Summary

Results
Study:

800MCM-dbp-2ckts

Execution:

01-05092014-A

Date:

5/9/2014

Frequency:

60 Hz

Conductor Resistances:
Installation Type:

IEC-228

Buried Ducts
Parameter

Unit

Ambient Soil Temperature at Installation Depth

25

C.m/W

1.5

Enabled/Disabled

Disabled

Thermal Resistivity of Native Soil


Non-Isothermal Earth surface modeling

Value

Summary Results
Solution converged
Location

Load Factor

Temperature

Ampacity

Y[m]

[p.u.]

[C]

[A]

1.3

84.3

394.1

1.3

90

394.1

Cable\Cable
type no

Circuit

Phase

X[m]

1\1

1.012

2\1

0.723

3\1

0.434

1.3

89.4

394.1

4\1

-1.012

1.3

84.3

394.1

5\1

-0.723

1.3

90

394.1

6\1

-0.434

1.3

89.4

394.1

Cables input data


Study:

800MCM-dbp-2ckts

Execution:

01-05092014-A

Date:

5/9/2014

Description

No

Unit

General cable information


1

Cable type no

Number of cores

Voltage

Conductor area

Maximum Steady-State Conductor Temperature

90

Maximum Emergency Conductor Temperature

110

kV

46

mm2

405.7

Construction
Conductor

Material

Resistivity @20C

Temperature coefficient

10

Construction

11

Is cable dried?

12

ks (Skin effect coefficient)

13

kp (Proximity effect coefficient)

14

Diameter

copper
u.cm

1.7241

1/K

0.00393
compact
No
1
1

mm

23.57

Conductor shield

15

Is layer present?

16

Thickness

mm

0.94

17

Diameter

mm

25.45

Yes

Insulation

18

Is layer present?

19

Material

20

Thermal resistivity

Yes
XLPE (unfilled)
K.m/w

3.5

21

Dielectric loss factor - ( tan )

22

Relative permeability ( )

23

Thickness

mm

11.3

24

Diameter

mm

48.05

0.001
2.5

Insulation screen

25

Is layer present?

26

Material

27

Thickness

mm

1.07

28

Diameter

mm

50.19

Yes
semi-conducting

Sheath

29

Is layer present?

Yes

30

Is around each core? (Only for Three core cable)

No

31

Material

32

Resistivity @20C

33

Temperature coefficient

copper
u.cm

1.7241

1/K

0.00393

34

Corrugated construction

35

Thickness

mm

0.2

36

Diameter

mm

50.59

Non-corrugated

Armour bedding

37

Is layer present?

Yes

38

Material

PVC

39

Thermal resistivity

K.m/w

40

Thickness

mm

2.03

41

Diameter

mm

54.65

Armour/Reinforcing tape

42

Is layer present?

Yes

43

Type of material

Wires

44

Material

AWA

45

Resistivity @20C

46

Temperature coefficient

47

Length of lay

48

Number of wires

49

Cross sectionnal area of tape armour

50

Tape lay

51

Permeability

52

AME

53

AMT

54

u.cm

2.8264

1/K

0.00403

mm

546.5
71

mm

GAMMA

55

Thickness

mm

2.5

56

Diameter

mm

59.65

Armour serving

57

Is layer present?

Yes

58

Material

PVC

59

Thermal resistivity

K.m/w

60

Thickness

mm

3.44

61

Diameter

mm

66.53

mm

66.53

Overall cable diameter

62

Diameter

Description/Value

No

Unit

SPECIFIC INSTALLATION DATA


Bonding

1-CON, sheaths bonded ends, flat configuration

Yes

Loss factor constant

Loss factor constant

0.3

Single conductor transposed

Cables are regularly transposed

Yes

Duct construction

Metallic conduit (non-magnetic)

Resistivity (RH)

Yes
0

Spacing of cables in section

Spacing is even

Yes

Cables touching

Single conductor cables NOT touching

Yes

Duct/Pipe dimensions

Inside diameter of Duct/Pipe

mm

154.17

Outside diameter of Duct/Pipe

mm

168.41

Unit

No

Symbol

Description

Temperature calculations
1

Cable type no

Circuit no

Phase

Conductor temperature

84.3

90

89.4

84.3

90

89.4

Sheath/Shield temperature

80.3

86

85.4

80.3

86

85.4

Armour/Pipe or Jacket temperature

79.5

85.2

84.6

79.5

85.2

84.6

Exterior duct temperature

70.2

76

75.4

70.2

76

75.4

Ambient temperature

25

25

25

25

25

25

Cable type no: 1


Cable type:

EXTRUDED

Cable ID:

DAGDAG01

Cable title:

1/C 800MCM (400mm2) Cu/XLPE/CTS/PVC/AWA/PVC 46kV 100IL ARM

Electrical Parameters
Study:

800MCM-dbp-2ckts

Execution:

01-05092014-A

Date:

5/9/2014

Description

No
1

Unit

Cable type no

Resistances (DC/AC)
2

DC Resistance of Conductor @ 20C

/km

0.04641

0.04641

0.04641

0.04641

0.04641

0.04641

DC Resistance of Conductor @ Operating Temperature

/km

0.05814

0.05917

0.05906

0.05814

0.05917

0.05906

AC Resistance of Conductor @ 20C

/km

0.04798

0.04798

0.04798

0.04798

0.04798

0.04798

AC Resistance of Conductor @ Operating Temperature

/km

0.06017

0.06117

0.06107

0.06017

0.06117

0.06107

DC Resistance of Sheath @ 20C

/km

0.54325

0.54325

0.54325

0.54325

0.54325

0.54325

DC Resistance of Sheath @ Operating Temperature

/km

0.67202

0.68417

0.68289

0.67202

0.68417

0.68289

DC Resistance of Armor @ 20C

/km

0.085

0.085

0.085

0.085

0.085

0.085

DC Resistance of Armor @ Operating Temperature

/km

0.10539

0.10733

0.10713

0.10539

0.10733

0.10713

9.49902

9.49902

9.49902

9.49902

9.49902

9.49902

Losses
10

Conductor Losses

W/m

11

Dielectric Losses

W/m

12

Metallic Screen Losses

W/m

1.57756

1.59667

1.59468

1.57756

1.59667

1.59468

13

Armor/Pipe Losses

W/m

10.05969

10.17743

10.16517

10.05969

10.17743

10.16517

14

Total Losses

W/m

21.13628

21.27313

21.25887

21.13628

21.27313

21.25887

0.21854

Capacitance, Inductance, Impedance


15

Capacitance

F/km

0.21854

0.21854

0.21854

0.21854

0.21854

16

Inductance of Conductor

mH/km

0.73614

0.73614

0.73614

0.73614

0.73614

0.73614

17

Reactance of Conductor

/km

0.27752

0.27752

0.27752

0.27752

0.27752

0.27752

18

Inductance of Metallic Sheath

mH/km

0.52045

0.52045

0.52045

0.52045

0.52045

0.52045

19

Reactance of Metallic Sheath

/km

0.19621

0.19621

0.19621

0.19621

0.19621

0.19621

20

Positive Sequence Impedance

/km

0.06017 +
j0.27752

0.06117 +
j0.27752

0.06107 +
j0.27752

0.06017 +
j0.27752

0.06117 +
j0.27752

0.06107 +
j0.27752

21

Negative Sequence Impedance

/km

0.06017 j0.27752

0.06117 j0.27752

0.06107 j0.27752

0.06017 j0.27752

0.06117 j0.27752

0.06107 j0.27752

22

Zero Sequence Impedance

/km

0.11991 +
j0.19621

0.11991 +
j0.19621

0.11991 +
j0.19621

0.11991 +
j0.19621

0.11991 +
j0.19621

0.11991 +
j0.19621

23

Surge Impedance

58.0382

58.0382

58.0382

58.0382

58.0382

58.0382

Others
24

Dielectric Stress at Conductor Surface

kV/mm

3.28412

3.28412

3.28412

3.28412

3.28412

3.28412

25

Dielectric Stress at Insulation Surface

kV/mm

1.73945

1.73945

1.73945

1.73945

1.73945

1.73945

26

Insulation Resistance @ 20C

M.km

27

Insulation Resistance @ 90C

M.km

28

Reduction factor

29

Charging Capacity of three phase system at Uo

30

Charging Current for One Phase

31

Voltage Drop for Three Phase System

32

Induced Voltage on Metallic Sheath

33

Induced Current on Metallic Sheath (see formula)

kVAR/km

101.14371 101.14371 101.14371 101.14371 101.14371 101.14371


1.01144

1.01144

1.01144

1.01144

1.01144

1.01144

0.42112

0.42112

0.42112

0.42112

0.42112

0.42112

174.34961 174.34961 174.34961 174.34961 174.34961 174.34961

A/km

2.18821

2.18821

2.18821

2.18821

2.18821

2.18821

V/A/km

0.10421

0.10595

0.10577

0.10421

0.10595

0.10577

V/km

110.44067 108.62974 108.81768 110.44067 108.62974 108.81768

Short-Circuit Current
34

Short Circuit Time

35

Non Adiabatic Short Circuit Current of Conductor

kA

187.91109 183.89301 184.31689 187.91109 183.89301 184.31689

36

Non Adiabatic Short Circuit Current of Sheath

kA

16.82495

16.47138

16.50868

16.82495

16.47138

16.50868

37

Non Adiabatic Short Circuit Current of Armour

kA

1.82169

1.78355

1.78758

1.82169

1.78355

1.78758

0.1

0.1

0.1

0.1

0.1

0.1

Cable Parameters under


Normal Operation
Study:

800MCM-dbp-2ckts

Execution:

01-05092014-A

Date:

5/9/2014

No

Symbol

Description

Unit

Cable type no

Normal Operation IEC 60287-1-1


2

Ro

Conductor DC Resistance at 20C

/m

4.64E-05

4.64E-05

4.64E-05

4.64E-05

4.64E-05

4.64E-05

R'

Conductor DC Resistance at Max Temp

/m

5.81E-05

5.92E-05

5.91E-05

5.81E-05

5.92E-05

5.91E-05

Conductor AC Resistance at Max Temp

/m

6.02E-05

6.12E-05

6.11E-05

6.02E-05

6.12E-05

6.11E-05

Ks

Factor Used in Calculating Xs (Skin Effect)

1.00E+00

1.00E+00

1.00E+00

1.00E+00

1.00E+00

1.00E+00

Kp

Factor Used in Calculating Xp (Proximity Effect)

1.00E+00

1.00E+00

1.00E+00

1.00E+00

1.00E+00

1.00E+00

ys

Skin Effect Factor

3.41E-02

3.29E-02

3.31E-02

3.41E-02

3.29E-02

3.31E-02

yp

Proximity Effect Factor

dc

Conductor Diameter

8.80E-04

8.54E-04

8.56E-04

8.80E-04

8.54E-04

8.56E-04

2.36E-02

2.36E-02

2.36E-02

2.36E-02

2.36E-02

2.36E-02

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

F/m

2.19E-10

2.19E-10

2.19E-10

2.19E-10

2.19E-10

2.19E-10

Dielectric Loss Factor

4.00E-03

4.00E-03

4.00E-03

4.00E-03

4.00E-03

4.00E-03

Insulation Relative Permitivity

2.50E+00

2.50E+00

2.50E+00

2.50E+00

2.50E+00

2.50E+00
0.00E+00

10

Distance Between Conductor Axes

11

Cable Capacitiance

12

tan

13

14

Wd

Cable Dielectric Losses Per Phase

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

15

Screen Loss Factor

1.66E-01

1.68E-01

1.68E-01

1.66E-01

1.68E-01

1.68E-01

16

'1

Screen Loss Factor Caused by Circulating Current

1.23E+00

1.24E+00

1.24E+00

1.23E+00

1.24E+00

1.24E+00

17

''1

Screen Loss Factor Caused by Eddy Current

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

18

Rs

Screen AC Resistance at Cable Normal Operation

6.72E-04

6.84E-04

6.83E-04

6.72E-04

6.84E-04

6.83E-04

W/m

/m

19

gs

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

20

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

21

Screen Electrical Resistivity @ Operating Temp.

.m

1.72E-08

1.72E-08

1.72E-08

1.72E-08

1.72E-08

1.72E-08

22

Ds

External diameter of Screen (Sheath)

5.06E-02

5.06E-02

5.06E-02

5.06E-02

5.06E-02

5.06E-02

23

ts

Screen (Sheath) Thickness

24

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

2.00E-04

2.00E-04

2.00E-04

2.00E-04

2.00E-04

2.00E-04

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

Centre Phase

25

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

26

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

27

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

Leading Phase

28

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

29

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

30

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

Lagging Phase

31

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

32

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

33

Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

34

Screen or sheath mean diameter

35

Screen (Sheath) Reactance

5.40E-02

5.40E-02

5.40E-02

5.40E-02

5.40E-02

5.40E-02

/m

1.96E-04

1.96E-04

1.96E-04

1.96E-04

1.96E-04

1.96E-04

36

Coefficient Used in IEC 60287-1-1 Clause 2.3.5

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

37

Coefficient Used in IEC 60287-1-1 Clause 2.3.5

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

38

Xm

Coefficient Used in IEC 60287-1-1 Clause 2.3.5

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

39

Coefficient Used in IEC 60287-1-1 Clause 2.3.5

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.00E+00

0.42103

/m

Normal Operation IEC 60287-2-1


40

T1

Thermal Resistance Between Conductor-Screen

C.m/W

0.42103

0.42103

0.42103

0.42103

0.42103

41

t1

Insulation Thickness Between Conductor-Screen

42

Ti

Thermal Resistivity of Insulation

C.m/W

3.5

3.5

3.5

3.5

3.5

3.5

43

T2

Thermal Resistance Between Screen and Sheath

C.m/W

0.07372

0.07372

0.07372

0.07372

0.07372

0.07372

44

t2

Thickness of Bedding

0.00203

0.00203

0.00203

0.00203

0.00203

0.00203

45

Tb

Thermal Resistivity of Bedding

C.m/W

46

T3

Thermal Resistance of Outer Serving

C.m/W

0.10855

0.10855

0.10855

0.10855

0.10855

0.10855

47

t3

Thickness of Serving

0.00344

0.00344

0.00344

0.00344

0.00344

0.00344

48

Ts

Thermal Resistivity of Serving

C.m/W

49

T3

Thermal Resistance of Jacket

C.m/W

50

t3

Thickness of Jacket

51

Tj

Thermal Resistivity of Jacket

C.m/W

0.32331

F. Ducts

52

T'4

Thermal Resistance of the Air

C.m/W

0.33104

0.32242

0.32331

0.33104

0.32242

53

T''4

Thermal Resistance of the Pipe

C.m/W

54

Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1

5.2

5.2

5.2

5.2

5.2

5.2

55

Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1

1.4

1.4

1.4

1.4

1.4

1.4

56

Coefficient Used in IEC 60287-2-1 Clause 2.2.7.1

0.011

0.011

0.011

0.011

0.011

0.011
78.83783

57

Mean Temprature of the Medium Filling the Space

73.70113

79.44202

78.83783

73.70113

79.44202

58

Do

Outside Diameter of the Pipe

0.16841

0.16841

0.16841

0.16841

0.16841

0.16841

59

Dd

Inside Diameter of the Pipe

0.15417

0.15417

0.15417

0.15417

0.15417

0.15417

Thermal Resistivity of the Pipe Material

C.m/W

60

F.3 Ducts Buried Soil

61

T4

Total Thermal Resistance

C.m/W

2.46941

2.7205

2.69419

2.46941

2.7205

2.69419

62

Cable Current Ampacity

394.1

394.1

394.1

394.1

394.1

394.1

Cable Sheath Short Circuit


Parameters (Adiabatic)
Study:

800MCM-dbp-2ckts

Execution:

01-05092014-A

Date:

5/9/2014

No

Symbol

Description

Unit

Cable type no

0.1

0.1

0.1

0.1

0.1

0.1

176.253

176.253

176.253

176.253

176.253

176.253

31.661

31.661

31.661

31.661

31.661

31.661
84.58

Cable Sheath Short Circuit Parameters (Adiabatic) IEC 60949


2

Short Circuit Time

s
1/2

Constant (see IEC 949)

Sheath cross section area

mm

Sheath initial temprature

79.49

85.18

84.58

79.49

85.18

Sheath final temperature

250

250

250

250

250

250

Reciprocal of temperature coefficient

234.5

234.5

234.5

234.5

234.5

234.5

IAD

Sheath short circuit current

kA

16.825

16.471

16.509

16.825

16.471

16.509

As /mm