Section 11

SWITCHES,
STARTERS,
CONTROLS, AND
GUTTERS
Manhour units for the installation of such items as externally operated safety switches, circuit breakers, motor control devices, auxiliary gutters, junction boxes, terminal cabinets, service entrance switches, meter troughts,
transformer cabinets, and meter test cabinets are included
in this section.
Consideration has been given to all labor operations as required for the installation of the individual item in accordance with the notes appearing with the tables.
Various labor operations that may be required to support
the complete installation of all items for the particular
block of work may be found under other sections of this
manual.

EXTERNALLY OPERATED SAFETY SWITCHES


GENERAL PURPOSE TYPE ENCLOSURE
25OVoIt Fusible and Nonfusible
Separate Installation
MANHOURS EACH
Maximum

Amperage
blze

30
60
100
200
400
600
800
1,200

Fusible
Nonfusible
2-Pole I 2-Pole I 3-Pole I 3-Pole 2-Pole I 2-Pole I 3-Pole I 3-Pole
2-Wire 3-Wire 3-Wire 4-Wire 2-Wire 3-Wire 3-Wire 4-Wire

Lug

Capacity
#14-#6
#14-#2
#14-#l/0
#6-#250MCM
2-#4-#250MCM
2-#2-#600MCM
3-#l/0-#600MCM
14-ai/0-#500MCM |

2.20
2.70
3.00
4.90
7.70
10.40
14.40
19.80 |

2.40 2.40
3.00 3.00
3.30 3.30
5.30 5.30
8.50 8.50
11.50 11.50
15.80 15.80
21.80 | 21.80 |

2.60
3.20
3.50
5.80
9.20
12.40
17.10
23.50 |

1.70
2.30
2.50
4.40
7.30
10.00
14.00
18.90 |

1.90
2.50
2.80
4.90
8.00
11.00
15.30
20.80 |

1.90 2.00
2.50 2.70
2.80 3.00
4.90 5.20
8.00 8.70
11.00 11.90
15.30 16.60
20.80 | 22.50

Combination Installation
MANHOURS EACH
Maximum
A
Amperage
Lug
^lze
Capacity
30
#14-#6
60
#14-#2
100
#14-#l/0
200
#6-#250MCM
400
2-#4-#250MCM
600
2-#2-#600MCM
800 3-#l/0-#600MCM
1,200 |4-#l/0-#500MCM|

Fusible
Nonfusible
2-Pole I 2-Pole I 3-Pole I 3-Pole 2-Pole I 2-Pole I 3-Pole I 3-Pole
2-Wire 3-Wire 3-Wire 4-Wire 2-Wire 3-Wire 3-Wire 4-Wire
2.60 2.90 2.90 3.10 2.20 2.40 2.40 2.60
3.60 4.00 4.00 4.30 3.20 3.50 3.50 3.70
3.90 4.30 4.30 4.60 3.40 3.80 3.80 4.10
5.80 6.30 6.30 6.80 5.30 5.80 5.80 6.30
8.60 9.50 9.50 10.30 8.20 9.00 9.00 9.70
11.30 12.50 12.50 13.50 10.90 12.00 12.00 12.90
15.30 16.80 16.80 18.20 14.90 16.30 16.30 17.60
20.70 | 22.80 | 22.80 | 24.60 | 19.80 | 21.80 | 21.80 | 23.50

Manhours include checking out of job storage, handling, job hauling, distributing, positioning, and
conductor terminations of switches as outlined.
Manhours exclude fastening or field cut knockouts. See respective tables for these time frames.
Separate installation involves the installation of the individual switch and does not require the
detailed layout of the combination installation. The combination installation manhours reflect the
additional layout time required.

EXTERNALLY OPERATED SAFETY SWITCHES


GENERAL PURPOSE TYPE ENCLOSURE
6OO-Volt Fusible and Nonfusible
Separate Installation
MANHOURS EACH
.
Amperage
IZC

30
60
100
200
400
600
800
1,200

Maximum
L u g

Capacity

Fusible
Nonfusible
2-Pole I 2-PoIe I 3-Pole I 3-Pole 2-Pole I 2-Pole I 3-Pole I 3-Pole
2-Wire 3-Wire 3-Wire 4-Wire 2-Wire 3-Wire 3-Wire 4-Wire

#14-#6
2.60 2.90 2.90
#14-#2
3.20 3.50 3.50
#14-#l/0
3.40 3.80 3.80
#6-#250MCM
5.80 6.30 6.30
2-#4-#250MCM
8.60 9.50 9.50
2-#2-#600MCM
11.30 12.50 12.50
3-#l/0-#600MCM 15.30 16.80 16.80
|4-#l/0-#500MCM| 20.70 | 22.80 | 22.80 |

3.10 2.20 2.40 2.40


3.70 2.70 3.00 3.00
4.10 3.00 3.30 3.30
6.80 5.30 5.80 5.80
10.30 8.20 9.00 9.00
13.50 10.90 12.00 12.00
18.20 14.90 16.30 16.30
24.60 | 19.80 | 21.80 | 21.80 |

2.60
3.20
3.50
6.30
9.70
13.00
17.60
23.50

Combination Installation
MANHOURS EACH
Maximum
Amperage
blze

30
60
100
200
400
600
800
1,200

L u g

Capacity

Fusible
Nonfusible
2-Pole I 2-Pole I 3-Pole I 3-Pole 2-Pole I 2-Pole I 3-Pole I 3-Pole
2-Wire 3-Wire 3-Wire 4-Wire 2-Wire 3-Wire 3-Wire 4-Wire

#14-#6
3.10 3.40 3.40
#14-#2
4.10 4.50 4.50
#14-#l/0
4.30 4.80 4.80
#6-#250MCM
6.20 6.80 6.80
2-#4-#250MCM
9.10 10.00 10.00
2-#2-#600MCM
11.80 13.00 13.00
3-#l/0-#600MCM 15.80 17.30 17.30
4-#l/0-#500MCM| 21.20 | 23.30 | 23.30 |

3.60
4.80
5.10
7.40
10.80
14.00
18.70
25.10 |

2.60
3.60
3.90
5.80
8.60
11.30
15.30
20.70 |

2.90
4.00
4.30
6.30
9.50
12.50
16.80
22.80 |

2.90 3.10
4.00 4.30
4.30 4.60
6.30 6.80
9.50 10.30
12.50 13.50
16.80 18.20
22.80 | 24.60

Manhours include checking out of job storage, handling, job hauling, distributing, positioning, and
conductor terminations of switches as outlined.
Manhours exclude fastening or field cut knockouts. See respective tables for these time frames.
Separate installation involves the installation of the individual switch and does not require the
detailed layout of the combination installation. The combination installation manhours reflect the
additional layout time required.

CIRCUIT BREAKERS
Separate and Combination Installation
MANHOURS EACH
Trip
Amperage
Range

Maximum
Lug
Capacity

Separate
Combination
2-Pole I 2-Pole I 3-Pole I 3-Pole 2-Pole I 2-Pole I 3-Pole I 3-Pole
2-Wire 3-Wire 3-Wire 4-Wire 2-Wire 3-Wire 3-Wire 4-Wire

15-50
#4
3.00 3.30 3.30 3.60 4.20 4.50 4.50 4.80
70-100
#1
3.60 4.40 4.40 5.00 4.80 5.60 5.60 6.20
70-125
#1/0
5.20 6.00 6.00 6.30 6.40 7.20 7.20 7.80
125-225
#1/0
5.00 5.80 5.80 6.50 6.20 7.00 7.00 7.70
125-225
#250 MCM
8.40 9.60 9.60 10.80 9.60 10.80 10.80 12.00
150-225
#300 MCM
7.00 8.00 8.00 9.20 8.20 9.20 9.20 10.30
150-225
#4/0
6.50 7.60 7.60 8.60 7.70 8.80 8.80 9.80
250-400
2-#250MCM
10.80 12.60 12.60 14.40 13.20 15.00 15.00 16.80
250-400
l-#600MCM
10.80 12.60 12.60 14.40 13.20 15.00 15.00 16.80
125
#1/0
6.60 7.50 7.50 8.10 7.80 8.70 8.70 9.30
250
#4/0
6.90 8.10 8.10 9.30 8.10 9.30 9.30 10.50
250
2-#250MCM
8.40 9.60 9.60 10.80 10.80 12.00 12.00 13.20
250
l-#600MCM
8.40 9.60 9.60 10.80 10.80 12.00 12.00 13.20
400
#4/0
11.40 12.90 13.80 15.30
400
2-#500MCM
10.80 12.60 12.60 14.40 13.20 15.00 15.00 16.80
400
l-#600MCM
10.80 12.60 12.60 14.40 13.20 15.00 15.00 16.80
600
2-#500MCM
12.65 14.40 14.40 16.80 15.00 16.70 16.70 18.40
600
l-#600MCM
12.65 14.40 14.40 16.80 15.00 16.70 16.70 18.40
800
3-#500MCM
15.40 17.10 17.10 18.70 17.60 19.30 19.30 20.90
800
2-#600MCM
15.40 17.10 17.10 18.70 17.60 19.30 19.30 20.90
1,000
I 3-#600MCM | 18.70 | 20.40 | 20.40 | 22.00 | 20.90 | 22.60 | 22.60 | 24.20
Manhours include checking out of job storage, handling, job hauling, distributing, positioning, and
conductor terminations of switches as outlined.
Manhours exclude fastening or field cut knockouts. See respective tables for these time frames.
Separate installation involves the installation of the individual switch and does not require the
detailed layout of the combination installation. The combination installation manhours reflect the
additional layout time required.

MAGNETIC STARTERS
Reversing Magnetic Starters
MANHOURS EACH
N E M A

~.
O
0
1
1
2
3
4
5

HP
1-2
3-5
2-3
7-1/2-10
15-25
30-50
50-100
I 100-200

Voltage

1 -Phase
3-Phase
Separate
Combination
Separate
Combination
~2-Pole I 3-Pole" 2-Pole 1 3-P"ole~ 3-Pole I 4-Pole " 3 ^ 1 e 1 4-Pole

115-230
208-550
115-230
208-550
208-550
208-550
208-550
208-550

3.00
4.10
-

4.10

3.60

4.70

5.20

4.70

5.80

4.70
5.50 5.20 6.00
6.30
7.70
6.90 8 2 9
9.30
9.70
9.60 9.90
11.30 13.50 11.80 14.00
18.90 22.60 19.40 23.10
28.30 32.50 29.40 33.60

Nonreversing Magnetic Starters


MANHOURS EACH
TPhase

Mr-** A

NEMA
Size
0
0
0
1
1
1
2
2
2
2
3
4
5

H p

1
2
2-5
2
3
3-10
3
7-1/2
10
7-1/2-25
15-50
50-100
1 100-200 1

^ r> i

^6

115
230
110-550
115
230
110-550
115
230
440-550
110-550
110-550
208-550
208-550 |

2-PoIe
Separate
Combination
2.20
2.20
2.45
2.45
2.75
3.30
3.85
-

2.75
2.75
3.00
3.00
~
3.30
3.85
4.40
~
-

J-rnase

Separate
Combination
3-Pole 1 4-PoIe" 3-Pole I 4-Pole
2.75
4.10
6.00
7.70
13.10
1 20.00 |

3.55

3.30

4.10

4.95

4.65

5.50

6.85
8.80
14.14
24.15 |

6.60
7 40
8.25
9.35
13.65 15.75
21.00 [ 25.20

Manhours include checking out of job storage, handling, job hauling, distributing, positioning, and
conductor terminations of starters as outlined.
Manhours exclude fastening or field cut knockouts. See respective tables for these time frames.
Separate installation involves the installation of the individual starter and does not require the
detailed layout of the combination installation. The combination installation manhours reflect the
additional layout time required.

MAGNETIC STARTERS
Circuit Breaker and Starter or
S w i t c h and Starter Combination
MANHOURS EACH

"TZTTTl
r/
0
1
2
3

I
HP

I
Voltage

1-5
5-10
10-25
I 20-50 I

3-Phase, 3-Pole
Reversing
Separate
Combination

208-550
208-550
208-550
208-550 |

8.25
11.00
14.30
18.15 |

8.50
11.55
14.85
18.70

Nonreversing
Separate
Combination

5.50
8.25
10.45
14.30

6.00
8.80
11.00
14.85

Pushbutton Stations
MANHOURS EACH
Number of
Positions

Stations
Separate

2
3
4
5
6

Combination

0.80
1.10
1.35
1.65
L90

1.10
1.35
1.65
1.90
2.20

Pilot
Light
1.65
1.90
2.20
2.45
2.75

Manual Motor Starting Switches


MANHOURS EACH
NPMA

Size
0
1
2

Separate Installation
1-Phase
I 3ThIsI
Toggle
Pushbutton Pushbutton
1.65
1.90
I 2.45 I

1.90
2.20
2.75

2.75
3.55
4.10

Combination Installation
1-Phase
I 3-Phase
Toggle
Pushbutton Pushbutton

2.20
2.45
3.00 |

2.45
2.75
3.30

3.00
3.85
4.40

Manhours include checking out of job storage, handling, job hauling, distributing, positioning, and
conductor terminations of starters, stations, and switches as outlined.
Manhours exclude fastening or field cut knockouts. See respective tables for these time frames.
Separate installation involves the installation of the individual item and does not require the detailed
layout of the combination installation. The combination installation manhours reflect the additional
layout time required.

DRUM SWITCHES
1-Speed Drum Switches
MANHOURS EACH
Horsepower
P

NEMA
Size

1-Phase
2-or3-Phase
110V.I220V. U0V.|220V.|550V.

1
1
2
2

1-1/2 3

5 7-1/2
15
15
10
10
100 100

Reversing
Drum Switches
Separate Combination
1.65
2.20

I - I - I - I 2 0 I 4Q I 4 . 4 0 I

Nonreversing
Drum Switches
Separate Combination

2.20

8.80

2.75
-

11.00

19.80

4.93 |

22.00

2-Speed Drum Wwitches


MANHOURS EACH
Kf~.,A
N M A

TT

Horsepower
HOV. I 220 V. I 550 V.

IZC

00
0
1
2
3
4
5

3/4
1-1/2
3

3/4
2
5
15
20
40

3/4
2
7-1/2
15
40
75
150

Reversing
Drum Switches
Separate Combination
2.55
4.10
4.95
5.50
8.25
14.30
23.10

4.65
5.20
6.00
6.60
9.90
16.50
25.30

Nonreversing
Drum Switches
Separate | Combination

1.90
2.45
3.30
3.85
6.00
11.00
19.80 |

3.00
3.55
4.40
4.95
7.70
13.20
22.00

Manhours include checking out of job storage, handling, job hauling, distributing, positioning, and
conductor terminations for switches as outlined.
Manhours exclude fastenings or field cut knockouts. See respective tables for these time frames.
Separate installation involves the installation of the individual switch and does not require the
detailed layout of the combination installation. The combination installation manhours reflect the
additional layout time required.

CONTROL DEVICES
MANHOURS EACH
Time Switches
.
y .

General Description
Operating Posittons
S.P.S.T. S.P.S.T. S.P.D T S.P.D.T. D.P.S.T. D.P.S.T. S.P.S.T S.P.S.T. D.P.D.T. S.P.S.T. -

Off-On - 24 Hrs.
Off-On - 24 Hrs.
Intermittent - 24 Hrs.
Intermittent - 24 Hrs.
Industrial Type
Industrial Type
Program Intervals
T-Rated Astrodial
4-Pole - T-Rated
4-Pole - T-Rated

1.50
6.5
10.0
5.0
55.0
55.0
5.0
40.0
40.0
20.0

Enclosed Magnetic Relays


Number
Manhours
of Poles
Separate
Combination

Installation
Separate
Combination

120
240
120
240
120
240
120
120/208
120/208
120/208

2.20
2.20
3.00
3.00
3.55
3.55
3.85
4.40
4.95
4.65

2.75
2.75
3.55
3.55
4.10
4.10
4.40
4.95
5.50
5.20

PressureFloatLimit Switches
Type of
Manhours
Switch
Separate
Combination

1
1.10
1.65
Pressure-S.P.
0.80
1.35
2
1.35
1.90
Pressure-D.P
1.35
1.90
3
1.65
2.20
Pressure-Four P
1.90
2.45
4
1.90
2.45
Float-S.P.
1.10
1.65
5
2.20
2.75
Float-D.P.
1.65
2.20
6
3.00
3.55
Float-Four P.
2.20
2.75
7
3.85
4.40
Limit-S.P
1.35
1.90
8
4.65
5.20
Limit-D.P.
1.90
2.45
I
I
I Limit-Four P
|
2.45
|
3.00
Manhours include checking out of job storage, handling, job hauling, distributing, positioning, and
conductor terminations of control devices as outlined.
Manhours exclude fastening or field cut knockouts. See respective tables for these time frames.
Separate installation involves the installation of the individual item and does not require the detailed
layout of the combination installation. The combination installation manhours reflect the additional
layout time required.

REDUCED VOLTAGE STARTERS


MANHOURS EACH FOR SEPARATE INSTALLATION
Reduced Voltage Starters
Nonreversing
Reversing
NEMA Horsepower
Voltage
3-Phase, 3-Pole
3-Phase, 3-Pole
Size
Range
Range
~ T~
I
Auto
~ T~ I
Auto
6
6
Resistor
_,
.
Resistor
_
c
Transformer
Transformer
1
5-10
208-550
18.90
21.00
24.15
28.35
2
10-25
208-550
21.00
25.20
31.50
37.80
3
20-50
208-550
25.20
29.40
40.95
44.10
4
40-100
208-550
29.40
39.10
43.30
58.70
5
I
60-200
I 208-550 |
35.00 |
49.40
| 52.50 |
73.40
Multi-Speed Starters Nonreversing, 3-Phase
Constant Horsepower I I" " ~.
I Starter and I
Starter and
KT~WA I
N
jf.MA
Rating
Starter Only
Circuit Breaker
D i s c o n n e c t Switch
Horsepower I Voltage
^Peed
2-Speed
2-Speed
0
1
2
3
4
5

1-2
3-5
10-20
20-40
30-60
75-150

208-550
208-550
208-550
208-550
208-550
I 208-550 [

5.00
6.60
9.20
11.30
18.50
28.80

7.85
11.00
14.20
17.85
24.70
37.00

7.85
11.00
14.20
18.35
25.00
37.50

Manhours include checking out of job storage, handling, job hauling, distributing, positioning of
enclosure, separate installation, and conductor terminations.
Manhours exclude fastenings and field cut knockouts. See respective tables for these time frames.

AUXILIARY GUTTERS AND FITTINGS


MANHOURS EACH
Item and Size
Gutters
4" x 4 " - 1 2 " Long
4" x 4" - 24" Long
4" x 4" - 36" Long
4" x 4" - 48" Long
4" x 4" - 60" Long
6" x 6 " - 1 2 " Long
6" x 6" - 24" Long
6" x 6" - 36" Long
6" x 6" - 48" Long
6" x 6" - 60" Long
8" x 8 " - 1 2 " Long
8" x 8" - 24" Long
8" x 8" - 36" Long
8" x 8" - 48" Long
8" x 8" - 60" Long
Fittings
Connectors
Connectors
Connectors
Adapter
Adapter
Adapter
End Wall
End Wall
End Wall
Tee
Tee
Tee
90 Elbow
90 Elbow
90 Elbow
Hanger Assembly
Hanger Assembly
Hanger Assembly

Manhours
0.60
0.90
150
2.10
2.70
0.90
120
180
2.70
3.30
1.20
1.50
2.10
3.00
3.00
-4"
-6"
-8"
-4"
-6"
-8"
-4"
-6"
-8"
-4"
-6"
-8"
-4"
-6"
-8"
-4"
-6"
-8^

0.30
0.48
0.60
0.12
0.18
0.24
0.12
0.18
0.24
0.90
1.02
1.08
0.60
0.72
0.90
0.60
0.72
0.85

Manhours include checking out of job storage, handling, job hauling, distributing, layout, assembling,
and installing auxiliary gutters and fittings.
Manhours exclude fastenings and field cut knockouts. See respective tables for these time frames.

JUNCTION BOXES
MANHOURS EACH
Junction
Approximate
.. ,
Junction
Approximate
.. ,
1
D c
\u u*
Manhours
i, o .
T1. . ,
Manhours
Box Size
Weight
1_
I Box Size
Weight
(Inches)
(Pounds)
Wall Ceiling
(Inches)
(Pounds)
Wall Ceiling
6x 6x 4
5.4
1.10
1.35 4 8 x 6 0 x 2 4
449.8
26.00 29.90
8x8x4
6.8
1.20
1.50 6 0 x 6 0 x 1 8
467.6
27.30 31.20
10 x 10 x 4
9.3
1.50
1.80 4 8 x 6 0 x 3 0
502.6
27.50 31.25
12 x 12 x 4
12.0
1.80
2.10 6 0 x 6 0 x 2 4
524.4
28.75 32.50
12 x 12 x 6
14.5
2.25
3.00 4 8 x 6 0 x 3 6
555.4
30.00 33.75
12 x 18 x 4
16.6
2.25
3.00 6 0 x 6 0 x 3 0
580.0
32.50 36.25
12 x 12 x 6
19.4
2.55
3.30 6 0 x 7 2 x 2 4
606.3
35.00 38.75
12 x 24 x 6
23.5
2.85
3.60 6 0 x 7 2 x 3 0
647.0
38.75 42.50
18 x 24 x 6
32.8
3.75
4.85 7 2 x 7 2 x 2 4
679.3
41.25 45.00
18 x 24 x 8
36.8
4.10
5.25 6 0 x 7 2 x 3 6
730.0
43.20 46.80
18 x 30 x 6
39.3
4.10
5.25 7 2 x 7 2 x 3 0
741.0
44.40 48.00
18 x 30 x 8
43.7
4.10
5.25 7 2 x 8 4 x 2 4
753.9
45.60 49.20
24 x 30 x 8
54.2
4.85
6.00 7 2 x 7 2 x 3 6
804.1
46.80 50.40
24 x 36 x 8
98.9
5.25
6.30 7 2 x 8 4 x 3 0
816.3
48.00 51.60
24 x 42 x 8
103.3
5.95
7.00 8 4 x 8 4 x 2 4
857.2
51.60 55.20
30x30x12
106.0
7.00
8.40 7 2 x 8 4 x 3 6
878.7
52.80 56.40
30x36x12
123.0
8.40
9.80 8 4 x 8 4 x 3 0
925.0
53.10 56.70
36x36x12
140.8
9.80 11.55 8 4 x 9 6 x 2 4
960.7
53.80 57.30
30x42x12
144.5
10.15 11.90 8 4 x 8 4 x 3 6
992.8
55.00 58.50
36x36x18
159.2
10.50 12.25 7 2 x 8 4 x 4 8
1,003.5
55.20 58.65
36x42x24
263.1
15.60 18.20 8 4 x 9 6 x 3 0
1,034.5
57.50 60.95
42x42x18
291.2
19.50 23.40 8 4 x 9 6 x 3 6
1,098.3
59.80 63.25
42x42x24
305.6
20.80 24.70 8 4 x 8 4 x 4 8
1,128.4
62.10 65.55
36x42x30
315.1
22.10 26.00 9 6 x 9 6 x 3 0
1,129.8
62.10 65.55
42x48x24
341.0
23.00 27.30 9 6 x 9 6 x 3 6
1,203.6
66.00 69.30
48x48x24
379.0
24.35 28.25 9 6 x 9 6 x 4 2
1,277.4
70.40 73.70
48x48x30 I
384.7
j 24.70 j 28.60 | 9 6 x 9 6 x 4 8 |
1,351.2 | 77.00 | 80.30
Manhours include checking out of job storage, handling, job hauling, distributing, layout, and positioning in place to heights of 12 feet.
Manhours exclude fastenings and field cut knockouts. See respective tables for these time frames.

1- and 2-DOOR TERMINAL CABINETS


MANHOURS EACH
Cabinet
Size
(Inches)

Approximate
Weight
(Pounds)

Manhours
Wall
Mounted

Cabinet
Size
(Inches)

Approximate
Weight
(Pounds)

M an hours
Wall
Mounted

37
26
37
44
52
66
66
78
92
29
41
47
39
57
70
70
90
99
123
109

3.35
3.00
3.75
4.15
4.35
4.70
4.85
5.25
5.45
3.00
3.75
4.15
3.75
4.35
4.55
4.55
5.10
5.25
5.30
5.60

42x30x 8
42x36x 8
48 x 24 x 8
48 x 30 x 8
48x36x 8
60x36x 8
16x12x10
20x16x10
20x20x10
24x12x10
24x20x10
24x24x10
30x24x10
30x24x10
36x24x10
36x30x10
42x30x10
48x30x10
48x36x10
60x36x10

142
170
128
150
181
224
31
44
51
41
61
74
75
92
105
129
149
159
190
233

7.70
9.80
6.65
8.75
9.80
12.60
3.00
4.15
4.35
3.75
4.35
4.85
4.85
5.40
5.60
6.30
8.75
9.10
975
11.70

273
428
431
540
597

14.30
23.40
23.40
28.60
33.80

72x72x10
60x48x12
60x60x12
72x60x12
| 72x72x12 |

701
450
535
637
743

40.80
26.00
28.60
36.00
43.20

1-Door

12x24x6
16x12x6
20x16x6
20x20x6
24x20x6
24x24x6
30x20x6
30x24x6
36x24x6
16x12x8
20x16x8
20x20x8
24x12x8
24x20x8
24x24x8
30x20x8
30x24x8
36x24x8
36x30x8
42 x 24 x 8
2-Door
54x42x8
60x48x8
60x48x10
60x60x10
72x60x10

Manhours include checking out of job storage, handling, job hauling, distribution, layout, and positioning cabinet.
Manhours exclude fastenings, field cut knockouts, and terminal strip installation. See respective
tables for these time frames.

CURRENT TRANSFORMER, METER TEST


CABINETS9 AND METER TROUGHS
Current Transformer Cabinets
MANHOURS EACH
Cabinet Size
/T , v
(Inches)
36x27x11
44x27x11
40x30-1/4x10
52x32-1/4x12
77 x 32-7/8 x 14-1/2

Amperage
T
n
Capacity
200-600
600-1,200
2-500 MCM Per Leg
4-500 MCM Per Leg
| 4-500 MCM Per Leg W/Cur. Limit

._ .
Manhours

9.75
15.60
11.70
23.40
31.20

Meter Test Cabinets


MANHOURSEACH
Cabinet Size
. ,
(inches)
14 x 9x3-3/8
14x29x3-3/8

Type of
t?
* rk
Equipment Design
10-Pole-Switch and Test Block
Same with Meter Adapter

.. ,
Manhours
4.55
^80

Meter Troughs
MANHOURS EACH
Number of
Meters

1-Phase

1
2
3
4
5
6

3.25
5.20
7.15
9.10
11.00
12.00

Manhours for
I

3-Phase

4.85
7.15
9.40
11.70
13.30
14.40

Manhours include checking out of job storage, handling, job hauling, distributing, and positioning of
items as outlined.
Manhours exclude fastening and field cut knockouts. See respective tables for these time frames.

METER SERVICE ENTRANCE SWITCHES AND


METER SOCKET-CIRCUIT BREAKER
COMBINATION
Meter Service Entrance Switches
MANHOURS EACH
.

Manhours Each
Fusable-No Current Transformers I Fusable-With Current Transformers
3-PoIe, 3-Wire I 3-Pole, 4-Wire
3-Pole, 3-Wire 1 3-Pole, 4-Wire

mperage
blze

100
200
400
600
800
1,000

4.85
7.90
13.50
16.00
21.60
27.50

6.00
8.85
16.40
18.20
24.00
28.60

10.90
18.70
22.10
28.60
39 75

11.75
22.00
25.00
31.80
41.30

METER SOCKET-CIRCUIT BREAKER


COMBINATION
MANHOURS EACH
,
- . .A
KT
Number
of Meters

Manhours for
=7T7
-pr. r 5 :
1 <nrt .
-pr. r - 5 ;
70-Amp Circuit Breaker
100-Amp Circuit Breaker
13.30
19.80
25.40
31.80
16.80
25.20
33.60
42.00
21.00
29.40
37.80

1-4
5-8
9-12
13-16
1-5
6-10
11-15
16-20
1-6
7-12
13-18

19-24

46.20

Manhours include checking out of job storage, handling, job hauling, distributing, installing, and
conductor terminations for items as outlined.
Manhours exclude cabinet installation, fastening, and field cut knockouts. See respective tables for
these time frames.

INTERCONNECTING CONDUCTORS, SPLIT BOLT


CONNECTORS AND LUGS
MANHOURS EACH
Conductor
or ^ j r e
Size

"
] ~ "
Interconnecting Conductors
3 Conductors
4 Conductors

4'
#14
#12
#10
#8
#6
#4
#2
#1
#1/0
#2/0
#3/0
#4/0
#250 MCM
#350 MCM
#500 MCM
#600 MCM
#750 MCM
#1000 MCM

0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.33
0.44
0.50
0.66
0.77
0.88
0.99
1.10
1.21
1.43
1.93

I 6' | 8' I 1 2 '


0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.50
0.66
0.77
0.94
1.21
1.32
1.49
1.65
1.82
2.20
2.86

0.60 0.88
0.60 0.88
0.60 0.88
0.60 0.88
0.60 0.88
0.60 0.88
0.60 0.88
0.66 1.05
0.83 1.27
0.99 1.49
1.27 1.87
1.60 2.42
1.76 2.59
1.98 2.86
2.20 3.30
2.42 3.63
2.92 4.40
3.80 [ 5.72 |

I ~
Connectors
Cable Lug

4 ' I 6' I 8' I 1 2 '


0.39
0.39
0.39
0.39
0.39
0.39
0.39
0.44
0.55
0.66
0.83
1.05
1.16
1.32
1.43
1.60
1.93
2.53 [

0.60
0.60
0.60
0.60
0.60
0.60
0.60
0.66
0.83
0.99
1.27
1.60
1.76
1.98
2.20
2.42
2.92
3.80 |

0.83 1.21
0.83 1.21
0.83 1.21
0.83 1.21
0.83 1.21
0.83 1.21
0.83 1.21
0.94 1.38
1.10 1.65
1.32 1.98
1.71 2.53
2.10 3.19
2.31 3.41
2.64 3.96
2.92 4.40
3.19 4.79
3.85 5.83
5.06 [ 7.59 |

0.33
0.44
0.55
0.66
0.77
0.88
1.27
1.38
1.54
1.65
1.93
2.20
2.64
3.10
3.96
4.95
5.78

0.22
0.22
0.22
0.33
0.33
0.33
0.66
0.83
0.99
1.21
1.38
1.70
2.10
2.53
3.10
3.85
| 4.40

Interconnecting conductor manhours for auxiliary gutters, switches, circuit breakers, and control
devices give consideration to conductors interconnected between the auxiliary gutter and operating
devices and allow for time required to measure, cut, and prepare conductors for termination and
cabling.
Split bolt cable connector manhours are based on 2 conductors in a split bolt connection.
Lug connector manhours are based on 1 conductor in a lug.
All manhours include checking materials out of job storage, handling, job hauling, distributing, and
layout.
Manhours exclude splicing conductors in gutter or connecting conductors to equipment. See respective tables for these time frames.

CONDUIT NIPPLES FOR SPLIT BOLT AND LUG


CONNECTORS
MANHOURS EACH
Conduit

Field Cut and Thread


____.
1
-
First Nipple
Additional Nipples
6" Long
6" Long
0.42
0.28
0.55
0.28
0.66
0.28
0.77
0.28
0.88
0.42
0.99
0.42
1.10
0.42
1.27
0.55
1.38
0.55

Size
(Inches)
1/2
3/4
1
1-1/4
1-1/2
2
2-1/2
3
3-1/2

1.54

055

P-O^K-;,^^
rreiabncated
/s"N" I
0.28
0.28
0.28
0.42
0.42
0.55
0.55
0.83
0.83

O83

Manhours include checking out of job storage, handling, job hauling, distributing, cutting and threading when required and assembling in position with locknuts and bushings conduit nipples for split
bolt and lug connectors.
Manhours exclude installation of split bolt or lug connector. See respective tables for these time
requirements.