Note 1: On engine wiring and wiring in an environment with a temperature > 50 degr. C,
cable rating of a general purpose polyethylene insulated wire with a minimum insulation
temperature of 105 degr. C should be used. When higher temperatures are present higher
cable insulation rating should be used.

UEGO Bosch LSU Sensor


(Optional)

Proact Driver
MIXTURE ACTUATOR 1

TecJet
EGS version
P/N 8407-522 / 523 / 524

WASTEGATE/
BYPASS
ACTUATOR 2

14
13

K3
13

A1

14

SPD_SW2
13

BLACK 18

Spare
Relay

Relay

14

J1939 to CAN Open


converter or J1939
Isolator

A B

K2

K1
BLACK 14

VIOLET/RED 18

RED 14

BLACK 18

BLACK 18

BLACK 18

AN11M_J1-A26

EST 14_J2-B5

EST RTN_J2-A22

BLACK 16

LS04_J2-B21

CAN1+_J1_B9

CAN1-_J1_B10

CAN2-_J1_C18

CAN2+_J1_C17

Ground connection to be made


through cable from Control
Chassis to Engine Chassis

BLUE/ORANGE 18

BLACK 16
BLACK 16
BLACK 16

BLACK 16

RED 18

120 ohm

120 ohm

DRVG_A_J2-A16
DRVG_B_J2-A24
DRVG_C_J2-A15
DRVG_D_J2-B9

RED 18
DRVP1_J2-A18

BLACK 18

DRVP2_J2-A19

BLACK 18
LS06_J2-B15

LS07_J2-B17

RED 18

BLACK 18
LS05_J2-B12

RED 18

EST16 J2-B8

EST15 J2-B7

EST13 J2-B6

24V
BATTERY

BATT_ J1-B8

F1 64A

KEY_SW_J1-B2

F5 10A

J1-B1

RED 16

J1-B14

F4 10A

BLACK 14

LSU1-IP_

RED 14

LSU1-VM_

RED 14

YELLOW/GREEN 18

Minor Alarm
Relay

F2 25A
F3 25A

ORANGE/BLUE 18

Relay

A2

BROWN/TAN 18

RED 18

A1

A2

J1-B15

13

J1-B21

14

SPD_SW1

LSU1-IA_

13

BLACK 18

ENGINE GND
14

RED 14

RED 18

BLACK 16

LSO1_ J1-B20

Major Alarm
Relay

LSU1-UN_

A2
Relay

RED 18

A1

A2

13

A1

A1

RED 18

A2

A2

RED 16

A1

14

SPD_SW3

BLACK 16
BLACK 16

TPS (+)
TPS (-)

Note 3: CAN communications for Dual Tecjet are shown in detail on page 3.

POWER

POS COMMAND (+)

Note 2: CAN communication to IC920 and Firefly as part of the EGS system are shown in
detail on page 2.
D

POS COMMAND (-)


GND

J1-A2_CNK_VRJ1-A13_CRANK

WHITE 18

WHITE 18
WHITE 18

J1-A21_AN07M

J1-C15_AN27M

WHITE 18

WHITE 18

J1-A10_AN13M

J1-B24_XDRG_A
WHITE 18

J1-A24_XDRG_B

J1-A11_XDRP_B
WHITE 18

WHITE 18

WHITE 18

J1-A6_AN06M

J1-A30_AN05M
WHITE 18

WHITE 18

WHITE 18

J1-C6 _AN29M

J1-A16 _AN10M

J1-A17 _AN08M
WHITE 18

J1-A29 _AN04M
WHITE 18

J1-A25 _AN09M
WHITE 18

WHITE 18

J1-A14 _AN01M

J1-C10_AN18M
WHITE 18

J1-A07_AN17M
WHITE 18

J1-C9_AN20M
WHITE 18

WHITE 18

WHITE 18

J1-C11_AN19M

J1-C2_AN21M

J1-C5_AN23M
WHITE 18

J1-C1_AN24M
WHITE 18

J1-C4_AN22M
WHITE 18

J1-B23 SCI- (RS-485)

J1-C3_AN25M
WHITE 18

WHITE 18

WHITE 18

J1-B22 SCI+ (RS-485)

U1 - PCMHD-128 EGS Mono System

RS485
RS232

NGK
UEGO SENSOR
A

V
P

V
P

MAP_1

MAP_2

FUEL ON
(RUN)

THROTTLE
FAULT
CONTACT

30

GENERATOR
BREAKER

3 2 1
A

N
S

70

GAS
SELECTION

40

RESET

LOWER

MAT_1

50

RAISE

60

IDLE/RATED

80

UTILITY
BREAKER

90

20

10

3 2
A B

COM

USE GALVANIC ISOLATION FOR THESE ANALOG


0-5Vdc INPUTS

CW

POWER

Service PC
Toolkit

SPEED BIAS
1-5V
(3V = 0 BIAS)

OUTPUT

CH4
SIGNAL

POWER

OUTPUT

kW LOAD
TORQUE

COM

SPEED/LOAD
REFERENCE

POWER

COM

OUTPUT

C
3

ECT_1

SPEED

PTP_1

AFR TRIM

DIAGRAM- CONTROL WIRING

WOODWARD NEDERLAND B.V.


ENGINE CONTROLS DIVISION
HOOFDDORP, THE NETHERLANDS
6

EGS Mono System


4

SIZE
A3
SCALE

CAGE CODE

DWG NO

REV

9971-1120
SHEET
1

OF 3

Note 1: Cable per ISO 11898-2:


Maximum length of 40 mtr. For the J1939 on 250 Kbps.
Ends of the network need to be terminated with 120 ohm resistors
Nominal resistance of line is 70 mohm/m
Nominal specific propagation delay of 5 ns/m.
Note 2: Maximum lenth of drop line length of 1 mtr at 250 Kbps
Note 3: Shielding only to be connected to Tecjet and EGS sides. The shielding needs to be continued through.
Note 4: Termination resistor on Tecjet side is mounted inside Tecjet. Only a jumper needs to be installed to make
the termination active.

TecJet
EGS version
P/N 8407-522 / 523 / 524
C

CAN - L

CAN - H

CAN - COM

CAN - L

CAN - H

CAN - L

120 ohm
termination

EGS
(CAN-Link)

CAN - H

4
B

FireFly connector
(CAN Link)

CAN - COM

IC920 SUB-D connector


(CAN link)

TecJet Receptacle

J2N1

J2N2

J1B24

J1B9

J1B10

120 ohm
termination

1
3

DIAGRAM- CONTROL WIRING

WOODWARD NEDERLAND B.V.


ENGINE CONTROLS DIVISION
HOOFDDORP, THE NETHERLANDS
6

EGS System CAN Link


4

SIZE
A3
SCALE

CAGE CODE

DWG NO

REV

9971-1120
SHEET
1

OF 3

Note 1: Cable per ISO 11898-2:


Maximum length of 40 mtr. For the J1939 on 250 Kbps.
Ends of the network need to be terminated with 120 ohm resistors
Nominal resistance of line is 70 mohm/m
Nominal specific propagation delay of 5 ns/m.
Note 2: Maximum lenth of drop line length of 1 mtr at 250 Kbps
Note 3: Shielding only to be connected to Tecjet and EGS sides. The shielding needs to be continued through.
Note 4: Termination resistor on Tecjet side is mounted inside Tecjet. Only a jumper needs to be installed to make
the termination active.
Note 5: The 2nd Tecjet needs a jumper between terminal H and J to select its unique CAN_ID node.

Dual Tecjet
D

TecJet #1

TecJet #2

EGS version
P/N 8407-522 / 523 / 524

EGS version
P/N 8407-522 / 523 / 524

TecJet Receptacle

CAN - L

CAN - L

CAN - H

CAN - COM

Common

CAN ID1

CAN - H

CAN - H

CAN - L

120 ohm
termination

CAN - COM

EGS
(CAN-Link)

TecJet Receptacle

J1B24

J1B9

J1B10

5
2

120 ohm
termination

1
3

DIAGRAM- CONTROL WIRING

WOODWARD NEDERLAND B.V.


ENGINE CONTROLS DIVISION
HOOFDDORP, THE NETHERLANDS
6

EGS System with Dual Tecjet - CAN Link


4

SIZE
A3
SCALE

CAGE CODE

DWG NO

REV

9971-1120
SHEET
1

OF 3