ROOF TOP AREA AVAILABLE FOR RAIN WATER HARVESTING FOR NIE COLLEGE

SL NO

DESCRIPTION

AREA IN Sqm

1 Ramaswamy Block
2 Golden Jubilee Block
Total

REMARKS

1585.66
2058.29
3643.95

AVERAGE
IN MYSORE
Reffering :- RAINFALL
Karnataka govt
bureau of economics and statistics department.

SL NO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

YEAR

1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
Average rainfall In Mysore

RAINFALL IN
mm
874.8
980.0
731.8
720.0
760.0
748.6
730.0
757.8
666.4
709.8
797.8
1010.0
782.6
882.8
776.2
1022.2
809.43
mm

TOTAL QUANTITY OF RAINWATER AVAILABLE FOR HARVESTING.

Quantity of water collection


Volume = Rooftop area x Average Rainfall
V= 3643.95 x 809.43/1000
V = 2949.50422875 cum
Harvestable water =
Harvestable water =

2949.5042 x 1000 x 0.8


2359603.383 Litres

Where,
0.8 is the runoff co efficient

TOTAL QUANTITY OF WATER REQUIRED FOR GOLDEN JUBILEE AND RAMASWAMY BLOCK

a)

Golden Jubilee block

2 Tanks of 50000 litres capacity are used except for drinking


50000 x 2 = 100000 liters / Day.

AS PER IS 1172:1993 INDIAN STANDARD CODE OF BASIC REQUIREMENTS FOR WATER SUPPLY PER
CONSUMPTION FOR OFFICE IS 40 litres/head/Day.
b)

Ramaswamy block

Considering 40 liters/head/Day
Total nos of staffs (Teaching & non teaching) = 36
40 x 36
1440 liters/ Day.
Total Quantity of water required per day = 100000 + 1440 =

TOTAL QUANTITY OF WATER REQUIRED ANNUALLY FOR GOLDEN JUBILEE BLOCK AND RA
= 101440 x 250 = 37025600 litres

Therefore Thirty Seven Lakhs Twenty Five Thousand Six Hundred Litres Of Water Required Ann

1585.66 1026784.61904
2058.29 1332833.33976

93750
183750

375000
1470000

PROVISION OF STORAGE
By considering 30% of harvested water i.e, 1842368 x 0.3 =
LOCATION AND CAPACITY OF SUMP
SUMP A:
Located near dome shaped building in Ramaswamy block
Size = 10 x 8 x 4
Capacity

320 cum
320000 litres

SUMP B:
Located near rear side of Golden Jubilee block
Size = 8 x 8 x 4
Capacity

256 cum
256000 litres

SUMP A
Location : Ramaswamy Block
Size : 10 x 8 x 4mt
Capacity : 320000 litres
DETAIL ESTIMATE
Item no

Description

1 Earth work excavation


2 C.C.Bed
3 First class brick masonry.
1. long walls
a) first footing
b) second footing
2. short walls
a) first footing
b) second footing
4 RCC Roof Slab
Deductions
Beam
Plastering
a) Interir surface
b) outer surface
5 Flooring

No

Length

(m) Breadth (m)

1
1

11
11

9
9

2
2

10.6
10.4

0.3
0.2

2
2
1
1
1

8.6
8.4
10.6
0.6
8.2

0.3
0.3
8.6
0.6
0.2

1
1
1

3.6
36.4
10

0.5

ABSTRACT ESTIMATE
Item no

Description

1 Earth work excavation


2 C.C.Bed
3 First class brick masonry.
RCC Roof Slab & beam 1:2:4,
4 including centring
5 Plastering
6 Flooring
7 M.S. cover plate
8 P.V.C pipe of A inch
9 Filter unit
10 T-bends
11 L-bows
12 Control Valve
Contractors profit &
contingencies etc..,

Unit
Cum
Cum
Cum
Cum
Sqm
Sqm
Sqm
Rmt
No
No
No
No

Quantity
376.2
29.7

Rate

IE COLLEGE

1026784.61904
1332818.76396

D RAMASWAMY BLOCK

used except for drinking

ENTS FOR WATER SUPPLY PER CAPITA

eaching) = 36

d per day = 100000 + 1440 =

101440 litres

EN JUBILEE BLOCK AND RAMASWAMY BLOCK


0 litres

ndred Litres Of Water Required Annually.


25360000
360000
25000000

360000

25000000

AGE

Y OF SUMP

552710.4 litres

3.95
57.4

E
Height (m)

Quantity

3.8
0.3

376.2
29.7

2
2

12.72
8.32

2
2
0.15
0.15
0.3

10.32
10.08
13.674
0.054
0.492

4
0.5
8

14.4
9.1
80

Remarks

ATE
Amount

Remarks