Vous êtes sur la page 1sur 94

ESTUDIO HIDROLGICO CENTRAL

HIDROELCTRICA CHILCAY

Pgina 1

ESTUDIO
HIDROLGICO DE
LA CENTRAL
HIDROELCTRICA
CHILCAY

EMPRESA DE GENERACIN ELECTRICA


CANCHAYLLO S.A.C.

HuancayoS.A.C.
- 2013
EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO
Calle los Flamengos Mz F, Lote 02 Huertos de Santa
Genoveva Lurn Lima, RUC N 20545538629

EGECSAC
ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 2

CONTENIDO
RESUMEN EJECUTIVO ......................................................................................................................... 7
CAPTULO I: ASPECTOS GENERALES ............................................................................................. 9
1.1.

INTRODUCCION ..................................................................................................................... 9

1.2.

ANTECEDENTES .................................................................................................................. 10

1.3.

OBJETIVO DEL ESTUDIO ................................................................................................... 10

1.4.

JUSTIFICACIN DEL ESTUDIO ......................................................................................... 11

CAPITULO II: EVALUACIN HIDROLGICA SUB CUENCA DEL RIO CANIPACO ................. 12
2.1
DESCRIPCIN GENERAL DE LA CUENCA Y EL CURSO PRINCIPAL DE LA
FUENTE NATURAL........................................................................................................................... 12
2.1.1

Ubicacin y Demarcacin de la Sub Cuenca del Rio Canipaco .............................. 12

Grfico N 01: Ubicacin del Estudio Hidrolgico .................................................................................. 14


Grfico N 02: Mapa de Agrupaciones Hidrogrficas del Per ............................................................... 15
Grfico N 03: Ubicacin de la cuenca del rio Mantaro .......................................................................... 15
Cuadro N 01 Ubicacin en coordenadas geogrficas UTM (WGS-84 / 18L - Sur) Captacin y
Devolucin de las aguas del rio Canipaco ............................................................................................... 16
2.1.2

Accesibilidad Vas de comunicacin a la Sub cuenca del rio Canipaco .............. 16

2.1.3

Aspectos Socioeconmicos de la Sub cuenca de Canipaco ................................... 16

Cuadro N 02: Poblacin Total del rea de Influencia de la Sub cuenca Canipaco ................................ 17
Grfico N 04: Poblacin por Distritos total del rea de influencia........................................................ 18
2.1.4

Geomorfologa de la Sub cuenca rio Canipaco.......................................................... 18

Cuadro N 03: Parmetros Geomorfolgicos de la sub cuenca Canipaco ............................................... 21


Cuadro N 04: Geologa de la Sub cuenca del ro Canipaco ................................................................... 23
Cuadro N 05: Capacidad de Uso Mayor de Tierras de la Sub cuenca del ro Canipaco ........................ 24
Cuadro N 06: Micro cuencas de la Sub cuenca del ro Canipaco ........................................................... 25
Cuadro N 07: Clasificacin Ordinal de la sub cuenca del ro Canipaco ................................................ 25
2.1.5
a)

Aspectos Ecolgicos ...................................................................................................... 26

ZONAS DE VIDA.................................................................................................................... 26

Cuadro N 08: Zonas de Vida de la sub cuenca del ro Canipaco ............................................................ 26


b)

FLORA Y FAUNA ................................................................................................................... 28

Cuadro N 09: Flora perteneciente a la Sub cuenca del rio Canipaco..................................................... 29


Cuadro N 10: Fauna perteneciente a la Sub cuenca del rio Canipaco ................................................... 30
2.1.6

Calidad del Agua ............................................................................................................ 30

Cuadro N 11: Anlisis Qumico de agua del ro Canipaco ..................................................................... 30

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 3

2.2
ANLISIS Y TRATAMIENTO DE LA INFORMACIN HIDROMETEOROLGICA E
HIDROMTRICA DE LA SUB CUENCA DEL RIO CANIPACO .................................................. 32
2.2.1

Anlisis de las Variables Meteorolgicas .................................................................... 32

Red Hidrometereolgica en la Sub cuenca del rio Canipaco ...................................................... 32


Cuadro N 12: Ubicacin de las Estaciones para determinar las variables Meteorolgicas ................... 32
Grfico N 05: Estaciones Pluviomtricas e Hidromtricas en la Sub cuenca del rio Canipaco. ............. 33
Cuadro N 13: Temperatura media mensual ............................................................................................ 33
Cuadro N 14: Humedad media mensual ................................................................................................. 34
Cuadro N 15: Evaporacin media mensual ............................................................................................ 34
Cuadro N 16: Velocidad de viento .......................................................................................................... 34
Cuadro N 17: Horas del sol da media mensual ..................................................................................... 35
Cuadro N 18: Evapotranspiracin en la Sub cuenca del rio Canipaco ................................................... 35
2.2.2

Tratamiento de la Informacin Hidrometeorolgica e Hidromtrica ........................ 35

Cuadro N 19: Precipitacin Total Mensual Completa y Consistente (mm) Ao Promedio Histrico
(1960 2002) ........................................................................................................................................... 36
Grfico N 06: Anlisis de Precipitacin Media Acumulada Multianual por Estaciones en la Sub cuenca
del rio Canipaco ....................................................................................................................................... 36
Cuadro N 20: Anlisis de Doble Masa para las estaciones Laive, Huancalpi, y Huichicocha Histrico
(1963 2011) ........................................................................................................................................... 37
Grfico N 07: Anlisis de Doble Masa para las Estaciones Laive, Huancalpi, y Huichicocha. .............. 38
Cuadro N 21: Anlisis de Precipitaciones Medias Mensuales Acumuladas............................................ 38
Grfico N 08: Anlisis de Precipitaciones Medias Mensuales Acumuladas para la Sub cuenca del rio
Canipaco (mm). ........................................................................................................................................ 39
2.3

DISPONIBILIDAD HDRICA EN LA SUB CUENCA DEL RIO CANIPACO .................... 39

Cuadro N 22: Caractersticas de las estaciones linnimetricas para determinar la Escorrenta superficial
.................................................................................................................................................................. 39
Grfico N 09: Ubicacin de estaciones de aforo con reglas linnimetricas en la sub cuenca del rio
Canipaco operadas por Electro Per S.A. ............................................................................................. 40
Grfico N 10: Fotografas de estaciones de aforo con reglas linnimetricas: Canipaco, Yulapuquio y
Quillon, en la sub cuenca del rio Canipaco operadas por Electro Per S.A. ........................................ 40
2.3.1

Disponibilidad Hdrica en la Sub cuenca del rio Canipaco ....................................... 41

Cuadro N 23: Caudales Naturales Medios Mensuales Estacin Quillon 2003 2012 (m3/s) ................. 42
Grafico N 11: Hidrograma de Caudales Naturales Medios Multianuales Estacin Quillon, Yulapuqio y
Canipaco 2003-2012 (m3/s) ...................................................................................................................... 43
Grafico N 12: Anlisis de Caudal Natural Medio Mensuales de las estaciones Quillon, Canipaco y
Yulapuquio................................................................................................................................................ 44

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY
2.3.2

Pgina 4

Anlisis de Persistencia de Probabilidad de Ocurrencia de Caudales ................... 44

Cuadro N 24: Descargas con Diferentes Probabilidades de Ocurrencia Balance de Masas de las
Estaciones Quillon.................................................................................................................................... 45
Grafico N 13: Curva de Variacin Estacional de caudales Naturales con Diferentes Probabilidades de
Ocurrencia de las Estaciones Quillon ...................................................................................................... 45
Cuadro N 25: Resultados de los clculos de la curva de duracin normal Estacin Quillon.................. 46
Grafico N 14: Curva de duracin normal de la estacin Quillon ........................................................... 48
2.3.3

Anlisis de Mximas Avenidas ..................................................................................... 48

Cuadro N 26: Caudales Mximos registrados por la estacin pluviomtrica Quillon, para la captacin
de la central hidroelctrica Chilcay en m3/s ............................................................................................. 49
2.3.4
2.4

Disponibilidad de Reservorios ...................................................................................... 50

USOS Y DEMANDAS DE AGUA ......................................................................................... 51

2.4.1

Consumo Actual del agua en el mbito de la sub Cuenca del Rio Canipaco ....... 51

Cuadro N 27: Caudales de uso no agrario en la sub cuenca del rio Canipaco para el ao 2012 .......... 52
2.4.2

Demanda Futura............................................................................................................. 52

Cuadro N 28: Demanda mensualizada futura de la central hidroelctrica chilcay en m3/s y MMC........ 53
La demanda futura se determin en funcin a la disponibilidad hdrica del rio Canipaco en
el punto de inters, respetando el caudal ecolgico que se demuestra en el siguiente
cuadro. ............................................................................................................................................. 53
Determinacin del caudal ecolgico determinado segn Memorndum Mltiple N 0182012-ANA-DCPRH-ERH-SUP ..................................................................................................... 53
Cuadro N 29: Caudal ecolgico determinado a una persistencia de 75% del rio Canipaco ................... 53
Grafico N 15: Curva de Caudal ecolgico con la medias de las avenidas del ro Canipaco .................. 53
Grafico N 16: Esquema hidrulico central hidroelctrica Chilcay ......................................................... 54
2.5

BALANCE HDRICO .............................................................................................................. 55

2.5.1

Disponibilidad Hdrica en la Unidad Hidrogrfica ....................................................... 55

Cuadro N 30: Oferta Hdrica Superficial de la sub cuenca del ro Canipaco (MMC) ............................ 55
2.5.2

Demanda Hdrica Total .................................................................................................. 55

Cuadro N 31: Demanda Hdrica Energtica disponible Superficial de la Sub cuenca del ro Canipaco 55
Grafico N 17: Calculo de caudal requerido para operacin al 100 %, central hidroelctrica Chilcay .. 56
2.5.3

Balance Hdrico .............................................................................................................. 56

Cuadro N 32: Balance Hdrico de Asignacin de Agua Superficial en la Sub cuenca del ro Canipaco . 57
Cuadro N 33: Resumen Balance Hdrico de Asignacin de Agua Superficial en la Sub cuenca del ro
Canipaco .................................................................................................................................................. 57
CAPTULO III: INGENIERA DEL PROYECTO HIDRULICO........................................................ 58

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 5

3.1

Planteamiento Hidrulico ...................................................................................................... 58

3.2

Obras Hidrulicas ................................................................................................................... 58

3.3

Dimensionamiento de las Obras de Captacin, Conduccin y Entrega a la Fuente .... 59

3.3.1

Bocatoma ........................................................................................................................ 59

3.3.2

Desarenador: .................................................................................................................. 60

3.3.3

Sistema de Conduccin ................................................................................................. 61

3.3.4

Cmara de Carga ........................................................................................................... 62

3.3.5

Equipamiento Hidromecnico ....................................................................................... 63

3.3.6

Tubera de Presin ......................................................................................................... 64

3.3.7

Sistema de Alivio de las Demasas.............................................................................. 65

3.3.8

Casa de Mquinas ......................................................................................................... 66

3.3.9

Canal de Restitucin ...................................................................................................... 67

3.4

Caractersticas Hidrulicas ................................................................................................... 67

3.5

Cronograma de Ejecucin de Obras ................................................................................... 68

3.6

Especificaciones Tcnicas ........................................................ Error! Marcador no definido.

3.7

Planos Generales Ubicacin Diseo .................................... Error! Marcador no definido.

CAPTULO IV: PLAN DE APROVECHAMIENTO DE LOS RECURSOS HDRICOS EN LA SUB


CUENCA DEL RIO CANIPACO ........................................................................................................... 69
4.1

Descripcin de la Operacin del Sistema Hidrulico del Proyecto ................................. 69

4.2

Descripcin de la operacin del sistema Hidrulico del Estudio ..................................... 70

4.3
Descripcin de los Impactos en la Operacin del Sistema del Proyecto y Planes o
Medidas de Compensacin .............................................................................................................. 71
4.3.1

Evaluacin de Impactos Ambientales .............................................................................. 71

4.3.2
Metodologa de Identificacin y Evaluacin de Impactos AmbientalesError! Marcador
no definido.
A.

Metodologa de Identificacin de Impactos Ambientales ...... Error! Marcador no definido.

4.3.3

Metodologa de Evaluacin de Impactos Ambientales ..... Error! Marcador no definido.

A.

Criterios de valoracin de impactos ambientales .................. Error! Marcador no definido.

Cuadro N 34: Escala de Valoracin de Impactos Ambientales ........... Error! Marcador no definido.
B.

Matriz de significancia de los impactos ambientales ............. Error! Marcador no definido.

Cuadro N 35: Calificacin del Valor Integral de los Impactos ........... Error! Marcador no definido.
4.3.4
Identificacin de Factores Ambientales considerados Susceptibles de ser
Impactados ............................................................................................. Error! Marcador no definido.
Cuadro N 36: Factores y Componentes Ambientales .............................. Error! Marcador no definido.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 6

4.3.5
Identificacin de Fuentes de Impacto o Acciones del Proyecto .......Error! Marcador no
definido.
Cuadro N 37: Identificacin de Actividades del Proyecto ....................... Error! Marcador no definido.
4.3.6

Identificacin y Descripcin de los Impactos Ambientales Error! Marcador no definido.

4.3.7

EVALUACIN DE IMPACTOS AMBIENTALES ............................................................ 76

4.3.8
EVALUACIN DE LOS IMPACTOS AMBIENTALES EN LA ETAPA DE
CONSTRUCCIN .............................................................................................................................. 76
4.3.9

Evaluacin de los Impactos Ambientales en la Etapa de Operaciones ...................... 79

4.3.10

Evaluacin de los Impactos Ambientales en la Etapa de Cierre ................................. 81

4.3.11

Evaluacin de Potenciales Impactos Sociales ............................................................... 83

Cuadro N 38: Evaluacin de impactos sociales .................................................................................. 84


4.3.12

Plan de Manejo Ambiental ................................................................................................ 85

4.3.13

Programas, Planes y Medidas .......................................................................................... 85

4.3.14

Programa de Prevencin y/o Mitigacin ......................................................................... 86

a)

Subprograma de Manejo de Componentes Fsico-Qumicos .............................................. 86

b)

Subprograma de proteccin del componente Biolgico ....................................................... 88

c)

Subprograma de Manejo del Componentes Socio-Econmico ........................................... 88

d)

Subprograma de Sealizacin ................................................................................................. 89

e)

Subprograma de Educacin Ambiental ................................................................................... 90

4.3.15

Medidas especficas para cada Actividad del Proyecto ................................................ 90

Medidas de Mitigacin para la Fase de Construccin .................................................................. 90


Medidas de Mitigacin para la Etapa de Operacin...................................................................... 92
4.4

Servidumbre para el Proyecto .............................................................................................. 92

CAPTULO V: ANEXOS ........................................................................................................................ 94


CAPITULO VI: CONCLUSIONES Y RECOMENDACIONES .......................................................... 94
6.1 Conclusiones ............................................................................................................................ 94

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 7

RESUMEN EJECUTIVO
El presente documento contiene el Estudio Hidrolgico de la Central Hidroelctrica
Chilcay, estudio efectuado por el Equipo Tcnico de la Empresa J & N Consultora e
Ingeniera E.I.R.L. Como encargo de la Empresa de Generacin Elctrica Canchayllo
S.A.C.; el mismo que fue desarrollado en el mbito hidrogrfico de la sub cuenca del rio
Canipaco perteneciente a la Sub Cuenca del Ro Vilca y Cuenca Hidrogrfica del Ro
Mantaro
El objetivo principal del estudio fue la elaboracin del Diagnstico de los Recursos Hdricos
de la sub cuenca del ro Canipaco que permita determinar la disponibilidad hdrica para la
generacin de energa elctrica, a travs de hidroelctricas (energas limpias); para
impulsar la implementacin de infraestructura de la central hidroelctrica Chilcay.
Como resultados del diagnstico podemos describir la presencia de cinco Zonas de Vida,
lo cual representa variedad de flora, fauna y condiciones climticas favorables para el
desarrollo de una serie de actividades que permitan la conservacin y manejo sostenible
de los recursos hdricos.
El estudio comprende cinco fases: evaluacin de los recursos hdricos encontrados en la
zona. Una actividad previa fue la delimitacin Poltica e Hidrogrfica del rea de estudio, la
cual facilit el monitoreo del espacio hidrogrfico.
La fase de evaluacin del recurso hdrico fue realizado en una superficie de 129 381.87
Ha. (Carta Nacional), en el mbito de la Sub Cuenca del ro Canipaco.
Para la fase de planificacin y estudio hdrico. El estudio cuenta con el respaldo de la
legislacin vigente de la Autoridad Nacional de Agua, lo cual impulsa al aprovechamiento
sostenible de los recursos hdricos.
Con el objetivo de la instalacin de una central hidroelctrica con una capacidad de
generacin de 19.21 MGW de potencia. Con el caudal disponible y el salto hidrulico que
se genere. La captacin estar ubicada en el distrito de Colca (centro poblado de Chilcay),
y la devolucin o descarga en el distrito de Colca (centro poblado Tinco), el canal de
conduccin tendr una longitud de 6 600.00 ml., caudal de captacin de 15.4 m 3/s y de
conduccin de 14.00 m 3/s.
Por su naturaleza de la infraestructura el tipo de uso de las aguas del rio Canipaco ser de
tipo No Consuntivo, respetando los derechos de uso de terceros, y el caudal ecolgico del
rio Canipaco, para la conservacin de la biodiversidad. En el trayecto donde se derivan las

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 8

aguas del rio Canipaco no existen usos de terceros hasta el punto de devolucin al cauce
del rio.
Con el desarrollo del proyecto energtico se beneficiaran ampliamente, los pobladores
locales con la mano de obra para construccin de las infraestructuras y los servicios que
prestara en su etapa de operacin
En el Captulo II del presente documento se hace una descripcin de las caractersticas de
la cuenca hidrogrfica del ro Canipaco, en su ubicacin, demarcacin hidrogrfica, vas de
acceso, aspecto socioeconmico tomando como base la informacin del INEI 2007, e
ndice de pobreza extrema 2009, haciendo nfasis en su fisiografa, geologa, ecologa,
climatologa y calidad de agua.
El anlisis y tratamiento de la informacin hidromtrica, se recopilo informacin de la
precipitacin de estudios cientficos realizados en la cuenca del rio Mantaro que es
validado por el Instituto Geofsico del Per (IGP) y Centro de Prediccin Numrica del
Tiempo y Clima (CPNTC), de fuentes como SENAMHI, Electro Per, e IGP que son el ente
oficial en el registro de la informacin hidromtrica del Per.
La hidrologa de la cuenca del ro Canipaco se trata con detenimiento en el Captulo II
donde se describe la red hidrometeorolgica bsica existente en el rea de influencia del
estudio, los parmetros meteorolgicos e hidrolgicos que se han utilizado y los mtodos
de anlisis hidrolgico empleado para la determinacin del caudal de diseo y el estudio de
mximas avenidas.
En el captulo III se trata de la ingeniera del proyecto, como el planteamiento hidrulico
obras hidrulicas, que se desarrollaran en la ejecucin de la central hidroelctrica Chilcay.
En el captulo IV, es planteado el aprovechamiento hdrico, a partir de la ingeniera del
proyecto con lo que respecta a la operacin y manteniendo de la infraestructura hidrulica
para la generacin de hidro - energa.
Finalmente se plantea una serie de conclusiones y recomendaciones que deben ser
tomadas en cuenta. El documento incluye adems Anexos que contiene toda la
informacin hidrometeorolgica, cartografa temtica, utilizada para la formulacin del
estudio y los anlisis realizados.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 9

CAPTULO I: ASPECTOS GENERALES


1.1. INTRODUCCION
El presente estudio hidrolgico se realiza por encargo de la Empresa EGECSAC con la
finalidad de determinar el potencial hidro - energtico en el punto de inters del ro
Canipaco. Cuenta con informacin hidrometeorolgica confiable y garantizada de
estaciones operadas por SENAMHI y Electro Per, datos a partir del cual aplicando
tcnicas y mtodos de anlisis hidrolgico se determina el caudal de diseo y de mximas
avenidas en las zonas de inters hidroenergtica.
Con el objetivo de la instalacin de una central hidroelctrica con una capacidad de
generacin de 19.21 MGW. La captacin estar ubicada en el distrito de Colca (centro
poblado de Chilcay), y la devolucin o descarga en el distrito de Colca (centro poblado de
Tinco), el canal de conduccin tendr una longitud de 6 600.00 ml., caudal de Captacin
15.4 m3/s, y conduccin 14.00 m3/s.
Por su naturaleza de la infraestructura el tipo de uso de las aguas del rio Canipaco ser de
tipo No Consuntivo, respetando los derechos de uso de terceros, y el caudal ecolgico del
rio, para la conservacin de la biodiversidad.
Con el desarrollo del proyecto energtico se beneficiaran ampliamente, los pobladores
locales con la mano de obra para construccin de las infraestructuras y los servicios que
prestara en su etapa de operacin
En el Captulo II del presente documento se hace una descripcin de las caractersticas de
la cuenca hidrogrfica del ro Canipaco, haciendo nfasis en su fisiografa, geologa,
ecologa, climatologa, Calidad de agua, vas y aspectos socioeconmicos, usos de
demandas de los Recursos Hdricos.
La hidrologa de la cuenca del ro Canipaco se trata con detenimiento en el Captulo III
donde se describe la red hidrometeorolgica bsica existente en el rea de influencia del
estudio, los parmetros meteorolgicos e hidrolgicos que se han utilizado y los mtodos
de anlisis hidrolgico empleado para la determinacin del caudal de diseo y el estudio de
mximas avenidas. Obras hidrulicas, dimensionamientos, especificaciones tcnicas.
En el captulo IV se describe el plan de aprovechamiento de los recursos hdricos, y la
operacin del sistema hidrulico e impactos en la construccin y operacin.
Las conclusiones ms importantes se exponen en el ltimo Captulo, referidas a los
resultados obtenidos en el estudio hidrolgico.
El documento incluye adems Anexos que contiene toda la informacin
hidrometeorolgica, cartografa temtica, utilizada para la formulacin del estudio y los
anlisis realizados.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 10

1.2. ANTECEDENTES

Estudio de Evaluacin del Potencial Hidroenergtico Nacional elaborado por el


Consorcio de Ingenieros Consultores Lahmeyer International GmbH y la Compaa
Consultora Salzgitter por encargo del Ministerio de Energa y Minas del Per.

Estudio Hidrolgico de la Cuenca del Ro Mantaro Ao 2011.

El Instituto Geofsico del Per IGP condujo los diversos estudios desarrollados en la
Cuenca del Mantaro, propiciando la participacin de diversas entidades regionales y
con aportes de la poblacin local, principalmente en el Valle del Mantaro, Atlas
Climtico de precipitacin y temperatura del aire de la Cuenca del Ro Mantaro - IGP Instituto Geofsico del Per 2005.

Inventario Nacional de Lagunas y Represamientos Segunda Aproximacin Ao


1980 Oficina Nacional de Evaluacin de Recursos Naturales (ONERN).

Diagnstico del Potencial de los Recursos Hdricos en la sub cuenca del ro Vilca,
realizado por Caritas Diocesana Huancavelica 2008.

1.3. OBJETIVO DEL ESTUDIO


El objetivo principal del estudio hidrolgico es determinar el caudal de diseo y el de
mximas avenidas, parmetros requeridos para disear y dimensionar la infraestructura
hidrulica e infraestructura asociada para el aprovechamiento hidroelctrico ubicado en el
punto de inters hidroenergtico en el rio Canipaco.

Objetivos especficos:

Realizar el balance hdrico del rio Canipaco en el sector de captacin para la central
hidroelctrica Chilcay.

Analizar la Geomorfologa de la Sub cuenca del rio Canipaco en un rea de 129


381.87 ha.

Determinar el balance hdrico, con el fin de determinar la oferta y demanda hdrica


para la operacin de la central hidroelctrica

Evaluar los recursos hdricos para un periodo de retorno de 10 aos. A una


persistencia del 75%.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 11

1.4. JUSTIFICACIN DEL ESTUDIO


Con la implementacin de la central Hidroelctrica Chilcay, se lograra satisfacer la
creciente demanda de energa limpia en la regin central del pas, mejorando la condicin
de vida de los pobladores, de los distritos prximos a la Sub Cuenca del Canipaco, por
brindarles de energa elctrica, proveniente de fuentes no contaminantes, como tambin
la generacin de mano de obra calificada en las etapas de estudios y construccin, en
forma directa e indirecta a toda la poblacin del rea de influencia de estudio.
Respetando los diferentes usos de las aguas, como el caudal ecolgico del rio para la
preservacin de la biodiversidad biolgica, en armona con el medio ambiente.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 12

CAPITULO II: EVALUACIN HIDROLGICA SUB CUENCA DEL RIO CANIPACO


2.1 DESCRIPCIN GENERAL DE LA CUENCA Y EL CURSO PRINCIPAL DE LA FUENTE
NATURAL
2.1.1 Ubicacin y Demarcacin de la Sub Cuenca del Rio Canipaco
El proyecto Central Hidroelctrica Canchayllo, es una de las centrales en cascada
que plantea EGECSAC. En la demarcacin hidrogrfica de la sub cuenca del rio
Canipaco y segn la demarcacin poltica del pas se encuentra ubicada en mayor
extensin:
Regin

Junn

Departamento

Junn

Provincia

Huancayo - Chupaca

Distritos

Yanacancha, Chongos Alto, Chicche, Colca,

Chongos Bajo, Chupuro, Huasicancha, Chacapampa, Carhuacallanga.

Polticamente la sub cuenca del ro Canipaco se encuentra dentro de la jurisdiccin


de los distritos de: Chongos Alto, Huasicancha, Colca, Chicche, Chacapampa,
Chupuro y Carhuacallanga, Chongos Bajo, Yanacancha, provincia de Huancayo y
Chupaca, departamento de Junn; Huayllahuara, Vilca, provincia de Huancavelica,
departamento

de

Huancavelica;

Huantan,

Laraos,

provincia

de

Yauyos,

departamento de Lima.
La sub cuenca Canipaco abarca desde 3 050 msnm, en su punto de descarga en el
rio Vilca, hasta los 5 150 msnm, decir desde las cumbres en la cabecera de cuenca,
en la cordillera Occidental de los andes peruanos, vertiente del Pacifico.
El ro Canipaco es uno de los afluentes del rio Vilca en su margen Izquierda y este
de la cuenca del ro Mantaro por su margen derecha. La cuenca se ubica dentro de
la regin alto andina, vertiente del atlntico, regin hidrogrfica del Amazonas,
Unidad Hidrogrfica Canipaco 499662. Mtodo de codificacin creado por Otto
Pfafstetter 1989.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 13

Nace al pie de los nevados Toroyoc y Tanjaniyoc ubicados a ms de 5 000 m.s.n.m.


Drena una hoya hidrogrfica de 12 9381.87 hectreas hasta su confluencia con el
ro Vilca (3,0 kilmetros antes de su desembocadura en el ro Mantaro). Est
formado por la confluencia de los ros Canipaco y ro La Virgen, en las zonas altas
se encuentran ubicadas un gran nmero de lagunas, siendo las principales:
Yurajcocha, Balsacocha, Coyllorcocha, Huichicocha, ahuincocha, Tinyari y
Capillayoc.
Desde su naciente hasta su afluencia el ro Canipaco recorre unos 82 695.67 ml.,
discurre por un curso de fuerte a mediana pendiente.
Se caracteriza fisiogrficamente por presentar por encima de los 5 000 m.s.n.m.
(parte alta de la cuenca del ro Canipaco) zonas cubiertas de nevados, con climas
fros y secos con temperaturas de 0C y precipitaciones que superan los

900

milmetros.
Entre los 4 000 y 5 000 m.s.n.m. se ubica las punas y los pramos andinos, que
tienen un aspecto caracterstico de praderas con suaves ondulaciones en las que
crece generalmente una vegetacin de pequeas plantas herbceas de carcter
permanente (ichu). En esta zona se ubican las lagunas ms importantes de la
cuenca. La temperatura vara a lo largo del da, presentando valores mximos de
hasta 15 C y mnimos cercanos a 0 C. La precipitacin media anual es del orden
de los 800 milmetros de precipitacin.
Debajo de los 4 000 m.s.n.m. se ubican los centros poblados ms importantes:
Huasicancha, Chongos Alto, Colca, Chacapampa. En esta zona las temperaturas
oscilan entre los 5

a 10 C con un clima favorable para las actividades

agropecuarias.
Geogrficamente se ubica entre las coordenadas UTM: extremos, Norte (473835 ,
8646173); Este (484029 , 8629709); Oeste (429705 , 8627587); Sur (449866 ,
8603263) UTM (WGS-84 / 18L - Sur).
Existe un aprovechamiento hidroelctrico en la cuenca del ro La Virgen (CC.HH El
Machu Chongos Alto).
La mayor actividad econmica en la cuenca es la ganadera (vacunos, ovinos y
auqunidos) complementada con la crianza de truchas. En la parte baja de la
cuenca se desarrolla agricultura de auto consumo.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 14

Grfico N 01: Ubicacin del Estudio Hidrolgico

rea de Estudio
C. H. Chilcay

Ubicacin por Unidad Hidrogrfica del Proyecto se localiza en:


Unidad Hidrogrfica
Sub Cuenca
Cuenca
Vertiente

:
:
:
:

Canipaco y La Virgen
Canipaco UH 499662
Mantaro
Atlntico

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 15

Grfico N 02: Mapa de Agrupaciones Hidrogrficas del Per

Fuente: Comisin Tcnica Multisectorial conformada por R.M. N 051-2007-PCM. Poltica y Estrategia Nacional de
Recursos Hdricos del Per. Per, Lima. 2009.

Grfico N 03: Ubicacin de la cuenca del rio Mantaro

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 16

El proyecto se ejecutara dentro de la jurisdiccin administrativa de la Administracin Local


de Agua Mantaro (ALA Mantaro), rgano desconcentrado de la Autoridad Nacional del
Agua (ANA).
Cuadro N 01 Ubicacin en coordenadas geogrficas UTM (WGS-84 / 18L - Sur) Captacin y
Devolucin de las aguas del rio Canipaco
VERTICE
CH-01

PUNTO DE CAPTACIN
ESTE
479097

NORTE
8635555

VERTICE
CH-02

PUNTO DE DEVOLUCIN
ESTE
485110

NORTE
8631048

Fuente: Memoria Descriptiva Proyecto C. H. Chilcay

2.1.2 Accesibilidad Vas de comunicacin a la Sub cuenca del rio Canipaco


Partiendo de la ciudad de Huancayo con direccin Sureste, por una va asfaltada
hasta el distrito de Chupuro con distancia de 13.38 km., luego en ascenso a la
cordillera Occidental por la va afirmada, donde se presentan varios desarrollos en
su trayecto, hasta la capital del distrito de Colca, une la distancia de 36.45 km., se
prosigue en direccin este por la va regularmente afirmada en direccin al distrito
al centro poblado de Chilcay, lugar donde realizara la estructura de captacin y
derivacin de las aguas para la central hidroelctrica Chilcay.

Terrestre: Lima - La Oroya Huancayo - 315 km, Asfaltado y en buen estado.


Huancayo - Colca centro poblado de Chilcay - zona de obra, afirmado en
regular estado de conservacin.

Area: Lima Jauja, luego prosiguiendo por va terrestres a la ciudad de


Huancayo, Colca, y al Centro poblado de Chilcay por vas de regular estado, en
direccin Sur Oeste al mbito de estudio.

Frrea: Estaciones, Lima - La Oroya Jauja Huancayo - Telleria,


prosiguiendo por va terrestres en direccin Este, por el distrito de Moya y
ascendiendo al mbito de estudio.

2.1.3 Aspectos Socioeconmicos de la Sub cuenca de Canipaco


La poblacin de la sub cuenca del ro Canipaco, polticamente se encuentra dentro
de la jurisdiccin de los distritos de: Carhuacallanga, Chacapampa, Chicche,
Chongos Alto, Chupuro, Colca, Huasicancha, provincia de Huancayo, Chongos
Bajo, Yanacancha, provincia de Chupaca y estos al departamento de Junn;
Huayllahuara, Vilca, provincia de Huancavelica, departamento de Huancavelica;

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 17

Huantan, Laraos, provincia de Yauyos, departamento de Lima. El cual representa


un aproximado de 23,485 habitantes, segn el instituto Nacional de Estadstica e
Informtica (INEI).
Cuadro N 02: Poblacin Total del rea de Influencia de la Sub cuenca Canipaco
Departamento

Provincia

HUANCAYO
JUNIN

CHUPACA
HUANCAVELICA

HUANCAVELICA

LIMA

YAUYOS

TOTAL

Poblacin
Proyectada
(2011)

Distrito
CARHUACALLANGA
CHACAPAMPA
CHICCHE
CHONGOS ALTO
CHUPURO
COLCA
HUASICANCHA
CHONGOS BAJO
YANACANCHA
HUAYLLAHUARA
VILCA
HUANTAN
LARAOS

1,076
1,070
1,143
1,574
1,943
2,088
948
4,326
3,461
840
3,164
964
888
23,485

Hombre

574
499
558
743
952
948
473
2,079
1,704
386
1,509
527
569
11,521

Mujer

502
571
585
831
991
1,140
475
2,247
1,757
454
1,655
437
319
11,964

ndice
de
Pobreza

Pobreza
Extrema

48.4
72.1
64.9
69.3
25.7
30.2
54.2
44.5
85.6
79.4
81.2
-

16.6
26.4
21.6
28.9
7.0
9.8
16.2
13.2
50.6
39.7
47.0
-

Fuente: Estimaciones y proyecciones de poblacin por sexo, segn Departamento, Provincia y Distrito, 2011-INEI.
Pobreza Distrital, INEI 2009

En el Cuadro N02. Se muestra que el mayor ndice de pobreza y Extrema pobreza,


se encuentra en el distrito de Yanacancha con un 85.6% y 50.6%. En el rea de
influencia de la sub cuenca del Canipaco.
(Ver Plano P-01)

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 18

Grfico N 04: Poblacin por Distritos total del rea de influencia.


Poblacin por Distritos
4,326

4,500

3,461
3,164

3,500
3,000
2,500

1,943

2,000

1,574
1,076

1,070

1,143

948

840

1,000

964

888

LARAOS

1,500

2,088

HUANTAN

Numero Total de Habitantes

4,000

HUANCAYO

CHUPACA

VILCA

HUAYLLAHUARA

YANACANCHA

CHONGOS BAJO

HUASICANCHA

COLCA

CHUPURO

CHONGOS ALTO

CHICCHE

CHACAPAMPA

CARHUACALLANGA

500

HUANCAVELICA

YAUYOS

Fuente: INEI 2009

En el Grafico N 04 nos muestra que el mayor nmero de habitantes se encuentra


en el distrito de Chongos Bajo 4,326 y el menor nmero de habitantes en el distrito
de Huayllahuara 840.

2.1.4 Geomorfologa de la Sub cuenca rio Canipaco


El anlisis morfomtrico de la sub cuenca del ro Canipaco, permite evaluar
cuantitativamente y cualitativamente, a partir de los diferentes parmetros e ndices
de forma que estima, el comportamiento de estas, ante un evento lluvioso extremo
(tormenta).
Se determin los siguientes parmetros morfomtricos: rea, permetro, cota
mxima, cota mnima, elevacin media, desnivel mximo, longitud axial y ancho de
la cuenca, adems se determin lo siguiente:

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 19

a) Factor de Forma
Es un ndice que permite establecer la tendencia morfolgica general en
funcin de la longitud axial de la cuenca y de su ancho promedio. Una cuenca
tiende a ser alargada si el factor de forma tiende a cero, mientras que su forma
redonda, en la medida que el factor forma tiende a uno.

b) Coeficiente de Compacidad
El coeficiente de compacidad es una relacin entre el permetro de la cuenca y
el permetro de una circunferencia con la misma superficie de la cuenca. Este
coeficiente define la forma de la cuenca, respecto a la similaridad con formas
redondas, dentro de rangos que se muestran a continuacin (FAO 1985).

Clase Kc1: Rango entre 1 y 1.25, corresponde a forma redonda a oval


redonda.

Clase Kc2: Rango entre 1.25 y 1.5, corresponde a forma oval redonda a
oval oblonga.

Clase Kc3: Rango mayor a 1.5, corresponde a forma oval oblonga a


rectangular oblonga.

c) Indic de Alargamiento
Este ndice propuesto por Horton, relaciona la longitud mxima encontrada en
la cuenca y el ancho mximo de ella medido perpendicularmente. Cuando el
ndice de alargamiento toma valores mayores a la unidad, se trata de cuencas
alargadas, mientras que los valores cercanos a 1, se trata de una cuenca poca
alargada.

d) Coeficiente de Masividad
Este coeficiente representa la relacin entre la elevacin media de la cuenca y
su superficie.
e) Factor de Circularidad (RC)
Propuesto por MILLER (1953), donde se pone en relacin el rea de la cuenca
y el rea de un circulo de igual permetro.

Los valores oscilan entre 0 y 1, y el mximo valor equivale a la unidad, lo que


corresponderan a una cuenca de forma circular.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 20

f) Razn de Elongacin (Re)


Es la relacin entre el dimetro de un circulo con igual rea que la de la cuenca
y la longitud mxima de la misma. La frmula propuesta por SCHUMM (1956)
es la siguiente:

Es la frmula ms extendida para calcular la razn de elongacin, debido a que


es la mejor correlacin que guarda con la hidrologa de la cuenca. As valores
de Re inferiores a 1 implican formas alargadas, cuanto menor sea Re ms
largada ser la forma de la cuenca.

g) Rectngulo Equivalente
Es el rectngulo equivalente a una transformacin geomtrica, que permite
representar a la cuenca de su forma heterognea con la forma de un
rectngulo, que tiene la misma rea y permetro (y por lo tanto el mismo ndice
de compacidad) e igual distribucin de alturas (y por lo tanto igual curva
hipsomtrica). En este rectngulo, las curvas de nivel se convierten en rectas
paralelas al lado menor. La Longitud del lado mayor y menor del rectngulo se
determin mediante la siguiente relacin:

) )

) )

Dnde:

I : Longitud del lado menor del rectngulo

L : Longitud del lado mayor del rectngulo

k : Coeficiente de compacidad

A : rea de la cuenca

h) Pendiente de la Cuenca Mtodo Alvord


Este criterio est basado, en la obtencin previa de las pendientes existentes
entre las curvas de nivel. Dividiendo el rea de la cuenca en reas parciales

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 21

por medio de sus curvas de nivel, y las lneas medias de las curvas de nivel. Se
determina mediante la siguiente ecuacin:
(

Dnde:

S
D1
Dn
D
A

: Pendiente de la cuenca
: Desnivel en la parte ms baja, en km
: Desnivel en la parte ms alta, en km
: Desnivel constante entre curvas de nivel, en km
: rea de la sub cuenca, en km2
: Longitud de las curvas de nivel

En el Cuadro N 03 se muestra el resultado del clculo de los parmetros


geomorfolgicos de la sub cuenca Canipaco:

Cuadro N 03: Parmetros Geomorfolgicos de la sub cuenca Canipaco


Parmetros
Morfo mtricos
rea (km2)
Permetro (km)
Cota Mxima
(msnm)
Cota Mnima
(msnm)
Desnivel entre
curvas de nivel
(km)
Longitud total de
curvas de nivel
(km)

Sub cuenca
Canipaco
1,293.82
206.52

Identificacin y
Formula
A
P

5 150.00

Cmax

Lectura de plano

3 050.00

Cmin

Lectura de plano

0,05

Dcn

Lectura de plano

6,945.78

Lcn

Calculo directo

Elevacin media
(msnm)

4,586.21

ELVm

Longitud de Rio
Principal (km)

82.70

Ancho de la
cuenca

15.64

W=A/L

54.89

Lmax

2 100.00

D=Cmax_Cmin

0.19

Ff=A/L2

Longitud mxima
de la cuenca
Desnivel Mximo
(m)
Factor de Forma

Interpretacin

Observacin
Calculo directo
Calculo directo

Se obtiene al
valor de la
mediana en la
curva
hipsomtrica

Segn curva
Hipsomtrica
Equivalente a la
longitud de la
cuenca
Determinado por la
relacin del rea y
longitud de la
cuenca

Diferencia de cota
mxima y mnima
Este ndice nos
muestra que la
cuenca es de

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 22

tendencia al
alargamiento

Coeficiente de
Compacidad

1.62

ndice de
Alargamiento

1.52

Coeficiente de
Masividad
(m/km2)

2.72

Factor de
Circularidad

Razn de
Elongacin

Longitud del lado


mayor del
rectngulo
equivalente (km)

Longitud del lado


menor del
rectngulo
equivalente (km)

Pendiente de la
cuenca Mtodo
Alvord (min)

0.38

0.49

K=0,282 P/A0,5

IAL= Lmax/Amax

Corresponde a
forma oval
oblonga a
rectangular
oblonga.
Indica que la
cuenca es poco
alargada

Rc=4 Pi A/P

Este indicador
muestra que la
cuenca tiene
tendencia al
alargamiento

Relaciona el rea
de la cuenca con el
rea de un circulo
de igual permetro

Re=1,1292A05/P

Este factor nos


indica que la
cuenca es
ligeramente
alargada

Relaciona el
dimetro de un
circulo con igual
rea que la cuenca
y la mxima
longitud de la
misma

Lado mayor del


rectngulo
equivalente

46.94

) )

Lado menor del


rectngulo
equivalente

27.56

1.34

Relaciona la
longitud mxima de
la cuenca el ancho
mximo de misma
medida
perpendicularmente
Relaciona la
elevacin media de
la cuenca y su
superficie

) )

S=Dcn Lcn/A

Indica que la
pendiente en la
cuenca en
general es baja

Relaciona
directamente el
desnivel entre
curvas de nivel.
Fuente: Elaboracin Propia

(Ver Plano P-02 / P-03)

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY
i)

Pgina 23

GEOLOGA
En la Sub cuenca del ro Canipaco, afloran rocas calizas, rocas que
desaparecen debajo de una capa de detritos.
En la sub cuenca del ro La Virgen existe un dimorfismo muy pronunciado entre
las dos mrgenes: rocas en la derecha y laderas detrticas en la izquierda.
(Ver Plano P-04)

Cuadro N 04: Geologa de la Sub cuenca del ro Canipaco


GEOLOGA - SUB CUENCA CANIPACO
SIMBOLO
Ji-c
Jm-c/ch
Ki-cs
Ki-g
Km-ch/p/j
Ks-chi
Ks-gr
Ks-gr/gd/to
Ks-j
Kti-ca
Qp-g
Qr-al
Qr-co
Qr-fg
T-an
T-gd
Tim-tt
TJ-pu
Tm-ss
Ts-va
Lag

DESCRIPCION
SERIE
SISTEMA
Formacin Condorsinga
INFERIOR
JURASICO
Formacin Cercapuquio, Chunumayo MEDIO
JURASICO
Grupo Casma
INFERIOR
CRETACEO
Grupo Goyllarisquizga
INFERIOR
CRETACEO
Formacin Chulec, Pariatambo, Jumasha
MEDIO
CRETACEO
Formacin Chilca
SUPERIOR
CRETACEO
Granito
SUPERIOR
CRETACEO
Granito, granodiorita, tonalita
SUPERIOR
CRETACEO
Formacin Jumasha
SUPERIOR
CRETACEO
Formacin Casapalca
SUPERIOR
CRETACEO
Depsitos glaciares
PLEISTOCENO CUATERNARIO
Depsito aluvial reciente
RECIENTE
CUATERNARIO
Depsito coluvial
RECIENTE
CUATERNARIO
Depsitos fluvioglaciares
RECIENTE
CUATERNARIO
Andesita
TERCIARIO
Granodiorita
TERCIARIO
Volcnico Tantar
INFERIOR
TERCIARIO
Grupo Pucar
TRIASICO
Grupo Sacsaquero
MEDIO
TERCIARIO
Volcnico Astobamba
SUPERIOR
TERCIARIO
Laguna
Total

ERA
MESOZOICO
MESOZOICO
MESOZOICO
MESOZOICO
MESOZOICO
MESOZOICO
MESOZOICO
MESOZOICO
MESOZOICO
MESOZOICO
CENOZOICO
CENOZOICO
CENOZOICO
CENOZOICO
MESOZOICO
MESOZOICO
CENOZOICO
MESOZOICO
CENOZOICO
MESOZOICO

AREA (ha)
12,814.17
18,888.32
1,084.85
4,363.56
14,367.43
1,214.16
1,540.23
201.10
1,243.73
5,266.10
6,768.60
5,673.95
726.28
10,945.32
865.17
262.59
3,480.17
19,545.96
6,621.91
12,453.50
1,054.78
129,381.87

Fuente: Base de Datos de R. N. INRENA

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY
j)

Pgina 24

CAPACIDAD DE USO MAYOR DE TIERRAS

Cuadro N 05: Capacidad de Uso Mayor de Tierras de la Sub cuenca del ro Canipaco
CAPACIDAD DE USO MAYOR DE TIERRAS SUB CUENCA CANIPACO (CUM)
SIMBOLO

DESCRIPCIN

AREA (ha)

Lag

Laguna

Nev

Nevado

P2sc-Xse

Pastoreo de paramo, Calidad Agrologica Media. Proteccin. Limitacin por suelo, erosin y clima.

50,911.14

P3sec-Xse

Pastoreo de paramo, Calidad Agrologica Baja - Proteccin. Limitacin por suelo y erosin

40,316.19

Xse

Proteccin (limitacin por suelo y erosin)

Xse**

Proteccin (formacin de nivales)

Xse-P2sc

Proteccin - Pastoreo de paramo, Calidad Agrologica Baja. Limitacin por suelo, erosin y clima

Xse-P3se-A3sec

Proteccin - Pastoreo temporal, Calidad Agrologica Baja - Cultivo en Limpio bajo riego. Limitacin por suelo.

1,179.82
255.96

1,728.38
1,377.65
22,332.03
11,280.70

Total

129,381.87

Fuente: Base de Datos de R. N. INRENA

En el Cuadro N 05, se muestra la Capacidad de uso mayor de tierras de la sub


cuenca del Canipaco, la que tiene mayor extensin es P2sc-Xse con 50 911.14
ha.
(Ver Plano P-05)

k) CLIMATOLOGA

Las zonas altas de la sub cuenca del ro Canipaco, por encima de los 5 000
m.s.n.m. estn cubiertas de nevados, donde la temperatura media anual se
mantiene en la proximidad de los 0C y la precipitacin es de tipo nival.
Entre los 4 000 y 5 000 m.s.n.m., se ubica las zonas de punas y pramos
andinos. Las condiciones climticas son muy variables con temperaturas
medias anuales que van desde 0C a 7C y lluvias entre los 750 a 800
milmetros al ao.
Por debajo de las punas y pramos andinos se encuentra la regin del alto
valle, entre

los 3500

y 4000 m.s.n.m. Climticamente se

registran

precipitaciones menores a 700 milmetros por ao, con temperaturas entre 5 y


10 C.
Las lluvias se concentran entre los meses de Diciembre a Abril con valores que
alcanzan el 70% del total anual.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 25

CONDICIONES AMBIENTALES

l)

Temperatura mnima : -12 C

Temperatura media : 12 C

Temperatura mxima : 23 C

Velocidad media / mxima del viento : 90 km/h

Altura msnm : 3050 - 5150 msnm

Nivel Isoserunico : Medio

HIDROLOGA MICROCUENCAS
Cuadro N 06: Micro cuencas de la Sub cuenca del ro Canipaco
MICROCUENCAS - SUB CUENCA CANIPACO
NOMBRE MICROCUENCA
La Virgen
Acchapata (rgimen temporal)
Canipaco Bajo
Canipaco
Colca (rgimen temporal)
Total

AREA (ha)
62 985.29
12 661.03
7 516.52
42 197.67
4 021.36
129,381.87
Fuente: Elaboracin Propia

En el Cuadro N 06, se muestra las microcuencas de la sub cuenca del


Canipaco, la que tiene mayor extensin es ro La Virgen con 62 985.29 ha.
Siendo la principal fuente de recursos hdricos conjuntamente con la micro
cuenca del rio Canipaco, sus orgenes son de origen nival y lacustres.
(Ver Plano P-06)

m) CLASIFICACIN ORDINAL DE LOS AFLUENTES DEL RIO CANIPACO


Cuadro N 07: Clasificacin Ordinal de la sub cuenca del ro Canipaco
CLASIFICACIN ORDINAL
Orden de Rio
Orden 1
Orden 2
Orden 3
Orden 4
Orden 5
Total

Longitud (ml)
383,549.09
156,871.42
80,798.23
79,310.89
20,550.01
721,079.63
Fuente: Elaboracin Propia

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 26

En el Cuadro N 07, el de mayor longitud es de primer orden con 383,549.09


ml. Y con menor longitud es del orden quinto con 20,550.01 ml. El que
descarga sus aguas al ro Vilca.
(Ver Plano P-07)

2.1.5 Aspectos Ecolgicos


a)

ZONAS DE VIDA

De acuerdo a la Clasificacin Ecolgica del Per, elaborada por el Dr. Leslie R.


Holdrige, la sub cuenca del ro Canipaco presenta las siguientes formaciones
ecolgicas:
Cuadro N 08: Zonas de Vida de la sub cuenca del ro Canipaco
ZONAS DE VIDA SUB CUENCA CANIPACO (Ecologa)
SIMBOLO
bh-MT
bs-MBT
NT
pmh-SaT
tp-AT

DESCRIPCION
VERTIENTE PROVINCIA HUMEDA PISO ALTITUDINAL REGION LATITUDINAL AREA (ha)
bosque hmedo - Montano Tropical
Pacfico
Hmedo
Montano
Tropical
22959.93
bosque seco - Montano Bajo Tropical
Pacfico
Subhmedo
Montano Bajo
Tropical
1404.39
Nival Tropical
Pacfico
Nival
Nival
Tropical
1679.41
pramo muy hmedo - Subalpino Tropical Pacfico
Perhmedo
Subalpino
Tropical
48433.29
tundra pluvial - Alpino tropical
Pacfico
Superhmedo
Alpino
Tropical
54904.85
Total
129381.87
Fuente: Base de Datos de R. N. INRENA

Formacin Nival Tropical (NT)


La zona de Vida Nival Tropical abarca totalmente el piso Nival. Estos
glaciares se extiende en la cresta de los andes generalmente por encima
de los 5000 m.s.n.m.
El Clima en esta Zona de Vida, las caractersticas bioclimticas han sido
estimadas en base al diagrama de Holdridge. La bio_temperatura media
anual generalmente se encuentra por debajo de 1.5C y el promedio de
precipitacin total anual por ao a menudo vara entre 500 y 1000
milmetros.
En cuanto al relieve y suelos la topo_fisiogrfica es abrupta y constituida
netamente por suelos netamente lticos, rocosos o peascosos; y las
nicas formas de vida observables son algunas algas sobre la nieve
misma, as como lquenes y crustceos que crecen sobre las rocas
oscuras, en los lmites inferiores del nival y muy cerca de la tundra.
Las formaciones nivales tienen importancia desde el punto de vista del
rgimen hidrolgico de los ros y lagunas alto andinas.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 27

Tundra pluvial Alpino Tropical (tp-AT)


Se extiende entre los 4 300 y 5 000 m.s.n.m. Comprende la parte alta de
la cuenca.
La biotemperatura media anual es de 3,2 C.

Pramo muy Hmedo Sub Alpino Tropical (pmh SaT)


Geogrficamente, ocupa la parte media de la cuenca y entre los 3 900 y 4
500 m.s.n.m.
La biotemperatura media anual mxima es de 6C y la media anual
mnima es de 3.8 C; en cuanto a las precipitaciones total por ao es de
1254.8 milmetros y el promedio mnimo, de 513.4 milmetros.
En cuanto al relieve y suelos la configuracin topogrfica est definida
por reas bastantes extensas, suaves a ligeramente onduladas y
colinadas; y el escenario vegetal est constituido por una abundante
mezcla de gramneas y otras hiervas de hbitat perenne.
De estas zonas de vida son estas las que actualmente presentan los
mejores pastos naturales y consecuentemente son las de mayor
capacidad para producir este tipo de plantas para el sostenimiento de
ganadera productiva.

Bosque hmedo Montano Tropical (bh-MT)


Geogrficamente se distribuye en la parte baja de la cuenca, entre los 2
800 y 3 800 m.s.n.m. y a veces llega hasta 4000 metros de altitud.
En esta zona de vida existen las estaciones climatolgicas y
pluviomtricas. La biotemperatura media anual mxima es de 13.1C y la
media anual mnima de 7.3 C. El promedio mximo de precipitacin total
por ao es de 1154 milmetros y el promedio mnimo de 498 milmetro.
El relieve es dominante empinado ya que conforma el borde o parte
superior de las laderas que enmarca a los valles interandinos, hacindose
un tanto ms suave en el lmite con las zonas de Paramo, por lo general
aqu predominan suelos profundos, arcillosos, de reaccin acida tonos
rojizos a pardos. La vegetacin natural clmax prcticamente no existe y

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 28

se reduce a pequeos bosques residuales homogneos. Esta Zona de


Vida permite llevar a cabo una agricultura secano.

Bosque seco - Montano Bajo Tropical (bs MBT)


Ocupan los valles mesoandinos, entre los 2500 y 3200 m.s.n.m.
La biotemperatura media anual mxima es de 16.5C y la mnima es de
10.9C. El promedio mximo de precipitacin total por ao es de 972.9
milmetros y el promedio mnimo es de 449.3 milmetros.
En cuanto al relieve varia de suave o plano, propio de los valles
interandinos, donde los suelos tienen buen drenaje y se hacen ms
superficiales y siempre de naturaleza calcrea.
La vegetacin primaria ha sido fuertemente deteriorada y sustituida gran
parte por los cultivos que se llevan a cabo mediante el riego o con la
lluvia en los lmites superiores de la formacin; en estas tierras se
desarrolla la agricultura de secano muy limitada, normalmente se recurre
al riego y se conducen cultivos de maz, papa, habas, arveja, trigo y otros.
(Ver Plano P-08)

b) FLORA Y FAUNA
En la sub cuenca del rio Canipaco existe una diversidad de fauna silvestre
(caractersticos de las zonas altas de la sierra) y flora silvestre (la gran mayora
de estos pastos nativos y silvestres sirven como alimento de subsistencia para
los animales tanto silvestres y domsticos), si observamos los cuadros a
continuacin, casi en todas las zonas la presencia de estas especies son muy
similares diferencindose segn piso ecolgico.

Flora:
Los inventarios florsticos, adems del inters cientfico que representan,
se han constituido en los ltimos aos una parte importante de la lnea
base de estrategias de manejo y conservacin de los recursos naturales.
En los siguientes cuadros se detalla la flora existente en los distritos de la
sub cuenca del ro Canipaco.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 29

Cuadro N 09: Flora perteneciente a la Sub cuenca del rio Canipaco


N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44

Nombre comn
Nombre cientfico
Especies forestales nativos
Quishuar
Buddleia incana
Quinual
Polylepis sp.
Molle
Schinus molle
Tojollhuay
Echinopsis sp.
Mutuy
Senna versicolor
Colle
Buddleia coricea
Aliso
Alnus acuminata
Arrayan
Sambucus peruviana
Especies forestales exticas
Eucalipto
Eucalyptus globulus
Pino
Pinus radiata
Cipres
Cupresuss macrocarpa
Especies frutales
Manzana
Malus sp.
Guinda
Prunus sertina
Membrillo
Cydonia oblonga
Durazno
Prunus prsica
Especies arbustivas y herbceas
Talla
Baccharis odorata
Machamacha
Pernettya prostrata
Yanatantar
Dunalia spinosa.
Pastos
Calamagrostis spp.
Chilca
Baccharis latifolia
Marco
Ambrosia arborescens
Marmaquilla
Ageratina stembergiana
Centadera de suegra
Oroya sp.
Huamanpinta
Chuquiraga spinoza
Garbancillo
Astragalus garbancillo
Valeriana
Valeriana sp.
Grama
Pennisetum clandestinum
Huamanripa
Senecio tephrosioides
Totora
Scirpus sp.
Cactus
Echinopsis pachanoi
Malva
Taraza jorgensenii
Manzanilla
Matricaria chamomilla
Chilataya
Baccharis sp.
Ichu
Stipa ichu
Chinches
Tagetes multiflora
Ajenjo
Artemisia sp.
Chamisa
Baccharis sp.
Malma
Ageratina azangaroensis
Cactus
Trichocereus spp.
Mua
Mintostachis mollis
Arnica
Achyrocline alata
Huayrasato
Nn.
Romero
Rosmarinus officinalis
Cola de caballo
Equisetum sp.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY
45
46
47

Grama china
Ua cusma
Hinojo

Pgina 30

Lolium sp.
Werneria villosa
Foeniculum vulgare
Fuente: CARITAS-Huancavelica-2008

Fauna:
La fauna dentro de los distritos de la sub cuenca del ro Canipaco es muy
variada como se muestra en los siguientes cuadros.
Cuadro N 10: Fauna perteneciente a la Sub cuenca del rio Canipaco
N

Nombre comn

1
2
3
4
6
7
8
9

Venado
Zorro
Zorrillo
Vizcacha
Puma
Comadreja
Zorrino
Taruca

10
11
12
13
14
15
16
17
18
19

Yanavico
Chihuaco
Cerncalo o Killin
Perdiz
Gaviln
Pato silvestre
guila
Aguilucho
Cerncalo
Huachua o Huallata

Nombre Cientfico
Mamferos
Odocoileus virginianus
Pseudalopex culpaeus
Conepatus chinga
Ladigium peruanum
Puma concolor
Mustela frenata
Conepatus sp.
Hippocamelus antisensis
Aves
Plegadis ridgwayi
Turdus chiguanco
Falco sparverius
Nothoprocta sp.
Buteo sp.
Anas spp.
Accipiter sp.
Geranoaetus melanoleucus
Falco sparverius
Chloephaga melanoptera
Fuente: CARITAS-Huancavelica-2008

2.1.6 Calidad del Agua


Cuadro N 11: Anlisis Qumico de agua del ro Canipaco
Anlisis

Mtodo de
Referencia

Lmite de
Cuantificacion

Resultado

Unidad

Fecha de Anlisis

pH

EPA 150.1

(1) 8.2

22/02/2013

Conductividad

EPA 120.1

0.5

(1) 274.1

uS/cm

22/02/2013

Aceites y Grasas

EPA 1664-A

N.D.

mg/L

28/02/2013

DBO5

EPA 405.1

mg/L

23/02/2013

DQO

EPA 410.1

20

mg/L

27/02/2013

Fenoles

SM 5530-C

0.0005

N.D.

mg/L

27/02/2013

N - Nitrato

EPA 352.1

0.05

0.16

mg/L

27/02/2013

N- Nitrito

EPA 354.1

0.005

0.007

mg/L

23/02/2013

Oxgeno Disuelto

EPA 360.1

0.1

(1) 8.1

mg/L

22/02/2013

Sulfatos

EPA 375.4

0.5

43

mg/L

26/02/2013

Sulfuro

SM 4500 S-2 D

0.002

N.D.

mg/L

26/02/2013

*Coliformes Totales

SM 9221 B

790

NMP/100mL

23/02/2013

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Anlisis
Aluminio Total
Arsnico Total
Boro Total
Bario Total
Berilio Total
Bismuto Total
Calcio Total
Cadmio Total
Cobalto Total
Cromo Total
Cobre Total
Hierro Total
Potasio Total
Litio Total
Magnesio Total
Manganeso Total
Molibdeno Total
Sodio Total
Niquel Total
Fsforo Total
Plomo Total
Antimonio Total
Selenio Total
Silicio Total
Estao Total
Estroncio Total
Titanio Total
Talio Total
Vanadio Total
Zinc Total
Plata Total
Mercurio Total

Mtodo de
Referencia
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 200.7
EPA 245.7

Lmite de
Cuantificacin
0.002
0.002
0.008
0.001
0.0005
0.01
0.005
0.001
0.001
0.001
0.002
0.003
0.02
0.001
0.002
0.001
0.002
0.02
0.001
0.01
0.001
0.002
0.002
0.01
0.003
0.0007
0.001
0.003
0.001
0.002
0.002
0.0001

Pgina 31

Resultado

Unidad

Fecha de Anlisis

3.495
0.022
0.08
0.126
N.D.
N.D.
84.46
N.D.
0.003
0.004
0.01
4.406
2.89
0.033
8.853
0.301
N.D.
10.81
0.005
0.41
0.022
N.D.
N.D.
12.79
0.031
0.3079
0.136
N.D.
0.012
0.087
N.D.
N.D.

mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L

25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
25/02/2013
27/02/2013

FUENTE: EIA 2013 Informe de Ensayo N 1302385-01

ANLISIS QUMICO DE AGUA DEL RO CANIPACO


PH:
ECXIO mm/hos:
DUREZA P.P.M:
BORO P.P.M:
FIERRO P.P.M.
Aniones solubles m gr/Lts:
CL :
CO3 :
=
HCO3 :
SO4=
NO3-:
Cationes solubles m gr/ Lts:
Ca++:
Mg++:
Na+:
K++:
RAS:
Clasificacin:
Nominacin:

8.3
0.57
24
2
0.00
0.71
0.36
2.10
1.3
0.1
3.7
1.01
0.00
0.00
0.00
C2
Salnd. media, sin Na.
FUENTE: ANA - Proyecto de Irrigacin Ullapata.- Canipaco

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 32

2.2 ANLISIS Y TRATAMIENTO DE LA INFORMACIN HIDROMETEOROLGICA E


HIDROMTRICA DE LA SUB CUENCA DEL RIO CANIPACO
2.2.1 Anlisis de las Variables Meteorolgicas

Red Hidrometereolgica en la Sub cuenca del rio Canipaco


En el presente estudio se consideran estaciones hidromtricas ms prximas a la
sub cuenca del ro Canipaco, con caractersticas similares como; fisiografa, altitud,
y climticas a la sub cuenca en estudio, considerando estaciones como las de
SENAMHI, Electro Per, Electro Andes e IGP, que son empleadas en el tratamiento
de la informacin climtica para trabajos de investigacin cientfica por el Instituto
Geofsico del Per (IGP), en la cuenca del ro Mantaro.
Se cuenta con estaciones hidromtricas en el interior y exteriores del mbito de la
sub cuenca del Canipaco, que se opera un conjunto de Doce (12) estaciones
hidromtricas operadas por diferentes instituciones, como se muestra en el cuadro
siguiente.

Cuadro N 12: Ubicacin de las Estaciones para determinar las variables Meteorolgicas
ESTACIN

ESTE

NORTE

ALTITUD

DEPTO

PROVINCIA

PERIODO

FUENTE

Acostambo

493640

8633350

3,650

Huancavelica

Tayacaja

1962 - 2004

Electro Per

Cercapuquio

465126

8631045

4,390

Junn

Huancayo

1962 - 2004

Electro Per

Chilicocha

455303

8599946

4,200

Huancavelica

Huancavelica

1962 - 2004

Electro Per

Huancalpi

473735

8609276

3,800

Huancavelica

Huancavelica

1965 - 2002

SENAMHI

Huantan

411251

8622074

3,271

Lima

Yauyos

1963 - 1976

IRI

Huichicocha

441616

8611429

4,660

Junn

Huancayo

1964 - 2004

Electro Per

Laive

460793

8645521

3,990

Junn

Chupaca

1963 - 2002

SENAMHI

Palaco

467661

8636261

3,650

Junn

Huancayo

1969 - 2004

Electro Per

Pilchaca

490734

8629112

3,570

Huancavelica

Huancavelica

1964 - 2002

SENAMHI

Telleria

486617

8631552

3,050

Huancavelica

Huancavelica

1964 - 2004

Electro Per

Viques

475151

8656186

3,186

Junn

Huancayo

1964 - 1998

SENAMHI

Yauricocha

422074

8638326

4,522

Lima

Yauyos

1943 - 2000

SENAMHI

Fuente: IGP Atlas Climtico de precipitacin y temperaturas del aire en la cuenca Mantaro

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 33

Grfico N 05: Estaciones Pluviomtricas e Hidromtricas en la Sub cuenca del rio Canipaco.

Fuente: IGP Consultor

a)

Temperatura
El registro de la temperatura ms representativo de la sub cuenca Canipaco es
la que corresponde a la estacin de Laive y Huancalpi, que involucra el rea de
estudio. Este parmetro vara de 5,10 C en julio y a 10,12 C en el mes de
Octubre, se considera la estacin Laive y Huancalpi por estar ms prximas a
la sub cuenca del Canipaco, que son administradas por SENAMHI.
Cuadro N 13: Temperatura media mensual
MESES

ESTACIONES
T C

ENE

FEB

Max

16,38 15,28

MAR

ABR

MAY

15,46 16,15

17,48

JUN

JUL

18,4 17,28

AGO

SEP

OCT

17,91 17,16 21,86

NOV

DIC

18,16 17,22

MEDIA
ANUAL
17.39

Huancalpi
Min.

5,23

4,96

Max. 15,11 14,36

5,29

4,84

16,23 14,34

3,39

-2,60

-1,86

-1,09

3,22

3,98

4,42

4,77

2.88

14,07 15,05 13,55

15,54 13,75 14,77

14,86 13,12

14.56

-0,15

-0,88

2,1

-1.67

8.54 10.12

9.14

9.30

8.29

Laive
Min.
Promedio

3,53

3,43

3,29

-2,35

-3,59

-9,49

-8,58

-7,36

10.06

9.51

10.07

8.25

7.84

5.34

5.10

6.25

0,04

Fuente: SENAMHI

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 34

b) Humedad relativa
Este parmetro no es medido en ninguna estacin existente dentro de la sub
cuenca del ro Canipaco. Como referencia mostramos los registros de la
estacin de Huayao ubicado en la cuenca vecina del ro Cunas. Durante los
meses de lluvia (Noviembre a Marzo) la humedad relativa, varia de 27,6% a
28,9%, en cambio en los meses de estiaje vara de 21.4% a 24%.
Cuadro N 14: Humedad media mensual
MESES
ESTACIN
Huayao

ANUAL
ENE

FEB

MAR

ABR

MAY

JUN

JUL

AGO

SEP

OCT

NOV

DIC

27,0

27,9

28,9

26,8

24,0

21,8

21,4

23,1

25,5

27,2

27,6

29,1

25.9

Fuente: SENAMHI

c)

Evaporacin
La evaporacin tambin es un parmetro que nicamente es medido en la
estacin de Huayao. En el ao variable en 39,4 mm/mes a 105,2 mm/mes.
Observndose una evaporizacin alta en la poca de estiaje.
Cuadro N 15: Evaporacin media mensual
MESES

ESTACIN
Huayao

ANUAL
ENE

FEB

MAR

ABR

MAY

JUN

JUL

AGO

SEP

OCT

NOV

DIC

46,2

39,4

39,0

54,8

105,2

81,7

87,6

95,3

82,7

83,6

76,7

58,0

850,1

Fuente: SENAMHI

d) Velocidad del viento


Este parmetro vara de 4,00 m/s a 6,06 m/s, presentndose mayor valor en el
mes de noviembre. En cambio el mes de menor valor se registra en Febrero.
Cuadro N 16: Velocidad de viento
MESES
ESTACIN

ANUAL
ENE

FEB

MAR

ABR

MAY

JUN

JUL

AGO

SEP

OCT

NOV

DIC

Huancalpi

4,67

3,00

4,75

5,86

5,60

3,67

4,00

4,63

3,67

3,94

5,38

3,86

4,42

Laive

5,21

5,00

4,08

3,90

4,32

4,70

4,19

4,90

5,20

5,39

6,73

5,87

4,69

Promedio

4,94

4,00

4,42

4,88

4,96

4,19

4,10

4,77

4,44

4,67

6,06

4,87

4,56

Fuente: SENAMHI

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

e)

Pgina 35

Horas del sol


Las horas del Sol mensual media diaria vara desde 8:00 horas en el mes de
Julio a 5:47 horas en el mes de Marzo, con un valor medio multianual de 7:27
horas diarias, estos valores son normales en las pocas de lluvia; las horas de
sol diarias son ms bajas en relacin al periodo de estiaje. En el cuadro N17,
se puede observar su variacin durante el ao medio.
Cuadro N 17: Horas del sol da media mensual
MESES

ESTACIN
Huayao

ANUAL
ENE

FEB

MAR

ABR

MAY

JUN

JUL

AGO

SEP

OCT

NOV

DIC

5,9

5,6

5,5

7,2

8,6

8,8

9,0

8,5

7,6

7,1

7,5

6,2

87,2

Fuente: SENAMHI

f)

Evapotranspiracin
La evapotranspiracin fue calculada mediante el mtodo de Penman-Monteith.
La informacin de humedad relativa, horas del sol y evaporacin corresponde a
la estacin de Huayao.
Cuadro N 18: Evapotranspiracin en la Sub cuenca del rio Canipaco
MESES

ESTACIN
Huayao

ANUAL
ENE

FEB

MAR

ABR

MAY

JUN

JUL

AGO

SEP

OCT

NOV

DIC

4,3

4,2

4,0

3,9

3,8

3,7

3,7

4,0

4,0

4,4

4,3

4,4

4,1

Fuente: SENAMHI

2.2.2 Tratamiento de la Informacin Hidrometeorolgica e Hidromtrica

En el tratamiento de la informacin se estar considerando la informacin


hidromtrica de la estaciones indicas en el tem anterior tomando nfasis con las
estaciones que se encuentren en mbito de la sub cuenca.
Para la determinacin de la precipitacin media en la sub cuenca del ro Canipaco
se utiliz el mtodo de ponderacin lluvia altitud. Para ello se utiliz adicional a los
datos pluviomtricos registrados en las Estaciones que estn ms prximas a la
sub cuenca, los promedios multianuales de seis estaciones pluviomtricas
existentes en el rea de estudio, de propiedad de SENAMHI (Chilicocha, Huancalpi,
Telleria y Laive) y Electro Per S.A.: (Palaco, Huichicocha y Cercapuquio).

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 36

Cuadro N 19: Precipitacin Total Mensual Completa y Consistente (mm) Ao Promedio Histrico
(1960 2002)
ESTACION
Acostambo
Cercapuquio
Chilicocha
Huancalpi
Huantan
Huichicocha
Laive
Palaco
Pilchaca
Telleria
Viques
Yauricocha
PROMEDIO
MENSUAL

ENERO

FEBRERO

MARZO

ABRIL

123.00
134.70
132.90
139.20
136.60
116.30
156.20
110.90
127.20
90.60
128.50
160.50

119.40
144.90
126.40
144.60
135.90
121.00
169.40
111.40
127.90
100.80
139.70
165.80

108.10
141.90
124.00
125.70
165.50
128.30
140.90
95.20
108.40
73.60
91.70
174.90

44.90
71.50
58.00
63.70
55.20
49.10
64.10
45.30
43.50
38.50
32.00
94.10

129.72

133.93

123.18

54.99

18.90
29.60
14.90
28.40
9.20
13.20
24.00
18.20
14.50
13.70
14.10
22.50

11.60
9.20
6.70
24.20
0.00
6.70
9.30
8.00
13.60
7.40
11.40
12.30

10.90
10.90
5.90
21.90
1.10
5.20
12.90
9.60
11.10
8.30
11.40
12.10

20.80
18.10
14.60
33.10
0.90
11.40
23.90
18.00
20.80
17.70
11.60
19.80

42.30
44.90
27.70
45.60
4.20
21.50
63.10
39.90
44.10
38.40
34.00
34.50

62.50
69.50
50.30
83.70
22.40
50.60
79.40
58.10
61.70
54.00
75.30
82.60

69.90
75.80
56.70
86.50
17.20
52.10
76.40
60.90
64.00
51.40
77.40
73.90

89.10
103.80
83.70
118.10
80.40
95.30
117.30
83.60
91.30
72.00
76.20
136.60

PROMEDIO
ANUAL
60.12
71.23
58.48
76.23
52.38
55.89
78.08
54.93
60.68
47.20
58.61
82.47

18.43

10.03

10.11

17.56

36.68

62.51

63.52

95.62

63.02

MAYO

JUNIO

JULIO

AGOSTO

SETIEMBRE

OCTUBRE

NOVIEMBRE

DICIEMBRE

Fuente: IGP Atlas Climtico de precipitacin y temperaturas del aire en la cuenca Mantaro

Del clculo efectuado se concluye que la precipitacin media anual acumulada en la


sub cuenca del ro Canipaco es de 756.28 milmetros.

Grfico N 06: Anlisis de Precipitacin Media Acumulada Multianual por Estaciones en la Sub
cuenca del rio Canipaco

Fuente: Procesado Consultor - IGP

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

P.A.
721.40
854.80
701.80
914.70
628.60
670.70
936.90
659.10
728.10
566.40
703.30
989.60
756.28

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 37

Cuadro N 20: Anlisis de Doble Masa para las estaciones Laive, Huancalpi, y Huichicocha Histrico
(1963 2011)
AO
1963
1964
1965
1966
1967
1968
1969
1970
1971
1972
1973
1974
1975
1976
1977
1978
1979
1980
1981
1982
1983
1984
1985
1986
1987
1988
1989
1990
1991
1992
1993
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011

Laive
P.A
506.60
737.90
795.60
867.20
851.50
776.90
586.30
854.50
1065.93
1251.83
782.80
779.40
702.30
844.80
525.39
735.71
713.50
1006.80
1321.00
1697.95
503.55
1148.70
966.50
945.40
1055.60
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1055.60
958.16
1080.83
1115.89
958.50
762.60
657.80
685.80
587.20
610.30
715.90
659.70
930.70

P.Aac
506.60
1244.50
2040.10
2907.30
3758.80
4535.70
5122.00
5976.50
7042.43
8294.26
9077.06
9856.46
10558.76
11403.56
11928.95
12664.66
13378.16
14384.96
15705.96
17403.91
17907.46
19056.16
20022.66
20968.06
22023.66
22023.66
22023.66
22023.66
22023.66
22023.66
22023.66
22023.66
22023.66
22023.66
22023.66
22023.66
23079.26
24037.42
25118.25
26234.14
27192.64
27955.24
28613.04
29298.84
29886.04
30496.34
31212.24
31871.94
32802.64

Huancalpi
P.A
P.Aac
0.00
0.00
306.83
306.83
342.43
649.26
665.70
1314.96
879.90
2194.86
555.10
2749.96
286.64
3036.60
707.00
3743.60
895.95
4639.55
963.97
5603.52
1308.85
6912.37
949.05
7861.42
627.70
8489.12
790.30
9279.42
1070.70
10350.12
1059.50
11409.62
654.40
12064.02
784.30
12848.32
987.65
13835.97
1091.07
14927.04
577.70
15504.74
791.50
16296.24
490.60
16786.84
1116.20
17903.04
502.30
18405.34
464.10
18869.44
559.40
19428.84
1192.50
20621.34
815.80
21437.14
1163.60
22600.74
2086.50
24687.24
1290.60
25977.84
940.10
26917.94
1460.80
28378.74
1059.40
29438.14
1000.55
30438.69
986.55
31425.24
677.10
32102.34
1204.40
33306.74
771.30
34078.04
865.90
34943.94
638.30
35582.24
884.10
36466.34
622.95
37089.29
594.50
37683.79
0.00
37683.79
0.00
37683.79
0.00
37683.79
0.00
37683.79

Huichicocha
P.A
P.Aac
0.00
0.00
39.20
39.20
494.80
534.00
750.70
1284.70
618.40
1903.10
460.60
2363.70
476.80
2840.50
578.70
3419.20
522.20
3941.40
489.60
4431.00
559.10
4990.10
343.50
5333.60
499.60
5833.20
534.00
6367.20
419.90
6787.10
460.60
7247.70
438.70
7686.40
510.30
8196.70
512.30
8709.00
663.50
9372.50
679.40
10051.90
1181.70
11233.60
595.10
11828.70
784.30
12613.00
317.60
12930.60
195.10
13125.70
584.40
13710.10
1237.40
14947.50
413.80
15361.30
120.60
15481.90
1051.70
16533.60
667.00
17200.60
657.90
17858.50
467.70
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20
0.00
18326.20

ESTACION PROMEDIO
P.A
P.Aac
168.87
168.87
361.31
530.18
544.28
1074.45
761.20
1835.65
783.27
2618.92
597.53
3216.45
449.91
3666.37
713.40
4379.77
828.03
5207.79
901.80
6109.59
883.58
6993.18
690.65
7683.83
609.87
8293.69
723.03
9016.73
672.00
9688.72
751.94
10440.66
602.20
11042.86
767.13
11809.99
940.32
12750.31
1150.84
13901.15
586.88
14488.03
1040.63
15528.67
684.07
16212.73
948.63
17161.37
625.17
17786.53
219.73
18006.27
381.27
18387.53
809.97
19197.50
409.87
19607.37
428.07
20035.43
1046.07
21081.50
652.53
21734.03
532.67
22266.70
642.83
22909.53
353.13
23262.67
333.52
23596.18
680.72
24276.90
545.09
24821.99
761.74
25583.73
629.06
26212.79
608.13
26820.93
466.97
27287.89
513.97
27801.86
436.25
28238.11
393.90
28632.01
203.43
28835.44
238.63
29074.08
219.90
29293.98
310.23
29604.21

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 38

Grfico N 07: Anlisis de Doble Masa para las Estaciones Laive, Huancalpi, y Huichicocha.

ANALISIS DE DOBLE MASA


40000.00
35000.00

Precipitacin Acumulada

30000.00
25000.00

Laive
Huancalpi

20000.00

Huichicocha

15000.00

ESTACION PROMEDIO

10000.00
5000.00

2011

2008

2005

2002

1999

1996

1993

1990

1987

1984

1981

1978

1975

1972

1969

1966

1963

0.00

Fuente: Procesado Consultor

Del anlisis realizado a las estaciones hidromtricas antes indicada se puede


observar que los datos de estas estaciones no son muy consistentes por presentar
varios punto de quiebre y periodos no muy extendidos, del grafico se recomienda
trabajar con la estacin de Huichicocha los datos son registrados en la misma
cuenca.
Cuadro N 21: Anlisis de Precipitaciones Medias Mensuales Acumuladas
MES

ESTACION

TOTAL
ANUAL

ENE

FEB

MAR

ABR

MAY

JUN

JUL

AGO

SEP

OCT

NOV

DIC

LAIVE

141.08

147.52

126.05

55.93

21.93

7.14

12.84

24.05

54.09

72.07

72.14

123.20

858.03

HUANCALPI

124.44

132.26

116.01

61.10

28.58

21.56

19.33

30.96

45.88

79.85

81.96

114.53

856.45

HUICHICOCHA

102.05

113.59

112.63

41.48

10.64

5.49

3.50

9.48

16.73

35.55

38.22

65.98

555.34

Promedios

122.52

131.12

118.23

52.84

20.38

11.40

11.89

21.50

38.90

62.49

64.11

101.24

756.61

Fuente: Procesado Consultor

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 39

Grfico N 08: Anlisis de Precipitaciones Medias Mensuales Acumuladas para la Sub


cuenca del rio Canipaco (mm).

Fuente: Procesado Consultor

Del clculo efectuado se concluye que la precipitacin media anual estimada en la


sub cuenca del ro Canipaco es de 756.61 milmetros.

2.3 DISPONIBILIDAD HDRICA EN LA SUB CUENCA DEL RIO CANIPACO

Caudales, para la determinacin de la disponibilidad hdrica en la sub cuenca del rio


Canipaco, para el estudio hdrico de la central hidroelctrica Canipaco, se emplean los
datos histricos registrados por las estaciones linnimetricas Yulapuquio ubicado en la micro
cuenca del rio La Virgen y la estacin linnimetrica Canipaco ubicada en la micro cuenca el
rio Canipaco.

Cuadro N 22: Caractersticas de las Estaciones Linnimetricas para determinar la Escorrenta


Superficial
CODIGO

ESTACIN

LATITUD

LNGITUD

ALTITUD

PERIODO

FUENTE

C273

Yulapuquio

12 22 50

75 18 50

3 580

2003-2012

ELP

C270

Canipaco

12 19 02

75 20 59

3 700

2003-2012

ELP

C261

Quilln

12 23 33

75 08 38

3 190

2003-2012

ELP

Fuente: ELP: Electro Per S.A.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 40

Grfico N 09: Ubicacin de estaciones de aforo con reglas linnimetricas en la sub cuenca
del rio Canipaco operadas por Electro Per S.A.

Fuente: ELP: Electro Per S.A.

Grfico N 10: Fotografas de estaciones de aforo con reglas linnimetricas: Canipaco,


Yulapuquio y Quillon, en la sub cuenca del rio Canipaco operadas por Electro Per S.A.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 41

2.3.1 Disponibilidad Hdrica en la Sub cuenca del rio Canipaco


Las descargas superficiales del ro Canipaco son utilizadas principalmente para la
Actividad pecuaria, en la parte alta de la sub cuenca, agricultura en la cuenca baja,
el uso poblacional y la piscicultura.
Los registros de descargas medios mensuales del ro Canipaco, fueron registrados
por la empresa Electro Per S.A. para el presente estudio se tiene un periodo de 10
aos, desde 2003 2012, los mismos que se presentan en el presente capitulo.
Generalidades
Para el diseo de una central hidroelctrica se debe conocer el caudal mnimo en
poca de estiaje.
Anlisis Hidrolgico
Dado que las zonas de inters del proyecto de aprovechamiento hidroelctrico que
proyecta la Empresa EGECSAC, se ubican en la Sub Cuenca del Ro Canipaco y
en las micro cuencas tributarias a esta como es del ro Canipaco, rio La Virgen y
Acchapata en menor cantidad y rgimen temporal respectivamente, para la
estimacin del caudal mnimo aprovechable se utilizaron los datos del perodo 2003
2012. Registrados en las estaciones Yulapuquio y Canipaco.
Se realiz el anlisis de consistencia de la informacin utilizando criterios fsicos y
mtodos estadsticos realizando los siguientes procesos:
Anlisis visual grfico (comparacin de hidrogramas)
En todos los registros histricos de las estaciones hidrolgicas de la sub cuenca del
ro Canipaco y el rio La Virgen, se han construido los grficos de las descargas
medias mensuales, que se han presentado en los diferentes aos de registro. Estos
grficos han tenido la finalidad de detectar visualmente posibles inconsistencias
(saltos o tendencias) en los perodos analizados. Los mismos que de ser el caso,
en estos periodos inconsistentes deben ser evaluados estadsticamente. En las
figuras se representan grficamente la variacin mensual de las series histricas de
las descargas medias mensuales a travs del tiempo registrado. En estos
histogramas analizados no se ha identificado visualmente alguna inconsistencia,
observndose que existen varios valores altos, as como tambin valores muy
bajos, lo que muestra la gran variabilidad de sus regmenes hdricos.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 42

Se muestra los parmetros estadsticos de cada una de las estaciones


hidromtricas, en donde se presenta las siguientes variables estadsticas
calculadas para la serie anual:

Nmero total de aos con datos de cada estacin,

Nmero de aos completos, es decir, con datos en todos los meses n ,

Valor medio de toda la serie anual m x

xi

n ,
i 1

Coeficiente de variacin de la serie anual CV

Coeficiente de sesgo de la serie anual CS

Anlisis doble masa.

Anlisis estadstico (saltos y tendencias).

De los anlisis efectuados se concluye que las series hidrolgicas

, y
m x

1 n xi m x
*
n i 1
3

(caudal) utilizado en el presente estudio son consistentes y confiables,


por ser informacin validad por Electro Per S. A.

Cuadro N 23: Caudales Naturales Medios Mensuales Estacin Quillon 2003 2012 (m3/s)
AO
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
Q. Media
Q. Max.
Q. Min.

MES
ENERO
19.62
8.10
13.87
11.54
23.07
19.57
6.67
29.96
25.78
13.31
17.15
29.96
2.00

FEBRERO
30.92
17.93
17.18
17.34
16.86
16.82
20.94
23.22
39.11
33.90
23.42
39.11
4.25

MARZO
29.93
10.84
18.69
20.99
25.30
15.09
14.71
25.69
30.08
29.68
22.10
30.08
5.78

ABRIL
21.24
7.18
11.96
18.07
19.78
5.47
9.26
15.96
27.94
27.99
16.49
27.99
4.98

MAYO

JUNIO

10.22
5.50
5.62
4.50
6.54
5.21
3.87
6.06
10.21
11.81
6.95
11.81
2.24

6.56
7.99
4.06
5.76
2.93
9.01
1.66
13.14
5.89
9.85
6.69
13.14
1.51

JULIO
6.38
4.92
5.29
10.39
3.37
7.21
5.33
7.13
4.60
4.82
5.94
10.39
1.28

AGOSTO
3.52
4.05
7.76
7.10
4.80
3.66
6.13
3.67
4.00
3.94
4.86
7.76
1.46

SETIEMBRE

OCTUBRE NOVIEMBRE DICIEMBRE

2.98
2.83
3.51
2.93
5.43
2.10
3.07
2.99
4.15
9.68
3.97
9.68
1.13

4.37
3.43
2.59
2.36
5.87
1.27
2.55
3.01
6.97
8.08
4.05
8.08
1.27

8.66
7.72
1.86
4.65
6.48
1.12
4.91
2.93
10.89
7.83
5.71
10.89
1.12

MEDIA
ANUAL

8.23
16.00
3.60
11.33
4.83
2.35
24.67
8.19
8.91
16.90
10.50
24.67
2.00

Fuente: Electro Per S. A.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

12.72
8.04
8.00
9.75
10.44
7.41
8.65
11.83
14.88
14.82
10.65
18.63
2.42

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 43

Grafico N 11: Hidrograma de Caudales Naturales Medios Multianuales Estacin Quillon, Yulapuqio
y Canipaco 2003-2012 (m3/s)

Fuente: Elaboracin Propia

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 44

Grafico N 12: Anlisis de Caudal Natural Medio Mensuales de las estaciones Quillon, Canipaco y
Yulapuquio

Fuente: Elaboracin Propia

2.3.2 Anlisis de Persistencia de Probabilidad de Ocurrencia de Caudales


El mtodo que se utiliza para tal fin es elaborar con los caudales medios, la Curva
de Duracin (o Persistencia) que nos indica el porcentaje del tiempo durante el cual
los caudales han sido igualados o excedidos.
Con esta informacin se procedi a obtener las diferentes probabilidades de
ocurrencia, al 70%, 75%, 80%, 85%, 90% y 95% utilizando al formula Weibull:

m
*100
1 N

Dnde:
P = Probabilidad de ocurrencia
m = Numero de Orden
N = Nmero total de registro, en este caso 10 aos

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 45

Cuadro N 24: Descargas con Diferentes Probabilidades de Ocurrencia Balance de Masas de las
Estaciones Quillon
Meses
Ene
Feb
Mar
Abr
May
Jun
Jul
Ago
Set
Oct
Nov
Dic
Media

70%
11.93
18.80
17.40
10.80
5.35
4.18
4.84
4.00
2.87
2.62
3.19
5.76
7.65

75%
11.07
17.91
16.50
9.93
5.05
3.81
4.62
3.83
2.70
2.41
2.86
5.16
7.15

Caudal m3/s
80%
85%
10.19
9.25
16.97
15.93
15.55
14.50
9.04
8.10
4.75
4.41
3.44
3.05
4.38
4.13
3.64
3.44
2.51
2.31
2.19
1.96
2.53
2.19
4.57
3.96
6.65
6.10

90%
8.19
14.72
13.29
7.06
4.02
2.62
3.83
3.20
2.08
1.70
1.83
3.31
5.49

95%
6.84
13.09
11.68
5.75
3.51
2.09
3.42
2.88
1.78
1.39
1.40
2.54
4.70
Fuente: Elaboracin Propia

Grafico N 13: Curva de Variacin Estacional de caudales Naturales con Diferentes Probabilidades de
Ocurrencia de las Estaciones Quillon

Fuente: Elaboracin Propia

Para el presente estudio hdrico se realizaran los anlisis los datos pluviomtricos
registrados por la estacin Quillon operada por Electro Per S.A. para tener la
ocurrencia de las magnitudes del fenmeno pluvial, con probabilidades del 70%,
75%, 80%, 85% y 90%.
Para el anlisis de la central Hidroelctrica Chilcay y determinar cul ser el caudal
con probabilidad al 75%.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 46

Anlisis de frecuencia de caudales, a travs de la curva de duracin


La curva de persistencia o permanencia de caudales clasificados nos indicara el
porcentaje de tiempo durante el cual los caudales han sido igualados o excedidos.
Para el presente estudio est definido por los caudales medios mensuales, del
periodo 2003 2012, registrado por Electro Per.
Tomando como datos mensuales del Cuadro N 23, de los 10 aos registrados en
la estacin Quillon, para lo cual se orden en forma descendente, registrndose un
caudal mximo de 39.11 m3/s y un caudal mnimo de 1.12 m3/s. Obteniendo los
siguientes resultados de los clculos de la curva de duracin, el Cuadro N 25, que
es el siguiente:
Cuadro N 25: Resultados de los clculos de la curva de duracin normal Estacin Quillon
N

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26

Q Ordenado
Q
Probabilidad
3
(m /s)
Adimensional
(Q=>%)

39.11
33.90
30.92
30.08
29.96
29.93
29.68
27.99
27.94
25.78
25.69
25.30
24.67
23.22
23.07
21.24
20.99
20.94
19.90
19.78
19.62
19.57
18.69
18.07
17.93
17.34

3.64
3.16
2.88
2.80
2.79
2.79
2.76
2.61
2.60
2.40
2.39
2.36
2.30
2.16
2.15
1.98
1.96
1.95
1.85
1.84
1.83
1.82
1.74
1.68
1.67
1.62

0.83
1.67
2.50
3.33
4.17
5.00
5.83
6.67
7.50
8.33
9.17
10.00
10.83
11.67
12.50
13.33
14.17
15.00
15.83
16.67
17.50
18.33
19.17
20.00
20.83
21.67

60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85

Q Ordenado
Q
Probabilidad
3
(m /s)
Adimensional
(Q=>%)

7.72
7.21
7.18
7.13
7.10
6.97
6.67
6.56
6.54
6.48
6.38
6.13
5.89
5.87
5.76
5.62
5.50
5.47
5.43
5.33
5.29
5.21
4.92
4.91
4.83
4.82

0.72
0.67
0.67
0.66
0.66
0.65
0.62
0.61
0.61
0.60
0.59
0.57
0.55
0.55
0.54
0.52
0.51
0.51
0.51
0.50
0.49
0.49
0.46
0.46
0.45
0.45

50.00
50.83
51.67
52.50
53.33
54.17
55.00
55.83
56.67
57.50
58.33
59.17
60.00
60.83
61.67
62.50
63.33
64.17
65.00
65.83
66.67
67.50
68.33
69.17
70.00
70.83

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59

17.18
16.85
16.82
16.00
15.96
15.09
14.71
13.87
13.31
13.15
13.14
11.96
11.81
11.54
11.33
10.89
10.84
10.39
10.22
10.21
9.85
9.68
9.26
9.01
8.91
8.66
8.23
8.19
8.10
8.08
7.99
7.83
7.76

1.60
1.57
1.57
1.49
1.49
1.41
1.37
1.29
1.24
1.22
1.22
1.11
1.10
1.07
1.06
1.01
1.01
0.97
0.95
0.95
0.92
0.90
0.86
0.84
0.83
0.81
0.77
0.76
0.75
0.75
0.74
0.73
0.72

22.50
23.33
24.17
25.00
25.83
26.67
27.50
28.33
29.17
30.00
30.83
31.67
32.50
33.33
34.17
35.00
35.83
36.67
37.50
38.33
39.17
40.00
40.83
41.67
42.50
43.33
44.17
45.00
45.83
46.67
47.50
48.33
49.17

86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118

Pgina 47
4.80
4.65
4.60
4.50
4.37
4.15
4.06
4.05
4.00
3.94
3.87
3.67
3.66
3.60
3.52
3.51
3.43
3.37
3.07
3.01
2.99
2.98
2.93
2.83
2.59
2.55
2.36
2.35
2.10
1.86
1.66
1.27
1.12

0.45
0.43
0.43
0.42
0.41
0.39
0.38
0.38
0.37
0.37
0.36
0.34
0.34
0.34
0.33
0.33
0.32
0.31
0.29
0.28
0.28
0.28
0.27
0.26
0.24
0.24
0.22
0.22
0.20
0.17
0.15
0.12
0.10

71.67
72.50
73.33
74.17
75.00
75.83
76.67
77.50
78.33
79.17
80.00
80.83
81.67
82.50
83.33
84.17
85.00
85.83
86.67
87.50
88.33
89.17
91.67
92.50
93.33
94.17
95.00
95.83
96.67
97.50
98.33
99.17
100.00

Fuente: Elaboracin Propia Procesada con el Programa Hidroesta

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 48

Caudal m /s

Grafico N 14: Curva de duracin normal de la estacin Quillon

Porcentaje %

Caudal Estimado
El caudal de diseo: Q = 25.30 m3/s, tiene una probabilidad del 10 %; Q = 20.94
m3/s, tiene una probabilidad del 15%; Q = 18.07 m3/s, tiene una probabilidad del
20%; Q = 13.15 m3/s, tiene una probabilidad del 30 %; Q = 8.19 m3/s, tiene una
probabilidad del 45%; Q = 7.72 m3/s, tiene una probabilidad del 50 %; Q = 4.37
m3/s, tiene una probabilidad del 75 %; Q = 2.98 m3/s, tiene una probabilidad del 90
%; de ser igualado o excedido, aseguramos que se tendr un caudal de 2.36 m3/s a
un 95% y 1.12 m3/s a un 100%.

2.3.3 Anlisis de Mximas Avenidas


El anlisis de caudales mximos en la sub cuenca del rio Canipaco permitir
determinar los caudales mximos instantneos producidos en diferentes escenarios
eventos. Para el diseo de las estructuras hidrulicas de la central hidroelctrica se
debe conocer el mximo caudal de avenidas.
El mtodo estadstico utilizado para estimar el mximo caudal de avenidas que se
presentara para un determinado perodo de retorno es el conocido Mtodo de
GUMBEL (que se contrasta con el Mtodo de NASH), ambos mtodos se basan en
considerar que el caudal mximo anual, es una variable aleatoria que tiene una
cierta distribucin.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 49

Cuadro N 26: Caudales Mximos Registrados por la Estacin Pluviomtrica Quillon, para la
Captacin de la Central Hidroelctrica Chilcay en m3/s
AO

ENERO

2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
Q. Max.

31.92
15.07
30.85
32.93
32.73
41.61
10.55
46.95
51.41
31.10
51.41

FEBRERO
51.33
57.17
34.32
37.42
42.73
41.98
37.58
46.43
57.03
64.99
64.99

MARZO
56.77
25.61
29.23
40.18
35.97
24.98
33.87
38.90
43.38
46.84
56.77

ABRIL
37.31
12.91
23.46
30.43
47.55
8.00
16.75
40.14
51.83
45.81
51.83

MAYO
13.06
7.24
8.95
6.42
11.32
10.54
6.62
15.34
14.76
21.77
21.77

MES
JUNIO
10.47
8.77
7.42
8.45
3.68
11.51
3.51
16.02
6.62
17.30
17.30

JULIO
AGOSTO SEPTIEMBRE OCTUBRE NOVIEMBRE DICIEMBRE
10.14
4.21
3.43
8.48
9.70
12.99
7.59
7.37
5.13
6.53
17.74
33.90
8.48
9.66
5.41
3.79
2.25
7.71
13.75
8.47
4.08
3.96
10.40
31.69
4.17
6.35
6.17
12.60
11.95
9.63
12.03
5.59
2.60
2.60
2.70
9.95
11.05
7.84
4.29
5.80
20.89
42.91
11.00
8.26
3.22
3.73
3.74
29.62
5.59
4.69
5.13
15.34
14.53
15.52
5.22
4.34
12.87
13.15
13.61
49.08
13.75
9.66
12.87
15.34
20.89
49.08

Fuente: Electro Per S. A. Estacin Quillon

Mtodo de GUMBEL
Utilizando el mtodo estadstico de GUMBEL se determina el caudal de mxima
avenida en la sub cuenca del ro Canipaco para un tiempo de retorno de 50 aos

Qmx

NQ 2 m

i 1

N 1

Se utiliz un tiempo de retorno de 50 aos por los siguientes factores:

Para no sobredimensionar las estructuras hidrulicas (obras civiles).

Tiempo de vida til de una estructura hidrulica es de 50 aos.

Resultados de los clculos:

Nmero de aos disponibles:

10

Promedio Q:

48.985

Desviacin estndar Q:

Parmetro YN:

0.4925

Parmetro SN:

0.9535

Q mximo:

83.4909

Delta Q:

11.5035

Intervalo variacin Q:

9.622

71 .99 - 94 .99

El caudal de diseo por Gumbel, para un perodo de retorno de 50 aos es:


94.9944 m3/s

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

Q Max
56.77
57.17
34.32
40.18
47.55
41.98
42.91
46.95
57.03
64.99
64.99

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 50

Mtodo de NASH
Utilizando el mtodo estadstico de NASH se determina el caudal de mxima
avenida en la sub cuenca del ro Canipaco para un tiempo de retorno de 50 aos

Qmx a b log

T
T 1

Se utiliz un tiempo de retorno de 50 aos por los siguientes factores:

Para no sobredimensionar las estructuras hidrulicas (obras civiles).

Tiempo de vida til de una estructura hidrulica es de 50 aos.

Resultados de los clculos:

Nmero de aos disponibles:

10

Qm:

48.985

Xm:

-0.5773

a:

36.5474

b:

-21.5452

Q mximo:

80.8616

Delta Q:

Intervalo variacin Q:

8.0722
72.79 - 88 .93

El caudal de diseo con el mtodo estadstico propuesto por Nash, para un perodo
de retorno de 50 aos es: 88.9338 m3/s
El caudal Medio de diseo con el mtodo estadstico propuesto por Gumbel y Nash,
para un perodo de retorno de 50 aos es: 91.9641 m3/s

2.3.4 Disponibilidad de Reservorios


La configuracin actual de los reservorios controlan 56 Mm3. Bajo las estructuras de
control construidas por Minas de Cercapuquio S.A. y posteriormente transferida a
Centraminas S.A., el control fue un poco ms del 15 por ciento y se informa que el
almacenamiento disponible ha sido de 39 Mm3 o 69.6% del total almacenamiento
actual. Las estructuras de control de Electroper en Balsacocha y Nahuincocha son
nuevas mientras que las de Coyllorcocha, Huichicocha y Yurajcocha utilizan todo o

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 51

parte de la estructura original construida por la compaa minera. Las operaciones


bajo ambos grupos de direccin son inexistentes o poco coherentes con respecto a
la naturaleza del contrato de derecho de uso de agua firmado.
En el ltimo caso tenemos registros de flujos bajos (menos que el mnimo diseado
en el contrato de Electro Per) durante la temporada seca junto con otros para los
reservorios que indican que estos estuvieron esencialmente llenos y que no ocurri
ninguna descarga. La razn ms probable para esta forma de operacin es que, en
ausencia de alguna necesidad de cumplir con el contrato de Centraminas S.A. (no
se llev a cabo ningn desarrollo despus de la firma del contrato), Electro Per ha
operado el sistema con el mejor beneficio lgico para sus instalaciones aguas abajo
del Ro Mantaro. Como se puede apreciar en los diagrama anuales (1998 a 2006).
Sobre la base de las descargas en la temporada seca de 4.25 a 4.5 m 3/s y
suponiendo que el flujo base mnimo en el ro sobre Cercapuquio en la temporada
seca es del orden de 0.75 a 0.5 m 3/s y que el volumen total del reservorio
disponible es de 56 Mm3, los perodos de descarga de (56/2.63 Mm 3 / mes x 4.25 a
4.5 m3/s) = 5.01 a 4.73 meses deben ser manejable.
Basados en los dos perodos de registro "instantneo" el flujo promedio anual del
ro es 5,1 cbicos m 3/s segn el escaso conjunto de datos tomados en 42 aos y,
6,76 de m3/s segn el mejor pero ms pequeo conjunto de datos entre 1998 a
2006. El suministro de un flujo mnimo anual de 5,75 m/s sera un valor real.
La revisin de todos los registros de flujo tambin indican que las lecturas
instantneas de eventos de flujo extremo mayores de 40 m3/s han ocurrido en 3
ocasiones durante los ltimos 42 aos, dos en el rango de 40 a 50 m 3/s en los
ltimos 9 aos. Basados en estas ocurrencias un proyecto de flujo de tormenta de
60 m3/s ha sido considerado para todo o casi todas las estructuras del ro en el
desarrollo, a lo largo de los accesos ms bajos del Ro Aimaraes y en el acceso
superior del Ro La Virgen.

2.4 USOS Y DEMANDAS DE AGUA


2.4.1 Consumo Actual del agua en el mbito de la sub Cuenca del Rio Canipaco
En la actualidad en la sub cuenca del rio Canipaco existen varios usos de las aguas
como son el uso energtico que viene siendo otorgado el derecho de usos a Electro
Per S.A., en la regulacin de las lagunas en la cabecera de cuenca, asimismo

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 52

existen dos infraestructuras importantes para el uso agropecuario que derivan las
aguas del rio Canipaco a travs de la toma y canal de riego de nombre Plan MERIS
Canipaco, y la captacin y canal de riego de nombre Cuatrocientos, del rio La
Virgen, con el cual irrigan pastos de los mdulos lecheros de Chongos alto y
Huasicancha, los que no se encuentran formalizados en su dotacin de volumen de
agua.
El uso poblacin para las principales poblaciones esta dado en las captaciones en
manantiales prximos a los centros poblados, donde captan con captaciones de
tipo ladera y son derivados por tuberas enterradas y distribuidas a la poblacin.
En el tramo del ro Canipaco, donde se desviaran las aguas para la central
hidroelctrica Chilcay, No Existe uso de terceros, como es el de uso poblacional,
pisccola y agropecuario, por encontrarse en su tramo estrecho de la cuenca media
del rio Canipaco. Punto de captacin en coordenadas UTM: 479024 (E); 8635606
(N), Punto de Devolucin Coordenada UTM: 485242 (E), 8631393 (N).
Cuadro N 27: Caudales de uso no agrario en la sub cuenca del rio Canipaco para el ao 2012
Datos del Punto de Captacin

Datos del Usuario


N

Nombre del Usuario / Razn Social

1.-ENEREGETICO
1 ELECTROCENTRO S.A.
2.-MINERO
1

Nombre Unidad Operativa

C.H. El Machu

COMPAA MINERA LOS CHUNCHOS SAC. Agua fines mineros

2 EMPRESA MINERA LOS QUENUALES SA


3.-POBLACIONAL
MUNICIPALIDAD DISTRITAL
1
CARHUACALLANGA

Fuente

Nombre

Ro

La Virgen

Laguna

La Esperanza

Proyecto El Gorila

Quebrada varios

Carhuacallanga

Manantial Suito

JASS - DE ANDABAMBA

Agua Potable C.C. AndabambaManantial Tantalpuquio 1 Y 2


Chacapampa

MUNICIPALIDAD DISTRITAL DE
CARHUACALLANGA

Carhuacallanga

Manantial Capchapuquio

Otorgamiento del Agua Punto Captacion

Ubicacin Politica

Caudal

Volumen

Lt/seg.

M3

Este

1700

8953200

468791 8636906 Junin Huancayo Huasicancha

Coord. Punto Captac.


Norte

Dpto.

Provincia

Distrito

2.5

78840

448653 8604852 Junin Huancayo Chongos Alto

18.77

444

451678 8614585 Junin Huancayo Chongos Alto

0.5

15768

0.38

11983.68

0.4

12614.4

Junin Huancayo Carhuacallanga


474904 8638120 Junin Huancayo Chacapampa
477105 8634140 Junin Huancayo Carhuacallanga

Fuente: Administracin local de agua Mantaro

2.4.2 Demanda Futura


La demanda futura para el proyecto de la central hidroelctrica Chilcay se describen
el siguiente cuadro considerando el caudal al 75% de persistencia en m3/s. as
mismo respetando el caudal ecolgico a un caudal de persistencia del 75%, del rio
Canipaco donde aseguramos la conservacin de la biodiversidad en el trnsito de
desvi de aguas del rio.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 53

Cuadro N 28: Demanda mensualizada futura de la central hidroelctrica chilcay en m3/s y MMC
DEMANDA HIDRICA C.
H. COLCA
Caudal m3/s
Volumen MMC

ENERO
FEBRERO
9.50
14.00
25.44
33.87

MARZO
14.00
37.50

ABRIL
8.50
22.03

MES
JUNIO
JULIO
AGOSTO SEPTIEMBRE OCTUBRE NOVIEMBRE DICIEMBRE
3.00
3.50
3.00
2.00
2.00
2.00
4.00
7.78
9.37
8.04
5.18
5.36
5.18
10.71

MAYO
4.00
10.71

TOTAL
ANUAL
181.18

La demanda futura se determin en funcin a la disponibilidad hdrica del rio


Canipaco en el punto de inters, respetando el caudal ecolgico que se demuestra
en el siguiente cuadro.

Caudal Ecolgico
Determinacin del caudal ecolgico determinado segn Memorndum Mltiple N
018-2012-ANA-DCPRH-ERH-SUP

Cuadro N 29: Caudal Ecolgico Determinado a una Persistencia de 75% del rio Canipaco
AO
EPOCA
Q. Ecolog - Media
Q. Ecolog. 75%

MES
ENERO

FEBRERO
MARZO
AVENIDA (10% Q. Med.)
1.71
2.34
2.21
1.11
1.79
1.65

ABRIL
1.65
0.99

MAYO
1.04
0.76

JUNIO

JULIO
AGOSTO SETIEMBRE OCTUBRE NOVIEMBRE DICIEMBRE
ESTIAJE (15% Q. Med.)
AVENIDA (10% Q. Med.)
1.00
0.89
0.73
0.60
0.61
0.57
1.05
0.57
0.69
0.57
0.41
0.36
0.29
0.52

MEDIA
ANUAL

Grafico N 15: Curva de Caudal ecolgico con la medias de las avenidas del ro Canipaco

El caudal ecolgico del ro Canipaco segn las directivas de la ANA, con caudales
medios, el mximo caudal ecolgico es de 2.34 m3/s es para el mes de Febrero, y el
caudal ecolgico mnimo con 0.57 m3/s para el mes de Noviembre en meses de
estiaje. En condiciones naturales sin que en el rio se est haciendo uso alguno de
sus aguas.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

1.20
0.81

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 54

Grafico N 16: Esquema hidrulico central hidroelctrica Chilcay


ESQUEMA HIDRAULICO CHILCAY
21.0
RO
SECO

20.5

QUEBRADA ACCHAPATA

DIST. CHACAPAMPA

LAGUNA
ITICOCHA

C
A
N
I
P
A
C
O

20.0
19.5
19.0
18.5
CERRO
SAYHUAPATA

18.0
17.5
17.0
16.5
16.0
15.5

DIST. COLCA

15.0
14.5
14.0

CH -01
E:
N:

13.5

CHILCAY
Captacin
479024
8635606

13.0
12.5
12.0
11.5
C.P. CHILCAY

DIST. CARHUACALLANGA

11.0
10.5
10.0

DIST. CANASKA

FUNDO OSOMA

8676.69 m + ???

DIST. INCHU

9.5
C.P. SAN MIGUEL

9.0
C.P. CERRO CHICO

8.5
8.0
7.5

C.P. ANTAPUQUIO

7.0
6.5
6.0
4.5
4.0

RO VILCA

C.P. TINCO

3.5
3.0

CH - 02
CHILCAY
Devolucin
E: 485242
N: 8631393

2.5
RO
QUILLON

2.0
1.5
1.0

RIO MANTARO
Cada cuadrado 500 metros de longitud

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 55

2.5 BALANCE HDRICO

2.5.1 Disponibilidad Hdrica en la Unidad Hidrogrfica


Oferta Hdrica Superficial Neta de la Sub Cuenca del ro Canipaco
Como se ha indicado, la oferta hdrica asignable en la cuenca del ro Canipaco, es
la disponibilidad al 75% de los caudales mensuales calculados para la cuenca del
ro Canipaco, que es equivalente a un volumen total anual de 167.82 MMC/ao.
Cuadro N 30: Oferta Hdrica Superficial de la sub cuenca del ro Canipaco (MMC)
DESCRIPCION
Q Media
70 % Persistencia
75% Persistencia
95% Persistencia

ENERO
FEBRERO
45.93
56.66
31.95
45.48
29.65
43.33
18.32
31.67

MARZO
59.19
46.60
44.19
31.28

ABRIL
42.73
27.99
25.74
14.90

MAYO
18.63
14.33
13.53
9.40

VOLUMEN (MMC)
JUNIO
JULIO
AGOSTO SEPTIEMBRE OCTUBRE NOVIEMBRE DICIEMBRE
17.33
15.92
13.03
10.28
10.85
14.79
28.13
10.83
12.96
10.71
7.44
7.02
8.27
15.43
9.88
12.37
10.26
7.00
6.45
7.41
13.82
5.42
9.16
7.71
4.61
3.72
3.63
6.80

TOTAL
ANUAL
333.46
239.03
223.63
146.64

Fuente: Elaboracin Propia

2.5.2 Demanda Hdrica Total


En el presente capitulo se calcul la demanda hdrica energtica para el ro
Canipaco, en trminos de Requerimiento Hdrico Bruto (RB), a partir del
Requerimiento Hdrico Neto (RN), formulado para cada una de las turbinas de
generacin elctrica.
Tambin se identific la demanda de agua con fines agrcolas, en la sub cuenca del
ro Canipaco, recordando que el uso de las aguas ser con fines No Consuntivo
(Energtico), el mismo que no afectara la cantidad y calidad del agua al ser
devuelto al cauce del rio.
Demanda Hdrica Energtica de la sub Cuenca del ro Canipaco
La demanda hdrica energtica de la sub cuenca del ro Canipaco es de 181.18
MMC/ao. En el Cuadro N 31, se muestra el resumen mensual de la demanda
hdrica energtica.
Cuadro N 31: Demanda Hdrica Energtica disponible Superficial de la Sub cuenca del ro
Canipaco
DEMANDA HIDRICA C.
H. COLCA
Caudal m3/s
Volumen MMC

ENERO
FEBRERO
9.50
14.00
25.44
33.87

MARZO
14.00
37.50

ABRIL
8.50
22.03

MAYO
4.00
10.71

MES
JUNIO
JULIO
AGOSTO SEPTIEMBRE OCTUBRE NOVIEMBRE DICIEMBRE
3.00
3.50
3.00
2.00
2.00
2.00
4.00
7.78
9.37
8.04
5.18
5.36
5.18
10.71

TOTAL
ANUAL
181.18

Fuente: Elaboracin Propia

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 56

Requerimiento Hdrico Neto, RN


Para el clculo del RN se ha determinado en funcin al diseo de la estructura de
captacin y conduccin desde la bocatoma a la cmara de carga segn los detalles
tcnicos en el diseo de estructura.
Grafico N 17: Calculo de caudal requerido para operacin al 100 %, central hidroelctrica
Chilcay

En el diseo de la estructura de captacin y conduccin es de 14 m3/s. en su


mxima capacidad de conduccin, convirtindose en la demanda bruta (DB).

La coordenada UTM de la Bocatoma es la siguiente;


479024 (E) 8635606 (N)

La coordenada UTM de la Casa de mquinas / descarga siguiente;


485242 (E) 8631393 (N)

2.5.3 Balance Hdrico


Balance Hdrico de Asignacin de Agua Superficial en la Sub cuenca del ro
Canipaco
Se efectu el Balance Hdrico de asignacin para la sub cuenca del ro Canipaco,
entre la oferta hdrica y la demanda hdrica agrcola energtica, con los valores
totales anuales de 223.63 y 181.18 MMC, establecindose los porcentajes de oferta

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 57

asignable y el dficit de asignacin, en el Cuadro N 32, se presenta el resumen de


la asignacin en la cuenca del ro Canipaco.
Cuadro N 32: Balance Hdrico de Asignacin de Agua Superficial en la Sub cuenca del ro
Canipaco
DESCRIPCION
Oferta Hidrica
Demanda Hidrica
Balance de Asignacion
Ofertas Asignadas
% Dda. Asignada

ENERO
FEBRERO
MARZO
29.65
43.33
44.19
25.44
33.87
37.50
25.44
100.00

33.87
100.00

ABRIL
25.74
22.03

MAYO
13.53
10.71

22.03
100.00

10.71
100.00

37.50
100.00

VOLUMEN (MMC)
JUNIO
JULIO
AGOSTO SEPTIEMBRE OCTUBRE NOVIEMBRE DICIEMBRE
9.88
12.37
10.26
7.00
6.45
7.41
13.82
7.78
9.37
8.04
5.18
5.36
5.18
10.71
7.78
100.00

9.37
100.00

8.04
100.00

5.18
100.00

TOTAL
ANUAL
223.63
181.18

5.36
5.18
10.71
100.00
100.00
100.00
Fuente: Elaboracin Propia

181.18
100.00

Cuadro N 33: Resumen Balance Hdrico de Asignacin de Agua Superficial en la Sub cuenca del
ro Canipaco
MES
DESCRIPCION
Oferta Hidrica 75%
Cuadal Ecologico
Demanda Proyecto
Disponibilidad para el Proyecto

ENERO
11.07
1.11
9.50
9.96

FEBRERO
17.91
1.79
14.00
16.12

MARZO
16.50
1.65
14.00
14.85

ABRIL

MAYO

9.93
0.99
8.50
8.94

5.05
0.76
4.00
4.29

DESCRIPCION
Oferta Hidrica 75%
Cuadal Ecologico
Demanda Proyecto
Disponibilidad para el Proyecto

JUNIO

JULIO

En Caudal (m3/s)
3.81
4.62
0.57
0.69
3.00
3.50
3.24
3.93

AGOSTO

SEPTIEMBRE OCTUBRE NOVIEMBRE DICIEMBRE

3.83
0.57
3.00
3.26

2.70
0.41
2.00
2.30

2.41
0.36
2.00
2.05

2.86
0.29
2.00
2.57

10.26
1.54
8.04
8.72

7.00
1.05
5.18
5.95

6.45
0.97
5.36
5.49

7.41
0.74
5.18
6.67

En Volumen (MMC)
29.65
2.96
25.44
26.68

43.33
4.33
33.87
39.00

44.19
4.42
37.50
39.77

25.74
2.57
22.03
23.16

13.53
2.03
10.71
11.50

9.88
1.48
7.78
8.39

12.37
1.86
9.37
10.52

PROMEDIO
7.15
0.81
5.79
6.35
TOTAL
ANUAL
13.82
223.63
1.38
25.34
10.71
181.18
12.44
198.29
5.16
0.52
4.00
4.64

Fuente: Elaboracin Propia

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 58

CAPTULO III: INGENIERA DEL PROYECTO HIDRULICO

3.1

Planteamiento Hidrulico
El proyecto: Central Hidroelctrica de Chilcay, ha sido concebido para generar 19.21
MGW de Potencia.
Es importante hacer notar que el sistema de transmisin asociado al proyecto ha sido
configurado como resultado de un planeamiento previo que permiti establecer que la C.
H. se implementara y atendera principalmente al sistema de transmisin existente;
Sistema Elctrico Interconectado Nacional (SEIN).
El proyecto comprende principalmente, los diseos de las obras Civil-hidrulicas y del
equipamiento electromecnico, estimacin de metrados, anlisis de precios unitarios de
las partidas principales, as como el costo de inversin, cronograma de construccin.

3.2

Obras Hidrulicas
Los alcances de las obras Hidrulicas del proyecto abarcan los aspectos de la
construccin de la Central Hidroelctrica Chilcay.
Comprende: Bocatoma, Desarenador, Sistema de conduccin, canal en conducto
cubierto, tneles, Cmara de Carga, Vertedero de las demasas y Tubera de conduccin
del Alivio-Limpia, Caseta de vlvulas, Tubera de Presin, Casa de Mquinas, Canal de
Descarga o Restitucin y Obras de arte de cruce de quebradas (Puente-Canoa).
Carreteras de Acceso internas a la obra.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY
3.3

Pgina 59

Dimensionamiento de las Obras de Captacin, Conduccin y Entrega a la Fuente


Los resultados de las dimensiones obtenidos de las obras hidrulicas, se han generado
como resultado de los clculos obtenidos del estudio realizado de la sub cuenca del
Canipaco.
La Central hidroelctrica de Chilcay operara con las aguas del Rio Canipaco
Desde la Bocatoma se derivar un caudal de 15.4 m3/seg, hasta el Desarenador,
habiendo considerado un porcentaje del 10% de este caudal para limpieza de partculas
slidas y como caudal ecolgico. Del Desarenador contina el flujo de 14 m 3/s por el
Sistema de Conduccin hasta la Cmara de Carga. Para el sistema de conduccin se
tiene previsto la construccin de un canal en Conducto Cerrado en concreto armado de
seccin b=3.20 m y H= 2.50 en una longitud de 10,961.99 ml. el que entrega el caudal a
la Cmara de Carga a una cota de pelo de agua 3,154 msnm. Altura o carga hidrulica de
154 m.
Caudal de Diseo
El mejor aprovechamiento de la energa potencial dispensada por las aguas del ro
Canipaco corresponde a considerar un caudal disponible en la cuenca por un periodo
aproximado de tres meses (87 das segn historia), de lo cual tomamos como caudal de
diseo de la Central Hidroelctrica 14.00 m 3/s. Con este caudal y el salto neto de 147.57
m se obtiene una potencia de 19.21 KW en bornes de los generadores, considerando una
eficiencia de 97% en las turbinas hidrulicas y 98% en los generadores.
El caudal normal derivable es de 14.0 m 3/s que se descompone de la siguiente manera:
Caudal que requieren las turbinas: 3 x 4.666 = 14.0 m 3/s
3.3.1 Bocatoma
Parmetros Bsicos de Diseo
La avenida mxima adoptada para el diseo del barraje es de 37.40 m3/s, caudal
correspondiente a un periodo de retorno de 10 aos.
El caudal mximo de diseo para derivacin, se ha definido en 15.40 m 3/s, para
ser captado por rebose a travs de dos ventanas, caudal total que incluye el
caudal de limpia para realizar la operacin de purga en el desarenador (10% del
caudal mximo a turbinar)

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 60

Para atenuar el ingreso de slidos de fondo y en suspensin a travs de las


ventanas de captacin, se ha proyectado un canal de limpia gruesa frente a las
ventanas de captacin.
El coeficiente de rugosidad de Manning (n) en el cauce natural se ha asumido
igual a 0,045.
Se precisa que la estructura de bocatoma se proyecta de concreto armado
reforzado con elementos de enrocado, privilegiando el aspecto tcnico frente a
otras soluciones econmicas, a fin de garantizar la estabilidad de la estructura y la
operacin del proyecto frente a ocurrencias de dinmica fluvial extraordinarias.
Seleccin del tipo de captacin
La captacin est proyectada, para derivar en forma lateral y por la margen
derecha un caudal de 15.40 m 3/s de las aguas del ro Canipaco.
El emplazamiento de la bocatoma proyectada se ha efectuado en un tramo recto
del curso natural del cauce del ro como se puede observar en los planos.
De acuerdo a las caractersticas morfolgicas del ro se ha estimado una
profundidad de socavacin general, para la descarga mxima de diseo, de 1.67
m, por lo que la profundidad mnima de cimentacin se recomend en 2.50 m.
Aguas abajo del barraje fijo, se ubica la poza disipadora de energa.
Se han ubicado muros laterales de encauzamiento en ambas mrgenes del cauce
y en la margen derecha una ventana de captacin con su respectiva rejilla
denominada tambin ventana de toma.
La toma consta de dos ventanas de captacin de 3.50 m de base por 2.00 m de
altura, con un alfizar de 1.10 m, protegida con una rejilla de 3.50 x 2.00 m, con
platinas de acero de 0,01 m x 0,15 m con espaciamiento libre entre platinas de
0,03 m.
3.3.2 Desarenador:
Parmetros bsicos de diseo
El desarenador est conformado por dos naves y cada nave se considera la mitad
del caudal de diseo y periodos de mantenimiento o limpia en avenidas estas
pueden operar independientemente para las condiciones de diseo indicadas

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 61

Factores bsicos de diseo y dimensionamiento


El desarenador se ha diseado para un caudal de 15.40 m 3/s que es el que llevar
la conduccin antes del desarenador y luego el caudal saldr 14.00 m 3/s.
El desarenador permitir sedimentar las partculas iguales o mayores de 0,5 mm
de dimetro, para lo cual se requiere una velocidad de flujo de 0,307 m/s dentro
del desarenador.
Los factores bsicos considerados en el diseo son el caudal y el dimetro
mximo de partculas a retener. Es importante tambin el control de la velocidad
de flujo y velocidad de cada del material slido.
Por la conduccin a la central hidroelctrica Chilcay puede conducirse 14.00m 3/s,
en la poca lluviosa debe suministrarse este caudal para que la central trabaje a
su mxima capacidad, en la poca lluviosa tambin el agua trae la mayor cantidad
de sedimentos.

Por ello se ha previsto dos (02) naves que pueden operar

independientemente con la finalidad de efectuar adecuadamente las operaciones


de mantenimiento y/o limpieza correspondientes.
Para cumplir este propsito se ha proyectado instalar compuertas y ataguas a la
entrada de cada nave para controlar el ingreso de agua a cada una de las naves.
Asimismo, cada nave tiene una compuerta de purga.
Se ha previsto proporcionar una pendiente longitudinal de 3,0% al desarenador,
para facilitar la evacuacin de sedimentos que sern retenidos.
Aspectos constructivos y materiales de construccin
Al igual que la bocatoma Chilcay no se tendr problemas de disponibilidad de
materiales para la construccin. Los materiales para los agregados de concreto
provienen de las mismas canteras que para la bocatoma.

3.3.3 Sistema de Conduccin


Canal de Conduccin
El canal se inicia al final de la transicin del desarenador, con una seccin
rectangular de 3.20 m de base por 2.50 m. de altura y pendiente de 0.1% para
transportar el caudal 14.00 m 3/s. El canal de enlace de concreto armado fc = 210
kg/cm2 ser cerrado en el total de su longitud; se inicia en la progresivas 0+000

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 62

con una cota de rasante de 3,154 y termina en el Km. 10+765.18. Siendo sus
caractersticas geomtricas e hidrulicas las siguientes:
Q=14.00m3/seg.
b=3.20m.
y=2.07m.
n=0.014
s=0.001

V=2.11m/seg.
A=6.63m2
P=7.35 m
R=0.9031

3.3.4 Cmara de Carga


Parmetros bsicos de diseo
La cmara de carga se ha diseado para un caudal nominal de llegada de la
conduccin 14.00 m3/s, las dimensiones de la estructura adems de funcionar
como desarenador terminal para sedimentar cualquier material mayor de 0,5 mm,
almacenar un volumen de 4,928.10 m3.
Descripcin de la estructura
La estructura est conformada de las siguientes partes:

En el sector: Llegada del sistema de conduccin Chilcay ubicada en la


progresiva 6+390.716 km.

Un aliviadero lateral de demasas de 12.00 m. de longitud permite la


evacuacin de hasta 14.00 m 3/s.

Una transicin de ingreso de 10.6 m de longitud, que permite el ingreso de


agua desde el canal de conduccin de 3.20 m de ancho hacia la nave de 7.50
m.

El desarenador terminal conformado por una nave de 7.50 m. de ancho, una


longitud de 57.00 m. y 10.20 m. de altura. La superficie de fondo tiene una
pendiente de 3.00 % y una canaleta de 1.30 m. de ancho y altura variable de
000 a 1.30 m, a lo largo del desarenador a fin de facilitar la evacuacin de los
sedimentos depositados. Transversalmente es de seccin compuesta, con
taludes 1:1 en los planos laterales.

La cmara de presin propiamente dicha:


Estar diseada para evitar la formacin de remolinos o depresiones que
produzcan la entrada de aire a la tubera, tendr una longitud de 5.20 x 5.20.m de

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 63

ancho y una altura de agua de 6.60 m sobre la parte superior de la bocal de la


tubera de presin.
Para evitar la entrada de material flotante se ha previsto una rejilla metlica de
4.28 x 5.20 m, con platinas de 8 x 100 mm, espaciado centro a centro 40 mm, y
montada con un ngulo de 72 respecto con la horizontal. La rejilla tendr el
propsito de evitar el ingreso de slidos flotantes que pudiera arrastrar el agua.
Estos dos ltimos elementos adems de la compuerta de fondo de la cmara de
carga estn provistos de sus respectivas losas de operacin las que cuentan con
barandas de fg para proteccin de las personas.
Para una mejor operacin en estas losas se contar con escaleras gato en los
lugares que se especifican en los planos y en los donde la supervisin estime
necesario.
Aspectos constructivos
Los muros, losas de piso, losa de maniobra de compuerta y canal vertedor sern
de concreto armado fc = 20 Mpa, acero de refuerzo fy = 4 200 kg/cm2.
La construccin se har conforme a los Planos

3.3.5 Equipamiento Hidromecnico


Compuertas de Limpia de Cmara de Carga
La compuerta de limpia es de tipo plana de 1.20 m x 1.200 m, la hoja de la
compuerta debe tener un espesor mnimo de 5/16. El pedestal de maniobra
estar colocado sobre el piso del canal de limpia, tal como se muestra en los
respectivos planos.
El sistema de izaje es similar al modelo Armco CPE-12 con vstago de elevacin
de 2 de .

Rejilla de Ingreso a la Cmara de Carga

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 64

Rejilla fina de ingreso a la cmara de carga, de 4.28 x 5.20 m, con platinas de 8 x


100 mm, espaciado centro a centro 40 mm, y montada con un ngulo de 72
respecto con la horizontal.

3.3.6 Tubera de Presin


La tubera forzada ha sido diseada considerando los siguientes aspectos:
Ejecutado los clculos respectivos se ha determinado que el nmero ms
conveniente de tuberas es de una unidad, la que se bifurcar en cuatro a la
llegada a la Casa de Mquinas mediante un pantaln, uno para cada turbina,
previamente se bifurcar en tres tuberas, que en la primera etapa servir para
tres turbinas, dejndose previsto uno adicional como se detalla en el plano.
El caudal de diseo de la tubera es de 14.00 m 3/seg.
La longitud de la tubera forzada es de 312.30 m desde la salida de la Cmara de
Carga hasta la bifurcacin del pantaln de distribucin, este ltimo tiene
longitudes respectivas de 16.49 m y un dimetro de 1.08 m. El diseo de la
tubera forzada se ilustra con los planos.
El total de la tubera de presin corresponde a tubera superficial.
El dimetro econmico para la altura de la cada, el caudal y los costos ha sido
determinado en 2.00 m. y un espesor variable de acuerdo a la altura, desde en
el inicio aguas arriba hasta 5/8 en el final de la tubera.
La tubera forzada ser construida de plancha de acero estructural que cumpla
con las normas de Siderper PG-E-24 equivalente a las normas ASTM-A36. La
fabricacin se ceir a lo indicado en los planos del proyecto, especificaciones
tcnicas y normas al respecto.
La unin de los tubos ser mediante soldadura elctrica y la unin con la vlvula
de admisin de cada turbina ser mediante bridas.
Se ha previsto una junta de dilatacin inmediatamente despus de cada bloque de
anclaje para amortiguar los esfuerzos por variaciones de la temperatura.
Se ha escogido como junta de dilatacin las uniones dresser tipo 38 del AWWA
que tienen una longitud de 13 1/8.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 65

3.3.7 Sistema de Alivio de las Demasas


El canal de alivio o demasa de la cmara de carga consta de un primer tramo
paralelo y pegado a la cmara en el muro lateral derecho que conforma el canal,
es circular de dimetro 2.00 m y longitud 315.00 m, en donde recibe el caudal de
purga del estanque decantador hasta terminar en una caja de toma tipo Buzn-ocmara de carga.
Parmetros bsicos de diseo
El sistema de conduccin de las demasas se ha diseado para un caudal de
evacuacin de hasta 14.00 m 3/s, vertedero y canal de evacuacin de las
demasas. Por el mismo sistema en la parte terminal desalojar las aguas de purga
o limpia de los sedimentos acumulados.
Descripcin de la estructura
Aliviadero de demasas y evacuacin:
Borde libre y altura del vertedero 0.80 m
El vertedero lateral de control de demasas, se ha diseado para una capacidad
total de 14.00 m 3/s, en caso de ocurrir imprevistos y sea necesario el cierre
instantneo de las turbinas.
Seccin del canal circular 2.00 m de dimetro.
Caja de toma: ubicada despus de la compuerta de purga, que se usar para
desaguar las aguas de purga y luego se conducir por medio de un conducto
circular y que adems recibir las aguas del canal vertedor.
Aspectos constructivos y materiales de construccin

Los muros, losas de piso del canal vertedor, caja de toma y el canal de purga, as
como los colchones de amortiguacin de energa sern de concreto armado fc =
210 kg/cm2, acero de refuerzo fy = 4 200 kg/cm 2.
Instalado en una zanja con apoyo de cama de arena y cubierto con material
clasificado debidamente compactado y bloques de anclaje en los cambios de

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 66

direccin de la tubera y sern de las dimensiones indicadas en el plano


correspondiente y de concreto ciclpeo fc = 20 kg/cm 2 con 30% de P.M.

3.3.8 Casa de Mquinas


La casa de mquinas incluye una sala de mquinas, oficina, talleres, almacn,
sala de bateras, sala de radio y sala para un grupo electrgeno de emergencia.
Cuenta adems con ambientes para los transformadores y tableros de control.
El edificio que albergar los grupos de generacin contar con los siguientes
ambientes:

Sala de Celdas

Sala de Control

Sala de Turbinas

Sala de bateras

Oficina y Radio

Sala de transformadores

Servicios higinicos

Almacn y oficinas.

Equipamiento de Generacin
Tomando en consideracin el caudal de diseo de las unidades de generacin, el
salto neto disponible y la velocidad especfica de los grupos, las turbinas Francis
permiten alcanzar la mxima eficiencia y son las adecuadas para las
caractersticas del aprovechamiento hidroelctrico.
As mismo, de acuerdo a la demanda y su crecimiento se ha definido que la
potencia total de la central sea distribuida en 3 unidades con el propsito de
adecuarse mejor a sta.
La casa de mquinas, de acuerdo a lo sealado, ser equipada con turbinas tipo
Francis de eje horizontal, y todos los dems equipos y elementos adicionales
requeridos para la generacin de energa y potencia elctricas.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 67

La turbina estar conformada por la vlvula mariposa, Inyectores, la carcasa,


paletas y estructura de evacuacin, gobernador de velocidad y sistema de control.
El

generador

estar

compuesto

por

el

generador

propiamente

dicho,

autoventilado, de polos salientes con excitacin esttica sin escobillas; los equipos
de maniobra y tableros de control respectivos.
En la sala de mquinas se instalar un puente gra, manual, para facilitar las
labores de montaje y mantenimiento.

3.3.9 Canal de Restitucin


El canal de restitucin o descarga evaca las aguas turbinadas devolvindola al
rio Canipaco.
El canal de descarga termina en una rpida hacia el ro y est protegido de la
erosin por medio de un enrocado.
El canal de restitucin para las tres turbinas tiene una longitud de 25.00 m.

3.4

Caractersticas Hidrulicas
La Central hidroelctrica de Chilcay tiene las siguientes caractersticas principales:

Bocatoma

: De derivacin con barraje mixto.

Sistema de Conduccin

: Canal en Conducto Cubierto de Concreto

armado.

Caudal de diseo

: 14.00 m3/s

Salto neto

: 147.57m.

Caudal de diseo de c/turbina

: 6.50 m3/s

Tensin de generacin

: 4.16 KV

Tensin de entrada en S.E. salida

: 4.16 KV

Tensin de salida en S.E. salida

: 60 KV

Tensin de instalaciones interiores y exteriores : 220 V.

Tensin de control y mando

: 110 Vcc

Rgimen de carga

: Full

Mayor informacin de datos de la memoria de clculos (Ver Anexos).

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

3.5

Pgina 68

Cronograma de Ejecucin de Obras


El cronograma para la ejecucin de la central Hidroelctrica Chilcay.se llevara como se
muestra en los anexos adjuntos.
Cuadro N 34: Cronograma de Actividades
ESTUDIO

OBRA

DEFINITIVO
ETAPAS DEL PROYECTO CH

OBRAS ELECTRO-MECANICAS
(GENERACION)
OBRAS ELECTRO-MECANICAS
(SUBESTACION)

Mes 9

Mes 10

Mes 11

Mes 12

Mes 13

Mes 14

Mes 15

Mes 16

Mes 17

Mes 18

Mes 19

Mes 20

Mes 21

Mes 22

Mes 8

Mes 7

Mes 4

Mes 6

Mes 3

Mes 5

OBRAS CIVILES

Mes 2

ESTUDIO DEFINITIVO C.H

Mes 1

CHILCAY

LINEA DE TRANSMISION
(SUMINISTRO Y MONTAJE)

Fuente: EGECSAC.2013

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 69

CAPTULO IV: PLAN DE APROVECHAMIENTO DE LOS RECURSOS HDRICOS EN


LA SUB CUENCA DEL RIO CANIPACO
4.1

Descripcin de la Operacin del Sistema Hidrulico del Proyecto

Esquema general del proyecto


La Central hidroelctrica de Chilcay funcionar con las aguas del Rio Canipaco
Desde la Bocatoma se derivar un caudal de 15.4 m 3/seg, hasta el Desarenador,
habiendo considerado un porcentaje del 10% de este caudal para limpieza de partculas
slidas y como caudal ecolgico. Del Desarenador contina el flujo de 14 m 3/s por el
Sistema de Conduccin hasta la Cmara de Carga. Para el sistema de conduccin se
tiene previsto la construccin de un canal en Conducto Cerrado en concreto armado de
seccin b=3.20 m y H= 2.50 en una longitud de 6,600 m el que entrega el caudal a la
Cmara de Carga a una cota de pelo de agua 3,340.508 msnm.
Caudal de diseo
El mejor aprovechamiento de la energa potencial dispensada por las aguas del ro
Canipaco corresponde a considerar un caudal disponible en la cuenca por un periodo
aproximado de tres meses (87 das segn historia), de lo cual tomamos como caudal de
diseo de la Central Hidroelctrica 14.00 m3/seg. Con este caudal y el salto neto de
147.57 m se obtiene una potencia de 19.21 KW en bornes de los generadores,
considerando una eficiencia de 97% en las turbinas hidrulicas y 98% en los
generadores.
El caudal normal derivable es de 14.0 m 3/s que se descompone de la siguiente manera:

Caudal que requieren las turbinas: 3 x 4.666 = 14.0 m 3/s

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY
4.2

Pgina 70

Descripcin de la operacin del sistema Hidrulico del Estudio


Con el estudio realizado de la topografa para la central Hidroelctrica Chilcay se
identific un salto hidrulico de 147.57 m. el cual hace posible la operacin de la central
hidroelctrica, tambin se considera que es una de las cuenca reguladas por Electro
Per, el uso de las aguas sern con fines No consuntivas, es decir sern devueltas a su
cauce natural sin ser alteradas en su cantidad y calidad. El punto de inters de Electro
Per es las aguas en la Represa de Tablachaca, el cuna no alteraremos el rgimen
hdrico energtico de Electro Per.
El costo de construccin de la central hidroelctrica es de US$. 38041,709.26 Dlares
americanos en valores de produccin se considera US$./MW 1678,736.66 teniendo una
seguridad productiva de 19.21 MW

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 71

Cuadro N 34: Presupuesto del Proyecto


CENTRAL HIDROELECTRICA
CHILCAY

ESTUDIO FACTIBILIDAD CH CHILCAY

Proyecto: C.H. CHILCAY 19.21 MW


Factor de cambio
N
A

DESCRIPCION

PARCIAL (S/.)

PARCIAL (US$.)

OBRAS CIVILES

OBRAS PROVISIONALES

2.00

OBRAS DE CAPTACION

3.00
4.00
5.00

CAMARA DE CARGA

6.00

CASETA DE VALVULA

7.00

SISTEMA DE ALIVIO

8.00

TUBERIA PRESION - ANCLAJES

798,921.39

312,078.67

3,956,049.72

1,545,331.92

CANAL DE CONDUCCION

24,641,645.46

9,625,642.76

ACUEDUCTO

10,910,887.38

4,262,065.38

1,068,062.36

417,211.86

970,008.87

378,909.71

67,624.28

26,415.73

336,587.51

131,479.49

9.00

CANAL DE DESCARGA

3,386,303.10

1,322,774.65

10.00

CASA DE MQUINAS

55,812.53

21,801.77

11.00

PUENTE CANOA
CASA DE MAQUINAS

71,052.18

27,754.76

1,127,377.44

440,381.81

OBRAS HIDROMECANICAS Y ELECTROMECANICAS (GENERACION)

6,515,636.72

1.00

SUMINISTRO, TRANSPORTE Y MONTAJE DE TUBERIA DE ALIVIO I (124 M)

2.00

EQUIPAMIENTO ELECTROMECANICO COMPUESTO POR DOS GRUPOS, HIDROELECTRICOS


PELTON DE 10 MW CADA UNO, INCLUIDO EL SISTEMA AUTOMATICO DE MEDICION, CONTROL
Y PROTECCION.

3.00

COMPUERTAS, REJILLAS, ATAGUIAS, VALVULAS (BOCATOMA, CAMARA DE CARA Y CASETA


DE VALVULA)

1.00

Total (US$.)
18,511,848.52

1.00

121.00

2.56

1,626,750.00

635,449.22

14,753,280.00

5,763,000.00

300,000.00

117,187.50

9,472,000.00

3,700,000.00

8,988,803.64

3,511,251.42

LINEA DE TRANSMISION (SUMINISTRO Y MONTAJE)

3,700,000.00

LNEA DE TRANSMISIN EN 60kV (34 KM)


COSTO DIRECTO
GASTOS GENERALES ( 12.22% )

28,727,485.24

UTILIDADES

3,511,251.42
-

SUBTOTAL

32,238,736.66

IMPUESTO GENERAL A LAS VENTAS

18%

5,802,972.60

US$.

38,041,709.26

COSTO DIRECTO DE OBRAS

US$.

32,238,736.66

MW GENERADOS

MW

COSTO TOTAL DE EJECUCION DE OBRAS


COSTOS POR MW

RATIO

19.21

US$./MW

1,678,226.79

Fuente: EGECSAC, 2013

4.3

Descripcin de los Impactos en la Operacin del Sistema del Proyecto y Planes o


Medidas de Compensacin

4.3.1

IMPACTOS EN LA ETAPA DE CONSTRUCCIN

A.

Medio Fsico

Alteracin de la calidad del aire

Este impacto tiene relacin con la alteracin que se producir en la calidad del aire
principalmente por el ruido y la generacin de material particulado causado por la
remocin de tierra, emisin de gases de combustin y generacin de ruido de los
equipos y maquinarias, que se originar a partir del inicio de las obras en los frentes
de trabajo del proyecto.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 72

Afectacin de suelos

Debido a probables derrames de combustibles, aceites, grasas y/o similares


durante los trabajos a efectuarse en esta etapa de construccin. As como su
erosin por la construccin de vas de acceso, apertura de zanjas para los canales
de conduccin y preparacin del terreno para la instalacin de la casa de mquinas.

Afectacin de calidad del agua

Es probable que por remocin de tierra para la construccin de la bocatoma, los


sedimentos puedan depositarse sobre los cuerpos de agua de manera natural.

Afectacin del relieve

Como se mencion la accin de remocin de tierra para la construccin e


instalacin de equipos y/o maquinarias alterara el relieve del rea de estudio.
B.

Medio Bitico

Perturbacin de la flora y fauna local silvestre

Este impacto se refiere a los efectos que pueden generarse sobre la flora y fauna
existente en las zonas cercanas al rea de emplazamiento del proyecto. Debido a
la presencia de personas, materiales, maquinarias y/o equipos a utilizarse durante
la etapa de construccin.
C.

Medio Socioeconmico

Generacin de empleo

Este impacto est referido a la generacin de empleo directo, para diferentes


niveles de mano de obra, tanto calificada como no calificada, como consecuencia
de la ejecucin de las distintas actividades involucradas en la etapa de
construccin del proyecto.
La ocupacin de mano de obra no calificada de la zona, permitir incrementar los
ingresos de los pobladores, generando mejores condiciones de accesos a los
bienes y servicios, lo que a su vez, se traducir en una mejora en el nivel de vida
de la poblacin beneficiada adems de bienestar para la poblacin y contribuye a
la mejora de la economa local.

Calidad de vida

Se mejorar el nivel de calidad de vida de la poblacin, ya que se generar trabajo


con los goces de ley correspondiente. Asimismo, se generar servicios a favor de

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 73

la comunidad, en el aspecto referido a los seguros ocupacionales y mejoras en las


infraestructuras de servicios bsicos como salud y seguridad.

Percepcin de la Poblacin

La poblacin del distrito de Colca, percibe este proyecto como un impulso para el
desarrollo de gestin de proyectos agropecuarios, difundir el turismo zonal, como
tambin promover la inversin pblica y privada de la zona, por tanto se puede
aseverar que existe una buena percepcin de la poblacin hacia el proyecto, lo
que se ha podido conocer en las visitas realizadas en campo y durante el taller de
difusin.
Ver detalle en la Tabla N02: Matriz de Significancia de los Impactos Ambientales
- Etapa de Construccin: (Ver anexos).

4.3.2

Impactos en la Etapa de Operaciones

A.

Medio Fsico

Afectacin de los suelos

La afectacin del suelo puede ocurrir potencialmente por derrame de combustible,


insumos qumicos, aceites y grasas sobre el suelo. Para ello se tomarn las
medidas necesarias de control y manejo.

Hidrologa y afectacin de la calidad de agua

Debido a la utilizacin de la bocatoma, en la captacin del agua, el agua


superficial del ro Canipaco, puede verse comprometida con sedimentos. As
mismo, el caudal se ver disminuido hasta alcanzar el caudal ecolgico.

Afectacin de los suelos

La afectacin del suelo puede afectarse potencialmente por derrame de


combustible, aceites y grasas sobre el suelo.
En el momento de la descarga del agua turbinada, potencialmente se puede
erosionar el borde del talud, con lo cual erosionar el suelo de la zona.
B.

Medio Bitico

Perturbacin de la fauna local silvestre

Las actividades ocasionarn un stress sobre la fauna existente en el rea de


influencia, provocando una reaccin de migracin, por los ruidos generados. Los

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 74

recursos hidrobiolgicos se podrn ver afectados por la disminucin del caudal en


el tramo del proyecto.
C.

Medio Socioeconmico

Generacin de empleo

Las actividades de operacin del proyecto requieren personal para

el

mantenimiento y gestin de las actividades, por lo que se requerir de mano de


obra de las poblaciones cercanas.

Calidad de vida

Se mejorar el nivel de calidad de vida de la poblacin, ya que se generar trabajo


con los goces de ley correspondiente. Asimismo, se generar servicios a favor de
la comunidad, en el aspecto referido a los seguros ocupacionales y mejoras en las
infraestructuras de servicios bsicos como salud y seguridad.

Percepcin de la Poblacin

La poblacin del distrito de Colca, percibe este proyecto como un impulso para el
desarrollo de gestin de proyectos agropecuarios, difundir el turismo zonal, como
tambin promover la inversin pblica y privada de la zona, por tanto se puede
aseverar que existe una buena percepcin de la poblacin hacia el proyecto, lo
que se ha podido conocer en las visitas realizadas en campo y durante el taller de
difusin.
Ver detalle en la Tabla N03: Matriz de Significancia de los Impactos Ambientales
- Etapa de Operaciones: (Ver anexos)

4.3.3

Impactos en la Etapa de Cierre

A.

Medio Fsico

Alteracin de la calidad del aire

Al ponerse fuera de servicio las instalaciones, se efectuar limpieza de las reas,


donde se ubicaron las estructuras permanentes como la Casa de Fuerza, los
canales y la zona de la Bocatoma; lo cual involucra remocin de tierra generando
material particulado.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 75

El nivel de ruido se incrementar en forma temporal por la utilizacin de equipo


para el retiro de las instalaciones, as como el transporte de los materiales que
sern retirados fuera de las instalaciones.

Afectacin de los suelos

La afectacin del suelo puede afectarse potencialmente por derrame de


combustible, aceites y grasas.

Hidrologa y afectacin de calidad del agua superficial

Debido a las actividades a realizarse en la margen del ro La Virgen, pueden que


se transporten sedimentos que pueden depositarse sobre los cuerpos de agua de
manera natural.
Por otro lado, debido al cierre del proyecto el caudal volver a su estado natural.

Afectacin del relieve

Se realizarn obras de empalme y cimentacin del relieve.

B.

Medio Bitico

Perturbacin de la flora y fauna local silvestre

Las actividades ocasionarn un stress sobre la flora y fauna existente en el rea


de influencia, provocando una reaccin de migracin, sin embargo al trmino de
las actividades se espera que la fauna retorne completamente.
Asimismo, al restituir componentes ambientales en el suelo se recuperar a la
flora nativa, por lo que se considera un impacto positivo.
C.

Medio Socioeconmico

Generacin de empleo

Las actividades del cierre originarn empleo temporal por las actividades de
desmantelamiento y desmontaje de los equipos y retiro de las estructuras.

Calidad de vida

Se mejorar el nivel de calidad de vida de la poblacin, ya que se generar trabajo


con los goces de ley correspondiente.
Ver detalle en la Tabla N04: Matriz de Significancia de los Impactos Ambientales
- Etapa de Cierre: (Ver anexos)

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 76

EVALUACIN DE IMPACTOS AMBIENTALES


Tomando en cuenta la metodologa de identificacin y evaluacin de impactos
ambientales, explicada anteriormente, se ha procedido a determinar las Matrices
de significancia de los impactos ambientales del proyecto para las etapas de
construccin, operacin y cierre, los cuales se indican en los cuadros anteriores,
respectivamente.

4.3.4 EVALUACIN DE LOS IMPACTOS AMBIENTALES EN LA ETAPA DE


CONSTRUCCIN
-

MEDIO FSICO

a)

Alteracin de la calidad de aire

Por emisin de material particulado

El material particulado, es originado por el movimiento de tierras por la nivelacin


del terreno donde se instalaran las construcciones permanentes, actividades de
perforacin y excavaciones para los canales de conduccin.
El transporte de camiones cisternas, camionetas por los accesos y el uso de
maquinaria. Estas emisiones son tpicas de cualquier actividad de construccin y
su impacto es temporal limitndose al tiempo que dure esta etapa del proyecto.

Por emisin de gases de combustin

Los gases de combustin (monxido de carbono, dixido de azufre, xidos de


nitrgeno e hidrocarburos) estn asociados al funcionamiento de la maquinaria y
vehculos. Debido al bajo nivel de emisiones y su localizacin cercana a la
construccin, permanecern en este lugar o se transportarn slo a cortas
distancias.
Las emisiones de polvo y gases asociadas a la etapa de construccin no afectar
significativamente la calidad del aire de la zona, la poca presencia de pobladores
en la zona, son factores determinantes para que no se ponga en riesgo la salud
de las personas. Del mismo modo, no se espera cambio alguno en los diferentes
procesos biolgicos y adaptativos de las especies animales presentes en el
entorno.

Incremento de nivel de ruido

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 77

Durante la etapa de construccin del proyecto se generar ruido producto de una


serie de actividades que involucran las tareas de movimiento de tierras y el
acondicionamiento del lugar, la construccin de los accesos y las excavaciones
para los canales correspondientes entre otros.
Dado que en el rea prxima al proyecto no existen pobladores que pudieran ser
afectados por los niveles de ruido, se puede inferir que el proyecto no generar
consecuencias con este parmetro.
Conclusin:
Basado en lo expuesto y tal como se indica en la matriz de significancia, este
impacto es de baja o leve significancia; de naturaleza negativa; de magnitud e
intensidad baja o leve; de alta importancia; reversibles y de duracin a mediano
plazo.
b) Afectacin del suelo
Como ya se describi anteriormente, durante la etapa de construccin siempre
existe el riesgo de contaminar los suelos por derrame de sustancias qumicas
tales como, combustibles, aceites y grasas; etc. utilizados en las maquinarias, as
como por los residuos y materiales domsticos e industriales tales como; cartn,
madera, pintura, trapos de grasa y combustibles, etc.
Conclusin:
Basndose en lo anterior y tal como se indica en la matriz de significancia, este
impacto es de baja o leve significancia; de naturaleza negativa; de magnitud e
intensidad baja o leve; de alta importancia; reversible y de duracin de mediano
plazo.
c)

Afectacin de calidad de agua superficial

Durante la etapa de construccin la remocin de tierras y la construccin de la


bocatoma puede depositarse sobre los cuerpos de agua.
Conclusin:
Basndose en lo anterior y tal como se indica en la matriz de significancia, este
impacto es de baja o leve significancia; de naturaleza negativa; de magnitud e
intensidad media; de alta importancia; reversible y de duracin de mediano plazo.
d) Modificacin de relieve

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 78

Este impacto se genera por las modificaciones del rea del proyecto y ser
ocasionado por los trabajos de nivelacin del terreno y remocin de tierra, lo que
modificar el relieve actual.
Conclusin:
Este impacto es de baja o leve significancia; de naturaleza negativa; de magnitud
e intensidad media; de alta importancia; reversible y de duracin de mediano
plazo.
-

MEDIO BITICO

En el rea de influencia del proyecto no se ha identificado especies de flora o


fauna que se encuentren en situacin vulnerable. Sin embargo el trabajo involucra
la migracin temporal de la fauna.
Conclusin:
Este impacto es de media a moderada significancia; de naturaleza negativa; de
magnitud e intensidad media; de alta importancia; reversible y de duracin de
mediano plazo.
-

MEDIO SOCIOECONMICO Y CULTURAL

a)

Generacin de empleo

La ocupacin de mano de obra de la zona permitir incrementar los ingresos de


los pobladores, generando mejores condiciones de accesos a los bienes y
servicios, lo que a su vez, significa una mejora en el nivel de calidad de vida de la
poblacin beneficiada.
b) Calidad de vida
Se mejorar el nivel de calidad de vida de la poblacin, ya que se generar trabajo
con los goces de ley correspondiente. Asimismo, se generar servicios a favor de
la comunidad, en el aspecto referido a los seguros ocupacionales y mejoras en las
infraestructuras de servicios bsicos como salud y seguridad.
c)

Percepcin de la Poblacin

La poblacin del distrito de Colca, percibe este proyecto como un impulso para el
desarrollo de gestin de proyectos agropecuarios, difundir el turismo zonal, como
tambin promover la inversin pblica y privada de la zona, por tanto se puede
aseverar que existe una buena percepcin de la poblacin hacia el proyecto, lo

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 79

que se ha podido conocer en las visitas realizadas en campo y durante el taller de


difusin.
Conclusin:
Este impacto muestra una valoracin de baja significancia; de naturaleza positiva;
de magnitud e intensidad baja; de alta importancia; reversible y de duracin
media.

4.3.5 Evaluacin de los Impactos Ambientales en la Etapa de Operaciones


MEDIO FSICO
a)

Calidad del aire

La generacin elctrica a travs del uso del recurso renovable (agua de ro) que
realizar la Central Hidroelctrica Chilcay, se constituye como un proyecto de
generacin limpia; por lo tanto no incurre en emisiones de gases de efecto
invernadero, sin embrago existir el trnsito vehicular para transporte de personas
e insumos, lo que generar gases de combustin y formacin de material
particulado, pero en zonas lejanas al Centro Poblado.
Conclusin:
Este impacto es de baja o leve significancia; de naturaleza negativa; de magnitud
e intensidad baja o leve; de alta importancia; reversibles y de duracin a mediano
plazo.
b) Calidad del suelo
La afectacin del suelo puede afectarse potencialmente por derrame de
combustible, aceites y grasas sobre el suelo. Asimismo, en el momento de la
descarga del agua turbinada, potencialmente se puede erosionar el borde del
talud, con lo cual erosionar el suelo de la zona.
Conclusin:
De la matriz de evaluacin, resulta que este impacto es de baja o leve
significancia.
c)

Calidad del agua

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 80

Alteracin de la calidad del agua: La limpieza y mantenimiento del embalse


durante la etapa de operacin del proyecto podra generar un incremento de la
turbidez en las aguas; sin embargo, se estima este ser mnimo, considerndose
que la purga de sedimentos se realizar durante el perodo de lluvias y se
efectuar de manera paulatina en varios das. As tambin se indica que las
operaciones de descarga de las aguas turbinadas podran generar el incremento
de la turbidez en las inmediaciones de su descarga sobre el ro Canipaco.
Disminucin de caudal en seccin del ro: La operacin de la seccin del ro
aguas abajo de la estructura de captacin, har que los niveles de caudal sean
menores a las condiciones actuales. Este efecto ser ms notorio en la poca de
estiaje, por cuanto en los perodos de precipitaciones los excedentes hdricos son
suficientes y no sern perceptibles en mayor medida. Esta disminucin del caudal
slo se realizar en el tramo del proyecto (3 Km).
Conclusin:
De la matriz de evaluacin, resulta que este impacto es de baja o leve
significancia; siendo adems un impacto negativo, de alta importancia; reversible y
de duracin a mediano plazo.
-

MEDIO BITICO

Este impacto es de magnitud media o moderada significancia, de alta importancia;


reversible y de duracin a mediano plazo.
-

MEDIO SOCIOECONMICO Y CULTURAL

a)

Generacin de empleo

Para el desarrollo del proyecto se requerir un total de 15 trabajadores. Un


porcentaje de trabajadores estar conformado por pobladores de la comunidad del
rea de influencia.
b) Calidad de vida
Se mejorar el nivel de calidad de vida de la poblacin, ya que se generar trabajo
con los goces de ley correspondiente. Asimismo, se generar servicios a favor de
la comunidad, en el aspecto referido a los seguros ocupacionales y mejoras en las
infraestructuras de servicios bsicos como salud y seguridad.
c)

Percepcin de la Poblacin

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 81

La poblacin del distrito de Colca, percibe este proyecto como un impulso para el
desarrollo de gestin de proyectos agropecuarios, difundir el turismo zonal, como
tambin promover la inversin pblica y privada de la zona, por tanto se puede
aseverar que existe una buena percepcin de la poblacin hacia el proyecto, lo
que se ha podido conocer en las visitas realizadas en campo y durante el taller de
difusin.
Conclusin:
Este impacto muestra una valoracin de baja significancia; de naturaleza positiva;
de magnitud e intensidad baja; de alta importancia; reversible y de duracin
media.

4.3.6 Evaluacin de los Impactos Ambientales en la Etapa de Cierre


-

MEDIO FSICO

a)

Alteracin de la calidad de aire

Durante la etapa de cierre tambin se generar emisiones gaseosas y material


particulado producto del desmantelamiento de las obras civiles. Este impacto sin
embargo es de menor envergadura que el de la etapa de construccin.
Durante los trabajos de desmontaje de los equipos y el desmantelamiento de las
obras civiles; se incrementar los niveles de ruido de manera puntual y a corto
plazo.
Conclusin
Este impacto es de naturaleza negativa y de significancia baja; de naturaleza
negativa; de magnitud e impacto medio; de moderada importancia; reversible y de
duracin de corto plazo.
b) Afectacin del suelo
Este impacto est vinculado a los posibles derrames de combustibles, aceites y/o
similares de los equipos y vehculos de transporte durante los trabajos de retiro de
equipos y demolicin de obras.
Conclusin:

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 82

Este impacto es de naturaleza negativa considerada de significancia baja; de


naturaleza negativa; de magnitud e impacto medio; de moderada importancia;
reversible y de duracin a mediano plazo.
c)

Afectacin de calidad de agua

Durante la desinstalacin la remocin de tierra puede verse depositados


sedimentos sobre los cuerpos de agua.
Conclusin:
Este impacto es de naturaleza negativa considerada de significancia baja o leve;
de naturaleza negativa; de magnitud e impacto medio; de moderada importancia;
reversible y de duracin a mediano plazo.
-

MEDIO BITICO

Este impacto es de naturaleza negativa considerado de significancia baja; de


magnitud e intensidad alta, reversible y de duracin de mediano plazo.
-

MEDIO SOCIOECONMICO

a)

Generacin de empleo

Como en la etapa de construccin, para realizar los trabajos de cierre: desmontaje


de los equipos, desmantelamiento de las obras civiles y limpieza del lugar, se
requerirn trabajadores calificados y no calificados de preferencia del distrito de
Colca.
b) Calidad de vida
Se mejorar el nivel de calidad de vida de la poblacin, ya que se generar trabajo
con los goces de ley correspondiente. Asimismo, se generar servicios a favor de
la comunidad, en el aspecto referido a los seguros ocupacionales y mejoras en las
infraestructuras de servicios bsicos como salud y seguridad.
Conclusin:
Este impacto es considerado de naturaleza positiva y de significancia leve.
CONCLUSIN GLOBAL DE LA EVALUACIN DE IMPACTOS AMBIENTALES
De la evaluacin de los impactos ambientales se puede concluir que las
actividades del proyecto, en sus diferentes etapas interactan con su entorno

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 83

produciendo impactos ambientales que se califican mayormente como de baja o


leve significancia.
Esta calificacin global obtenida es un indicador de la magnitud y complejidad
operacional del presente proyecto, lo cual infiere que las implicancias del proyecto
sobre su entorno son significativamente bajas o leves.

4.3.7 Evaluacin de Potenciales Impactos Sociales


En esta seccin

se identifican y evalan los posibles impactos sociales que

pudiera generar el desarrollo de las actividades del Proyecto Central


Hidroelctrica Chilcay.
a)

Metodologa de Identificacin y Evaluacin de Impactos Sociales

Para el presente estudio se ha considerado como herramienta fundamental


terica, la Gua de Relaciones Comunitarias del Ministerio de Energa y Minas; la
evaluacin del impacto social,

utiliza varios mtodos para identificar los

potenciales impactos y el nivel de los mismos que, a criterio profesional, se


considere ms probable que ocurran. Los puntos de partida esenciales son una
lnea base general y familiaridad con el contexto social. El anlisis comparativo
con proyectos similares, sirve para identificar el parecido de ciertos impactos que
estn ocurriendo, con otros que hayan ocurrido en ambientes similares. Se hace
uso de la opinin profesional y de la experiencia para evaluar el parecido del
contexto con otros ejemplos. Debido a que el ambiente humano es muy
impredecible, se requiere un seguimiento de monitoreo, para evaluar si los
impactos ocurren como se pronostican, y evaluar la efectividad de las medidas de
mitigacin.
b) Importancia de los Impactos Sociales
En esta seccin se identifican y evalan los posibles impactos sociales que
pudieran originarse por efecto del desarrollo de las actividades del Proyecto C.H.
Chilcay para la Central Hidroelctrica CHILCAY, por ello se ha definido esta
matriz, la que tiene como objetivo reconocer y entender los distintos impactos
sociales que podran ocurrir durante las fases de un Proyecto.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 84

Institucional

Capacidad

Reversibilidad

Posibilidad de Correccin

Magnitud

Local

Sensibilidad

Gravedad

Duracin

Extensin

Demogrfica

Impactas

Personas

Ocurrencia

Probabilidad de

Naturaleza del Impacto


IMPACTOS

EVALUACIN DE LOS

Cuadro N 35: Evaluacin de impactos sociales

La Comunidad

Generacin
de empleo

Es inevitable,
el impacto es
positivo.

50

Tiempo de

Pobladores de

Reversible,

Campesina hace

personas

duracin

la zona

ya que el

vigilancia social

del

dispuestos al

impacto es

para inscripcin de

proyecto.

trabajo.

de la

AID y AISI

comunidad

Leve

temporal

los nuevos
trabajadores.

Se prev que

Percepcin
del Proyecto

Es Probable

Pobladores

Tiempo de

es positiva la

que viven

duracin

percepcin

del

por parte de

proyecto.

los pobladores

dentro del

AID

AID

Las autoridades,
dirigentes hacen
Moderada

Reversible

la empresa.

del AID.

Las
Calidad de
Vida

Es Probable,

personas

el impacto es

que viven

positivo

c)

Tiempo

Se prev que

seguimiento y
coordinaciones con

Dirigentes y

de

es positiva por

duracin

parte de los

dentro del

del

pobladores

monitoreo del

AID

proyecto.

del AID.

tema.

AID

autoridades hacen
Leve

Irreversible

seguimiento y

Identificacin de Impactos sociales

En esta seccin se identifican los potenciales impactos que pudieran originarse


por efecto del desarrollo de las actividades del Central Hidroelctrica Chilcay,
Entre los principales impactos identificados tenemos:

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 85

La generacin de empleo, es un impacto positivo que involucra beneficio


para una pequea parte de la poblacin,

por lo que est referido a la

generacin de empleo directo, en diferentes niveles de mano de obra, como


consecuencia de la ejecucin de las distintas actividades involucradas en la
etapa de construccin del proyecto.

Percepcin de los pobladores, se prev una percepcin positiva del proyecto


por parte de las personas que viven dentro del rea de influencia.

La calidad de vida de las personas est relacionada con la mejora

del

bienestar social de las pobladores que viven en el rea de influencia del


proyecto.

4.3.8 Plan de Manejo Ambiental


El Plan de Manejo Ambiental (PMA), contiene un conjunto de medidas destinadas
a prevenir y mitigar los impactos ambientales potenciales en todas las etapas del
proyecto.
El Plan de Manejo Ambiental tiene como objetivo formular y adoptar las medidas
de prevencin, mitigacin y control de los impactos ambientales que se puedan
generar debido al desarrollo de las actividades del proyecto elctrico,
considerando todas sus etapas a fin de asegurar que los niveles de calidad
ambiental se encuentren dentro de los estndares permitidos. Este Plan considera
un conjunto de programas y de sus respectivas acciones encaminadas a que el
proyecto se realice con el mnimo grado de afectacin al entorno ambiental. Los
programas propuestos tendrn como objetivos cumplir con los estndares de
calidad ambiental aceptables y condiciones ptimas de seguridad y salud para el
personal.

4.3.9 Programas, Planes y Medidas


A continuacin se presentan los programas, planes y medidas que permiten el
cumplimiento de los objetivos del Plan de Manejo Ambiental:

Programa de Prevencin y/o Mitigacin


-

Subprograma de Proteccin del Componente Fsico-Qumico.

Subprograma de Proteccin del Componente Biolgico.

Subprograma de Proteccin del Componente Socio-Econmico.

Subprograma de Proteccin del Componente de Inters Humano.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Subprograma de Sealizacin.

Subprograma de Educacin Ambiental.

Pgina 86

Programa de Manejo de las actividades del Proyecto


-

Subprograma de Mantenimiento de Maquinarias.

Subprograma de Manejo de Residuos Lquidos.

Subprograma de Manejo de Residuos Slidos.

Subprograma de Manejo de Mantenimiento de Vehculos.

Subprograma de Manejo de Residuos Lquidos.

Subprograma de Manejo de Residuos Slidos.

Medidas Especficas para cada actividad del proyecto.


-

Medidas de Mitigacin para la Fase de Construccin

Medidas de Mitigacin para la Fase de Operacin.

Programa de Monitoreo Ambiental

Plan de Contingencias

Plan de Relaciones Comunitarias

4.3.10 Programa de Prevencin y/o Mitigacin

Las principales medidas de este Programa de Manejo Ambiental han sido


estructuradas en Subprogramas que se detallan en los acpites siguientes.
a)

Subprograma de Manejo de Componentes Fsico-Qumicos

Medidas para el Control de la Calidad del Aire

Las fuentes mviles de combustin usadas durante la construccin de las


obras, no podrn emitir al ambiente material particulado por encima de los
lmites establecidos por el Ministerio de Transportes.

Las actividades para el control de las emisiones atmosfricas buscan


asegurar el cumplimiento de las normas, para lo cual todos los vehculos y
equipos utilizados deben ser sometidos a un programa de mantenimiento y
sincronizacin preventiva antes del inicio de la obra.

El vehculo que no controle sus emisiones, y que excedan de los lmites


permisibles, deber ser separado de sus funciones, revisado, reparado y
ajustado antes de entrar nuevamente al servicio del transporte.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 87

Todas las unidades vehiculares contarn con sus respectivos silenciadores


para reducir la generacin de ruidos en la zona donde se ejecutar el
proyecto.

Medidas para la proteccin del Suelo

Los aceites y lubricantes usados, as como los residuos de limpieza,


mantenimiento y desmantelamiento del taller debern ser almacenados en
recipientes hermticamente sellados, asimismo debern contar con una
etiqueta para facilitar su rpido reconocimiento, debiendo sta indicar la
procedencia del mismo y la fecha en que fue almacenado.

La disposicin de desechos de construccin se har en los lugares


seleccionados para tal fin. Al finalizar la obra y/o mantenimiento, se dispondr
adecuadamente los residuos generados.

Los materiales excedentes de las excavaciones se retirarn en forma


inmediata de las reas de trabajo, protegindolos adecuadamente con tapas
o bolsa hermticas, y se colocarn en las zonas de depsito previamente
seleccionadas o aquellas indicadas por el Supervisor Ambiental.

Los residuos lquidos aceitosos debern ser depositados en recipientes


hermticos y dispuestos en lugares adecuados. Por ningn motivo debern
ser vertidos en tierra.

Los suelos contaminados con aceites, debern ser trasladados y dispuestos


por una Empresa Prestadora de Servicios de Residuos Slidos (EPS-RS) o
una Empresa Comercializadora de Residuos Slidos (EC-RS) estas empresas
debern estar autorizados por la DIGESA de acuerdo a las competencias
normativas legales.

Limitar estrictamente el movimiento de tierras en el rea aledaa donde se


construirn las obras del Proyecto.

El material superficial removido de una zona de prstamo, deber ser


retirado, apilado y protegido para su posterior utilizacin en las obras de
restauracin.

Los desperdicios originados durante la construccin sern clasificados.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 88

Los restos del material de construccin excedente debern ser retirados y


trasladados al relleno respectivo para su disposicin final. No se deben dejar
reas sin recubrir utilizndose para ello la misma cobertura que tena.

b) Subprograma de proteccin del componente Biolgico

Evitar el desbroce innecesario de los cultivos fuera de las zonas en donde se


emplazar las obras del Proyecto.

Se emplear tcnicas apropiadas para la limpieza y desbroce.

Una vez finalizada la obra, se realizar a la brevedad posible la recuperacin


de las zonas afectadas (excavaciones y movimientos de tierra) con la
colocacin de la misma cobertura que fueron extradas, proceso que significa
la restauracin del rea afectada.

Se limitar las actividades de construccin y operacin estrictamente al rea


en donde se levantarn las obras civiles, evitando de este modo alterar los
hbitats de la fauna silvestre.

Se evitar la intensificacin de ruidos, por lo que los silenciadores de las


mquinas empleadas debern estar en buenas condiciones.

c)

Subprograma de Manejo del Componentes Socio-Econmico

Componente Social

Se apoyar a los pobladores locales contratndolos como mano de obra no


calificada y en servicios de alimentacin en caso se requiera.

Todos los trabajadores asignados a la labor de campo se sometern a un


examen mdico pre-ocupacional y al finalizar las obras, el que incluirn
anlisis de laboratorio, sobre todo de existir personal forneo recientemente
arribado y contratado solamente para este proyecto.

Durante la etapa de construccin de la C.H. Chilcay se colocarn en lugares


visibles afiches alusivos a costumbres higinicas (lavado de manos,
disposicin de desechos, etc.).

Para cumplir las disposiciones relacionadas con la salud ocupacional, la


seguridad industrial y la prevencin de accidentes en las obras, se dispondr
en conjunto con la Gerencia General un rea de Supervisin Ambiental, con
un plan especfico del tema acompaado del anlisis de riesgos y salud
ocupacional.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 89

Se dispondr a los empleados, subcontratistas, proveedores y agentes


relacionados con la ejecucin de la obra, el cumplimiento de todas las
condiciones relativas a salud ocupacional, seguridad industrial y prevencin
de accidentes establecidas en los documentos del contrato.

Todo el personal estar dotado de elementos para la proteccin personal y


colectiva durante el trabajo, de acuerdo con los riesgos a que estn
sometidos (uniforme, casco, guantes, botas, lentes, arns, proteccin
auditiva, etc.). Los elementos sern de buena calidad y sern revisados
peridicamente para garantizar su buen estado.

Todo el personal de la obra ser capacitado sobre los riesgos de cada oficio,
la manera de utilizar el material disponible y como auxiliar en forma oportuna
y acertada a cualquier accidentado. EGECSAC, se comprometer a fin de
contar con la dotacin mnima de camillas, botiquines y dems implementos
para atender los primeros auxilios.

EGECSAC, suministrar equipos, mquinas, herramientas e implementos


adecuados para cada tipo de trabajo, los cuales sern operados por personal
calificado y autorizado, slo para el fin con el que fueron diseados. Se
revisarn peridicamente para proceder a su reparacin o reposicin y
debern estar dotados con los dispositivos, inductivos, controles y seales de
seguridad exigidos o recomendados por los fabricantes.

La ejecucin de la obra se ejecutar en lo posible durante el da.

d) Subprograma de Sealizacin
-

Sealizacin para riesgos de excavacin

En lo referente a los riesgos que se producen por acciones de movimientos


de tierra y excavaciones, se colocarn letreros de instrucciones y
advertencias para el personal de la obra y ajeno a ella, acerca de riesgos y
procedimientos.

Excavacin profunda

Las reas colindantes a la excavacin deben encontrarse protegidas con


cercos de seguridad para evitar accidentes por cada de personas y animales.

Las calicatas que se realicen, son muy difciles de visualizar desde el mismo
nivel, constituyendo riesgos de accidentes para los trabajadores, pblico en
general y animales. Si por alguna circunstancia se tenga que dejar alguna
excavacin expuesta se colocar una cubierta de madera de proteccin.

Sealizacin para la circulacin de vehculos

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 90

Los vehculos que inicien un movimiento lo anunciarn mediante seales


acsticas, esto incluye la seal de retroceso que es de carcter obligatorio
para todo vehculo

Se prever la actuacin de seales para advertir del movimiento de vehculos.


Por ejemplo:
o

Entrada de vehculos

Disminuya la velocidad, salida de vehculos

Peligro, salida y entrada de vehculos

Sealizacin para la proteccin del medio ambiente

La sealizacin que se propone consistir bsicamente en la colocacin de


paneles informativos en los que se indique al personal de la obra sobre la
importancia de la conservacin de los recursos naturales, los que sern
colocados en el rea de la obra en puntos estratgicos designados por el rea
de Supervisin Ambiental. Entre cuyos objetivos estarn:
o

A la prohibicin de alterar la fauna existente.

Disponer adecuadamente los residuos slidos

Evitar la contaminacin del aire y de las aguas, etc.

e)

Subprograma de Educacin Ambiental

Este Subprograma se refiere a la realizacin de campaas de educacin y


conservacin ambiental, siendo impartido al responsable de la aplicacin del
Plan de Manejo Ambiental, a los trabajadores del Proyecto, respecto a las
normas elementales de higiene, seguridad y comportamiento de orden
ambiental.

La educacin ambiental ser impartida mediante charlas (charlas de cinco


minutos antes del inicio de operaciones diarias), afiches informativos, o
cualquier otro instrumento de posible utilizacin.

El material escrito complementario quedar a disposicin del personal para su


consulta y aplicacin durante el tiempo que dure el Proyecto.

4.3.11 Medidas especficas para cada Actividad del Proyecto


Medidas de Mitigacin para la Fase de Construccin
a)

Medidas especficas para la construccin de la Bocatoma

Se colocarn defensas ribereas que permitan estabilizar las obras en esta


zona.

Asimismo se colocarn estructuras de disipacin de energa con la intencin


de controlar la erosin del cauce e inundacin de los mrgenes del ro.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 91

El diseo final de las estructuras, en las obras de bocatoma y desarenador,


tendr que adecuarse a la forma del terreno y paisaje natural, con la finalidad
de lograr un escenario concordante al entorno.

b) Medidas especficas para el Desarenador

Se construirn dispositivos que permitan el pase normal del caudal excedente


en poca de avenida y mantener el caudal ecolgico (para este caso el 10%
del caudal natural) en tiempo de sequa.

Se deber retirar la capa orgnica del suelo y disponerlo adecuadamente


para su posterior utilizacin.

Evitar el desbroce innecesario de los arbustos de esta zona.

Realizar trabajos de defensa riberea.

Restablecer la vegetacin mediante sembro de arbustos y pajonales en


reas adyacentes a las operaciones.

c)

Medidas Especficas Para el Canal de Conduccin

Se deber hacer un tratamiento en la estabilidad de taludes de las laderas del


cerro para evitar deslizamientos sobre el canal de conduccin.

d) Medidas para construccin de la Cmara de carga

Se tendr que prever la presencia de filtraciones de aguas subterrneas


durante la excavacin de la obra, en tal caso se tendr que recubrir con un
material impermeable las paredes y pisos evitando as prdidas de agua por
infiltracin.

Se dispondrn de zonas adecuadas para todo el material de excavacin, que


an siendo mnimo generar un impacto a los suelos.

e)

Medidas para la construccin de las Tuberas Forzadas

Ante la probable generacin de derrumbes de taludes se deber hacer una


adecuada estabilidad fsica o colocar un tipo de proteccin que evite que
estos deslizamientos impacten negativamente al ambiente o pueda ocasionar
dao.

f)

Medidas para la casa de Mquinas

Se contar con zonas adecuadas para disponer todo el material de


excavacin, en lo posible usar este material en alguna obra civil que requiera
el proyecto.

Se construirn instalaciones sanitarias mediante pozos spticos o baos


qumicos y sistemas para el tratamiento de aguas residuales.

g) Medidas para los caminos de Acceso

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 92

Se considerar las mismas medidas para las obras referidas al manejo de


desmontes y corte de suelo orgnico. As como tambin las medidas de
sealizacin.

Concluida las obras en los accesos construidos, deben restablecerse la


morfologa, suelos y realizar actividades de revegetacin de ser necesario.

h) Medidas para la Flora y Fauna Silvestre

Prohibir la caza y deforestacin por parte de los trabajadores del proyecto.

i)

Medidas para las Propiedades de Terceros

El proyecto no afectar ninguna propiedad privada, Asimismo se proceder a


su compensacin si fuera el caso.

Medidas de Mitigacin para la Etapa de Operacin


a)

Medidas para el rio Canipaco (Captacin)

El sistema estar asociado a la medicin de caudal en los canales del


desarenador que controlarn las compuertas de la bocatoma, asegurando
que en ningn caso pueda captarse ms de lo debido.

Se dispondr de un caudal ecolgico (para este caso el 10% del caudal


natural) que rebosar al cauce del ro, para su uso aguas abajo durante el
tiempo de sequa, con esto no habra conflicto con el agua captada por los
pobladores que usan para el regado de sus reas de cultivo.

b) Medidas en el Medio Socio-Econmico

Potenciar los beneficios sociales del proyecto a la comunidad local, dndoles


preferencia de empleo durante la construccin.

c)

Medidas para la Flora y Fauna Silvestre

Establecer y reforzar proyectos de conservacin de los recursos naturales del


rea.

4.4

Prohibir la caza y deforestacin por parte de los trabajadores del proyecto.

Servidumbre para el Proyecto


El acceso desde el distrito de Colca centro poblado de Chilcay, hasta la Central
Hidroelctrica, ser por un camino existente afirmado, en regular estado, a partir de la
cual se continuar con un camino carrozable hasta los puntos de la Bocatoma y la casa
de mquina.
LLa Comunidad Campesina de Chilcay cede una parte de sus tierras comunales para el
desarrollo del proyecto. Dicha concesin se encuentra en acuerdo mutuo suscrito en libro
de actas, La empresa se compromete a otorgar a la comunidad campesina de Chilcay, la

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 93

suma de S/.100,000.00 (ochenta mil y 00/100 Nuevos soles) anuales como parte de la
concesin. El plazo convenido por la Cesin de uso y la Constitucin de Servidumbre es
de 30 aos, contados a partir de la suscripcin del documento, con una extensin
superficial de 445.72 Hectreas, encerrado dentro de los linderos y medidas perimtricas
siguientes:
Cuadro N 36: Concesin del proyecto Central Hidroelctrica Chilcay
CUADRO DE COORDENADAS DE LA
POLIGONAL DE CHILCAY
Puntos

NORTE

ESTE

8635573

478756

8631932

480823

8630143

482149

8629614

483241

8631197

483885

8631197

484769

8631490

484416

8630153

483672

8630471

8630471

8635835

479363

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY

ESTUDIO HIDROLGICO CENTRAL


HIDROELCTRICA CHILCAY

Pgina 94

CAPTULO V: ANEXOS
CAPITULO VI: CONCLUSIONES Y RECOMENDACIONES
6.1 Conclusiones
Del estudio hidrolgico realizado en la sub cuenca del rio Canipaco, con la finalidad de
determinar los caudales de diseo para dimensionar un aprovechamiento hidroelctrico se
concluye lo siguiente:

La fase de evaluacin del recurso hdrico fue realizado en una superficie de 129
381.87 Ha., en el mbito de la sub cuenca del ro Canipaco.
El estudio cuenta con el respaldo de la legislacin vigente de la Autoridad Nacional
de Agua, lo cual impulsa al aprovechamiento sostenible de los recursos hdricos.
La capacidad de generacin de 19.21 MGW de potencia.
La captacin estar ubicada en el distrito de Colca, Cc. Cc.. Chilcay y la devolucin
o descarga en el distrito de Huayllahura - Huancavelica, el canal de conduccin
tendr una longitud de 10 765.18 ml., caudal de captacin de 15.00 m3/s y de
conduccin de 14.00 m3/s.
El caudal ecolgico del ro Canipaco se determin segn las directivas de la ANA,
con caudales medios, el mximo caudal ecolgico es de 2.34 m3/s es para el mes
de Febrero, y el caudal ecolgico mnimo con 0.60 m3/s para el mes de Setiembre
en meses de estiaje.
Del Balance Hdrico de asignacin para la sub cuenca del ro Canipaco, entre la
oferta hdrica y la demanda hdrica agrcola energtica, con los valores totales
anuales de 223.63 y 181.18 MMC.
El caudal de diseo: Q = 25.30 m3/s, tiene una probabilidad del 10 %; Q = 20.94
m3/s, tiene una probabilidad del 15%; Q = 18.07 m3/s, tiene una probabilidad del
20%; Q = 13.15 m3/s, tiene una probabilidad del 30 %; Q = 8.19 m3/s, tiene una
probabilidad del 45%; Q = 7.72 m3/s, tiene una probabilidad del 50 %; Q = 4.37
m3/s, tiene una probabilidad del 75 %; Q = 2.98 m3/s, tiene una probabilidad del 90
%; de ser igualado o excedido, aseguramos que se tendr un caudal de 2.36 m3/s
a un 95% y 1.12 m3/s a un 100%.
Los datos analizados son del registro de ELECTROPERU S.A. del periodo 2003
2012, con un registro de 10 aos mensualizados.

5.2 Recomendaciones
Del estudio hidrolgico realizado en la sub cuenca del rio Canipaco, se recomienda la
ejecucin de la construccin de central Hidroelctrica Chilcay, por existir el caudal mnimo
necesario para su operacin.

EMPRESA DE GENERACIN ELECTRICA CANCHAYLLO S.A.C. EGECSAC


Calle Miguel Dasso 117 Piso 11
San Isidro Lima, RUC N 20545538629

ESTUDIO
HIDROLGICO
CENTRAL HIDROELCTRICA
CHILCAY