TECHNICAL SPECIFICATION OF EPC CONTRACT


FOR
218 MW COMBINED CYCLE POWER PROJECT
AT LIBREVILLE, GABON
Volume III Part B
Electrical

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 1 of 88

TABLEOFCONTENT

1 DATA SHEET TO BE FILLED BY BIDDER......................................................


1.1

GENERATOR.........................................................................................................

1.2

GENERATOR CIRCUIT BREAKER..........................................................................

1.3

ISOLATED PHASE BUS DUC.................................................................................

1.4

TRANSFORMERS.................................................................................................

1.5

HIGH MEDIUM VOLTAGE SWITCHGEAR...............................................................

1.6

LOW VOLTAGE SWITCHGEAR..............................................................................

1.7

MOTOR...............................................................................................................

1.8

DIESEL GENERATOR SET....................................................................................

1.9

DC BATTERY AND BATTERY CHARGER................................................................

1.10 UPS.....................................................................................................................
1.11 ILLUMINATION.....................................................................................................
1.12 SWITCHYARD......................................................................................................
1.13 CABLE................................................................................................................

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 2 of 88

DATA SHEET TO BE FILLED BY BIDDER

1.1

Generator

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 3 of 88

Sr.No.

Description

Unit

1.0

GENERATOR
PARAMETERS

1.1

Make, type and model & serial


number

1.2

Maximumcontinuousrating

Parameter

MAIN

Asperapprovedvendorlist.
MWMVA

70MW/82.5MVAforGasturbinegenerator.
80MW/95MVAforSteamturbinegenerator

1.3

Ratedterminalvoltage

1.4

Ratedcurrent

kV

11KV

Amps

4332AforGTG
4987AforSTG

1.5

Ratedfrequency

1.6

Ratedpowerfactor

1.7

Rotor current at Max. Continuous


rating(MCR0

Amps

Tobefurnishedduringdetailengg.

1.8

RotorvoltageatMCR

Volts

Tobefurnishedduringdetailengg

1.9

Maximum permissible variation


rangein:

a)

Ratedterminalvoltage

+/5%atratedpowerfactor

b)

Ratedfrequency

47.5Hzto51.5Hz.

c)

Combined permissible variation of


frequency and voltage (with
characteristic

curves)without
exceedingsafetemperaturerise.

+/10%

1.10

Synchronousspeed

rpm

3000

1.11

Numberofpoles

Number

a)

Lineterminalsbroughtout

Tobefurnishedduringdetailedengg.

b)

Parallelpathsperphase

Tobefurnishedduringdetailedengg.

b)

Neutralterminalsbroughtout

Tobefurnishedduringdetailedengg.

1.12

Typeofstatorwindingconnection

Rev. 0 06.03.12

Hz

50
0.85

DocumentNo:P.003080E490457

3Phase,Star

Page 4 of 88

Sr.No.

Description

Unit

Parameter

1.13

Degreeofprotectionoftheenclosure
forgeneratorinstalledIndoor

IP54

1.14

Detailsoffiredetection/protection
provided for the generator with
writeup,supplied

ByCO2injectioninternally

1.15

Generatorefficiencyat:

a)

100%load

Tobefurnishedduringdetailedengg.

b)

75%load

Tobefurnishedduringdetailedengg.

c)

50%load

Tobefurnishedduringdetailedengg.

1.16

Minimum guaranteed short circuit


ratio corresponding to maximum
capability

1.17

1.1

Designationformethodofcoolingas
perIS/IECstandards

Aircooled

1.18

RatedHydrogenpressure

Kg/cm2
(g)

NA

1.19

Basic impulse insulation withstand


voltage of stator winding with
respecttoearth

kV(peak)

Tobefurnishedduringdetailedengg.

1.20

Permissible unbalanced loading


subject to rated current not being
exceededinanyphase

a)

Maximumcontinuousnegativephase
sequencecurrentI2

b)

MaximumvalueofI22tFortransient
operation under system fault
conditions(wheretisinseconds)

1.21

Maximum permissible capacitive


loadingatratedload&voltage

MVAR

63.2

1.22

Generator short time overload


capability

Tobefurnishedduringdetailedengg.

1.23

Generatoroverspeedcapability

Tobefurnishedduringdetailedengg.

Rev. 0 06.03.12

Tobefurnishedduringdetailedengg.

10%

Tobefurnishedduringdetailedengg.

DocumentNo:P.003080E490457

Page 5 of 88

Sr.No.

Rev. 0 06.03.12

Description

Unit

DocumentNo:P.003080E490457

Parameter

Page 6 of 88

Sr.No.

Description

Unit

Parameter

2.0

GENERATORPARAMETERS

2.1

Generator reactances in percent at


rated kV and MVA, both saturated
andunsaturated

2.1.1

Direct axis synchronous reactance


Xd

Tobefurnishedduringdetailedengg.

2.1.2

Quadrature axis synchronous


reactanceXq

Tobefurnishedduringdetailedengg.

2.1.3

DirectaxistransientreactanceXd

Tobefurnishedduringdetailedengg.

2.1.4

Quadrature axis transient reactance


Xq

Tobefurnishedduringdetailedengg.

2.1.5

Direct axis subtransient reactance


Xd

Tobefurnishedduringdetailedengg.

2.1.6

Quadrature axis subtransient


reactanceXq

Tobefurnishedduringdetailedengg.

2.1.7

Negative phase sequence reactance


X2

Tobefurnishedduringdetailedengg.

2.1.8

ZerophasesequencereactanceXo

Tobefurnishedduringdetailedengg.

2.1.9

Potierreactance

Tobefurnishedduringdetailedengg.

2.1.10

Waveformfactor

2.1.11

Telephoneinterferencefactor

2.2

Tobefurnishedduringdetailedengg.

Tobefurnishedduringdetailedengg.
%

Tobefurnishedduringdetailedengg.

Permissible tolerance on all


guaranteedreactancevalues

%(+)

Tobefurnishedduringdetailedengg.

2.3

Synchronousimpedance

Ohms

Tobefurnishedduringdetailedengg.

2.4

Transientopencircuittimeconstant
T

msec.

Tobefurnishedduringdetailedengg.

2.5

Effective winding capacitance to


earth

a)

Perphase

Rev. 0 06.03.12

Tobefurnishedduringdetailedengg.
F

DocumentNo:P.003080E490457

Tobefurnishedduringdetailedengg.

Page 7 of 88

Sr.No.

Description

Unit

Parameter

Tobefurnishedduringdetailedengg.

b)

Allphaseconnectedtogether

3.0

GENERATOR TEMPERATURE
RISES

3.1

Guaranteed temperature rise over


max. inlet cooling air / Hydrogen
temperatureatratedload

a)

Statorwindings

b)

Statorcore

i)

Incontactwithinsulatedwinding

ii)

Notincontactwithinsulatedwinding

c)

Rotorwindings

3.2

Maximumcoolinginletair/
hydrogentemperaturecorresponding
to the highest cooling water
temperatureatratedload

3.3

Maximumtemperaturerise

a)

Collectorrings

b)

GeneratorBearings

Tobefurnishedduringdetailedengg.

Unit

Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.

Tobefurnishedduringdetailedengg.
0

Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.

Turbineend

Tobefurnishedduringdetailedengg.

Exciterend

Tobefurnishedduringdetailedengg.

c)

Oil inlet temperature at highest


bearingcoolingwatertemperature

4.0

GENERATORLOSSES

4.1

Generatorlosses(curvesforvarious
lossesvsloadatdifferent hydrogen
pressureshallbeenclosed)

a)

Ironlossatnoload

kW

b)

Ironlossatfullload

kW

Rev. 0 06.03.12

Tobefurnishedduringdetailedengg.

DocumentNo:P.003080E490457

Tobefurnishedduringdetailedengg.

Tobefinalizedlater
Tobefinalizedlater

Page 8 of 88

Sr.No.

Description

Unit

c)

Strayloss

kW

d)

Statorcopperlossatfullload

kW

e)

RotorcopperlossatNoload

kW

f)

Rotorcopperlossatfullload

kW

g)

Frictionandwindagelosses

kW

h)

Mechanicallossesincludingbearing
losses

kW

i)

Totalgeneratorlosses

kW

5.0

GENERATORSTATORCORE
PARTICULARS

5.1

Statorcoreouterdiameter

mm

5.2

Statorcorelength

mm

5.3

Airgap

mm

5.4

Fluxdensitiesinvariouspartsofthe
stator core under noload and full
load

5.4.1

Airgap

5.4.2

Statorcore

5.4.3

Statorteeth

5.4.4

Rotorcore

5.4.5

Rotorteeth

6.0

TYPEANDCONNECTIONOF
STATORWINDINGS

6.1

Total No. of stator bars (top &


bottom)

a)

@25degC

ohms

b)

@75degC

ohms

Rev. 0 06.03.12

Parameter
Tobefinalizedlater
Tobefinalizedlater
Tobefinalizedlater
Tobefinalizedlater
Tobefinalizedlater
Tobefinalizedlater
Tobefinalizedlater

Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
NOLOAD/FULLLOAD

No.

DocumentNo:P.003080E490457

Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.

Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.

Page 9 of 88

Sr.No.
7.0

Description

Unit

Parameter

ROTORWINDING
PARTICULARS

7.1

Classoffieldwindinginsulation

CLASSF

7.2

Rotorwindingresistance

a)

@25deg.C

Ohms

b)

@75deg.C

Ohms

8.0

GENERATOR
MISCELLANEOUS
PARTICULARS

8.1

Noise level in free field / semi


reverberantconditions

a)

Noload(indicatedistancealso)

dB(A)

b)

Onload(indicatedistancealso)

dB(A)

8.2

Directionofrotationofgeneratoras
seenfromturbineend

8.3

Vibrationamplitude(peaktopeak)

a)

Statorcorevibration

micro
meter

b)

Statorcorenaturalfrequency

c/s

c)

Statorframevibration

micro
meter

d)

Rotorvibration

micro
meter

e)

Bearingvibration

micro
meter

8.4

No. and type of RTDs /


thermocouplesprovided

8.4.1

Statorwinding

No.

Aspersystemrequirement

8.4.2

Statorcore

No.

Aspersystemrequirement

Rev. 0 06.03.12

Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.

DocumentNo:P.003080E490457

Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.
Tobefurnishedduringdetailedengg.

Page 10 of 88

Sr.No.

Description

8.4.3

Rotorwinding

8.4.4

Bearings

a)

Turbineend

Unit
No.

Parameter
Aspersystemrequirement
Aspersystemrequirement

No.

1No.forGasturbineGenerator
1No.forSteamturbineGenerator

b)

Exciterend

No.

1No.forGasturbineGenerator
1No.forSteamturbineGenerator

9.0

EXCITATIONSYSTEMS

9.1

ExcitationSystemParameter

9.1.1

Typeofexcitationsystemoffered

a)

Nominalfieldvoltage

Volts

b)

Maximumfieldvoltage

Volts

Tobefurnishedduringdetailedengg.*

c)

Ceiling/Fieldforcingvoltage

Volts

Asindicated

d)

Minimum and maximum field


currentwithgeneratorati)Noload
ii)generatorat100%load

Amps

Tobefurnishedduringdetailedengg.*

9.1.2

Generatorfieldcharacteristics

a)

Withgeneratoratnoloadandrated
voltage

VoltAmps

b)

Withgeneratorat125%ofMCR

VoltAmps

c)

With generator at rated load and


ratedVoltageat:

i)

Ratedp.f

VoltAmps

ii)

Unityp.f.

VoltAmps

9.2

Make & type of online diode


monitoringsystem

Rev. 0 06.03.12

STATIC

Brushless/Static

313.7VforGasturbineGenerator250.1V.forStea
turbineGenerator

DocumentNo:P.003080E490457

Page 11 of 88

Sr.No.

Description

9.3

Brushless/StaticExcitationSystem

9.3.1

Ratings:
(a)Continuousmax.Output

Unit

Parameter
STATIC

kW

212.2KWforGasturbineGenerator.

175.7KWforSteamturbineGenerator
(b)Ratedvoltage

Volts

(c)Ratedcurrent

Amps

313.7VforGasturbineGenerator250.1V.forStea
turbineGenerator
676.1AforGasturbineGenerator
702.3AforSteamturbineGenerator

9.3.1.2

(d)Ratedfullloadspeed

rpm

(e)Ratedfrequency

Hz

(f)Ceilingvoltage

Volts

(g)Responseratio

(h) Expected peak current for


terminalshortcircuit

Amps

(i)

kW/sec

Shorttimecapacity

Winding(Stator/Rotor):
(a) Type

(b) Classofinsulation
9.3.1.3

Typeofcoolingprovided

9.3.1.4

Degreeofprotectionfortheexciter
enclosure

9.3.1.5

Typeofdrive

9.3.2

Auxiliaryexciterpermanentmagnet
generator(PMG)

Rev. 0 06.03.12

*
*
*

DocumentNo:P.003080E490457

Page 12 of 88

Sr.No.
9.3.2.1

Description

Unit

Ratings:

(a)

Continuousmaximumoutput output

kW

Parameter

Continu
ous
maximu
m

output
(b)
Rated
voltage

Ratedvoltage

Volts

(c)
Rated
current

Ratedcurrent

Amps

(d)
Rated
frequen
cy

Ratedfrequency

(e)
Short
time
capacity

Shorttimecapacity

9.3.2.2

Winding:

Hz

kVA/sec

(a)

Type

(b)

ClassofInsulation

*
*

9.3.2.3

Typeofcoolingprovided

9.3.2.4

Degree of protection for the PMG


enclosure

9.3.3

RotatingDiodes&fuses

9.3.3.1

Makeandtypeofdiodes

9.3.3.2

Totalnumberofdiodes

No.

9.3.3.3

Numberofparallelpathsperbridge

No.

Rev. 0 06.03.12

*
*

DocumentNo:P.003080E490457

*
*

Page 13 of 88

Sr.No.

Description

Unit

Parameter

arm

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 14 of 88

Sr.No.
9.3.3.4

Description
No.ofparallelpathsperbridgearm
necessaryforgeneratorMCR

Unit
No.

9.3.3.5

Method of cooling adopted for


diodes

9.3.3.6

Type of protection provided for


rotatingdiodes

9.3.3.7

Ceilingoutputvoltage/current

9.3.4

Excitationsystemcooling

9.3.4.1

AirtoWaterCooler

V/A

(a)

Type

(b)

No.ofcoolersand
capacitypercooler

Parameter
*

9.4

VoltageRegulatorandAccessories

9.4.1a)

Type

9.4.1b)

Quantity

9.4.2

No.ofauto&manualchannels

9.4.3

Guaranteedsensitivity

9.4.4

Rangeofvoltagelevelsetting:

9.4.5

auto

manual

Thyristorcontrolleddualchannel

Whether following limiters and


compensatorsprovided
(a)Minimumexcitationlimiter
(b)Maximumstatorcurrentlimiter
(c)Maximumexcitationlimiter
(d)Maximumrotorcurrentlimiter

Rev. 0 06.03.12

DocumentNo:P.003080E490457

*
*
*
*

Page 15 of 88

Sr.No.

Description

Unit

(e)Volts/Hz.Limiter

(f)Reactivedropcompensator

(g)Loadanglelimiter

(h)Powersystemstabiliser
(j)

9.4.6

Parameter
*

PowerfactorRegulator

Whetherfollowingfeatures/monitors
provided
*

(i)Autosynchroniser

(ii) Field earth fault monitor 2


Stagebasedoninjectionprinciple
(iii)Onlineshaftleakage

current/voltagemonitoring
device,withsamelocation
(iv)Detailsofanyother

features/devicesprovided
9.4.7

Criticalspeed

(1st,2nd,3rdvalues)
9.4.8

Type of cooling for field control


cubicles
Natural/Forced

9.5

MainExciterFieldBreaker

9.5.1

Type

9.5.2

Currentrating

Amps

9.5.3

Voltagerating

Volts

9.5.4

Rupturingcapacity

Rev. 0 06.03.12

kA

DocumentNo:P.003080E490457

Page 16 of 88

Sr.No.

Description

Unit

9.5.5

Makingcapacity

9.5.6i)

Typeofoperatingmechanism

ii)

OperatingVoltage

9.6
9.6.1

Parameter

kAp

MiscellaneousDetailsOf
ExcitationSystem
Whether the following accessories/
schemesprovided
(a) Fielddischargeresistor
(b) Field current measurement
facility
(c) Field and exciter earth fault
protectionscheme
NA

10.0

HYDROGEN
SYSTEM

10.1

Hydrogen

10.1.1

Type & total number of coolers


provided

Nos.

10.1.2

Number of coolers required in


simultaneoususeatMCR

Nos.

10.1.3

Maximum Generator Loading with


onecooleroutofservice

MVA

10.1.4

Cooling water maximum inlet


temperature at highest ambient air
temperature

10.1.5

Inlet cooling air / hydrogen


temperature at above cooling water
temperature

10.1.6

Typeandmaterialoftubes

10.1.7

Tubesheetmaterial

Rev. 0 06.03.12

COOLING

NA

DocumentNo:P.003080E490457

NA

NA

NA

NA

NA

NA
NA

Page 17 of 88

Sr.No.

Description

Unit

10.1.8

Waterboxandshellmaterial

10.2

Hydrogengas/airsystem

10.2.1

Max. Inlet / outlet temp. of


hydrogen/air

11.0

SEALOILSYSTEM

11.1

SealOilH2side

11.1.1

No.ofpumps

11.2

SealoilAirside

11.2.1

No.ofpumps

Parameter
NA
NA

NA

Tobefurnishedduringdetailengineering

No.

(a)

AC

No.

(b)

DC

No.

12.0

EXCITATION
COOLING

12.1

TypeofcoolingAir/Water

12.1.1

Ifair,forcedornatural

SYSTEM

(a)RectifierTransformerpanel

(b)Thyristorpanels
(c)AVRpanels
(d) Otherpanels
12.1.2

If forced, No. of fans each 100%


duty.

12.1.3

Whether automatic changeover of


fansprovidedornot?

12.1.4

Whether standby fan provided to


achieve100%duty

Rev. 0 06.03.12

Nos.

*
*

Yes/No

DocumentNo:P.003080E490457

Page 18 of 88

Sr.No.

Description

Unit

Parameter

13.0

GENERATOR CAPABILITY
ANDOTHERMISCELLANEOUS
DATA/DIAGRAMS

13.1

Capability of generator with and


without AVR (furnish capability
diagram)

13.2

Open circuit and short circuit


characteristic (calculated) curves
enclosed

Yes/No

13.3

CurrentandkVAratingofgenerator
atvoltageabove100%

Amps/
kVA

13.4

Overload capacity of generator for


1,2,3,4,5,6,10,15and60sec.

MVA

13.5

Value of voltage rise of generator


withandwithoutAVRincircuit at
fullloadthrowoff

p.u

13.6

The maximum continuous voltage /


frequency at which the generator
couldoperate,particularlyduringrun
up or after a load throwoff with
AVRonmanualcontrol

Volts/Hz

13.7

Themaximumpossiblepeakvoltage
which will appear across the two
ends of the generator field winding
afterafullloadthrowoff

Volts

13.8

Recommended mode of generator


statorneutralearthingandparticulars
ofsurgecapacitorforgenerator.

13.9

Tests

13.9.1

All type and routine tests will be


carriedoutasperrelevantNational/
InternationalStandards.

Yes/No

13.9.2

Runningtrialswillbeconductedin
theshopwiththegenerator,exciter
and AVR connected up and
combinedasaunitonthetestbed

Yes/No

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 19 of 88

1.2

Generator Circuit breaker

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 20 of 88

Sr.
No.
1

Description

Unit

Parameter

Manufacturer

Standards

Type

RatedVoltage

Ratedfrequency
Ratedshorttimewithstandcurrentfor

kV

Hz

kA
*

1sec.withbreakerashousedinthe
panel

Makingcurrent(peak)

Dynamicovercurrentrating

BasicInsulationLvel
Oneminutepowerfrequencywithstand

kA
kA

kV rms

voltage
Impulsewithstandvoltage
10

Temperaturerise

a)

Maximumtemp.riseoverambient

kV peak

specified
b)

Ambienttemperature

11

Interchangeabilityofsimilarequipment

12

Type&no.ofphases

13

Arrangementforisolatingbreakerfor
maintenanceprovided

14

Standardapplicable

15

Whetherantipumpingdeviceprovided

16

Rev. 0 06.03.12

Whethercontrolcircuitrysuitablefor

DocumentNo:P.003080E490457

Page 21 of 88

Sr.
No.

Description

Unit

Parameter

monitoringofclosing&tripping
circuits

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 22 of 88

Sr.
No.
17
a)

Description

Unit

Maximumdesignvoltage

Parameter
*

Symmetricalbreakingcapacity(inkA
atratedvoltage)

b)

Asymmetricalbreakingcapacityfor
variousbreakersatratedvoltage
a)Ratedcontinuouscurrentratingfor

18

variousbreakersandcorresponding
temperature.
b)Ratedcontinuouscurrentratingfor
variousbreakersatthespecified
ambienttemperature.

19

No.ofbreaks/pole

20

Typeofmaterialofcontacts

21

Whethercontactssilverplatedand
thicknessofplating

22

Whetherbreakerdesignedtocloseand
latchformakingcurrentrelease

23

Weathertripfreeorfixedtrip

24

Typeofclosingmechanism

25

Normalvoltageofclosing/tripping
mechanism/springchargingmotor

26

Allowablevibrationofvoltagefor
above

27

Powerrequiredfornormalvoltagefor

a)

Tripcoil

b)

Closingcoil

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 23 of 88

Sr.
No.
c)
28

Description

Unit

Parameter

Springchargingmotor
Weightofcircuitbreakerwitharc
extinguishingmedium

29

Openingtimeincycles

30

Makingtimeincycles

31

Openingtimeat

a)

10%Current

b)

50%Current

c)

100%Current

32

Dutycycle
Weather6Nos.adjustable(eitherin
NOorNC)auxiliarycontactsoverand

33

abovethoserequiredforbreaker
operation/annunciationhavebeen
providedornot.

34

Currentcarryingcapacityofauxiliary
switches.

35

No.ofbreakeroperationsnecessary
beforeinspection&maintenanceof

a)

Switchingratedload

b)

Faultat100%capacity

c)

Faultsat50%capacity

d)

Makingunderfaultconditions

36

Accessibilityoflineconnection
Whetherterminalssuitablewith

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 24 of 88

Sr.
No.

Description

Unit

Parameter

isolatedphasebusducts

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 25 of 88

Sr.
No.

Description

Unit

Parameter

Heatdissipationatnormalcurrent
(KW)
Minimumvalueforpickupcurrentfor
i)Closingcoil
ii)Trippingcoil
37

Schematiccontroldiagramofcircuit
breakerenclosed

38

Arethefollowingitemssuppliedwith
thebreakerenclosure

39

Currenttransformers(CTs)

a)

No.ofCTsprovidedwithcoreson
generatorsideofbreaker

b)

TechnicalparticularsofC.Ts

40

Voltagetransformers(VTs)

a)

No.ofVTsprovidedwithcoreson
generatorsideofbreaker
No.ofVTsprovidedwithcoresonL.V

b)

sideGentransformer(GT)sideof
breaker

c)

TechnicalparticularsofV.Ts

41

SurgeCapacitor

a)

No.ofSurgeCapacitorprovidedon
generatorsideofbreaker

b)

No.ofSurgeCapacitorprovidedon
L.VsideGTsideofbreaker

c)

Rev. 0 06.03.12

TechnicalparticularsofSurge

DocumentNo:P.003080E490457

Page 26 of 88

Sr.
No.

Description

Unit

Parameter

Capacitor
42

SurgeArrestor

a)

No.ofSurgeArrestor

b)

Technicalparticulars

42

Disconnectorswitchbetweenbreaker
&LVsideofGT

a)

No.

b)

Technicalparticulars

43

EarthingSwitches(ES)

a)

No.

b)

Technicalparticulars

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 27 of 88

1.3

Isolated Phase Bus Duct

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 28 of 88

Sr.
No.
1.

Make

2.

Applicablestandard

3.

Voltageratingofbusduct

KV

4.

Ratedcurrentofmainbusduct

KA

5.

Threesecondshortcircuitcurrent
rating

a)

Main

KA

b)

Tapoff

KA

6.

MomentaryOvercurrent

a)

Main

KA

b)

Tapoff

KA

7.

Degreeofprotection

8.

Thicknessofthe

a)

Conductor

mm

b)

Enclosure

mm

9.

Lossesinthe

a)

Conductor

KW/m

b)

Enclosure

KW/m

10.

Typeofcooling

11.

Disconnectinglinks

12.

Materialofconductor

13.

Materialofenclosure

14.

Temperature rise while operating at


rated continuous current at ambient
temp.of500C

a)

Conductor(hotspot)

Rev. 0 06.03.12

Description

Unit

Parameter
*
*

DocumentNo:P.003080E490457

Page 29 of 88

Sr.
No.
b)

Description

Unit

Enclosure(hotspot)

Parameter
*

15.

Creepage distance for Insulators &


bushing

16.

Voltagetransformer

a)

Accuracyclass

b)

Ratedvoltagefactor

17.

Typeofinsulationforcurrent
transformerandneutralgrounding
transformer.

18.

Dutyrating

a)

Neutralgroundingtransformer

b)

Neutralgroundingresistor

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 30 of 88

1.4

Gas Turbine Generator Transformers

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 31 of 88

Sr.
No.

Description

Unit

Parameter

Transformerapplications

Type&make

Aspervendorlist

Applicablestandard

AsperIS/EDFstd.

Quantity

No(s).

Fullloadrating(ONAN/ONAF)

MVA

90

Ratingofeachwindings

MVA

72/90

RatingnoloadvoltageHV/LV

kV

11/95

Ratingofdifferentcoolingmethods

Impedancevalue

12

10

Ratedfrequency

Hz

50

11

Winding connection of different


windingsandvectorgroup

12

SystemEarthing(HVLV)

13

Typeoftapchangeroffcircuit/onload

14

Fullpowertappingprovided

15

Type of voltage variation


(CFVV/VFVV/CBVV)

16

Overfluxingcapability

17

Winding insulation type uniformly or


nonuniformlyinsulated

17.1

HV

NonUniform

17.2

LV

Uniform

Rev. 0 06.03.12

Stepup

ONAN/ONAF

Ynd11
HV
OCTC
Yes/No

Yes
CFVV

For
Over fluxing Factor 1.1 :
Continuous
1.25 : 60 Sec
1.4 : 10 Sec.

UniformonLVside&nonUniformonHVside

DocumentNo:P.003080E490457

Page 32 of 88

Sr.
No.

Description

18

Highestsystemvoltage

19

Powerfrequencywithstandvoltageof
winding

19.1

Unit

Parameter

kV

95

HV

kVrms

200

19.2

LV

kVrms

70

20

Standard rated lightning impulse


withstandvoltage

20.1

HV

kVp

650

20.2

LV

kVp

170

21

Maximumtemperatureriseatfullload
with100%coolers:

21.1

Oil

oC

40

21.2

Winding

oC

45

22

Bushingparticulars.

22.1

Applicablestandardforbushing

22.2

Clearance in air HV/LV/Neutral


(betweenphasesandphasetoearth)

22.2.
1

HV(PP)

mm

Aspertechspec

22.2.
2

HV(PE)

mm

Aspertechspec

22.2.
3

LV(PP)

mm

22.2.
4

HVN

mm

22.3

Quantityofoilinoilfilledbushing

litre

22.4

Creepagedistance

mm/kV

Rev. 0 06.03.12

IS-2099
Aspertechspec

Aspertechspec
Aspertechspec

Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

31

Page 33 of 88

Sr.
No.

Description

Unit

Parameter

23

Noloadlossat100%ratedvoltage&
frequency

kW

24

Loadlossatratedcurrentwith75deg
C

kW

25

Coolerlossatfullload

kW

26

Efficiency(0.85Pf)

26.1

Fullload

26.2

75%load

27

Noloadcurrent

A(approx)

28

Totalestimatedweight

Kgs

29

OCTC/OLTC

29.1

Make

29.2

RatedVoltage

Volts

110KV

29.3

RatedCurrent

Amps

800

29.4

No.ofsteps

29.5

StepVoltage

Volts

29.6

Time of operation from one step to


otherforAuto/manualmode

Sec.

30

Typeofaxialandradialcoilsupports
forHV/LV

31

No. of cooler banks and capacity of


eachcoolerbank

32

GuaranteedNoloadcurrent

31.1

WhenexcitedfromLVsideat 100%
and110%ratedvoltage

Amps

33

Max. Flux density when rated and


110%ratedvoltage

Wb/m2

Rev. 0 06.03.12

5.6(allfansrunning)

99.7

TobefurnishedduringDE
OCTC
Asperapprovedvendorlistprovided

13
+/2.5%atastepof2.5%
57

Asper2X50%requirement
*

DocumentNo:P.003080E490457

*
1.7

Page 34 of 88

Sr.
No.

Description

Unit

Parameter

34

Vacuum withstand capability main


tank,radiatorsandaccessories

35

Weight

35.1

Core

kg

35.2

Netcopperwt.HV/LV

kg

do

35.3

Oil

kg

do

35.4

Tank,coolers&fittings

kg

do

35.5

Total

kg

do

35.6

Untankingweight

kg

do

36

Coolingfans,oilpumpsrating

kW

do

37

Capabilityoftransformertoremainin
operation from hot conditions after
failureofforcedcoolingwithfullload

minutes

do

38

Online dissolved Gas Analyser


Provided?

Yes/No

no

39

Fibre optic based direct hot spot


temperature measurement System
Provided?

Yes/No

no

Rev. 0 06.03.12

mmofHg

Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

Page 35 of 88

1.5

Steam Turbine Generator Transformers

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 36 of 88

Sr.
No.

Description

Unit

Parameter

Transformerapplications

Type&make

Aspervendorlist

Applicablestandard

AsperIS/EDFstd.

Quantity

No(s).

Fullloadrating(ONAN/ONAF)

MVA

100

Ratingofeachwindings

MVA

80/100

RatingnoloadvoltageHV/LV

kV

11/95

Ratingofdifferentcoolingmethods

Impedancevalue

12

10

Ratedfrequency

Hz

50

11

Winding connection of different


windingsandvectorgroup

12

SystemEarthing(HVLV)

13

Typeoftapchangeroffcircuit/onload

14

Fullpowertappingprovided

15

Type of voltage variation


(CFVV/VFVV/CBVV)

16

Overfluxingcapability

17

Winding insulation type uniformly or


nonuniformlyinsulated

17.1

HV

NonUniform

17.2

LV

Uniform

Rev. 0 06.03.12

Stepup

ONAN/ONAF

Ynd11
HV
OCTC
Yes/No

Yes
CFVV

For
Over fluxing Factor 1.1 :
Continuous
1.25 : 60 Sec
1.4 : 10 Sec.

DocumentNo:P.003080E490457

Page 37 of 88

Sr.
No.

Description

18

Highestsystemvoltage

19

Powerfrequencywithstandvoltageof
winding

19.1

Unit

Parameter

kV

95

HV

kVrms

200

19.2

LV

kVrms

70

20

Standard rated lightning impulse


withstandvoltage

20.1

HV

kVp

650

20.2

LV

kVp

170

21

Maximumtemperatureriseatfullload
with100%coolers:

21.1

Oil

oC

40

21.2

Winding

oC

45

22

Bushingparticulars.

22.1

Applicablestandardforbushing

22.2

Clearance in air HV/LV/Neutral


(betweenphasesandphasetoearth)

22.2.
1

HV(PP)

mm

Aspertechspec

22.2.
2

HV(PE)

mm

Aspertechspec

22.2.
3

LV(PP)

mm

22.2.
4

HVN

mm

22.3

Quantityofoilinoilfilledbushing

litre

22.4

Creepagedistance

mm/kV

Rev. 0 06.03.12

IS-2099
Aspertechspec

Aspertechspec
Aspertechspec

Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

31

Page 38 of 88

Sr.
No.

Description

Unit

Parameter

23

Noloadlossat100%ratedvoltage&
frequency

kW

24

Loadlossatratedcurrentwith75deg
C

kW

25

Coolerlossatfullload

kW

26

Efficiency(0.85Pf)

26.1

Fullload

26.2

75%load

27

Noloadcurrent

A(approx)

28

Totalestimatedweight

Kgs

29

OCTC/OLTC

29.1

Make

29.2

RatedVoltage

Volts

110

29.3

RatedCurrent

Amps

800

29.4

No.ofsteps

29.5

StepVoltage

Volts

29.6

Time of operation from one step to


otherforAuto/manualmode

Sec.

30

Typeofaxialandradialcoilsupports
forHV/LV

31

No. of cooler banks and capacity of


eachcoolerbank

2X50%asperrequirement

32

GuaranteedNoloadcurrent

31.1

WhenexcitedfromLVsideat 100%
and110%ratedvoltage

Amps

33

Max. Flux density when rated and


110%ratedvoltage

Wb/m2

Rev. 0 06.03.12

5.6

99.75

OCTC
Asperapprovedvendorlistprovided

13
+/2.5%atastepof2.5%
57

DocumentNo:P.003080E490457

*
1.71

Page 39 of 88

Sr.
No.

Description

Unit

Parameter

34

Vacuum withstand capability main


tank,radiatorsandaccessories

35

Weight

35.1

Core

kg

35.2

Netcopperwt.HV/LV

kg

do

35.3

Oil

kg

do

35.4

Tank,coolers&fittings

kg

do

35.5

Total

kg

do

35.6

Untankingweight

kg

do

36

Coolingfans,oilpumpsrating

kW

do

37

Capabilityoftransformertoremainin
operation from hot conditions after
failureofforcedcoolingwithfullload

minutes

do

38

Online dissolved Gas Analyser


Provided?

Yes/No

no

39

Fibre optic based direct hot spot


temperature measurement System
Provided?

Yes/No

no

Rev. 0 06.03.12

mmofHg

Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

Page 40 of 88

1.6 Distribution Transformers

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 41 of 88

Sr.
No.

Description

Unit

Parameter

Transformerapplications

Type&make

Applicablestandard

Quantity

No(s).

Fullloadrating(ONAN/ONAF)

MVA

125

Ratingofeachwindings

MVA

104/125

RatingnoloadvoltageHV/LV

kV

Ratingofdifferentcoolingmethods

Impedancevalue

15

10

Ratedfrequency

Hz

50

11

Winding connection of different


windingsandvectorgroup

12

SystemEarthing(HVLV)

13

Typeoftapchangeroffcircuit/onload

14

Fullpowertappingprovided

15

Type of voltage variation


(CFVV/VFVV/CBVV)

16

Overfluxingcapability

17

Winding insulation type uniformly or


nonuniformlyinsulated

17.1

HV

NonUniform

17.2

LV

Uniform

Rev. 0 06.03.12

Distribution
Aspervendorlist
*

90/33
ONAN/ONAF

YNYnO
Both
OLTC
Yes/No

Yes
CFVV

For
Over fluxing Factor 1.1 :
Continuous
1.25 : 60 Sec
1.4 : 10 Sec.

DocumentNo:P.003080E490457

Page 42 of 88

Sr.
No.

Description

18

Highestsystemvoltage

19

Powerfrequencywithstandvoltageof
winding

19.1

Unit

Parameter

kV

90

HV

kVrms

185

19.2

LV

kVrms

70

20

Standard rated lightning impulse


withstandvoltage

20.1

HV

kVp

650

20.2

LV

kVp

200

21

Maximumtemperatureriseatfullload
with100%coolers:

21.1

Oil

oC

40

21.2

Winding

oC

45

22

Bushingparticulars.

22.1

Applicablestandardforbushing

22.2

Clearance in air HV/LV/Neutral


(betweenphasesandphasetoearth)

22.2.
1

HV(PP)

mm

Aspertechspec

22.2.
2

HV(PE)

mm

Aspertechspec

22.2.
3

LV(PP)

mm

22.2.
4

HVN

mm

22.3

Quantityofoilinoilfilledbushing

litre

22.4

Creepagedistance

mm/kV

Rev. 0 06.03.12

IS-2099
Aspertechspec

Aspertechspec
Aspertechspec

Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

31

Page 43 of 88

Sr.
No.

Description

Unit

Parameter

23

Noloadlossat100%ratedvoltage&
frequency

kW

24

Loadlossatratedcurrentwith75deg
C

kW

25

Coolerlossatfullload

kW

26

Efficiency(0.85Pf)

26.1

Fullload

26.2

75%load

27

Noloadcurrent

A(approx)

28

Totalestimatedweight

Kgs

29

OCTC/OLTC

29.1

Make

29.2

RatedVoltage

Volts

110KV

29.3

RatedCurrent

Amps

800

29.4

No.ofsteps

29.5

StepVoltage

Volts

29.6

Time of operation from one step to


otherforAuto/manualmode

Sec.

30

Typeofaxialandradialcoilsupports
forHV/LV

31

No. of cooler banks and capacity of


eachcoolerbank

2X50%asperrequirement

32

GuaranteedNoloadcurrent

31.1

WhenexcitedfromLVsideat 100%
and110%ratedvoltage

Amps

33

Max. Flux density when rated and


110%ratedvoltage

Wb/m2

Rev. 0 06.03.12

OCTC
Asperapprovedvendorlistprovided

13
+/2.5%atastepof2.5%
57

DocumentNo:P.003080E490457

*
1.71

Page 44 of 88

Sr.
No.

Description

Unit

Parameter

34

Vacuum withstand capability main


tank,radiatorsandaccessories

35

Weight

35.1

Core

kg

35.2

Netcopperwt.HV/LV

kg

do

35.3

Oil

kg

do

35.4

Tank,coolers&fittings

kg

do

35.5

Total

kg

do

35.6

Untankingweight

kg

do

36

Coolingfans,oilpumpsrating

kW

do

37

Capabilityoftransformertoremainin
operation from hot conditions after
failureofforcedcoolingwithfullload

minutes

do

38

Online dissolved Gas Analyser


Provided?

Yes/No

no

39

Fibre optic based direct hot spot


temperature measurement System
Provided?

Yes/No

no

Rev. 0 06.03.12

mmofHg

Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

Page 45 of 88

1.7 Unit Auxiliary Transformer

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 46 of 88

Sr.No.

Description

Unit

Parameter

Transformerapplications

Type&make

Applicablestandard

Quantity

No(s).

Fullloadrating(ONAN/ONAF)

MVA

10

Ratingofeachwindings

MVA

10

RatingnoloadvoltageHV/LV

kV

Ratingofdifferentcoolingmethods

Impedancevalue

10

Ratedfrequency

Hz

50

11

Winding connection of different


windingsandvectorgroup

12

SystemEarthing(HVLV)

13

Typeoftapchangeroffcircuit/onload

14

Fullpowertappingprovided

15

Type of voltage variation


(CFVV/VFVV/CBVV)

16

Overfluxingcapability

17

Winding insulation type uniformly or


nonuniformlyinsulated

17.1

HV

NonUniform

17.2

LV

Uniform

18

Highestsystemvoltage

Rev. 0 06.03.12

Auxiliary
Aspervendorlist
AsperIS/EDFstandards

11/6.9
ONAN/ONAF

Dyn1
LV
OLTC
Yes/No

Yes
CFVV

For
Over fluxing Factor 1.1 :
Continuous
1.25 : 60 Sec
1.4 : 10 Sec.

kV

DocumentNo:P.003080E490457

12

Page 47 of 88

Sr.No.

Description

Unit

Parameter

19

Powerfrequencywithstandvoltageof
winding

19.1

HV

kVrms

20

19.2

LV

kVrms

20

Standard rated lightning impulse


withstandvoltage

20.1

HV

kVp

50

20.2

LV

kVp

24

21

Maximumtemperatureriseatfullload
with100%coolers:

21.1

Oil

oC

55

21.2

Winding

oC

45

22

Bushingparticulars.

22.1

Applicablestandardforbushing

22.2

Clearance in air HV/LV/Neutral


(betweenphasesandphasetoearth)

22.2.1

HV(PP)

mm

AsperIEC/EDFspec

22.2.2

HV(PE)

mm

AsperIEC/EDFspec

22.2.3

LV(PP)

mm

22.2.4

HVN

mm

22.3

Quantityofoilinoilfilledbushing

litre

22.4

Creepagedistance

mm/kV

23

Noloadlossat100%ratedvoltage&
frequency

kW

24

Loadlossatratedcurrentwith75deg
C

kW

25

Coolerlossatfullload

kW

Rev. 0 06.03.12

IS-2099
AsperIEC/EDFspec

DocumentNo:P.003080E490457

AsperIEC/EDFspec
Aspertechspec
Tobefurnishedduringdetailedengineering

31
12KW

2KW

Page 48 of 88

Sr.No.

Description

Unit

Parameter

26

Efficiency(0.85Pf)

26.1

Fullload

99.47

26.2

75%load

99.57

27

Noloadcurrent

A(approx)

28

Totalestimatedweight

Kgs

29

OCTC/OLTC

29.1

Make

29.2

RatedVoltage

Volts

29.3

RatedCurrent

Amps

29.4

No.ofsteps

29.5

StepVoltage

Volts

29.6

Time of operation from one step to


otherforAuto/manualmode

Sec.

30

Typeofaxialandradialcoilsupports
forHV/LV

31

No. of cooler banks and capacity of


eachcoolerbank

32

GuaranteedNoloadcurrent

31.1

WhenexcitedfromLVsideat 100%
and110%ratedvoltage

Amps

33

Max. Flux density when rated and


110%ratedvoltage

Wb/m2

34

Vacuum withstand capability main


tank,radiatorsandaccessories

mmofHg

35

Weight

35.1

Core

Rev. 0 06.03.12

TobedecidedduringDE
OLTC
Asperapprovedvendorlistprovided

*
*

kg

Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

Page 49 of 88

Sr.No.

Description

Unit

Parameter

35.2

Netcopperwt.HV/LV

kg

do

35.3

Oil

kg

do

35.4

Tank,coolers&fittings

kg

do

35.5

Total

kg

do

35.6

Untankingweight

kg

do

36

Coolingfans,oilpumpsrating

kW

do

37

Capabilityoftransformertoremainin
operation from hot conditions after
failureofforcedcoolingwithfullload

minutes

do

38

Online dissolved Gas Analyser


Provided?

Yes/No

no

39

Fibre optic based direct hot spot


temperature measurement System
Provided?

Yes/No

no

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 50 of 88

1.8 Unit Station Transformer/Station Service Transformer

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 51 of 88

Sr.No.

Description

Parameter

Unit

Transformerapplications

Type&make

Aspervendorlist

Applicablestandard

AsperIS/EDFstd.

Quantity

No(s).

Fullloadrating(ONAN/ONAF)

MVA

2.5

Ratingofeachwindings

MVA

2.5

RatingnoloadvoltageHV/LV

kV

Ratingofdifferentcoolingmethods

Impedancevalue

7.2

10

Ratedfrequency

Hz

50

11

Winding connection of different


windingsandvectorgroup

12

SystemEarthing(HVLV)

13

Typeoftapchangeroffcircuit/onload

14

Fullpowertappingprovided

15

Type of voltage variation


(CFVV/VFVV/CBVV)

16

Overfluxingcapability

17

Winding insulation type uniformly or


nonuniformlyinsulated

17.1

HV

NonUniform

17.2

LV

Uniform

Rev. 0 06.03.12

Auxiliary

6.6/0.433
ONAN

Dyn11
LV
OLTC
Yes/No

Yes
CFVV

For
Over fluxing Factor 1.1 :
Continuous
1.25 : 60 Sec
1.4 : 10 Sec.

DocumentNo:P.003080E490457

Page 52 of 88

Sr.No.

Description

18

Highestsystemvoltage

19

Powerfrequencywithstandvoltageof
winding

19.1

Unit

Parameter

kV

12

HV

kVrms

20

19.2

LV

kVrms

20

Standard rated lightning impulse


withstandvoltage

20.1

HV

kVp

50

20.2

LV

kVp

24

21

Maximumtemperatureriseatfullload
with100%coolers:

21.1

Oil

oC

55

21.2

Winding

oC

45

22

Bushingparticulars.

22.1

Applicablestandardforbushing

22.2

Clearance in air HV/LV/Neutral


(betweenphasesandphasetoearth)

22.2.1

HV(PP)

mm

AsperIEC/EDFspec

22.2.2

HV(PE)

mm

AsperIEC/EDFspec

22.2.3

LV(PP)

mm

22.2.4

HVN

mm

22.3

Quantityofoilinoilfilledbushing

litre

22.4

Creepagedistance

mm/kV

31

23

Noloadlossat100%ratedvoltage&
frequency

kW

2.5

24

Loadlossatratedcurrentwith75deg

kW

23

Rev. 0 06.03.12

IS-2099
AsperIEC/EDFspec

DocumentNo:P.003080E490457

AsperIEC/EDFspec
Aspertechspec
Tobefurnishedduringdetailedengineering

Page 53 of 88

Sr.No.

Description

Unit

Parameter

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 54 of 88

Sr.No.

Description

Parameter

Unit

25

Coolerlossatfullload

26

Efficiency(0.85Pf)

26.1

Fullload

98.75

26.2

75%load

98.99

27

Noloadcurrent

A(approx)

28

Totalestimatedweight

Kgs

29

OCTC/OLTC

29.1

Make

29.2

RatedVoltage

Volts

29.3

RatedCurrent

Amps

29.4

No.ofsteps

29.5

StepVoltage

Volts

29.6

Time of operation from one step to


otherforAuto/manualmode

Sec.

30

Typeofaxialandradialcoilsupports
forHV/LV

31

No. of cooler banks and capacity of


eachcoolerbank

32

GuaranteedNoloadcurrent

31.1

WhenexcitedfromLVsideat 100%
and110%ratedvoltage

Amps

33

Max. Flux density when rated and


110%ratedvoltage

Wb/m2

34

Vacuum withstand capability main


tank,radiatorsandaccessories

mmofHg

35

Weight

Rev. 0 06.03.12

kW

7150
OLTC
Asperapprovedvendorlistprovided

*
*

DocumentNo:P.003080E490457

Page 55 of 88

Sr.No.

Description

Parameter

Unit

35.1

Core

kg

35.2

Netcopperwt.HV/LV

kg

do

35.3

Oil

kg

do

35.4

Tank,coolers&fittings

kg

do

35.5

Total

kg

do

35.6

Untankingweight

kg

do

36

Coolingfans,oilpumpsrating

kW

do

37

Capabilityoftransformertoremainin
operation from hot conditions after
failureofforcedcoolingwithfullload

minutes

do

38

Online dissolved Gas Analyser


Provided?

Yes/No

no

39

Fibre optic based direct hot spot


temperature measurement System
Provided?

Yes/No

no

Rev. 0 06.03.12

Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

Page 56 of 88

1.6

High Medium Voltage Switchgear

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 57 of 88

Sr.
No.

Description

Unit

Parameter

Manufacturersname

Asperapprovedvendorlistprovided

ApplicableStandard

AsperIS/EDF

Nominal system voltage, phase &


frequency

Systemneutralearthingconsidered

Max.systemvoltage

Oneminutepowerfrequencywithstand
voltage

kVrms

1.2/50uSimpulsewithstandvoltage
7

Switchingovervoltagesgeneratedand
timetocrest

a)

Switching off motor with its rotor


locked

b)

Switchingoffunloadedtransformer

Ref.ambienttemperature

S. C. Current withstand capability


(current/duration)

a)

3310%,Three,50Hz5%

earthed
36
70
170
kVpeak
kV p /
microsec
Tobefurnishedduringdetailedengineering
*
Deg.C

50C

Shorttimefor1sec

kArms

31.5

b)

Dynamicrating

kApeak

2.5 x rated short time current

10

Cableentry

11

Busbar

AsperSld

a)

Material

AsperSld

b)

Continuouscurrentrating

c)

Max. temp. of bus bars, dropper,


connectors & contacts at continuous

Deg.C

Rev. 0 06.03.12

Frombottom

AsperSld
Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

Page 58 of 88

Sr.
No.

Description

Unit

Parameter

current rating under site reference


ambienttemperature.

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 59 of 88

Sr.
No.

Description

steel

2/2.5CRCA

Thickness of
enclosures/doors.

a)

Coldrolled

b)

Hotrolled

2.5

13

Degreeofprotection

a)

BusBar

IPH4

b)

Forothers

IPH6

c)

Forcompleteswitchgear

IP4X

14

Paintshade

15

Earthing bus bar size & material


considered

16

Clearanceinairoflivefaults

b)

sheet

Parameter

12

a)

Unit
mm

RAL7032

Phasetophase
Phasetoearth

50X6mm,Copper

Mm

AsperIEC/EDFStandards

mm

AsperIEC/EDFStandards

17

Circuitbreakers

a)

Manufacturer

b)

Typeofcircuitbreaker

c)

Ratedoperatingduty

d)

Rated currents under site ambient


temp.(foreachtypeofbreaker)

e)

Ratedsymmetricalbreakingcurrent

kArms

AsperIEC/EDFStandards

f)

Makingcurrent

kApeak

AsperIEC/EDFStandards

g)

S.Ccurrentwithstand&duration
Shorttimefor1sec

kArms

31.5

Dynamicrating

kApeak

2.5 x rated short time current

Rev. 0 06.03.12

Asperapprovedvendorlistprovided

Vacuum
Continuous(O3mCO3mCO)
Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

Page 60 of 88

Sr.
No.
h)

Description

Unit

Parameter

Asymmetricalbreakingcurrent
ACcomponent

AsperIEC/EDFStandards

DCcomponent
t)

AsperIEC/EDFStandards

Operatingtime
Openingtime
Closingtime

j)

Closing&Openingcoilparticulars

k)

Switchingovervoltage

l)

Tripfreeoperatingmechanismtype

m)

Aux. control voltage for trip, close,


annunciation&springcharging

Cycles

Not more than 60

Cycles

Not more than 100


Twotripcoils
AsperIEC/EDFStandards
Springchargedmotor

Close- 220V DC, 2W (+10% to 15%)

Trip-220V DC, 2W (+10% to 30%)


Spring-220V DC, 2W (+10% to 15%)

n)

Aux.controlvoltageforspaceheater,
DC failure annunciation, motor
winding/spaceheaters,lightingetc

p)

Breakersapplication

240V 10%, 1 Ph, 2W

Transformercontrol

YES

Motorcontrol

NO

q)

Type of external switching over


voltagelimitingdeviceprovided

19

CTs

Tobefurnishedduringdetailedengineering

a)

Type

b)

Ratio

c)

Burden

d)

Accuracyclass

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 61 of 88

Sr.
No.

Description

Unit

Parameter

e)

KneepointVoltage

f)

Magnetisingcurrent@Vk/2

g)

Secondaryresistance

h)

ClassofInsulation

i)

Shorttime&Dynamiccurrentrating

j)

ApplicableStandard

k)

No.ofCores

20

DetailsofCBCTs

21

VTs

a)

Type

b)

Ratio

c)

Burden

d)

Acuracyclass

e)

MagnetisingCharacterstics

f)

Methodofconnection

g)

ClassofInsulation

h)

RatedVoltagefactor(Continuous&08
hours)

i)

ApplicableStandard

j)

No.ofCores

22

Earthingarrangementfor

a)

Busbarside

b)

Cableside

24

DetailsofLA/SA

Rev. 0 06.03.12

Tobefurnishedduringdetailedengineering

DocumentNo:P.003080E490457

Page 62 of 88

Sr.
No.

Description

Unit

25

ParticularsofBreakerhandlingTools

27

Particularsofmeters

28

ParticularsofRelays

29

ParticularsofSpringchargingmotor

30

Panelconstructiondetails

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Parameter

Page 63 of 88

1.7

Low Voltage switchgear

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 64 of 88

Sr.
No.
1
2
3

Manufacturer'sname
ApplicableStandard
Nominalsystemvoltage,phase&

4
5
5.1

frequency
Systemneutralearthingconsidered
Maximumsystemvoltage
Oneminutepowerfrequency

V
kVrms

20 kV ( r.m.s)

5.2
6
6.1
6.2
7

withstandvoltage
1.2/50Secimpulsewithstandvoltage
ShortCircuitwithstandcapability
Shorttimefor1sec
Dynamicrating
Referenceambienttemperature

kVpeak

60 kV ( peak)

kArms
kApeak
Deg.C

40 kA
100 kA
50C

Continuouscurrentratingundersite

referenceambientcondition
MaximumtemperatureofBusBars,

Deg.C

Description

Unit

Parameter
Asperapprovedvendorlist
AsperIEC/Frenchstandards

6600 10%
Three

dropper,connectors&contactsat

6900

AsperSLD
40C for plain joints
50C for Silver plated joints

continuouscurrentratingundersite
10
11

referenceambienttemperature
Materialofbusbarsconsidered
Cableentry

12
13

Degreeofprotection
Thicknessofsheetsteel

13.1
13.2
14
15

enclosures/doors
ColdRolled
HotRolled
Shapeofpaints
Earthingbusbarsize&material

16
16.1
16.2
17
a)
b)
c)

considered
Clearanceinairofliveparts
phasetophase
phasetoearth
CircuitBreaker
type
ratedoperatingduty
ratedcurrentatsitereferenceambient

d)
e)

temp.
ratedbreakingcurrent
ratedmakingcurrent

Copper
a) Power Cables-Bottom
b) Control Cables- Bottom

Rev. 0 06.03.12

mm
mm

2
2.5

mm

150X12mm2copper

mm
mm

AsperIEC/FrenchStandards
AsperIEC/FrenchStandards
AsperIEC/FrenchStandards

Vaccum / SF6
Amps
kArms
kArms

DocumentNo:P.003080E490457

0-3-CO-3-CO
1600
AsperIEC/FrenchStandards
AsperIEC/FrenchStandards

Page 65 of 88

Sr.
No.
f)

shorttimecurrentwithstandcapacity

g)

h)

i)
j)
18

for1secduration
asymmetricalbreakingcurrent
1)accomponent
2)dccomponent
operatingtime
1)openingtime
2)closingtime
closingandopeningcoilparticulars
switchingovervoltagefactor
Tripfreeoperatingmechanismtype

19

Auxilarycontrolvoltagefortrip,

storedenergy
220 V DC (85%-110%)

20

close,annunciation&springcharging
Auxilarycontrolvoltageforspace

220 V DC (85%-110%)

Description

Unit

Parameter

kApeak

AsperIEC/FrenchStandards

kArms
kArms

AsperIEC/FrenchStandards
AsperIEC/FrenchStandards

sec
sec
cycle

Not more than 60


Not more than 100
AsperIEC/FrenchStandards
Motorwoundspringcharged

heater,DCfailureannunciation,motor
21
a)
b)
22

winding/spaceheaters,lightingetc
Breakerapplication
incomers&ties
outgoing
Detailsofcontractors/switches/fuses

a)type
b)ratedoperatingduty
c)ratedcurrentatsitereference

ambienttemp.
d)ratedbreakingcurrent
e)ratedmakingcurrent
f)shorttimecurrentwithstand

23

capacityfor1secduration
g)asymmetricalbreakingcurrent
1)accomponent
2)dccomponent
h)operatingtime
1)openingtime
2)closingtime
DetailsofCTs

Asperrequirement
Asperrequirement
Castresinbarprimary

AsperIEC/FrenchStandards
AsperIEC/FrenchStandards
AsperIEC/FrenchStandards
AsperIEC/FrenchStandards

Tobefurnishedduringdetailed
engineering

a)
b)
c)
d)

Rev. 0 06.03.12

type
ratio
burden
accuracyclass

DocumentNo:P.003080E490457

Page 66 of 88

Sr.
No.
e)
f)
g)
h)
i)
j)
k)
24

kneepointvoltage
magnetizingcurrentatVk/2
secondaryresistance
classofinsulation
shorttime&dynamiccurrentrating
applicablestandard
no.ofcores
DetailsofVTs

a)
b)
c)
d)
e)
f)
g)
h)

type
ratio
burden
accuracyclass
magnetizingcharacteristic
methodofconnection
classofinsulation
ratedvoltagefactor(continuous&8

i)
j)
25
26
27

hours)
applicablestandard
noofcores
Particularsofmeters
Particularsofrelays
Panelconstructiondetails

Description

Unit

Parameter

3
Tobefurnishedduringdetailed
engineering

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 67 of 88

1.8

Motor

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 68 of 88

Sr.
No.

Description

Unit

Parameter

1.0
2.0

ACMotor
Application/Designation
NameoftheManufacturer

Asperapprovedvendorlist

3.0

Typeofmotors/framesize

provided
Squirrelcagethree/singlephase
induction

4.0
4.1
4.2
4.3
4.4
4.5
5.0
5.1
5.2

Rated
Output
Speed
Voltage
No.ofPhases/Frequency
Systemneutral
TypeofDuty
TypeofDuty(IS325orequivalent)
Dutydesignation(IS325or

kW
rpm
V

0.22,1604000
3000
230/400,6.6
3/1,50Hz
Asperrequirement
AsperIEC/FrenchStandards
AsperIEC/FrenchStandards
AsperIEC/FrenchStandards

6.0
6.1
6.2
6.3
6.4

equivalent)
SupplyConditions
(a)Allowablevariationsin
Voltage
Frequency
Combined

%
%
%

6.5

Permissibleunbalanceinsupply

7.0
7.1
7.2

voltage
Current
Fullload
Starting

Amps
%FL

8.0

Methodofstarting

8.1

Startingtime

8.1.1

WithratedVoltage

TobefurnishedduringDE

8.1.2

Withmin.Voltage

TobefurnishedduringDE

8.1.3

WithMax.Voltage

TobefurnishedduringDE

8.2

Safestalltimeunderhot/cold

8.2.1

condition
WithratedVoltage

TobefurnishedduringDE

8.2.2

Withmin.Voltage

TobefurnishedduringDE

Rev. 0 06.03.12

10%
5%
10%(absolutesum)+frequency

80
TobefurnishedduringDE
TobefurnishedduringDE
TobefurnishedduringDE
TobefurnishedduringDE

Sec

Sec

DocumentNo:P.003080E490457

TobefurnishedduringDE

TobefurnishedduringDE

Page 69 of 88

Sr.
No.
8.2.3

WithMax.Voltage

TobefurnishedduringDE

9.0

Insulation

TobefurnishedduringDE

9.1

Classofinsulation

TobefurnishedduringDE

9.2

Temperaturerisebywinding

Deg.C

TobefurnishedduringDE

10.0

resistancemethod
Typeofcooling(IS:6362)

Deg.C

TobefurnishedduringDE

11.0

Degreeofprotection(IS:4691or

12.0

equivalent)
Suitableforoutdooroperation

Yes/No

TobefurnishedduringDE

13.0

Normalwindingconnection

Star/

TobefurnishedduringDE

14.0

PermissibleNo.ofequallyspread

Description

Unit

Parameter

TobefurnishedduringDE

Delta
TobefurnishedduringDE

startsperhourundernormalservice
15.0

conditions
Efficiency(%)

15.1

Fullload

TobefurnishedduringDE

15.2

75%Load

TobefurnishedduringDE

15.3

50%Load

TobefurnishedduringDE

15.4

25%Load

TobefurnishedduringDE

16.0

PowerFactor

16.1

FullLoad

16.2

75%Load

16.3

50%Load

16.4

25%Load

17.0

Torque

TobefurnishedduringDE

17.1

Starting

TobefurnishedduringDE

17.2

Maximum(Pullout)

TobefurnishedduringDE

17.3

Pullup

TobefurnishedduringDE

Rev. 0 06.03.12

DocumentNo:P.003080E490457

TobefurnishedduringDE

Page 70 of 88

Sr.
No.
18.0

Motorreactance(pu)

TobefurnishedduringDE

18.1

Subtransient

TobefurnishedduringDE

18.2

Transient

TobefurnishedduringDE

18.3

Steadystate

TobefurnishedduringDE

Description

Unit

Parameter

19.0

Faultlevel
kA/sec
DCMOTORS
1.0
RatedVoltage
V
125
2.0
ClassofInsulation
AsperIEC/EDF
3.0
Temperaturerise
*
4.0
Methodofstarting
*
ItemsunderACmotorswhichareapplicableforDCmotorsshallalsobelisted

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 71 of 88

1.9

Diesel Generator Set

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 72 of 88

Sr.
No.
1.0

Description

Unit

DieselEngineGeneralData

1.1

Manufacturers name, make, model


number

1.2

StandardratingatISOconditions

1.3

Deratingfactorsdueto:

1.3.1

Harmonics

1.3.2

Altitude

1.3.3

Inletairtemperature

1.3.4

Humidity

1.3.5

Coolingwatertemperature

1.3.6

Overallderatingfactor(max.10%)

1.4

Conditionsoutputatsiteconditions

KW

1.5

Maximum engine rating at site


conditionswith10%overload

KW

1.6

Numberofcylinders

1.7

Arrangementofcylinders

1.8

Directionofrotationasviewedfrom
freeend

1.9

Operatingspeed

1.10

Numberofstrokes

1.11

Pistonspeed

M/sec

1.12

Minimum acceptable lube oil


temperatureatstartup

1.13

Maximumperiodforwhichtheengine Min
can operate without cooling water
supply

1.14

Foundation bolts and anti vibration


padstobeprovided

Rev. 0 06.03.12

Parameter

Asperapprovedvendorlistprovided
KW

RPM

1.6

Notmorethan750
4

DocumentNo:P.003080E490457

Yes

Page 73 of 88

Sr.
No.
2.0

Turbocharger/Supercharged

2.1

Manufacturer

2.2

Speed

3.0

Fueloilsystem

3.1

Daytank

3.2

Numberofdaystanks

3.3

CapacityEach

3.4

Materialofconstruction

3.5

Thicknessofshell

3.6

Handoperatedfueloilpumpprovided

3.7

Filters

3.8

Type

3.9

Number

4.0

Lubeoilsystem

4.1

Filters

4.1.1

Type

4.1.2

Number

4.1.3

Gradeoflubeoiltobeused

4.2

AC/DCmotordrivenstandbypump,if
any,tobeincluded

4.3

AC motor driven primary oil pump with


Clocktimer

5.0

Enginecoolingsystem

5.1

Cooling water/makeup water quality


acceptable

5.1.1

Ifno,indicaterequirement

Rev. 0 06.03.12

Description

Unit

Parameter

RPM

Litres

DocumentNo:P.003080E490457

Page 74 of 88

Sr.
No.
5.2

Coolingwaterflowrate

5.2.1

Enginecoolingcircuit

LPM

5.2.2

Lubeoilcooler

LPM

5.2.3

Turbochargercooler

LPM

5.2.4

Total5.2.1to5.2.3

LPM

5.3

Expansiontank

5.3.1

Capacity

5.3.2

Materialofconstruction

5.3.3

Thickness

5.4

Bypasscontrolvalvestobeincluded

5.5

Temperatureofcoolingwater

5.5.1

Atengineinlet

5.5.2

Atengineoutlet

6.0

Airintakeandexhaust

6.1

Intakefiltertype

6.2

Exhaustsilencertype

6.3

Maximumbackpressure

7.0

Stack

7.1

FlowrateoffluegasesleavingDG

M3/Hr

7.2

Temperature of flue gas leaving DG


set/enteringstack

7.3

Densityoffluegasesatstackinlet

Kg/M3

7.4

Stackdiameterxheight

7.5

Numberoffluegasopenings

7.6

Fluegasconnectionsize

Rev. 0 06.03.12

Description

Unit

Parameter

Litres

Mm
*

mmWc

DocumentNo:P.003080E490457

Page 75 of 88

Sr.
No.
7.7

Description
Heightoffluegasconnectioncentre
lineabovethefoundationlevel

Unit
M

8.0

Heatexchangers

8.1

Typeofconstruction

8.2

Shellside

8.2.1

Flowrateoffluidcirculated

8.2.2

Inlet/Outlettemperature

8.3

Typeside

8.3.1

Fluidcirculated

Cooling
water

8.3.2

Flowrateoffluidcirculated

Kg/Hr

8.3.3

Inlet/Outlettemperature

8.4

Materialspecification

8.4.1

Shell/frame(forplatetype)

8.4.2

Tubes/plates(forplatetype)

8.4.3

Tubesheets/endplate(forplatetype)

8.5

Bolts/Nuts

8.6

Gaskets

8.7

Radiator

8.7.1

Materialofconstruction

8.7.2

Fanmotorrating

9.0

Generatorandaccessories

9.1

ManufacturersName

9.2

Designrating

KW

9.3

Continuousoutputrating

KW

9.3.1

NominalISOrating

KW

Rev. 0 06.03.12

Parameter

KW

DocumentNo:P.003080E490457

Page 76 of 88

Sr.
No.
8.3.2

Description

Unit

Maximumratingatsite

KW

9.3.3

Derated output under harmonic


loading

KW

9.4

Powerfactor

9.5

Ratedvoltage

9.6

Ratedcurrent/Phase

Amps

9.7

Speed

RPM

9.8

Frequency

Hz

9.9

Fieldcurrentatratedoutputandvoltage Amps

9.10

Insulationclass

9.10.1

Stator

9.10.2

Rotor

9.11

Temperatureriseaboveambientof50 0
(Bythermometer)

9.11.1

Stator

9.11.2

Rotor

9.11.3

Cores

9.12

Momentofinertiaofrotatingmassin
dieselengine,generator,exciteretc.,

Kg/M2

9.13

Efficiency

9.13.1

50%load/75%load/Fullload

9.14

Largestmotorallowedtostartwithin
15% maximum allowable starting
voltageDIP

KW

9.14.1

WithDOLstarter/Stardeltastarter

9.15

KWratingofspaceheaters

9.16

Transientreactances

Rev. 0 06.03.12

Parameter

//

KW

DocumentNo:P.003080E490457

Page 77 of 88

Sr.
No.
9.16.1

Xd

9.16.2

Xd

9.17

Degreeofprotection

10.0

Mainexciter

10.1

Ratedvoltage

10.2

Ratedcurrent

10.3

Ceilingvoltageatzeroloadandrated
speed

10.4

Ceiling voltage at rated current and


ratedspeed

10.5

Excitationsystemresponseratio

10.6

Insulationclass

10.6.1

Stator

10.6.2

Rotor

11.0

Automaticvoltageregulator

11.1

Type

11.2

BurdenofAVRonCTsandPTs

11.2.1

CTs

VA

11.2.2

PTs

VA

11.3

Deadband,ifany

11.4

Fielddischargeresistor

11.5

Typeandratingoffieldbreaker

12.0

Performanceguarantees

12.1

Continuousoutputatsiteconditions

KW

12.2

10%overloadforone(1)houroutofa
total of 12 consecutive hours of
operationwithoutoverheating

KW

Rev. 0 06.03.12

Description

Unit

Parameter

Ohms

DocumentNo:P.003080E490457

Page 78 of 88

Sr.
No.
12.3

Description

Unit

Parameter

Fuel oil consumption at 50%, 75%


andfullload

Gms/KWHr *

12.4

Lubeoilconsumption

Gms/KWHr

12.5

Coolingwatertemperatureat

Engine
Outlet

12.6

Coolingwaterpressuredrop

Kg/cm2

12.7

Noiselevel

dB(A)

13.0

Weightschedu1e

13.1

Weight of engine and standard


accessories excluding the weight of
flywheel

Kg

13.2

Weightofflywheel

Kg

13.3

Totalshippingweight

Kg

13.3.1

Weightofgenerator

Kg

13.3.2

Weightofcontrolpanel

Kg

13.4

Weightofsingleheaviestpiecetobe
handledduring:

13.4.1

Erection

Kg

13.4.2

Maintenance

Kg

14.0

Dimensions

14.1

Shippingdimensions

14.1.1

EngineLxBxH

14.1.2

Generator

15.0

Miscellaneous

15.1

General arrangement drawing to be


enclosed

Rev. 0 06.03.12

LxBxH

DocumentNo:P.003080E490457

Page 79 of 88

Sr.
No.
15.2

P&Idiagramtobeenclosed

15.3

TotalheatdissipationfromDGset

15.4

Ventilationrequirementstobeenclosed

15.5

Synchronising scheme as per


requirement

15.6

Protectionschemetobeenclosed

15.7

Suitabilityofoperationfortheload

Description

Unit

Parameter
*

Kcal/Her

Patternassumed
16.0

CODES&STANDARDS

16.1

BS5514/ISO3046 Specification for


reciprocating internal combustion
engine(Part(IVI)

*
16.2

BS5000 : Part 99 Machines for


miscellaneousapplication

16.3

IS4722Rotaryelectricalmachinery

16.4

VDI 2063 : Measurement and


evaluationofmechanicalvibrationsof
reciprocating piston engines and
pistoncompressors

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 80 of 88

1.10

DC Battery and Battery Charger

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 81 of 88

Sr.
No.
1.0

NameoftheManufacturer(NiCd

1.1
1.2
1.3

battery)
Application
No.ofbatteryBankrequired
.
Referenceambienttemperaturefor

Nos
0C

1.4
1.5

designofelectricaldevices
DCsystemvoltage
Amperehourcapacityofbatteryat27

V
Ah

1.6

deg.Ctemperaturefor5HOURSrate
Dischargedutyconsideredforbattery

1.7

sizing
a)Requiredareaofbatteryand

Description

Unit

Parameter
Asperapprovedvendorlist
provided
DCloadrequirements
TobefurnishedduringDE
50
220

1350 AH

a)To be furnished during DE

chargerroom
b)Batteryorientation/mounting
arrangement

b)Steel Rack

1.8

Chargingmethodproposed

Float-cum-boost charger

1.9

Batterychargerratingrequiredto

2.15 to 2.25 Volts per

chargethebatteryin10hrsfrom

cell

fullydischargedconditions(both
Voltageandcurrentrangetobe
specified).

1.10

No.ofcellsperset

1.11

Opencircuitvoltageofeachcell

1.12

Capacityfactorconsideredfor

To be furnished during DE

batterysizing
1.13

Thedetailsofderatingfactor

consideredfortemperaturecorrection,
ageing,futuremarginconsidered
(min.10%)andany
otherrequiredasperrelevant
1.14
1.15

Rev. 0 06.03.12

standard
Typeofenclosure
Typeofbatterycell

DocumentNo:P.003080E490457

*
*

Page 82 of 88

Sr.
No.
1.16
1.17

Lifeofthebattery
No.offullchargedischargecyclesin

1.18

alife
Recommendedchargingand

Description

Unit
Hour
Nos.

Parameter
*
*
*

dischargingrate
a)

Normaloperation

b) Quickcharging
c)

Firstcharging

2.0

BATTERYCHARGER

2.1

Numberofchargerrequired

2.2

Type

2.3

DCsystemvoltage(nominal)

2.4

DCsystemearthing

2.5

Ambientdesigntemperature

2.6

2.7

Nos.

To be furnished during DE
Solid-state (thyristor
based), full wave, fully
controlled (6 pulse), three
phase bridge for
continuous application

DCbusloadconsideredwithbreak
up

Volts

230-240 Volt
ungrounded

Deg.C

50C

Amp
Forsec

a) Shorttimeload
b) Continuousload
c) Starting current of largest
connectedDCmotor
Batterychargercurrentandvoltage
rating
Float
Boost

2.8

Float/Trickle charging current of


battery

2.9

MaximumBoostchargingcurrentof

Rev. 0 06.03.12

*
Amp

DocumentNo:P.003080E490457

Page 83 of 88

Sr.
No.

Description

Unit

Max.Boostchargingvoltagebattery

Volt

Parameter

battery

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 84 of 88

Sr.
No.

Description

Unit

Parameter

2.10

Max. time for Boost charging of


battery

Hours

2.11

ACsystemdata
Supply

415V,3phase,50Hz,4wire

Variationinsupply

Voltagevariation10%
Frequencyvariation5%

Shortcircuitlevel

kA

50kA(rms)symmetrical

Typeofearthing
2.12

Performance
DC voltage setting adjustment for
floatcharger

Maximum permissible variation in


DCvoltage(Noloadtofullload)

Within1%ofthesetvalue

DC voltage setting adjustment for


boostchargingatconstantvoltage

DC volt adjustment for boost


charging

Minimumpermissiblepowerfactor
atratedcontinuousload

2.13

Voltage stabilisation for constant


voltageregulator

2.14

Cableentry

2.15

Permissible ripple content at rated


continuousload

Rev. 0 06.03.12

Solidlyearthed

*
*

Withoutbattery

withbattery

DocumentNo:P.003080E490457

Page 85 of 88

Sr.
No.

Description

Unit

Parameter

2.16

Peak inverse voltage of power


devices

2.17

Thyristorbridgecooling

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 86 of 88

1.11

UPS

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 87 of 88

Sr.
No.
1.0

NameoftheManufacturer

1.1

Type

1.2

PowerRatingatloadPF0.8lagging

1.3

Application

1.4

Quantity(Nos.)

1.5

Methodofenergystorage

1.6

Designation

1.7

Whethertransferswitchrequiredfor

1.8

secondarybackup
Installation

1.9

Temperature

Description

Unit

Parameter
Asperapprovedvendorlist
provided

1.9.1

1.9.2

Ni-Cd

CriticalPowersupply
1
Static
*
Yes

Ambient
ForOperation

50

ForStorage

50

Ref.DesignTemp.

2.0

Enclosure

2.1

Material

2.2

Sheetthickness

2.3

DegreeofProtectionasperIS247

2.4

Painting

Sheet steel, IP42

mm

*
IP32

Exterior

TobedecidedduringDE

Interior

TobedecidedduringDE

Frombottom

2.5

Cableentry

2.6

Acousticnoiselevel

Rev. 0 06.03.12

Aspertechspecs

DocumentNo:P.003080E490457

AsperIEC/EDFstandards

Page 88 of 88

Sr.
No.

Description

3.0

UPSsystem

3.1

Input

3.1.1

Unit

Parameter

190302

Supplyvoltagewith

230

Isolationtransformer.
3.1.2

3.2

Allowablevariation
Voltage

10%

Frequency

5%

Combinedvoltage+Frequency

Output

230

3.2.1

Outputvoltage

3.2.2

ACvoltageaccuracy(Steadystate)

2%

overentireload,loadPF&DC
voltagerange
3.2.3

Transientvoltageregulation

3.2.4

TransientRecovery

3.2.5

Voltagewaveform

3.2.6

RangeofadjustmentofACoutput

+/-2
50msec

50+_ 0.5 Hz to 50+_ 2 Hz

voltage
3.2.7

ACharmoniccontent

3.2.8

Nominalfrequency

3.2.9

Frequencyregulation

4.0

DCLink(Battery)

4.1

No.of100%capacitybatteries

Rev. 0 06.03.12

DocumentNo:P.003080E490457

3% maximum
50 Hz

5%

2X100

Page 89 of 88

Sr.
No.

Rev. 0 06.03.12

Description

Unit

DocumentNo:P.003080E490457

Parameter

Page 90 of 88

Sr.
No.
4.2

Typeofbatterycell

4.3

DClinkvoltage

4.4

DCvoltagevariationrange

4.5

Batterysupporttime

4.6

Mountingarrangement

5.0

BatteryCharger

5.1

(RectifierUnit)
No.ofchargers

2X100%

5.2

RectifierUnit

Fullwave

5.3

Type

5.4

Paralleloperation

5.5

Rechargetimeonboostcharge

5.6

Inrushcurrent

5.7
6.0
6.1

Batteryparalleloperation
Inverter
No.ofinvertersinsystem

6.2

Typeofpowerswitchingdevice

6.3

Currentcapacity

6.3.1

Overload

6.3.2

Shorttimewithstand

6.3.3

Overcurrentsettingrange

6.3.4

Synchronising
Betweeninverters

yes

Betweeninvertersandstandby

yes

6.4

Rev. 0 06.03.12

Description

Unit

Parameter

LeadAcidPlante/stationary
NickelCadmiumtype
*
*
1hour
Steelracks

Solidstate,fullwavefully
controlled.3PhaseBridge.

supply
Synchronisingrange

DocumentNo:P.003080E490457

5hrs

TobedecidedduringDE
Static,ParallelDualRedundant

125%ofratedKVA&p.ffor
10minutes
500%for5msec

To be decided during DE

Page 91 of 88

Sr.
No.

Description

Unit

Parameter

7.0
7.1
7.2

StaticSwitch
Type
No.ofswitches

Solidstate,SCR

7.3

Rating

To be decided during DE

7.4

NominalFrequency

7.5
7.6

Maximumtransfertime
Shorttimerating

7.7

Whethermakebeforebreak

8.0

Staticvoltagestabilizerwithstep

To be decided during DE

50Hz
1/4th cycle maximum.
50KA
Yes

downtransformers.
8.1
8.1.1
8.1.2

Input.
Inputvoltage
Allowablevariation
Voltage

*
*

Frequency
8.2

Output

8.2.1

Outputvoltage

8.2.2

Outputvoltageaccuracy

8.3

Overload

9.0

RedundantA.C.Distributionboard

*
%

*
*

withrequiredNo.offeedersalong
with20%sparefeeders,adequate
10.0

protection&meeting.
Grounddetectorsystem

11.0

ManualBypassswitch&isolators.

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 92 of 88

1.12

Illumination

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 93 of 88

Sr.
No.

Description

Unit

Parameter

1.0

Make of light fittings

Asperapprovedvendorlist
provided

2.0

Make of main DB

Asperapprovedvendorlist
provided

3.0

Make of sub-lighting DB

Asperapprovedvendorlist
provided

4.0

Type of fitting for periphery


lighting and control for same

5.0

Cable laying method

6.0

Control operations:

7.0

Escape lighting

8.0

Type of cable proposed

9.0

Make of light fittings

Asperapprovedvendorlist
provided

10.0

Make of cables

Asperapprovedvendorlist
provided

11.0

Type of fittings at various


locations

As per IEC/EDF standards


Continuous

As per IEC/EDF standards

As per IEC/EDF standards

12.0

DC emergency lighting
control board with necessary
contactor.

13.0

Type of incomer for main


and sub-DBs.

As per IEC/EDF standards

14.0

Type of outgoing for main


and sub-DBs

As per IEC/EDF standards

15.0

Second source of supply


considered for all the areas

Rev. 0 06.03.12

Yes

a)Degree of protection for


main and sub-DB enclosure:

As per IEC/EDF standards

b)Mounting details for DBs:

As per IEC/EDF standards

DocumentNo:P.003080E490457

Page 94 of 88

Sr.
No.

Description

16.0

Phase to phase and phase to


earth clearances in main
and sub-DBs:

17.0

Busbar arrangement in SubDBs:

18.0

Make of ballast

Asperapprovedvendorlist
provided

19

Make of cables

.do.

20

Make of switches

.do.
.do.

21

Erection accessories such as


junction boxes, clamps,
saddles

22

Make of ceiling fans

.do.

23

Make of exhaust fans

.do.

24

Make of flame-proof fittings


and catalogue numbers

.do.

25

Rating of exhaust fans

To be decided during DE

26

Deviations, if any, on
technical design data:

27

Make of switches

28

Erection accessories such as


junction boxes, clamps,
saddles

Rev. 0 06.03.12

Unit

DocumentNo:P.003080E490457

Parameter

As per IEC/EDF standards

Asperapprovedvendorlist
provided
Asperapprovedvendorlist
provided

Page 95 of 88

For Outdoor Lighting


Sr.
No.

Description

1.0

Typeoffittingsenvisaged:

2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0

Makeoffittings:
Luxleveltobeobtained:
Provisionofescapelighting:
LocationofmainandsubDBs
Controloflighting:
Automatic/Manual:
Cablelayingaboveground:
Typeoffittingsenvisaged:
Makeoffittings:
Luxleveltobeobtained:

Rev. 0 06.03.12

Unit

DocumentNo:P.003080E490457

Parameter
Asperapprovedvendorlist
provided
.do.
*
*
*

*
*
*

Page 96 of 88

1.13

Switchyard

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 97 of 88

Sr.
No.

Description

Unit

Parameter

1.0

RATING

1.0

Switchyard Design &


layout

1.1

Rated Voltage

kV

90

1.2

1.2/50 Micro sec impulse


withstand voltage

kV

1.3

One minute power


frequency withstand
voltage

kV

1.4

Current ratings

1.5

a)

Continuous for Main


buses

Amp

2000 Amps

b)

Phase to phase

Amp

c)

Short time withstand


current and duration

kA &sec

40kA for 1 sec

Minimum air clearance


a)

Phase to phase

mm

900 mm

b)

Phase to ground

mm

900 mm

c)

Live point to ground

mm

4600 mm

d)

Section clearance

mm

4600 mm

1.6

Bay width

10

1.7

Phase to phase spacing

2.5

1.8

Size of the i) switchyard

Lx B

136x90

ii) switchyard
building

LxBx
H

136x90x15

1.9

Rev. 0 06.03.12

Design tensions

DocumentNo:P.003080E490457

Page 98 of 88

1.10

a) Main bus

Kg

To be furnished during
detail engineering

b) Bay bus

Kg

To be furnished during
detail engineering

a) Overhead conductors
for GT connection

Kg

To be furnished during
detail engineering

Total creepage distance for


all equipment

Ref-31mm/KV
mm

Indoor
Out door
1.11

Protected creepage
distance

1.12

Factor of safety adopted


for the structural design

1.13

mm

Ref-31mm/KV

a)

Normal condition

To be furnished during
detail engineering

b)

Short circuit condition

To be furnished during
detail engineering

c)

Seismic condition

To be furnished during
detail engineering

Type of design for Main &


bay buses
a)

Strung bus or tubular


bus

To be furnished during
detail engineering

b)

Material

To be furnished during
detail engineering

2.0

Circuit Breakers

2.1

Make, type, country of


manufacture

Asperapprovedvendorlist
provided

2.2

Applicable standard

As per IEC/EDF Standards

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 99 of 88

2.3

Rated voltage

2.4

Type of circuit breaker


(SF6)

SF6

2.5

Reference ambient
temperature

500C

2.6

Rated continuous current

Amp

1600Amps

2.7

Rated short circuit


breaking current and rated
making current

kA

40 KA for 1 sec

2.8

Temperature rise of
contacts over an ambient
of 450C while carrying
rated current

2.9

Rated operating duty

2.10

Total break time

msec

To be furnished during
detail engineering

2.11

Total make time

msec

To be furnished during
detail engineering

2.12

Rated transient recovery


voltage for terminal fault

kV

To be furnished during
detail engineering

2.13

Rated transient recovery


voltage for short line faults

kV

To be furnished during
detail engineering

2.14

No. of breaks in series

2.15

Insulation level

Rev. 0 06.03.12

kV

As per IEC/EDF Standards

100 KA(peak)
C

As per IEC/EDF Standards

0-0.3 sec-C0-3mins-CO

To be furnished during
detail engineering

a)

One minute P.F.


withstand voltage

kV

185

b)

Impulse withstand
voltage

kVp

450

c)

Switching surge
withstand voltage

kVp

To be furnished during
detail engineering

DocumentNo:P.003080E490457

Page 100 of 88

2.16

Minimum clearance in air


a)

Between live parts

mm

Ref-SLD

b)

Between live part &


earth

mm

Ref-SLD

c)

Centre to centre
distance between
phases

mm

Ref-SLD

2.17

Fixed trip or trip free

To be finalised during
detail engineering

2.18

Type of operating
mechanism

Spring-spring

2.19

Normal method of tripping

To be furnished during
detail engineering

2.20

Emergency method of
tripping

To be furnished during
detail engineering

2.21

No. of trip coils per phase

125 V DC

2.22

Range of voltage for


(a
)

Trip coils

To be furnished during
detail engineering

(b
)

Closing coils

To be furnished during
detail engineering

2.23

Rated line charging current

To be furnished during
detail engineering

2.24

Rated cable charging


current

To be furnished during
detail engineering

2.25

Maximum over voltage


when switching off

Rev. 0 06.03.12

(a
)

Unloaded transformer

To be furnished during
detail engineering

(b
)

Unloaded lines

To be furnished during
detail engineering

DocumentNo:P.003080E490457

Page 101 of 88

2.26

2.27

(c)

Cable charging

To be furnished during
detail engineering

(d
)

Capacitor banks

To be furnished during
detail engineering

When switching off a


synchronous system
(a
)

Maximum current

kA

To be furnished during
detail engineering

(b
)

Maximum recovery
voltage between
contacts

kA

To be furnished during
detail engineering

No. of operating circuit


breaker can perform
without inspection,
replacement of contacts
(a
)

At rated breaking
current

To be furnished during
detail engineering

(b
)

At rated continuous
current

To be furnished during
detail engineering

2.28

Creepage distance for the


interrupter insulator

mm

31 mm / KV

2.29

Creepage distance for the


interrupter insulator

mm

31 mm / KV

2.30

Cantilever strength of
circuit breaker at the
terminal pad

kg

To be furnished during
detail engineering

2.31

Whether pressure switches


for SF6 pressure low
alarm, trip, lockout closing,
lock out, opening are
provided

2.32

Compressed air system


details

Rev. 0 06.03.12

DocumentNo:P.003080E490457

YES

Page 102 of 88

(a) Type (unit / centralised)

To be furnished during
detail engineering

(b) Rated pressure

To be furnished during
detail engineering

(c) Time for the


compressor to charge to
reservoir from atmospheric
pressure

To be furnished during
detail engineering

(d
)

Time for the


compressor to
replenish the reservoir
from starting pressure
to rated pressure

To be furnished during
detail engineering

(e
)

Number of stored close


open operation before
lockout pressure is
reached

To be furnished during
detail engineering

(f
)

Whether pressure,
switches for start, stop
of compressor, high,
low alarm, close
lockout, open lockout,
auto reclose lockout
provided

To be furnished during
detail engineering

3.0

90kV Isolators

3.1

Make, type, and country of


manufacture

As per approved vendor


list

3.2

Reference standard

As per IEC/EDF Standards

3.3

Rated voltage & frequency

Volts,
Hz

90 KV/50Hz

3.4

Rated current

Amp

Ref-SLD

3.5

Reference ambient
temperature

50

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 103 of 88

3.6

Short time withstand


current & duration

kA. sec

40 KA for 1 sec

3.7

Dynamic withstand current

kAp

To be furnished during
detail engineering

3.8

Maximum temperature rise


of current carrying parts

3.9

Insulation Test values


(a)

50 0C

One minute P.F. wet


withstand voltage
(i)

Between poles
& earth

kV

To be furnished during
detail engineering

(ii)

Across isolating
distance

kV

To be furnished during
detail engineering

(i)
Between
poles & earth

kVp

To be furnished during
detail engineering

(ii)

kVp

To be furnished during
detail engineering

(b)
Impulse
withstand voltage

3.10

Across isolating
distance

Material
(a)

Main contact

To be furnished during
detail engineering

(b)

Arcing contact

To be furnished during
detail engineering

(c)

Current carrying
parts

To be furnished during
detail engineering

3.11

Whether contacts are


silver faced

3.12

Clearance
(a)

Rev. 0 06.03.12

Between poles

YES

mm

DocumentNo:P.003080E490457

To be furnished during
detail engineering

Page 104 of 88

(b)

Between live parts


and earth

mm

To be furnished during
detail engineering

(c)

Between live parts


when switch is open

(i)

Between same pole

mm

To be furnished during
detail engineering

(ii)

Between adjacent
pole

mm

To be furnished during
detail engineering

mm

To be furnished during
detail engineering

To be furnished during
detail engineering

3.13

Phase spacing

3.14

Type of interlock

Both interlock electrically


operated

(a)

External

(b)

Earth switch

3.15

Insulators

Solid core

(a)

Type of insulator (solid


core)

Horizontal,centre break

(b)

Cantilever strength

800 Kg

(c)

Total creepage distance

31 mm / KV

(d)

Applicable standards

As per IEC/EDF Standards

3.16

Operating
mechanism(motor/manual)

(a)

Main blade

Motorized & Manual

(b)

Earth blade

Motorized & Manual

4.0

90kV Current
Transformer

4.1

Make & country of


Manufacture

As per IEC/EDF Standards

4.2

Applicable standards

As per IEC/EDF Standards

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 105 of 88

4.3

Rated voltage class

90 Kv

4.4

Insulation withstand level

450 KV (peak)

(a)

Impulse withstand voltage


1.2/50 microsec wave

kV peak

To be furnished during
detail engineering

(b)

One minute power


frequency withstand
voltage

kV rms

To be furnished during
detail engineering

4.5

Number of cores per CT

4.6

Rated secondary current


for each core
1.1 Core 1

To be furnished during
detail engineering

2.1 Core 2

To be furnished during
detail engineering

3.1 Core 3

To be furnished during
detail engineering

4.1 Core 4

To be furnished during
detail engineering

5.1 Core 5

To be furnished during
detail engineering

6.1 Core 6

To be furnished during
detail engineering

4.7

Rev. 0 06.03.12

Ratio taps for each core

Core 1

To be furnished during
detail engineering

Core 2

To be furnished during
detail engineering

Core 3

To be furnished during
detail engineering

Core 4

To be furnished during
detail engineering

DocumentNo:P.003080E490457

Page 106 of 88

Core 5

To be furnished during
detail engineering

Core 6

To be furnished during
detail engineering

4.8

Whether it is possible to
adjust tap setting of any
core independent of other
cores

4.9

Relaying cores

To be furnished during
detail engineering

(a)

Accuracy class (for 5P20)

Shall be 0.2 sec for


metering cores

(b)

Rated burden (for 5P20)

(c)

Accuracy limit factor


(5P20)

(d)

Minimum knee point


voltage VK for PS class

Volts

To be furnished during
detail engineering

(e)

Maximum excitation
current at VK, VK/2 Volts
(for PS class

mA

To be furnished during
detail engineering

(f)

Maximum secondary
resistance (for PS class)

4.10

For metering cores :

a)

Accuracy class

To be furnished during
detail engineering

b)

Rated burden

To be furnished during
detail engineering

c)

Rated power factor

d)

Instrument security factor

Rev. 0 06.03.12

YES/ NO

VA

Yes

To be furnished during
detail engineering
To be furnished during
detail engineering

To be furnished during
detail engineering

VA

DocumentNo:P.003080E490457

To be furnished during
detail engineering
To be furnished during
detail engineering

Page 107 of 88

Short time thermal current


rating

40 KA for 1 sec.

a)

Current

kA

b)

Rated time

sec

4.12

Dynamic current rating

kA peak

100 KAp

4.13

Maximum temperature rise


of windings at rated
primary current and rated
burden, when referred to
specified ambient
temperature

To be furnished during
detail engineering

4.14

Class of insulation of
windings

4.15

Radio influence voltage

To be furnished during
detail engineering

4.16

Cantilever strength at
terminal

Kg

To be furnished during
detail engineering

4.17

Creepage distance of
insulator housing

31mm/KV

5.0

Voltage Transformer

5.1

Manufacturer and country


of manufacture

As per IEC/EDF Standards

5.2

Applicable standards

As per IEC/EDF Standards

5.3

Type of VT

As per IEC/EDF Standards

5.4

Insulation withstand level

To be furnished during
detail engineering

5.4.1

Impulse withstand voltage


1.20/50 micro sec.

Rev. 0 06.03.12

To be furnished during
detail engineering

Oil immersed,Class-A

kV peak

DocumentNo:P.003080E490457

450 KV (peak)

Page 108 of 88

5.4.2

One minute power


frequency withstand
voltage

5.5

Number of secondary
windings for each VT

5.6

Rated primary voltage

kV

90/3

5.7

Rated secondary voltage

110/3

5.8

Rated VA burden for each


secondary windings

VA

To be furnished during
detail engineering

5.9

Rated power factor

5.10

Accuracy class for each


secondary winding

5.10.1

Winding 1

To be furnished during
detail engineering

5.10.2

Winding 2

To be furnished during
detail engineering

5.10.3

Winding 3

To be furnished during
detail engineering

5.11

Method of connection

To be furnished during
detail engineering

5.11.1

Primary winding

5.11.2

Each
(a)
(b)
(c)

kV rms

185

secondary
winding

To be furnished during
detail engineering

NA

Winding 1
Winding 2
Winding 3

5.12

Rev. 0 06.03.12

Rated voltage factor

DocumentNo:P.003080E490457

1.2 continuous & 1.5 for


30 sec

Page 109 of 88

5.13

Maximum temperature rise


of windings at 110%
excitation and rated
burden, when referred to
specified ambient
temperature

5.14

Class of insulation of
windings

Oil immersed,Class-A

5.15

Capacitor data

To be furnished during
detail engineering

5.15.1

High voltage capacitance

pF

To be furnished during
detail engineering

5.15.2

Intermediate voltage
capacitance

pF

To be furnished during
detail engineering

5.15.3

Nominal intermediate
voltage

kV

90/110

5.15.4

Equivalent capacitance for


carrier coupling

pF

To be furnished during
detail engineering

5.15.5

Maximum permissible
impedance at power
frequency

Ohms

To be furnished during
detail engineering

5.16

Total creepage distance

mm

31mm/KV

5.17

Radio influence voltage

Volts

To be furnished during
detail engineering

5.18

Details of high speed


switch(es) on secondary
winding (alternative to
fuses)

5.18.1

Make, type, rating , coil


rating, other technical
details

Amp

As per IEC/EDF Standards

5.19

Cantilever strength

Kg

As per IEC/EDF Standards

6.0

Lightning Arresters

Rev. 0 06.03.12

As per IEC/EDF Standards

To be furnished during
detail engineering

DocumentNo:P.003080E490457

Page 110 of 88

6.1

Makers Name and Type


and country of
manufacture

As per IEC/EDF Standard

6.2

Arrester type

As per IEC/EDF Standards

6.3

Applicable standards

As per IEC/EDF Standards

6.4

Arrester class

kV

As per IEC/EDF Standards

6.6

Rated frequency

Hz

50

6.7

Nominal discharge current


(8/20 micro seconds wave)

kA

20

6.8

Minimum discharge
capability

KJ/kV

As per IEC/EDF Standards

6.9

Residual voltage
corresponding to

kV
(peak)

6.9.1

Steep current impulse

As per IEC/EDF Standards

6.9.2

Lighting impulse

As per IEC/EDF Standards

6.9.3

Switching impulse

As per IEC/EDF Standards

6.10

Reference voltage (TEC


TC37-WG-4 1985)

To be furnished during
detail engineering

6.11

Reference voltage (TEC


TC37-WG-4 1985)

kV(rms)

To be furnished during
detail engineering

6.12

Overvoltage withstand
capability for :

6.13

Rev. 0 06.03.12

a)

10 cycles

kV(rms)

To be furnished during
detail engineering

b)

1 second

kV(rms)

To be furnished during
detail engineering

c)

Continuous

kV(rms)

To be furnished during
detail engineering

KJ/kV

To be furnished during
detail engineering

Energy discharge capacity

DocumentNo:P.003080E490457

Page 111 of 88

6.14

Maximum residual voltage


at nominal discharge
current

kV(rms)

To be furnished during
detail engineering

6.15

Discharge voltage at 5kA


discharge current

kV(peak
)

To be furnished during
detail engineering

6.16

Discharge voltage at 10 kA
discharge current

kV(peak
)

To be furnished during
detail engineering

6.17

Discharge voltage at 20 kA
discharge current

KV(peak
)

To be furnished during
detail engineering

6.18

Impulse current withstand


(a)

High current
short
duration
(4/10 micro
second
wave)

kV(peak
)

To be furnished during
detail engineering

(b)

Low current
long duration

A(peak)

To be furnished during
detail engineering

(c)

Virtual
duration of
rectangular
wave

Microsecond

To be furnished during
detail engineering

6.19

One minute power


frequency (dry) withstand
voltage of arrester housing

kV(rms)

To be furnished during
detail engineering

6.20

Impulse withstand test


voltage of arrester housing
with 1.2/50 micro-second
wave

kV(peak
)

450KVp (peak)

6.21

Total creepage distance of


whole arrester housing

mm

31mm/kv

6.22

Cantilever strength of
complete arrester

kg

800 ( minimum)

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 112 of 88

6.23

Pressure relief class (as per


IEC 60099)

6.24

Routine Tests

6.25

a)

Measuremen
t of
reference
voltage test

Yes/No

Yes

b)

Residual
voltage test

Yes/No

Yes

c)

Leakage
check for
arrester units
with sealed
housings

Yes/No

Yes

d)

Current
distribution
test for
multi-column
arrester

Yes/No

Yes

Yes/No

Yes

Acceptance Tests
(a)

Rev. 0 06.03.12

To be furnished during
detail engineering

Measuremen
t of power
frequency
voltage on
the complete
arrester at
the reference
current
measured at
the bottom
of the
arrester

DocumentNo:P.003080E490457

Page 113 of 88

(b)

Lighting
impulse
residual
voltage on
the complete
arrester or
arrester unit
at nominal
discharge
current

Yes/No

Yes

(c)

Partial
discharge
test at 1.05
times
continuous
operating
voltage

Yes/No

Yes

7.0

Insulator and hardware


(Fill in for bus post
Insulator as well as
insulator string)

7.1

Insulator / Insulator string

Rev. 0 06.03.12

(a)

Manufacturer
and country
of
manufacture

As per IEC/EDF Standards

(b)

Applicable
standard

As per IEC/EDF Standards

(c)

Type of
insulator
(Antifog /
normal)

Solid core

(d)

Insulating
material

To be furnished during
detail engineering

DocumentNo:P.003080E490457

Page 114 of 88

(e)

No. of units
per string

(f)

Creepage
distance
(i) disc unit

mm

To be furnished during
detail engineering

mm

(ii) string
assembly
(g)

One minute
power
frequency
withstand
dry

To be furnished during
detail engineering
kV
kV

(i) single
disk
(ii) string
assembly /
bus post
(h)

One minute
power
frequency
withstand
(wet)

To be furnished during
detail engineering
kV
kV

i) disk unit
ii) string
assembly /
bus post

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 115 of 88

(i)

Impulse
withstand
voltage (dry)

kVp

To be furnished during
detail engineering

kVp
ii)

disk
unit

ii) string
assembly /
bus post
(j)

Impulse
withstand
voltage (wet)

kVp

To be furnished during
detail engineering

kVp
i) disk unit
ii) string
assembly /
bus post

Rev. 0 06.03.12

(k)

Electro
mechanical
strength of
each disk

kg

To be furnished during
detail engineering

(l)

Live parts to
earth
clearance
(spark over
distance)

mm

To be furnished during
detail engineering

(m)

Cantilever
strength (for
bus post
insulator
only)

kg

To be furnished during
detail engineering

DocumentNo:P.003080E490457

Page 116 of 88

7.2

(n)

Tensile
strength (for
bus post
insulator
only)

kg

To be furnished during
detail engineering

(o)

Compression
strength (for
bus post
insulator
only)

kg

To be furnished during
detail engineering

(p)

Visual
discharge
voltage for
falling power
frequency
voltage
(string and
bus post
insulator)

kg

To be furnished during
detail engineering

Insulator Hardware
(a)

Manufacturer

As per IEC/EDF Standards

(b)

Applicable
standard

As per IEC/EDF Standards

(c)

All ferrous
parts are hot
dip
galvanised

8.0

Bus Conductors, Clamps


and Connectors

8.1

Flexible Conductor

Rev. 0 06.03.12

Yes/No

Yes

AAC/AC
SR

Aster

DocumentNo:P.003080E490457

Page 117 of 88

8.2

(a)

Size of
conductor for
main bus
and bus
coupler bay
buses

To be furnished during
detail engineering

(b)

Size of
conductor for
other bay
buses,
transfer bus

To be furnished during
detail engineering

(c)

The
temperature
rise of the
conductor
while
carrying the
rated current

To be furnished during
detail engineering

(d)

Purity of
Aluminium /
copper

To be furnished during
detail engineering

Tubular Conductor

(a)

Rev. 0 06.03.12

Alumini
um
tube

Size of the
tabular
conductor for
bus

DocumentNo:P.003080E490457

To be furnished during
detail engineering

Page 118 of 88

8.3

8.4

Rev. 0 06.03.12

(b)

The
temperature
rise of the
tabular
conductor
while
carrying the
rated current

To be furnished during
detail engineering

(c)

Purity of
Aluminium/c
opper

To be furnished during
detail engineering

a)

Material of
the shield
wire

To be furnished during
detail engineering

b)

Size of the
shield wire

To be furnished during
detail engineering

Shield wire

Clamps and connectors


(a)

Whether material
specification of the
clamps and
connectors are as
per specification

Yes/No

Yes

(b)

Temperature rise of
the clamp while
carrying the rated
current

To be furnished during
detail engineering

(c)

Minimum thickness
at any part of the
clamps

mm

To be furnished during
detail engineering

(d)

Corona extinction
voltage for falling
power frequency
voltage.

To be furnished during
detail engineering

DocumentNo:P.003080E490457

Page 119 of 88

(e)

Wedge type
connectors

Yes

Yes

9.0

SWITCHYARD CONTROL
PANEL (SCP)

9.1

Make and country of


manufacture

As per IEC/EDF Standards

9.2

Degree of protection for


enclosure

As per IEC/EDF Standards

9.3

Applicable standards

As per IEC/EDF Standards

9.4

Indicating Meters

yes

9.4.1

Meter size

9.4.2

Accuracy

As per EDF Std.

9.4.3

Type

Analog/Digital

9.5

MWHr / MVARHr Energy


meters

Yse

9.5.1

Accuracy (Required 0.2S)

Yes

9.5.2

Whether retransmission
contact provided
(Required)

Yes

9.6

Transducers

Yes

9.6.1

Accuracy

yes

9.6.2

Output current

To be furnished during
detail engineering

9.6.3

No. of channels

To be furnished during
detail engineering

9.6.4

Type No. & Make

As per approved vendor


list

Rev. 0 06.03.12

mm

DocumentNo:P.003080E490457

48x48 or 96x96

Page 120 of 88

9.7

Whether annunciators
scheme, features,
sequence and size are
same as the one offered
for plant control system

yes

9.8

Mimic material and width


in mm

To be furnished during
detail engineering

10.0

Switchyard Relay Panel

10.1

Panel make and country of


manufacture

As per approved vendor


list

10.2

Degree of protection for


enclosure of panel

IP-43

10.3

Mounting of relays

Front-Top

10.3.1

On conventional panels

Front mounting

10.3.2

On pre-engineered panel

Front mounting

10.4

Relay Particulars

To be furnished during
detail enginering

10.4.1

Control voltage

127 V

10.4.2

Current rating

50 KA for 1 sec

10.4.3

Voltage rating

AC supply 415V/240 V,3


Ph,4 wire

10.4.4

Operating temperature
range

Ambient Temp.

10.4.5

Applicable standards

As per IEC/EDF Standards

10.4.6

Aux. supply operating


range

10.4.7

On line automatic testing


facility provided

Yes

10.4.8

On line manual testing


facility provided

Yes

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 121 of 88

10.5

Relay types offered (list


each relay and furnish the
data)

10.6

All the relays offered are


type tested

10.7

If no which are all not type


tested

Rev. 0 06.03.12

As per approved vendor


list
Yes / No

DocumentNo:P.003080E490457

yes
NA

Page 122 of 88

1.14

Cable

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 123 of 88

Sr.
No.
1.0
2.0

NameoftheManufacturer
Conductor

Asperapprovedvendorlist
Strandedandcompactedcopperor
Aluminium

3.0
4.0
5.0

No.CoreXSize
Formcircular/segmented
Effectivecrosssectionalarea

Aspersystemrequirement
circular
Min2.5

6.0

Singlecorepowercablesarmouring

Galvanised single round

7.0

Multicorepowercablearmouring

steel wire
Galvanised single round

8.0

Whethercoresidentificationnumbers

Description

Unit

sq.mm

Parameter

Max6

steel wire
Yes

forcableswith5coresandabovetobe
9.0

provided
Whetherincrementalrunninglengths

10.0
10.1
10.2
10.3
11.0
11.1

aremarkedoncable
FinishedCable
Diameterunderarmour
Diameteroverarmour
Overalldiameter
Cabledrums
WhetercabledrumsconfirmtoIS:

11.2
11.3
11.4
11.5
12.0
12.1

10417
Lengthofcablesindrum&tolerance
Weightofcabledrumwithoutcables
Weightofcabledrumwithcables
Typeofendsealing
FRLSCables
Criticaloxygenindexvalueatroom

*
AsperIEC/EDFstandards
mm
mm
mm

km
kg
kg

TobedecidedduringDE
..do..
..do..

29

temp.whentestedasperASTMD
12.2

2863
Temp.indexvalueat21Oxygenindex

2500C

whentestedasperASTMD2863/
12.3

NES7151
Totalacidgasgenerationbyweight

Lessthan20%

12.4

whentestedasperIEC7541in%
c)Smokegenerationunderfirewhen

60%

testedasperASTMD2843insmoke

Rev. 0 06.03.12

DocumentNo:P.003080E490457

Page 124 of 88

Sr.
No.
12.5

Description

Unit

Parameter

densityrating
d)Willthecablesofferedagainstthis

specificationpasstheflammability

testsasper
1.ClassF3SwedishstandardSS

Yes

4241475
2.IEC3321
3.IEC3311

Yes
Yes

13.0

WhetherCablepassthehydraulic

Yes

stabilityandultraviolettestsasper
14.0

DIN53377
WhetherFinishedCablepassthe

15.0

flammabilitytestasperIEC60322
Maximumdielectriclossofcableas

Yes
Watt/km

perkmatnormalvoltageand
16.0
17.0

frequency
Shortcircuitcapabilityfor1Sec
Maximumdielectricstressatcore

kArms
kV/cm

18.0

screen
Maximumoveralldiameterofcables

mm

NOTE:

* Information shall be filled furnished by CONTRACTOR along with offer

Rev. 0 06.03.12

DocumentNo:P.003080E490457