ERECTION AND COMMISSIONING CHECK LIST FOR CURRENT TRANSFORMERS


i)

Name of substation : 66 KV Sub-Station ii)Date of Erection:______________________

iii)

Date of Energization_______________________________
Feeder Name/Bay name:_
1.

Tan Delta and Capacitance Measurement (By Automatic Tan Delta Kit)
Details of Test Kit:Megger 4000
A Voltage Capacitance (Measured Value)
Remarks
R-Phase
Y-Phase
B-Phase
5 KV
175.3
175.5
173.9
10 KV 175.5
175.9
173.9
Voltage
5 KV
10 KV

Tan Delta (Measured Value in %)


R-Phase
Y-Phase
0.213
0.203
0.213
0.203

Remarks
B-Phase
0.205
0.205

xvi) Current Ratio Test


Primary Injection through Primary Injection Kit at Primary Terminal P1 P2
Measure Current on the Secondary Terminals which found OK.
LIGHTENING ARRESTERS
i)

Region: ______________________ ii) Date of Erection:______________________


iii)

Date of Energization_______________________________

Detail of Equipment:
LOA No.______________________
Make:-________________________
Type:_________________________
Sl. No.______________ R-Phase:_____________ Y-Phase:___________ B-Phase:____________
Year of Manufacture:_____________________ Feeder Name:_____________________________
v)

Rating:
Voltage Rating:
vii) Insulation Resistance Measurement :
(Using 5KV Megger)
SL. No.

Min: Value >1000 M Ohms

Between
R

1.
2.
3.
4.
5.
6.

1st Stack & Earth


2nd Stack & Earth
3rd Stack & Earth
4th Stack & Earth
5th Stack & Earth
6th Stack & Earth

viii) Surge Counter Reading

Phase
Y

B
MOHM
MOHM
MOHM
MOHM

SL. No.

Reading

1.
2.
3.

Counter Sr. No.


Counter Make
Counter Reading

Phase
Y-Phase

R-Phase

x) Checking of healthiness of Surge Monitor


Refer Manufacturers Catalogue for detail checking of Surge Monitor
i)
ii)

CIRCUIT BREAKER

iii)

Date of Energization_______________________________

iv)

Detail of Equipment:

B-Phase

OK

Not OK

Region: ______________________ ii) Date of Erection:______________________

LOA No.______________________
Make:-________________________
Type:_________________________
Sl. No.______________
Year of Manufacture:_____________________ Feeder Name:_____________________________
Operating Voltage: ____________kV
Rated Breaking Capacity:
Control Voltage: __________________ Volt DC

16.0

Operating Time (In Milli. Seconds)


Phase

R-PH Main contact


R-PH PIR
Auxiliary Contact
R-PH Main contact
R-PH PIR
Auxiliary Contact
R-PH Main contact
R-PH PIR
Auxiliary Contact
R-PH Main contact
R-PH PIR
Auxiliary Contact
R-PH Main contact
R-PH PIR
Auxiliary Contact
R-PH Main contact
R-PH PIR
Auxiliary Contact

Break

Close

Trip
Trip-I
Trip-II

Break 1
Break 2
Break 1
Break 2
Break 1
Break 2

Note: For 765 KV, Take measurement for Breaks


17.0 IR Value of Control Circuit :
Using 500 Volt Megger

Close Trip. Using


Trip-I
Trip-II

Minimum Value 2 MOHM


Caution: Isolate necessary DC for trip coil I and trip Coil-II, closing coil before
meggering.

18.0 IR Value with Breaker Open:


Across Open Contact
R-Phase Break 1
R-Phase Break 2
Y-Phase Break 1
Y-Phase Break 2
B-Phase Break 1
B-Phase Break 2
19.0 IR Value with respect to Earth with Breaker
Close, Earth Switch and Isolator Open :
Using 5000 Volt Megger
Across Open Contact
R-Phase and Earth
Y-Phase and Earth
B-Phase and Earth

22.

Contact Resistance Measurement :


SL.
Phase
Across Each Pole
No.
Factory
Site
A.
R-Phase
B.
Y-Phase
C.
B-Phase

Using 5000 Volt Megger


Minimum Value 1000 MOHM
Measurement Value
MOHM
MOHM
MOHM
MOHM
MOHM
MOHM

Minimum Value 1000 MOHM


Measurement Value
MOHM
MOHM
MOHM

Across Interrupter 1
Factory
Site

Across Interrupter 2
Factory
Site

Factory Test Report Ref No. _____________________

ISOLATORS AND EARTH SWITCHES

Region: ______________________________________II. Date of Erection:___________________

III.

Date of Energization_____________

IV.

Detail of Equipment:
LOA No.__________________________________

Make:-____________________________________
Type:_____________________________________
Rating_____________________________________
Sl. No.

R-Phase___________ Y-Phase________________ B-Phase______________

Year of Manufacture:_________________________
V.

Feeder Name:_66KV Link Line_________________________________

VI.

Operating Voltage:_66KV

VII.

Current carrying Capacity:_2500 Ampere

VIII.

Control Voltage:

Type of operating Mechanism_Spring Coil

__220 Volt DC

IX.

XII.

Operational checks:
A.

Operate the Isolator and record the Motor current


Isolator
operatio
n
Close
Open

B.

R-Phase
Factory
Site

Control Panel
Local

C.

XIV.
A.

B-Phase
Factory
Site

Operation of Isolator from local/ remote OK/Not OK


Isolator
operatio
n

Motor Current
Y-Phase
Factory
Site

Remote

Measurement of operating time


Operation
R-Phase
Opening Time
Closing Time

Phase
Y-Phase

B-Phase

Contact Resistance Measurement


(To be measured after 50 operations)
Isolator close condition
(Contact Resistance should be less than 10 Micro Ohms / connector)

Sec.
Sec.

Across

Phase
R-Phase

Y-Phase

B-Phase

Connector (Male Side)


Connector (Female Side)
Main Connector (Male & Female side)
B.

Micro - Ohm
Micro - Ohm
Micro - Ohm

Isolator open condition and ground switch close


(Contact Resistance should be less than 150 Micro Ohms /Break)
Across
R-Phase
Main contact (Male & Female)
(Ground Switch)

Phase
Y-Phase

B-Phase
Micro - Ohm