverse voltage and phase failure detection, with N-conductor
monitoring, switching thresholds: 0.7 ... 0.9 x Uc, not adjustable
230

3
4

Weight
1 unit
approx.

for general overvoltage monitoring of 1, 2 or 3 phases against N,


with reverse voltage and phase failure detection
switching thresholds: 0.9 ... 1.3 x Uc, 4 % hysteresis, adjustable

5TT3 194

1
2

13

for general undervoltage monitoring of 1, 2 or 3 phases against N,


with phase failure detection, switching
thresholds: 0.7/0.9 x Uc, not adjustable

14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

11/9

17

Monitoring Devices
5TT3 1 and 5TT3 4 voltage relays
Ue

V AC
Voltage relays with transparent cap

Ie

Uc

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

for general overvoltage monitoring of 1, 2 or 3 phases against N,


with reverse voltage and phase failure detection
switching thresholds: 0.9 ... 1.3 x Uc, 4 % hysteresis, adjustable
Contact, 2 CO contacts
230
4
230/400
for general undervoltage monitoring of 1, 2 or 3 phases against N,
with phase failure detection, switching
thresholds: 0.9 ... 0.95 x Uc, 5 % hysteresis, adjustable
5TT3 402

5TT3 402

027

0.110

Contact, 2 CO contacts
230
4
230/400
2
for general undervoltage monitoring of 3 phases against N, with asymmetry, reverse voltage and phase failure detection, with N-conductor
monitoring,
switching thresholds: 0.7/0.9 x Uc, not adjustable
Contact, 2 CO contacts
230
4
230/400
2

5TT3 403

027

0.110

5TT3 404

027

0.110

5TT3 405

027

0.110

5TT3 406

027

0.110

5TT3 407

027

0.110

230/400

5TT3 408

027

0.110

230/400

5TT3 410

027

0.110

for undervoltage monitoring of safety light devices of 3-phases against


N, with asymmetry, reverse voltage and phase failure detection,
with N-conductor monitoring,
switching thresholds: 0.85/0.95 x Uc, not adjustable
Contacts, 2 CO contacts
230
4
230/400
2
5TT3 404

for undervoltage monitoring of medical premises of 3 phases against


N, with asymmetry, reverse voltage and phase failure detection,
with N-conductor monitoring,
switching thresholds: 0.9 ... 0.95 x Uc, 5 % hysteresis, adjustable
Contact, 2 CO contacts

230

230/400

for monitoring of short-time failure detection 20 ms of 1, 2 or 3


phases against N, with phase failure detection and N-conductor
monitoring,
switching thresholds: 0.8 ... 0.85 x Uc, not adjustable
Contact, 2 CO contacts
5TT3 407

230

230/400

for general under and overvoltage monitoring of 3 phases against N,


with asymmetry, reverse voltage and phase failure detection,
with N-conductor monitoring and adjustable time delay of 0.1 ... 20 s,
switching thresholds:
undervoltage: 0.7 ... 1.1 x Uc, 4 % hysteresis, adjustable
overvoltage: 0.9 ... 1.3 x Uc, 4 % hysteresis, adjustable
Contact, 2 CO contacts

230

5TT3 408
N-conductor monitors with transparent cap
with asymmetry detection and N-conductor monitoring
Contact, 2 CO contacts
230
4

5TT3 410

11/10

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Monitoring Devices
5TT6 1 current relays

Overview
Direct measurement,
transformer measurement
All current relays can be connected with direct measurement or
through transformers.

Response time
Current relays are not circuit-protective devices for lines.
They switch with a delay in the ms range.
Overload capability
Independent of the set measuring range and set measured value,
current relays can be permanently overloaded up to 15 A and 20 A;
for 3 s, even up to 20 A and 30 A.

N potential
Versions 5TT6 113 to 5TT6 120 can be connected with a
separate N potential.
Device overview

5TT6 111

5TT6 112

5TT6 113

5TT6 114

5TT6 115

5TT6 120

Undercurrent

--

--

Overcurrent
1-phase

--

3-phase

--

--

--

--

--

Separate N potential
Measuring
Link:
ranges:

--

--

0.1 ... 1 A
0.5 ... 5 A

Z1-Z2
Z1-Z3

---

---

Z1-Z4

--

---

---

---

1 CO contact

--

--

--

--

2 CO contacts

--

--

... 10 A

1.5 ... 15 A
Z1-Z3-Z4
Can be programmed over links
Contacts

Ie

Measuring
range

V AC

A AC

MW

Order No.

Price

PG

1 unit

3
4
5
6
7

Selection and ordering data


Ue

1
2

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Current relays with transparent cap for 1-phase loads up to


230 V AC, auxiliary voltage and measuring circuit,
not isolated
Undervoltage monitoring, 1-phase
1 CO
230

1 ... 10

5TT6 111

027

0.065

Overvoltage monitoring, 1-phase


1 CO
230

1 ... 10

5TT6 112

027

0.065

8
9
10
11

5TT6 111
Current relays with transparent cap for 1-phase loads up to
230 V AC, auxiliary voltage and measuring circuit,
isolated
undervoltage monitoring, 1-phase
2 COs

5TT6 113

230

4 ranges
0.1 ... 1
0.5 ... 5
1 ... 10
1.5 ... 15

5TT6 113

027

0.122

230

4 ranges
0.1 ... 1
0.5 ... 5
1 ... 10
1.5 ... 15

5TT6 114

027

0.122

4 ranges
0.1 ... 1
0.5 ... 5
1 ... 10
1.5 ... 15

5TT6 115

027

0.122

overvoltage monitoring, 1-phase


2 COs

Over/undervoltage monitoring, 1-phase


2 COs

230

5TT6 115

* You can order this quantity or a multiple thereof.

230

0.5 ... 5

13
14
15

Current relays, mounting depth 55 mm, for 3-phase loads


for 3 400 V AC, separate signal with N-wire connection
Over/undervoltage monitoring, 3-phase
2 CO contacts each for overcurrent/undercurrent respectively

12

5TT6 120

027

0.220

Siemens ET B1 2007

11/11

16
17

Monitoring Devices
5TT6 10 priority switches

Overview

Application

Control circuit terminals, sealable


Reduction of the connection fee, which depends on the maximum
load to be supplied (BTO, German Federal Regulation on Tariffs
6 Section 4), when used in systems with continuous-flow heaters
and electric storage heaters where the continuous-flow heaters are
switched with priority.

In mixed operation of electric hot water and electric storage heaters,


the priority switch interrupts the charging procedure of the storage
heater if hot water is required during the low-tariff time, thus limiting
the connected load.

Selection and ordering data


Ue

Ie

Responsecurrent

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Priority switches, mounting depth 55 mm


for continuous-flow heaters up to 27 kW
230

40

13

5TT6 101

027

0.100

54

23

5TT6 102

027

0.100

5TT6 103

027

0.100

for continuous-flow heaters up to 33 kW


230

for electronically controlled continuous-flow heaters up to 27 kW


230

40

6 ... 40

5TT6 101

5TT3 47
insulation monitors for industrial applications

Overview

Application

Version for AC voltage:


For AC voltage systems from 0 to 500 V AC and 10 to 1000 Hz
Adjustable alarm value 2 to 100 k
Electrical insulation of measuring circuit, power supply and contact
voltage
Also supports monitoring in current-free systems.
Version for direct voltage:
For direct voltage systems from 12 to 280 V DC
Adjustable alarm value 2 to 200 k
Selective insulation-fault detection according to L+ and L Electrical insulation of measuring circuit contact voltage.
Both versions:
Closed-circuit principle
Adjustable fault storage and hysteresis
LED display for operation and insulation faults
With canceling and test button

We recommend using insulation monitors in all non-grounded


systems according to regulations:
VDE 0100 erection of power installations up to 1000 V
VDE 0105 operation of power installations up to 1000 V
VDE 0113 working and processing machines
VDE 0118 underground mining
VDE 0168 open-pit mining, quarries and others

Selection and ordering data


Uc

Ue

V AC
V
Insulation monitors with transparent cap

Measur- MW
ing range

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

for monitoring the insulation resistance in non-grounded AC and


3-phase systems from 10 ... 1000 Hz
Contacts, 2 CO contacts
250
0 ... 500 V
for monitoring the insulation resistance in non-grounded
DC systems

5 ... 100

5TT3 470

027

0.160

Contacts, 2 CO contacts

5 ... 200

5TT3 471

027

0.170

250

12 ... 280 V

5TT3 470

11/12

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Monitoring Devices
7LQ3 35 insulation monitors
for medical premises

Overview

Application

7LQ3 350 insulation monitors


7LQ3 350 insulation monitors are combination monitoring
devices for:
Insulation monitoring of an AC IT system
Load current monitoring of an IT system transformer up to 50 A
Monitoring of an IT system transformer for a non-permissible
temperature rise
Device features:
Adjustable response value 50 k to 500 k
Lad and temperature monitoring
Alarm LED
Connection monitoring for system, ground, current transformer and
temperature sensor
TEST pushbutton
RS485 interface
Group alarm relay with floating CO contact
Illuminated plain text display
7LQ3 351 signaling and test combinations
The 7LQ3 351 signaling and test combination serves the display of
status and fault signals of the insulation monitor.
7LQ3 352 power supply units
The 7LQ3 352 power supply unit serves the supply of the 7LQ3 351
signaling and test combination with a power supply of 20 V AC and
a total power input of maximum 9 VA.

7LQ3 350 insulation monitors


The 7LQ3 350 insulation monitors are used for monitoring the insulation resistance of non-grounded systems on medical premises, such
as hospitals, doctors' surgeries and outpatient treatment centers.
They also simultaneously monitor the load current and the temperature of the IT system transformer. Used together with the 7LQ3 351
signaling and test combination they comply with the demands of the
standards DIN VDE 0100, Part 710 (VDE 0100-710):2002-11 and
IEC 60364-7-710:2002-11.
7LQ3 351 signaling and test combinations
The alarm and event messages output by the 7LQ3 350 insulation
monitors are displayed by the 7LQ3 351 with different LEDs and
acoustic signals.
7LQ3 352 power supply units
This supplies a maximum of 3x 7LQ3 351 signaling and test
combinations.
7LQ3 353 measuring current transformers
The measuring current transformer converts currents with a transformation ratio of 50/0.05. The measuring current transformer is connected to terminals k and l of the 7LQ3 350 line insulation monitor.
Measuring range:
Primary rated current min. 0.5 A
Primary rated current max. 50 A

7LQ3 353 measuring current transformers


7LQ3 353 measuring current transformers are used for monitoring
power supplies on medical premises. They record the load current
and convert it into a usable signal for evaluation devices.

Ue

MW

Order No.

V AC
Isolation monitor with load and temperature monitoring

Signaling and test combinations


with flush-mounting box

3
4
5
6
7
8

Selection and ordering data

Contacts, 2 CO contacts
Response value 50 ... 500 k

1
2

250

Price

PG

1 unit
5.5

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

7LQ3 350

027

0.523

7LQ3 351

027

0.250

9
10
11

250

12
Power supply units

250

7LQ3 352

027

0.560

13
14

Measuring current transformers 50 A/50 mA AC


with snap-in base, mounting bracket, tapping screws 3 x 8,
cap screws M3 x 6, connectors
Measuring range 0.5 ... 50 A
250

7LQ3 353

027

0.100

15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

11/13

17

Monitoring Devices
5TT3 472 p.f. monitors

Overview

Application

For AC and 3-phase loads, such as motors


Adjustable p.f. response value, from 0 to 0.97
Current range up to 8 A
For motors up to approx. 5 A, phase-sequence independent
Suitable for transformer connection
LED display for operation and alarm
Automatic resetting of alarm

Monitoring of asynchronous motors for underload and no-load operation, e.g. for fan monitoring in the case of V-belt breakage, for
monitoring filters in the event of filter blockages, for pump monitoring
in the event of valve closure or dry runs, or for general power factor
monitoring.

Selection and ordering data


Ie

Uc

Measuring
range

V AC

A AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.065

p.f. monitors with transparent cap


for monitoring of the underload of motors up to approx. 5 A AC by
making p.f. measurements, setting range p.f. from 0 to 0.97
Contact, 1 CO contact
4
3 400
0.4 ... 8

027

5TT3 472

5TT3 435 level relays

Overview

Application

3 electrode connections for 1-step and 2-step level control


All standard products can be used as electrodes
High immunity to interference of the measuring circuit isolated from
the system
Max. cable length to the electrodes: 1500 m
Large setting range: 2 to 450 k,
which enables differentiation between foam and liquid
Programmable for open-circuit principle (with bridge X2 COM) or
closed-circuit principle (without jumper)
Separately adjustable delay times for tv min and tv max, 0.2 to 2 s.

Level monitoring and control of conductive liquids and powders,


e.g. maximum and minimum levels, overflow and dry run protection.
Monitoring and control of mixture ratio of conductive liquids. General
resistance monitoring tasks, e.g. temperature limit detection with
PTC.
LED displays:
Green LED: lights up if operational voltage is applied
Yellow LED: lights up if MIN output relay is activated
Red LED: lights up if MAX output relay is activated.

Selection and ordering data


Ue

Ie

Uc

V AC

V AC

230

230

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Level relays with transparent cap


2

5TT3 435

027

0.162

5TG8 223

027

0.100

1/24

Immersion electrodes
Made of stainless steel, with PG13 sealing cap
Temperature range 0 ... 60 C
Suitable for pure water in open containers
with terminal connection

11/14

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Monitoring Devices
5TT3 43 thermistor motor protection relays

Overview

Application

For the detection of


- temperature limits being exceeded
- wire breaks in sensor circuits
1 input for 1 to 6 thermistors
With 2 LEDs green/yellow for ready-to-run and fault
Response value: 3.2 to 3.8 k
Release value: 1.5 to 1.8 k
Max. cable length of sensor supply cable NYM 2 1.5 is 100 m
Remote reset: over A1/A2 (NC contact) or over X1/X2 (NO contact)

For the prevention of thermal motor overloads, e.g. due to high


switching frequency, single-phasing, disabled cooling or excessive
ambient temperatures.
LED displays:
Green LED: lights up if operational voltage is applied
Red LED: lights up in the event of overtemperature or an
interruption in the sensor circuit

Selection and ordering data


Ue

Ie

Uc

V AC

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

0.160
0.160

1
1

1
2
3
4
5

Unit(s)

Thermistor motor protection relays with transparent cap


with fault storage,
reset pushbutton and remote reset

230
230

5
5

230
230

2
2

5TT3 431
5TT3 432

027
027

5TT3 431

6
7
8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

11/15

17

Monitoring Devices
5TT7 1 GSM alarm modules

Benefits

Application

Mobile monitoring and control of electrical plants and system


components
Fast and reliable alarm message by SMS
Simple operation and parameterization by means of SMS
Saves space and can be retrofitted in any plant
1 administrator telephone number from any mobile network for
configuration
Transmission of alarm messages to up to 5 cell phones
Customized tests for 2 alarm inputs and switchable output.

The GSM alarm module (GSM = Global System for Mobile Communications) enables cost-effective remote control of industrial and
private building management, e.g. of heating, air-conditioning and
cooling systems. But it is also possible to safely control elevators
and escalators and all kinds of production equipment, such as
machines, automatic devices and conveyor belts. The GSM alarm
module is particularly suitable for distant plants, such as monitoring
the heating of summer houses or the pumps of a water treatment
plant.
By using voltage relays, current relays, fuse monitors, miniature
circuit-breakers, residual current operated circuit-breakers or surge
suppressors fitted with auxiliary switches or signal contacts there are
virtually no limits to the type of monitoring tasks that can be carried
out. The use of remote control mechanisms with miniature circuitbreakers and residual current operated circuit-breakers also allows
realization of a range of cost-effective solutions.
Note:
Because the availability of mobile networks cannot be guaranteed,
GSM alarm modules should not be used for safety-relevant control
functions.

Selection and ordering data


Ue

Ie

Uc

V AC

A AC

V DC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

GSM alarm modules


for GSM network operatin with two alarm inputs
and one switching output
230
5
24
With backup battery for signaling in the event of
power failures

5TT7 110-0

027

0.205

230

5TT7 120-0

027

0.250

Rod aerial with magnet base, MMC connection


and connecting cable

5TT7 908-1

027

0.070

Flat form for adhesion, with MMC connection


and connecting cable

5TT7 908-2

027

0.050

24

Aerials

11/16

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

SR60 Busbar System

12/2

Busbar supports,
connection methods

12/3

Components with fuses, device


adapters and equipment racks

12/6

Partition components

12/7

Assembly kits for ALPHA


distribution boards

12

12/1

SR60 Busbar System


Busbar supports, connection methods

Selection and ordering data


Dimensions
WHD

Order No.

mm mm mm

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Busbar supports
for SR60 busbar system
for busbars with a bar thickness of 5 or 10 mm
and a 12, 15, 20, 25 or 30 mm busbar height
60 mm busbar distance
external
3-phase
internal
3-phase
internal
4-phase

20 215 50
20 191 50
20 245 51/56

8US19 23-2AA01
8US19 23-3AA01
8US19 23-4AA00

103
103
103

0.200
0.200
0.269

10
10
10

N/PE busbar supports


for mounting onto busbar supports,
can also be used as single support
1-phase

26 63 51

5SH3 506

016

0.060

4/240

8US19 21-1BA00

103

0.397

8US19 21-1AA00
5SH3 535

103
016

0.607
1.657

1
1

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

8US19 23-3AA01

SR60 connecting terminal plates, with cover1)

3-phase, for conductor 6 ... 50 mm2


3-phase, for conductor 35 ... 120 mm2
3-phase, for conductor 150 ... 300 mm2

5SH3 535
1)

illustration without cover

Accessories
Conductor
cross-section

Tightening
torque

up to mm2

Nm

Order No.

Price

1 unit

Terminals
Terminals for one busbar
12 mm 5 mm

8JH4 102

8JH4 105

8JH4 102
8JH4 104

046
046

0.010
0.030

10
10

16
16
25

... 70
... 95
... 120

6.0
10.0
10.0

8JH4 105
8JH4 106
8JK3 061

046
046
046

0.030
0.070
0.090

10
10
10

16
16
25

... 35
... 70
... 50

6.0
10.0
10.0

8JH4 105
8JH4 106
8JK3 061

046
046
046

0.030
0.070
0.090

10
10
10

6.0

8JK3 201

046

0.100

10

8US19 41-2BB00

103

0.307

8JK3 061

8JK3 061
Extension terminals
for 12 mm 5 mm busbar
busbar not included in delivery
(1 set = 2 units)

Terminals for circular conductors


20 mm 5 mm to
30 mm 10 mm
150

12/2

1.4
3.0

8JH4 104

Terminals for two busbars


12 mm 10 mm

8JH4 105

1.5 ... 16
16
... 35

Siemens ET B1 2007

... 240

* You can order this quantity or a multiple thereof.

SR60 Busbar System


Components with fuses,
device adapters and equipment racks

Selection and ordering data


Size

Rated current

Rated voltage

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

NEOZED SR60 bus-mounting bases


for busbar thickness 5 mm
NEOZED adapter sleeves
3-pole
D02
63
excess width with clearance for wiring

400

5SG6 202

016

0.141

4/104

D02
for busbar thickness 10 mm
NEOZED adapter sleeves
3-pole

63

400

5SG6 204

016

0.154

4/104

D02

63

400

5SG6 203

016

0.138

4/104

400

5SG6 205

016

0.149

4/104

25
63

500
690

5SF6 014
5SF6 214

016
016

0.230
0.318

2/52
2/52

for use of DIAZED screw adapters


3-pole
DII
25
DIII
63

500
690

5SF6 015
5SF6 215

016
016

0.222
0.310

2/52
2/52

25
63

500
690

5SF6 016
5SF6 216

016
016

0.233
0.316

2/52
2/52

for use of DIAZED screw adapters


3-pole
DII
25
DIII
63

500
690

5SF6 017
5SF6 217

016
016

0.220
0.328

2/52
2/52

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

excess width with clearance for wiring


D02
63
DIAZED SR60 bus-mounting bases
for busbar thickness 5 mm
for use of DIAZED SR60 adapter rings
3-pole
DII
DIII

for busbar thickness 10 mm


for use of DIAZED SR60 adapter rings
3-pole
DII
DIII

Size

MW

Order No.

Price

1 unit
NEOZED SR60 covers
D02

1.5

5SH5 241

016

0.026

4/200

excess width with clearance for wiring


D02

5SH5 242

016

0.031

4/140

with double width for a larger clearance for wiring


D02

5SH5 243

016

0.040

4/120

2.3
3.2

5SH2 042
5SH2 242

016
016

0.050
0.061

2/120
2/120

DIAZED SR60 covers


DII
DIII

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

with double width for a larger clearance for wiring


DII
DIII

* You can order this quantity or a multiple thereof.

4.7
6.4

5SH2 043
5SH2 243

016
016

0.084
0.106

Siemens ET B1 2007

2/60
2/30

12/3

16
17

SR60 Busbar System


Components with fuses,
device adapters and equipment racks
Size

Thread

For fuse links

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

DIAZED SR60 adapter rings


only for DIAZED SR60 bus-mounting bases
DII

E 27

2
4
6
10
16
20

5SH3 071
5SH3 072
5SH3 073
5SH3 074
5SH3 075
5SH3 076

016
016
016
016
016
016

0.005
0.005
0.005
0.005
0.005
0.004

10/1500
10/1500
10/3000
10/4000
10/5000
10/3000

DIII

E 33

2
4
6

5SH3 078
5SH3 080
5SH3 081

016
016
016

0.008
0.008
0.008

10
10
10

10
16
20
25
35
50

5SH3 082
5SH3 083
5SH3 084
5SH3 085
5SH3 086
5SH3 087

016
016
016
016
016
016

0.008
0.008
0.006
0.007
0.006
0.005

10
10
10
10/1000
10/3500
10/600

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

For NEOZED screw caps, adapter sleeves and fuse links, see the Chapter "Low-voltage fuse systems",
NEOZED fuse systems.
For DIAZED screw caps, screw adapters and fuse links, see the Chapter "Low-voltage fuse systems",
DIAZED fuse systems.

AC rated
current

AC rated
voltage

NEOZED SR60 bus-mounting switch disconnectors


for bar thickness 5 and 10 mm
for 3-phase busbar system
Width: 1.5 MW
3-pole
Size D02
63
400

Order No.

Price

1 unit

5SG7 230

016

0.700

1/20

3NW7 430

018

0.700

1/40

Auxiliary switches
1 CO contact, 24 to 230 V AC, 2 A AC

5SH5 525

016

0.007

1/50

Lateral modules
for NEOZED SR60 bus-mounting switch disconnectors
for better heat dissipation at permanent loads over 35 A
Width: 0.5 MW

5SH5 526

016

0.060

1/50

Reducers
for NEOZED fuse links D01
in the SR60 bus-mounting switch disconnector

5SH5 527

016

0.003

10/100

2 4 6

1 3 5

SR60 bus-mounting disconnectors


for 10 x 38 mm cylindrical fuses
for bar thickness 5 and 10 mm
for 3-phase busbar system
3-pole
32

690

2 4 6

1 3 5

12/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

SR60 Busbar System


Components with fuses,
device adapters and equipment racks
Order No.

Price

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

014
014

0.641
0.646

1
1

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

1 unit
SR60 LV HRC bus-mounting fuse bases
size 000 and 00
with cover, top terminals,
for 5 and 10 mm busbar thickness
3-pole
Terminals up to 70 mm2
Rated voltage 690 V AC
with saddle-type terminal connection
with flat connection, screw M8

Iu

For LV HRC Conductor


fuse links
cross-section

Sizes

3NH4 052
3NH4 053

Type of connection/
adapter

Order No.

up to mm2

Price

1 unit

Fuse switch disconnectors


for SR60 busbars
climate-proof, rated operational voltage 690 V AC
delivered without LV HRC fuse links
100
000 and 00 1.5 ... 35
top
bottom

Unit(s)

Unit(s)

3NP40 16-1CK01
3NP40 16-1CJ01

103
103

0.916
0.950

1
1

160

000 and 00

up to 2 70

top
bottom

3NP40 76-1CE01
3NP40 76-1CF01

103
103

1.203
1.201

1
1

160

000 and 00

250

0 and 1

2.5 ... 70
(SIGUT terminal)
max. 150

top
bottom
top or bottom

3NP40 76-1CK01
3NP40 76-1CJ01
3NP42 76-1CG01

103
103
103

1.295
1.249
3.713

1
1
1

400

max. 240

top or bottom

3NP43 76-1CG01

103

5.440

630

max. 2 240

top or bottom

3NP44 76-1CG01

103

7.688

Conduc- Length
tor cross- of
section
adapter

Width of Un
adapter

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

690

8US12 50-5RM07

103

0.174

1/6

Device adapters with top connecting cables


1
25
4
182
45

690

103

0.183

55

690

N
N

8US12 51-5DM07

8US12 61-5FM08

103

0.263

Device adapters with Cage Clamp connections


1
12.5
2.5
182
45

690

8US12 51-5CM47

103

0.190

1/4

56

10

182

45

5
6
7
9

mm2

Device adapters with top terminal


1
25
4
182

3
4

For additional busbar adapters, see Catalog LV 1.


For additional fuse switch disconnectors, see Chapter "Low-voltage fuse systems".

Number of
Rated
mounting rails current
(35 mm)

1
2

10
11
12

8US12 51-5DM07
Equipment racks for lateral mounting on device adapters of the
same length

13

1
--182
45
Connecting plates (2 units required for mounting)

--

8US12 50-5AM00

103

0.158

--

--

8US19 98-1AA00

103

10.000

100

--

--

--

--

14
15

8US12 50-5AM00
Lateral modules for widening device adapters and equipment
racks of the same length
--

--

--

182

13.5

--

8US19 98-2BM00

103

0.036

16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

12/5

17

SR60 Busbar System


Partition components

Selection and ordering data


Length

Order No.

mm

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

SR60 covers
Bases
Height
230 mm, for 3 busbars
290 mm, for 4 busbars

1100

5SH3 526
5SH3 527

016
016

1.100
1.300

2
2

32 mm

1000

5SH3 537

016

0.075

Cover profiles for busbars


up to 30 x 5 mm
up to 30 x 10 mm

1000

8US19 22-2AA00
8US19 22-2BA00

103
103

0.156
0.105

10
10

1100

5SH3 528
5SH3 530

016
016

0.311
0.583

2
2

1100

5SH3 531

016

0.365

Blanking covers
Depth

Edges
Height x width
17 x 36 mm, for 3 busbars
77 x 36 mm, for 4 busbars

Partitions, slotted
Height x width
17 x 86 mm

12/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

SR60 Busbar System


Partition components
Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

SR60 covers
End covers for busbar supports, lateral
Height
230 mm

5SH3 533

016

0.038

290 mm (1 set = 2 right and 2 left end covers)

5SH3 534

016

0.048

4/40

1
2
3
4
5

End covers for busbar support, top


3-pole
4-pole

8US19 22-1AC00
8US19 22-1AB00

103
103

0.020
0.055

10
1

5SH3 532

016

0.106

5SH3 536

016

0.040

4/160

Edge supports and supports for partitions

Supports for blanking cover


for blanking cover

6
7
8
9

Assembly kits for ALPHA distribution boards

Selection and ordering data


External
dimensions
Height
mm

Order No.
Width
mm

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.500
0.700
0.900
0.650
0.900
1.150

1
1
1
1
1
1

Assembly kits for ALPHA distribution boards


60 mm busbar spacing
300

450

250
500
750
250
500
750

8GK4 801-2KK13
8GK4 801-2KK23
8GK4 801-2KK33
8GK4 801-3KK13
8GK4 801-3KK23
8GK4 801-3KK33

039
039
039
039
039
039

10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

12/7

17

SR60 Busbar System


Notes

12/8

Siemens ET B1 2007

Busbars for Modular


Installation Devices

General Data

13/2

Introduction

For Fuse Systems

13/3
13/4
13/5
13/6
13/6

NEOZED fuse bases


NEOZED fuse disconnectors
MINIZED switch disconnectors
DIAZED fuse links
Cylindrical fuse systems

For Miniature CircuitBreakers and Residual


Current Protective
Devices

13/7

5ST3 7 busbars with pin-type


connections
5ST3 6 busbars with pin-type
connections
5ST2 13 ... 5ST2 16 busbars with
fork-type connections
5ST2 18, 5ST2 19 busbars with
fork-type connections
5ST2 4 busbars with fork-type
connections

13/8
13/10
13/11
13/12

For Lightning and


Overvoltage Protection
Devices

13/13

Lightning and overvoltage


protection devices

For Control Switches

13/14

Control switches

13

13/1

Busbars for Modular Installation Devices


General Data
Introduction

Overview
Busbars serve the safe and fast connection of modular installation
devices, such as miniature circuit-breakers, residual current operated circuit-breakers and switching and control devices.
A selection of important parameters:
Types of busbar (fork-type, pin-type)
Busbar cross-section (current load rating)
Device pole numbers
(e.g. 1, 2, 3, 4-pole, (1 + N)-pole, (3 + N)-pole
Implementation of additional devices (e.g. auxiliary switches and
fault signal contacts)

13/2

Siemens ET B1 2007

Busbars for Modular Installation Devices


For Fuse Systems
NEOZED fuse bases

Selection and ordering data


Size

Length
approx.
mm

Conductor
crosssection
mm2

Load
capacity
up to
A

For
MW
terminals1)

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Busbars
The load capacity values are valid for centered infeed.
Fork-type terminals, non-insulated
1-pole
D01 and
D02

1000
1000

20
36

116
168

FR0, K
FR0, K

1.5
1.5

5SH5 321
5SH5 322

016
016

0.214
0.321

1/50
1/50

Fork-type terminals, insulated


1-pole
D01/D02

1000

24

160

FR0, K

1.5

5SH5 517

016

0.550

1/50

3-pole
D01/D02

1000

16

120

FR0, K

1.5

5SH5 320

016

0.843

1/20

Pins, insulated
Degree of pollution 2
1-pole
D01/D02

1000

16

130

FR2, S

1.5

5ST3 703

027

0.190

1/50

3-pole
D01/D02

1000

16

120

FR2, S

1.5

5ST3 714

027

0.430

1/20

for 5SH5 320,


for 5ST3 714

5SH5 514
5ST3 750

016
027

0.001
0.001

10
10

for 5SH5 517, 5ST3 703

5ST3 748

027

0.001

10

End caps for busbars

1)

1
2
3
4
5
6
7
8
9
10
11

For terminal versions, see chapter "Low-voltage fuse systems".

12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

13/3

17

Busbars for Modular Installation Devices


For Fuse Systems
NEOZED fuse bases
Version/size

Conductor
cross-section

Order No.

mm2

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Busbar terminals
Non-insulated, pin-type

6 ... 35

5ST2 203

027

0.001

1/20

Insulated, for clipping onto fork-type or pin-type

6 ... 35

5ST2 157

027

0.030

10

Insulated, fork-type

6 ... 25

5SH5 328

016

0.014

10/300

Insulated, pin-type

2 ... 25

5SH5 327

016

0.014

10/300

Non-insulated, pin-type

2 ... 16

5SH5 326

016

0.016

10

Version

Order No.

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

NEOZED fuse disconnectors

Selection and ordering data


Size

Length
approx.

Conductor
Load
cross-section capacity
up to

mm

mm2

Price

1 unit

The load capacity values are valid for centered infeed.


Fork, insulated
Degree of pollution 2
Busbars, 1-phase
D01

220
1000

16
16

120
120

with end caps

5ST2 186
5ST2 190

027
027

0.090
0.500

1/50
1/20

16
16

120
120

with end caps

5ST2 187
5ST2 191

027
027

0.160
0.710

1/25
1/20

220
16
1000
16
End caps for busbars

120
120

with end caps

5ST2 188
5ST2 192

027
027

0.230
1.100

1/25
1/20

5ST3 748
5ST2 197

027
027

0.001
0.001

10
10

Busbars, 2-phase
D01
220
1000
Busbars, 3-phase
D01

1-phase
2 and 3-phase

13/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Busbars for Modular Installation Devices


For Fuse Systems
MINIZED switch disconnectors

Selection and ordering data


Size

Length
approx.
mm

Conductor
crosssection
mm2

Load
capacity
up to
A

For
MW
terminals1)

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

0.430
0.100

1/20
1/25

0.012

1/50

Unit(s)

For MINIZED D01, draw-out technology, mounting depth: 55 mm


Busbars
Pins, insulated, degree of pollution 2, 3-pole
D01
1000
16
120
D01
216
16
120

R
R

1
1

5ST3 710
5ST3 708

027
027

5SH5 510

Terminals
not insulated, up to 25 mm2

For MINIZED D02, draw-out technology, mounting depth: 70 mm

1
2
3
4
5

Busbars
Pins, insulated, degree of pollution 2
1-pole
D02

1000

16

130

FR2

1.5

5ST3 703

027

0.190

1/50

3-pole
D02

1000

16

120

FR2

1.5

5ST3 714

027

0.430

1/20

for 5ST3 708, 5ST3 710, 5ST3 714

5ST3 750

027

0.001

10

for 5ST3 703

5ST3 748

027

0.001

10

End caps for busbars

6
7
8
9

1)

For terminal versions, see chapter "Low-voltage fuse systems".

10
11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

13/5

17

Busbars for Modular Installation Devices


For Fuse Systems
DIAZED fuse links

Selection and ordering data


Size

Thread

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

DIAZED busbars with oblong holes


DIAZED busbars with oblong holes
Approx. 1000 mm long
Cross-section: 12 mm 2 mm, load capacity up to 80 A
for DII, sufficient for 25 bases,
Cross-section: 13 mm 3 mm, load capacity up to 120 A
for DIII, sufficient for 19 bases

5SH3 500

016

0.095

1/25

5SH3 501

016

0.180

1/25

Terminals, non-insulated
Pin, for 2 conductors, from 2 1.5 mm2 to 16 mm2

5SH5 326

016

0.016

10

Fork-type, for conductors up to 35 mm2

5SH3 502

016

0.010

10/50

5SH3 54
5SH3 55
5SH3 56

016
016
016

0.740
0.740
0.740

1/5
1/5
1/5

8JH4 122
8JH4 124

046
046

0.012
0.024

10
10

PG

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Busbars for DIAZED EZR bus-mounting bases


Busbars for DIAZED EZR bus-mounting bases
suitable for fork-type terminal connection,
ready-made drilling with thread for screw adapters,
approx. 2000 mm long
Cross-section: 16 mm x 3 mm, load capacity up to 150 A
for lateral infeed
for DII
for DII and DIII
for DII

sufficient for 42 5SF6 005 bases


sufficient for 34 5SF6 205 bases
sufficient for 27 5SF2 07 bases

EZR bus-mounting terminals


Non-insulated
for conductors up to 16 mm2
for conductors up to 35 mm2

Cylindrical fuse systems

Selection and ordering data


Size

Length
approx.

Conductor
Load
cross-section capacity
up to

mm

mm2

Version

Order No.

Price

1 unit

Busbars with pins, insulated


The load capacity values are valid for centered infeed.
Degree of pollution 2
Busbars, 1-phase
8 x 32 and 220
10 x 38
1000
14 x 51
1000
Busbars, 2-phase

16
16

120
120

16

120

fully insulated

027
027

0.040
0.190

1/50
1/50

5SH5 324

016

0.320

1/50

8 x 32 and 220
10 x 38
1000
Busbars, 3-phase

16

120

5ST3 704

027

0.060

1/25

16

120

5ST3 705

027

0.290

1/20

8 x 32 and 220
10 x 38
1000

16
16

120
120

5ST3 708
5ST3 710

027
027

0.100
0.430

1/25
1/20

14 x 51
1000
16
End caps for busbars

120

5SH5 323

016

0.843

1/20

5ST3 748
5ST3 750

027
027

0.001
0.001

10
10

1-phase
2 and 3-phase

fully insulated

5ST3 700
5ST3 701

Busbars also suitable for SITOR cylindrical fuse switch


disconnectors.

13/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Busbars for Modular Installation Devices


For Miniature Circuit-Breakers and Residual Current Protective Devices
5ST3 7 busbars with
pin-type connections

Application
For miniature circuit-breakers; 5SJ6, 5SY6, 5SY4, 5SY7, 5SY8,
5SY5
For 5SM3 and 5SU1 residual current operated circuit-breakers
Standards: IEC 60664-1, EN 60439-1
Pin-type connections
Single and multi-phase

Cu 10 mm2, 16 mm2, fully insulated


Lug spacing: 18 mm
No additional connection terminal required for stranded
connections up to 35 mm2
Excellent accessibility of the feeder cables

3
4

Selection and ordering data


Length

Order No.

mm

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

5ST3 7 busbar system


Busbars 10

1
2

mm2

fully insulated
1-phase
1-phase + AS/FC
2-phase
2-phase + AS/FC

214

6
7

5ST3 730
5ST3 732
5ST3 734
5ST3 736

027
027
027
027

0.040
0.040
0.060
0.060

1/50
1/50
1/25
1/25

3-phase
3-phase + AS/FC
3 x (1-phase + AS/FC)

5ST3 738
5ST3 741
5ST3 743

027
027
027

0.100
0.100
0.100

1/25
1/25
1/25

4-phase

5ST3 745

027

0.150

1/20

5ST3 731
5ST3 733

027
027

0.190
0.190

1/50
1/50

2-phase
2-phase + AS/FC
3-phase
3-phase + AS/FC
3 x (1-phase + AS/FC)

5ST3 735
5ST3 737
5ST3 740
5ST3 742
5ST3 744

027
027
027
027
027

0.290
0.290
0.430
0.430
0.430

1/20
1/20
1/20
1/20
1/20

4-phase

5ST3 746

027

0.700

1/15

5ST3 700
5ST3 702
5ST3 704
5ST3 706

027
027
027
027

0.040
0.040
0.060
0.060

1/50
1/50
1/25
1/25

3-phase
3-phase + AS/FC
3 x (1-phase + AS/FC)

5ST3 708
5ST3 711
5ST3 713

027
027
027

0.100
0.100
0.100

1/25
1/25
1/25

4-phase

5ST3 715

027

0.150

1/20

5ST3 701
5ST3 703

027
027

0.190
0.190

1/50
1/50

2-phase
2-phase + AS/FC
3-phase
3-phase + AS/FC
3 x (1-phase + AS/FC)

5ST3 705
5ST3 707
5ST3 710
5ST3 712
5ST3 714

027
027
027
027
027

0.290
0.290
0.430
0.430
0.430

1/20
1/20
1/20
1/20
1/20

4-phase

5ST3 716

027

0.700

1/15

13

End caps
for lateral insulation of cut-to-length busbars
1-phase
2 and 3-phase
4-phase

5ST3 748
5ST3 750
5ST3 718

027
027
027

0.001
0.001
0.001

10
10
10

14

without end caps


1-phase
1-phase + AS/FC

Busbars 16 mm
fully insulated

1016

8
9

1-phase
1-phase + AS/FC
2-phase
2-phase + AS/FC

without end caps


1-phase
1-phase + AS/FC

214

1016

10
11
12

AS/FC = Auxiliary switches (AS) or fault signal contacts (FC)

15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

13/7

17

Busbars for Modular Installation Devices


For Miniature Circuit-Breakers and Residual Current Protective Devices
5ST3 6 busbars with
pin-type connections

Application
For miniature circuit-breakers; 5SJ6, 5SY6, 5SY4, 5SY7, 5SY8,
5SY5
For 5SM3 and 5SU1 residual current operated circuit-breakers
Standards: IEC 60664-1, EN 60439-1
Pin-type connections
Any length possible thanks to the combination of 3 fixed busbar
lengths

Favorable current and temperature conduction thanks to the overlapping of individual components
No further need for time-consuming tasks, such as cutting, cutting
to length, deburring, cleaning of cut surfaces and mounting of end
caps
Safe touch protection for non-assigned connections.

Selection and ordering data


Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

5ST3 6 busbar systems


Busbars 10 mm2
fully insulated
5ST3 613

5ST3 614

5ST3 615

1-phase
2 x 1-phase
6 x 1-phase
12 x 1-phase

5ST3 600
5ST3 601
5ST3 602

027
027
027

0.005
0.018
0.036

1/10
1/10
1/10

2 x (1-phase + AS/FC)
6 x (1-phase + AS/FC)
9 x (1-phase + AS/FC)

5ST3 603
5ST3 604
5ST3 605

027
027
027

0.008
0.024
0.036

1/10
1/10
1/10

2-phase
2 x 2-phase
3 x 2-phase
6 x 2-phase

5ST3 606
5ST3 607
5ST3 608

027
027
027

0.016
0.024
0.048

1/10
1/10
1/10

2 x (2-phase + AS/FC)
3 x (2-phase + AS/FC)
5 x (2-phase + AS/FC)

5ST3 610
5ST3 611
5ST3 612

027
027
027

0.020
0.030
0.050

1/10
1/10
1/10

3-phase
2 x 3-phase
3 x 3-phase
4 x 3-phase

5ST3 613
5ST3 614
5ST3 615

027
027
027

0.039
0.060
0.076

1/10
1/10
1/10

2 x (3-phase + AS/FC)
4 x (3-phase + AS/FC)

5ST3 616
5ST3 617

027
027

0.040
0.080

1/10
1/10

2 x (3 x (1-phase) + AS/FC)1)
3 x (3 x (1-phase) + AS/FC)1)
4-phase

5ST3 618
5ST3 620

027
027

0.044
0.066

1/10
1/10

2 x 4-phase
3 x 4-phase
2 x 3 x (1-phase + N)2)

5ST3 621
5ST3 622
5ST3 623

027
027
027

0.051
0.078
0.078

1/10
1/10
1/10

3-phase, for a 4-pole 5SM3 RCCB with 8 miniature circuit-breakers:


3/N + 8 terminals

5ST3 624

027

0.075

1/10

5ST3 655

027

0.003

1/10

5ST3 656

027

5.330

Touch protection
for free connections, yellow (RAL 1004)

1 set

Assortments
20 x 5ST3 613 + 10 x 5ST3 614 +
50 x 5ST3 615 + 50 x 5ST3 655

1 set

AS/FC = Auxiliary switches (AS) or fault signal contacts (FC)


1)
3 x (1-phase + AS/FC) r (L1 + AS/FC, L2 + AS/FC, L3 + AS/FC).
2)

3 x (1-phase + N) r (L1 + N, L2 + N, L3 + N).

13/8

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Busbars for Modular Installation Devices


For Miniature Circuit-Breakers and Residual Current Protective Devices
5ST3 6 busbars with
pin-type connections
Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

5ST3 6 busbar systems


Busbars 16 mm2
fully insulated
5ST3 643

1-phase

5ST3 644

2 x 1-phase
6 x 1-phase
12 x 1-phase
2 x (1-phase + AS/FC)
6 x (1-phase + AS/FC)
9 x (1-phase + AS/FC)

5ST3 630
5ST3 631
5ST3 632
5ST3 633
5ST3 634
5ST3 635

027
027
027
027
027
027

0.008
0.025
0.048
0.013
0.039
0.059

1/10
1/10
1/10
1/10
1/10
1/10

2 x 2-phase
3 x 2-phase
6 x 2-phase
2 x (2-phase + AS/FC)
3 x (2-phase + AS/FC)
5 x (2-phase + AS/FC)

5ST3 636
5ST3 637
5ST3 638
5ST3 640
5ST3 641
5ST3 642

027
027
027
027
027
027

0.024
0.039
0.076
0.026
0.045
0.084

1/10
1/10
1/10
1/10
1/10
1/10

3-phase
2 x 3-phase
3 x 3-phase
4 x 3-phase
2 x (3-phase + AS/FC)
4 x (3-phase + AS/FC)

5ST3 643
5ST3 644
5ST3 645
5ST3 646
5ST3 647

027
027
027
027
027

0.058
0.083
0.110
0.060
0.120

1/10
1/10
1/10
1/10
1/10

2 x (3 x (1-phase) + AS/FC)1)
3 x (3 x (1-phase) + AS/FC)1)

5ST3 648
5ST3 650

027
027

0.061
0.093

1/10
1/10

2 x 4-phase
3 x 4-phase
2 x 3 x (1-phase + N)2)
3-phase, for a 4-pole 5SM3 RCCB with 8 miniature circuit-breakers:

5ST3 651
5ST3 652
5ST3 653

027
027
027

0.080
0.116
0.116

1/10
1/10
1/10

3/N + 8 terminals

5ST3 654

027

0.114

1/10

Touch protection
for free connections, yellow (RAL 1004)

5ST3 655

027

0.003

1/10

5ST3 657

027

7.640

2-phase

5ST3 645

4-phase

1 set

Assortments
20 x 5ST3 643 + 10 x 5ST3 644 +
50 x 5ST3 645 + 50 x 5ST3 655

1 set

AS/FC = Auxiliary switches (AS) or fault signal contacts (FC)


1)

3 x (1-phase + AS/FC) r (L1 + AS/FC, L2 + AS/FC, L3 + AS/FC).

2)

3 x (1-phase + N) r (L1 + N, L2 + N, L3 + N).

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

13/9

17

Busbars for Modular Installation Devices


For Miniature Circuit-Breakers and Residual Current Protective Devices
5ST2 13 ... 5ST2 16 busbars
with fork-type connections

Application
For 5SX2 miniature circuit-breakers
For 5SM1 residual current protective devices
Fork-type connections
Single and multi-phase

Cu 10 mm2 to 16 mm2, fully insulated


Lug spacing: 18 mm
No additional connection terminal required for bottom connection.

Selection and ordering data


Version

Length

Order No.

mm

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

5ST2 13, 5ST2 14, 5ST2 15, 5ST2 16 busbar systems


Cu busbars 10 mm2
with end caps
1-phase
2-phase
3-phase

210

5ST2 137
5ST2 138
5ST2 140

027
027
027

0.088
0.103
0.153

1/25
1/10
1/10

5ST2 146
5ST2 147
5ST2 148

027
027
027

0.408
0.523
0.838

1/10
1/5
1/10

5ST2 142
5ST2 143
5ST2 144
5ST2 145

027
027
027
027

0.102
0.154
0.231
0.315

1/25
1/10
1/10
1/10

1000

5ST2 151
5ST2 152
5ST2 153
5ST2 154

027
027
027
027

0.487
0.692
1.100
1.498

1/10
1/5
1/10
1/5

1000

5ST2 163
5ST2 164
5ST2 165

027
027
027

0.460
0.900
1.490

1/5
1/5
1/10

5ST2 155
5ST2 156

027
027

0.013
0.017

10
10

5ST2 166
5ST2 167

027
027

0.020
0.020

1/10
1/10

5ST2 157

027

0.030

10

without end caps


1-phase
2-phase
3-phase

1000

Cu busbars 16 mm2
with end caps
1-phase
2-phase
3-phase
3-phase + N

210

without end caps


1-phase
2-phase
3-phase
3-phase + N
without end caps
lug spacing to match busbar mountings of devices
1-pole, 2-pole, 3-pole, each with
1 auxiliary switch respectively
1-phase + AS/FC
2-phase + AS/FC
3-phase + AS/FC
End caps
for lateral insulation of cut-to-length busbars
1 and 2-phase
3 and 4-phase
Connection terminals up to 35 mm2 (stranded)
for top or bottom direct infeed into miniature
circuit-breakers; side-by-side mounting possible
for 1- and 2-phase busbars
for 3- and 4-phase busbars
Connection terminals up to 35 mm2 (stranded)
for direct infeed into miniature circuit-breakers,
side-by-side mounting posssible

AS/FC = Auxiliary switches (AS) or fault signal contacts (FC)

13/10

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Busbars for Modular Installation Devices


For Miniature Circuit-Breakers and Residual Current Protective Devices
5ST2 18, 5ST2 19 busbars with
fork-type connections

Application
For 5SX2 miniature circuit-breakers
For 5SM1 residual current protective devices
Fork-type connections

Single and multi-phase


Cu 10 mm2 to 16 mm2, fully insulated
Lug spacing: 17.8 mm

Selection and ordering data


Version

Length

Order No.

mm

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

1
2
3
4

5ST2 18, 5ST2 19 busbar systems


Cu busbars 10 mm2
with end caps
1-phase
2-phase
3-phase

214

5ST2 180
5ST2 181
5ST2 182

027
027
027

0.060
0.080
0.110

1/50
1/25
1/25

5ST2 183
5ST2 184
5ST2 185

027
027
027

0.290
0.600
0.820

1/20
1/20
1/20

5ST2 186
5ST2 187
5ST2 188

027
027
027

0.090
0.160
0.230

1/50
1/25
1/25

5ST2 190
5ST2 191
5ST2 192

027
027
027

0.500
0.710
1.100

1/20
1/20
1/20

without end caps


1-phase
2-phase
3-phase

1016

Cu busbars 16 mm2
with end caps
1-phase
2-phase
3-phase

214

without end caps


1-phase
2-phase
3-phase

1016

5ST2 193
5ST2 194
5ST2 195

027
027
027

0.450
0.890
1.470

1/10
1/10
1/10

5ST2 196
5ST2 197

027
027

0.001
0.001

1/10
10

End caps
for Cu busbars, for the lateral insulation of cut-to-length busbars
1-phase
2 and 3-phase

6
7
8
9

without end caps


lug spacing to match busbar mountings of devices
1-pole, 2-pole, 3-pole, each with 1 auxiliary switch respectively
1-phase + AS/FC
1016
2-phase + AS/FC
3-phase + AS/FC

AS/FC = Auxiliary switches (AS) or fault signal contacts (FC)

10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

13/11

17

Busbars for Modular Installation Devices


For Miniature Circuit-Breakers and Residual Current Protective Devices
5ST2 4 busbars with
fork-type connections

Application
For 5SX2 miniature circuit-breakers
For 5SM1 residual current protective devices
Fork-type connections
Any length possible thanks to the combination of 3 fixed busbar
lengths

Favorable current and temperature conduction thanks to the overlapping of individual components
No further need for time-consuming tasks, such as cutting, cutting
to length, deburring, cleaning of cut surfaces and mounting of end
caps
Safe protection against contact for non-assigned connections

Selection and ordering data


Version

Order No.

Number of electrical circuits

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

5ST2 4 busbar systems


Cu busbars
1-phase
2 x 1-phase
6 x 1-phase
12 x 1-phase
2 x (1-phase + AS/FC)
6 x (1-phase + AS/FC)
9 x (1-phase + AS/FC)

5ST2 400
5ST2 401
5ST2 402
5ST2 403
5ST2 404
5ST2 405

027
027
027
027
027
027

0.006
0.017
0.033
0.008
0.024
0.036

1/20
1/20
1/20
1/20
1/20
1/20

2-phase
2 x 2-phase
3 x 2-phase
6 x 2-phase

5ST2 406
5ST2 407
5ST2 408

027
027
027

0.011
0.017
0.033

1/10
1/10
1/10

2 x (2-phase + AS/FC)
3 x (2-phase + AS/FC)
5 x (2-phase + AS/FC)

5ST2 410
5ST2 411
5ST2 412

027
027
027

0.023
0.034
0.056

1/10
1/10
1/10

3-phase
2 x 3-phase
3 x 3-phase
4 x 3-phase

5ST2 413
5ST2 414
5ST2 415

027
027
027

0.037
0.060
0.086

1/10
1/10
1/10

2 x (3-phase + AS/FC)
4 x (3-phase + AS/FC)
2 x (3 x (1-phase) + AS/FC)1)
3 x (3 x (1-phase) + AS/FC)1)

5ST2 416
5ST2 417
5ST2 418
5ST2 420

027
027
027
027

0.057
0.065
0.057
0.086

1/10
1/10
1/10
1/10

4-phase
2 x 4-phase
3 x 4-phase
2 x 3 x (1-phase + N)2)

5ST2 421
5ST2 422
5ST2 423

027
027
027

0.046
0.091
0.060

1/5
1/5
1/5

3-phase, for a 4-pole 5SM1 RCCB with


8 miniature circuit-breakers:
3/N + 8 terminals

5ST2 424

027

0.091

1/5

Feeder terminals
side-by-side mounting posssible, for supply to 35 mm2 busbar
system (stranded)

5ST2 425

027

0.024

1/10

Touch protection
for free connections, yellow (RAL 1004)

5ST2 426

027

0.004

1/10

AS/FC = Auxiliary switches (AS) or fault signal contacts (FC)


1)
3 x (1-phase + AS/FC) r 3 x (L 1 + AS/FC, L 2 + AS/FC, L3 + AS/FC).
2)

3 x (1-phase + N) r 3 x (L 1 + N, L 2 + N, L3 + N).

13/12

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Busbars for Modular Installation Devices


For Lightning and Overvoltage Protection Devices
Lightning and overvoltage protection devices

Selection and ordering data


Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Busbars
for arrester combinations
TN-S/TT and 4-pole residual current protective devices
(5SM1 and 5SM3)

5SD7 084

008

0.133

TN-S/TT and 4-pole miniature circuit-breakers (5SY)

5SD7 085

008

0.143

TN-C and 3-pole residual current protective devices


(5SM1 and 5SM3)

5SD7 086

008

0.079

TN-C and 3-pole miniature circuit-breaker (5SY)

5SD7 087

008

0.084

for multipole surge arresters


TN-S/TT and 4-pole miniature circuit-breaker (5SY)

5SD7 088

008

0.104

TN-C and 3-pole miniature circuit-breaker (5SY)

5SD7 090

008

0.064

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

13/13

17

Busbars for Modular Installation Devices


For Control Switches
Control switches

Selection and ordering data


Version

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

1-phase busbars
for all 5TE8 switches, 20 A and 32 A,
in the 12 MW version for the cutting of unused terminal lugs to
ensure insulation clearances if one device terminal is to be
supplied separately despite being mounted on the busbar,
modular clearance = 1 MW

5TE9 100

027

0.040

1/10

5TE9 101

027

0.060

1/10

5TE9 102

027

0.001

Infeed of the busbar at the device terminal with a conductor


cross-section of 6 mm2 to 32 A
can be mounted top or bottom in the front or rear terminal area
2-phase busbars
for all 5TE8 switches, 20 and 32 A, in 12 MW version, each with
1 MW division, whereby the two rails are offset by 0.5 MW.
Both copper conductors of the 2-phase busbar are insulated
together.
Infeed of the busbar at the device terminal with a conductor
cross-section of 6 mm2 to 32 A,
can be mounted from top or bottom, or in the front or rear terminal area, thus allowing realization of a 4-conductor connection
using two 2-phase busbars.
End caps for 2-phase busbars
end caps for 5TE9 101 2-phase busbars to keep insulation
clearances when the bar is being cut.

1 set
1 set

1 set = 10 units
5ST3 6 and 5ST3 7 busbar systems
for all 5TE8 switches,
32 A to 125 A in 1 MW per pole version,

see pages 13/7 to 13/9

13/14

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Modular Installation Devices,


Mounting Depth 55 mm >N<

Miniature
Circuit-Breakers

14/2
14/4
14/5

5SX2, 6 kA
Additional components for 5SX2
Accessories for 5SX2

Residual Current
Protective Devices

14/6

14/8
14/8

5SM1 residual current operated


circuit-breakers (RCCBs),
type A, 16 ... 80 A
Additional components for 5SM1
Accessories for 5SM1

Switches

14/9
14/9

5TE7 1 ... 5TE7 3 switches


5TE7 5 switches

Switching Devices

14/10
14/10
14/11

5TT5 remote control switches


5TT3 0 switching relays
5TT3 8 Insta contactors

Timers

14/12
14/12
14/13

5TT1 3 timers for building lighting


7LF4 4 digital time switches
7LF5 3 mechanical time switches

Transformers

14/14

4AC2 9 transformers

Monitoring Devices

14/15
14/15

7LQ2 1 dusk switches


5TT3 45 alarm sensors, 55/70 mm

14

14/1

Modular Installation Devices, Mounting Depth 55 mm >N<


Miniature Circuit-Breakers
5SX2, 6 kA

Application
Un: 230/400 V, 50 ... 60 Hz, can be used in systems up
to 250/440 V AC, 60 V DC per pole

Standards: IEC/EN 60898, DIN VDE 0641-11


Additional components can be retrofitted individually.

Selection and ordering data


In

MW

Price

PS*/
P. unit

1 unit

Unit(s)

Characteristic B
Order No.

PG

Price

Weight
1 unit
approx.

PS*/
P. unit

1 unit

kg

Unit(s)

Characteristic C
Order No.

PG

1-pole
2

0.3
0.5
1

1.6
2
3

----

5SX2 114-7
5SX2 105-7
5SX2 101-7

003
003
003

0.140
0.140
0.141

1
1/12
1/12

----

5SX2 115-7
5SX2 102-7
5SX2 103-7

003
003
003

0.140
0.141
0.140

1
1/12
1/12

003
003
003
003
003
003

0.141
0.138
0.140
0.141
0.140
0.134

1/12
1/12
1/12
1/12
1/12
1/12

4
6
8
10
13
16

-5SX2 106-6
-5SX2 110-6
5SX2 113-6
5SX2 116-6

20
25
321)

002

1/12

002
002
002

1/12
1/12
1/12

5SX2 104-7
5SX2 106-7
5SX2 108-7
5SX2 110-7
5SX2 113-7
5SX2 116-7

5SX2 120-6
5SX2 125-6
5SX2 132-6

002
002
002

1/12
1/12
1/12

5SX2 120-7
5SX2 125-7
5SX2 132-7

003
003
003

0.138
0.143
0.140

1/12
1/12
1/12

5SX2 506-6
5SX2 510-6
5SX2 513-6

002
002
002

1
1
1/6

5SX2 506-7
5SX2 510-7
5SX2 513-7

003
003
003

0.210
0.210
0.210

1/6
1/6
1/6

16
20
25

5SX2 516-6
5SX2 520-6
5SX2 525-6

002
002
002

1/6
1
1

5SX2 516-7
5SX2 520-7
5SX2 525-7

003
003
003

0.210
0.210
0.210

1/6
1
1

32

5SX2 532-6

002

5SX2 532-7

003

0.210

5SX2 205-7
5SX2 201-7
5SX2 215-7
5SX2 202-7
5SX2 203-7
5SX2 204-7

003
003
003
003
003
003

0.280
0.280
0.280
0.280
0.280
0.280

1
1/6
1
1/6
1/6
1/6

003
003
003

0.276
0.280
0.280

1/6
1
1/6

003
003
003
003
003

0.280
0.280
0.280
0.280
0.280

1
1/6
1/6
1/6
1/6

1-pole + N
2 N/14

1 N/13

6
10
13

2-pole
2 4

1 3

0.5
1
1.6
2
3
4

-------

6
8
10

5SX2 206-6
-5SX2 210-6

002

1/6

002

1/6

5SX2 206-7
5SX2 208-7
5SX2 210-7

13
16
20
25
32

5SX2 213-6
5SX2 216-6
5SX2 220-6
5SX2 225-6
5SX2 232-6

002
002
002
002
002

1
1/6
1
1
1

5SX2 213-7
5SX2 216-7
5SX2 220-7
5SX2 225-7
5SX2 232-7

The versions 5SX2 B 6 ... 32 and C 0.5 ... 32 1-pole, 2-pole and
3-pole are certified according to UL 1077 and CSA 22.2
No. 235-M 89 and can be used as supplementary protectors up to
277 V AC (1-pole) and 480 V AC (2-pole, 3-pole).
For additional components see page 14/4.
Accessories see page 14/5.
1)

Also suitable for 21-kW active power with three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). For continuous
load applications, we recommend using miniature circuit-breakers,
characteristic B or C and In = 40 A = 40 A.

14/2

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Modular Installation Devices, Mounting Depth 55 mm >N<


Miniature Circuit-Breakers
5SX2, 6 kA

Selection and ordering data


MW

In

Price

PS*/
P. unit

1 unit

Unit(s)

Characteristic B
Order No.

PG

Price

PG

Weight
1 unit
approx.

PS*/
P. unit

1 unit

kg

Unit(s)

Characteristic C
Order No.

3-pole
2 4 6

1 3 5

0.5
1
1.6

----

5SX2 305-7
5SX2 301-7
5SX2 315-7

003
003
003

0.440
0.440
0.440

1
1
1

2
3
4
6
8
10

---5SX2 306-6
-5SX2 310-6

003
003
003
003
003
003

0.440
0.440
0.440
0.440
0.440
0.440

1/4
1
1/4
1/4
1
1/4

13
16
20

5SX2 313-6
5SX2 316-6
5SX2 320-6

25
321)

002

002

1/4

5SX2 302-7
5SX2 303-7
5SX2 304-7
5SX2 306-7
5SX2 308-7
5SX2 310-7

002
002
002

1
1/4
1

5SX2 313-7
5SX2 316-7
5SX2 320-7

003
003
003

0.440
0.440
0.440

1
1/4
1/4

5SX2 325-6
5SX2 332-6

002
002

1
1/4

5SX2 325-7
5SX2 332-7

003
003

0.434
0.440

1/4
1/4

-5SX2 610-6
5SX2 613-6

002
002

1
1

5SX2 606-7
5SX2 610-7
5SX2 613-7

003
003
003

0.450
0.450
0.450

1
1
1/3

5SX2 616-6
5SX2 620-6
5SX2 625-6
5SX2 632-6

002
002
002
002

1
1
1
1

5SX2 616-7
5SX2 620-7
5SX2 625-7
5SX2 632-7

003
003
003
003

0.450
0.450
0.450
0.450

1/3
1
1
1/3

003
003
003
003
003
003

0.590
0.590
0.590
0.590
0.590
0.590

1
1
1
1
1
1

003

0.590

3-pole + N
2 4 6 N/14

1 3 5 N/13

6
10
13

16
20
25
32

4-pole
2 4 6 8

1 3 5 7

62)
102)
132)
162)
202)
252)

2)

32

----5SX2 420-6
5SX2 425-6

002
002

1
1

5SX2 406-7
5SX2 410-7
5SX2 413-7
5SX2 416-7
5SX2 420-7
5SX2 425-7

5SX2 432-6

002

5SX2 432-7

Also suitable for 21-kW active power with three-phase currents of 400 V
(e.g. continuous-flow heaters with short-time operation duty) or 7-kW active
power at 230 V AC (e.g. storage in not-continuous duty). For continuous
load applications, we recommend using miniature circuit-breakers,
characteristic B or C and In = 40 A = 40 A.

2)

Without

3
4
5
6
7
8
9
10

The versions 5SX2 B 6 ... 32 and C 0.5 ... 32 1-pole, 2-pole and
3-pole are certified according to UL 1077 and CSA 22.2
No. 235-M 89 and can be used as supplementary protectors up to
277 V AC (1-pole) and 480 V AC (2-pole, 3-pole).
For additional components see page 14/4.
Accessories see page 14/5.
1)

1
2

11
12

V mark.

13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

14/3

17

Modular Installation Devices, Mounting Depth 55 mm >N<


Miniature Circuit-Breakers
Additional components for 5SX2

Benefits
Additional components
Can be retrofitted individually
Can be connected to instabus KNX EIB and AS-Interface bus over
binary inputs.
Auxiliary switches (AS) and fault signal contacts (FC)
Mounting with factory-fitted clips
Max. contact load:
6 A, 230 V AC, AC-15
1 A, 220 V DC, DC-13
according to DIN VDE 0660-200, EN 60947-5-1
Short-circuit protection through 5SX2 ...-6, ...-7 miniature circuitbreakers with In = 6 A or gL 6 A fuse, depending on the version.
Remote display of the miniature circuit-breaker switching state
- AS: ON/OFF
- FC: tripped

Shunt trips (ST)


Assembly with enclosed screws
Applicable for voltages of 110 to 415 V AC
Short-circuit protection through 5SX2 ...-7 miniature circuit-breakers with In 16 A
Remote tripping of the miniature circuit-breaker
I2 _ 0 7 4 1 8 d

o r
S T

M C B

A C

o r

o r
F C

o u tp u t

A C

A C

A C

F C

in p u t
in s ta b u s K N X E IB

Selection and ordering data


Version

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Auxiliary switches (AS)


24 12

1 NO + 1 NC

0.5

5SX9 100

027

0.050

1/10

2 NO

5SX9 101

027

0.040

2 NC

5SX9 102

027

0.040

5SX9 200

027

0.040

2 NO

5SX9 201

027

0.040

2 NC

5SX9 202

027

0.040

5SX9 300

027

0.141

23 11
44 34
43 33
42 32
41 31

Fault signal contacts (FC)


24 12

1 NO + 1 NC

0.5

23 11
44 34
43 33
42 32
41 31

Shunt trips (ST) 100 % duty ratio


C2

C1

14/4

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Modular Installation Devices, Mounting Depth 55 mm >N<


Miniature Circuit-Breakers
Accessories for 5SX2

Selection and ordering data


Version

Length

Order No.

mm

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Mounting and cover parts


Cable links
cross-section 6 mm2
end sleeves at both ends

125
250

5ST1 292
5ST1 293

027
027

0.008
0.017

5/1000
5/500

for 16 mm2 1-wire or


10 mm2 stranded
width: 0.5 MW

5ST2 112

027

0.008

1/50

Spacers
(contour miniature circuit-breakers, 0.5 MW)

5ST2 122

027

0.009

1/10

Snap-on terminals

Elevation parts
for increasing height from 53 to 60 mm
snap-on adapter
1 MW

5ST2 120

027

0.002

1/200

5ST2 201

027

0.012

1/20

5ST2 168
5ST2 170

027
027

0.007
0.007

1/10
1/10

5SW3 004
5SW3 005

008
008

0.084
0.114

1/10
1

1
2
3
4
5
6
7

Fixing parts
4 MW (plastic)

Handle locking devices


for 5SX miniature circuit-breaker 1-pole for protection against
accidental mechanical
switching on (part red)
switching off (part transparent)

8
9

Terminal covers, gray


surface mounting, degree of protection IP40
with 35 mm standard mounting rail, sealable
up to 2.5 MW
up to 4.5 MW

10
11

flush mounting, degree of protection IP40


with 35 mm standard mounting rail
up to 2.5 MW
up to 4.5 MW

5SW3 006
5SW3 007

008
008

0.126
0.147

1/4
1/5

12
13

Molded-plastic enclosures
surface mounting, IP54 with 35 mm mounting rail, sealable,
with transparent hinged lid
up to 4.5 MW

5SW1 200

008

0.450

15

Covers
can be assembled as mini distribution board
cover parts prepared for rail mounting of conventional
label caps, comprising:
End plates
(for snapping onto standard mounting rail)

5ST2 134

027

0.022

1/10

Angle section (approx. 1 m long)


Flat section (as cover between the device types)

5ST2 135
5ST2 136

027
027

0.330
0.260

1/5
1/5

For busbars for miniature circuit-breakers, see chapter "Busbars for modular installation devices".
* You can order this quantity or a multiple thereof.

14

Siemens ET B1 2007

14/5

16
17

Modular Installation Devices, Mounting Depth 55 mm >N<


Residual Current Protective Devices

-25

(Type A)

5SM1 residual current operated circuit-breakers


(RCCBs), type A, 16 ... 80 A

Benefits

Application

Terminals with wire protection can be directly busbar-mounted to


the underneath of devices with terminals in the hole pitch, e.g. with
5SX miniature circuit-breakers
An auxiliary switch can be fitted to the right-hand side of the
enclosure by the customer
Operating handle and test button can be locked by means of a
handle locking device
Particularly suitable for installation in flat distribution boards

Personnel and fire protection


- In 30 mA: additional protection in the case of direct contact
- In 300 mA: preventive fire protection in the case of ground
fault currents
Product standards: IEC/EN 61008-1 (VDE 0664, Part 10);
IEC/EN 61008-2-1 (VDE 0664, Part 11); IEC/EN 61543
(VDE 0664, Part 30)
Un 230/400 V; 50 to 60 Hz; can be used in systems up to
240/415 V AC
Un 500 V; 50 to 60 Hz; can be used in systems up to 500 V AC
Definition of surge current withstand capability with current
waveform 8/20 s according to DIN VDE 0432, Part 2
S-type: can be used as upstream group switch for selective
tripping contrary to downstream standard RCCBs.
Very high surge current withstand capability: > 5 kA
K-type, super resistant: Short-time delayed tripping in the
case of transient leakage currents.
High surge current withstand capability: > 3 kA
50 ... 400 Hz version for use with power supply frequencies
between 50 and 400 Hz

Selection and ordering data


Maximum permissible shortcircuit series
fuse

Rated
Rated
residual current
current
I n

In

mA

MW Version

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Instantaneous trippings, surge current withstand capability > 1 kA


125 ... 230 V AC; 50 ... 60 Hz
2-pole
63 A
10 000

1 N

10

16

5SM1 111-6

007

0.218

30

16

5SM1 311-6

007

0.218

30

25
40
25
40

5SM1 312-6
5SM1 314-6
5SM1 412-6
5SM1 414-6

007
007
007
007

0.218
0.218
0.218
0.218

1
1
1
1

25
40
63
80

5SM1 612-6
5SM1 614-6
5SM1 316-6
5SM1 317-6

007
007
007
007

0.218
0.218
0.300
0.300

1
1
1
1

100

I2_05982c

2 NT

300
30

100 A
10 000

2.5

100

63
80

5SM1 416-6
5SM1 417-6

007
007

0.280
0.280

1
1

300

63
80

5SM1 616-6
5SM1 617-6

007
007

0.280
0.280

1
1

30

25
40
63
80
40
63

5SM1 342-6
5SM1 344-6
5SM1 346-6
5SM1 347-6
5SM1 444-6
5SM1 446-6

007
007
007
007
007
007

0.473
0.473
0.473
0.473
0.483
0.509

1
1
1
1
1
1

230 ... 400 V AC; 50 ... 60 Hz


4-pole

100 A

10 000

100
I2 _ 0 5 9 7 7 d

300

25
40
63
80

5SM1 642-6
5SM1 644-6
5SM1 646-6
5SM1 647-6

007
007
007
007

0.473
0.473
0.473
0.473

1
1
1
1

500

25
40
63

5SM1 742-6
5SM1 744-6
5SM1 746-6

007
007
007

0.473
0.473
0.473

1
1
1

Additional components see page 14/8,


accessories see page 14/8.

14/6

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

-25

Modular Installation Devices, Mounting Depth 55 mm >N<


Residual Current Protective Devices

(Type A)

5SM1 residual current operated circuit-breakers


(RCCBs), type A, 16 ... 80 A
Maximum permissible shortcircuit series
fuse

Rated
Rated
residual current
current
I n
mA

MW Version

Order No.

In
A

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

0.473
0.473
0.473

1
1
1

short-time delayed, super resistant, surge current withstand capability > 3 kA


230 ... 400 V AC; 50 ... 400 Hz
4-pole
1

30

100 A

10 000

100

25
40
63

5SM1 342-6KK01
5SM1 344-6KK01
5SM1 446-6KK01

007
007
007

3
4
5

I2 _ 0 5 9 7 7 d

1
2

selective, surge current withstand capability > 5 kA


125 ... 230 V AC; 50 ... 60 Hz
2-pole
100 A

1 N

300

63

2.5

5SM1 616-8

007

0.280

100
300

40
40
63

5SM1 444-8
5SM1 644-8
5SM1 646-8

007
007
007

0.473
0.473
0.473

1
1
1

1 000

63

5SM1 846-8

007

0.473

6
7

10 000

I2_05982c

2 NT

230 ... 400 V AC; 50 ... 60 Hz


4-pole
1

100 A
10 000

I2 _ 0 5 9 7 7 d

Type A, 500 V, 25 ... 63 A


500 V AC1); 50 ... 60 Hz
4-pole

30

63 A
10 000

300

25
40
63
25
40
63

5SM1 352-6
5SM1 354-6
5SM1 356-6
5SM1 652-6
5SM1 654-6
5SM1 656-6

007
007
007
007
007
007

0.515
0.515
0.515
0.515
0.515
0.515

1
1
1
1
1
1

10
11

Type A, 50 ... 400 Hz, 25 ... 40 A


230 ... 400 V AC; 50 ... 400 Hz
4-pole
80 A
1

30
10 000

25
40

5SM1 342-6KK03
5SM1 344-6KK03

007
007

0.473
0.473

1
1

12

I2 _ 0 5 9 7 7 d

13

Additional components see page 14/8,


accessories see page 14/8.
1)

Approval according to IEC/EN 61008 (VDE 0664) only to 440 V.

14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

14/7

17

Modular Installation Devices, Mounting Depth 55 mm >N<


Residual Current Protective Devices
Additional components for 5SM1

Benefits

Application

An auxiliary switch can be fitted to the right-hand side of the RCCB


enclosure by the customer
Mounting with factory-fitted clips
Particularly suitable for installation in flat distribution boards
Can be connected to instabus KNX EIB and AS-Interface bus or
PROFIBUS through binary inputs.

Remote indications of the circuit state of the RCCB: ON/OFF


Max. contact load:
6 A/230 V AC
1 A/220 V DC
Short-circuit protection ensured by miniature circuit-breakers,
characteristic B or C with In = 6 A or gL 6 A fuse
Product standards: IEC/EN 62019 (VDE 0640).

5SW3 00.
RCCB

I2_7482

AS
input
i n s t a b u s KNX E I B

Selection and ordering data


MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Auxiliary switches (AS)


21 13

1 NO + 1 NC

0.5

5SW3 000

008

0.042

2 NC

0.5

5SW3 001

008

0.042

2 NO

0.5

5SW3 002

008

0.042

PG

Weight
1 unit
approx.
kg

PS*/
P. unit

22 14
21 11
22 12
23 13
24 14

Accessories for 5SM1

Selection and ordering data


Order No.

Price

1 unit

Unit(s)

Covers for connection terminals

5SW3 010
5SW3 011
5SW3 008

008
008
008

0.003
0.004
0.006

1/50
1/50
1/50

Locking devices
sealable and lockable
4.5 mm lock hasp diameter

5SW3 003

008

0.008

1/10

5ST3 802

027

0.027

008

1 set
0.035

1 set

I2_11431

for residual current operated circuit-breakers up to 80 A,


sealable (2 units in plastic bag)
2 MW
2.5 MW
4 MW

Padlocks
for 5SW3 003 locking device
Locking devices with padlock
comprising 5SW3 003 locking device and
5ST3 802 padlock

5SW3 012

For busbars for RCCBs, see chapter "Busbars for modular


installation devices".

14/8

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Modular Installation Devices, Mounting Depth 55 mm >N<


Switches
5TE7 1 ... 5TE7 3 switches

Selection and ordering data


Ue

Ie

Conductor
M
cross-sections W

V AC

up to mm2

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

0.058

1/12

Unit(s)

Group switches with center position


with sealable switch position
1 CO contacts
230

1 2

16

027

5TE7 141

1
2
3
4

Control switches with glow lamp


with sealable switch position
for max. 5 m cable length
1

230

16

5TE7 101

027

0.055

1/12

230

16
32

5TE7 111
5TE7 211

027
027

0.050
0.050

1/12
1

ON/OFF switches (16 A to 32 A)


with sealable switch position
1 NO contact
1

6
7
8

9
5TE7 5 switches

Selection and ordering data


Ue

Ie

Conductor
M
cross-sections W

V AC

up to mm2

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

0.311

1/4

Unit(s)

ON/OFF switches
can be used as switch disconnector according to EN 60947-1

10
11

with sealable switch position


3 NO contacts
1 3 5

63

5TE7 513

027

12

2 4 6

13

For busbars, see chapter "Busbars for modular installation devices".

14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

14/9

17

Modular Installation Devices, Mounting Depth 55 mm >N<


Switching Devices
5TT5 remote control switches

Selection and ordering data


Version

Ue

Ie

Uc

V AC

A AC

V AC

MW

V DC

Remote control switches


contact gap 3 mm, short-circuit strength up to 800 A
1 NO contact
230
16
8
12

2 NO contacts

400

16

5TT5 511

Order No.

---

24
230

24
220

8
12

---

24
230

24
220

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Units

5TT5 511
5TT5 501

027
027

0.090
0.090

1
1

5TT5 521
5TT5 531

027
027

0.090
0.090

1
1/12

5TT5 512
5TT5 502

027
027

0.097
0.097

1
1

5TT5 522
5TT5 532

027
027

0.097
0.097

1
1/12

5TG8 230

027

0.050

Compensators
PTC resistor combination for increasing glow lamp loads
230

--

--

--

5TG8 230

5TT3 0 switching relays

Overview
Functions
Switching relays are used in control systems as coupling relays for
the electrical or safe isolation of electrical circuits.
Protective separation
The magnet coil and the contacts meet the requirements for safety
extra-low voltage, from the actuating voltage safely through to disconnection

Checking functions using the manual switch


Switching relays have a manual switch that shows the switching
position. This switch can be used to manually switch the switching
relay, thus allowing system components and control functions to be
checked.

Selection and ordering data


Version

Ue

Ie

Uc

V AC

A AC

V AC

230

16

230

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Units

0.100

Switching relays
1 NO contact

5TT3 045

027

5TT3 045

14/10

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Modular Installation Devices, Mounting Depth 55 mm >N<


Switching Devices
5TT3 8 Insta contactors

Selection and ordering data


Ue

Ie

Uc

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Units

5TT3 8 Insta contactors


Insta contactors, 40 A
for DC or AC continuous operation, with position indication
and DC magnetic system
4 NO contacts
400

40

230 AC, 220 DC


24 AC/DC

5TT3 806
5TT3 816

027
027

0.395
0.395

1
1

3 NO contacts, 1 NC contact
400
(+) A1 1 3 5 21

40

230 AC, 220 DC


24 AC/DC

5TT3 821
5TT3 841

027
027

0.400
0.400

1
1

40

230 AC, 220 DC


24 AC/DC

5TT3 822
5TT3 842

027
027

0.400
0.400

1
1

40

230 AC, 220 DC


24 AC/DC

5TT3 823
5TT3 843

027
027

0.400
0.400

1
1

(+) A1 1 3 5 7(13)
( ) A2 2 4

( ) A2 2 4

6 8(14)

6 22

2 NO contacts, 2 NC contacts
400
(+) A1 13 21 31 43
(-) A2 14 22 32 44

4 NC contacts
(+) A1 11 21 31 41

400

(-) A2 12 22 32 42

1
2
3
4
5
6
7

Insta contactors, 63 A

for DC or AC continuous operation, with position indication


and DC magnetic system
4 NO contacts
400

63

230 AC, 220 DC


24 AC/DC

5TT3 807
5TT3 817

027
027

0.395
0.395

1
1

3 NO contacts, 1 NC contact
400
(+) A1 1 3 5 21

63

230 AC, 220 DC


24 AC/DC

5TT3 824
5TT3 844

027
027

0.400
0.400

1
1

63

230 AC, 220 DC


24 AC/DC

5TT3 825
5TT3 845

027
027

0.400
0.400

1
1

(+) A1 1 3 5 7(13)
( ) A2 2 4

( ) A2 2 4

6 8(14)

6 22

2 NO contacts, 2 NC contacts
400

(+) A1 13 21 31 43

10

(-) A2 14 22 32 44

11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

14/11

17

Modular Installation Devices, Mounting Depth 55 mm >N<


Timers
5TT1 3
timers for building lighting

Selection and ordering data


Ue

Ie

Uc

V AC

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Stairwell lighting timers,


setting range 0.5 to 10 minutes, manual switch
four-wire connection L-momentary contact or
3-wire circuit N-momentary contact, can be reset
L

230

10

230

5TT1 311-1

027

0.080

230

5TT1 310-1

027

0.080

230

5TT1 313-1

027

0.075

t
2

for 3-wire circuit, L-momentary contact, cannot be reset


2

230

10

t
L

for four-wire connection L-momentary contact or


3-wire circuit N-momentary contact,
can be reset, with warning prior to switch-off
230
16

7LF4 4 digital time switches

Selection and ordering data


Contacts

Ue

Ie

Uc

V AC

V AC

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Units

Mini digital time switches


Week program
Mini digital time switches, 1 channel
1 CO

250

16

230

7LF4 481-0

027

0.180

Top digital time switches


Week program
With text-assisted programming concept
- Languages: German, English, French, Italian, Spanish
Top digital time switches, 1 channel
56 programs
1 CO
250
16

230

7LF4 491-0

027

0.225

Top digital time switches, 2 channels


56 programs (28 per channel)
2 COs
250
16

230

7LF4 492-0

027

0.225

for mounting on panels with a sheet thickness of up to 2.5 mm.


the mount must be completely filled with devices.
for devices with 2 MW
cutout dimensions H W: 45+0.5 mm 45+0.5 mm
front dimensions H W: 72 mm 55 mm
--

7LF9 002

027

0.017

for devices with 4 MW


cutout dimensions H W: 45+0.5 mm 81+0.5 mm
front dimensions H W: 72 mm 90 mm
--

7LF9 003

027

0.017

universal application for devices from 1 to 6 MW


cutout dimensions:
height 45+0.5 mm
width: 23, 41, 59, 77, 95 or 113 mm
--

7LF9 006

027

0.071

7LF9 00 mount for the front-mounting of time switches

I2_08105

14/12

Siemens ET B1 2007

* You can order this quantity or a multiple thereof.

Modular Installation Devices, Mounting Depth 55 mm >N<


Timers
7LF5 3 mechanical time switches

Selection and ordering data


Ue

Ie

Uc

V AC

V AC

16

230

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit

0.800

Units

Synchronous time switches without power reserve


Synchronous time switches
Day disk
1 NO contact

250

7LF5 390-1

027

1
2
3
4
5

Quartz-clock time switches with power reserve


Quartz-clock time switches
Day disk
1 NO contact

250

16

230

7LF5 391-1

027

0.850

Quartz-clock time switch with transparent cap, 3 MW


Day disk
1 CO

250

16

230

7LF5 391-6

027

0.160

Week disk
1 CO

250

16

230

7LF5 391-7

027

0.160

6
7
8
9
10
11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

14/13

17

Modular Installation Devices, Mounting Depth 55 mm >N<


Transformers
4AC2 9 transformers

Selection and ordering data


Ue

Usec

Isec

Ps

V AC

V AC

A AC

VA

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.
kg

PS*/
P. unit
Unit(s)

Transformers for permanent loads

14/14

with PTC protection for AC voltage/current supply as safety


extra-low voltage for continuous operation for the supply of
calibration circuits, switching relays and Insta contactors
with one secondary voltage
230
8
1
8
3
24

3
4

4AC2 940-8
4AC2 952-4

027
027

0.380
0.940

1
1

with two secondary voltages, optionally for


series or parallel switching
230
2 x 4/8
2 x 2/2
2 x12/24
2 x 0.67/0.67
2 x 1.0/1.0
2 x 1.67/1.67

3
3
4
4

4AC2 951-6
4AC2 961-6
4AC2 962-4
4AC2 964-0

027
027
027
027

0.600
0.600
0.590
0.840

1
1
1
1

Siemens ET B1 2007

16
16
24
40

* You can order this quantity or a multiple thereof.

Modular Installation Devices, Mounting Depth 55 mm >N<


Monitoring Devices
7LQ2 1 dusk switches

Function
A light sensor measures the level of daylight. Switching depends on
the desired brightness. A time delay and the switching hysteresis
prevent clock-pulse behavior.
The sensor must be mounted so that it is not influenced by the
lighting (feedback).

Energy saving
Dusk switches are used for the demand-oriented switching of
lighting installations for shop windows or paths in order to cut
operating costs.

Selection and ordering data


Ue

Ie

Uc

V AC

V AC

250

16

230

MW

Order No.

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Dusk switches, 55 mm
Setting range 2 ... 500 lux
1-channel version,
with light sensor
for surface mounting, IP55
2

0.280

6
7

7LQ2 910

027

0.060

5TT3 45 alarm sensors 55/70 mm

Benefits

9
10

Continuous tone, fixed pitch


Interval/continuous tone, adjustable

Selection and ordering data


Uc

MW

Order No.

V AC

Price

PG

1 unit

Weight
1 unit
approx.

PS*/
P. unit

kg

Unit(s)

Alarm sensors
Non-adjustable continuous tone and pitch
230
24

5TT3 450
5TT3 451

027
027

0.110
0.110

1
1

5TT3 452
5TT3 453

027
027

0.110
0.110

1
1

A2

Adjustable pitch and continuous tone/interval


A1

027

Replacement light sensors


with watertight/resistant resin molding material,
heat-resistant to 70 C

A1

3
4

7LQ2 100-1

7LQ2 100-1

Degree of protection IP55, for 7LQ2 100 and 7LQ2 101,


for surface mounting, 2 ... 500 lux

1
2

230
24

A2

11
12
13
14
15
16

* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

14/15

17

Modular Installation Devices, Mounting Depth 55 mm >N<


Notes

14/16

Siemens ET B1 2007

Notes on
Product Changeover

15/2

Product changeover

15

15/1

Notes on Product Changeover


Product changeover

Overview
In this chapter you will find notes on product changeovers:

Successor products for devices with a mounting depth of 55 mm


Successor products for devices with a mounting depth of 70 mm.

Devices that offer long term availability


Replacement products for devices with a mounting depth of
55 mm (from chapter "Modular installation devices, mounting
depth; 55 mm >N<")
Type

Product

Mounting
depth

Type

Successor product

4AC2 020

Transformers 8 V, 1 A

55

4AC2 940-8

Transformers, continuous duty, 8 V, 8 VA, PTC

4AC2 020

55

Transformers 8 V, 1 A

55

4AC3 408

Transformers, continuous duty, 8 V, 8 VA, PTC

70

4AC2 021

Transformers 8 V, 1 A, switch

55

--

Without switch: 4AC2 940-8

55

14

4AC2 021

Transformers 8 V, 1 A, switch

55

--

Without switch: 4AC3 408

70

4AC2 022

Transformers 4/8/12 V, 1/1/0.67 A

55

--

4 V: 4AC2 951-6,

55

14

8 V: 4AC2 940-8,

55

14

12 V: 4AC2 961-6

55

14

4 V: 4AC3 516,

70

8 V: 4AC3 516,

70

12 V: 4AC3 616

70

4 V: 4AC2 951-6,

55

14

6 V: no replacement,

55

14

8 V: 4AC2 951-6

55

14

4 V: 4AC3 516,

70

6 V: no replacement

70

8 V: 4AC3 516

70

mm

4AC2 022

4AC2 023

4AC2 023

4AC2 100

Transformers 4/8/12 V, 1/1/0.67 A

Transformers 4/6/8 V, 1/1/1 A PTC

Transformers 4/6/8 V, 1/1/1 A PTC

Transformers 8 V, 1 A, PTC

55

55

55

Mounting
depth

Chapter

mm

--

--

--

14

55

4AC2 940-8

Transformers, continuous duty, 8 V, 8 VA, PTC

55

14
9

4AC2 100

Transformers 8 V, 1 A, PTC

55

4AC3 408

Transformers, continuous duty, 8 V, 8 VA, PTC

70

4AC2 101

Transformers 8 V, 2 A, PTC

55

4AC2 951-6

Transformers, continuous duty, 4+4 V, 16 VA, PTC

55

14

4AC2 101

Transformers 8 V, 2 A, PTC

55

4AC3 524

Transformers, continuous duty, 8 V, 24 VA, PTC

70

4AC2 102

Transformers 12 V, 1.33 A, PTC

55

4AC2 961-6

Transformers, continuous duty, 12+12 V, 16 VA, PTC

55

14

4AC2 102

Transformers 12 V, 1.33 A, PTC

55

4AC3 616

Transformers, continuous duty, 12+12 V, 16 VA, PTC

70

4AC2 103

Transformers 8 V, 1 A, PTC, switch

55

--

Without switch: 4AC2 940-8

55

14

4AC2 103

Transformers 8 V, 1 A, PTC, switch

55

--

Without switch: 4AC3 408

70

4AC2 104

Transformers 8 V, 2 A, PTC, switch

55

--

Without switch: 4AC2 952-4

55

14

4AC2 104

Transformers 8 V, 2 A, PTC, switch

55

--

Without switch: 4AC3 524

70

4AC2 105

Transformers 12 V, 1.33 A, PTC, switch

55

--

Without switch: 4AC2 961-6

55

14

4AC2 105

Transformers 12 V, 1.33 A, PTC, switch

55

--

Without switch: 4AC3 616

70

4AC2 120

Transformers 4/8/12 V, 2/2/2 A PTC

55

--

4 V: 4AC2 951-6,

55

14

--

8 V: 4AC2 951-6,

--

12 V: 4AC2 962-4

--

4 V: 4AC3 516,

70

--

8 V: 4AC3 516,

--

12 V- 4AC3 624

--

8 V: 4AC2 951-6,

55

14

--

12 V: 4AC2 962-4,

--

24 V: 4AC2 962-4

--

8 V: 4AC3 524,

70

--

12 V: 4AC3 624,

--

24 V: 4AC3 624

4AC2 120

4AC2 121

4AC2 121

Transformers 4/8/12 V, 2/2/2 A PTC

Transformers 8/12/24 V, 2/2/1 A PTC

Transformers 8/12/24 V, 2/2/1 A PTC

55

55

55

4AC2 122

Transformers 24 V, 1 A, PTC

55

4AC2 962-4

Transformers, continuous duty, 12+12 V, 24 VA, PTC

55

14

4AC2 122

Transformers 24 V, 1 A, PTC

55

4AC3 624

Transformers, continuous duty, 12+12 V, 24 VA, PTC

70

4AC2 123

Transformers 12/24 V, 5.25/2.65 A PTC

55

4AC3 663

Transformers, continuous duty, 12+12 V, 63 VA, PTC

70

4AC2 222

Transformers 24 V, 1.25 A, FS

55

4AC2 964-0

Transformers, continuous duty, 12+12 V, 40 VA, PTC

55

14

4AC2 222

Transformers 24 V, 1.25 A, FS

55

4AC3 640

Transformers, continuous duty, 12+12 V, 40 VA, PTC

70

4AC2 223

Transformers 12/24 V, 1/1/0.67 A, FS

55

4AC2 961-6

Transformers, continuous duty, 12+12 V, 16 VA, PTC

55

14

4AC2 223

Transformers 12/24 V, 1/1/0.67 A, FS

55

4AC3 616

Transformers, continuous duty, 12+12 V, 16 VA, PTC

70

4AC2 224

Transformers 4/8/12 V, 3/3/2.5 A, FS

55

--

4 V: no replacement,

55

14

--

8 V: 4AC2 952-4,

--

12 V: 4AC2 964-0

--

4 V: no replacement,

70

--

8 V: 4AC3 524,

--

12 V: 4AC3 640

4AC2 224

15/2

Transformers 4/8/12 V, 3/3/2.5 A, FS

Siemens ET B1 2007

55

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

Mount- Chaping
ter
depth

4AC2 225

Transformers 2 X 12/24 V, 2 x 1.5/1 A, FS

55

4AC2 962-4

Transformers, continuous duty, 12+12 V, 24 VA, PTC

55

14

4AC2 225

Transformers 2 X 12/24 V, 2 x 1.5/1 A, FS

55

4AC3 640

Transformers, continuous duty, 12+12 V, 40 VA, PTC

70

4AC2 320

Power supply units 12 V DC, 1 A

55

4AC2 400

Power supply units 12 V DC, 40 VA

70

4AC2 321

Power supply units 24 V DC, 1 A

55

4AC2 401

Power supply units 24 V DC, 63 VA

70

5SG7 111

MINIZED switch disconnectors for NEOZED, 2...63 A,


D02, 1-pole

55

5SG7 113

MINIZED switch disconnectors for NEOZED, D02,


1-pole, drawer technology

70

5SG7 121

MINIZED switch disconnectors for NEOZED, 2...63 A,


D02, 2-pole

55

5SG7 123

MINIZED switch disconnectors for NEOZED, D02,


2-pole, drawer technology

70

5SG7 131

MINIZED switch disconnectors for NEOZED, 2...63 A,


D02, 3-pole

55

5SG7 133

MINIZED switch disconnectors for NEOZED, D02,


3-pole, drawer technology

70

5SG7 151

MINIZED switch disconnectors for NEOZED, 2...63 A,


D02, 1+N-pole

55

5SG7 153

MINIZED switch disconnectors for NEOZED, D02,


1+N-pole, drawer technology

70

5SG7 161

MINIZED switch disconnectors for NEOZED, 2...63 A,


D02, 3+N-pole

55

5SG7 163

MINIZED switch disconnectors for NEOZED, D02,


3+N-pole, drawer technology

70

5SH5 217

Shock protection cover for NEOZED fuse bases

55

--

Cover does not fit successor devices

--

--

5SG1 504

NEOZED fuse bases D01, 16 A,


with cover

55

5SG1 330

NEOZED fuse bases D01, 16 A,


with cover

70

5SG1 604

NEOZED fuse bases D02, 63 A,


with cover

55

5SG1 730

NEOZED fuse bases D02, 63 A,


with cover

70

5SG1 614

NEOZED fuse bases D02, 63 A,


with cover

55

5SG1 730

NEOZED fuse bases D02, 63 A,


with cover

70

5SG1 506

NEOZED fuse bases D01, 16 A,


without cover

55

5SG1 331

NEOZED fuse bases D01, 16 A,


without cover

70

5SG1 606

NEOZED fuse bases D02, 63 A,


without cover

55

5SG1 731

NEOZED fuse bases D02, 63 A,


without cover

70

5SG1 616

NEOZED fuse bases D02, 63 A,


without cover

55

5SG1 731

NEOZED fuse bases D02, 63 A,


without cover

70

5SM1 111-6

RCCBs, type A, 16 A, 2-pole, 10 mA, 2 MW

55

5SM3 111-6 RCCBs, type A, 16 A, 2-pole, 10 mA, 2 MW

70

5SM1 311-6

RCCBs, type A, 16 A, 2-pole, 30 mA, 2 MW

55

5SM3 311-6 RCCBs, type A, 16 A, 2-pole, 30 mA, 2 MW

70

5SM1 312-6

RCCBs, type A, 25 A, 2-pole, 30 mA, 2 MW

55

5SM3 312-6 RCCBs, type A, 25 A, 2-pole, 30 mA, 2 MW

70

5SM1 314-6

RCCBs, type A, 40 A, 2-pole, 30 mA, 2 MW

55

5SM3 314-6 RCCBs, type A, 40 A, 2-pole, 30 mA, 2 MW

70

5SM1 316-6

RCCBs, type A, 63 A, 2-pole, 30 mA, 2.5 MW

55

5SM3 316-6 RCCBs, type A, 63 A, 2-pole, 30 mA, 2.5 MW

70

mm

mm

5SM1 317-6

RCCBs, type A, 80 A, 2-pole, 30 mA, 2.5 MW

55

5SM3 317-6 RCCBs, type A, 80 A, 2-pole, 30 mA, 2.5 MW

70

5SM1 342-6

RCCBs, type A, 25 A, 4-pole, 30 mA, 4 MW

55

5SM3 342-6 RCCBs, type A, 25 A, 4-pole, 30 mA, 4 MW

70

5SM1 3426KK01

RCCBs, type A, 25 A, 4-pole, 30 mA, 4 MW

55

5SM3 3426KK01

RCCBs, type A, 25 A, 4-pole, 30 mA, 4 MW

70

5SM1 3426KK03

RCCBs, type A, 25 A, 4-pole, 30 mA,


50... 400 Hz

55

5SM3 3426KK03

RCCBs, type A, 25 A, 4-pole, 30 mA, 4 MW, 50...400 Hz 70

5SM1 344-6

RCCBs, type A, 40 A, 4-pole, 30 mA, 4 MW

55

5SM3 344-6 RCCBs, type A, 40 A, 4-pole, 30 mA, 4 MW

70

5SM1 3446KK01

RCCBs, type A, 40 A, 4-pole, 30 mA, 4 MW

55

5SM3 3446KK01

RCCBs, type A, 40 A, 4-pole, 30 mA, 4 MW

70

5SM1 3446KK03

RCCBs, type A, 40 A, 4-pole, 30 mA,


50... 400 Hz

55

5SM3 3446KK03

RCCBs, type A, 40 A, 4-pole, 30 mA, 4 MW, 50...400 Hz 70

5SM1 346-6

RCCBs, type A, 63 A, 4-pole, 30 mA, 4 MW

55

5SM3 346-6 RCCBs, type A, 63 A, 4-pole, 30 mA, 4 MW

5SM1 347-6

RCCBs, type A, 80 A, 4-pole, 30 mA, 4 MW

55

5SM3 347-6 RCCBs, type A, 80 A, 4-pole, 30 mA, 4 MW

70

5SM1 352-6

RCCBs, type A, 25 A, 4-pole, 30 mA, 500 V, 4 MW

55

5SM3 352-6 RCCBs, type A, 25 A, 4-pole, 30 mA, 500 V, 4 MW

70

5SM1 354-6

RCCBs, type A, 40 A, 4-pole, 30 mA, 500 V, 4 MW

55

5SM3 354-6 RCCBs, type A, 40 A, 4-pole, 30 mA, 500 V, 4 MW

70

5SM1 356-6

RCCBs, type A, 63 A, 4-pole, 30 mA, 500 V, 4 MW

55

5SM3 356-6 RCCBs, type A, 63 A, 4-pole, 30 mA, 500 V, 4 MW

70

5SM1 412-6

RCCBs, type A, 25 A, 2-pole, 0.1 A, 2 MW

55

5SM3 412-6 RCCBs, type A, 25 A, 2-pole, 0.1 A, 2 MW

70

5SM1 414-6

RCCBs, type A, 40 A, 2-pole, 0.1 A, 2 MW

55

5SM3 414-6 RCCBs, type A, 40 A, 2-pole, 0.1 A, 2 MW

70

5SM1 416-6

RCCBs, type A, 63 A, 2-pole, 0.1 A, 2.5 MW

55

5SM3 416-6 RCCBs, type A, 63 A, 2-pole, 0.1 A, 2.5 MW

70

5SM1 417-6

RCCBs, type A, 80 A, 2-pole, 0.1 A, 2.5 MW

55

5SM3 417-6 RCCBs, type A, 80 A, 2-pole, 0.1 A, 2.5 MW

70

5SM1 444-6

RCCBs, type A, 40 A, 4-pole, 0.1 A, 4 MW

55

5SM3 444-6 RCCBs, type A, 40 A, 4-pole, 0.1 A, 4 MW

70

5SM1 444-8

RCCBs, type A, 40 A, 4-pole, 0.1 A, 4 MW

55

5SM3 444-8 RCCBs, type A, 40 A, 4-pole, 0.1 A, 4 MW

70

5SM1 446-6

RCCBs, type A, 63 A, 4-pole, 0.1 A, 4 MW

55

5SM3 446-6 RCCBs, type A, 63 A, 4-pole, 0.1 A, 4 MW

70

5SM1 4466KK01

RCCBs, type A, 63 A, 4-pole, 0.1 A, 4 MW

55

5SM3 4466KK01

RCCBs, type A, 63 A, 4-pole, 0.1 A, 4 MW

70

5SM1 612-6

RCCBs, type A, 25 A, 2-pole, 0.3 A, 2 MW

55

5SM3 612-6 RCCBs, type A, 25 A, 2-pole, 0.3 A, 2 MW

70

5SM1 614-6

RCCBs, type A, 40 A, 2-pole, 0.3 A, 2 MW

55

5SM3 614-6 RCCBs, type A, 40 A, 2-pole, 0.3 A, 2 MW

70

5SM1 616-6

RCCBs, type A, 63 A, 2-pole, 0.3 A, 2.5 MW

55

5SM3 616-6 RCCBs, type A, 63 A, 2-pole, 0.3 A, 2.5 MW

70

5SM1 616-8

RCCBs, type A, 63 A, 2-pole, 0.3 A, 2.5 MW

55

5SM3 616-8 RCCBs, type A, 63 A, 2-pole, 0.3 A, 2.5 MW

70

5SM1 617-6

RCCBs, type A, 80 A, 2-pole, 0.3 A, 2.5 MW

55

5SM3 617-6 RCCBs, type A, 80 A, 2-pole, 0.3 A, 2.5 MW

70

5SM1 642-6

RCCBs, type A, 25 A, 4-pole, 0.3 A, 4 MW

55

5SM3 642-6 RCCBs, type A, 25 A, 4-pole, 0.3 A, 4 MW

70

5SM1 644-6

RCCBs, type A, 40 A, 4-pole, 0.3 A, 4 MW

55

5SM3 644-6 RCCBs, type A, 40 A, 4-pole, 0.3 A, 4 MW

70

5SM1 644-8

RCCBs, type A, 40 A, 4-pole, 0.3 A, 4 MW

55

5SM3 644-8 RCCBs, type A, 40 A, 4-pole, 0.3 A, 4 MW

70

5SM1 646-6

RCCBs, type A, 63 A, 4-pole, 0.3 A, 4 MW

55

5SM3 646-6 RCCBs, type A, 63 A, 4-pole, 0.3 A, 4 MW

70

5SM1 646-8

RCCBs, type A, 63 A, 4-pole, 0.3 A, 4 MW

55

5SM3 646-8 RCCBs, type A, 63 A, 4-pole, 0.3 A, 4 MW

70

5SM1 647-6

RCCBs, type A, 80 A, 4-pole, 0.3 A, 4 MW

55

5SM3 647-6 RCCBs, type A, 80 A, 4-pole, 0.3 A, 4 MW

70

5SM1 652-6

RCCBs, type A, 25 A, 4-pole, 0.3 A, 500 V, 4 MW

55

5SM3 652-6 RCCBs, type A, 25 A, 4-pole, 0.3 A, 500 V, 4 MW

70

5SM1 654-6

RCCBs, type A, 40 A, 4-pole, 0.3 A, 500 V, 4 MW

55

5SM3 654-6 RCCBs, type A, 40 A, 4-pole, 0.3 A, 500 V, 4 MW

70

70

Siemens ET B1 2007

15/3

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

5SM1 656-6

RCCBs, type A, 63 A, 4-pole, 0.3 A, 500 V, 4 MW

55

5SM3 656-6 RCCBs, type A, 63 A, 4-pole, 0.3 A, 500 V, 4 MW

70

5SM1 742-6

RCCBs, type A, 25 A, 4-pole, 0.5 A, 4 MW

55

5SM3 742-6 RCCBs, type A, 25 A, 4-pole, 0.5 A, 4 MW

70

5SM1 744-6

RCCBs, type A, 40 A, 4-pole, 0.5 A, 4 MW

55

5SM3 744-6 RCCBs, type A, 40 A, 4-pole, 0.5 A, 4 MW

70

5SM1 746-6

RCCBs, type A, 63 A, 4-pole, 0.5 A, 4 MW

55

5SM3 746-6 RCCBs, type A, 63 A, 4-pole, 0.5 A, 4 MW

70

5SM1 846-8

RCCBs, type A, 63 A, 4-pole, 1.0 A, 4 MW

55

5SM3 846-8 RCCBs, type A, 63 A, 4-pole, 1.0 A, 4 MW

5SX2 101-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 1 A

55

5SY6 101-7

5SX2 102-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 2 A

55

5SY6 102-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 2 A

70

5SX2 103-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 3 A

55

5SY6 103-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 3 A

70

5SX2 104-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 4 A

55

5SY6 104-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 4 A

70

5SX2 105-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 0.5 A

55

5SY6 105-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 0.5 A

70

5SX2 106-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 6 A

55

5SY6 106-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 6 A

70

5SX2 106-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 6 A

55

5SY6 106-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 6 A

70

5SX2 108-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 8 A

55

5SY6 108-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 8 A

70

5SX2 110-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 10 A

55

5SY6 110-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 10 A

70

5SX2 110-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 10 A

55

5SY6 110-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 10 A

70

5SX2 113-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 13 A

55

5SY6 113-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 13 A

70

5SX2 113-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 13 A

55

5SY6 113-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 13 A

70

5SX2 114-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 0.3 A

55

5SY6 114-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 0.3 A

70

5SX2 115-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 1.6 A

55

5SY6 115-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 1.6 A

70

5SX2 116-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 16 A

55

5SY6 116-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 16 A

70

5SX2 116-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 16 A

55

5SY6 116-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 16 A

70

5SX2 120-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 20 A

55

5SY6 120-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 20 A

70

5SX2 120-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 20 A

55

5SY6 120-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 20 A

70

5SX2 125-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 25 A

55

5SY6 125-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 25 A

70

5SX2 125-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 25 A

55

5SY6 125-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 25 A

70

5SX2 132-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 32 A

55

5SY6 132-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 32 A

70

5SX2 132-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 32 A

55

5SY6 132-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 32 A

70

5SX2 140-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 40 A

55

5SY6140-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 40 A

70

5SX2 140-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 40 A

55

5SY6 140-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 40 A

70

5SX2 150-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 50 A

55

5SY6 150-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 50 A

70

5SX2 150-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 50 A

55

5SY6 150-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 50 A

70

5SX2 163-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 63 A

55

5SY6 163-6

Miniature circuit-breakers, 6 kA, 1-pole, Char. B, 63 A

70

5SX2 163-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 63 A

55

5SY6 163-7

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 63 A

70

5SX2 201-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 1 A

55

5SY6 201-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 1 A

70

5SX2 202-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 2 A

55

5SY6 202-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 2 A

70

5SX2 203-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 3 A

55

5SY6 203-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 3 A

70

5SX2 204-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 4 A

55

5SY6 204-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 4 A

70

5SX2 205-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 0.5 A

55

5SY6 205-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 0.5 A

70

5SX2 206-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 6 A

55

5SY6 206-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 6 A

70

5SX2 206-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 6 A

55

5SY6 206-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 6 A

70

5SX2 208-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 8 A

55

5SY6 208-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 8 A

70

5SX2 210-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 10 A

55

5SY6 210-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 10 A

70

5SX2 210-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 10 A

55

5SY6 210-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 10 A

70

5SX2 213-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 13 A

55

5SY6 213-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 13 A

70

5SX2 213-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 13 A

55

5SY6 213-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 13 A

70

5SX2 215-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 1.6 A

55

5SY6 215-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 1.6 A

70

5SX2 216-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 16 A

55

5SY6 216-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 16 A

70

5SX2 216-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 16 A

55

5SY6 216-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 16 A

70

5SX2 220-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 20 A

55

5SY6 220-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 20 A

70

5SX2 220-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 20 A

55

5SY6 220-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 20 A

70

5SX2 225-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 25 A

55

5SY6 225-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 25 A

70

5SX2 225-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 25 A

55

5SY6 225-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 25 A

70

5SX2 232-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 32 A

55

5SY6 232-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 32 A

70

5SX2 232-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 32 A

55

5SY6 232-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 32 A

70

5SX2 240-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 40 A

55

5SY6 240-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 40 A

70

5SX2 240-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 40 A

55

5SY6 240-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 40 A

70

5SX2 250-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 50 A

55

5SY6 250-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 50 A

70

5SX2 250-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 50 A

55

5SY6 250-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 50 A

70

5SX2 263-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 63 A

55

5SY6 263-6

Miniature circuit-breakers, 6 kA, 2-pole, Char. B, 63 A

70

5SX2 263-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 63 A

55

5SY6 263-7

Miniature circuit-breakers, 6 kA, 2-pole, Char. C, 63 A

70

5SX2 301-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 1 A

55

5SY6 301-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 1 A

70

5SX2 302-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 2 A

55

5SY6 302-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 2 A

70

5SX2 303-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 3 A

55

5SY6 303-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 3 A

70

5SX2 304-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 4 A

55

5SY6 304-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 4 A

70

mm

15/4

Siemens ET B1 2007

Mount- Chaping
ter
depth
mm

Miniature circuit-breakers, 6 kA, 1-pole, Char. C, 1 A

70

70

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

Mount- Chaping
ter
depth

5SX2 305-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 0.5 A

55

5SY6 305-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 0.5 A

70

5SX2 306-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 6 A

55

5SY6 306-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 6 A

70

5SX2 306-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 6 A

55

5SY6 306-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 6 A

70

5SX2 308-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 8 A

55

5SY6 308-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 8 A

70

5SX2 310-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 10 A

55

5SY6 310-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 10 A

70

5SX2 310-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 10 A

55

5SY6 310-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 10 A

70

5SX2 313-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 13 A

55

5SY6 313-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 13 A

70

5SX2 313-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 13 A

55

5SY6 313-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 13 A

70

5SX2 315-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 1.6 A

55

5SY6 315-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 1.6 A

70

5SX2 316-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 16 A

55

5SY6 316-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 16 A

70

5SX2 316-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 16 A

55

5SY6 316-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 16 A

70

5SX2 320-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 20 A

55

5SY6 320-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 20 A

70

5SX2 320-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 20 A

55

5SY6 320-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 20 A

70

5SX2 325-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 25 A

55

5SY6 325-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 25 A

70

5SX2 325-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 25 A

55

5SY6 325-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 25 A

70

5SX2 332-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 32 A

55

5SY6 332-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 32 A

70

5SX2 332-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 32 A

55

5SY6 332-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 32 A

70

5SX2 340-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 40 A

55

5SY6 340-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 40 A

70

5SX2 340-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 40 A

55

5SY6 340-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 40 A

70

5SX2 350-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 50 A

55

5SY6 350-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 50 A

70

5SX2 350-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 50 A

55

5SY6 350-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 50 A

70

5SX2 363-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 63 A

55

5SY6 363-6

Miniature circuit-breakers, 6 kA, 3-pole, Char. B, 63 A

70

5SX2 363-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 63 A

55

5SY6 363-7

Miniature circuit-breakers, 6 kA, 3-pole, Char. C, 63 A

70

5SX2 406-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 6 A

55

5SY6 406-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 6 A

70

5SX2 410-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 10 A

55

5SY6 410-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 1 0 A

70

5SX2 413-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 13 A

55

5SY6 413-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 13 A

70

5SX2 416-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 16 A

55

5SY6 416-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 16 A

70

5SX2 420-6

Miniature circuit-breakers, 6 kA, 4-pole, Char. B, 20 A

55

5SY6 420-6

Miniature circuit-breakers, 6 kA, 4-pole, Char. B, 20 A

70

5SX2 420-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 20 A

55

5SY6 420-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 20 A

70

5SX2 425-6

Miniature circuit-breakers, 6 kA, 4-pole, Char. B, 25 A

55

5SY6 425-6

Miniature circuit-breakers, 6 kA, 4-pole, Char. B, 25 A

70

5SX2 425-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 25 A

55

5SY6 425-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 25 A

70

5SX2 432-6

Miniature circuit-breakers, 6 kA, 4-pole, Char. B, 32 A

55

5SY6 432-6

Miniature circuit-breakers, 6 kA, 4-pole, Char. B, 32 A

70

5SX2 432-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 32 A

55

5SY6 432-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 32 A

70

5SX2 440-6

Miniature circuit-breakers, 6 kA, 4-pole, Char. B, 40 A

55

5SY6 440-6

Miniature circuit-breakers, 6 kA, 4-pole, Char. B, 40 A

70

5SX2 440-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 40 A

55

5SY6 440-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 40 A

70

5SX2 450-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 50 A

55

5SY6 450-7

Miniature circuit-breakers, 6 kA, 4-pole, Char. C, 50 A

70

5SX2 506-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 6 A

55

5SY6 506-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 6 A

70

5SX2 506-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 6 A

55

5SY6 506-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 6 A

70

5SX2 510-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 10 A 55

5SY6 510-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 10 A 70

5SX2 510-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 10 A 55

5SY6 510-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 10 A 70

5SX2 513-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 13 A 55

5SY6 513-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 13 A 70

5SX2 513-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 13 A 55

5SY6 513-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 13 A 70

5SX2 516-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 16 A 55

5SY6 516-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 16 A 70

5SX2 516-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 16 A 55

5SY6 516-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 16 A 70

5SX2 520-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 20 A 55

5SY6 520-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 20 A 70

5SX2 520-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 20 A 55

5SY6 520-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 20 A 70

5SX2 525-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 25 A 55

5SY6 525-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 25 A 70

5SX2 525-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 25 A 55

5SY6 525-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 25 A 70

5SX2 532-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 32 A 55

5SY6 532-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 32 A 70

5SX2 532-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 32 A 55

5SY6 532-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 32 A 70

5SX2 540-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 40 A 55

5SY6 540-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 40 A 70

5SX2 540-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 40 A 55

5SY6 540-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 40 A 70

5SX2 550-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 50 A 55

5SY6 550-6

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. B, 50 A 70

5SX2 550-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 50 A 55

5SY6 550-7

Miniature circuit-breakers, 6 kA, 1-pole+N, Char. C, 50 A 70

5SX2 606-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 6 A

55

5SY6 606-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 6 A

5SX2 610-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 10 A 55

5SY6 610-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 10 A 70

5SX2 610-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 10 A 55

5SY6 610-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 10 A 70

5SX2 613-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 13 A 55

5SY6 613-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 13 A 70

5SX2 613-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 13 A 55

5SY6 613-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 13 A 70

5SX2 616-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 16 A 55

5SY6 616-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 16 A 70

5SX2 616-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 16 A 55

5SY6 616-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 16 A 70

5SX2 620-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 20 A 55

5SY6 620-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 20 A 70

5SX2 620-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 20 A 55

5SY6 620-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 20 A 70

5SX2 625-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 25 A 55

5SY6 625-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 25 A 70

mm

mm

70

Siemens ET B1 2007

15/5

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

5SX2 625-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 25 A 55

5SY6 625-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 25 A 70

5SX2 632-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 32 A 55

5SY6 632-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 32 A 70

5SX2 632-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 32 A 55

5SY6 632-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 32 A 70

5SX2 640-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 40 A 55

5SY6 640-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 40 A 70

5SX2 640-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 40 A 55

5SY6 640-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 40 A 70

5SX2 650-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 50 A 55

5SY6 650-6

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. B, 50 A 70

5SX2 650-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 50 A 55

5SY6 650-7

Miniature circuit-breakers, 6 kA, 3-pole+N, Char. C, 50 A 70

5SX4 101-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 1 A

55

5SY4 101-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 1 A

70

5SX4 102-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 2 A

55

5SY4 102-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 2 A

70

5SX4 103-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 3 A

55

5SY4 103-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 3 A

70

5SX4 104-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 4 A

55

5SY4 104-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 4 A

70

5SX4 105-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 0.5 A

55

5SY4 105-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 0.5 A

70

5SX4 106-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 6 A

55

5SY4 106-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 6 A

70

5SX4 106-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 6 A

55

5SY4 106-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 6 A

70

5SX4 108-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 8 A

55

5SY4 108-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 8 A

70

5SX4 110-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 10 A

55

5SY4 110-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 10 A

70

5SX4 110-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 10 A

55

5SY4 110-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 10 A

70

5SX4 113-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 13 A

55

5SY4113-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 13 A

70

5SX4 113-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 13 A

55

5SY4 113-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 13 A

70

5SX4 115-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 1.6 A

55

5SY4 115-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 1.6 A

70

5SX4 116-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 16 A

55

5SY4 116-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 16 A

70

5SX4 116-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 16 A

55

5SY4 116-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 16 A

70

5SX4 120-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 20 A

55

5SY4 120-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 20 A

70

5SX4 120-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 20 A

55

5SY4 120-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 20 A

70

5SX4 125-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 25 A

55

5SY4 125-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 25 A

70

5SX4 125-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 25 A

55

5SY4 125-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 25 A

70

5SX4 132-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 32 A

55

5SY4 132-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 32 A

70

5SX4 132-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 32 A

55

5SY4 132-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 32 A

70

5SX4 140-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 40 A

55

5SY4 140-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 40 A

70

5SX4 140-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 40 A

55

5SY4 140-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 40 A

70

5SX4 150-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 50 A

55

5SY4 150-6

Miniature circuit-breakers, 10 kA, 1-pole, Char. B, 50 A

70

5SX4 150-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 50 A

55

5SY4 150-7

Miniature circuit-breakers, 10 kA, 1-pole, Char. C, 50 A

70

5SX4 201-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 1 A

55

5SY4 201-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 1 A

70

5SX4 202-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 2 A

55

5SY4 202-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 2 A

70

5SX4 203-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 3 A

55

5SY4 203-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 3 A

70

5SX4 204-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 4 A

55

5SY4 204-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 4 A

70

5SX4 205-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 0.5 A

55

5SY4 205-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 0.5 A

70

5SX4 206-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 6 A

55

5SY4 206-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 6 A

70

5SX4 206-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 6 A

55

5SY4 206-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 6 A

70

5SX4 208-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 8 A

55

5SY4 208-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 8 A

70

5SX4 210-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 10 A

55

5SY4 210-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 10 A

70

5SX4 210-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 10 A

55

5SY4 210-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 10 A

70

5SX4 213-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 13 A

55

5SY4 213-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 13 A

70

5SX4 213-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 13 A

55

5SY4 213-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 13 A

70

5SX4 215-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 1.6 A

55

5SY4 215-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 1.6 A

70

5SX4 216-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 16 A

55

5SY4 216-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 16 A

70

5SX4 216-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 16 A

55

5SY4 216-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 16 A

70

5SX4 220-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 20 A

55

5SY4 220-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 20 A

70

5SX4 220-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 20 A

55

5SY4 220-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 20 A

70

5SX4 225-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 25 A

55

5SY4 225-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 25 A

70

5SX4 225-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 25 A

55

5SY4 225-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 25 A

70

5SX4 232-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 32 A

55

5SY4 232-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 32 A

70

5SX4 232-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 32 A

55

5SY4 232-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 32 A

70

5SX4 240-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 40 A

55

5SY4 240-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 40 A

70

5SX4 240-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 40 A

55

5SY4 240-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 40 A

70

5SX4 250-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 50 A

55

5SY4 250-6

Miniature circuit-breakers, 10 kA, 2-pole, Char. B, 50 A

70

5SX4 250-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 50 A

55

5SY4 250-7

Miniature circuit-breakers, 10 kA, 2-pole, Char. C, 50 A

70

5SX4 301-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 1 A

55

5SY4 301-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 1 A

70

5SX4 302-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 2 A

55

5SY4 302-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 2 A

70

5SX4 303-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 3 A

55

5SY4 303-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 3 A

70

5SX4 304-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 4 A

55

5SY4 304-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 4 A

70

5SX4 305-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 0.5 A

55

5SY4 305-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 0.5 A

70

5SX4 306-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 6 A

55

5SY4 306-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 6 A

70

5SX4 306-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 6 A

55

5SY4 306-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 6 A

70

mm

15/6

Siemens ET B1 2007

Mount- Chaping
ter
depth
mm
3

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

Mount- Chaping
ter
depth

5SX4 308-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 8 A

55

5SY4 308-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 8 A

70

5SX4 310-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 10 A

55

5SY4 310-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 10 A

70

5SX4 310-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 10 A

55

5SY4 310-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 10 A

70

mm

mm

5SX4 313-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 13 A

55

5SY4 313-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 13 A

70

5SX4 313-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 13 A

55

5SY4 313-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 13 A

70

5SX4 315-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 1.6 A

55

5SY4 315-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 1.6 A

70

5SX4 316-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 16 A

55

5SY4 316-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 16 A

70

3
3

5SX4 316-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 16 A

55

5SY4 316-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 16 A

70

5SX4 320-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 20 A

55

5SY4 320-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 20 A

70

5SX4 320-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 20 A

55

5SY4 320-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 20 A

70

5SX4 325-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 25 A

55

5SY4 325-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 25 A

70

5SX4 325-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 25 A

55

5SY4 325-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 25 A

70

5SX4 332-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 32 A

55

5SY4 332-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 32 A

70

5SX4 332-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 32 A

55

5SY4 332-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 32 A

70

5SX4 340-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 40 A

55

5SY4 340-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 40 A

70

5SX4 340-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 40 A

55

5SY4 340-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 40 A

70

5SX4 350-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 50 A

55

5SY4 350-6

Miniature circuit-breakers, 10 kA, 3-pole, Char. B, 50 A

70

5SX4 350-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 50 A

55

5SY4 350-7

Miniature circuit-breakers, 10 kA, 3-pole, Char. C, 50 A

70

5SX4 406-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 6 A

55

5SY4 406-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 6 A

70

5SX4 410-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 10 A

55

5SY4 410-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 10 A

70

5SX4 413-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 13 A

55

5SY4 413-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 13 A

70

5SX4 416-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 16 A

55

5SY4 416-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 16 A

70

5SX4 420-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 20 A

55

5SY4 420-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 20 A

70

5SX4 425-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 25 A

55

5SY4 425-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 25 A

70

5SX4 432-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 32 A

55

5SY4 432-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 32 A

70

5SX4 440-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 40 A

55

5SY4 440-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 40 A

70

5SX4 450-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 50 A

55

5SY4 450-7

Miniature circuit-breakers, 10 kA, 4-pole, Char. C, 50 A

70

5SX4 506-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 6 A 55

5SY4 506-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 6 A 70

5SX4 510-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 10 A 55

5SY4 510-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 10 A 70

5SX4 510-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 10 A 55

5SY4 510-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 10 A 70

5SX4 513-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 13 A 55

5SY4 513-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 13 A 70

5SX4 513-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 13 A 55

5SY4 513-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 13 A 70

5SX4 516-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 16 A 55

5SY4 516-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 16 A 70

5SX4 516-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 16 A 55

5SY4 516-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 16 A 70

5SX4 520-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 20 A 55

5SY4 520-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 20 A 70

5SX4 520-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 20 A 55

5SY4 520-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 20 A 70

5SX4 525-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 25 A 55

5SY4 525-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 25 A 70

5SX4 525-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 25 A 55

5SY4 525-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 25 A 70

5SX4 532-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 32 A 55

5SY4 532-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 32 A 70

5SX4 532-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 32 A 55

5SY4 532-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 32 A 70

5SX4 540-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 40 A 55

5SY4 540-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 40 A 70

5SX4 540-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 40 A 55

5SY4 540-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 40 A 70

5SX4 550-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 50 A 55

5SY4 550-6

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. B, 50 A 70

5SX4 550-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 50 A 55

5SY4 550-7

Miniature circuit-breakers, 10 kA, 1-pole+N, Char. C, 50 A 70

5SX4 606-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 6 A

55

5SY4 606-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 6 A

5SX4 610-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 10 A 55

5SY4 610-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 10 A 70

5SX4 610-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 10 A 55

5SY4 610-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 10 A 70

5SX4 613-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 13 A 55

5SY4 613-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 13 A 70

5SX4 613-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 13 A 55

5SY4 613-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 13 A 70

5SX4 616-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 16 A 55

5SY4 616-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 16 A 70

5SX4 616-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 16 A 55

5SY4 616-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 16 A 70

5SX4 620-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 20 A 55

5SY4 620-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 20 A 70

5SX4 620-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 20 A 55

5SY4 620-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 20 A 70

5SX4 625-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 25 A 55

5SY4 625-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 25 A 70

5SX4 625-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 25 A 55

5SY4 625-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 25 A 70

5SX4 632-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 32 A 55

5SY4 632-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 32 A 70

5SX4 632-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 32 A 55

5SY4 632-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 32 A 70

5SX4 640-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 40 A 55

5SY4 640-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 40 A 70

5SX4 640-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 40 A 55

5SY4 640-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 40 A 70

5SX4 650-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 50 A 55

5SY4 650-6

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 50 A 70

5SX4 650-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. B, 50 A 55

5SY4 650-7

Miniature circuit-breakers, 10 kA, 3-pole+N, Char. C, 50 A 70

5SZ3 4260KG00

RCCBs, universal current sensitive, type B, 25 A, 4-pole, 55


30 mA, 8 MW

5SM3 342-4 RCCBs, SIQUENCE, universal current sensitive, type B,


25 A, 4-pole, 30 mA, 4 MW

70

5SZ3 4460KG00

RCCBs, universal current sensitive, type B, 40 A, 4-pole, 55


30 mA, 8 MW

5SM3 344-4 RCCBs, SIQUENCE, universal current sensitive, type B,


40 A, 4-pole, 30 mA, 4 MW

70

70

Siemens ET B1 2007

15/7

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

5SZ3 4660KG00

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


30 mA, 8 MW

5SM3 346-4 RCCBs, SIQUENCE, universal current sensitive, type B,


63 A, 4-pole, 30 mA, 4 MW

70

5SZ3 4660KG05

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


30 mA, 8 MW, med.

5SM3 346-4 RCCBs, SIQUENCE, universal current sensitive, type B,


63 A, 4-pole, 30 mA, 4 MW

70

5SZ3 4660KG30

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


30 mA, 8.5 MW, AS

5SM3 346-4 RCCBs, SIQUENCE, universal current sensitive, type B,


+5SW3 300 63 A, 4-pole, 30 mA, 4 MW+AS

70

5SZ3 4660KG35

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


30 mA, 8 MW, AS

5SM3 346-4 RCCBs, SIQUENCE, universal current sensitive, type B,


+5SW3 300 63 A, 4-pole, 30 mA, 4 MW+AS

70

5SZ6 4260KG00

RCCBs, universal current sensitive, type B, 25 A, 4-pole, 55


300 mA, 8 MW

5SM3 642-4 RCCBs, SIQUENCE, universal current sensitive, type B,


25 A, 4-pole, 300 mA, 4 MW

70

5SZ6 4460KG00

RCCBs, universal current sensitive, type B, 40 A, 4-pole, 55


300 mA, 8 MW

5SM3 644-4 RCCBs, SIQUENCE, universal current sensitive, type B,


40 A, 4-pole, 300 mA, 4 MW

70

5SZ6 4660KG00

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


300 mA, 8 MW

5SM3 646-4 RCCBs, SIQUENCE, universal current sensitive, type B,


63 A, 4-pole, 300 mA, 4 MW

70

5SZ6 4660KG05

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


300 mA, 8 MW, med.

5SM3 646-4 RCCBs, SIQUENCE, universal current sensitive, type B,


63 A, 4-pole, 300 mA, 4 MW

70

5SZ6 4660KG30

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


300 mA, 8.5 MW, AS

5SM3 646-4 RCCBs, SIQUENCE, universal current sensitive, type B,


+5SW3 300 63 A, 4-pole, 300 mA, 4 MW+AS

70

5SZ6 4660KG35

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


300 mA, 8 MW, AS

5SM3 646-4 RCCBs, SIQUENCE, universal current sensitive, type B,


+5SW3 300 63 A, 4-pole, 300 mA, 4 MW+AS

70

5SZ6 4680KG00

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


300 mA, 8 MW, selective

5SM3 646-5 RCCBs, SIQUENCE, universal current sensitive, type B,


63 A, 4-pole, 300 mA, 4 MW, selective

70

5SZ6 4680KG30

RCCBs, universal current sensitive, type B, 63 A, 4-pole, 55


300 mA, 8.5 MW, selective, AS

5SM3 646-5 RCCBs, SIQUENCE, universal current sensitive, type B,


+5SW3 300 63 A, 4-pole, 300 mA, 4 MW, selective+AS

70

5TE4 700

Pushbuttons, 16 A, 1 NO, 1 NC, gray

55

5TE4 800

Pushbuttons, 1 NO, 1 NC, 1 button, without maintainedcontact function

70

5TE4 701

Pushbuttons, 16 A, 1 NO, gray, illuminated

55

5TE4 821

Pushbuttons, 1 NO, 1 button, lamp

70

5TE4 702

Pushbuttons, 16 A, 1 NO, gray, illuminated

55

5TE4 820

Pushbuttons, 1 NO, 1 NC, 1 button, lamp

70

5TE4 703

Pushbuttons, 16 A, 1 NO, gray, illuminated

55

5TE4 822

Pushbuttons, 1 NO, 1 button, lamp, for long cables

70

5TE4 704

Pushbuttons, 16 A, 1 NO, 1 NC, red

55

5TE4 805

Pushbuttons, 16 A, 1 NO, 1 NC, red

70

5TE4 705

Pushbuttons, 16 A, 1 NO, 1 NC, green

55

5TE4 806

Pushbuttons, 16 A, 1 NO, 1 NC, green

70

5TE4 706

Pushbuttons, 16 A, 1 NO, 1 NC, yellow

55

5TE4 807

Pushbuttons, 16 A, 1 NO, 1 NC, yellow

70

5TE4 707

Pushbuttons, 16 A, 1 NO, 1 NC, blue

55

5TE4 808

Pushbuttons, 16 A, 1 NO, 1 NC, blue

70

5TE4 708

Pushbuttons, 16 A, 1 NO, 1 NC, blue

55

5TE4 808

Pushbuttons, 16 A, 1 NO, 1 NC, blue

70

5TE5 700

Light signals, lamp without caps

55

5TE5 800

Light indicator, 1 lamp

70

11

5TE5 701

Light signals, 230 V AC, 2 diodes

55

--

No replacement

--

--

5TE5 702

Light signals, lamp without caps, for long cables

55

5TE5 804

Light indicators, 1 lamp, for long cables

70

11

5TE6 700

SCHUKO socket outlets, 230 V AC, 16 A

55

5TE6 800

SCHUKO socket outlets, without cover, 230 V AC, 16 A

55/70

5TE6 710

SCHUKO socket outlets, acc. acc. to CEE7, 230 V AC,


16 A

55

5TE6 803

SCHUKO socket outlets, acc. to CEE 7, with grounding


pin, 230 V AC, 16 A

55/70

5TE6711

Outlets acc. to CEE7, child-proof

55

5TE6 803

SCHUKO socket outlets, acc. to CEE 7, with grounding


pin, 230 V AC, 16 A

55/70

5TE7 101

Control switches, 16 A, 1-pole, 16 A, OFF

55

5TE8 101

Control switches, 20 A, 1 NO, 1 lamp

70

5TE7 105

Control switches, 16 A, 1-pole, 16 A, OFF

55

5TE8 105

Control switches, 20 A, 1 NO, 1 lamp for long cables

70

5TE7 111

OFF switch, 16 A, 1-pole, 16 A, OFF, sealed

55

5TE8 111

OFF switches, 20 A, 1 S

70

5TE7 112

OFF switches, 16 A, 2-pole, 16 A, OFF, sealed

55

5TE8 112

OFF switches, 20 A, 2 S

70

5TE7 113

OFF switches, 16 A, 3-pole, 16 A, OFF, sealed

55

5TE8 113

OFF switches, 20 A, 3 S

70

5TE7 141

Group switches, 16 A, 1-pole,

55

5TE8 141

Group switches, 20 A, 1 group

70

5TE7 142

Group switches, 16 A, 2-pole,

55

5TE8 142

Group switches, 20 A, 2 groups

70

5TE7 161

Two-way switches, 16 A, 1-pole

55

5TE8 151

Two-way switches, 20 A, 1 NO, 1 NC

70

5TE7 162

Two-way switches, 16 A, 2-pole

55

5TE8 152

Two-way switches, 20 A, 2 NO, 2 NC

70

5TE7 165

Two-way switches, 16 A, 2 NO, 2 NC

55

5TE8 152

Two-way switches, 20 A, 2 NO, 2 NC

70

5TE7 211

OFF switches, 32 A, 1-pole, sealed

55

5TE8 211

OFF switches, 32 A, 1 NO, terminal 6 mm2

70

5TE7 212

OFF switches, 32 A, 2-pole, sealed

55

5TE8 212

OFF switches, 32 A, 2 NO, terminal 6 mm2

70

5TE7 213

OFF switches, 32 A, 3-pole, sealed

55

5TE8 213

OFF switches, 32 A, 3 NO, terminal 6 mm2

70

5TE7 214

OFF switches, 32 A, 3-pole+N, sealed

55

5TE8 214

OFF switches, 32 A, 3 NO+N, terminal 6 mm2

70

5TE7 313

OFF switches, 25 A, 3-pole, sealed

55

5TE8 213

OFF switches, 32 A, 3 NO, terminal 6 mm2

70

5TE7 314

OFF switches, 25 A, 3-pole+N, sealed

55

5TE8 218

OFF switches, 32 A, 3 NO+N+AS , terminal 6 mm2

70

5TE7 411

OFF switches, 40 A, 1-pole, sealed

55

5TE8 411

OFF switches, 40 A, 1 S

70

5TE7 412

OFF switches, 40 A, 2-pole, sealed

55

5TE8 412

OFF switches, 40 A, 2 S

70

5TE7 413

OFF switches, 40 A, 3-pole, sealed

55

5TE8 413

OFF switches, 40 A, 3 S

70

5TE7 414

OFF switches, 40 A, 3-pole+N, sealed

55

5TE8 414

OFF switches, 40 A, 3 NO+N

70

5TE7 511

OFF switches, 63 A, 1-pole, sealed

55

5TE8 511

OFF switches, 63 A, 1 S

70

5TE7 512

OFF switches, 63 A, 2-pole, sealed

55

5TE8 512

OFF switches, 63 A, 2 S

70

5TE7 513

OFF switches, 63 A, 3-pole, sealed

55

5TE8 513

OFF switches, 63 A, 3 S

70

5TE7 513-2

OFF switches, 63 A, 3-pole, lockable

55

--

No replacement

--

--

5TE7 514

OFF switches, 63 A, 3-pole+N, sealed

55

5TE8 514

OFF switches, 63 A, 3 NO+N

70

5TE7 514-2

OFF switches, 63 A, 3 -pole+N, lockable

55

--

No replacement

--

--

5TE7 611

OFF switches, 80 A, 1-pole, sealed

55

5TE8 611

OFF switches, 80 A, 1 S

70

mm

15/8

Siemens ET B1 2007

Mount- Chaping
ter
depth
mm

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

Mount- Chaping
ter
depth

5TE7 612

OFF switches, 80 A, 2-pole, sealed

55

5TE8 612

OFF switches, 80 A, 2 S

70

5TE7 613

OFF switches, 80 A, 3-pole, sealed

55

5TE8 613

OFF switches, 80 A, 3 S

70

5TE7 614

OFF switches, 80 A, 3-pole+N, sealed

55

5TE8 614

OFF switches, 80 A, 3 NO+N

70

5TE7 711

OFF switches, 100 A, 1-pole, sealed

55

5TE8 711

OFF switches, 100 A, 1 S

70

5TE7 712

OFF switches, 100 A, 2-pole, sealed

55

5TE8 712

OFF switches, 100 A, 2 S

70

5TE7 713

OFF switches, 100 A, 3-pole, sealed

55

5TE8 713

OFF switches, 100 A, 3 S

70

5TE7 714

OFF switches, 100 A, 3-pole+N, sealed

55

5TE8 714

OFF switches, 100 A, 3 NO+N

70

5TE7 813

OFF switches, 125 A, 3-pole, sealed

55

5TE8 813

OFF switches, 125 A, 3 S

70

5TE9 110

Phase connector, 50 mm2

55

5TE9 112

Phase connector, 50 mm2

70

5TE9 111

N-conductor connector, 50 mm2

55

5TE9 113

N-conductor connector, 50 mm2

70

mm

mm

5TT1 300

Energy-saving timers, 230 V

55

7LF6 115

Energy-saving timers, 230 V AC

70

5TT1 301

Lighting timers, 230 V

55

7LF6 114

Lighting timers, 230 V AC

70

5TT1 310

Timers, 230 V, 3-wire switch, L-momentary contact

55

5TT1 310-1

Timers, 230 V, 3-wire switch, L-momentary contact

55

14

5TT1 310

Timers, 230 V, 3-wire switch, L-momentary contact

55

7LF6 110

Timers, 230 V, 2000 W, 3-wire switch, L-momentary contact 70

5TT1 311

Timers, 230 V, 3/4-wire switch, N/L-momentary contact

55

5TT1 311-1

Timers, 230 V, 3/4-wire switch, N/L-momentary contact

55

14

5TT1 311

Timers, 230 V, 3/4-wire switch, N/L-momentary contact

55

7LF6 111

Timers, 230 V, 2000 W, 3/4-wire switch, N/L-momentary


contact

70

5TT1 312

Timers, 230 V, fan

55

7LF6 112

Timers, 230 V AC, fan

70

5TT1 313

Timers, 230 V, 3/4-wire switch, advance warning

55

5TT1 313-1

Timers, 230 V, 3/4-wire switch, advance warning

55

14

5TT1 313

Timers, 230 V, 3/4-wire switch, advance warning

55

7LF6 113

Timers, 230 V AC, warning

70

5TT3 180

Multifunctional timers, 24...230 V

55

5TT3 185

Multifunctional timers, 12...230 V

70

5TT3 304

Dusk switches, 500 lux, 1 channel

55

7LQ2 100

Dusk switches, 500 lux, 1 channel, 230 V

70

11

5TT3 305

Dusk switches, 500 lux, 2 channels

55

7LQ2 101

Dusk switches, 500 lux, 2 channels, 230 V

70

11

5TT3 306

Dusk switches, 500 lux, 1 channel

55

7LQ2 100

Dusk switches, 500 lux, 1 channel, 230 V

70

11

5TT3 420

Phase indicators, 230 V AC

55

5TE5 802

Phase monitors, 3 lamps

70

11

5TT3 422

Phase sequence indicators, 230 V AC

55

5TT3 423

Phase sequence monitors, 230 V, 4 A

70

11

5TT3 450

Alarm sensors, 230 V

55

--

No replacement

--

--

5TT3 451

Alarm sensors, 24 V

55

--

No replacement

--

--

5TT3 452

Alarm sensors, 230 V AC, adjustable

55

--

No replacement

--

--

5TT3 453

Alarm sensors, 24 V AC, adjustable

55

--

No replacement

--

--

5TT3 600

Temperature controllers, ON/OFF/Frost

55

--

No replacement

--

--

5TT3 601

Temperature controllers, Summer/OFF/Winter

55

--

No replacement

--

--

5TT3 602

Temperature controllers, Summer/Winter

55

--

No replacement

--

--

5TT3 608

Temperature display, for 5TT3 602

55

--

No replacement

--

--

5TT3 610

Temperature controllers, -30 ...+30 C

55

7LQ2 001

Temperature controllers, -30 ...+30 C, KTY

70

11

5TT3 611

Temperature controllers, -20 ...+40 C

55

7LQ2 001

Temperature controllers, -30 ...+30 C, KTY

70

11

5TT3 612

Temperature controllers, 0 ...+60 C

55

7LQ2 002

Temperature controllers, 0 ...+60 C, KTY

70

11

5TT3 613

Temperature controllers, +40 ...+100 C

55

7LQ2 003

Temperature controllers, +40 ...+100 C, KTY

70

11

5TT3 701

Insta contactors, 230 V, 24 A, 4 NO

70

5TT5 830-0

Insta contactors, 230 V AC, 24 A, 4 NO

70

5TT3 702

Insta contactors, 230 V, 24 A, 3 NO, 1 NC

70

5TT5 831-0

Insta contactors, 230 V AC, 24 A, 3 NO, 1 NC

70

5TT3 703

Insta contactors, 230 V, 24 A, 2 NO, 2 NC

70

5TT5 832-0

Insta contactors, 230 V AC, 24 A, 2 NO, 2 NC

70

5TT3 704

Insta contactors, 230 V, 24 A, 4 NC

70

5TT5 833-0

Insta contactors, 230 V AC, 24 A, 4 NC

70

5TT3 706

Insta contactors, 230 V, 40 A, 4 NO

70

5TT5 840-0

Insta contactors, 230 V AC, 40 A, 4 NO

70

5TT3 707

Insta contactors, 230 V, 63 A, 4 NO

70

5TT5 850-0

Insta contactors, 230 V AC, 63 A, 4 NO

70

5TT3 711

Insta contactors, 24 V, 24 A, 4 NO

70

5TT5 830-2

Insta contactors, 24 V AC, 24 A, 4 NO

70

5TT3 712

Insta contactors, 24 V, 24 A, 3 NO, 1 NC

70

5TT5 831-2

Insta contactors, 24 V AC, 24 A, 3 NO, 1 NC

70

5TT3 713

Insta contactors, 24 V, 24 A, 2 NO, 2 NC

70

5TT5 832-2

Insta contactors, 24 V AC, 24 A, 2 NO, 2 NC

70

5TT3 714

Insta contactors, 24 V, 24 A, 4 NC

70

5TT5 833-2

Insta contactors, 24 V AC, 24 A, 4 NC

70

5TT3 716

Insta contactors, 24 V, 40 A, 4 NO

70

5TT5 840-2

Insta contactors, 24 V AC, 40 A, 4 NO

70

5TT3 717

Insta contactors, 24 V, 63 A, 4 NO

70

5TT5 850-2

Insta contactors, 24 V AC, 63 A, 4 NO

70

5TT3 721

Insta contactors, 230 V, 40 A, 3 NO, 1 NC

70

5TT5 841-0

Insta contactors, 230 V AC, 40 A, 3 NO, 1 NC

70

5TT3 722

Insta contactors, 230 V, 40 A, 2 NO, 2 NC

70

5TT5 842-0

Insta contactors, 230 V AC, 40 A, 2 NO, 2 NC

70

5TT3 723

Insta contactors, 230 V, 40 A, 4 NC

70

5TT5 843-0

Insta contactors, 230 V AC, 40 A, 4 NC

70

5TT3 724

Insta contactors, 230 V, 63 A, 3 NO, 1 NC

70

5TT5 851-0

Insta contactors, 230 V AC, 63 A, 3 NO, 1 NC

70

5TT3 725

Insta contactors, 230 V, 63 A, 2 NO, 2 NC

70

5TT5 852-0

Insta contactors, 230 V AC, 63 A, 2 NO, 2 NC

70

5TT3 726

Insta contactors, 230 V, 63 A, 4 NC

70

5TT5 853-0

Insta contactors, 230 V AC, 63 A, 4 NC

70

5TT3 731

Insta contactors, 115 V, 24 A, 4 NO

70

5TT5 830-1

Insta contactors, 115 V AC, 24 A, 4 NO

70

5TT3 735

Insta contactors, 230 V, 21 A, 4 NO

70

--

No replacement

--

--

5TT3 741

Insta contactors, 24 V, 40 A, 3 NO, 1 NC

70

5TT5 841-2

Insta contactors, 24 V AC, 40 A, 3 NO, 1 NC

70

5TT3 742

Insta contactors, 24 V, 40 A, 2 NO, 2 NC

70

5TT5 842-2

Insta contactors, 24 V AC, 40 A, 2 NO, 2 NC

70

5TT3 743

Insta contactors, 24 V, 40 A, 4 NC

70

5TT5 843-2

Insta contactors, 24 V AC, 40 A, 4 NC

70

5TT3 744

Insta contactors, 24 V, 63 A, 3 NO, 1 NC

70

5TT5 851-2

Insta contactors, 24 V AC, 63 A, 3 NO, 1 NC

70

5TT3 745

Insta contactors, 24 V, 63 A, 2 NO, 2 NC

70

5TT5 852-2

Insta contactors, 24 V AC, 63 A, 2 NO, 2 NC

70

5TT3 746

Insta contactors, 24 V, 63 A, 4 NC

70

5TT5 853-2

Insta contactors, 24 V AC, 63 A, 4 NC

70

Siemens ET B1 2007

15/9

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

5TT3 761

Insta contactors, 230 V, 20 A, 2 NO

70

5TT5 800-0

Insta contactors, 230 V AC, 20 A, 2 NO

70

5TT3 762

Insta contactors, 230 V, 20 A, 1 NO, 1 NC

70

5TT5 801-0

Insta contactors, 230 V AC, 20 A, 1 NO, 1 NC

70

5TT3 763

Insta contactors, 230 V, 20 A, 2 NC

70

5TT5 802-0

Insta contactors, 230 V AC, 20 A, 2 NC

70

5TT3 764

Insta contactors, 230 V, 25 A, 1 NO

70

--

No replacement

--

--

5TT3 765

Insta contactors, 230 V, 25 A, 1 NC

70

--

No replacement

--

--

5TT3 771

Insta contactors, 24 V, 20 A, 2 NO

70

5TT5 800-2

Insta contactors, 24 V AC, 20 A, 2 NO

70

5TT3 772

Insta contactors, 24 V, 20 A, 1 NO, 1 NC

70

5TT5 801-2

Insta contactors, 24 V AC, 20 A, 1 NO, 1 NC

70

5TT3 773

Insta contactors, 24 V, 20 A, 2 NC

70

5TT5 802-2

Insta contactors, 24 V AC, 20 A, 2 NC

70

5TT3 774

Insta contactors, 24 V, 25 A, 1 NO

70

--

No replacement

--

--

5TT3 775

Insta contactors, 24 V, 25 A, 1 NC

70

--

No replacement

--

5TT3 791

Auxiliary switches, 230 V, 6 A, 2 NO

70

5TT5 910-0

Auxiliary switches for 5TT58 Insta contactors, 230 V, 6 A, 70


2 NO

5TT3 792

Auxiliary switches, 230 V, 6 A, 1 NO, 1 NC

70

5TT5 910-1

Auxiliary switches for 5TT58 Insta contactors, 230 V, 6 A, 70


1 NO + 1 NC

5TT3 794

Auxiliary switches, 48 V, 1 A, 1 CO

70

--

No replacement

--

--

5TT5 700-0

Insta contactors, 230 V AC, 20 A, 2 NO

70

5TT5 800-0

Insta contactors, 230 V AC, 20 A, 2 NO

70

5TT5 701-0

Insta contactors, 230 V AC, 20 A, 1 NO, 1 NC

70

5TT5 801-0

Insta contactors, 230 V AC, 20 A, 1 NO, 1 NC

70

5TT5 702-0

Insta contactors, 230 V AC, 20 A, 2 NC

70

5TT5 802-0

Insta contactors, 230 V AC, 20 A, 2 NC

70

5TT5 700-2

Insta contactors, 24 V AC, 20 A, 2 NO

70

5TT5 800-2

Insta contactors, 24 V AC, 20 A, 2 NO

70

5TT5 701-2

Insta contactors, 24 V AC, 20 A, 1 NO, 1 NC

70

5TT5 801-2

Insta contactors, 24 V AC, 20 A, 1 NO, 1 NC

70

5TT5 702-2

Insta contactors, 24 V AC, 20 A, 2 NC

70

5TT5 802-2

Insta contactors, 24 V AC, 20 A, 2 NC

70

5TT3 801

Remote switches, 230 V, 24 A, 4 NO

55

5TT5 730-0

Insta contactors, 230 V AC/DC, 24 A, 4 NO

70

5TT3 802

Remote switches, 230 V, 24 A, 3 NO, 1 NC

55

5TT5 731-0

Insta contactors, 230 V AC/DC, 24 A, 3 NO, 1 NC

70

mm

Mount- Chaping
ter
depth
mm
7

--

5TT3 803

Remote switches, 230 V, 24 A, 2 NO, 2 NC

55

5TT5 732-0

Insta contactors, 230 V AC/DC, 24 A, 2 NO, 2 NC

70

5TT3 804

Remote switches, 230 V, 24 A, 4 NO

55

5TT5 733-0

Insta contactors, 230 V AC/DC, 24 A, 4 NC

70

5TT3 806

Remote switches, 230 V, 40 A, 4 NO

55

5TT5 740-0

Insta contactors, 230 V AC/DC, 40 A, 4 NO

70

5TT3 807

Remote switches, 230 V, 63 A, 4 NO

55

5TT5 750-0

Insta contactors, 230 V AC/DC, 63 A, 4 NO

70

7
7

5TT3 811

Remote switches, 24 V, 24 A, 4 NO

55

5TT5 730-2

Insta contactors, 24 V AC/DC, 24 A, 4 NO

70

5TT3 812

Remote switches, 24 V, 24 A, 3 NO, 1 NC

55

5TT5 731-2

Insta contactors, 24 V AC/DC, 24 A, 3 NO, 1 NC

70

5TT3 813

Remote switches, 24 V, 24 A, 2 NO, 2 NC

55

5TT5 732-2

Insta contactors, 24 V AC/DC, 24 A, 2 NO, 2 NC

70

5TT3 814

Remote switches, 24 V, 24 A, 4 NO

55

5TT5 733-2

Insta contactors, 24 V AC/DC, 24 A, 4 NC

70

5TT3 816

Remote switches, 24 V, 40 A, 4 NO

55

5TT5 740-2

Insta contactors, 24 V AC/DC, 40 A, 4 NO

70

5TT3 817

Remote switches, 24 V, 63 A, 4 NO

55

5TT5 750-2

Insta contactors, 24 V AC/DC, 63 A, 4 NO

70

5TT3 821

Remote switches, 230 V, 40 A, 3 NO, 1 NC

55

5TT5 741-0

Insta contactors, 230 V AC/DC, 40 A, 3 NO, 1 NC

70

5TT3 822

Remote switches, 230 V, 40 A, 2 NO, 2 NC

55

5TT5 742-0

Insta contactors, 230 V AC/DC, 40 A, 2 NO, 2 NC

70

5TT3 823

Remote switches, 230 V, 40 A, 4 NO

55

--

No replacement

--

--

5TT3 824

Remote switches, 230 V, 63 A, 3 NO, 1 NC

55

5TT5 751-0

Insta contactors, 230 V AC/DC, 63 A, 3 NO, 1 NC

70

5TT3 825

Remote switches, 230 V, 63 A, 2 NO, 2 NC

55

5TT5 752-0

Insta contactors, 230 V AC/DC, 63 A, 2 NO, 2 NC

70

5TT3 831

Remote switches, 115 V, 24 A, 4 NO

55

5TT5 730-1

Insta contactors, 115 V AC/DC, 24 A, 4 NO

70

5TT3 835

Remote switches, 230 V, 21 A, 4 NO

55

--

No replacement

--

--

5TT3 841

Remote switches, 24 V, 40 A, 3 NO, 1 NC

55

5TT5 741-2

Insta contactors, 24 V AC/DC, 40 A, 3 NO, 1 NC

70

7
7

5TT3 842

Remote switches, 24 V, 40 A, 2 NO, 2 NC

55

5TT5 742-2

Insta contactors, 24 V AC/DC, 40 A, 2 NO, 2 NC

70

5TT3 843

Remote switches, 24 V, 40 A, 4 NO

55

--

No replacement

--

--

5TT3 844

Remote switches, 24 V, 63 A, 3 NO, 1 NC

55

5TT5 751-2

Insta contactors, 24 V AC/DC, 63 A, 3 NO, 1 NC

70

5TT3 845

Remote switches, 24 V, 63 A, 2 NO, 2 NC

55

5TT5 752-2

Insta contactors, 24 V AC/DC, 63 A, 2 NO, 2 NC

70

5TT3 861

Remote switches, 230 V, 20 A, 2 NO

55

5TT5 800-0

Insta contactors, 230 V AC, 20 A, 2 NO

70

5TT3 862

Remote switches, 230 V, 20 A, 1 NO, 1 NC

55

5TT5 801-0

Insta contactors, 230 V AC, 20 A, 1 NO, 1 NC

70

5TT3 863

Remote switches, 230 V, 20 A, 2 NO

55

5TT5 802-0

Insta contactors, 230 V AC, 20 A, 2 NC

70

5TT3 864

Remote switches, 230 V, 25 A, 1 NO

55

--

No replacement

--

--

5TT3 865

Remote switches, 230 V, 25 A, 1 NO

55

--

No replacement

--

--

5TT3 871

Remote switches, 24 V, 20 A, 2 NO

55

5TT5 800-2

Insta contactors, 24 V AC, 20 A, 2 NO

70

5TT3 872

Remote switches, 24 V, 20 A, 1 NO, 1 NC

55

5TT5 801-2

Insta contactors, 24 V AC, 20 A, 1 NO, 1 NC

70

5TT3 873

Remote switches, 24 V, 20 A, 2 NO

55

5TT5 802-2

Insta contactors, 24 V AC, 20 A, 2 NC

70

5TT3 874

Remote switches, 24 V, 25 A, 1 NO

55

--

No replacement

--

--

5TT3 875

Remote switches, 24 V, 25 A, 1 NO

55

--

No replacement

--

--

5TT3 893

Interference voltage limiter

55

--

No replacement

--

--

5TT3 983

Remote switches, 230 V, 20 A, 4 NO

55

5TT5 830-0

Insta contactors, 230 V AC, 25 A, 4 NO

70

5TT3 984

Remote switches, 110 V, 20 A, 4 NO

55

5TT5 830-1

Insta contactors, 115 V AC, 25 A, 4 NO

70

5TT3 985

Remote switches, 24 V, 20 A, 4 NO

55

5TT5 830-2

Insta contactors, 24 V AC, 25 A, 4 NO

70

5TT3 986

Remote switches, 24 V DC, 20 A, 4 NO

55

5TT5 730-2

Insta contactors, 24 V AC/DC, 24 A, 4 NO

70

5TT3 987

Remote switches, 230 V, 20 A, 3 NO, 1 NC

55

5TT5 831-0

Insta contactors, 230 V AC, 25 A, 3 NO + 1 NC

70

5TT3 988

Remote switches, 110 V, 20 A, 3 NO, 1 NC

55

5TT5 831-1

Insta contactors, 115 V AC, 25 A, 3 NO + 1 NC

70

5TT3 990

Remote switches, 24 V, 20 A, 3 NO, 1 NC

55

5TT5 831-2

Insta contactors, 24 V AC, 25 A, 3 NO + 1 NC

70

5TT3 991

Remote switches, 24 V DC, 20 A, 3 NO, 1 NC

55

5TT5 730-2

Insta contactors, 24 V AC/DC, 24 A, 3 NO + 1 NC

70

5TT3 041

Switching relays, 8 V, 16 A, 1 NO

55

5TT4 201-4

Switching relays, 8 V AC, 16 A, 1 NO

70

15/10

Siemens ET B1 2007

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

Mount- Chaping
ter
depth

5TT3 042

Switching relays, 12 V, 16 A, 1 NO

55

5TT4 201-3

Switching relays, 12 V AC, 16 A, 1 NO

70

5TT3 043

Switching relays, 24 V, 16 A, 1 NO

55

5TT4 201-2

Switching relays, 24 V AC, 16 A, 1 NO

70

5TT3 044

Switching relays, 110 V, 16 A, 1 NO

55

5TT4 201-2

Switching relays, 115 V AC, 16 A, 1 NO

70

5TT3 045

Switching relays, 230 V, 16 A, 1 NO

55

5TT4 201-0

Switching relays, 230 V AC, 16 A, 1 NO

70

5TT3 051

Switching relays, 8 V, 16 A, 2 NO

55

5TT4 202-4

Switching relays, 8 V AC, 16 A, 2 NO

70

5TT3 052

Switching relays, 12 V, 16 A, 2 NO

55

5TT4 202-3

Switching relays, 12 V AC, 16 A, 2 NO

70

5TT3 053

Switching relays, 24 V, 16 A, 2 NO

55

5TT4 202-2

Switching relays, 24 V AC, 16 A, 2 NO

70

5TT3 054

Switching relays, 110 V, 16 A, 2 NO

55

5TT4 202-1

Switching relays, 115 V AC, 16 A, 2 NO

70

mm

mm

5TT3 055

Switching relays, 230 V, 16 A, 2 NO

55

5TT4 202-0

Switching relays, 230 V AC, 16 A, 2 NO

70

5TT3 061

Switching relays, 8 V, 16 A, 1 CO

55

5TT4 206-4

Switching relays, 8 V AC, 16 A, 1 CO

70

5TT3 062

Switching relays, 12 V, 16 A, 1 CO

55

5TT4 206-3

Switching relays, 12 V AC, 16 A, 1 CO

70

5TT3 063

Switching relays, 24 V, 16 A, 1 CO

55

5TT4 206-2

Switching relays, 24 V AC, 16 A, 1 CO

70

5TT3 064

Switching relays, 110 V, 16 A, 1 CO

55

5TT4 206-1

Switching relays, 115 V AC, 16 A, 1 CO

70

5TT3 065

Switching relays, 230 V, 16 A, 1 CO

55

5TT4 206-0

Switching relays, 230 V AC, 16 A, 1 CO

70

5TT3 071

Switching relays, 8 V, 16 A, 2 CO

55

5TT4 207-4

Switching relays, 8 V AC, 16 A, 2 CO

70

5TT3 072

Switching relays, 12 V, 16 A, 2 CO

55

5TT4 207-3

Switching relays, 12 V AC, 16 A, 2 CO

70

5TT3 073

Switching relays, 24 V, 16 A, 2 CO

55

5TT4 207-2

Switching relays, 24 V AC, 16 A, 2 CO

70

5TT3 074

Switching relays, 110 V, 16 A, 2 CO

55

5TT4 207-1

Switching relays, 115 V AC, 16 A, 2 CO

70

5TT3 075

Switching relays, 230 V, 16 A, 2 CO

55

5TT4 207-0

Switching relays, 230 V AC, 16 A, 2 CO

70

5TT3 076

Switching relays, 24 V DC, 16 A, 2 CO

55

--

Available soon

--

--

5TT3 077

Switching relays, 110 V DC, 16 A, 2 CO

55

--

Available soon

--

--

5TT3 078

Switching relays, 12 V DC, 16 A, 2 CO

55

--

Available soon

--

--

5TT3 080

Sealable enable relays, 230 V, 16 A, 1 CO

55

--

no changeover

--

--

5TT3 081

Switching relays, 230 V, 16 A, 1 NO, capacitive loads

55

--

No replacement

--

--

5TT3 082

Switching relays, 30 V DC, 16 A, 2 CO

55

--

Available soon

--

--

5TT3 085

Switching relays, 230 V, 16 A, 1 NO, PLC control

55

--

No replacement

--

--

5TT5 150

Remote control switches, 24 V, 16 A, 1 S, ZA/ZE group

55

--

No replacement

--

--

5TT5 151

Remote control switches, 230 V, 16 A, 1 S, ZA/ZE group

55

--

No replacement

--

--

5TT5 152

Remote control switches, 24 V, 16 A, 2 S, ZA/ZE group

55

--

No replacement

--

--

5TT5 153

Remote control switches, 230 V, 16 A, 2 S, ZA/ZE group

55

--

No replacement

--

--

5TT5 163

Remote control switches, shutter/blind, 230 V, 2 NO

55

5TT4 142-0

Remote control switches, shutter/blind, 230 V AC,


16 A, 2 NO

70

5TT5 164

Remote control switches, series, 230 V AC, 16 A, 2 NO

55

5TT4 132-0

Remote control switches, series, 230 V AC, 16 A, 2 NO

70

5TT5 165

Remote control switches, series, 24 V AC, 16 A, 2 NO

55

--

No replacement

--

--

5TT5 166

Remote control switches, series, 12 V AC, 16 A, 2 NO

55

--

No replacement

--

--

5TT5 501

Remote control switches, 12 V AC, 16 A, 1 NO

55

5TT4 101-3

Remote control switches, 12 V AC, 16 A, 1 NO

70

5TT5 502

Remote control switches, 12 V AC, 16 A, 2 NO

55

5TT4 102-3

Remote control switches, 12 V AC, 16 A, 2 NO

70

5TT5 503

Remote control switches, 12 V, 16 A, 3 NO

55

--

No replacement

--

--

5TT5 506

Remote control switches, 12 V, 16 A, 1 CO

55

--

No replacement, alternatively, 5TT4 105-3, 12 V AC,


16 A, 1 NO+ 1 NC

70

5TT5 511

Remote control switches, 8 V, 16 A, 1 NO

55

5TT4 101-4

Remote control switches, 8 V AC, 16 A, 1 NO

70

5TT5 512

Remote control switches, 8 V, 16 A, 2 NO

55

5TT4 102-4

Remote control switches, 8 V AC, 16 A, 2 NO

70

5TT5 516

Remote control switches, 8 V, 16 A, 1 CO

55

--

No replacement,
alternatively, 5TT4 105-4, 8 V AC, 16 A, 1 NO+ 1 NC

70

5TT5 521

Remote control switches, 24 V, 16 A, 1 NO

55

5TT4 101-2

Remote control switches, 24 V AC, 16 A, 1 NO

70

5TT5 522

Remote control switches, 24 V, 16 A, 2 NO

55

5TT4 102-2

Remote control switches, 24 V AC, 16 A, 2 NO

70

5TT5 523

Remote control switches, 24 V, 16 A, 3 NO

55

5TT4 103-2

Remote control switches, 24 V AC, 16 A, 3 NO

70

5TT5 526

Remote control switches, 24 V, 16 A, 1 CO

55

--

No replacement, alternatively, 5TT4 105-2, 24 V AC,


16 A, 1 NO+ 1 NC

70

5TT5 531

Remote control switches, 230 V, 16 A, 1 NO

55

5TT4 101-0

Remote control switches, 230 V AC, 16 A, 1 NO

70

5TT5 532

Remote control switches, 230 V, 16 A, 2 NO

55

5TT4 102-0

Remote control switches, 230 V AC, 16 A, 2 NO

70

5TT5 533

Remote control switches, 230 V, 16 A, 3 NO

55

5TT4 103-0

Remote control switches, 230 V AC, 16 A, 3 NO

70

5TT5 534

Remote control switches, 230 V, 16 A, 2 NO, ZA/ZE group 55

5TT4 122-0

Remote control switches, 230 V AC, 16 A, 2 NO, ZA/ZE


group

70

5TT5 535

Remote control switches, 230 V, 16 A, 1 CO, ZA/ZE group 55

--

No replacement, alternatively, 5TT4 125-0, 230 V AC,


16 A, 1 NO+ 1 NC

70

5TT5 536

Remote control switches, 230 V, 16 A, 1 CO

--

No replacement, alternatively, 5TT4 105-1, 230 V AC,


16 A, 1 NO+ 1 NC

70

5TT5 537

Remote control switches, 230 V, 16 A, 3 NO, ZA/ZE group 55

5TT4 123-0

Remote control switches, 230 V AC, 16 A, 3 NO, ZA/ZE


group

70

5TT5 541

Remote control switches, 110 V, 16 A, 1 NO

55

5TT4 101-1

Remote control switches, 115 V AC, 16 A, 1 NO

70

5TT5 542

Remote control switches, 110 V, 16 A, 2 NO

55

5TT4 102-1

Remote control switches, 115 V AC, 16 A, 2 NO

70

5TT5 543

Remote control switches, 110 V, 16 A, 3 NO

55

--

No replacement

--

--

5TT5 546

Remote control switches, 110 V, 16 A, 1 CO

55

--

No replacement

--

--

5TT5 551

Remote control switches, 12 V DC, 16 A, 1 NO

55

--

Available soon

--

--

5TT5 552

Remote control switches, 12 V DC, 16 A, 2 NO

55

--

Available soon

--

--

5TT5 650

Remote control switches, 12 V, 16 A, 2 NO, series

55

--

No replacement

--

--

55

Siemens ET B1 2007

15/11

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

5TT5 601

Remote control switches, 24 V, 16 A, 1 NO

55

--

No replacement

--

5TT5 602

Remote control switches, 230 V, 16 A, 1 NO

55

--

No replacement

--

--

5TT5 603

Remote control switches, 12 V, 16 A, 1 NO,

55

--

No replacement

--

--

mm

Mount- Chaping
ter
depth
mm
--

5TT5 605

Remote control switches, 24 V, 10 A, 1 NO, 2 syst.

55

--

No replacement

--

--

5TT5 606

Remote control switches, 230 V, 10 A, 1 NO, 2 syst.

55

--

No replacement

--

--

5TT5 607

Remote control switches, 12 V, 10 A, 1 NO, 2 syst.

55

--

No replacement

--

--

5TT5 611

Remote control switches, 230 V, 10 A, 1 NO,


central switching

55

--

No replacement

--

--

5TT5 612

Remote control switches, 230 V, 10 A, 1 NO, 2 syst.,


central switching

55

--

No replacement

--

--

5TT5 613

Remote control switches, 230 V, 10 A, 1 NO, 3 syst.,


central switching

55

--

No replacement

--

--

5TT5 614

Remote control switches, 230 V, 10 A, 1 NO, 4 syst.,


central switching

55

--

No replacement

--

--

5TT5 621

Remote control switches, 230 V, 10 A, 1 NO,


central + group switching

55

--

No replacement

--

--

5TT5 623

Remote control switches, 230 V, 10 A, 1 NO, 3 syst.,


central + group switching.

55

--

No replacement

--

--

5TG8 230

Compensators 230 V

55

--

Available soon for 5TT4 1...

--

--

5TG8 236

Transparent caps 1 MW(1 set = 5 units) for 5TT5 5.., 1TE --

--

No replacement

--

--

5TG8 237

Transparent caps, 1 MW(1 set = 5 units) for 5TT3,


5TT5 1, 5TT5 6

--

--

No replacement

--

--

5TG8 238

Transparent caps, 2 MW(1 set = 5 units) for 5TT3, 5TT5, -2 MW

--

No replacement

--

--

5TT6 110

Current monitors, 230 V, 5 A, for transformers

55

--

No replacement

--

--

7KT1 130

Multimeters with S0 interface, direct connection

70

7KT1 310

Multicounters with S0 interface

70

10

7KT1 131

Multimeters with S0 interface, transformer connection

70

7KT1 311

Multicounters with S0 interface, transformer connection

70

10

7KT1 132

Multimeters with S0 interface, direct connection

70

7KT1 310

Multicounters with S0 interface

70

10

7KT1 133

Multimeters with S0 interface, transformer connection

70

7KT1 311

Multicounters with S0 interface, transformer connection

70

10

7KT1 151

E-counters, 3/4L, 63 A, S0 pulse output, single rate

70

7KT1 500

E-counters, 63 A, kWh, single rate

70

10

7KT1 152

E-counters, 3/4L, 63 A, S0 pulse output, double rate

70

7KT1 510

E-counters, 63 A, kWh, double rate

70

10

7KT1 154

E-counters, 3/4L, /5 A, S0 pulse output, single rate

70

7KT1 501

E-counters, /5 A, kWh, single rate

70

10

7KT1 155

E-counters, 3/4L, /5 A, S0 pulse output, double rate

70

7KT1 511

E-counters, /5 A, kWh, double rate

70

10

7KT1 160

E-counters, 3/4L, 63 A, 1 x S0 pulse output

70

7KT1 502

E-counters, 63 A, kWh/kvarh, single rate

70

10

7KT1 161

E-counters, 3/4L, 63 A, 2 x S0 pulse output

70

7KT1 512

E-counters, 63 A, kWh/kvarh, double rate

70

10

7KT1 163

E-counters, 3/4L, /5 A, 1 x S0 pulse output

70

7KT1 503

E-counters, /5 A, kWh/kvarh, single rate

70

10

7KT1 164

E-counters, 3/4L, /5 A, 2 x S0 pulse output

70

7KT1 513

E-counters, /5 A, kWh/kvarh, double rate

70

10

7KT5 745

Time counters, 12...24 V DC

55

7KT5 801

Mech. time counters, 10...27 V DC

70

10

7KT5 745-0

Time counters, 115 V AC 50 Hz

55

7KT5 803

Mech. time counters, 115 V AC 50 Hz

70

10

7KT5 745-1

Time counters, 230 V AC 50 Hz

55

7KT5 804

Mech. time counters, 230 V AC 50 Hz

70

10

7KT5 745-2

Time counters, 115 V AC 60 Hz

55

7KT5 806

Mech. time counters, 115 V AC 60 Hz

70

10

7KT5 745-3

Time counters, 230 V AC 60 Hz

55

7KT5 807

Mech. time counters, 230 V AC 60 Hz

70

10

7KT5 745-4

Time counters, 24 V AC 50 Hz

55

7KT5 802

Mech. time counters, 24 V AC 50 Hz

70

10

7KT5 751

Pulse counters 24 V DC

55

7KT5 811

Mech. pulse counter 24 V DC

70

10

7KT5 752

Pulse counters, 24 V AC 50 Hz

55

7KT5 812

Mech. pulse counters, 24 V AC 50/60 Hz

70

10

7KT5 753

Pulse counters, 230 V AC 50 Hz

55

7KT5 814

Mech. pulse counters, 230 V AC 50/60 Hz

70

10

7KT5 761

Time counters, 2 x 230 V AC, 50 Hz

55

--

No replacement

--

--

7KT5 762

Time/Pulse counters, 2 x 230 V AC

55

--

No replacement

--

--

7KT5 763

Pulse counters, 2 x 230 V AC 50 Hz

55

--

No replacement

--

--

7KT5 770

Time counters, 12...60 V DC

55

7KT5 821

El. time counters, 12...150 V DC, 24...240 V AC,


50/60 Hz

70

10

7KT5 771

Time counters, 80...230 V AC, 50 Hz

55

7KT5 821

El. time counters, 12...150 V DC, 24...240 V AC,


50/60 Hz

70

10

7KT5 775

Time counters, 12...60 V DC reset

55

7KT5 822

El. time counters, 12...150 V DC, 24...240 V AC,


50/60 Hz, el. reset

70

10

7KT5 776

Time counters, 80...230 V AC, 50 Hz, reset

55

7KT5 822

El. time counters, 12...150 V DC, 24...240 V AC,


50/60 Hz, el. reset

70

10

7KT5 780

Pulse counters, 12...60 V DC

55

7KT5 833

El. pulse counters, 12...150 V DC, 24...240 V AC,


50/60 Hz, el./mech. reset

70

10

7KT5 781

Pulse counters, 80...230 V AC, 50 Hz

55

7KT5 833

El. pulse counters, 12...150 V DC, 24...240 V AC,


50/60 Hz, el./mech. reset

70

10

7KT5 785

Pulse counters, 12...60 V DC, reset

55

7KT5 833

El. pulse counters, 12...150 V DC, 24...240 V AC,


50/60 Hz, el./mech. reset

70

10

7KT5 786

Pulse counters, 80...230 V, 50 Hz, reset

55

7KT5 833

El. pulse counters, 12...150 V DC, 24...240 V AC,


50/60 Hz, el./mech. reset

70

10

7LF4 101

Dig. time switches, 1 channel, 230 V, 16 A

55

7LF4 401-0

Dig. time switches, Mini, 1 channel, week, 230 V

70

7LF4 110

Dig. time switches, 1 channel, day, 230 V, 16 A

55

7LF4 411-0

Dig. time switches, Top 1 channel, week, 230 V

70

7LF4 111

Dig. time switches, 1 channel, week, 230 V, 16 A

55

7LF4 411-0

Dig. time switches, Top 1 channel, week, 230 V

70

7LF4 112

Dig. time switches, 1 channel, week, 24 V, 16 A

55

7LF4 421-2

Dig. time switches, Profi, 1 channel, week, 24 V

70

7LF4 114

Dig. time switches, 1 channel, week, 230 V, 16 A

55

7LF4 421-0

Dig. time switches, Profi, 1 channel, week, 230 V

70

15/12

Siemens ET B1 2007

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

Mount- Chaping
ter
depth

7LF4 120

Dig. time switches, 2 channels, week, 230 V

55

7LF4 412-0

Dig. time switches, Top, 2 channel, week, 230 V

70

7LF4 121

Dig. time switches, 2 channels, week, 230 V

55

7LF4 422-0

Dig. time switches, Profi, 2 channels, week, 230 V

70

7LF4 143

DC F-77 power supply unit

55

--

No replacement

--

--

7LF4 144

DC F-77 power supply unit+IR interface

55

--

No replacement

--

--

7LF4 150

Dig. time switches, year

55

7LF4 444-0

Dig. time switches, Expert, 4 channels, year, 85...240 V

70

7LF4 151

Dig. time switches, 2 channels, year

55

7LF4 444-0

Dig. time switches, Expert, 4 channels, year, 85...240 V

70

7LF4 152

Dig. time switches, 3 channels, year

55

7LF4 444-0

Dig. time switches, Expert, 4 channels, year, 85...240 V

70

7LF4 153

Dig. time switches, 3 channels, year, 24 V

55

7LF4 444-2

Dig. time switches, Expert, 4 channels, year, 24 V AC/DC 70

7LF4 154

Dig. time switches, 3 channels, year, 12 V

55

--

No replacement

--

--

7LF5 101

Synchronous time switches, 1 MW

55

7LF5 390-1

Synchronous time switches, 1 NO, day, 1 MW

55

14

7LF5 141

Quartz-clock time switches, day, 1 MW

55

7LF5 391-1

Quartz-clock time switches, 1 NO, day, 1 MW

55

14

7LF5 201

Synchronous time switches, 1 NO, day, 1 MW

55

7LF5 300-1

Synchronous time switches, 1 NO, day, 1 MW

70

7LF5 211

Quartz-clock time switches, 1 NO, 1 MW

55

7LF5 301-1

Quartz-clock time switches, 1 NO, day, 1 MW

70

7LF5 216

Quartz-clock time switches, 1 CO, day, 3 MW

55

7LF5 301-6

Quartz-clock time switches, 1 CO, day, 3 MW

70

7LF5 217

Quartz-clock time switches, 1 CO, week, 3 MW

55

7LF5 301-7

Quartz-clock time switches, 1 CO, week, 3 MW

70

7LQ1 005

Quartz-clock time switches, 1 NO, day

55

7LF5 391-1

Quartz-clock time switches, 1 NO, day, 1 MW

55

14

7LQ1 005

Quartz-clock time switches, 1 NO, day

55

7LF5 301-1

Quartz-clock time switches, 1 NO, day, 1 MW

70

7LQ1 006

Quartz-clock time switches, 1 CO, day

55

7LF5 391-6

Quartz-clock time switches, 1 CO, day, 3 MW

55

14

7LQ1 006

Quartz-clock time switches, 1 CO, day

55

7LF5 301-6

Quartz-clock time switches, 1 CO, day, 3 MW

70

7LQ1 007

Quartz-clock time switches, day/week

55

7LF5 391-7

Quartz-clock time switches, 1 CO, week, 3 MW

55

14

7LQ1 007

Quartz-clock time switches, day/week

55

7LF5 301-7

Quartz-clock time switches, 1 CO, week, 3 MW

70

7LQ1 008

Quartz-clock time switches, day/week

55

--

No replacement

--

--

7LQ1 106

Quartz-clock time switches, day, 3 MW

55

7LF5 391-6

Quartz-clock time switches, 1 CO, day, 3 MW

55

14

mm

mm

7LQ1 107

Quartz-clock time switches, week, 3 MW

55

7LF5 391-7

Quartz-clock time switches, 1 CO, week, 3 MW

55

14

7LS1 004

Synchronous time switches, 1 NO, day

55

7LF5 390-1

Synchronous time switches, 1 NO, day, 1 MW

55

14

7LS1 004

Synchronous time switches, 1 NO, day

55

7LF5 300-1

Synchronous time switches, 1 NO, day, 1 MW

70

7LS1 005

Synchronous time switches, 1 CO, day

55

7LF5 300-5

Synchronous time switches, 1 CO, day, 3 MW

70

7LS1 006

Synchronous time switches, 1 CO, week

55

7LF5 300-6

Synchronous time switches, 1 CO, week, 3 MW

70

7LS1 007

Synchronous time switches, 1 CO, hour

55

7LF5 300-7

Synchronous time switches, 1 NO, hour, 1 MW

70

7LS1 008

Synchronous time switches, day/week

55

--

No replacement

--

--

7LS1 010

Synchronous time switches, day/day

55

--

No replacement

--

--

7LS1 105

Synchronous time switches, day, 3 MW

55

7LF5 300-5

Synchronous time switches, 1 CO, day, 3 MW

70

7LS1 106

Synchronous time switches, week, 3 MW

55

7LF5 300-6

Synchronous time switches, 1 CO, week, 3 MW

70

7LS1 107

Synchronous time switches, hour, 3 MW

55

7LF5 300-7

Synchronous time switches, 1 NO, hour, 1 MW

70

5SD7 311-0

Lightning arresters, type 1, 1-pole, unenclosed, 75 kA

58

--

Alternatively use multipole 5SD7 41.-. lightning arresters 70

5SD7 318-0

Lightning arresters, type 1, 1-pole, N/PE, unenclosed, 100 kA 58

--

Alternatively use multipole 5SD7 41.-. lightning arresters 70

5SD7 311-1

Lightning arresters, type 1, 1-pole, enclosed, 50 kA

58

--

Alternatively use multipole 5SD7 41.-. lightning arresters 70

5SD7 318-1

Lightning arresters, type 1, 1-pole, N/PE, enclosed, 100 kA

58

--

Alternatively use multipole 5SD7 41.-. lightning arresters 70

5SD7 315-0

Lightning arresters, type 1, 1-pole, unenclosed, 50 kA

58

--

Alternatively use multipole 5SD7 41.-. lightning arresters 70

5SD7 343-0

Combination arresters, type 1+2, 3-pole, for TN-C systems 58

5SD7 443-1

Combination arresters, type 1+2, 3-pole, for TN-C systems 70

5SD7 344-0

Combination arresters, type 1+2, 4-pole, circuit,


for TN-C systems

58

5SD7 444-1

Combination arresters, type 1+2, 4-pole,


for TN-S- and TT systems

70

5SD7 343-1

Combination arresters, type 1+2, 4-pole,


for TN-S- and TT systems

58

5SD7 444-1

Combination arresters, type 1+2, 4-pole,


for TN-S- and TT systems

70

5SD7 341-1

Combination arresters, type 1+2, 2-pole,


for TN-S- and TT systems

58

5SD7 442-1

Combination arresters, type 1+2, 2-pole,


for TN-S- and TT systems

70

5SD7 348-3

Remote signaling modules for 5SD7 343-0, 5SD7 3.4-0


and 5SD7 3.3-1 combination arresters

58

--

No replacement, no longer required


(integral remote signaling)

--

--

5SD7 348-1

Remote signaling modules for 5SD7 341-1 combination


arresters

58

--

No replacement, no longer required


(integral remote signaling)

--

--

5SD7 300-2

Surge arresters, type 2, 1-pole, L/N, 275 V, not plug-in

70

5SD7 466-0

Surge arresters, type 2, 1-pole, L/N, 350 V, not plug-in

70

5SD7 300-5

Surge arresters, type 2, 1-pole, L/N, 385 V, not plug-in

70

--

No replacement

--

--

5SD7 301-2

Surge arresters, type 2, 1-pole, L/N, 275 V,


remote signaling, not plug-in

70

5SD7 466-1

Surge arresters, type 2, 1-pole, L/N, 350 V, remote


signaling, not plug-in

70

5SD7 302-2

Surge arresters, type 2, 1-pole, L/N, 275 V, plug-in

70

5SD7 461-0

Surge arresters, type 2, 1-pole, L/N, 350 V, plug-in

70

5SD7 302-4

Surge arresters, type 2, 1-pole, L/N, 335 V, plug-in

70

5SD7 461-0

Surge arresters, type 2, 1-pole, L/N, 350 V, plug-in

70

5SD7 303-2

Surge arresters, type 2, 1-pole, L/N, 275 V,


remote signaling, plug-in

70

5SD7 461-1

Surge arresters, type 2, 1-pole, L/N, 350 V, remote


signaling, plug-in

70

5SD7 303-4

Surge arresters, type 2, 1-pole, L/N, 335 V,


remote signaling, plug-in

70

5SD7 461-1

Surge arresters, type 2, 1-pole, L/N, 350 V, remote


signaling, plug-in

70

5SD7 303-5

Surge arresters, type 2, 1-pole, L/N, 385 V,


remote signaling, plug-in

70

--

No replacement

--

--

5SD7 308-0

Surge arresters, type 2, 1-pole, N/PE, 275 V, plug-in

70

5SD7 481-0

Surge arresters, type 2, 1-pole, N/PE, 275 V, plug-in

70

5SD7 323-2

Surge arresters, type 2, 3-pole, 275 V,


for TN-C systems, plug-in

70

5SD7 463-0

Surge arresters, type 2, 3-pole, 350 V,


for TN-C systems, plug-in

70

5SD7 323-4

Surge arresters, type 2, 3-pole, 335 V,


for TN-C systems, plug-in

70

5SD7 463-0

Surge arresters, type 2, 3-pole, 350 V,


for TN-C systems, plug-in

70

Siemens ET B1 2007

15/13

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Notes on Product Changeover


Product changeover
Type

Product

Mount- Type
ing
depth

Successor product

5SD7 323-5

Surge arresters, type 2, 3-pole, 385 V,


for TN-C systems, plug-in

70

--

No replacement

--

--

5SD7 324-2

Surge arresters, type 2, 3-pole, 275 V,


for TN-C systems, remote signaling, plug-in

70

5SD7 463-1

Surge arresters, type 2, 3-pole, 350 V,


for TN-C systems, remote signaling, plug-in

70

5SD7 324-4

Surge arresters, type 2, 3-pole, 335 V,


for TN-C systems, remote signaling, plug-in

70

5SD7 463-1

Surge arresters, type 2, 3-pole, 350 V,


for TN-C systems, remote signaling, plug-in

70

5SD7 324-5

Surge arresters, type 2, 3-pole, 385 V,


for TN-C systems, remote signaling, plug-in

70

--

No replacement

--

--

5SD7 325-2

Surge arresters, type 2, 4-pole, 275 V,


for TN-S systems, plug-in

70

5SD7 464-0

Surge arresters, type 2, 4-pole, 350 V,


for TN-S and TT systems, plug-in

70

5SD7 325-4

Surge arresters, type 2, 4-pole, 335 V,


for TN-S systems, plug-in

70

5SD7 464-0

Surge arresters, type 2, 4-pole, 350 V,


for TN-S and TT systems, plug-in

70

5SD7 325-5

Surge arresters, type 2, 4-pole, 385 V,


for TN-S systems, plug-in

70

--

No replacement

--

--

5SD7 326-2

Surge arresters, type 2, 4-pole, 275 V,


for TN-S systems, remote signaling, plug-in

70

5SD7 464-1

Surge arresters, type 2, 4-pole, 350 V,


for TN-S and TT systems, remote signaling, plug-in

70

5SD7 326-4

Surge arresters, type 2, 4-pole, 335 V,


for TN-S systems, remote signaling, plug-in

70

5SD7 464-1

Surge arresters, type 2, 4-pole, 350 V,


for TN-S and TT systems, remote signaling, plug-in

70

5SD7 326-5

Surge arresters, type 2, 4-pole, 385 V,


for TN-S systems, remote signaling, plug-in

70

--

No replacement

--

--

5SD7 327-2

Surge arresters, type 2, 4-pole, 275 V,


for TT systems, plug-in

70

5SD7 464-0

Surge arresters, type 2, 4-pole, 350 V,


for TN-S and TT systems, plug-in

70

5SD7 327-4

Surge arresters, type 2, 4-pole, 335 V,


for TT systems, plug-in

70

5SD7 464-0

Surge arresters, type 2, 4-pole, 350 V,


for TN-S and TT systems, plug-in

70

5SD7 327-5

Surge arresters, type 2, 4-pole, 385 V,


for TT systems, plug-in

70

--

No replacement

--

--

5SD7 328-2

Surge arresters, type 2, 4-pole, 275 V,


for TT systems, remote signaling, plug-in

70

5SD7 464-1

Surge arresters, type 2, 4-pole, 350 V,


for TN-S and TT systems, remote signaling, plug-in

70

5SD7 328-4

Surge arresters, type 2, 4-pole, 335 V,


for TT systems, remote signaling, plug-in

70

5SD7 464-1

Surge arresters, type 2, 4-pole, 350 V,


for TN-S and TT systems, remote signaling, plug-in

70

5SD7 328-5

Surge arresters, type 2, 4-pole, 385 V,


for TT systems, remote signaling, plug-in

70

--

No replacement

--

--

5SD7 332-0

Surge arresters, type 3, 2-pole,


230 V AC/DC, 255 V AC/DC, remote signaling

58

5SD7 432-1

Surge arresters, type 3, 2-pole,


230 V AC/DC, 253 V AC/275 V DC, remote signaling

58

5SD7 334-0

Surge arresters, Type 3, 4-pole,


230/400 V AC/DC, 255 V AC, remote signaling

58

5SD7 434-1

Surge arresters, Type 3, 4-pole,


230/400 V AC, 335 V AC, remote indication

58

5SD7 335-0

Protective adapters, standard(line protection only)


for SCHUKO socket outlets

--

5SD7 435-0

Protective adapters, standard(line protection only)


for SCHUKO socket outlets

--

5SD7 335-0

Protective adapters, with line filter(line protection only)


for SCHUKO socket outlets

--

--

No replacement

--

--

5SD7 335-2

NTBA/DSL splitter protective adapters

--

5SD7 435-2

TAE protective adapters

--

5SD7 335-3

ISDN protective adapters

--

5SD7 435-3

Protective adapters for ISDN/RDSI

--

5SD7 335-4

LAN protective adapters

--

--

No replacement

--

--

mm

Mount- Chaping
ter
depth
mm

5SD7 335-5

TV/RADIO protective adapters

--

5SD7 435-5

TV/RADIO protective adapters

--

5SD7 360-0

Through-type terminals, 1-pole

70

5SD7 490-1

Through-type terminals, 1-pole

70

5SD7 390-0

Decoupling reactors, 35 A

58

--

No replacement, no longer required

--

5SD7 390-1

Decoupling reactors, 63 A

58

--

No replacement, no longer required

--

15/14

Siemens ET B1 2007

Appendix

16/2

Order information

16/3

Contacts

16/4

A&D-Online services

16/5

Customer Support

16/6

Glossar

16/13

Subject index

16/17

Order number index

16/48

Terms and conditions of


sale and delivery

16/48

Export regulations

16
16/1

Appendix
Order information
Ag and Cu surcharges
All products containing silver/copper shall be subject to surcharges
if the limit value is exceeded. The level of the surcharges is calculated as follows:
The limit value is as follows
For copper (Cu)150, /100 kg
For silver (Ag)150, /001 kg.

The basis is as follows:


For copper (CU) 175.- /100 kg
For silver (AG) 150.- /1 kg
The surcharges are made in % of the list price (see Table "Copper
surcharges" and Table "Silver surcharges").

Copper surcharge as % of list price of Cu-DEL notation in per 100 kg


from
to below
Miniature circuit-breakers incl. accessories 5SX, 5SY, 5SP, 5SJ, 5ST
RCCBs
5SM, 5SU, 5SW
NEOZED and DIAZED fuses
5SA - 5SH

175
225

225
275

275
325

325
375

375
425

each additional step

0.1

0.2

0.3

0.4

0.5

0.1

0.2

0.4

0.6

0.8

0.2

LV HRC fuses
3NA, 3ND, 3NG, 3NH, 3WX
SITOR fuses
3NE, 3NC
Overvoltage protection devices
5SD7
Switching devices, monitoring devices
5TE, 5TT
Power supply units
4AC

SITOR fuses
3NE, 3NC

Silver surcharge as % of list price of Ag notation in per kg


from
150
200
250
300
350

400

450

to below
a

450
7.2

500
8.4

200
1.2

250
2.4

The surcharge increase will be implemented as a percentage in


"steps", depending on the deviation of the daily notation to the metal
basis already included in the price. This allows us to maintain a degree of consistency for surcharges within the framework of these
"steps". An increased percentage will be calculated for each new
step. Please refer to the Tables "Copper surcharges" and "Silver surcharges" for the actual percentage.
For further up-to-date information on metal surcharges, please visit
our website on the Internet at
http://www.siemens.de/installationstechnik/metallzuschlaege
Trademarks
All product designations may be registered trademarks or product
names of Siemens AG or other supplying companies. Third parties
using these trademarks or product names for their own purposes
might infringe upon the rights of the trademark owners.
Ordering special designs
When ordering products that differ from the standard designs, the
Order No. in the catalog must be supplemented by a "Z"; the required characteristics must then be specified either by means of
brief alphanumeric data or in plain text.

300
3.6

350
4.8

400
6.0

each additional step


1.2

Ordering very small quantities


When ordering very small quantities, the cost of order processing often exceeds the order value. We therefore recommend that you
combine several small orders. Where this is not possible, please
note that we are obliged to make a small processing charge: for orders with a net goods value of less than 100. we charge a 15.
supplement to cover our order processing and invoicing costs.
Internet
You can also visit our Automation & Drives site on the Internet at the
following addresses:
For the sector Automation and Drives:
http://www.siemens.com/automation
For Installation Technology:
http://www.siemens.com/e-installation
For the A&D Mall:
http://www.siemens.com/automation/mall
Notes
All technical data, dimensions and weights are subject to change
without notice unless otherwise specified on the pages of this
catalog.
All dimensions are specified in mm, the illustrations are for reference
purposes only.
The technical data are for general information. The instruction manuals and the instructions on the products must be observed during
assembly, operation and maintenance.

16/2

Siemens ET B1 2007

Appendix
Contacts
Siemens contacts worldwide

Siemens contacts in the WWW

1
2

At:

3
4

http://www.siemens.com/automation/partner
you can find details of Siemens contact partners worldwide
responsible for particular technologies.
You can obtain in most cases a contact partner for
Technical Support,
Spare parts/repairs,
Service,
Training,
Sales or
Consultation/engineering.

You start by selecting a


Country,
Product or
Sector.
By further specifying the remaining criteria you will find exactly the
right contact partner with his/her respective expertise.

6
7
8
9
10
11
12
13
14
15
16

Siemens ET B1 2007

16/3

Appendix
A&D Online Services
Information and ordering options
on the Internet and CD-ROM

A&D in the WWW


A detailed knowledge of the range of products and services
available is essential when planning and configuring automation
systems. It goes without saying that this information must always
be fully up-to-date.
The Siemens Automation and Drives Group (A&D) has therefore
built up a comprehensive range of information in the World Wide
Web, which offers quick and easy access to all data required.
Under the address
http://www.siemens.com/automation
you will find everything you need to know about products, systems and services.

Product Selection Using the Offline Mall of Automation and Drives


Detailed information together with convenient interactive
functions:
The interactive catalog CA 01 covers more than 80.000 products
and thus provides a full summary of the Siemens Automation
and Drives product base.
Here you will find everything that you need to solve tasks in the
fields of automation, switchgear, installation and drives.
All information is linked into a user interface which is easy to work
with and intuitive.
After selecting the product of your choice you can order at the
press of a button, by fax or by online link.
Information on the interactive catalog CA 01 can be found on the
Internet under
http://www.siemens.com/automation/ca01
or on CD-ROM or DVD.

Easy Shopping with the A&D Mall


The A&D Mall is the virtual department store of Siemens AG in
the Internet. Here you have access to a huge range of products
presented in electronic catalogs in an informative and attractive
way.
Data transfer via EDIFACT allows the whole procedure from
selection through ordering to tracking of the order to be carried
out online via the Internet.
Numerous functions are available to support you.
For example, powerful search functions make it easy to find the
required products, which can be immediately checked for availability. Customer-specific discounts and preparation of quotes
can be carried out online as well as order tracking and tracing.
Please visit the A&D Mall on the Internet under:
http://www.siemens.com/automation/mall

16/4

Siemens ET B1 2007

Appendix
Customer Support
Our Services for Every Phase of Your Project

General

Configuration and Software Engineering


Support in configuring and developing with customer-oriented
services from actual configuration to implementation of the automation project.1)

Service On Site
With Service On Site we offer
services for startup and maintenance, essential for ensuring
system availability.

.I

In the face of harsh competition you need optimum conditions to


keep ahead all the time:
A strong starting position. A sophisticated strategy and team for
the necessary support - in every phase.
Service & Support from Siemens provides this support with a
complete range of different services for automation and drives.

In Germany Tel.:
+49 (0)180 50 50 4441)

In every phase: from planning and startup to maintenance and


upgrading.
Our specialists know when and where to act to keep the productivity and cost-effectiveness of your system running in top form.

Repairs and Spare Parts


In the operating phase of a machine or automation system we
provide a comprehensive repair
and spare parts service ensuring the highest degree of operating safety and reliability.

Online Support
The comprehensive information
system available round the
clock via Internet ranging from
Product Support and Service &
Support services to Support
Tools in the Shop.

In Germany Tel.:
+49 (0)180 50 50 4481)

http://www.siemens.com/
automation/service&support

Optimization and Upgrading

Technical Support
Competent consulting in technical questions covering a wide
range of customer-oriented services for all our products and
systems.

To enhance productivity and


save costs in your project we offer high-quality services in optimization and upgrading.1)

Tel.: +49 (0)911 895 59001)


Fax: +49 (0)911 895 59071)
E-Mail: technical-assistance@
siemens.com

1
2
3
4
5
6
7
8
9
10
11
12
13

Technical Consulting
Support in the planning and designing of your project from detailed actual-state analysis,
target definition and consulting
on product and system questions right to the creation of the
automation solution.1)

14
15
16
1) For country-specific telephone numbers go to our Internet site at:
http://www.siemens.com/automation/service&support

Siemens ET B1 2007

16/5

Appendix
Glossary
Ambient temperature

Conductive component

The temperature of the air surrounding an electrical device, determined under prescribed conditions (e.g. for enclosed miniature
circuit-breakers; the temperature of the air outside the enclosure).
The ambient temperature affects the heat dissipation, so that it may
be necessary to reduce the rated current.

Component through which current can flow, even if it is not necessarily used to carry currents during normal operation.
Contact

Apparent power

Component of the contact system over which the circuit is opened


or closed. A distinction is made between fixed and adjustable contacts and main and auxiliary contacts.

In the case of alternating current, the product of voltage and current,


without taking into account the power factor p.f.. The apparent power is a measurable variable. It is specified in VA (power).

Contactor

Auxiliary circuit
All conductive components of a switchgear combination in a circuit
(with the exception of the main circuit), that serve for control, measurement, signaling, latching, data processing, etc.
Backup protection
Interaction of two coordinated, series-connected overcurrent protective devices at points where a device (e.g. miniature circuitbreakers) cannot switch the prospective short-circuit current alone
in the event of a fault. If a high short-circuit current occurs, the backup overcurrent protective device relieves the downstream device,
thus prevent it from being subject to overload. Both protective devices must be have sufficient switching capacity.
Body (of electrical device)
Exposed conductive component of an electrical device that is not
normally live, but which may be live in the event of a fault.
Breaker mechanism
Component of a key-operated switching device that locks the switch
in the ON position. The breaker mechanism includes all the mechanical parts required for switching and latching to a closed component.
It also contains the release-free mechanism.
Breaking capacity
R.m.s. value of the current at a specified p.f. and specified voltage,
which can still safely switch off a switching device or fuse under prescribed conditions (rated breaking capacity) In the case of alternating current, the r.m.s. value of the symmetric components applies.
Breaking current
Current in one pole of a switching device or of a fuse at the moment
the arc is formed (in the case of alternating current, this is the r.m.s.
value of the AC components).
Characteristic curve
The graphical representation of the connection between the tripping
time and the influencing variable is shown in the characteristic curve
The time/current diagram shows, e.g. how long the release or
tripping relay takes to respond to a specific current.
Central p.f. correction
P.f. correction units are primarily used for central p.f. correction.
These are assigned directly to a switchgear and installed centrally.
Circuit-breakers
General key-operated switching devices that switch on, control and
switch off currents in circuits under normal operating conditions.
Under prescribed conditions that are not normal through to shortcircuit, they can also switch on the current, control it for a specified
interval and interrupt it.
Note:
Miniature circuit-breakers are generally designed for infrequent
switching, although some versions are also suitable for more
frequent switching.
Circuit (electrical)
A circuit comprises all the electrical devices in an installation that are
protected by the same overcurrent protective device(s).
Clearance
The shortest (thread measure) distance between two conductive
components. It is decisive for the level of insulation of an electrical
device.

16/6

Siemens ET B1 2007

Switching device with only one off position, usually without mechanical lock, which is not operated manually and which, under normal
conditions, can switch on, transmit, and switch off the circuit, including normal overload currents. Contactors are preferably used for
high switching frequencies. A distinction is made: Contactors for
switching motors and auxiliary contactors for control.
Note:
a contactor can switch short-circuit currents on and off if designed
for this purpose. It is not generally designed for separation. A contactor whose main contact elements are locked in the OFF position
is described as a "rupteur" in French. There is no comparable term
in English.
Control circuit
This is part of an auxiliary circuit and covers all components of a circuit that do not belong to the main circuit. Control circuits are circuits
for:
Signal generation and signal input,
Signal processing, including conversion, storage, locking and amplification,
Signal output and the control of actuators and signal transmitters.
Creepage
Current that forms on a surface that is insulating material when dry
and clean, due to conductive soiling between two live components.
Creepage distance
The shortest distance the length of an insulating surface between
two reference points (taking into account possible grooves) along
which a current can flow (rated insulation voltage).
Current limitation
The expected peak short-circuit current, taking into account the
circuit constants (R, L) does not occur, but is limited to a lower value;
the let-through current. This is achieved by means of fuses or
so-called current-limiting circuit-breakers and instantaneous switches that switch off extremely quickly in the event of high short-circuit
currents (in a couple of milliseconds).
Current limiter
Circuit-breakers and miniature circuit-breakers whose contactors
are directly opened dynamically in the event of a short-circuit without
waiting for the release through the breaker mechanism. The resulting
arc considerably reduces the current.
The current limitation effect is achieved by the fast opening of the
contactor as the short-circuit current is rising and through the
outstanding efficacy of the arc quenching device. The arc must be
extinguished before the natural (prospective) current reaches its
peak if a limiting effect is to be achieved.
DC component
The largest of the deviations from the zero line of the normal sinusoidal oscillation of the AC current. Occurs briefly, for example, in the
event of a short-circuit. The DC component can be no greater than
100 % of the peak value of the symmetrical short-circuit current and
in the usual low-voltage systems is usually a maximum 50 %.

Appendix
Glossary
Degree of protection

Functional extra-low voltage

The degree of protection of a device specifies the scope of protection. The scope of protection comprises the protection of persons
against contact with live parts and the protection of electrical devices against the penetration of foreign bodies and water by means of
enclosures and encapsulation.

Protective measure, during which the circuits are operated with a


rated voltage of up to 50 V alternating voltage or 120 V direct voltage, but which do not fulfill the requirements of safety extra-low voltage (SELV) and are therefore subject to further conditions. With
functional extra-low voltages, a distinction is made between with and
without safety separation.

The degree of protection is expressed internationally by a combination of letters (IP = International Protection) and numbers. The first
number defines the degree of contact and foreign body protection,
the second the water protection.
Dynamic short-circuit strength
Mechanical strength against short-circuit loads at switching devices
and particularly for busbars in switchgear assemblies and distribution boards. (short-circuit strength)
Electric arcs
Sparking that always occurs when an electric circuit is turned on at
voltages > 15 V. The strength of the arc depends on, among other
things, the type and level of the load, the power factor, as well as the
phase relation of the voltage curve at the instant of the contact separation. Temperatures of 10 000 to 15 000 C can occur at the center of an arc, which may cause the contact material to vaporize.
Because the arc has a direct influence on the service life of the contact, it is essential to take measures to ensure that the arc is kept
small and/or that it is extinguished as quickly as possible.

Fuse
Protective device that serves to open the circuit in which it is installed
if the current exceeds a specified value for a prescribed duration. It
does this by melting one or more fuse elements, thus interrupting the
current according to the respective tripping characteristic.
Note:
the fuse covers all components that are part of the complete protective device.
Specially shaped conductors made of copper (in special cases of
silver) in the fuse body of the fuse link. It melts in the case of overloads or short-circuits due to joule heat. Key features are the solder
area and limiters. The solder area melts in the event of a non-permissible overload, the limiters are defined fusing points in the event of
short-circuits.
Fuse link

Electromagnetic compatibility (EMC) is the ability of an electrical


device to function perfectly in its electromagnetic environment,
i.e. without being unacceptably influenced by it or vice versa.
Encapsulation

Ground

Enclosure for the protection of electrical devices. If offers enclosed


equipment protection against harmful environmental influences
(degrees of protection) and protection against direct contact (protective measures).

Designation for the conductive earth whose electrical potential is set


to zero. According to DIN VDE 0100 Part 200 the word ground is the
designation for the place as well as the material.

Enclosure

Group p.f. correction

Component that protects the equipment against certain external influences and which offers degree of protection of at least IP 2X
against direct contact from any direction.

With group p.f. correction, the correction device is assigned a load


group. This may comprise motors or fluorescent lamps that are connected to the system over a common contactor or other switching
devices.

Equipment (electrical)

Impedance (Z)

Technical products or their components insofar as their function and


design serve the use of electrical energy. This includes products
that generate, transmit, distribute, store, measure, monitor, control or
convert electrical energy.

Impedance (Z) is the sum of the resistors in a circuit at the rated current. It is made up of the resistance (R) and inductive resistance/reactance ( X = L ). The specified values refer to the rated frequency.

EVU / VNB

3
4
5

Fuse element

The fuse link is the part of the fuse that holds one or more fuse elements and which must be replaced after the fuse has been tripped
in order to restart the device. The current interruption and all associated actions are carried out inside an enclosed melting chamber
filled with quartz sand.

Electromagnetic compatibility (EMC)

1
2

6
7
8
9
10
11

Individual p.f. correction

German abbreviation for electric utility companies, i.e. the providers


of electrical energy (power stations).

For individual p.f. correction, the capacitors are connected directly


to the terminals of the individual loads and switched on together with
these over a common switching device.

Fault current (differential current)

Inherently ground-fault-proof

A fault current is the current that flows due to an insulation fault. For
example, it is measured as the differential between the currents
flowing into the system over a measuring device and those flowing
out over the same device (DIN VDE 0664).

Equipment or conducting paths are inherently ground-fault-proof


when, through the application of suitable measures under prescribed operating conditions, no ground faults (short-circuits to
frame) are to be expected (inherently short-circuit-proof).

Fault voltage

Inherently short-circuit-proof

Voltage that occurs between exposed, conductive components that


do not belong to the main circuit, or between these components and
the earth. If a person comes into contact with faulty machines or
plants and, for example, if he/she is standing on conductive flooring,
he/she will be subjected to a partial fault voltage, the so-called touch
voltage.

Equipment or conducting paths are inherently short-circuit-proof


when, through the application of suitable measures under prescribed operating conditions, no short-circuits are to be expected
(inherently earth-fault-proof).

12
13
14
15

Function classes
These specify which current range the fuse link can switch off (operational classes).

16
Siemens ET B1 2007

16/7

Appendix
Glossary
Inrush current

Melting time

Current peak when switching on transformers or switching motors on


and off. Caused by electromagnetic transient reactions (inrush
effect) when the magnetic field is set up. The current peak can take
the following values for motors at the rated voltage:

The time required to melt the fuse element of a fuse link, from the
start of the non-permissible overload current or short-circuit current
through to the start of the interruption process.

On-switching: Imax =

2 Ion * (1.8 to 2.0),

star-delta time transfer: Imax =


Reversing: Imax =

2 Ion * (2.1 to 3.7),

2 Ion * (2.7 to 5.0).

With transformers, the inrush current (starting current) depends on


the design, version, winding construction, application, power rating,
etc. As r.m.s. value is approx. 15 to 30 times the primary rated
current.
The inrush current dies down very quickly and is considerably
smaller after just 20 ms.
Insulation monitoring
Measure that monitors the insulation resistance of an electrical system of a measuring device of which neither an outer conductor nor
a neutral point is directly grounded. Any insulation fault that occurs
is indicated or, if a second fault occurs, the electrical system may be
switched off.
Insulation resistance
The smallest resistance that is measured between components that
are insulated from each other - or between these and the ground.
Let-through current ID
The largest instantaneous value of the current during the OFF time of
a switching device or fuse. Limited short-circuit currents occur when
the switching device, e.g. as result of resistance, operating delay
and peak arc voltage, lowers the amplitude of the short-circuit current. The let-through current of a device (e.g. current-limiting miniature circuit-breakers) is decisive for the thermal load (It-value) of
downstream devices (current limitation).
Live component
Conductive component of a device that will be live under normal operating conditions. This also includes the neutral conductor (N) and
conductive components that are connected to it. However, this does
not apply if the neutral conductor is also the PEN conductor.
Load / current-using equipment
Devices or installations that convert electrical energy to another nonelectronic energy form. In the field of alternating current technology,
loads are divided into three categories:
Resistive loads that do not cause phase displacement between
current and voltage in the system, e.g. heating, incandescent
lamps.
Inductive loads that cause the current to lag behind the voltage,
e.g. motors, coils, electromagnets.
Capacitive loads that cause the current to lead the voltage,
e.g. capacitors.

Meshed network
The meshed network is used to distribute energy over a cable system with a network-like topology. The power is generally infed over
a number of points. If a cable fails, each load is automatically fed
(no need for switchover) over the remaining cable branches (radial
network, ring network).
Miniature circuit-breakers
Mechanical switching device that serves to manually connect or disconnect a circuit to the mains and automatically disconnect the circuit from the mains if the current exceeds a specific maximum value.
In the event of the thermal overload of a connected load or branch,
a thermally delayed release initiates the switch-off process. In the
event of a short-circuit, the instantaneous short-circuit release takes
over disconnection. Both releases function independently of each
other and protect each other. The release-free mechanism of the
miniature circuit-breaker ensures that the switch trips in the case of
overcurrent and short-circuit, even if the actuating lever is jammed
in one setting or is held in place by an operator. In order to provide
optimum branch protection, the miniature circuit-breakers are produced with several different tripping characteristics (B, C and D).
Modular width (MW)
The width
of modular installation devices is specified at
+0,5
n ( 17,5 ) mm, whereby n=0.5; 1.0; 1.5; 2.0; 2.5 is possible.
-0

A modular width (MW) is 18 mm (17.5 + 0.5 mm) and the mounting


depth n * 18 mm, available for modular installation devices. e.g.
distribution boards.
N devices
Installation devices to DIN 43 830, with a mounting depth of
max. 55 mm.
N distribution boards
Small distribution boards to DIN 43 871 with a small mounting depth
for N devices up to 63 A.
Neutral conductor (N)
A conductor connected to the neutral or star point of the network that
is suitable for transmitting electrical energy.
No-load voltage U0
Output voltage of an unloaded transformer at the rated input voltage
and rated frequency.
OFF time
Duration from the start of the command output to open a switching
device through to the final extinguishing of the arcs (ON and OFF
time).

Loop impedance

ON or OFF time

The impedance of a fault loop is the sum of the impedances (apparent resistances) in a current loop, comprising the impedance of the
power source, the impedance of the outer conductor from one pole
of the power source to the measuring point and the impedance of the
return conductor (e.g. protective conductor, ground electrode and
ground) from the measuring point to the other pole of the power
source.

Duration from the start of the command output to switch a switching


device ON or OFF until the current is flowing uniformly in all poles, or
is no longer flowing.

Main circuit
Circuit that contains devices that generate, convert, distribute,
switch and pick-up electrical energy.
Making capacity
The value of the prospective starting current, which can switch on a
switching device under the prescribed conditions at a specified
voltage

16/8

Siemens ET B1 2007

When connecting to a short-circuit current, the time that elapses


from the moment the response current of a release is reached to the
time when the arc is extinguished in all poles.

Appendix
Glossary
Operational classes

Pollution severity

Operational classes for low-voltage fuses are designated by letters,


the first of which represents the function class and the second the
object to be protected. The objects to be protected are specified as
follows:

A conventional classification for the degree of pollution to be expected in the micro-environment. Pollution refers to any foreign, solid,
liquid or gaseous substance that might change the withstand voltage or surface resistance.

1st letter

Power

a
g

r partial range protection


r full range protection

2nd letter
G

Cables and lines (general applications)

M
R

Switching devices
Semiconductors

B
Tr

Mining plants
Transformers

This produces the following operational classes:


gG

Full range cable and line protection

aM
gR

Partial range switching device protection


Partial range semiconductor protection

gB
gTr

Full range mining plant protection


Full range transformer protection

Operational voltage
The voltage between two lines respectively on any equipment or system component.
Overcurrent
Every current in a circuit that exceeds the value of the rated current;
overload, short-circuit current. Overcurrent can damage lines, electrical machines and device due to unacceptably high heat generation and the possible occurrence of mechanical forces
Overload
Operating conditions that cause an overcurrent in an electrical
circuit that is undisturbed and problem-free. Overload can cause
damage when it is sustained over an extended period and not
switched off.
Overload current
The overcurrent that occurs in a circuit that is undisturbed and problem-free.
Overvoltage U
Peak value of the high-frequency transient recovery voltage; it is
greater than the rated operational voltage Ue (U > Ue)
Peak short-circuit current Ip
The highest instantaneous value of the prospective current after the
short-circuit has occurred. It is made up of the short-circuit current
and a direct current component and is specified as the peak value.
PEN conductor
Grounded neutral conductor with protective function in three-phase
system.
P.f.
Power factor: The ratio of active power to apparent power in AC and
three-phase systems.
P.f. correction
Measure to increase the cost-effectiveness of electrical systems. In
doing so it corrects (compensates) the reactive power generated in
the inductive loads during operation. In a p.f. corrected system, the
current in the infeed is smaller than that of an uncorrected system.
This enables the use of smaller conductor cross-sections and reduces the cross-section of the winding wires of transformers and generators. Depending on the application, a distinction is made between:
Individual, group and central p.f. correction.
P.f. correction unit
This comprises capacitors that can be connected and disconnected
to compensate the changing reactive power in systems.

1. physical
The energy expended per time unit in Watts.
2. electrical
The electrical energy consumed from the system by a load per time
unit.
Depending on the load, the following types of power occur in an
AC system:
Active power (P)
Part of the power that is converted to a different form of energy.
The proportion of active power to apparent power is calculated as
follows: P (W) = U * I * p.f.
Reactive power (Q)
the part of the power that cannot be converted to the desired energy form. Reactive power is created as a result of induction, whereby the current and voltage curve are offset.
The proportion of reactive power to apparent power is calculated as
follows:
Q (var) = U * I * sin
Apparent power (S)
This is the power taken from the system, which is a vectorial combination of active and reactive power.
The apparent power is calculated as follows:
S (VA) = U * I
These three types of power are geometrically interdependent. This
can be illustrated on a power chart.
The relationship between active power and apparent power is determined by the power factor (p.f.). It is expressed through a trigonometric function as the cosine of the angle .
Protection against direct contact
Measures to protect persons (and domestic animals) from the
dangers resulting coming into contact with live components of an
electrical device.
This may be full or partial protection. In the case of partial protection,
protection is only given in the case of inadvertent contact.
Protection against indirect contact
Measures to protect persons (and domestic animals) from the dangers resulting from a fault when coming into contact with frames or
other extraneous conductive components.
Protective conductor / PE conductor
Conductors used for some protective measures against indirect
contact for the bonding connection of frames with other frames and
extraneous conductive components that do not belong to the electrical installation: e.g., ground electrodes, ground conductors and
grounded live components, PEN conductors of the grounded terminal of the power source or an artificial neutral point.
Protective measures
Measures for the protection of persons and animals against touch
voltages, resulting from insulation faults in electrical devices.

1
2
3
4
5
6
7
8
9
10
11
12
13
14

Protective separation
Protective separation is ensured when an individual fault does not
cause the overspill of the voltage of one circuit to another. This is
particularly important when safety extra-low voltages (SELV) and
other voltages up to 1000 V are transmitted in a single device.
PTC thermistor detector
Component of the thermistor protective device that is installed in the
winding of the motor to be protected or in the cast resin transformer.
As the temperature rises, the PTC thermistor detector increases its
resistance within a small specified temperature range by several
powers of ten.

Siemens ET B1 2007

16/9

15
16

Appendix
Glossary
Radial network

Rated peak withstand current Ip (peak short-circuit current)

The wiring diagram corresponds to the branches of a tree, whereby


the supply comes from the trunk and there is only one route (branch)
for the electrical energy to reach each load (leaf) (see also; meshed
network, ring network)

The largest permissible instantaneous value (peak value) of the prospective short-circuit current in the most stressed conducting path.
It characterizes the dynamic short-circuit strength of an electrical
equipment.

Rated breaking capacity

Rated residual current In

The highest current that a switching device can switch off under
certain conditions.

The value specified by the manufacturer for the RCD for the residual
operating current at which the RCD must switch off under prescribed
conditions.

Rated breaking capacity Ien (Ier)


The rated breaking capacity of a miniature circuit-breaker is the
value of the short-circuit current that it can switch off at the rated operational voltage, rated frequency and specified power factor p.f. (or
specified time constant). The value of the prospective current
applies (in the case of alternating current: R.m.s. value of the
AC components) as specified by the manufacturer.

Rated short-circuit capacity


Rated making and rated breaking capacity. The switching capacity
for short-circuit currents is expressed by the prospective sustained
short-circuit current at the installation site of the miniature circuitbreaker. In the case of alternating current, the r.m.s. value of the
symmetric components applies.

Rated current In (Ir)

Rated short-time current

The voltage for which the electrical equipment is rated and to which
specific characteristics refer, e.g. rated power Sn (Sr).

Permissible r.m.s. value of the AC components of the prospective


short-circuit current, which can control the electrical equipment, e.g.
a control room, for a specific length of time, e.g. from 0.05 s to 1 s
(1-s current) (thermal short-circuit strength). This is specified as an
r.m.s. value of the short-circuit current.

Rated frequency
The rated frequency is the frequency for which the electrical equipment is designed and to which the device characteristics refer.
Rated impulse withstand voltage (Uimp)
The peak value of a surge voltage of specified form and polarity to
which, under specified test conditions, the electrical equipment can
be subjected without failing and to which the clearance refers.
The rated impulse withstand voltage of an electrical device must correspond to, or be greater than, the transient overvoltages that occur
in the system in which the electrical equipment is installed.
Rated input voltage U1n (U1r)
Input voltage (in the case of three-phase currents, the phase-tophase voltage) with which a transformer can be excited at the rated
frequency.
Rated insulation voltage Ui
The voltage value, which specifies the insulation resistance of the
electrical equipment and accessories and to which the insulation
tests and creepage and clearances refer.
On no account must the rated operational voltage exceed the rated
insulation voltage.
Note:
In the case of electrical equipment without specified rated insulation
voltage, the highest rated operational voltage should be taken as the
rated insulation voltage.
Rated making capacity
The highest current that a switching device can switch on under certain conditions.
Rated making capacity Iem
The rated making capacity of a miniature circuit-breaker is the value
of the short-circuit current as specified by the manufacturer that it
can switch on at the rated operational voltage, rated frequency and
specified power factor p.f. (or specified time constant). It is
expressed by the maximum peak value of the prospective current.

Rated voltage Un (Ur)


The voltage of an electrical equipment to which its other characteristics refer. In the case of three-phase circuits, the phase-to-phase
voltage of the system is taken as the rated voltage. For switchgear
assemblies, the manufacturer must specify the voltage limits within
which the problem-free function of the main and auxiliary circuits can
be guaranteed. These limits must always be such that, under normal
load conditions, the voltage at the terminals of the control circuits of
the installed device stay within the limit values specified in the standards applicable for the respective equipment.
Reactive power
The power required to create electromagnetic fields, e.g. in electrical motors and transformers, for AC or three-phase currents. It is essential for the operation of all inductive loads but, in contrast to active
power, cannot be converted to a useful form of energy. It is therefore
an "unnecessary" load on cables and plants, particularly the systems
of electrical supply companies.
Capacitor control units, reactive-power compensation equipment
and capacitors that have to be subsequently installed provide loads
with the necessary capacitive reactive power, thus compensating
electromagnetic fields and relieving the energy supply.
Release (of a mechanical switching device)
A device connected to a mechanical switching device, which trips
latching if the prescribed variables (e.g. current, voltage) are exceeded or fallen below, thus enabling the opening or closing of the
switching device.
Response current, ground fault (g)
Ground-fault current, which, when reached or exceeded, activates
and triggers the ground-fault release (g), e.g. a miniature circuitbreaker.
Response current, instantaneous (n)
Current, which when exceeded causes immediate tripping.

Rated operational current Ie

Response current, overload (a)

The rated operational current is the current that is determined by the


specified conditions of an electrical equipment. It takes into account
the rated voltage and frequency, the rated duty and the degree of
protection.

Continuous current, which when exceeded, causes tripping within a


specified time (current-dependent delayed release!)

Rated operational voltage Ue


The rated operational voltage of a circuit is the voltage value which,
together with the rated current, determines the usability of the circuit.
In the case of multiphase circuits, the voltage between the outer conductors is specified.

16/10

Siemens ET B1 2007

Response current, short-time delay (z)


Current, which when exceeded causes tripping after a userdefinable delay time.
Ring network
In a ring network, several transformers supply a closed cable ring to
which all loads are connected. If the ring is separated at any point,
the loads are supplied from one side as in a radial network. The ring
network is a type of energy supply network (meshed network).

Appendix
Glossary
r.m.s. value

Starting current

Value, which corresponds to the r.m.s. value of a periodic quantity.


Because the values in an AC system are instantaneous values that
are dependent on the phase relation, current and voltage are specified in the theory of alternating currents as r.m.s. values. Measuring
devices (moving coil instruments) always display the r.m.s. value.
For the sine curve, the
r.m.s. value = 1 / 2 * Amplitude (peak value).

The current that occurs immediately after closing a circuit, e.g. when
connecting a transformer or motor. The size depends on the instant
of closing (phase relation of the voltage). Maximum current flows
when switching on at voltage zero; it then decreases to the rated
value after approx. 20 ms.

The r.m.s. value of an alternating current is the same as that of a direct current, which generates the same heat (power) as the alternating current.

The peak value of the current that a circuit or switching device can
withstand in closed position under prescribed applications or corresponding use.

Safety extra-low voltage (SELV)

Switch / switching device

Protective measure through which circuits with rated voltages up to


50 V AC voltage or 120 V DC voltage can be operated without
grounding and the supply from circuits with higher voltages is safely
isolated.

Device for switching on or interrupting current in one or more


circuits.

Selectivity
Co-ordination of series-connected overcurrent protective devices
(miniature circuit-breakers, fuses) for sequenced switch-off. It must
switch off the overcurrent protective device closest to the point of
short-circuit. The other overcurrent protective devices in the busbar
run remain switched on. Selectivity minimizes the effect of a fault
both spatially and time-wise.
Service life
The period that electrical equipment works problem-free under normal operating conditions. It is specified in (for example) operating
hours or switching cycles. A distinction is made between mechanical and electrical service life.
The end of the electrical service life is reached, for example,
when the number of operating hours are exceeded or when the
switching contacts are worn out through contact erosion that reliable
and safe contact can no longer be ensured.
The mechanical service life is specified by the manufacturer as the
number of switching cycles without load that the device can execute
without the need for servicing or the replacement of parts.
Short-circuit
Connection with negligible small impedance between two conductors that are live under operating conditions. In this case, the current
is a multiple of the operational current; this can cause a thermal
(rated short-time current) or mechanical (peak withstand current)
overloading of the electrical equipment and system components.
Short-circuit current (sustained short-circuit current Ik)
Overcurrent that occurs in an electrical circuit with negligible impedance between points with different potentials, in the event of a fault,
e.g. with short-circuited terminals on electrical equipment or in the
case of defective jumpering.
Short-circuit strength
Resistance of an electrical device against the electrodynamic
(dynamic short-circuit strength) and thermal (thermal short-circuit
strength) stress that occurs in the event of a short-circuit.
The characteristic for the dynamic stress is the peak short-circuit
current as the highest instantaneous value of the short-circuit
current.
The characteristic for the thermal stress of the short-circuit current is
the r.m.s. value of the short-circuit current for its duration (sustained
short-circuit current).
Short-circuit voltage Ukr (Ukn)
Rated value of the voltage in % of the rated input voltage that needs
to be applied to the input terminals of a transformer, so that if the output terminals are short-circuited, the rated output current (I2r) flows,
relative to 20 C.
Short-circuits to frame
A conductive connection between the frame and live components of
an electrical device due to a fault.

Surge current withstand capability

Switchgear combination
Combination of l.v. switching devices, designed and tested to
DIN VDE 0660 Part 500. This standard distinguishes between typetested (TSK) and partially type-tested (PTSK) l.v. switchgear combinations.
TSK: The TSK is a switchgear combination that corresponds to the
switchgear combination type-tested according to the aforementioned standards without any significant deviations from the original
type or system.
PTSK: The PTSK is a switchgear combination that contains both
type-tested and non-type-tested components that can be shown to
conform to the respective testing requirements.

1
2
3
4
5
6
7
8

Switching capacity
Current that can switch a switching device on and off under
prescribed conditions. (breaking and making capacity)
If a switching device can switch on larger currents than it can switch
off or vice versa, the specifications of the switching capacity can be
separated into making and breaking capacity (short-circuit, making
and breaking capacity).

Switching frequency
Switching frequency specifies how many switching cycles can be
carried out with the switching device in a specified time period
(e.g. in 1 h) under field conditions.

10

Switching operation
The result of actuating from one switching position to another and
back to the original position and, where applicable, passing through
all intermediate positions
Note:
This could be closing followed by opening. Actuations that do not
form a switching operation are called a series of actuations.
Temperature limit
The highest temperature that individual components of an electrical
equipment can withstand continuously without suffering damage. It
is reached by adding the ambient temperature and the permissible
self-heating temperature for the electrical equipment. The functional
safety of the device is at risk if the temperature limit is exceeded.

11
12
13

Temperature-rise limit
The specified maximum overtemperature for the individual components of an electrical device (temperature rise).
Temperature sensor
Semiconductor device that changes its resistance value depending
on the temperature. It serves to monitor the winding temperature,
e.g. in three-phase asynchronous motors (thermistor protection) and
cast resin transformers.

14
15

Thermistor protection
Protection of the motor or cast resin transformer through temperature
sensors fitted in the windings (PTC or NTC thermistors). These
directly monitor the winding temperature.

Siemens ET B1 2007

16/11

16

Appendix
Glossary
Time/current characteristic curve
This is the characteristic curve that specifies the virtual time for specific operating conditions (e.g. melting time or switch-off time) as a
function of the prospective breaking current.
Total operating time
The time from the start of the switch off command to the end of the
arcing time.
Touch voltage
The voltage that can occur between two simultaneously exposed
components in the event of an insulation fault.
Trip-free mechanism
Design feature of key-operated switching devices and releases. The
trip-free mechanism prevents any obstruction of the release process
- even when the drive is blocked or the device is manually held in the
"ON" position.
Tripping time
Current value at which a release trips within a specified time.
Types of networks and systems
Electrical networks are categorized according to voltage, configuration and topology. AC voltages are categorized according to:
Low-voltage networks up to 1000 V,
High-voltage networks over 1 KV to 380 kV,
e.h.v. systems over 380 kV.
the topology of the networks are distinguished as follows:
open network (e.g. radial network) and
closed network (e.g. ring network, meshed network)
There are the following system types for low voltages:
TN system (network)
In the TN system, one point of the network (star point or outer
conductor) is directly grounded. The frames of the electrical
equipment are linked to the ground network point over a protective
or PEN conductor. The TN system is available in the following
versions:
- TN-S system (network)
Neutral conductor (N) and protective conductor (PE) are separated throughout the network.
- TN-C system (network)
The neutral conductor and the PE/ground conductor function are
combined in a single conductor, the PEN conductor, throughout
the network.
- TN-C-S system (network)
The neutral conductor and PE/ground conductor function are
combined in a single conductor, the PEN conductor, in part of the
network only; in the rest of the system, the neutral and PE conductor are installed separately.
TT system (network)
In the TT system, one point of the network is directly grounded; the
frames of the electrical equipment are linked to ground electrodes.
IT system (network)
The IT system has no direct connection between live conductors
and grounded components: the frames of the electrical equipment
are grounded.
Voltage drop UR (V); UR (%); U (V);U (%)
The difference between the no-load voltage U0 and the rated voltage
U2r of a transformer at rated power, in relation to 20 C ambient temperature. The degree to which the voltage drop will affect the power
depends on the length, cross-section and which material is used for
the conductors. When covering large distances, the expected voltage drop must be taken into account.

16/12

Siemens ET B1 2007

Appendix
Subject index
A
Adapter rings SR60 DIAZED 12/4
Adapter sleeve fitters for NEOZED 1/6
Adapter sleeves for
DIAZED 1/14, 1/15
NEOZED 1/6
Additional components for miniature circuit-breakers
Auxiliary switches 3/5, 3/25, 14/4
Fault signal contacts 3/5, 3/25, 14/4
RCCB modules 3/23 ... 3/24
Remote controlled mechanism 3/26
Shunt trips 3/27, 14/4
Undervoltage releases 3/27
Alarm sensors 14/15
Ammeter selector switches 10/10
Ammeters
Analog 10/5
Digital 10/5
Analog measuring devices
Ammeters 10/5
Voltmeters 10/5
Auxiliary switches for
Cylindrical fuses 1/47
Insta contactors 7/5
LV HRC fuse switch disconnectors 1/34
Miniature circuit-breakers 3/5, 3/25, 14/4
MINIZED switch disconnectors 1/9
Remote control switches 7/3
Residual current protective devices 4/11, 4/18,
14/8
SR60 busbar systems 12/4
Switches 6/4, 6/9, 6/12

B
Base
for busbars 13/4
Bell transformers 9/3
Blind remote control switches 7/3
Breaker blocking covers for
Miniature circuit-breakers 3/30
Busbar adapters for
Main miniature circuit-breakers (SHU) 3/30
Busbar supports 12/2
Busbars 13/2 ... 13/14
Busbar adapters 1/5
for cylindrical fuses 13/5
for DIAZED 13/5
for DIAZED bus-mounting bases 13/5
for lightning and surge arresters 13/13
for LV HRC fuse switch disconnectors 1/33
for miniature circuit-breakers 13/7 ... 13/12
for NEOZED 13/3
for residual current protective devices
13/7 ... 13/12
for switches 13/14
Bus-mounting bases
for DIAZED EZR 1/13
SR60 DIAZED 12/3
SR60 NEOZED 12/3
Bus-mounting bases for
LV HRC fuses 1/23
Bus-mounting disconnectors
SR60 NEOZED 12/4
Bus-mounting fuse bases
SR60 LV HRC 12/5

C
Cage Clamp terminals for
Switches 6/12
Cap sets for
Light indicators 6/7
Switches 6/4, 6/6
Caps for
DIAZED 1/14
NEOZED 1/5
Centralized fault signaling unit 11/5
Changeable scales for
Ammeters 10/5
Circuit-breaker terminals for auxiliary circuits 3/31
Combination arresters 5/4
Compensators 14/10
Connectors for switches 6/9
Contactors
Insta 7/5
Control pushbuttons 6/5
Control switches 6/3, 14/9
Control switches 6/3
ECG 8/3
Group switches 6/3
Two-way switches 6/3
Conversion kits for
Switches 6/12
Covers
SR60 12/6
SR60 DIAZED 12/3
SR60 NEOZED 12/3
Covers for
DIAZED 1/14
Miniature circuit-breakers 14/5
NEOZED 1/5
Residual current protective devices 4/26
Covers for time counters 10/4
Current relays 11/11
Current transformers 10/10
Cylindrical fuses
Base 1/47
Busbars 13/5
Fuse bases (SITOR) 2/12
Fuse links 1/46
for motor circuits 1/49
SITOR 2/11
Fuse systems 1/46, 1/47
Switch disconnectors (SITOR) 2/12
Tongs (SITOR) 2/12

D
Data keys for
Digital time switches 8/7
Delay timers 8/4
DIAZED
Adapter sleeves 1/14, 1/15
Base 1/12, 1/15
Busbars 13/5
Bus-mounting bases, EZR 1/13
Caps 1/14
Covers 1/14
Fuse bases 1/12 ... 1/15
Fuse links 1/10, 1/11
SILIZED 2/13
Fuse systems 1/10 ... 1/15
Screw adapters 1/14
Screw caps 1/15
SR60 adapter rings 12/4
SR60 bus-mounting bases 12/3
SR60 covers 12/3
Terminals 13/5
Digital measuring devices
Ammeters 10/5
Voltmeters 10/5
Digital time switches 8/6, 14/12
Data key 8/7
USB adapter 8/7
Double pushbuttons 6/5
Drives for
Switches 6/12
Dusk switches 11/6, 14/15
Light sensor 11/6

1
2
3
4
5
6
7
8

E
ECG control switches 8/3
E-counters 10/8 ... 10/9
for 3/4 wire connection 10/8, 10/9
for active and reactive energy 10/8, 10/9
for active energy 10/8
Electronic pulse counters 10/4
Electronic time counters 10/4
EMERGENCY-STOP modules 7/9
Enclosures for
Miniature circuit-breakers 14/5
Residual current protective devices 4/26
End caps for
Busbars 6/4, 13/7, 13/10, 13/11, 13/14
Energy-saving timers 8/3
Expansion fault signaling unit 11/5
EZR
DIAZED bus-mounting bases 1/13

9
10
11
12
13
14
15
16

Siemens ET B1 2007

16/13

Appendix
Subject index
F

Fan timers 8/3


Fault signal contacts for
Miniature circuit-breakers 3/5, 3/25, 14/4
Residual current protective devices 4/18
Fault signaling units
Centralized fault signaling unit 11/5
Expansion fault signaling unit 11/5
Feeder terminal 3/32
Feeder terminals for
Miniature circuit-breakers 13/12
Fixing parts for
Miniature circuit-breakers 3/28, 14/5
Residual current protective devices 4/26
Fixpoint terminals for
Switches 6/9
Flashing timers 8/4
Fuse bases
Cylinders 1/47
DIAZED 1/12, 1/15
NEOZED 1/3, 1/6
Fuse bases for
Cylindrical fuses (SITOR) 2/12
LV HRC fuses 1/22 ... 1/25
Fuse disconnectors
NEOZED 1/7
Fuse links
American/Canadian (Class CC) 1/50
Cylindrical fuses 1/46
for motor circuits 1/49
SITOR 2/11
DIAZED 1/10, 1/11
for special applications (SITOR) 2/9, 2/10
LV HRC 1/16 ... 1/21
for motor circuits 1/48
SITOR 2/2 ... 2/8
NEOZED 1/2
SILIZED 2/13
SITOR 2/2 ... 2/12
for special applications 2/9, 2/10
Fuse monitors 11/7
Fuse tongs for
Cylindrical fuse links (SITOR) 2/12
Fuses
Class CC 1/50
Cylinders 1/46 ... 1/47
DIAZED 1/15
LV HRC 1/16
NEOZED 1/2, 1/9
Semiconductor protection 2/2 ... 2/13

16/14

Siemens ET B1 2007

Group switches 6/3, 14/9


GSM alarm module 11/16

H
Handle coupler for
Residual current protective devices 4/18, 4/19
Handle locking devices for
Miniature circuit-breakers 3/28, 14/5
Switches 6/4, 6/9

I
Immersion electrodes for
Level relays 11/14
Inscription labels for
Miniature circuit-breakers 3/28
Residual current protective devices 4/26
Insta contactors 7/5, 14/10
with manual switch 0/I/Automatic 7/7
without manual switch 7/6
Insulation monitors 11/12 ... 11/13
for industry 11/12
for medical premises 11/13
Signaling and test combinations 11/13

L
Lamps for
Light indicators 6/7
Switches 6/6
LAN couplers 10/9
Leakage current measuring device 4/13
Level relays 11/14
Light indicators 6/7
Light sensors for
Dusk switches 11/6
Lighting timer 8/3
Lightning and overvoltage protection devices
5/2 ... 5/10
Busbars 13/13
Combination arrester 5/4
Lightning arresters, 5/3
Surge suppressors 5/5 ... 5/9
Multipole 5/8
Narrow version 5/5
Protective adapters 5/9
Wide version 5/6
Link rails
Single-pole 3/32
Two-pole 3/32
Locking devices 4/20
Locking devices for
Miniature circuit-breakers 3/28
Residual current protective devices 4/12, 14/8
Locking units for
Switches 6/12
Locks for
Miniature circuit-breakers 3/28
Residual current protective devices 4/12, 4/20
LV HRC
Bus-mounting bases for
Busbars 1/23
Fuse bases 1/22, 1/25
Fuse links 1/16 ... 1/21
for motor circuits 1/48
SITOR 2/2 ... 2/8
with combination alarm 1/16 ... 1/18
with front indicator 1/19 ... 1/21
Fuse switch disconnectors 1/27 ... 1/45
for Extended Technical Requirements
1/38 ... 1/45
for power distribution 1/27 ... 1/37
Fuse systems 1/16 ... 1/45
Signal detector 1/26
SR60 bus-mounting fuse bases 12/5
SR60 fuse switch disconnectors 12/5
LV HRC fuse switch disconnectors 1/27 ... 1/45
for Extended Technical Requirements
1/38 ... 1/45
for power distribution 1/27
SR60 12/5
LV HRC signal detector 1/26

Appendix
Subject index
M
Main miniature circuit-breakers (SHU) 3/29
Mains isolating relay 11/8
Male connectors for lightning and surge arresters
5/10
Measuring devices 10/2 ... 10/10
Analog 10/5
Current transformers 10/10
Digital 10/5
E-counters 10/8 ... 10/9
LAN couplers 10/9
Multicounters 10/7
Multimeters 10/6
Pulse counters 10/4
Time counters 10/4
Measuring selector switches 10/10
Mechanical time switches 8/8, 8/9, 14/13
Miniature circuit-breakers 3/2 ... 3/32, 14/2, 14/3
Additional components 3/23 ... 3/27, 14/4
Busbars 13/7 ... 13/12
High-capacity product range 3/6 ... 3/20
High-current product range 3/22
Power supply company product range 3/29
RCCB modules 3/23 ... 3/24
Special range 3/31
Standard product range 3/3 ... 3/5, 14/2, 14/3
UC product range 3/21
MINIZED switch disconnectors 1/8 ... 1/9
Molded-plastic covers for
LV HRC fuse switch disconnectors 1/35
Molded-plastic enclosures for
Miniature circuit-breakers 14/5
Residual current protective devices 4/26
Monitoring devices 11/2 ... 11/16
Alarm sensors 14/15
Current relays 11/11
Dusk switches 11/6, 14/15
Fault signaling units 11/5
Fuse monitors 11/7
GSM alarm module 11/16
Insulation monitors 11/12, 11/13
Level relays 11/14
Mains isolating relay 11/8
N-conductor monitors 11/10
Phase monitors 11/8
Phase sequence monitors 11/8
Power factor monitoring 11/14
Priority switches 11/12
Temperature controllers 11/7
Thermistor motor protection relays 11/15
Voltage relays 11/9
Monitors
Insulation 11/12, 11/13
N-conductor 11/10
Phase 11/8
Phase sequence 11/8
Power factor 11/14
Mounting parts for
LV HRC bus-mounting bases 1/24
LV HRC fuse bases 1/24
LV HRC fuses 1/25
Multicounters 10/7
Multifunction timers 8/4
Multimeters 10/6

N
N-conductor connectors 6/9
N-conductor monitors 11/10
NEOZED
Adapter sleeve fitter 1/6
Adapter sleeves 1/6
Busbar adapters 1/5
Busbars 13/3
Caps 1/5
Covers 1/5
Fuse bases 1/3 ... 1/6
Fuse disconnectors 1/7
Fuse links 1/2
SILIZED 2/13
Fuse systems 1/2 ... 1/9
MINIZED switch disconnectors 1/8, 1/9
Retaining springs 1/6
Screw caps 1/5
SR60 bus-mounting bases 12/3
SR60 bus-mounting switch disconnectors 12/4
SR60 covers 12/3
Terminals 13/4

O
Off-delay timers 8/4
ON/OFF switches 6/8, 14/9
Operating protective covers for
Miniature circuit-breakers 3/30

P
Padlocks 3/28, 14/8
Phase connectors 6/9
Phase monitors 11/8
Phase sequence monitors 11/8
Power factor monitoring 11/14
Power Supply Units
Transformers 14/14
Power supply units 9/2 ... 9/4
Bell transformers 9/3
Power supply units 9/3
Socket outlets 9/4
Transformers 9/3
Priority switches 11/12
Protective adapters 5/9
Pulse counters 10/4
Pushbuttons 6/5, 6/6
Control pushbuttons 6/5
Double pushbuttons 6/5, 6/6

Q
Quartz-clock time switches 8/9

R
Railway supply rectifiers (fuse links) 2/10
RC units for
Miniature circuit-breakers 4/21 ... 4/23
RCBO residual current circuit-breakers with integral
overcurrent protection
SIQUENCE, UC sensitive 4/14
RCCB modules for
Miniature circuit-breakers 3/23, 3/24
RCCB protective socket outlets 4/24, 4/25
RCCB residual current operated circuit-breakers
4/3 ... 4/13
SIGRES 4/6
RCCB residual current operated circuit-breakersresidual currents
SIQUENCE, UC sensitive 4/9
RCCB socket outlets (SRCDs) 4/24, 4/25
RCCBs with integral overcurrent protection (RCBO)
4/14 ... 4/20
RCCBs with integral overcurrent protection, combined devices (RCBOs) 4/14 ... 4/20
Rectifiers in electrolysis systems (fuse links) 2/9
Remote control switches 7/3, 14/10
Blind remote control switches 7/3
Compensators 14/10
Series remote control switches 7/3
with central switching 7/3
Remote controlled mechanisms for
Miniature circuit-breakers 3/26
Residual current protective devices 4/10, 4/17
Residual current protective devices 4/2 ... 4/26,
14/6 ... 14/8
Auxiliary switches 4/11, 4/18, 14/8
Busbars 13/7 ... 13/12
Enclosures 4/26
Fault signal contacts 4/18
Key-operated switch 4/12, 4/20
Leakage current measuring device 4/13
Molded-plastic enclosure 4/26
RC Units for Miniature Circuit-Breakers 3/23,
3/24, 4/21, 4/23
RCCBs with integral overcurrent protection,
combined devices (RCBOs) 4/14 ... 4/20
Remote controlled mechanism 4/10, 4/17
Residual current circuit-breakers with integral
overcurrent protection, combined devices (RCBOs)
SIQUENCE, UC sensitive 4/14
Residual current operated circuit-breakers (RCCB) 4/3 ... 4/13
SIGRES 4/6
Residual current operated circuit-breakers (RCCBs)
SIQUENCE, UC sensitive 4/9
Shunt trips 4/19
Snap-on terminals 4/26
Undervoltage releases 4/19
Retaining springs for
NEOZED 1/6
Rotary actuators for
Switches 6/12

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Siemens ET B1 2007

16/15

Appendix
Subject index
S
SCHUKO socket outlets 4/24, 4/25, 9/4
Screw adapters for
DIAZED 1/14
Screw caps for
DIAZED 1/15
NEOZED 1/5
Sealable terminal covers
for Insta contactors 7/7
Sections for
Busbars 12/6
Selector switches for
Ammeters 10/10
Voltmeters 10/10
Semiconductor fuses
SILIZED 2/13
DIAZED 2/13
NEOZED 2/13
SITOR 2/2 ... 2/13
Cylindrical fuse links 2/11 ... 2/12
for special applications 2/9 ... 2/13
LV HRC fuse links 2/2 ... 2/8
Series remote control switches 7/3
Shunt trips for
Miniature circuit-breakers 3/27, 14/4
Residual current protective devices 4/19
SILIZED
Fuse links 2/13
Semiconductor fuses 2/2
Single-phase busbars for
Switches 6/4, 13/14
SITOR
for special applications 2/9 ... 2/10
for railway supply rectifiers 2/10
for rectifiers in electrolysis systems 2/9
for SITOR thyristor sets 2/10
Semiconductor fuses 2/2 ... 2/12
Cylindrical fuse links 2/11 ... 2/12
for special applications 2/9 ... 2/10
LV HRC fuse links 2/2 ... 2/8
Snap-on terminals for
Miniature circuit-breakers 3/28, 14/5
Residual current protective devices 4/26
Switches 6/9
Socket outlets 4/24, 4/25, 9/4
Soft-starting devices 7/8
Spacers for
Insta contactors 7/5
Miniature circuit-breakers 3/28, 14/5
Switches 6/4, 6/9
SR60 assembly kits for ALPHA distribution boards
12/7
SR60 busbar systems 12/2 ... 12/7
Assembly kits for ALPHA distribution boards
12/7
Auxiliary switches 12/4
Covers 12/6
DIAZED adapter rings 12/4
DIAZED bus-mounting bases 12/3
DIAZED covers 12/3
LV HRC bus-mounting fuse bases 12/5
LV HRC fuse switch disconnectors 12/5
NEOZED bus-mounting bases 12/3
NEOZED bus-mounting switch disconnectors
12/4
NEOZED covers 12/3

16/16

Siemens ET B1 2007

Stairwell lighting timers 8/3, 14/12


Surge protection adapters 5/9
Surge suppressors 5/9
Multipole 5/8
Narrow version 5/5
Protective adapters 5/9
Wide version 5/6
Switch disconnectors 6/11, 14/9
for cylindrical fuses (SITOR) 2/12
MINIZED 1/8 ... 1/9
Switches 6/2 ... 6/12
Busbars 13/14
Control switches 6/3
ON/OFF switches 6/8, 14/9
Pushbuttons 6/5, 6/6
Switch disconnectors 6/11, 14/9
Switching devices 7/2 ... 7/9, 14/10 ... 14/11
EMERGENCY-STOP modules 7/9
Insta contactors 7/5, 14/10
Remote control switches 7/3, 14/10
Soft-starting devices 7/8
Switching relays 7/4, 14/10
Switching relays 7/4, 14/10
Synchronous time switches 8/8

T
Temperature controllers 11/7
Temperature sensor 11/7
Terminal covers for
Insta contactors 7/5
Miniature circuit-breakers 3/28, 14/5
Residual current protective devices 4/26
Switches 6/9, 6/12
Time counters 10/4
Terminals for
Busbars 12/2
DIAZED 13/5
Miniature circuit-breakers 13/10
NEOZED 13/4
Switches 6/9, 6/12
Thermistor motor protection relays 11/15
Through-type terminals for lightning and surge arresters 5/10
Time counters 10/4
Time switches
Digital 8/6, 14/12
Mechanical 8/8, 8/9, 14/13
Quartz 8/9
Synchronous 8/8
Timers 8/2 ... 8/9, 14/12 ... 14/13
for buildings 8/3, 14/12
for industry 8/4
Time switches 8/5 ... 8/9, 14/12 ... 14/13
Timers for
Buildings 8/3, 14/12
Industry 8/4
Tongs for
Cylindrical fuse links (SITOR) 2/12
Transformers 9/3, 14/14
Two-phase busbars for
Switches 6/4, 13/14
Two-way switches 6/3

U
Undervoltage releases (UR) for
Miniature circuit-breakers 3/27
Residual current protective devices 4/19
USB adapters for
Digital time switches 8/7

V
Voltage relays 11/9
N-conductor monitors 11/10
Voltmeter selector switches 10/10
Voltmeters
Analog 10/5
Digital 10/5

W
Wall enclosures for
Residual current protective devices 4/26
Wiper timers 8/4

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

PS*/
P. unit
Unit(s)

1/19
1/19
1/19
1/19
1/19
1/19
1/19
1/19
1/19
1/19
1/19
1/19
1/19
1/19

1
1
1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3
3
3
3
3

1/19
1/19
1/19
1/19
1/19
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/19

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1/20
1/20
1/20
1/20
1/21
1/20
1/21
1/20
1/21
1/20
1/21
1/20
1/21
1/20
1/21
1/20
1/21
1/20
1/21
1/20
1/21
1/20
1/20

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1/20
1/20
1/20
1/21
1/20
1/20
1/21

1
1
1
1
1
1
1

013
013
013
013
013
013
013

3
3
3
3
3
3
3

3NA3 0
3NA3 001
3NA3 003
3NA3 005
3NA3 007
3NA3 010
3NA3 012
3NA3 014
3NA3 017
3NA3 020
3NA3 022
3NA3 024
3NA3 030
3NA3 032
3NA3 036

3NA3 1
3NA3 105
3NA3 107
3NA3 110
3NA3 114
3NA3 117
3NA3 120
3NA3 120-6
3NA3 122
3NA3 122-6
3NA3 124
3NA3 124-6
3NA3 130
3NA3 130-6
3NA3 132
3NA3 132-6
3NA3 136
3NA3 136-6
3NA3 140
3NA3 140-6
3NA3 142
3NA3 144

3NA3 2
3NA3 214
3NA3 220
3NA3 222
3NA3 224
3NA3 224-6
3NA3 230
3NA3 230-6
3NA3 232
3NA3 232-6
3NA3 236
3NA3 236-6
3NA3 240
3NA3 240-6
3NA3 242
3NA3 242-6
3NA3 244
3NA3 244-6
3NA3 250
3NA3 250-6
3NA3 252
3NA3 252-6
3NA3 254
3NA3 260

3NA3 3
3NA3 340
3NA3 342
3NA3 344
3NA3 344-6
3NA3 350
3NA3 352
3NA3 352-6

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NA3 354
3NA3 354-6
3NA3 360
3NA3 360-6
3NA3 362
3NA3 362-6
3NA3 365
3NA3 365-6
3NA3 372

1/20
1/21
1/20
1/21
1/20
1/21
1/20
1/21
1/20

1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013

PS*/
P. unit
Unit(s)
3
3
3
3
3
3
3
3
3

1/20
1/20
1/20
1/20

1
1
1
1

013
013
013
013

1
1
1
1

1/20
1/20
1/20
1/20
1/20

1
1
1
1
1

013
013
013
013
013

1
1
1
1
1

1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/21
1/19
1/19
1/21
1/19
1/21
1/19
1/19
1/21
1/19
1/19
1/21
1/19
1/19
1/21
1/19
1/19
1/19

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3/90
3
3
3
3
3/90
3
3
3/90
3
3
3/90
3
3
3/90
3
3
3
3

1/17
1/17
1/17
1/17
1/16
1/17
1/16
1/17
1/16
1/18
1/17
1/16

1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3
3
3

3NA3 4
3NA3 472
3NA3 475
3NA3 480
3NA3 482

3NA3 6
3NA3 665
3NA3 672
3NA3 675
3NA3 680
3NA3 682

3NA3 8
3NA3 801
3NA3 801-6
3NA3 802
3NA3 802-6
3NA3 803
3NA3 803-6
3NA3 804
3NA3 804-6
3NA3 805
3NA3 805-6
3NA3 807
3NA3 807-6
3NA3 810
3NA3 810-6
3NA3 812
3NA3 812-6
3NA3 814
3NA3 814-6
3NA3 814-7
3NA3 817
3NA3 817-6
3NA3 820
3NA3 820-6
3NA3 820-7
3NA3 822
3NA3 822-6
3NA3 822-7
3NA3 824
3NA3 824-6
3NA3 824-7
3NA3 830
3NA3 830-6
3NA3 830-7
3NA3 832
3NA3 836

3NA6 1
3NA6 105
3NA6 107
3NA6 110
3NA6 114
3NA6 114-4
3NA6 117
3NA6 117-4
3NA6 120
3NA6 120-4
3NA6 120-6
3NA6 122
3NA6 122-4

Siemens ET B1 2007

16/17

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NA6 122-6
3NA6 124
3NA6 124-4
3NA6 124-6
3NA6 130
3NA6 130-4
3NA6 130-6
3NA6 132
3NA6 132-4
3NA6 132-6
3NA6 136
3NA6 136-4
3NA6 136-6
3NA6 140
3NA6 140-4
3NA6 140-6
3NA6 142
3NA6 142-4
3NA6 144
3NA6 144-4

1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/17
1/16

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013

PS*/
P. unit
Unit(s)
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1/17
1/17
1/16
1/17
1/16
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/17
1/16

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1/17
1/18
1/17
1/18
1/17
1/16
1/18
1/17
1/18
1/17
1/16

1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3
3

3NA6 2
3NA6 214
3NA6 220
3NA6 220-4
3NA6 222
3NA6 222-4
3NA6 224
3NA6 224-4
3NA6 224-6
3NA6 230
3NA6 230-4
3NA6 230-6
3NA6 232
3NA6 232-4
3NA6 232-6
3NA6 236
3NA6 236-4
3NA6 236-6
3NA6 240
3NA6 240-4
3NA6 240-6
3NA6 242
3NA6 242-4
3NA6 242-6
3NA6 244
3NA6 244-4
3NA6 244-6
3NA6 250
3NA6 250-4
3NA6 250-6
3NA6 252
3NA6 252-4
3NA6 252-6
3NA6 254
3NA6 254-4
3NA6 260
3NA6 260-4

3NA6 8
3NA6 801
3NA6 801-6
3NA6 802
3NA6 802-6
3NA6 803
3NA6 803-4
3NA6 803-6
3NA6 804
3NA6 804-6
3NA6 805
3NA6 805-4

16/18

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NA6 805-6
3NA6 807
3NA6 807-4
3NA6 807-6
3NA6 810
3NA6 810-4
3NA6 810-6
3NA6 812
3NA6 812-4
3NA6 812-6
3NA6 814
3NA6 814-4
3NA6 814-6
3NA6 817
3NA6 817-4
3NA6 817-6
3NA6 820
3NA6 820-4
3NA6 820-6
3NA6 822
3NA6 822-4
3NA6 822-6
3NA6 824
3NA6 824-4
3NA6 824-4KK
3NA6 824-6
3NA6 824-7
3NA6 830
3NA6 830-4
3NA6 830-4KK
3NA6 830-6
3NA6 830-7
3NA6 832
3NA6 832-4
3NA6 836
3NA6 836-4

1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/18
1/17
1/16
1/16
1/18
1/17
1/17
1/16
1/16
1/18
1/17
1/17
1/16
1/17
1/16

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013

PS*/
P. unit
Unit(s)
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1/17
1/17
1/17
1/17
1/17
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/17

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1/17
1/17
1/17
1/17
1/18
1/17
1/18
1/17
1/18
1/17

1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3

3NA7 1
3NA7 105
3NA7 107
3NA7 110
3NA7 114
3NA7 117
3NA7 120
3NA7 120-6
3NA7 122
3NA7 122-6
3NA7 124
3NA7 124-6
3NA7 130
3NA7 130-6
3NA7 132
3NA7 132-6
3NA7 136
3NA7 136-6
3NA7 140
3NA7 140-6
3NA7 142
3NA7 144

3NA7 2
3NA7 214
3NA7 220
3NA7 222
3NA7 224
3NA7 224-6
3NA7 230
3NA7 230-6
3NA7 232
3NA7 232-6
3NA7 236

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NA7 236-6
3NA7 240
3NA7 240-6
3NA7 242
3NA7 242-6
3NA7 244
3NA7 244-6
3NA7 250-6
3NA7 252
3NA7 252-6
3NA7 260

1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/18
1/17
1/18
1/17

1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013

PS*/
P. unit
Unit(s)
3
3
3
3
3
3
3
3
3
3
3

1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/18
1/17
1/17
1/18
1/17
1/17
1/17

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013
013

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

2/12
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/12
2/12
2/12
2/12
2/12
2/12
2/12
2/11
2/11
2/11
2/11
2/11
2/11
2/11

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047

1
10
10
10
10
10
10
10
10
10
20
10
8
6
12
6
4
10
10
10
10
10
10
10

3NA7 8
3NA7 801
3NA7 801-6
3NA7 802
3NA7 802-6
3NA7 803
3NA7 803-6
3NA7 804
3NA7 804-6
3NA7 805
3NA7 805-6
3NA7 807
3NA7 807-6
3NA7 810
3NA7 810-6
3NA7 812
3NA7 812-6
3NA7 814
3NA7 814-6
3NA7 817
3NA7 817-6
3NA7 820
3NA7 820-6
3NA7 822
3NA7 822-6
3NA7 824
3NA7 824-6
3NA7 824-7
3NA7 830
3NA7 830-6
3NA7 830-7
3NA7 832
3NA7 836

3NC1
3NC1 000
3NC1 003
3NC1 006
3NC1 008
3NC1 010
3NC1 012
3NC1 016
3NC1 020
3NC1 025
3NC1 032
3NC1 038
3NC1 038-1
3NC1 038-2
3NC1 038-3
3NC1 091
3NC1 092
3NC1 093
3NC1 401
3NC1 402
3NC1 403
3NC1 404
3NC1 405
3NC1 406
3NC1 410

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NC1 410-5
3NC1 415
3NC1 415-5
3NC1 420
3NC1 420-5
3NC1 425
3NC1 425-5
3NC1 430
3NC1 430-5
3NC1 432
3NC1 432-5
3NC1 440
3NC1 440-5
3NC1 450
3NC1 450-5
3NC1 451
3NC1 451-1
3NC1 491
3NC1 491-5
3NC1 492
3NC1 493

2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/12
2/12
2/12
2/12
2/12
2/12

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047

PS*/
P. unit
Unit(s)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
3
6
6
3
2

2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/11
2/12
2/11
2/11
2/11
2/11
2/12
2/12
2/12
2/12
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047

5
10
5
10
5
10
5
10
5
10
5
10
3
5
10
5
10
6
6
3
2
3
3
3
3
3
3
3
3
3
3
1/3
3

2/9
2/9
2/9
2/9

1
1
1
1

047
047
047
047

1/3
3
3
3

2/10
2/10

1
1

047
047

3
3

2/3
2/3
2/3
2/3
2/3

1
1
1
1
1

047
047
047
047
047

3
3
3
3
3

3NC2
3NC2 200
3NC2 200-5
3NC2 220
3NC2 220-5
3NC2 225
3NC2 225-5
3NC2 232
3NC2 232-5
3NC2 240
3NC2 240-5
3NC2 250
3NC2 250-5
3NC2 258-1
3NC2 263
3NC2 263-5
3NC2 280
3NC2 280-5
3NC2 291
3NC2 291-5
3NC2 292
3NC2 293
3NC2 423
3NC2 423-3
3NC2 425
3NC2 425-3
3NC2 427
3NC2 427-3
3NC2 428
3NC2 428-3
3NC2 431
3NC2 431-3
3NC2 432
3NC2 432-3

3NC5
3NC5 531
3NC5 838
3NC5 840
3NC5 841

3NC7
3NC7 327-2
3NC7 331-2

3NC8
3NC8 423
3NC8 423-3
3NC8 425
3NC8 425-3
3NC8 427

Siemens ET B1 2007

16/19

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NC8 427-3
3NC8 431
3NC8 431-3
3NC8 434
3NC8 434-3
3NC8 444-3

2/3
2/3
2/3
2/3
2/3
2/3

1
1
1
1
1
1

047
047
047
047
047
047

PS*/
P. unit
Unit(s)
3
3
3
3
3
3

1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

014
014
014
014
014
014
014
014
014
014
014
014
014
014
014
014

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48
1/48

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

014
014
014
014
014
014
014
014
014
014
014
014
014
014
014
014
014

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

2/5
2/4
2/5
2/4
2/5
2/4
2/5
2/4
2/5
2/4
2/5
2/4
2/5
2/4
2/5
2/4
2/4
2/5
2/4
2/5
2/4
2/5
2/4
2/5
2/4
2/2
2/5

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

3ND1
3ND1 365
3ND1 372
3ND1 801
3ND1 803
3ND1 805
3ND1 807
3ND1 810
3ND1 812
3ND1 814
3ND1 817
3ND1 820
3ND1 822
3ND1 824
3ND1 830
3ND1 832
3ND1 836

3ND2
3ND2 122
3ND2 124
3ND2 130
3ND2 132
3ND2 136
3ND2 140
3ND2 144
3ND2 232
3ND2 236
3ND2 240
3ND2 244
3ND2 252
3ND2 254
3ND2 260
3ND2 352
3ND2 354
3ND2 360

3NE1
3NE1 020-2
3NE1 021-0
3NE1 021-2
3NE1 022-0
3NE1 022-2
3NE1 224-0
3NE1 224-2
3NE1 225-0
3NE1 225-2
3NE1 227-0
3NE1 227-2
3NE1 230-0
3NE1 230-2
3NE1 331-0
3NE1 331-2
3NE1 332-0
3NE1 333-0
3NE1 333-2
3NE1 334-0
3NE1 334-2
3NE1 435-0
3NE1 435-2
3NE1 436-0
3NE1 436-2
3NE1 437-0
3NE1 437-1
3NE1 437-2

16/20

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NE1 438-0
3NE1 438-1
3NE1 438-2
3NE1 447-2
3NE1 448-2
3NE1 802-0
3NE1 803-0
3NE1 813-0
3NE1 814-0
3NE1 815-0
3NE1 817-0
3NE1 818-0
3NE1 820-0

2/4
2/2
2/5
2/5
2/5
2/4
2/4
2/4
2/4
2/4
2/4
2/4
2/4

1
1
1
1
1
1
1
1
1
1
1
1
1

047
047
047
047
047
047
047
047
047
047
047
047
047

PS*/
P. unit
Unit(s)
3
3
3/1
3
3
3
3
3
3
3
3
3
3

2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/6
2/10
2/10
2/6
2/6
2/6
2/6
2/6
2/6

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

2/6
2/6
2/6
2/10
2/6
2/6
2/6
2/10
2/6
2/6
2/10
2/6
2/10
2/6
2/10
2/6
2/10
2/6
2/10
2/6
2/10

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047

3
3
3
1/3
3
3
3
1/3
3
3
1/3
3
3
3
3
3
3
3
3
3
3

2/7
2/7
2/7

1
1
1

047
047
047

2
2
2

3NE3
3NE3 221
3NE3 222
3NE3 224
3NE3 225
3NE3 227
3NE3 230-0B
3NE3 231
3NE3 232-0B
3NE3 233
3NE3 332-0B
3NE3 333
3NE3 334-0B
3NE3 335
3NE3 336
3NE3 337-8
3NE3 338-8
3NE3 340-8
3NE3 421
3NE3 430
3NE3 432
3NE3 434
3NE3 525-5
3NE3 535-5
3NE3 626
3NE3 635
3NE3 635-6
3NE3 636
3NE3 637
3NE3 637-1

3NE4
3NE4 101
3NE4 102
3NE4 117
3NE4 117-5
3NE4 118
3NE4 120
3NE4 121
3NE4 121-5
3NE4 122
3NE4 124
3NE4 146-5
3NE4 327-0B
3NE4 327-6B
3NE4 330-0B
3NE4 330-6B
3NE4 333-0B
3NE4 333-6B
3NE4 334-0B
3NE4 334-6B
3NE4 337
3NE4 337-6

3NE5
3NE5 424
3NE5 426
3NE5 430

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NE5 431
3NE5 433
3NE5 433-1
3NE5 627
3NE5 633
3NE5 643

2/7
2/7
2/7
2/7
2/7
2/7

1
1
1
1
1
1

047
047
047
047
047
047

PS*/
P. unit
Unit(s)
2
2
2
3
3
3

2/9
2/9
2/9

1
1
1

047
047
047

3
3
3

2/7
2/7
2/7
2/7
2/7
2/7
2/7
2/7
2/7
2/7

1
1
1
1
1
1
1
1
1
1

047
047
047
047
047
047
047
047
047
047

2
2
2
2
2
2
2
2
2
2

2/5
2/5
2/5
2/5
2/5
2/5
2/5
2/5
2/3
2/3
2/3
2/3
2/3
2/3
2/3
2/3
2/3
2/3
2/3
2/3
2/3

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047
047

3
3
3
3
3
3
3
3
10
10
10
10
10
10
10
10
10
10
10
10
10

2/9
2/9
2/9
2/8
2/8
2/8

1
1
1
1
1
1

047
047
047
047
047
047

3
3
3
1
1
1

1/25
1/25
1/25
1/25
1/25
1/25
1/25

1
1
1
1
1
1
1

014
014
014
014
014
014
014

1/30
3
1/10
1/5
1/5
1/5
1/5

1/22
1/22
1/22
1/22
1/23
1/23
1/22
1/23
1/22
1/22

1
1
1
1
1
1
1
1
1
1

014
014
014
014
014
014
014
014
014
014

3
3
3
3
1
1
3
1
3
1/10

3NE6
3NE6 437
3NE6 437-7
3NE6 444

3NE7
3NE7 425
3NE7 427
3NE7 431
3NE7 432
3NE7 633
3NE7 633-1
3NE7 636
3NE7 636-1
3NE7 637-1
3NE7 648-1

3NE9
3NE9 440-6
3NE9 450
3NE9 450-7
3NE9 632-1
3NE9 634-1
3NE9 636-1A

3NG1
3NG1 002
3NG1 102
3NG1 202
3NG1 302
3NG1 402
3NG1 503
3NG1 505

3NH3
3NH3 030
3NH3 031
3NH3 032
3NH3 035
3NH3 036
3NH3 037
3NH3 038
3NH3 048
3NH3 050
3NH3 051

Page

Price
per PU

PU
PG
Unit(s)

3NH3 052
3NH3 053
3NH3 120
3NH3 122
3NH3 220
3NH3 230
3NH3 320
3NH3 330
3NH3 420
3NH3 430
3NH3 530

1/22
1/22
1/22
1/22
1/22
1/22
1/22
1/22
1/22
1/22
1/22

1
1
1
1
1
1
1
1
1
1
1

014
014
014
014
014
014
014
014
014
014
014

PS*/
P. unit
Unit(s)
1/10
1/10
3
3
3
3
1
1
1
1
1

1/22
1/22
1/22
1/22
1/23
1/23
12/5
12/5
1/22

1
1
1
1
1
1
1
1
1

014
014
014
014
014
014
014
014
014

1
1
1
1
1
1
1
1
1

1/23
1/23
1/23
1/23
1/23
1/23
1/23
1/23
1/23
1/23

1
1
1
1
1
1
1
1
1
1

014
014
014
014
014
014
014
014
014
014

1
1/3
1/3
1
1
1
1
1
1
1

1/27
1/28
1/28
1/28
1/28
1/29, 12/5
1/29, 12/5

1
1
1
1
1
1
1

103
103
103
103
103
103
103

1
1
1
1
1
1
1

1/27
1/27
1/30
1/30
1/28
1/28
1/28
1/28
1/31
1/31
1/31
1/31
1/28
1/28
1/28
1/28
1/31
1/31
1/31
1/31
1/29, 12/5
1/29, 12/5
1/29, 12/5
1/29, 12/5
1/32
1/32
1/32
1/32

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3NH4
3NH4 030
3NH4 031
3NH4 032
3NH4 035
3NH4 037
3NH4 045
3NH4 052
3NH4 053
3NH4 230

3NH7

3NE8
3NE8 003-1
3NE8 015-1
3NE8 017-1
3NE8 018-1
3NE8 020-1
3NE8 021-1
3NE8 022-1
3NE8 024-1
3NE8 701-1
3NE8 702-1
3NE8 714-1
3NE8 715-1
3NE8 717-1
3NE8 718-1
3NE8 720-1
3NE8 721-1
3NE8 722-1
3NE8 724-1
3NE8 725-1
3NE8 727-1
3NE8 731-1

Order No.

* You can order this quantity or a multiple thereof.

3NH7 030
3NH7 031
3NH7 032
3NH7 230
3NH7 231
3NH7 232
3NH7 330
3NH7 331
3NH7 332
3NH7 520

3NP40 1
3NP40 10-0CH01
3NP40 15-0CJ01
3NP40 15-0CK01
3NP40 15-1CJ01
3NP40 15-1CK01
3NP40 16-1CJ01
3NP40 16-1CK01

3NP40 7
3NP40 70-0CA01
3NP40 70-0CH01
3NP40 70-0FA01
3NP40 70-0FH01
3NP40 75-0CE01
3NP40 75-0CF01
3NP40 75-0CJ01
3NP40 75-0CK01
3NP40 75-0FE01
3NP40 75-0FF01
3NP40 75-0FJ01
3NP40 75-0FK01
3NP40 75-1CE01
3NP40 75-1CF01
3NP40 75-1CJ01
3NP40 75-1CK01
3NP40 75-1FE01
3NP40 75-1FF01
3NP40 75-1FJ01
3NP40 75-1FK01
3NP40 76-1CE01
3NP40 76-1CF01
3NP40 76-1CJ01
3NP40 76-1CK01
3NP40 76-1FE01
3NP40 76-1FF01
3NP40 76-1FJ01
3NP40 76-1FK01

Siemens ET B1 2007

16/21

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

PS*/
P. unit
Unit(s)

1/27
1/30
1/28
1/31
1/29, 12/5
1/32

1
1
1
1
1
1

103
103
103
103
103
103

1
1
1
1
1
1

1/27
1/30
1/29, 12/5
1/32

1
1
1
1

103
103
103
103

1
1
1
1

1/27
1/30
1/29, 12/5
1/32

1
1
1
1

103
103
103
103

1
1
1
1

1/38
1/38
1/38
1/38
1/40
1/40
1/40
1/40
1/42
1/42
1/39
1/39
1/39
1/39
1/41
1/41
1/41
1/41
1/43

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1/38
1/38
1/38
1/38
1/40
1/40
1/40
1/40
1/42

1
1
1
1
1
1
1
1
1

103
103
103
103
103
103
103
103
103

1
1
1
1
1
1
1
1
1

1/38
1/38
1/40
1/40
1/42

1
1
1
1
1

103
103
103
103
103

1
1
1
1
1

1/38
1/38
1/40
1/40
1/42

1
1
1
1
1

103
103
103
103
103

1
1
1
1
1

1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50

1
1
1
1
1
1
1
1
1

018
018
018
018
018
018
018
018
018

10
10
10
10
10
10
10
10
10

3NP42
3NP42 70-0CA01
3NP42 70-0FA01
3NP42 75-1CG01
3NP42 75-1FG01
3NP42 76-1CG01
3NP42 76-1FG01

Page

Price
per PU

PU
PG
Unit(s)

3NW1 080-0HG
3NW1 100-0HG
3NW1 120-0HG
3NW1 150-0HG
3NW1 200-0HG
3NW1 250-0HG
3NW1 300-0HG

1/50
1/50
1/50
1/50
1/50
1/50
1/50

1
1
1
1
1
1
1

018
018
018
018
018
018
018

PS*/
P. unit
Unit(s)
10
10
10
10
10
10
10

1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50

1
1
1
1
1
1
1
1
1
1
1
1
1

018
018
018
018
018
018
018
018
018
018
018
018
018

10
10
10
10
10
10
10
10
10
10
10
10
10

1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50
1/50

1
1
1
1
1
1
1
1
1
1
1
1
1

018
018
018
018
018
018
018
018
018
018
018
018
018

10
10
10
10
10
10
10
10
10
10
10
10
10

1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46
1/46

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018

10
10
10
10
10
10/100
10
10
10
10
10
10
10
10
10/100
10
10/100
10
10
10
10
10/100
10
10/100
10
10/100
10
10
10
10
10
10
10

3NW2

3NP43
3NP43 70-0CA01
3NP43 70-0FA01
3NP43 76-1CG01
3NP43 76-1FG01

3NP44
3NP44 70-0CA01
3NP44 70-0FA01
3NP44 76-1CG01
3NP44 76-1FG01

3NP50
3NP50 60-0CA00
3NP50 60-0CA10
3NP50 60-0CB00
3NP50 60-0CB10
3NP50 60-0EA26
3NP50 60-0EA86
3NP50 60-0EB26
3NP50 60-0EB86
3NP50 60-0HA13
3NP50 60-0HB13
3NP50 65-1CF00
3NP50 65-1CF10
3NP50 65-1CG00
3NP50 65-1CG10
3NP50 65-1EF26
3NP50 65-1EF86
3NP50 65-1EG26
3NP50 65-1EG86
3NP50 65-1HF13

3NP52
3NP52 60-0CA00
3NP52 60-0CA10
3NP52 60-0CB00
3NP52 60-0CB10
3NP52 60-0EA26
3NP52 60-0EA86
3NP52 60-0EB26
3NP52 60-0EB86
3NP52 60-0HA13

3NP53
3NP53 60-0CA00
3NP53 60-0CA10
3NP53 60-0EA26
3NP53 60-0EA86
3NP53 60-0HA13

3NP54
3NP54 60-0CA00
3NP54 60-0CA10
3NP54 60-0EA26
3NP54 60-0EA86
3NP54 60-0HA13

3NW1
3NW1 006-0HG
3NW1 008-0HG
3NW1 010-0HG
3NW1 015-0HG
3NW1 020-0HG
3NW1 030-0HG
3NW1 040-0HG
3NW1 050-0HG
3NW1 060-0HG

16/22

Order No.

Siemens ET B1 2007

3NW2 010-0HG
3NW2 020-0HG
3NW2 030-0HG
3NW2 040-0HG
3NW2 050-0HG
3NW2 060-0HG
3NW2 080-0HG
3NW2 100-0HG
3NW2 120-0HG
3NW2 150-0HG
3NW2 200-0HG
3NW2 250-0HG
3NW2 300-0HG

3NW3
3NW3 010-0HG
3NW3 020-0HG
3NW3 030-0HG
3NW3 040-0HG
3NW3 050-0HG
3NW3 060-0HG
3NW3 080-0HG
3NW3 100-0HG
3NW3 120-0HG
3NW3 150-0HG
3NW3 200-0HG
3NW3 250-0HG
3NW3 300-0HG

3NW6
3NW6 001-1
3NW6 002-1
3NW6 003-1
3NW6 004-1
3NW6 005-1
3NW6 006-1
3NW6 007-1
3NW6 008-1
3NW6 010-1
3NW6 012-1
3NW6 101-1
3NW6 103-1
3NW6 104-1
3NW6 105-1
3NW6 106-1
3NW6 107-1
3NW6 108-1
3NW6 110-1
3NW6 112-1
3NW6 117-1
3NW6 120-1
3NW6 203-1
3NW6 205-1
3NW6 206-1
3NW6 207-1
3NW6 208-1
3NW6 210-1
3NW6 212-1
3NW6 217-1
3NW6 220-1
3NW6 222-1
3NW6 224-1
3NW6 230-1

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NW6 301-1
3NW6 302-1
3NW6 303-1
3NW6 304-1
3NW6 305-1
3NW6 307-1

1/46
1/46
1/46
1/46
1/46
1/46

1
1
1
1
1
1

018
018
018
018
018
018

PS*/
P. unit
Unit(s)
10
10
10
10
10
10

1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
1/47
12/4
1/50
1/50
1/50
1/47
1/47

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018

1
1/12
1
1/6
1
1/4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/40
12
6
4
1
1

1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

018
018
018
018
018
018
018
018
018
018
018
018
018
018
018

10
10
10
10
10
10
10/100
10
10
10
10
10/50
10/50
10
10

3NW7
3NW7 012
3NW7 013
3NW7 022
3NW7 023
3NW7 032
3NW7 033
3NW7 052
3NW7 053
3NW7 062
3NW7 063
3NW7 111
3NW7 112
3NW7 121
3NW7 122
3NW7 131
3NW7 132
3NW7 151
3NW7 152
3NW7 161
3NW7 162
3NW7 211
3NW7 212
3NW7 221
3NW7 222
3NW7 231
3NW7 232
3NW7 251
3NW7 252
3NW7 261
3NW7 262
3NW7 312
3NW7 313
3NW7 322
3NW7 323
3NW7 332
3NW7 333
3NW7 352
3NW7 353
3NW7 362
3NW7 363
3NW7 430
3NW7 513-0HG
3NW7 523-0HG
3NW7 533-0HG
3NW7 901
3NW7 902

3NW8
3NW8 000-1
3NW8 001-1
3NW8 002-1
3NW8 003-1
3NW8 004-1
3NW8 005-1
3NW8 006-1
3NW8 007-1
3NW8 008-1
3NW8 010-1
3NW8 011-1
3NW8 101-1
3NW8 102-1
3NW8 103-1
3NW8 104-1

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NW8 105-1
3NW8 106-1
3NW8 107-1
3NW8 108-1
3NW8 110-1
3NW8 112-1
3NW8 117-1
3NW8 120-1
3NW8 203-1
3NW8 205-1
3NW8 206-1
3NW8 207-1
3NW8 210-1
3NW8 212-1
3NW8 217-1
3NW8 220-1
3NW8 222-1
3NW8 224-1
3NW8 230-1

1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49
1/49

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018
018

PS*/
P. unit
Unit(s)
10
10/50
10
10/50
10
10
10
10
10/50
10/50
10/50
10
10
10
10
10
10
10
10

1/25
1/25
1/25
1/25
1/26
1/26
1/26
1/26

1
1
1
1
1
1
1
1

014
014
014
014
014
014
014
014

3
3
1
1
1/4
1/12
1/12
1

1/24
1/24
1/24
1/24
1/24
1/24
1/24
1/24

1
1
1
1
1
1
1
1

014
014
014
014
014
014
014
014

2/40
2/20
2/10
2/8
2/50
2/50
2/30
2/30

1/24
1/24
1/24
1/24
1/24
1/24
1/24
1/24

1
1
1
1
1
1
1
1

014
014
014
014
014
014
014
014

2/20
2/20
2/12
2/10
2/50
2/40
10
10

1/44
1/44
1/44
1/44
1/45
1/45
1/45
1/45
1/45
1/45
1/45
1/45
1/45
1/45
1/45
1/33
1/33
1/33
1/45
1/45
1/37
1/35, 1/37

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103

1
1
1
1
1/400
1/225
1
1/200
1/400
1/225
1
1
1
1
1
1 Satz
1
1
1 Satz
1 Satz
1
1

3NX1
3NX1 003
3NX1 004
3NX1 013
3NX1 014
3NX1 021
3NX1 022
3NX1 023
3NX1 024

1
2
3
4
5
6
7
8

3NX2
3NX2 023
3NX2 024
3NX2 025
3NX2 026
3NX2 027
3NX2 028
3NX2 030
3NX2 031

3NX3
3NX3 105
3NX3 106
3NX3 107
3NX3 108
3NX3 113
3NX3 114
3NX3 115
3NX3 116

3NY1
3NY1 074
3NY1 102
3NY1 103
3NY1 104
3NY1 105
3NY1 106
3NY1 107
3NY1 108
3NY1 115
3NY1 116
3NY1 125
3NY1 208
3NY1 210
3NY1 211
3NY1 212
3NY1 236
3NY1 237
3NY1 238
3NY1 241
3NY1 245
3NY1 247
3NY1 248

Siemens ET B1 2007

16/23

9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NY1 250
3NY1 251
3NY1 253
3NY1 254
3NY1 255
3NY1 256
3NY1 257
3NY1 258
3NY1 260
3NY1 261
3NY1 262
3NY1 263
3NY1 264
3NY1 265
3NY1 270
3NY1 271
3NY1 371
3NY1 372
3NY1 373
3NY1 420
3NY1 421
3NY1 422
3NY1 423
3NY1 438
3NY1 513-0
3NY1 513-2
3NY1 513-3
3NY1 513-4
3NY1 822
3NY1 824
3NY1 903
3NY1 907
3NY1 910
3NY1 911
3NY1 915
3NY1 940
3NY1 995

1/36
1/35
1/36
1/36
1/36
1/36
1/36
1/35, 1/36
1/35, 1/37
1/35, 1/37
1/35
1/33
1/35
1/33
1/37
1/36
1/44
1/44
1/44
1/44
1/44
1/44
1/44
1/33
1/44
1/44
1/44
1/44
1/19, 1/34
1/19, 1/34
1/45
1/45
1/34, 1/44
1/34, 1/44
1/44
1/45
1/33

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
013
013
103
103
103
103
103
103
103

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 Satz
1 Satz
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 Satz
1 Satz
1
1
1
1 Satz
1/200

1/34
1/44
1/44
1/34

1
1
1
1

103
103
103
103

1
1
1
1

1/44
1/44
1/44

1
1
1

103
103
103

1
1
1

1/34
1/34
1/33
1/33
1/33
1/33
1/33
1/33
1/33
1/33
1/33
1/35
1/35
1/35
1/35, 1/37
1/35, 1/37
1/33
1/33
1/33
1/33
1/35, 1/37
1/35, 1/37

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103

1
1
1 Satz
1 Satz
1 Satz
1 Satz
1 Satz
1 Satz
1 Satz
1 Satz
1 Satz
1
1
1
1
1
1
1 Satz
1
10
1
1

3NY3
3NY3 030
3NY3 033
3NY3 034
3NY3 035

3NY4
3NY4 011
3NY4 012
3NY4 031

3NY7
3NY7 001
3NY7 003
3NY7 101
3NY7 102
3NY7 105
3NY7 120
3NY7 121
3NY7 130
3NY7 131
3NY7 140
3NY7 141
3NY7 200
3NY7 201
3NY7 220
3NY7 230
3NY7 240
3NY7 322
3NY7 381
3NY7 481
3NY7 482
3NY7 500
3NY7 501

16/24

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

3NY7 502
3NY7 600
3NY7 601
3NY7 800
3NY7 801
3NY7 802
3NY7 820

1/35, 1/37
1/35
1/35
1/37
1/37
1/37
1/35, 1/37

1
1
1
1
1
1
1

103
103
103
103
103
103
103

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1

1/45

101

1 Satz

9/3
9/3
14/14
14/14
14/14
14/14
14/14
14/14

1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1

9/3
9/3
9/3
9/3
9/3
9/3
9/3
9/3
9/3
9/3
9/3
9/3
9/3

1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1
1

1/10
1/10
1/10
1/10
1/10
1/10
1/10

1
1
1
1
1
1
1

016
016
016
016
016
016
016

10
10
10
10
10
10
10

1/10
1/10
1/10
1/10
1/10
1/10
1/10

1
1
1
1
1
1
1

016
016
016
016
016
016
016

10
10
10
10
10
10
10

1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10

1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016

5
5
5
5
5
5
5
5

1/10
1/10
1/10
1/10
1/10
1/10
1/10

1
1
1
1
1
1
1

016
016
016
016
016
016
016

5
5
5
5
5
5
5

1/10
1/10
1/10

1
1
1

016
016
016

5
5
5

3TX6
3TX6 546-3B

4AC2
4AC2 400
4AC2 401
4AC2 940-8
4AC2 951-6
4AC2 952-4
4AC2 961-6
4AC2 962-4
4AC2 964-0

4AC3
4AC3 008
4AC3 016
4AC3 108
4AC3 116
4AC3 140
4AC3 408
4AC3 516
4AC3 524
4AC3 540
4AC3 616
4AC3 624
4AC3 640
4AC3 663

5SA1
5SA1 11
5SA1 21
5SA1 31
5SA1 51
5SA1 61
5SA1 71
5SA1 81

5SA2
5SA2 11
5SA2 21
5SA2 31
5SA2 51
5SA2 61
5SA2 71
5SA2 81

5SB1
5SB1 11
5SB1 21
5SB1 31
5SB1 41
5SB1 51
5SB1 61
5SB1 71
5SB1 81

5SB2
5SB2 11
5SB2 21
5SB2 31
5SB2 51
5SB2 61
5SB2 71
5SB2 81

5SB3
5SB3 11
5SB3 21
5SB3 31

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

PS*/
P. unit
Unit(s)

1/10
1/10
1/10
1/10

1
1
1
1

016
016
016
016

5
5
5
5

1/10
1/10

1
1

016
016

3
3

1/10
1/10

1
1

016
016

3
3

2/13
2/13
2/13
2/13
2/13
2/13
2/13

1
1
1
1
1
1
1

016
016
016
016
016
016
016

5
5
5
5
5
5
5

2/13
2/13

1
1

016
016

3
3

1/11
1/11
1/11
1/11
1/11
1/11
1/11
1/11
1/11
1/11

1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016

5
5
5
5
5
5
5
5
5
5

13/13
13/13
13/13
13/13
13/13
13/13
5/3
5/3
5/3
5/10
5/10
5/5
5/5
5/5
5/5
5/5
5/5
5/10
5/10
5/8
5/8
5/8
5/8
5/8
5/9
5/9
5/9
5/9
5/9
5/9
5/10
5/10
5/10
5/10
5/10

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SB4
5SB4 010
5SB4 11
5SB4 21
5SB4 31

5SC1
5SC1 11
5SC1 21

5SC2
5SC2 11
5SC2 21

5SD4
5SD4 20
5SD4 30
5SD4 40
5SD4 50
5SD4 60
5SD4 70
5SD4 80

5SD5
5SD5 10
5SD5 20

5SD6
5SD6 01
5SD6 02
5SD6 03
5SD6 04
5SD6 05
5SD6 06
5SD6 07
5SD6 08
5SD6 10
5SD6 11

5SD7
5SD7 084
5SD7 085
5SD7 086
5SD7 087
5SD7 088
5SD7 090
5SD7 412-1
5SD7 413-1
5SD7 414-1
5SD7 418-0
5SD7 418-1
5SD7 422-0
5SD7 422-1
5SD7 423-0
5SD7 423-1
5SD7 424-0
5SD7 424-1
5SD7 428-0
5SD7 428-1
5SD7 432-1
5SD7 432-2
5SD7 432-3
5SD7 432-4
5SD7 434-1
5SD7 435-0
5SD7 435-2
5SD7 435-3
5SD7 435-5
5SD7 435-6
5SD7 435-7
5SD7 437-1
5SD7 437-2
5SD7 437-3
5SD7 437-4
5SD7 438-1

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SD7 442-1
5SD7 443-1
5SD7 444-1
5SD7 448-1
5SD7 461-0
5SD7 461-1
5SD7 463-0
5SD7 463-1
5SD7 464-0
5SD7 464-1
5SD7 466-0
5SD7 466-1
5SD7 468-1
5SD7 481-0
5SD7 488-0
5SD7 490-1

5/4
5/4
5/4
5/10
5/6
5/6
5/7
5/7
5/7
5/7
5/6
5/6
5/10
5/6
5/10
5/10

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008

PS*/
P. unit
Unit(s)
1
1
1
1/100
1
1
1
1
1
1
1
1
1
1
1
1

1/11
1/11
1/11
1/11
1/11
1/11
1/11
1/11
1/11
1/11

1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016

5
5
5
5
5
5
5
5
5
5

2/13
2/13
2/13
2/13
2/13
2/13
2/13

1
1
1
1
1
1
1

016
016
016
016
016
016
016

10
10
10
10
10
10
10

1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1/12
1/12
1/12
1/12
1/13
1/12
1/12
1/12
1/12
1/13
1/12

1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016

5
5
5
5
3/108
5
5
5
5
3/108
1

1/13

016

1/5

1/12

016

5SD8
5SD8 002
5SD8 004
5SD8 006
5SD8 010
5SD8 016
5SD8 020
5SD8 025
5SD8 035
5SD8 050
5SD8 063

5SE1
5SE1 310
5SE1 316
5SE1 320
5SE1 325
5SE1 335
5SE1 350
5SE1 363

5SE2
5SE2 013-2A
5SE2 280
5SE2 300
5SE2 302
5SE2 304
5SE2 306
5SE2 310
5SE2 316
5SE2 320
5SE2 325
5SE2 332
5SE2 335
5SE2 340
5SE2 350
5SE2 363
5SE2 820
5SE2 825

5SF1
5SF1 005
5SF1 01
5SF1 012
5SF1 024
5SF1 060
5SF1 205
5SF1 214
5SF1 215
5SF1 224
5SF1 260
5SF1 401

5SF2
5SF2 07

5SF4
5SF4 230

Siemens ET B1 2007

16/25

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

PS*/
P. unit
Unit(s)

1/12
1/12
1/13
1/12
1/12
1/13

1
1
1
1
1
1

016
016
016
016
016
016

1
1
1/36
1
1
1/36

1/13
12/3
12/3
12/3
12/3
1/13
12/3
12/3
12/3
12/3

1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016

5
2/52
2/52
2/52
2/52
5
2/52
2/52
2/52
2/52

1/3
1/3
1/3
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/3
1/3
1/3
1/4
1/4
1/4

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016

1
6
6
6
6
6
6
6
6
6
6
6
6
1
6
6
10
10
10

1/3
1/3
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/3
1/3

1
1
1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016
016
016

1
2
2
2
2
2
2
2
2
2
2
1
2

12/3
12/3
12/3
12/3

1
1
1
1

016
016
016
016

4/104
4/104
4/104
4/104

1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
12/4
1/7
1/7

1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016

1
1
1
1
1
1
1
1
1/20
1
1

5SF5
5SF5 066
5SF5 067
5SF5 068
5SF5 236
5SF5 237
5SF5 268

5SF6
5SF6 005
5SF6 014
5SF6 015
5SF6 016
5SF6 017
5SF6 205
5SF6 214
5SF6 215
5SF6 216
5SF6 217

5SG1
5SG1 301
5SG1 330
5SG1 331
5SG1 553
5SG1 590
5SG1 594
5SG1 595
5SG1 650
5SG1 653
5SG1 655
5SG1 693
5SG1 694
5SG1 695
5SG1 701
5SG1 730
5SG1 731
5SG1 810
5SG1 812
5SG1 813

5SG5
5SG5 301
5SG5 330
5SG5 550
5SG5 553
5SG5 555
5SG5 650
5SG5 653
5SG5 655
5SG5 690
5SG5 693
5SG5 695
5SG5 701
5SG5 730

5SG6
5SG6 202
5SG6 203
5SG6 204
5SG6 205

5SG7
5SG7 113
5SG7 123
5SG7 133
5SG7 133-8BA25
5SG7 133-8BA35
5SG7 133-8BA50
5SG7 153
5SG7 163
5SG7 230
5SG7 610
5SG7 620

16/26

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SG7 630
5SG7 650
5SG7 660
5SG7 713
5SG7 713-1B
5SG7 723
5SG7 723-1B
5SG7 733
5SG7 733-1B
5SG7 753
5SG7 753-1B
5SG7 763
5SG7 763-1B

1/7
1/7
1/7
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8

1
1
1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016
016
016

PS*/
P. unit
Unit(s)
1
1
1
3
3
2
2
1
1
2
2
1
1

1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15

1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016

5/5000
5/30000
5/20000
1
1
1
5/5000
5/5000
5/5000
5/5000

1/14
1/14
1/14
12/3
12/3
1/14
1/14
12/3
12/3

1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016

5
5
10/620
2/120
2/60
5
10/620
2/120
2/30

5SH3 01
5SH3 02
5SH3 05
5SH3 06
5SH3 07
5SH3 071
5SH3 072
5SH3 073
5SH3 074
5SH3 075
5SH3 076
5SH3 078
5SH3 080
5SH3 081
5SH3 082
5SH3 083
5SH3 084
5SH3 085
5SH3 086
5SH3 087
5SH3 10
5SH3 11
5SH3 12

1/15
1/15
1/14
1/14
1/14
12/4
12/4
12/4
12/4
12/4
12/4
12/4
12/4
12/4
12/4
12/4
12/4
12/4
12/4
12/4
1/14
1/14
1/14

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016

5SH3 13

1/14

016

5SH3 14

1/14

016

5SH3 15
5SH3 16

1/14
1/14

1
1

016
016

5SH3 17

1/14

016

5SH3 18
5SH3 20

1/14
1/14

1
1

016
016

10
10
10
10
10
10/1500
10/1500
10/3000
10/4000
10/5000
10/3000
10
10
10
10
10
10
10/1000
10/3500
10/600
10/5000
10/5000
10/
10000
10/
10000
10/
10000
10/5000
10/
10000
10/
10000
10/5000
10/6000

5SH1
5SH1 11
5SH1 12
5SH1 13
5SH1 141
5SH1 161
5SH1 170
5SH1 22
5SH1 221
5SH1 23
5SH1 231

5SH2
5SH2 01
5SH2 02
5SH2 032
5SH2 042
5SH2 043
5SH2 22
5SH2 232
5SH2 242
5SH2 243

5SH3

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SH3 21
5SH3 22
5SH3 28
5SH3 30
5SH3 31
5SH3 32
5SH3 34
5SH3 401
5SH3 411
5SH3 500
5SH3 501
5SH3 502
5SH3 506
5SH3 526
5SH3 527
5SH3 528
5SH3 530
5SH3 531
5SH3 532
5SH3 533
5SH3 534
5SH3 535
5SH3 536
5SH3 537
5SH3 54
5SH3 55
5SH3 56
5SH3 703

1/14
1/14
1/14
1/14
1/14
1/14
1/14
1/14
1/14
13/6
13/6
13/6
12/2
12/6
12/6
12/6
12/6
12/6
12/7
12/7
12/7
12/2
12/7
12/6
13/6
13/6
13/6
1/15

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016

PS*/
P. unit
Unit(s)
10/1000
10/1000
10
5
10
10
10
5/60
5/60
1/25
1/25
10/50
4/240
2
2
2
2
2
2
4
4/40
1
4/160
2
1/5
1/5
1/5
1

1/5
1/5
1/5
1/5
1/5
1/5
1/5

1
1
1
1
1
1
1

016
016
016
016
016
016
016

3
10/1000
10/1000
10
20
20
10

1/6
1/6
1/6
1/6
1/6, 1/9
1/6, 1/9
1/6, 1/9
1/6, 1/9
1/6
1/6, 1/9
1/5
1/5
1/5
12/3
12/3
12/3
1/5
1/5
1/5
1/5
1/5
1/5
13/3
13/3
13/3
13/6
13/6
13/4, 13/6
13/4
13/4
1/6
1/6, 1/9

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016
016

10
10
10
10
10
10
10
10
10
1/10
20
10
5
4/200
4/140
4/120
5
5
15
5
15
5
1/20
1/50
1/50
1/20
1/50
10
10/300
10/300
25
10

5SH4
5SH4 100
5SH4 116
5SH4 163
5SH4 316
5SH4 317
5SH4 362
5SH4 363

5SH5
5SH5 002
5SH5 004
5SH5 006
5SH5 010
5SH5 020
5SH5 025
5SH5 035
5SH5 050
5SH5 080
5SH5 100
5SH5 233
5SH5 234
5SH5 235
5SH5 241
5SH5 242
5SH5 243
5SH5 244
5SH5 245
5SH5 251
5SH5 252
5SH5 253
5SH5 254
5SH5 320
5SH5 321
5SH5 322
5SH5 323
5SH5 324
5SH5 326
5SH5 327
5SH5 328
5SH5 400
5SH5 402

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SH5 404
5SH5 406
5SH5 410
5SH5 416
5SH5 417
5SH5 503
5SH5 510
5SH5 514
5SH5 517
5SH5 525
5SH5 526
5SH5 527

1/6, 1/9
1/6, 1/9
1/6, 1/9
1/6, 1/9
1/6
1/5
13/5
13/3
13/3
12/4
12/4
1/9, 12/4

1
1
1
1
1
1
1
1
1
1
1
1

016
016
016
016
016
016
016
016
016
016
016
016

PS*/
P. unit
Unit(s)
10
10
10
10
25
1
1/50
10
1/50
1/50
1/50
10/100

3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/11
3/10
3/11
3/10
3/10
3/10
3/10
3/10
3/10
3/11
3/10
3/11
3/10
3/10
3/11
3/10
3/11
3/10
3/10
3/11
3/10
3/11
3/10
3/10
3/11
3/10
3/11
3/10
3/10
3/11
3/10
3/11
3/10
3/10

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
003
004
002
003
003
004
004
003
004
003
004
002
003
003
004
004
002
003
003
004
004
002
003
003
004
004
002
003
003
004
004
002
003
003
004
004
002
003

1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1
1/12
1
1/12
1/12
1/12
1/12
1/12
1/12
1
1/12
1
1/12
1/12
1
1/12
1
1/12
1/12
1
1/12
1
1/12
1/12
1
1/12
1
1/12
1/12
1
1/12
1
1/12
1/12

5SJ4
5SJ4 101-7HG40
5SJ4 101-8HG40
5SJ4 102-7HG40
5SJ4 102-8HG40
5SJ4 103-7HG40
5SJ4 103-8HG40
5SJ4 104-7HG40
5SJ4 104-8HG40
5SJ4 105-7HG40
5SJ4 105-8HG40
5SJ4 106-6HG40
5SJ4 106-7HG40
5SJ4 106-8HG40
5SJ4 108-7HG40
5SJ4 108-8HG40
5SJ4 110-6HG40
5SJ4 110-7HG40
5SJ4 110-8HG40
5SJ4 111-7HG40
5SJ4 111-8HG40
5SJ4 113-6HG40
5SJ4 113-7HG40
5SJ4 113-7HG41
5SJ4 113-8HG40
5SJ4 113-8HG41
5SJ4 114-7HG40
5SJ4 114-8HG40
5SJ4 115-7HG40
5SJ4 115-8HG40
5SJ4 116-6HG40
5SJ4 116-7HG40
5SJ4 116-7HG41
5SJ4 116-8HG40
5SJ4 116-8HG41
5SJ4 118-6HG40
5SJ4 118-7HG40
5SJ4 118-7HG41
5SJ4 118-8HG40
5SJ4 118-8HG41
5SJ4 120-6HG40
5SJ4 120-7HG40
5SJ4 120-7HG41
5SJ4 120-8HG40
5SJ4 120-8HG41
5SJ4 125-6HG40
5SJ4 125-7HG40
5SJ4 125-7HG41
5SJ4 125-8HG40
5SJ4 125-8HG41
5SJ4 130-6HG40
5SJ4 130-7HG40
5SJ4 130-7HG41
5SJ4 130-8HG40
5SJ4 130-8HG41
5SJ4 132-6HG40
5SJ4 132-7HG40

Siemens ET B1 2007

16/27

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SJ4 132-7HG41
5SJ4 132-8HG40
5SJ4 132-8HG41
5SJ4 135-6HG40
5SJ4 135-7HG40
5SJ4 135-7HG41
5SJ4 135-8HG40
5SJ4 135-8HG41
5SJ4 140-6HG40
5SJ4 140-7HG40
5SJ4 140-7HG41
5SJ4 140-8HG40
5SJ4 140-8HG41
5SJ4 145-6HG40
5SJ4 145-7HG40
5SJ4 145-7HG41
5SJ4 145-8HG40
5SJ4 145-8HG41
5SJ4 150-6HG40
5SJ4 150-7HG40
5SJ4 150-8HG40
5SJ4 160-6HG40
5SJ4 160-7HG40
5SJ4 160-8HG40
5SJ4 163-6HG40
5SJ4 163-7HG40
5SJ4 163-8HG40
5SJ4 213-7HG41
5SJ4 213-8HG41
5SJ4 216-7HG41
5SJ4 216-8HG41
5SJ4 218-7HG41
5SJ4 218-8HG41
5SJ4 220-7HG41
5SJ4 220-8HG41
5SJ4 225-7HG41
5SJ4 225-8HG41
5SJ4 230-7HG41
5SJ4 230-8HG41
5SJ4 232-7HG41
5SJ4 232-8HG41
5SJ4 235-7HG41
5SJ4 235-8HG41
5SJ4 240-7HG41
5SJ4 240-8HG41
5SJ4 245-7HG41
5SJ4 245-8HG41
5SJ4 313-7HG41
5SJ4 313-8HG41
5SJ4 316-7HG41
5SJ4 316-8HG41
5SJ4 318-7HG41
5SJ4 318-8HG41
5SJ4 320-7HG41
5SJ4 320-8HG41
5SJ4 325-7HG41
5SJ4 325-8HG41
5SJ4 330-7HG41
5SJ4 330-8HG41
5SJ4 332-7HG41
5SJ4 332-8HG41
5SJ4 335-7HG41
5SJ4 335-8HG41
5SJ4 340-7HG41
5SJ4 340-8HG41
5SJ4 345-7HG41
5SJ4 345-8HG41

3/11
3/10
3/11
3/10
3/10
3/11
3/10
3/11
3/10
3/10
3/11
3/10
3/11
3/10
3/10
3/11
3/10
3/11
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/10
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11
3/11

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
004
002
003
003
004
004
002
003
003
004
004
002
003
003
004
004
002
003
004
002
003
004
002
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004

PS*/
P. unit
Unit(s)
1
1/12
1
1/12
1/12
1
1/12
1
1/12
1/12
1
1/12
1
1/12
1/12
1
1/12
1
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/3

002

1/12

5SJ6
5SJ6 110-6KS

16/28

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SJ6 110-7KS
5SJ6 113-6KS
5SJ6 113-7KS
5SJ6 116-6KS
5SJ6 116-7KS
5SJ6 120-6KS
5SJ6 120-7KS
5SJ6 210-6KS
5SJ6 210-7KS
5SJ6 213-6KS
5SJ6 213-7KS
5SJ6 216-6KS
5SJ6 216-7KS
5SJ6 220-6KS
5SJ6 220-7KS
5SJ6 310-6KS
5SJ6 310-7KS
5SJ6 313-6KS
5SJ6 313-7KS
5SJ6 316-6KS
5SJ6 316-7KS
5SJ6 320-6KS
5SJ6 320-7KS
5SJ6 510-6KS
5SJ6 510-7KS
5SJ6 513-6KS
5SJ6 513-7KS
5SJ6 516-6KS
5SJ6 516-7KS
5SJ6 520-6KS
5SJ6 520-7KS

3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003

PS*/
P. unit
Unit(s)
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12

14/6
14/6
14/6
14/6
14/6
14/6
14/6
14/7
14/7
14/6
14/7
14/7
14/6
14/6
14/7
14/7
14/7
14/6
14/6
14/6
14/6
14/6
14/7
14/6
14/7
14/6
14/6
14/6
14/7
14/6
14/6
14/6
14/7
14/6
14/7
14/6
14/7

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SM1
5SM1 111-6
5SM1 311-6
5SM1 312-6
5SM1 314-6
5SM1 316-6
5SM1 317-6
5SM1 342-6
5SM1 342-6KK01
5SM1 342-6KK03
5SM1 344-6
5SM1 344-6KK01
5SM1 344-6KK03
5SM1 346-6
5SM1 347-6
5SM1 352-6
5SM1 354-6
5SM1 356-6
5SM1 412-6
5SM1 414-6
5SM1 416-6
5SM1 417-6
5SM1 444-6
5SM1 444-8
5SM1 446-6
5SM1 446-6KK01
5SM1 612-6
5SM1 614-6
5SM1 616-6
5SM1 616-8
5SM1 617-6
5SM1 642-6
5SM1 644-6
5SM1 644-8
5SM1 646-6
5SM1 646-8
5SM1 647-6
5SM1 652-6

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SM1 654-6
5SM1 656-6
5SM1 742-6
5SM1 744-6
5SM1 746-6
5SM1 846-8
5SM1 920-5
5SM1 920-8
5SM1 930-0

14/7
14/7
14/6
14/6
14/6
14/7
4/24
4/24
4/13

1
1
1
1
1
1
1
1
1

007
007
007
007
007
007
008
008
008

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1

3/23, 4/22
3/23, 4/22
3/23, 4/22
3/24, 4/23
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/24, 4/23
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/24, 4/23
3/24, 4/23
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/24, 4/23
3/24, 4/23
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/23, 4/22
3/24, 4/23

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

4/4
4/4
4/8
4/4
4/6
4/4
4/6
4/4
4/4
4/6
4/4
4/6
4/4
4/9
4/4
4/5
4/7
4/6
4/4
4/9
4/4
4/5

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

007
007
007
007
007
007
007
007
007
007
007
007
007
008
007
007
007
007
007
008
007
007

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SM2
5SM2 121-6
5SM2 322-6
5SM2 325-6
5SM2 327-6
5SM2 332-6
5SM2 335-6
5SM2 342-6
5SM2 342-6KK01
5SM2 345-6
5SM2 345-6KK01
5SM2 347-6
5SM2 425-6
5SM2 435-6
5SM2 445-6
5SM2 622-6
5SM2 622-8
5SM2 625-6
5SM2 625-8
5SM2 627-6
5SM2 627-8
5SM2 632-6
5SM2 635-6
5SM2 635-8
5SM2 642-6
5SM2 645-6
5SM2 645-8
5SM2 647-6
5SM2 647-8
5SM2 725-6
5SM2 735-6
5SM2 735-8
5SM2 745-6
5SM2 745-8
5SM2 835-8
5SM2 845-8
5SM2 847-8

5SM3
5SM3 111-6
5SM3 311-6
5SM3 311-6KK13
5SM3 312-6
5SM3 312-6KK12
5SM3 314-6
5SM3 314-6KK12
5SM3 315-6KK
5SM3 316-6
5SM3 316-6KK12
5SM3 317-6
5SM3 317-6KK12
5SM3 318-6KK
5SM3 342-4
5SM3 342-6
5SM3 342-6KK01
5SM3 342-6KK03
5SM3 342-6KK12
5SM3 342-6KL
5SM3 344-4
5SM3 344-6
5SM3 344-6KK01

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SM3 344-6KK03
5SM3 344-6KK12
5SM3 344-6KL
5SM3 345-6
5SM3 346-4
5SM3 346-6
5SM3 346-6KK01
5SM3 346-6KK12
5SM3 346-6KL
5SM3 347-4
5SM3 347-6
5SM3 347-6KK12
5SM3 347-6KL
5SM3 352-6
5SM3 354-6
5SM3 356-6
5SM3 412-6
5SM3 414-6
5SM3 415-6KK
5SM3 416-6
5SM3 416-8
5SM3 417-6
5SM3 418-6KK
5SM3 444-6
5SM3 444-8
5SM3 445-6
5SM3 446-6
5SM3 446-6KK01
5SM3 446-8
5SM3 612-6
5SM3 614-6
5SM3 615-6KK
5SM3 616-6
5SM3 616-8
5SM3 617-6
5SM3 618-6KK
5SM3 642-4
5SM3 642-6
5SM3 642-6KL
5SM3 644-4
5SM3 644-6
5SM3 644-6KK12
5SM3 644-6KL
5SM3 644-8
5SM3 645-6
5SM3 645-8
5SM3 646-4
5SM3 646-5
5SM3 646-6
5SM3 646-6KK12
5SM3 646-6KL
5SM3 646-8
5SM3 646-8KK12
5SM3 646-8KL
5SM3 647-4
5SM3 647-5
5SM3 647-6
5SM3 647-6KL
5SM3 652-6
5SM3 654-6
5SM3 656-6
5SM3 742-6
5SM3 744-6
5SM3 745-6
5SM3 745-8
5SM3 746-6
5SM3 846-8

4/7
4/6
4/4
4/5
4/9
4/4
4/5
4/6
4/4
4/9
4/4
4/6
4/4
4/7
4/7
4/7
4/4
4/4
4/4
4/4
4/5
4/4
4/4
4/4
4/5
4/5
4/4
4/5
4/5
4/4
4/4
4/4
4/4
4/5
4/4
4/4
4/9
4/4
4/4
4/9
4/4
4/6
4/4
4/5
4/5
4/5
4/9
4/9
4/4
4/6
4/4
4/5
4/6
4/5
4/9
4/9
4/4
4/4
4/7
4/7
4/7
4/4
4/4
4/5
4/5
4/4
4/5

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

007
007
007
007
008
007
007
007
007
008
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
007
008
007
007
008
007
007
007
007
007
007
008
008
007
007
007
007
007
007
008
008
007
007
007
007
007
007
007
007
007
007
007

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/29

005

1/3

5SP3
5SP3 716

Siemens ET B1 2007

16/29

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SP3 716-1
5SP3 720
5SP3 720-1
5SP3 725
5SP3 725-1
5SP3 732
5SP3 732-1
5SP3 735
5SP3 735-1
5SP3 740
5SP3 740-1
5SP3 750
5SP3 750-1
5SP3 763
5SP3 763-1
5SP3 780
5SP3 780-1
5SP3 791
5SP3 791-1

3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29
3/29

1 Satz
1
1 Satz
1
1 Satz
1
1 Satz
1
1 Satz
1
1 Satz
1
1 Satz
1
1 Satz
1
1 Satz
1
1 Satz

005
005
005
005
005
005
005
005
005
005
005
005
005
005
005
005
005
005
005

PS*/
P. unit
Unit(s)
1 Satz
1/3
1 Satz
1/3
1 Satz
1/3
1 Satz
1/3
1 Satz
1/3
1 Satz
1/3
1 Satz
1/3
1 Satz
1/3
1 Satz
1/3
1 Satz

3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22
3/22

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

002
003
004
002
003
004
002
003
002
003
004
002
003
004
002
003
002
003
004
002
003
004
002
003
002
003
004
002
003
004
002
003

1
1
1
1
1/6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

14/5
14/5
3/30
3/30
3/30
3/30

1
1
1
1
1
1

027
027
005
005
005
005

5/1000
5/500
6
3/10
1/3
1

3/28, 4/26,
6/9, 14/5
14/5
14/5
4/26, 14/5
4/26, 14/5
4/26, 14/5
13/10
13/10

027

1/50

1
1
1
1
1
1
1

027
027
027
027
027
027
027

1/200
1/10
1/10
1/5
1/5
1/25
1/10

5SP4
5SP4 180-6
5SP4 180-7
5SP4 180-8
5SP4 191-6
5SP4 191-7
5SP4 191-8
5SP4 192-6
5SP4 192-7
5SP4 280-6
5SP4 280-7
5SP4 280-8
5SP4 291-6
5SP4 291-7
5SP4 291-8
5SP4 292-6
5SP4 292-7
5SP4 380-6
5SP4 380-7
5SP4 380-8
5SP4 391-6
5SP4 391-7
5SP4 391-8
5SP4 392-6
5SP4 392-7
5SP4 480-6
5SP4 480-7
5SP4 480-8
5SP4 491-6
5SP4 491-7
5SP4 491-8
5SP4 492-6
5SP4 492-7

5ST1
5ST1 292
5ST1 293
5ST1 316
5ST1 318
5ST1 323
5ST1 328

5ST2
5ST2 112
5ST2 120
5ST2 122
5ST2 134
5ST2 135
5ST2 136
5ST2 137
5ST2 138

16/30

Siemens ET B1 2007

Order No.

Page

5ST2 140
5ST2 142
5ST2 143
5ST2 144
5ST2 145
5ST2 146
5ST2 147
5ST2 148
5ST2 151
5ST2 152
5ST2 153
5ST2 154
5ST2 155
5ST2 156
5ST2 157
5ST2 163
5ST2 164
5ST2 165
5ST2 166
5ST2 167
5ST2 168
5ST2 170
5ST2 173
5ST2 180
5ST2 181
5ST2 182
5ST2 183
5ST2 184
5ST2 185
5ST2 186
5ST2 187
5ST2 188
5ST2 190
5ST2 191
5ST2 192
5ST2 193
5ST2 194
5ST2 195
5ST2 196
5ST2 197
5ST2 201

13/10
13/10
13/10
13/10
13/10
13/10
13/10
13/10
13/10
13/10
13/10
13/10
13/10
13/10
13/4, 13/10
13/10
13/10
13/10
13/10
13/10
14/5
14/5
3/28, 4/26
13/11
13/11
13/11
13/11
13/11
13/11
13/4, 13/11
13/4, 13/11
13/4, 13/11
13/4, 13/11
13/4, 13/11
13/4, 13/11
13/11
13/11
13/11
13/11
13/4, 13/11
3/28, 4/26,
14/5
13/4
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12
13/12

5ST2 203
5ST2 400
5ST2 401
5ST2 402
5ST2 403
5ST2 404
5ST2 405
5ST2 406
5ST2 407
5ST2 408
5ST2 410
5ST2 411
5ST2 412
5ST2 413
5ST2 414
5ST2 415
5ST2 416
5ST2 417
5ST2 418
5ST2 420
5ST2 421
5ST2 422
5ST2 423
5ST2 424
5ST2 425
5ST2 426

Price
per PU

PU
PG
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 Satz
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

PS*/
P. unit
Unit(s)
1/10
1/25
1/10
1/10
1/10
1/10
1/5
1/10
1/10
1/5
1/10
1/5
10
10
10
1/5
1/5
1/10
1/10
1/10
1/10
1/10
1 Satz
1/50
1/25
1/25
1/20
1/20
1/20
1/50
1/25
1/25
1/20
1/20
1/20
1/10
1/10
1/10
1/10
10
1/20

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/5
1/5
1/5
1/5
1/10
1/10

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

PS*/
P. unit
Unit(s)

027

027

027

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10

5ST3
5ST3 010

5ST3 011
5ST3 012
5ST3 013
5ST3 014
5ST3 015
5ST3 018-0KV
5ST3 020
5ST3 021
5ST3 022
5ST3 028-0KV
5ST3 030
5ST3 031
5ST3 040
5ST3 041
5ST3 042
5ST3 043
5ST3 044
5ST3 045
5ST3 050
5ST3 051
5ST3 600
5ST3 601
5ST3 602
5ST3 603
5ST3 604
5ST3 605
5ST3 606
5ST3 607
5ST3 608
5ST3 610
5ST3 611
5ST3 612
5ST3 613
5ST3 614
5ST3 615
5ST3 616
5ST3 617
5ST3 618
5ST3 620
5ST3 621
5ST3 622
5ST3 623
5ST3 624
5ST3 630
5ST3 631
5ST3 632
5ST3 633
5ST3 634
5ST3 635
5ST3 636
5ST3 637
5ST3 638
5ST3 640
5ST3 641
5ST3 642
5ST3 643
5ST3 644
5ST3 645
5ST3 646
5ST3 647
5ST3 648
5ST3 650
5ST3 651
5ST3 652

1/9, 3/25,
4/18, 6/4,
6/9
3/25, 4/18,
6/4, 6/9
3/25, 4/18,
6/4, 6/9
3/25, 4/18
3/25, 4/18
3/25, 4/18
3/5
3/25, 4/18
3/25, 4/18
3/25, 4/18
3/5
3/27, 4/19
3/27, 4/19
3/27, 4/19
3/27, 4/19
3/27, 4/19
3/27, 4/19
3/27, 4/19
3/27, 4/19
3/26, 4/17
4/10
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/8
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9
13/9

* You can order this quantity or a multiple thereof.

Order No.

Page

5ST3 653
5ST3 654
5ST3 655
5ST3 656
5ST3 657
5ST3 700
5ST3 701
5ST3 702
5ST3 703

13/9
13/9
13/8, 13/9
13/8
13/9
13/6, 13/7
13/6, 13/7
13/7
13/3, 13/5,
13/7
13/6, 13/7
13/6, 13/7
13/7
13/7
13/5, 13/6,
13/7
13/5, 13/6,
13/7
13/7
13/7
13/7
13/3, 13/5,
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/7
13/3, 13/4,
13/5, 13/6,
13/7
13/3, 13/5,
13/6, 13/7
3/28, 6/9
3/28, 6/4,
6/9
4/20
3/28, 4/12,
4/20, 14/8
3/28
4/18, 4/19

1
1
1
1 Satz
1 Satz
1
1
1
1

027
027
027
027
027
027
027
027
027

PS*/
P. unit
Unit(s)
1/10
1/10
1/10
1 Satz
1 Satz
1/50
1/50
1/50
1/50

1
1
1
1
1

027
027
027
027
027

1/25
1/20
1/25
1/20
1/25

027

1/20

1
1
1
1

027
027
027
027

1/25
1/20
1/25
1/20

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1/20
1/15
10
1/50
1/50
1/50
1/50
1/25
1/20
1/25
1/20
1/25
1/20
1/25
1/20
1/25
1/20
1/20
1/15
10

027

10

1
1

027
027

5/10
1

1
1

027
027

1
1

1 Satz 027
1 Satz 027

1 Satz
1 Satz

4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5ST3 704
5ST3 705
5ST3 706
5ST3 707
5ST3 708
5ST3 710
5ST3 711
5ST3 712
5ST3 713
5ST3 714
5ST3 715
5ST3 716
5ST3 718
5ST3 730
5ST3 731
5ST3 732
5ST3 733
5ST3 734
5ST3 735
5ST3 736
5ST3 737
5ST3 738
5ST3 740
5ST3 741
5ST3 742
5ST3 743
5ST3 744
5ST3 745
5ST3 746
5ST3 748

5ST3 750
5ST3 800
5ST3 801
5ST3 801-1
5ST3 802
5ST3 803
5ST3 805-1

Price
per PU

PU
PG
Unit(s)

5SU1
5SU1 154-6KK06
5SU1 154-6KK10
5SU1 154-6KK13
5SU1 154-6KK16
5SU1 154-7KK06
5SU1 154-7KK10
5SU1 154-7KK13
5SU1 154-7KK16
5SU1 324-6FA06
5SU1 324-6FA10
5SU1 324-6FA13
5SU1 324-6FA16
5SU1 324-6FA20
5SU1 324-6FA25
5SU1 324-6FA32

011
011
011
011
011
011
011
011
011
011
011
011
011
011
011

Siemens ET B1 2007

16/31

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

5SU1 324-6FA40
5SU1 324-7FA06
5SU1 324-7FA10
5SU1 324-7FA13
5SU1 324-7FA16
5SU1 324-7FA20
5SU1 324-7FA25
5SU1 324-7FA32
5SU1 324-7FA40
5SU1 354-6KK06
5SU1 354-6KK10
5SU1 354-6KK13
5SU1 354-6KK16
5SU1 354-6KK20
5SU1 354-6KK25
5SU1 354-6KK32
5SU1 354-6KK40
5SU1 354-7KK06
5SU1 354-7KK08
5SU1 354-7KK10
5SU1 354-7KK13
5SU1 354-7KK16
5SU1 354-7KK20
5SU1 354-7KK25
5SU1 354-7KK32
5SU1 354-7KK40
5SU1 356-6KK06
5SU1 356-6KK10
5SU1 356-6KK13
5SU1 356-6KK16
5SU1 356-6KK20
5SU1 356-6KK25
5SU1 356-6KK32
5SU1 356-6KK40
5SU1 356-7KK06
5SU1 356-7KK08
5SU1 356-7KK10
5SU1 356-7KK13
5SU1 356-7KK16
5SU1 356-7KK20
5SU1 356-7KK25
5SU1 356-7KK32
5SU1 356-7KK40
5SU1 374-7AK81
5SU1 374-7AK82
5SU1 374-8AK81
5SU1 654-6KK06
5SU1 654-6KK10
5SU1 654-6KK13
5SU1 654-6KK16
5SU1 654-6KK20
5SU1 654-6KK25
5SU1 654-6KK32
5SU1 654-6KK40
5SU1 654-7KK06
5SU1 654-7KK10
5SU1 654-7KK13
5SU1 654-7KK16
5SU1 654-7KK20
5SU1 654-7KK25
5SU1 654-7KK32
5SU1 654-7KK40
5SU1 656-6KK06
5SU1 656-6KK10
5SU1 656-6KK13
5SU1 656-6KK16
5SU1 656-6KK20
5SU1 656-6KK25
5SU1 656-6KK32

4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/14
4/14
4/14
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16

16/32

Siemens ET B1 2007

Price
per PU

PU
PG
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SU1 656-6KK40
5SU1 656-7KK06
5SU1 656-7KK10
5SU1 656-7KK13
5SU1 656-7KK16
5SU1 656-7KK20
5SU1 656-7KK25
5SU1 656-7KK32
5SU1 656-7KK40
5SU1 674-7AK81
5SU1 674-7AK82
5SU1 674-7BK82
5SU1 674-7CK81
5SU1 674-7CK82
5SU1 674-8AK81
5SU1 674-8BK81

4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/16
4/14
4/14
4/14
4/14
4/14
4/14
4/14

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

011
011
011
011
011
011
011
011
011
011
011
011
011
011
011
011

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

4/26, 14/5

008

14/8
14/8
14/8
14/8
4/26, 14/5
4/26, 14/5
4/26, 14/5
4/26, 14/5
4/12, 14/8
4/12, 14/8
4/12, 14/8
14/8
4/11
4/11
4/11
4/12
4/12
4/11

1
1
1
1
1
1
1
1
1
1
1
1 Satz
1
1
1
1
1 Satz
1

008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008
008

1
1
1
1/10
1/10
1
1/4
1/5
1/50
1/50
1/50
1 Satz
1/10
1/10
1/10
1
1 Satz
1

14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
003
003
003
003
002
003
003
002
003
002
003
003
003
002
003
002
003
002
003
002
003
003
003
003
003
003
002
003
003
002

1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1
1
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/6
1/6
1/6
1/6
1
1/6
1/6
1
1/6

5SW1
5SW1 200

5SW3
5SW3 000
5SW3 001
5SW3 002
5SW3 003
5SW3 004
5SW3 005
5SW3 006
5SW3 007
5SW3 008
5SW3 010
5SW3 011
5SW3 012
5SW3 300
5SW3 301
5SW3 302
5SW3 303
5SW3 312
5SW3 330

5SX2
5SX2 101-7
5SX2 102-7
5SX2 103-7
5SX2 104-7
5SX2 105-7
5SX2 106-6
5SX2 106-7
5SX2 108-7
5SX2 110-6
5SX2 110-7
5SX2 113-6
5SX2 113-7
5SX2 114-7
5SX2 115-7
5SX2 116-6
5SX2 116-7
5SX2 120-6
5SX2 120-7
5SX2 125-6
5SX2 125-7
5SX2 132-6
5SX2 132-7
5SX2 201-7
5SX2 202-7
5SX2 203-7
5SX2 204-7
5SX2 205-7
5SX2 206-6
5SX2 206-7
5SX2 208-7
5SX2 210-6

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

5SX2 210-7
5SX2 213-6
5SX2 213-7
5SX2 215-7
5SX2 216-6
5SX2 216-7
5SX2 220-6
5SX2 220-7
5SX2 225-6
5SX2 225-7
5SX2 232-6
5SX2 232-7
5SX2 301-7
5SX2 302-7
5SX2 303-7
5SX2 304-7
5SX2 305-7
5SX2 306-6
5SX2 306-7
5SX2 308-7
5SX2 310-6
5SX2 310-7
5SX2 313-6
5SX2 313-7
5SX2 315-7
5SX2 316-6
5SX2 316-7
5SX2 320-6
5SX2 320-7
5SX2 325-6
5SX2 325-7
5SX2 332-6
5SX2 332-7
5SX2 406-7
5SX2 410-7
5SX2 413-7
5SX2 416-7
5SX2 420-6
5SX2 420-7
5SX2 425-6
5SX2 425-7
5SX2 432-6
5SX2 432-7
5SX2 506-6
5SX2 506-7
5SX2 510-6
5SX2 510-7
5SX2 513-6
5SX2 513-7
5SX2 516-6
5SX2 516-7
5SX2 520-6
5SX2 520-7
5SX2 525-6
5SX2 525-7
5SX2 532-6
5SX2 532-7
5SX2 606-7
5SX2 610-6
5SX2 610-7
5SX2 613-6
5SX2 613-7
5SX2 616-6
5SX2 616-7
5SX2 620-6
5SX2 620-7
5SX2 625-6
5SX2 625-7
5SX2 632-6

14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/2
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3
14/3

Price
per PU

PU
PG
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

* You can order this quantity or a multiple thereof.

003
002
003
003
002
003
002
003
002
003
002
003
003
003
003
003
003
002
003
003
002
003
002
003
003
002
003
002
003
002
003
002
003
003
003
003
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003
003
002
003
002
003
002
003
002
003
002
003
002

PS*/
P. unit
Unit(s)
1/6
1
1
1
1/6
1/6
1
1/6
1
1/6
1
1/6
1
1/4
1
1/4
1
1
1/4
1
1/4
1/4
1
1
1
1/4
1/4
1
1/4
1
1/4
1/4
1/4
1
1
1
1
1
1
1
1
1
1
1
1/6
1
1/6
1/6
1/6
1/6
1/6
1
1
1
1
1
1
1
1
1
1
1/3
1
1/3
1
1
1
1
1

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SX2 632-7

14/3

003

PS*/
P. unit
Unit(s)
1/3

14/4
14/4
14/4
14/4
14/4
14/4
14/4

1
1
1
1
1
1
1

027
027
027
027
027
027
027

1/10
1
1
1
1
1
1

3/12
3/14
3/14
3/12
3/14
3/14
3/12
3/14
3/14
3/12
3/14
3/14
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/14
3/14
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

001
003
004
001
003
004
001
003
004
001
003
004
003
004
001
002
003
004
001
003
004
001
002
003
004
001
002
003
004
003
004
001
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001

1
1/12
1
1
1/12
1/12
1
1/12
1
1/12
1/12
1/12
1
1
1/12
1/12
1/12
1
1
1
1
1
1/12
1/12
1/12
1
1
1/12
1
1
1
1
1
1
1
1/12
1/12
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SX9
5SX9 100
5SX9 101
5SX9 102
5SX9 200
5SX9 201
5SX9 202
5SX9 300

5SY4 1
5SY4 101-5
5SY4 101-7
5SY4 101-8
5SY4 102-5
5SY4 102-7
5SY4 102-8
5SY4 103-5
5SY4 103-7
5SY4 103-8
5SY4 104-5
5SY4 104-7
5SY4 104-8
5SY4 105-7
5SY4 105-8
5SY4 106-5
5SY4 106-6
5SY4 106-7
5SY4 106-8
5SY4 108-5
5SY4 108-7
5SY4 108-8
5SY4 110-5
5SY4 110-6
5SY4 110-7
5SY4 110-8
5SY4 113-5
5SY4 113-6
5SY4 113-7
5SY4 113-8
5SY4 114-7
5SY4 114-8
5SY4 115-5
5SY4 115-7
5SY4 115-8
5SY4 116-5
5SY4 116-6
5SY4 116-7
5SY4 116-8
5SY4 120-5
5SY4 120-6
5SY4 120-7
5SY4 120-8
5SY4 125-5
5SY4 125-6
5SY4 125-7
5SY4 125-8
5SY4 132-5
5SY4 132-6
5SY4 132-7
5SY4 132-8
5SY4 140-5
5SY4 140-6
5SY4 140-7
5SY4 140-8
5SY4 150-5
5SY4 150-6
5SY4 150-7
5SY4 150-8
5SY4 163-5

Siemens ET B1 2007

16/33

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY4 163-6
5SY4 163-7
5SY4 163-8
5SY4 180-6
5SY4 180-7

3/12
3/14
3/14
3/12
3/14

1
1
1
1
1

002
003
004
002
003

PS*/
P. unit
Unit(s)
1
1
1
1/12
1/12

3/12
3/14
3/14
3/12
3/14
3/14
3/12
3/14
3/14
3/12
3/14
3/14
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/14
3/14
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

001
003
004
001
003
004
001
003
004
001
003
004
003
004
001
002
003
004
001
003
004
001
002
003
004
001
002
003
004
003
004
001
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
002

1
1
1
1
1/6
1
1
1
1
1
1/6
1
1
1
1
1
1/6
1
1
1
1
1
1/6
1/6
1
1
1
1
1
1
1
1
1
1
1
1/6
1/6
1
1
1
1
1
1
1
1/6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/6

5SY4 2
5SY4 201-5
5SY4 201-7
5SY4 201-8
5SY4 202-5
5SY4 202-7
5SY4 202-8
5SY4 203-5
5SY4 203-7
5SY4 203-8
5SY4 204-5
5SY4 204-7
5SY4 204-8
5SY4 205-7
5SY4 205-8
5SY4 206-5
5SY4 206-6
5SY4 206-7
5SY4 206-8
5SY4 208-5
5SY4 208-7
5SY4 208-8
5SY4 210-5
5SY4 210-6
5SY4 210-7
5SY4 210-8
5SY4 213-5
5SY4 213-6
5SY4 213-7
5SY4 213-8
5SY4 214-7
5SY4 214-8
5SY4 215-5
5SY4 215-7
5SY4 215-8
5SY4 216-5
5SY4 216-6
5SY4 216-7
5SY4 216-8
5SY4 220-5
5SY4 220-6
5SY4 220-7
5SY4 220-8
5SY4 225-5
5SY4 225-6
5SY4 225-7
5SY4 225-8
5SY4 232-5
5SY4 232-6
5SY4 232-7
5SY4 232-8
5SY4 240-5
5SY4 240-6
5SY4 240-7
5SY4 240-8
5SY4 250-5
5SY4 250-6
5SY4 250-7
5SY4 250-8
5SY4 263-5
5SY4 263-6
5SY4 263-7
5SY4 263-8
5SY4 280-6

16/34

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY4 280-7

3/14

003

PS*/
P. unit
Unit(s)
1

3/13
3/15
3/15
3/13
3/15
3/15
3/13
3/15
3/15
3/13
3/15
3/15
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/15
3/15
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/15

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

001
003
004
001
003
004
001
003
004
001
003
004
003
004
001
002
003
004
001
003
004
001
002
003
004
001
002
003
004
003
004
001
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
002
003

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/4
1
1
1
1
1
1
1
1
1
1
1
1/4
1/4
1/4
1
1
1
1
1
1
1
1
1
1/4
1/4
1
1
1
1
1
1
1
1
1
1
1
1
1
1/4
1

3/13
3/15

1
1

001
003

1
1

5SY4 3
5SY4 301-5
5SY4 301-7
5SY4 301-8
5SY4 302-5
5SY4 302-7
5SY4 302-8
5SY4 303-5
5SY4 303-7
5SY4 303-8
5SY4 304-5
5SY4 304-7
5SY4 304-8
5SY4 305-7
5SY4 305-8
5SY4 306-5
5SY4 306-6
5SY4 306-7
5SY4 306-8
5SY4 308-5
5SY4 308-7
5SY4 308-8
5SY4 310-5
5SY4 310-6
5SY4 310-7
5SY4 310-8
5SY4 313-5
5SY4 313-6
5SY4 313-7
5SY4 313-8
5SY4 314-7
5SY4 314-8
5SY4 315-5
5SY4 315-7
5SY4 315-8
5SY4 316-5
5SY4 316-6
5SY4 316-7
5SY4 316-8
5SY4 320-5
5SY4 320-6
5SY4 320-7
5SY4 320-8
5SY4 325-5
5SY4 325-6
5SY4 325-7
5SY4 325-8
5SY4 332-5
5SY4 332-6
5SY4 332-7
5SY4 332-8
5SY4 340-5
5SY4 340-6
5SY4 340-7
5SY4 340-8
5SY4 350-5
5SY4 350-6
5SY4 350-7
5SY4 350-8
5SY4 363-5
5SY4 363-6
5SY4 363-7
5SY4 363-8
5SY4 380-6
5SY4 380-7

5SY4 4
5SY4 401-5
5SY4 401-7

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY4 401-8
5SY4 402-5
5SY4 402-7
5SY4 402-8
5SY4 403-5
5SY4 403-7
5SY4 403-8
5SY4 404-5
5SY4 404-7
5SY4 404-8
5SY4 405-7
5SY4 405-8
5SY4 406-5
5SY4 406-6
5SY4 406-7
5SY4 406-8
5SY4 408-5
5SY4 408-7
5SY4 408-8
5SY4 410-5
5SY4 410-6
5SY4 410-7
5SY4 410-8
5SY4 413-5
5SY4 413-6
5SY4 413-7
5SY4 413-8
5SY4 414-7
5SY4 414-8
5SY4 415-5
5SY4 415-7
5SY4 415-8
5SY4 416-5
5SY4 416-6
5SY4 416-7
5SY4 416-8
5SY4 420-5
5SY4 420-6
5SY4 420-7
5SY4 420-8
5SY4 425-5
5SY4 425-6
5SY4 425-7
5SY4 425-8
5SY4 432-5
5SY4 432-6
5SY4 432-7
5SY4 432-8
5SY4 440-5
5SY4 440-6
5SY4 440-7
5SY4 440-8
5SY4 450-5
5SY4 450-6
5SY4 450-7
5SY4 450-8
5SY4 463-5
5SY4 463-6
5SY4 463-7
5SY4 463-8
5SY4 480-6
5SY4 480-7

3/15
3/13
3/15
3/15
3/13
3/15
3/15
3/13
3/15
3/15
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/15
3/15
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/15

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

004
001
003
004
001
003
004
001
003
004
003
004
001
002
003
004
001
003
004
001
002
003
004
001
002
003
004
003
004
001
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
002
003

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/3
1
1
1
1
1
1
1
1
1
1
1
1/3
1
1
1
1
1
1
1
1
1
1
1
1
1
1/3
1/3

3/12
3/14
3/14
3/12
3/14
3/14

1
1
1
1
1
1

001
003
004
001
003
004

1
1
1
1
1
1

5SY4 5
5SY4 501-5
5SY4 501-7
5SY4 501-8
5SY4 502-5
5SY4 502-7
5SY4 502-8

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY4 503-5
5SY4 503-7
5SY4 503-8
5SY4 504-5
5SY4 504-7
5SY4 504-8
5SY4 505-7
5SY4 505-8
5SY4 506-5
5SY4 506-6
5SY4 506-7
5SY4 506-8
5SY4 508-5
5SY4 508-7
5SY4 508-8
5SY4 510-5
5SY4 510-6
5SY4 510-7
5SY4 510-8
5SY4 513-5
5SY4 513-6
5SY4 513-7
5SY4 513-8
5SY4 514-7
5SY4 514-8
5SY4 515-5
5SY4 515-7
5SY4 515-8
5SY4 516-5
5SY4 516-6
5SY4 516-7
5SY4 516-8
5SY4 520-5
5SY4 520-6
5SY4 520-7
5SY4 520-8
5SY4 525-5
5SY4 525-6
5SY4 525-7
5SY4 525-8
5SY4 532-5
5SY4 532-6
5SY4 532-7
5SY4 532-8
5SY4 540-5
5SY4 540-6
5SY4 540-7
5SY4 540-8
5SY4 550-5
5SY4 550-6
5SY4 550-7
5SY4 550-8
5SY4 563-5
5SY4 563-6
5SY4 563-7
5SY4 563-8
5SY4 580-7

3/12
3/14
3/14
3/12
3/14
3/14
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/14
3/14
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/12
3/12
3/14
3/14
3/14

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

001
003
004
001
003
004
003
004
001
002
003
004
001
003
004
001
002
003
004
001
002
003
004
003
004
001
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
003

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/6
1/6
1
1
1
1
1
1
1
1/6
1/6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/6

3/13
3/15
3/15
3/13
3/15
3/15
3/13
3/15
3/15
3/13
3/15

1
1
1
1
1
1
1
1
1
1
1

001
003
004
001
003
004
001
003
004
001
003

1
1
1
1
1
1
1
1
1
1
1

1
2
3
4
5
6
7
8
9
10
11
12
13
14

5SY4 6
5SY4 601-5
5SY4 601-7
5SY4 601-8
5SY4 602-5
5SY4 602-7
5SY4 602-8
5SY4 603-5
5SY4 603-7
5SY4 603-8
5SY4 604-5
5SY4 604-7

Siemens ET B1 2007

16/35

15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY4 604-8
5SY4 605-7
5SY4 605-8
5SY4 606-5
5SY4 606-6
5SY4 606-7
5SY4 606-8
5SY4 608-5
5SY4 608-7
5SY4 608-8
5SY4 610-5
5SY4 610-6
5SY4 610-7
5SY4 610-8
5SY4 613-5
5SY4 613-6
5SY4 613-7
5SY4 613-8
5SY4 614-7
5SY4 614-8
5SY4 615-5
5SY4 615-7
5SY4 615-8
5SY4 616-5
5SY4 616-6
5SY4 616-7
5SY4 616-8
5SY4 620-5
5SY4 620-6
5SY4 620-7
5SY4 620-8
5SY4 625-5
5SY4 625-6
5SY4 625-7
5SY4 625-8
5SY4 632-5
5SY4 632-6
5SY4 632-7
5SY4 632-8
5SY4 640-5
5SY4 640-6
5SY4 640-7
5SY4 640-8
5SY4 650-5
5SY4 650-6
5SY4 650-7
5SY4 650-8
5SY4 663-5
5SY4 663-6
5SY4 663-7
5SY4 663-8
5SY4 680-7

3/15
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/15
3/15
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/13
3/13
3/15
3/15
3/15

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

004
003
004
001
002
003
004
001
003
004
001
002
003
004
001
002
003
004
003
004
001
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
001
002
003
004
003

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/3

3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
002
003
003
002
003
003
002
003
003
002
003
002
003
003
003

1
1/12
1
1
1/12
1
1
1
1
1
1
1
1
1
1
1

5SY5 1
5SY5 101-7
5SY5 102-6
5SY5 102-7
5SY5 103-7
5SY5 104-6
5SY5 104-7
5SY5 105-7
5SY5 106-6
5SY5 106-7
5SY5 108-7
5SY5 110-6
5SY5 110-7
5SY5 113-6
5SY5 113-7
5SY5 114-7
5SY5 115-7

16/36

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY5 116-6
5SY5 116-7
5SY5 120-6
5SY5 120-7
5SY5 125-6
5SY5 125-7
5SY5 132-6
5SY5 132-7
5SY5 140-6
5SY5 140-7
5SY5 150-6
5SY5 150-7
5SY5 163-6
5SY5 163-7

3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21

1
1
1
1
1
1
1
1
1
1
1
1
1
1

002
003
002
003
002
003
002
003
002
003
002
003
002
003

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21
3/21

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
003
003
003
003
002
003
003
002
003
002
003
003
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003

1
1
1
1
1
1
1/6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
003
002
003
003
002
003
002
003
002
003
002
003
002
003
002
003
002
003

1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12

3/8
3/8
3/6
3/8
3/8

1
1
1
1
1

003
004
002
003
004

1/12
1
1/12
1/12
1/12

5SY5 2
5SY5 201-7
5SY5 202-7
5SY5 203-7
5SY5 204-7
5SY5 205-7
5SY5 206-6
5SY5 206-7
5SY5 208-7
5SY5 210-6
5SY5 210-7
5SY5 213-6
5SY5 213-7
5SY5 214-7
5SY5 215-7
5SY5 216-6
5SY5 216-7
5SY5 220-6
5SY5 220-7
5SY5 225-6
5SY5 225-7
5SY5 232-6
5SY5 232-7
5SY5 240-6
5SY5 240-7
5SY5 250-6
5SY5 250-7
5SY5 263-6
5SY5 263-7

5SY6 0
5SY6 002-7KV
5SY6 004-7KV
5SY6 006-6KV
5SY6 006-7KV
5SY6 008-7KV
5SY6 010-6KV
5SY6 010-7KV
5SY6 013-6KV
5SY6 013-7KV
5SY6 016-6KV
5SY6 016-7KV
5SY6 020-6KV
5SY6 020-7KV
5SY6 025-6KV
5SY6 025-7KV
5SY6 032-6KV
5SY6 032-7KV
5SY6 040-6KV
5SY6 040-7KV

5SY6 1
5SY6 101-7
5SY6 101-8
5SY6 102-6
5SY6 102-7
5SY6 102-8

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY6 103-7
5SY6 103-8
5SY6 104-6
5SY6 104-7
5SY6 104-8
5SY6 105-7
5SY6 105-8
5SY6 106-6
5SY6 106-7
5SY6 106-8
5SY6 108-7
5SY6 108-8
5SY6 110-6
5SY6 110-7
5SY6 110-8
5SY6 113-6
5SY6 113-7
5SY6 113-8
5SY6 114-7
5SY6 114-8
5SY6 115-7
5SY6 115-8
5SY6 116-6
5SY6 116-7
5SY6 116-8
5SY6 120-6
5SY6 120-7
5SY6 120-8
5SY6 125-6
5SY6 125-7
5SY6 125-8
5SY6 132-6
5SY6 132-7
5SY6 132-8
5SY6 140-6
5SY6 140-7
5SY6 140-8
5SY6 150-6
5SY6 150-7
5SY6 150-8
5SY6 163-6
5SY6 163-7
5SY6 163-8

3/8
3/8
3/6
3/8
3/8
3/8
3/8
3/6
3/8
3/8
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/8
3/8
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
002
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

PS*/
P. unit
Unit(s)
1/12
1
1/12
1/12
1
1/12
1
1/12
1/12
1/12
1/12
1
1/12
1/12
1
1/12
1/12
1
1
1
1
1
1/12
1/12
1
1/12
1/12
1
1/12
1/12
1
1/12
1/12
1
1
1/12
1
1
1/12
1
1
1/12
1

3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/6
3/8
3/8
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/8
3/8
3/8
3/8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004
003
004
003
004

1/6
1
1/6
1/6
1/6
1
1/6
1/6
1
1
1/6
1/6
1/6
1
1
1/6
1/6
1/6
1
1
1
1
1
1
1

5SY6 2
5SY6 201-7
5SY6 201-8
5SY6 202-7
5SY6 202-8
5SY6 203-7
5SY6 203-8
5SY6 204-7
5SY6 204-8
5SY6 205-7
5SY6 205-8
5SY6 206-6
5SY6 206-7
5SY6 206-8
5SY6 208-7
5SY6 208-8
5SY6 210-6
5SY6 210-7
5SY6 210-8
5SY6 213-6
5SY6 213-7
5SY6 213-8
5SY6 214-7
5SY6 214-8
5SY6 215-7
5SY6 215-8

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY6 216-6
5SY6 216-7
5SY6 216-8
5SY6 220-6
5SY6 220-7
5SY6 220-8
5SY6 225-6
5SY6 225-7
5SY6 225-8
5SY6 232-6
5SY6 232-7
5SY6 232-8
5SY6 240-6
5SY6 240-7
5SY6 240-8
5SY6 250-6
5SY6 250-7
5SY6 250-8
5SY6 263-6
5SY6 263-7
5SY6 263-8

3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

PS*/
P. unit
Unit(s)
1/6
1/6
1
1
1/6
1
1
1/6
1
1
1/6
1
1
1
1
1
1
1
1
1
1

3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/6
3/9
3/9
3/9
3/9
3/6
3/9
3/9
3/6
3/9
3/9
3/9
3/9
3/9
3/9
3/6
3/9
3/9
3/6
3/9
3/9
3/6
3/9
3/9
3/6
3/9
3/9
3/6
3/9
3/9
3/6
3/9
3/9
3/6
3/9
3/9

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

1
1
1/4
1
1
1
1/4
1
1
1
1
1/4
1
1
1
1/4
1/4
1
1
1
1
1
1
1
1
1/4
1/4
1
1
1/4
1
1
1/4
1
1/4
1/4
1
1
1/4
1
1
1/4
1
1
1/4
1

5SY6 3
5SY6 301-7
5SY6 301-8
5SY6 302-7
5SY6 302-8
5SY6 303-7
5SY6 303-8
5SY6 304-7
5SY6 304-8
5SY6 305-7
5SY6 305-8
5SY6 306-6
5SY6 306-7
5SY6 306-8
5SY6 308-7
5SY6 308-8
5SY6 310-6
5SY6 310-7
5SY6 310-8
5SY6 313-6
5SY6 313-7
5SY6 313-8
5SY6 314-7
5SY6 314-8
5SY6 315-7
5SY6 315-8
5SY6 316-6
5SY6 316-7
5SY6 316-8
5SY6 320-6
5SY6 320-7
5SY6 320-8
5SY6 325-6
5SY6 325-7
5SY6 325-8
5SY6 332-6
5SY6 332-7
5SY6 332-8
5SY6 340-6
5SY6 340-7
5SY6 340-8
5SY6 350-6
5SY6 350-7
5SY6 350-8
5SY6 363-6
5SY6 363-7
5SY6 363-8

Siemens ET B1 2007

16/37

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

PS*/
P. unit
Unit(s)

3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/7
3/9
3/9
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/9
3/9
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/3
1
1
1
1
1
1
1
1
1
1/3
1
1
1/3
1
1
1/3
1
1
1/3
1
1
1/3
1
1
1
1
1
1/3
1

3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/6
3/8
3/8
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004

1
1
1
1
1
1
1
1
1
1
1
1/6
1
1
1
1
1/6
1
1/6
1/6
1

5SY6 4
5SY6 401-7
5SY6 401-8
5SY6 402-7
5SY6 402-8
5SY6 403-7
5SY6 403-8
5SY6 404-7
5SY6 404-8
5SY6 405-7
5SY6 405-8
5SY6 406-6
5SY6 406-7
5SY6 406-8
5SY6 408-7
5SY6 408-8
5SY6 410-6
5SY6 410-7
5SY6 410-8
5SY6 413-6
5SY6 413-7
5SY6 413-8
5SY6 414-7
5SY6 414-8
5SY6 415-7
5SY6 415-8
5SY6 416-6
5SY6 416-7
5SY6 416-8
5SY6 420-6
5SY6 420-7
5SY6 420-8
5SY6 425-6
5SY6 425-7
5SY6 425-8
5SY6 432-6
5SY6 432-7
5SY6 432-8
5SY6 440-6
5SY6 440-7
5SY6 440-8
5SY6 450-6
5SY6 450-7
5SY6 450-8
5SY6 463-6
5SY6 463-7
5SY6 463-8

5SY6 5
5SY6 501-7
5SY6 501-8
5SY6 502-7
5SY6 502-8
5SY6 503-7
5SY6 503-8
5SY6 504-7
5SY6 504-8
5SY6 505-7
5SY6 505-8
5SY6 506-6
5SY6 506-7
5SY6 506-8
5SY6 508-7
5SY6 508-8
5SY6 510-6
5SY6 510-7
5SY6 510-8
5SY6 513-6
5SY6 513-7
5SY6 513-8

16/38

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY6 514-7
5SY6 514-8
5SY6 515-7
5SY6 515-8
5SY6 516-6
5SY6 516-7
5SY6 516-8
5SY6 520-6
5SY6 520-7
5SY6 520-8
5SY6 525-6
5SY6 525-7
5SY6 525-8
5SY6 532-6
5SY6 532-7
5SY6 532-8
5SY6 540-6
5SY6 540-7
5SY6 540-8
5SY6 550-6
5SY6 550-7
5SY6 550-8
5SY6 563-6
5SY6 563-7
5SY6 563-8

3/8
3/8
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8
3/6
3/8
3/8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

PS*/
P. unit
Unit(s)
1
1
1
1
1/6
1/6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/9
3/7
3/9
3/9
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/9
3/9
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9
3/7
3/9
3/9

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1/3
1
1
1
1
1
1
1/3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SY6 6
5SY6 601-7
5SY6 601-8
5SY6 602-7
5SY6 602-8
5SY6 603-7
5SY6 603-8
5SY6 604-7
5SY6 604-8
5SY6 605-7
5SY6 605-8
5SY6 606-6
5SY6 606-7
5SY6 606-8
5SY6 608-7
5SY6 608-8
5SY6 610-6
5SY6 610-7
5SY6 610-8
5SY6 613-6
5SY6 613-7
5SY6 613-8
5SY6 614-7
5SY6 614-8
5SY6 615-7
5SY6 615-8
5SY6 616-6
5SY6 616-7
5SY6 616-8
5SY6 620-6
5SY6 620-7
5SY6 620-8
5SY6 625-6
5SY6 625-7
5SY6 625-8
5SY6 632-6
5SY6 632-7
5SY6 632-8
5SY6 640-6
5SY6 640-7
5SY6 640-8
5SY6 650-6
5SY6 650-7
5SY6 650-8

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY6 663-6
5SY6 663-7
5SY6 663-8

3/7
3/9
3/9

1
1
1

002
003
004

PS*/
P. unit
Unit(s)
1
1
1

3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/16
3/17
3/17
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/17
3/17
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/16
3/17
3/17
3/17
3/17
3/16
3/17
3/17

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SY7 1
5SY7 101-7
5SY7 101-8
5SY7 102-7
5SY7 102-8
5SY7 103-7
5SY7 103-8
5SY7 104-7
5SY7 104-8
5SY7 105-7
5SY7 105-8
5SY7 106-6
5SY7 106-7
5SY7 106-8
5SY7 108-7
5SY7 108-8
5SY7 110-6
5SY7 110-7
5SY7 110-8
5SY7 113-6
5SY7 113-7
5SY7 113-8
5SY7 114-7
5SY7 114-8
5SY7 115-7
5SY7 115-8
5SY7 116-6
5SY7 116-7
5SY7 116-8
5SY7 120-6
5SY7 120-7
5SY7 120-8
5SY7 125-6
5SY7 125-7
5SY7 125-8
5SY7 132-6
5SY7 132-7
5SY7 132-8
5SY7 140-6
5SY7 140-7
5SY7 140-8
5SY7 150-6
5SY7 150-7
5SY7 150-8
5SY7 163-6
5SY7 163-7
5SY7 163-8

5SY7 2
5SY7 201-7
5SY7 201-8
5SY7 202-7
5SY7 202-8
5SY7 203-7
5SY7 203-8
5SY7 204-7
5SY7 204-8
5SY7 205-7
5SY7 205-8
5SY7 206-6
5SY7 206-7
5SY7 206-8
5SY7 208-7
5SY7 208-8
5SY7 210-6
5SY7 210-7
5SY7 210-8

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY7 213-6
5SY7 213-7
5SY7 213-8
5SY7 214-7
5SY7 214-8
5SY7 215-7
5SY7 215-8
5SY7 216-6
5SY7 216-7
5SY7 216-8
5SY7 220-6
5SY7 220-7
5SY7 220-8
5SY7 225-6
5SY7 225-7
5SY7 225-8
5SY7 232-6
5SY7 232-7
5SY7 232-8
5SY7 240-6
5SY7 240-7
5SY7 240-8
5SY7 250-6
5SY7 250-7
5SY7 250-8
5SY7 263-6
5SY7 263-7
5SY7 263-8

3/16
3/17
3/17
3/17
3/17
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/16
3/18
3/18
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/18
3/18
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1
2
3
4
5
6
7
8

5SY7 3
5SY7 301-7
5SY7 301-8
5SY7 302-7
5SY7 302-8
5SY7 303-7
5SY7 303-8
5SY7 304-7
5SY7 304-8
5SY7 305-7
5SY7 305-8
5SY7 306-6
5SY7 306-7
5SY7 306-8
5SY7 308-7
5SY7 308-8
5SY7 310-6
5SY7 310-7
5SY7 310-8
5SY7 313-6
5SY7 313-7
5SY7 313-8
5SY7 314-7
5SY7 314-8
5SY7 315-7
5SY7 315-8
5SY7 316-6
5SY7 316-7
5SY7 316-8
5SY7 320-6
5SY7 320-7
5SY7 320-8
5SY7 325-6
5SY7 325-7
5SY7 325-8
5SY7 332-6
5SY7 332-7
5SY7 332-8
5SY7 340-6
5SY7 340-7
5SY7 340-8

Siemens ET B1 2007

16/39

9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY7 350-6
5SY7 350-7
5SY7 350-8
5SY7 363-6
5SY7 363-7
5SY7 363-8

3/16
3/18
3/18
3/16
3/18
3/18

1
1
1
1
1
1

002
003
004
002
003
004

PS*/
P. unit
Unit(s)
1
1
1
1
1
1

3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/16
3/18
3/18
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/18
3/18
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/17
3/16
3/17
3/17
3/17
3/17

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SY7 4
5SY7 401-7
5SY7 401-8
5SY7 402-7
5SY7 402-8
5SY7 403-7
5SY7 403-8
5SY7 404-7
5SY7 404-8
5SY7 405-7
5SY7 405-8
5SY7 406-6
5SY7 406-7
5SY7 406-8
5SY7 408-7
5SY7 408-8
5SY7 410-6
5SY7 410-7
5SY7 410-8
5SY7 413-6
5SY7 413-7
5SY7 413-8
5SY7 414-7
5SY7 414-8
5SY7 415-7
5SY7 415-8
5SY7 416-6
5SY7 416-7
5SY7 416-8
5SY7 420-6
5SY7 420-7
5SY7 420-8
5SY7 425-6
5SY7 425-7
5SY7 425-8
5SY7 432-6
5SY7 432-7
5SY7 432-8
5SY7 440-6
5SY7 440-7
5SY7 440-8
5SY7 450-6
5SY7 450-7
5SY7 450-8
5SY7 463-6
5SY7 463-7
5SY7 463-8

5SY7 5
5SY7 501-7
5SY7 501-8
5SY7 502-7
5SY7 502-8
5SY7 503-7
5SY7 503-8
5SY7 504-7
5SY7 504-8
5SY7 505-7
5SY7 505-8
5SY7 506-6
5SY7 506-7
5SY7 506-8
5SY7 508-7
5SY7 508-8

16/40

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY7 510-6
5SY7 510-7
5SY7 510-8
5SY7 513-6
5SY7 513-7
5SY7 513-8
5SY7 514-7
5SY7 514-8
5SY7 515-7
5SY7 515-8
5SY7 516-6
5SY7 516-7
5SY7 516-8
5SY7 520-6
5SY7 520-7
5SY7 520-8
5SY7 525-6
5SY7 525-7
5SY7 525-8
5SY7 532-6
5SY7 532-7
5SY7 532-8
5SY7 540-6
5SY7 540-7
5SY7 540-8
5SY7 550-6
5SY7 550-7
5SY7 550-8
5SY7 563-6
5SY7 563-7
5SY7 563-8

3/16
3/17
3/17
3/16
3/17
3/17
3/17
3/17
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17
3/16
3/17
3/17

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

002
003
004
002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004
002
003
004

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/18
3/16
3/18
3/18
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/18
3/18
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
002
003
004
003
004
002
003
004
002
003
004
003
004
003
004
002
003
004
002
003
004
002
003
004
002
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SY7 6
5SY7 601-7
5SY7 601-8
5SY7 602-7
5SY7 602-8
5SY7 603-7
5SY7 603-8
5SY7 604-7
5SY7 604-8
5SY7 605-7
5SY7 605-8
5SY7 606-6
5SY7 606-7
5SY7 606-8
5SY7 608-7
5SY7 608-8
5SY7 610-6
5SY7 610-7
5SY7 610-8
5SY7 613-6
5SY7 613-7
5SY7 613-8
5SY7 614-7
5SY7 614-8
5SY7 615-7
5SY7 615-8
5SY7 616-6
5SY7 616-7
5SY7 616-8
5SY7 620-6
5SY7 620-7
5SY7 620-8
5SY7 625-6
5SY7 625-7
5SY7 625-8
5SY7 632-6
5SY7 632-7
5SY7 632-8

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY7 640-6
5SY7 640-7
5SY7 640-8
5SY7 650-6
5SY7 650-7
5SY7 650-8
5SY7 663-6
5SY7 663-7
5SY7 663-8

3/16
3/18
3/18
3/16
3/18
3/18
3/16
3/18
3/18

1
1
1
1
1
1
1
1
1

002
003
004
002
003
004
002
003
004

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1

3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SY8 1
5SY8 101-7
5SY8 101-8
5SY8 102-7
5SY8 102-8
5SY8 103-7
5SY8 103-8
5SY8 104-7
5SY8 104-8
5SY8 105-7
5SY8 105-8
5SY8 106-7
5SY8 106-8
5SY8 108-7
5SY8 108-8
5SY8 110-7
5SY8 110-8
5SY8 113-7
5SY8 113-8
5SY8 114-7
5SY8 114-8
5SY8 115-7
5SY8 115-8
5SY8 116-7
5SY8 116-8
5SY8 120-7
5SY8 120-8
5SY8 125-7
5SY8 125-8
5SY8 132-7
5SY8 132-8
5SY8 140-7
5SY8 140-8
5SY8 150-7
5SY8 150-8
5SY8 163-7
5SY8 163-8

5SY8 2
5SY8 201-7
5SY8 201-8
5SY8 202-7
5SY8 202-8
5SY8 203-7
5SY8 203-8
5SY8 204-7
5SY8 204-8
5SY8 205-7
5SY8 205-8
5SY8 206-7
5SY8 206-8
5SY8 208-7
5SY8 208-8
5SY8 210-7
5SY8 210-8
5SY8 213-7
5SY8 213-8
5SY8 214-7
5SY8 214-8
5SY8 215-7
5SY8 215-8

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY8 216-7
5SY8 216-8
5SY8 220-7
5SY8 220-8
5SY8 225-7
5SY8 225-8
5SY8 232-7
5SY8 232-8
5SY8 240-7
5SY8 240-8
5SY8 250-7
5SY8 250-8
5SY8 263-7
5SY8 263-8

3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19

1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
003
004
003
004

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SY8 3
5SY8 301-7
5SY8 301-8
5SY8 302-7
5SY8 302-8
5SY8 303-7
5SY8 303-8
5SY8 304-7
5SY8 304-8
5SY8 305-7
5SY8 305-8
5SY8 306-7
5SY8 306-8
5SY8 308-7
5SY8 308-8
5SY8 310-7
5SY8 310-8
5SY8 313-7
5SY8 313-8
5SY8 314-7
5SY8 314-8
5SY8 315-7
5SY8 315-8
5SY8 316-7
5SY8 316-8
5SY8 320-7
5SY8 320-8
5SY8 325-7
5SY8 325-8
5SY8 332-7
5SY8 332-8
5SY8 340-7
5SY8 340-8
5SY8 350-7
5SY8 350-8
5SY8 363-7
5SY8 363-8

5SY8 4
5SY8 401-7
5SY8 401-8
5SY8 402-7
5SY8 402-8
5SY8 403-7
5SY8 403-8
5SY8 404-7
5SY8 404-8
5SY8 405-7
5SY8 405-8
5SY8 406-7
5SY8 406-8
5SY8 408-7
5SY8 408-8
5SY8 410-7
5SY8 410-8
5SY8 413-7

Siemens ET B1 2007

16/41

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY8 413-8
5SY8 414-7
5SY8 414-8
5SY8 415-7
5SY8 415-8
5SY8 416-7
5SY8 416-8
5SY8 420-7
5SY8 420-8
5SY8 425-7
5SY8 425-8
5SY8 432-7
5SY8 432-8
5SY8 440-7
5SY8 440-8
5SY8 450-7
5SY8 450-8
5SY8 463-7
5SY8 463-8

3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19
3/19

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20

1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
003
004

1
1
1
1
1
1
1
1
1
1
1
1

5SY8 5
5SY8 501-7
5SY8 501-8
5SY8 502-7
5SY8 502-8
5SY8 503-7
5SY8 503-8
5SY8 504-7
5SY8 504-8
5SY8 505-7
5SY8 505-8
5SY8 506-7
5SY8 506-8
5SY8 508-7
5SY8 508-8
5SY8 510-7
5SY8 510-8
5SY8 513-7
5SY8 513-8
5SY8 514-7
5SY8 514-8
5SY8 515-7
5SY8 515-8
5SY8 516-7
5SY8 516-8
5SY8 520-7
5SY8 520-8
5SY8 525-7
5SY8 525-8
5SY8 532-7
5SY8 532-8
5SY8 540-7
5SY8 540-8
5SY8 550-7
5SY8 550-8
5SY8 563-7
5SY8 563-8

5SY8 6
5SY8 601-7
5SY8 601-8
5SY8 602-7
5SY8 602-8
5SY8 603-7
5SY8 603-8
5SY8 604-7
5SY8 604-8
5SY8 605-7
5SY8 605-8
5SY8 606-7
5SY8 606-8

16/42

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5SY8 608-7
5SY8 608-8
5SY8 610-7
5SY8 610-8
5SY8 613-7
5SY8 613-8
5SY8 614-7
5SY8 614-8
5SY8 615-7
5SY8 615-8
5SY8 616-7
5SY8 616-8
5SY8 620-7
5SY8 620-8
5SY8 625-7
5SY8 625-8
5SY8 632-7
5SY8 632-8
5SY8 640-7
5SY8 640-8
5SY8 650-7
5SY8 650-8
5SY8 663-7
5SY8 663-8

3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20
3/20

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004
003
004

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

4/24
4/25
4/25
4/24

1
1
1
1

008
008
008
008

1
1
1
1

6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11
6/11

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

6/5
6/5
6/5
6/5
6/5
6/5
6/5
6/5
6/5
6/5
6/5
6/5
6/5
6/5

1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1
1
1

5SZ9
5SZ9 206
5SZ9 211
5SZ9 212
5SZ9 216

5TE1
5TE1 210
5TE1 220
5TE1 230
5TE1 240
5TE1 310
5TE1 315
5TE1 320
5TE1 325
5TE1 330
5TE1 335
5TE1 340
5TE1 345
5TE1 410
5TE1 415
5TE1 420
5TE1 425
5TE1 430
5TE1 435
5TE1 440
5TE1 445
5TE1 610
5TE1 620
5TE1 630
5TE1 640

5TE4
5TE4 800
5TE4 804
5TE4 805
5TE4 806
5TE4 807
5TE4 808
5TE4 810
5TE4 811
5TE4 812
5TE4 813
5TE4 814
5TE4 820
5TE4 821
5TE4 822

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5TE4 823
5TE4 824
5TE4 830
5TE4 831
5TE4 840
5TE4 841

6/5
6/5
6/5
6/5
6/6
6/6

1
1
1
1
1
1

027
027
027
027
027
027

PS*/
P. unit
Unit(s)
1
1
1
1
1
1

6/7
6/7
6/7
6/7

1
1
1
1

027
027
027
027

1/12
1
1
1

9/4
9/4
9/4
9/4
9/4

1
1
1
1
1

027
027
027
027
027

1
1
1
1
1

5TE5
5TE5 800
5TE5 801
5TE5 802
5TE5 804

5TE6
5TE6 800
5TE6 801
5TE6 802
5TE6 803
5TE6 804

14/9
14/9
14/9
14/9
14/9

1
1
1
1
1

027
027
027
027
027

1/12
1/12
1/12
1
1/4

6/3
6/3
6/3
6/3
6/3
6/3
6/8
6/8
6/8
6/8
6/8
6/3
6/3
6/3
6/3
6/3
6/3
6/3
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/9
6/8
6/8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1/12
1/120
1/12
1/12
1
1/80
1/12
1/12
1/12
1/120
1/80
1/12
1/12
1/12
1/12
1/120
1/12
1
1
1/12
1/12
1/120
1/80
1/12
1/6
1/40
1/30
1
1/12
1/6
1/40
1/3
1
1/120
1/60
1/40
1/3
1
1/120
1/6
1/40
1/30
1/40
1/12
1/6

5TE8
5TE8 101
5TE8 101-3
5TE8 102
5TE8 103
5TE8 105
5TE8 108
5TE8 111
5TE8 112
5TE8 113
5TE8 114
5TE8 118
5TE8 141
5TE8 142
5TE8 151
5TE8 152
5TE8 153
5TE8 161
5TE8 162
5TE8 211
5TE8 212
5TE8 213
5TE8 214
5TE8 218
5TE8 311
5TE8 312
5TE8 313
5TE8 314
5TE8 315
5TE8 411
5TE8 412
5TE8 413
5TE8 414
5TE8 415
5TE8 511
5TE8 512
5TE8 513
5TE8 514
5TE8 515
5TE8 521
5TE8 522
5TE8 523
5TE8 524
5TE8 533
5TE8 611
5TE8 612

Page

Price
per PU

PU
PG
Unit(s)

5TE8 613
5TE8 614
5TE8 615
5TE8 711
5TE8 712
5TE8 713
5TE8 714
5TE8 715
5TE8 721
5TE8 722
5TE8 723
5TE8 724
5TE8 811
5TE8 812
5TE8 813
5TE8 814
5TE8 815

6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8
6/8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

PS*/
P. unit
Unit(s)
1/4
1/30
1
1/120
1/6
1/4
1/3
1
1/120
1/60
1/40
1/30
1/120
1/60
1/40
1/30
1

6/12
6/12
6/12
6/12
6/12
6/12
6/12
6/12
6/12
6/12
6/12
13/14
13/14
13/14
6/10
6/10
9/4

1
1
1 Satz
1 Satz
1
1
1
1
1
1
1
1
1
1 Satz
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1 Satz
1 Satz
1
1
1
1
1
1
1
1/10
1/10
1 Satz
1
1
1

5TG8 050
5TG8 051
5TG8 052
5TG8 053
5TG8 054
5TG8 055
5TG8 060

6/6, 6/7
6/6, 6/7
6/6, 6/7
6/6, 6/7
6/6, 6/7
6/6, 6/7
6/6

1
1
1
1
1
1
1 Satz

027
027
027
027
027
027
027

5TG8 061

6/6, 6/7

1 Satz 027

5TG8 062

6/6, 6/7

1 Satz 027

5TG8 063

6/6, 6/7

1 Satz 027

5TG8 064

6/6, 6/7

1 Satz 027

5TG8 065

6/6

1 Satz 027

5TG8 066

6/6, 6/7

1 Satz 027

5TG8 067

6/6, 6/7

1 Satz 027

5TG8 068

6/4

1 Satz 027

5TG8 070

6/6, 6/7

1 Satz 027

5TG8 222
5TG8 223
5TG8 230
5TG8 240

11/8
11/14
14/10
3/28, 6/4,
6/9, 7/5

1
1
1
1

027
027
027
027

1/10
1/10
1/10
1/10
1/10
1/10
1 Satz/
10 Stze
1 Satz/
10 Stze
1 Satz/
10 Stze
1 Satz/
10 Stze
1 Satz/
10 Stze
1 Satz/
10 Stze
1 Satz/
10 Stze
1 Satz/
10 Stze
1 Satz/
30 Stze
1 Satz/
10 Stze
1
1/24
1
2

8/3
14/12
14/12

1
1
1

027
027
027

1
1
1

5TE9

5TE7
5TE7 101
5TE7 111
5TE7 141
5TE7 211
5TE7 513

Order No.

* You can order this quantity or a multiple thereof.

5TE9 000
5TE9 001
5TE9 003
5TE9 004
5TE9 005
5TE9 006
5TE9 010
5TE9 011
5TE9 012
5TE9 013
5TE9 014
5TE9 100
5TE9 101
5TE9 102
5TE9 112
5TE9 113
5TE9 120

5TG8

5TT1
5TT1 303
5TT1 310-1
5TT1 311-1

Siemens ET B1 2007

16/43

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5TT1 313-1

14/12

027

PS*/
P. unit
Unit(s)
1

14/10
11/7
11/8
8/4
8/4
8/4
8/4
8/4
11/9
11/9
11/6
11/9
11/9
11/10
11/10
11/10
11/10
11/10
11/10
11/10
11/10
11/8
11/8
11/15
11/15
11/14
7/8
7/8
14/15
14/15
14/15
14/15
11/5
11/5
11/12
11/12
11/14
14/11
14/11
14/11
14/11
14/11
14/11
14/11
14/11
14/11
14/11
14/11
14/11
14/11
14/11

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1/12
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5TT3
5TT3 045
5TT3 170
5TT3 171
5TT3 181
5TT3 182
5TT3 183
5TT3 184
5TT3 185
5TT3 194
5TT3 195
5TT3 303
5TT3 400
5TT3 401
5TT3 402
5TT3 403
5TT3 404
5TT3 405
5TT3 406
5TT3 407
5TT3 408
5TT3 410
5TT3 421
5TT3 423
5TT3 431
5TT3 432
5TT3 435
5TT3 440
5TT3 441
5TT3 450
5TT3 451
5TT3 452
5TT3 453
5TT3 460
5TT3 461
5TT3 470
5TT3 471
5TT3 472
5TT3 806
5TT3 807
5TT3 816
5TT3 817
5TT3 821
5TT3 822
5TT3 823
5TT3 824
5TT3 825
5TT3 841
5TT3 842
5TT3 843
5TT3 844
5TT3 845

5TT4
5TT4 101-0
5TT4 101-1
5TT4 101-2
5TT4 101-3
5TT4 101-4
5TT4 102-0
5TT4 102-1
5TT4 102-2
5TT4 102-3
5TT4 102-4
5TT4 103-0
5TT4 103-2
5TT4 104-0
5TT4 104-2
5TT4 105-0

16/44

Siemens ET B1 2007

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5TT4 105-1
5TT4 105-2
5TT4 105-3
5TT4 105-4
5TT4 122-0
5TT4 123-0
5TT4 125-0
5TT4 132-0
5TT4 142-0
5TT4 142-2
5TT4 142-3
5TT4 201-0
5TT4 201-1
5TT4 201-2
5TT4 201-3
5TT4 201-4
5TT4 202-0
5TT4 202-1
5TT4 202-2
5TT4 202-3
5TT4 202-4
5TT4 204-0
5TT4 204-1
5TT4 204-2
5TT4 204-3
5TT4 204-4
5TT4 205-0
5TT4 205-1
5TT4 205-2
5TT4 205-3
5TT4 205-4
5TT4 206-0
5TT4 206-1
5TT4 206-2
5TT4 206-3
5TT4 206-4
5TT4 207-0
5TT4 207-1
5TT4 207-2
5TT4 207-3
5TT4 207-4
5TT4 900
5TT4 901

7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/3
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/3
7/3

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1/12
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

7/9
14/10
14/10
14/10
14/10
14/10
14/10
14/10
14/10
7/5
7/5
7/5
7/5
7/5
7/5
7/5
7/5
7/5
7/5
7/5
7/5
7/5
7/5
7/5
7/5

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1/12
1/12
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5TT5
5TT5 200
5TT5 501
5TT5 502
5TT5 511
5TT5 512
5TT5 521
5TT5 522
5TT5 531
5TT5 532
5TT5 730-0
5TT5 730-1
5TT5 730-2
5TT5 731-0
5TT5 731-2
5TT5 732-0
5TT5 732-2
5TT5 733-0
5TT5 733-2
5TT5 740-0
5TT5 740-2
5TT5 741-0
5TT5 741-2
5TT5 742-0
5TT5 742-2
5TT5 750-0

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

5TT5 750-2
5TT5 751-0
5TT5 751-2
5TT5 752-0
5TT5 752-2
5TT5 800-0
5TT5 800-2
5TT5 800-6
5TT5 800-8
5TT5 801-0
5TT5 801-2
5TT5 801-6
5TT5 801-8
5TT5 802-0
5TT5 802-2
5TT5 830-0
5TT5 830-1
5TT5 830-2
5TT5 830-6
5TT5 830-8
5TT5 831-0
5TT5 831-1
5TT5 831-2
5TT5 831-6
5TT5 831-8
5TT5 832-0
5TT5 832-2
5TT5 833-0
5TT5 833-2
5TT5 840-0
5TT5 840-2
5TT5 840-6
5TT5 840-8
5TT5 841-0
5TT5 841-2
5TT5 841-6
5TT5 841-8
5TT5 842-0
5TT5 842-2
5TT5 843-0
5TT5 843-2
5TT5 850-0
5TT5 850-2
5TT5 850-6
5TT5 851-0
5TT5 851-2
5TT5 852-0
5TT5 852-2
5TT5 853-0
5TT5 853-2
5TT5 900
5TT5 901
5TT5 902

7/5
7/5
7/5
7/5
7/5
7/6
7/6
7/7
7/7
7/6
7/6
7/7
7/7
7/6
7/6
7/6
7/6
7/6
7/7
7/7
7/6
7/6
7/6
7/7
7/7
7/6
7/6
7/6
7/6
7/6
7/6
7/7
7/7
7/6
7/6
7/7
7/7
7/6
7/6
7/6
7/6
7/6
7/6
7/7
7/6
7/6
7/6
7/6
7/6
7/6
7/5
7/5
7/5

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 Satz

5TT5 903

7/5

1 Satz 027

5TT5 910-0
5TT5 910-1
5TT5 910-5
5TT5 910-6
5TT5 910-7

7/6, 7/7
7/6, 7/7
7/6, 7/7
7/6, 7/7
7/6, 7/7

1
1
1
1
1

027
027
027
027
027

PS*/
P. unit
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 Satz/
25 Stze
1 Satz/
25 Stze
1
1
2
2
2

11/12
11/12
11/12
11/11
11/11
11/11
11/11
11/11

1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

5TT6
5TT6 101
5TT6 102
5TT6 103
5TT6 111
5TT6 112
5TT6 113
5TT6 114
5TT6 115

* You can order this quantity or a multiple thereof.

Order No.

Page

Price
per PU

PU
PG
Unit(s)

5TT6 120

11/11

027

PS*/
P. unit
Unit(s)
1

11/16
11/16
11/16
11/16

1
1
1
1

027
027
027
027

1
1
1
1

10/5
10/5
10/5
10/5
10/5
10/5
10/5
10/8
10/8
10/9
10/9
10/10
10/10
10/10
10/6
10/6
10/6
10/7
10/7
10/7
10/7
10/7
10/7
10/7
10/7
10/7
10/9
10/8
10/8
10/8
10/8
10/8
10/8
10/8
10/8
10/8
10/8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4
10/4

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

5TT7
5TT7 110-0
5TT7 120-0
5TT7 908-1
5TT7 908-2

7KT1
7KT1 000
7KT1 010
7KT1 011
7KT1 012
7KT1 020
7KT1 110
7KT1 120
7KT1 140
7KT1 141
7KT1 162
7KT1 165
7KT1 200
7KT1 201
7KT1 202
7KT1 300
7KT1 301
7KT1 302
7KT1 310
7KT1 311
7KT1 312
7KT1 340
7KT1 341
7KT1 342
7KT1 350
7KT1 351
7KT1 352
7KT1 390
7KT1 500
7KT1 501
7KT1 502
7KT1 503
7KT1 510
7KT1 511
7KT1 512
7KT1 513
7KT1 520
7KT1 521

7KT5
7KT5 500
7KT5 501
7KT5 502
7KT5 503
7KT5 504
7KT5 505
7KT5 600
7KT5 601
7KT5 602
7KT5 603
7KT5 604
7KT5 801
7KT5 802
7KT5 803
7KT5 804
7KT5 806
7KT5 807
7KT5 811
7KT5 812
7KT5 814
7KT5 821
7KT5 822
7KT5 823
7KT5 833

Siemens ET B1 2007

16/45

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Appendix
Order number index
Order No.

Page

Price
per PU

PU
PG
Unit(s)

PS*/
P. unit
Unit(s)

1 Satz
1
1
1
1
1

1 Satz
1/48
1
5/1
5
1

7KT9
7KT9 000
7KT9 010
7KT9 011
7KT9 020
7KT9 021
7KT9 030

027
027
027
027
027
027

8/6
8/6
8/6
8/6
8/6
8/6
8/6
8/6
8/6
8/6
8/6
8/6
8/6
8/7
8/7
14/12
14/12
14/12
8/7
8/7
8/7

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

8/8
8/8
8/8
8/8
8/8
8/9
8/9
8/9
8/9
8/9
8/9
14/13
14/13
14/13
14/13

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

8/3
8/3
8/3
8/3
8/3
8/3

1
1
1
1
1
1

027
027
027
027
027
027

1
1
1
1
1
1

14/12
14/12
14/12

1
1
1

027
027
027

1
1
1

11/7
11/7
11/7
11/7
11/6
14/15
11/6
11/6
11/6
11/7
11/6, 14/15
11/6

1
1
1
1
1
1
1
1
1
1
1
1

027
027
027
027
027
027
027
027
027
027
027
027

1
1
1
1
1
1
1
1
1
1
1
1

7LF6
7LF6 110
7LF6 111
7LF6 112
7LF6 113
7LF6 114
7LF6 115

7LF9
7LF9 002
7LF9 003
7LF9 006

16/46

PU
PG
Unit(s)

PS*/
P. unit
Unit(s)

7LQ3 350
7LQ3 351
7LQ3 352
7LQ3 353

11/13
11/13
11/13
11/13

1
1
1
1

027
027
027
027

1
1
1
1

6/9

032

12/7
12/7
12/7
12/7
12/7
12/7

1
1
1
1
1
1

039
039
039
039
039
039

1
1
1
1
1
1

1/36
1/36
1/36
1/36
1/36
1/36

1
1
1
1
1
1

046
046
046
046
046
046

1
1
1
1
1
1

12/2
12/2
12/2
12/2
13/6
13/6

1
1
1
1
1
1

046
046
046
046
046
046

10
10
10
10
10
10

12/2
12/2

1
046
1 Satz 046

10
10

1/45
12/5
12/5
12/5
12/5
12/5
1/45

1
1
1
1
1
1
1

103
103
103
103
103
103
103

1
1
1/6
1/4
1
1
1

12/2
12/2
12/7
12/7
12/6
12/6
12/2
12/2
12/2
12/2
12/5
12/5

1
1
1
1
1
1
1
1
1
1
100
1

103
103
103
103
103
103
103
103
103
103
103
103

1
1
1
10
10
10
10
10
10
6
100
4

3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

041
041
041
041
041
041
041
041
041
041
041
041
041
041
041
041

10
10
10
10
10
10
10
10
10
10
5
5
5
5
5
5

8GB4
8GB4 576
8GK4 801-2KK13
8GK4 801-2KK23
8GK4 801-2KK33
8GK4 801-3KK13
8GK4 801-3KK23
8GK4 801-3KK33

8HP6
8HP6 422
8HP6 423
8HP6 424
8HP6 427
8HP6 431
8HP6 432

8JH4
8JH4 102
8JH4 104
8JH4 105
8JH4 106
8JH4 122
8JH4 124

8JK3
8JK3 061
8JK3 201

8US12
8US12 10-4AG00
8US12 50-5AM00
8US12 50-5RM07
8US12 51-5CM47
8US12 51-5DM07
8US12 61-5FM08
8US12 91-4SB00

8US19
8US19 21-1AA00
8US19 21-1BA00
8US19 22-1AB00
8US19 22-1AC00
8US19 22-2AA00
8US19 22-2BA00
8US19 23-2AA01
8US19 23-3AA01
8US19 23-4AA00
8US19 41-2BB00
8US19 98-1AA00
8US19 98-2BM00

8WA1

7LQ2
7LQ2 001
7LQ2 002
7LQ2 003
7LQ2 005
7LQ2 100
7LQ2 100-1
7LQ2 101
7LQ2 102
7LQ2 103
7LQ2 900
7LQ2 910
7LQ2 911

Price
per PU

8GK4

7LF5
7LF5 300-1
7LF5 300-5
7LF5 300-6
7LF5 300-7
7LF5 301-0
7LF5 301-1
7LF5 301-4
7LF5 301-5
7LF5 301-6
7LF5 301-7
7LF5 305-0
7LF5 390-1
7LF5 391-1
7LF5 391-6
7LF5 391-7

Page

7LQ3
10/4
10/10
10/10
10/4
10/4
10/9

7LF4
7LF4 401-0
7LF4 411-0
7LF4 411-1
7LF4 412-0
7LF4 412-1
7LF4 421-0
7LF4 421-1
7LF4 421-2
7LF4 422-0
7LF4 422-1
7LF4 422-2
7LF4 431-0
7LF4 432-0
7LF4 444-0
7LF4 444-2
7LF4 481-0
7LF4 491-0
7LF4 492-0
7LF4 940-0
7LF4 940-1
7LF4 940-2

Order No.

Siemens ET B1 2007

8WA1 011-1SF24
8WA1 011-1SF25
8WA1 011-1SF26
8WA1 011-1SF27
8WA1 011-1SF28
8WA1 011-2SF24
8WA1 011-2SF25
8WA1 011-2SF26
8WA1 011-2SF27
8WA1 011-2SF28
8WA1 011-4SF24
8WA1 011-4SF25
8WA1 011-4SF26
8WA1 011-4SF27
8WA1 011-4SF28
8WA1 011-6SF24

* You can order this quantity or a multiple thereof.

Appendix
Order number index
Order No.

Page

8WA1 011-6SF25
8WA1 011-6SF26
8WA1 011-6SF27
8WA1 011-6SF28
8WA1 011-8SF23
8WA1 011-8SF24
8WA1 011-8SF25
8WA1 011-8SF26
8WA1 011-8SF27
8WA1 011-8SF28
8WA1 822-7VD00
8WA1 822-7VD01
8WA1 822-7VD02
8WA1 822-7VD03
8WA1 822-7VD04
8WA1 822-7VD06
8WA1 822-7VD07

3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/32
3/32
3/32
3/32
3/32
3/32
3/32

Price
per PU

PU
PG
Unit(s)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

041
041
041
041
041
041
041
041
041
041
041
041
041
041
041
041
041

PS*/
P. unit
Unit(s)
5
5
5
5
5
5
5
5
5
5
10
20
20
10
10
20
20

3
4
5
6
7

Legend:
PU
PG
PS
P. unit

1
2

Price unit
Price group
Package size
Package unit

8
9
10
11
12
13
14
15
16
* You can order this quantity or a multiple thereof.

Siemens ET B1 2007

16/47

Appendix
Terms and conditions of sale and delivery
Export regulations

Terms and conditions of sale and delivery


By using this catalog you can acquire hardware and software
products described therein from Siemens AG subject to the following terms. Please note! The scope, the quality and the conditions for supplies and services, including software products, by
any Siemens entity having a registered office outside of Germany, shall be subject exclusively to the General Terms and
Conditions of the respective Siemens entity. The following terms
apply exclusivelyfor orders placed with Siemens AG.
For customers with a seat or registered office in Germany
The General Terms of Payment as well as the General Conditions for the Supply of Products and Services of the Electrical
and Electronics Industry shall apply.
For software products, the General License Conditions for
Software Products for Automation and Drives for Customers with
a Seat or registered Office in Germany shall apply.
For customers with a seat or registered office outside of
Germany
The General Terms of Payment as well as the General Conditions for Supplies of Siemens, Automation and Drives for Customers with a Seat or registered Office outside of Germany shall
apply.
For software products, the General License Conditions for Software Products for Automation and Drives for Customers with a
Seat or registered Office outside of Germany shall apply.
General
The dimensions are in mm. In Germany, according to the German law on units in measuring technology, data in inches only
apply to devices for export.
Illustrations are not binding.
Insofar as there are no remarks on the corresponding pages,
- especially with regard to data, dimensions and weights given these are subject to change without prior notice.
The prices are in (Euro) ex works, exclusive packaging.
The sales tax (value added tax) is not included in the prices.
It shall be debited separately at the respective rate according to
the applicable legal regulations.
Prices are subject to change without prior notice. We will debit
the prices valid at the time of delivery.
Surcharges will be added to the prices of products that contain
silver, copper, aluminum, lead and/or gold, if the respective basic official prices for these metals are exceeded. These surcharges will be determined based on the official price and the
metal factor of the respective product.
The surcharge will be calculated on the basis of the official price
on the day prior to receipt of the order or prior to the release order.
The metal factor determines the official price as of which the
metal surcharges are charged and the calculation method used.
The metal factor, provided it is relevant, is included with the price
information of the respective products. An exact explanation of
the metal factor can be found on the page entitled Metal surcharges.

16/48

Siemens ET B1 2007

The texts of the Comprehensive Terms and Conditions of Sale


and Delivery are available free of charge from your local Siemens business office under the following Order Nos.:
6ZB5310-0KR30-0BA1
(for customers based in Germany)
6ZB5310-0KS53-0BA1
(for customers based outside of Germany)
or download them from the Internet
http://www.siemens.com/automation/mall
(Germany: A&D Mall Online-Help System)

Export regulations
The products listed in this catalog / price list may be subject to
European / German and/or US export regulations.
Therefore, any export requiring a license is subject to approval
by the competent authorities.
According to current provisions, the following export regulations
must be observed with respect to the products featured in this
catalog / price list:
AL

Number of the German Export List


Products marked other than N require an export
license.
In the case of software products, the export designations of the relevant data medium must also
be generally adhered to.
Goods labeled with an AL not equal to N are
subject to a European or German export authorization when being exported out of the EU.

ECCN

Export Control Classification Number.


Products marked other than N are subject to a
reexport license to specific countries.
In the case of software products, the export
designations of the relevant data medium must
also be generally adhered to.
Goods labeled with an ECCN not equal to N
are subject to a US re-export authorization.

Even without a label or with an AL: N or ECCN: N, authorization may be required due to the final destination and purpose for
which the goods are to be used.
The deciding factors are the AL or ECCN export authorization
indicated on order confirmations, delivery notes and invoices.
Errors excepted and subject to change without prior notice.
A&D/VuL_mit MZ/En 05.09.06

Catalogs of the
Automation and Drives Group (A&D)
Further information can be obtained from our branch offices listed
in the appendix or at www.siemens.com/automation/partner
Automation and Drives
Interactive catalog on CD-ROM and on DVD

Catalog

The Offline Mall of Automation and Drives

CA 01

Automation Systems for Machine Tools


SINUMERIK & SIMODRIVE

NC 60

SINUMERIK & SINAMICS

NC 61

Drive Systems
Variable-Speed Drives

Industrial Communication for


Automation and Drives

Catalog
IK PI

Low-Voltage
Controls and Distribution
SIRIUS, SENTRON, SIVACON

LV 1

Controls and Distribution


Technical Information
SIRIUS, SENTRON, SIVACON

LV 1 T

SIDAC Reactors and Filters

LV 60

SIVENT Fans

LV 65

SINAMICS G130 Drive Converter Chassis Units,


SINAMICS G150 Drive Converter Cabinet Units

D 11

SIVACON 8PS Busbar Trunking Systems

LV 70

SINAMICS G110 Inverter Chassis Units

D 11.1

Motion Control System SIMOTION

PM 10

SINAMICS GM150/SINAMICS SM150


Medium-Voltage Converters

D 12

SINAMICS S120 Drive Converter Systems

D 21.1

SINAMICS S150 Drive Converter Cabinet Units

D 21.3

Asynchronous Motors Standardline

D 86.1

Synchronous Motors with Permanent-Magnet


Technology, HT-direct

D 86.2

PDF: Indicators for panel mounting

MP 12

DC Motors

DA 12

SIREC Recorders and Accessories

MP 20

SIMOREG DC MASTER 6RA70 Digital Chassis


Converters

DA 21.1

SIPART, Controllers and Software

MP 31

SIWAREX Weighing Systems

WT 01

SIMOREG K 6RA22 Analog Chassis Converters

DA 21.2

Continuous Weighing and Process Protection

WT 02

SIMOREG DC MASTER 6RM70 Digital Converter


Cabinet Units

DA 22

Process Analytical Instruments

PA 01
PA 11

SIMOVERT PM Modular Converter Systems

DA 45

PDF: Process Analytics,


Components for the System Integration

SIEMOSYN Motors

DA 48

MICROMASTER 410/420/430/440 Inverters

DA 51.2

MICROMASTER 411/COMBIMASTER 411

DA 51.3

SIMOVERT MASTERDRIVES Vector Control

DA 65.10

SIMOVERT MASTERDRIVES Motion Control

DA 65.11

Synchronous and asynchronous servomotors for


SIMOVERT MASTERDRIVES

DA 65.3

SIMODRIVE 611 universal and POSMO

DA 65.4

Low-Voltage Three-Phase-Motors

Process Instrumentation and Analytics


Field Instruments for Process Automation
Measuring Instruments for Pressure,
Differential Pressure, Flow, Level and Temperature,
Positioners and Liquid Meters

FI 01

SIMATIC Industrial Automation Systems


SIMATIC PCS Process Control System

ST 45

Products for Totally Integrated Automation and


Micro Automation

ST 70

SIMATIC PCS 7 Process Control System

ST PCS 7

Add-ons for the SIMATIC PCS 7


Process Control System

ST PCS 7.1

Migration solutions with the SIMATIC PCS 7


Process Control System

ST PCS 7.2

IEC Squirrel-Cage Motors

D 81.1

pc-based Automation

ST PC

Automation Systems for Machine Tools SIMODRIVE

NC 60

SIMATIC Control Systems

ST DA

SIMATIC Sensors

FS 10

SIPOS Electric Actuators


Electric Rotary, Linear and Part-turn Actuators

MP 35

Electric Rotary Actuators for Nuclear Plants

MP 35.1/.2

Systems Engineering
Power supplies SITOP power

KT 10.1

System cabling SIMATIC TOP connect

KT 10.2

Main Spindle/Feed Motors


Converter Systems SIMODRIVE 611/POSMO
Automation Systems for Machine Tools SINAMICS

NC 61

Main Spindle/Feed Motors


Drive System SINAMICS S120
Drive and Control Components for Hoisting Equipment

HE 1

Electrical Installation Technology


PDF: ALPHA Small Distribution Boards and
Distribution Boards, Terminal Blocks

ET A1

PDF: ALPHA 8HP Molded-Plastic Distribution System

ET A3

BETA Low-Voltage Circuit Protection

ET B1

PDF: DELTA Switches and Socket Outlets

ET D1

GAMMA Building Controls

ET G1

Human Machine Interface Systems SIMATIC HMI

ST 80

System Solutions
Applications and Products for Industry are part of the
interactive catalog CA 01
TELEPERM M Process Control System
PDF: AS 488/TM automation systems

PLT 112

PDF: These catalogs are only available as pdf files.


A&D/3U/En 24.10.06

Seite 1

www.siemens.com/e-installation
Siemens AG
Automation and Drives
Electrical Installation Technology
Postfach 10 09 53
93009 REGENSBURG
GERMANY
w w w. s i e m e n s . c o m / e - i n s t a l l a t i o n
w w w. s i e m e n s . c o m / b et a

The information provided in this catalog contains descriptions or


characteristics of performance which in case of actual use do not always
apply as described or which may change as a result of further development
of the products. An obligation to provide the respective characteristics shall
only exist if expressly agreed in the terms of contract. Availability and
technical specifications are subject to change without notice.
All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for their own
purposes could violate the rights of the owners.

pdf only: (E86060-K8220-A101-A8-7600)

Subject to change without prior notice | Dispo 18301 | KG 1106 318 En / 703069 | Siemens AG 2006

ET_B1_2007_en.FH10 Fri Dec 01 11:30:58 2006