SPECIFICATION FOR AN IEC 61850-COMPATIBLE TELEPROTECTION

SYSTEM

1.- ABSTRACT COMMUNICATION SERVICE INTERFACE (ACSI) SERVICES


The teleprotection system shall provide the following ACSI services with the specified
profiles (see IEC 61850-7-2 ver. 1.0) and a PICS file specifying the degree of
conformance statement;
1.1.- GOOSE messages
Application Association Model:

Multicast

Application profile (A-profile):

According to IEC 61850-8-1 Annex A


Server

Transport profile (T-profile):

IEEE 8802-3 frames with priority tagging and VLAN


identifier (IEEE 802.1Q)
Server and publisher

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 1A, class P2/P3 (3 msec)

1.2.- Time synchronization


Application Association Model:

Two-party or Multicast

Application profile (A-profile):

Simple Network Time Protocol, modes 3 & 4


implemented
Subscriber

Transport profile (T-profile):

ICMP over UDP/IP, ARP


Subscriber

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 6, class T1 (1 msec)

1.3.- Buffered Control Block Report / Unbuffered Control Block Report


The teleprotection system shall provide at least one of the two types of control block
report, with the following profile;

Application Association Model:

Two-party (client/server)

Application profile (A-profile):

MMS (Manufacturing Message Specification)


ACSE (Association Control Service Element)
Publisher

Transport profile (T-profile):

ISO Transport over TCP (RFC 1006)


TCP/IP with TCP_KEEPALIVE implemented and a
Transport Selector of 4 bytes
ICMP, ARP
Publisher

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 3 (500 msec)

Services implemented (if


BCBR):

Report (data-change, qchg-change, data-update)


GetBCBRValues
SetBCBRValues

Services implemented (if


UCBR):

Report (data-change, qchg-change, data-update)


GetUCBRValues
SetUCBRValues

1.4.- File Transfer


Application Association Model:

Two-party (client/server)

Application profile (A-profile):

MMS (Manufacturing Message Specification)


ACSE (Association Control Service Element)
Subscriber/Publisher

Transport profile (T-profile):

ISO Transport over TCP (RFC 1006)


TCP/IP with TCP_KEEPALIVE implemented and a
Transport Selector of 4 bytes
ICMP, ARP
Subscriber/Publisher

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 5 (no specific time requirement but access


control is mandatory)

Services implemented:

GetFile
SetFile
DeleteFile
GetFileAttributeValues

1.5.- Log
Application Association Model:

Two-party (client/server)

Application profile (A-profile):

MMS (Manufacturing Message Specification)


ACSE (Association Control Service Element)
Publisher

Transport profile (T-profile):

ISO Transport over TCP (RFC 1006)


TCP/IP with TCP_KEEPALIVE implemented and a
Transport Selector of 4 bytes
ICMP, ARP
Publisher

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 5 (no specific time requirement but access


control is mandatory)

Services implemented:

GetLCBValues
SetLCBValues
GetLogStatusValues
QueryLogByTime
QueryLogAfter

1.6.- Logical Device


Application Association Model:

Two-party (client/server)

Application profile (A-profile):

MMS (Manufacturing Message Specification)


ACSE (Association Control Service Element)
Publisher

Transport profile (T-profile):

ISO Transport over TCP (RFC 1006)


TCP/IP with TCP_KEEPALIVE implemented and a
Transport Selector of 4 bytes
ICMP, ARP
Publisher

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 5 (no specific time requirement but access


control is mandatory)

Services implemented:

LogicalDeviceDirectory

1.7.- Logical Node


Application Association Model:

Two-party (client/server)

Application profile (A-profile):

MMS (Manufacturing Message Specification)


ACSE (Association Control Service Element)
Publisher

Transport profile (T-profile):

ISO Transport over TCP (RFC 1006)


TCP/IP with TCP_KEEPALIVE implemented and a
Transport Selector of 4 bytes
ICMP, ARP
Publisher

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 5 (no specific time requirement but access


control is mandatory)

Services implemented:

LogicalNodeDirectory
GetAllDataValues

1.8.- Server
Application Association Model:

Two-party (client/server)

Application profile (A-profile):

MMS (Manufacturing Message Specification)


ACSE (Association Control Service Element)
Publisher

Transport profile (T-profile):

ISO Transport over TCP (RFC 1006)


TCP/IP with TCP_KEEPALIVE implemented and a
Transport Selector of 4 bytes
ICMP, ARP
Publisher

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 5 (no specific time requirement but access


control is mandatory)

Services implemented:

ServerDirectory

1.9.- Application Association


Application Association Model:

Two-party (client/server)

Application profile (A-profile):

MMS (Manufacturing Message Specification)


ACSE (Association Control Service Element)
Publisher

Transport profile (T-profile):

ISO Transport over TCP (RFC 1006)


TCP/IP with TCP_KEEPALIVE implemented and a
Transport Selector of 4 bytes

ICMP, ARP
Publisher
Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 5 (no specific time requirement but access


control is mandatory)

Services implemented:

Associate
Abort
Release

1.10.- Data
Application Association Model:

Two-party (client/server)

Application profile (A-profile):

MMS (Manufacturing Message Specification)


ACSE (Association Control Service Element)
Publisher

Transport profile (T-profile):

ISO Transport over TCP (RFC 1006)


TCP/IP with TCP_KEEPALIVE implemented and a
Transport Selector of 4 bytes
ICMP, ARP
Publisher

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 5 (no specific time requirement but access


control is mandatory)

Services implemented:

GetDataValues
SetDataValues
GetDataDirectory
GetDataDefinition

1.11.- Data Set


Application Association Model:

Two-party (client/server)

Application profile (A-profile):

MMS (Manufacturing Message Specification)


ACSE (Association Control Service Element)
Publisher

Transport profile (T-profile):

ISO Transport over TCP (RFC 1006)


TCP/IP with TCP_KEEPALIVE implemented and a
Transport Selector of 4 bytes
ICMP, ARP
Publisher

Physical medium:

100Base-Fx with MT-RJ connector

Performance class (according


to IEC 61850-5 section 13.7):

Type 5 (no specific time requirement but access


control is mandatory)

Services implemented:

GetDataSetValues
GetDataSetDirectory

2.- LOGICAL NODES


The following logical nodes shall be implemented:
2.1.- LPHD: Physical Device Information

2.2.- LLN0: Device Status

2.3.- GGIO: Generic Process Input/Output

2.4.- PSCH: Protection Scheme

In this Logical Node the variables LosOfGrd (Loss of Guard), GrdRx (Guard
received), SchTyp (Scheme Type) and OpDlTmms (Operate Delay Time) shall be
mandatory.
3.- DOCUMENTS AND FILES
The manufacturer of the Teleprotection IED shall provide at least the following
documents (according to IEC 61850-10);
-

ICD (IED Capability Description)


PICS (Protocol Implementation Conformance Statement)
PIXIT (Protocol Implementation Information for Testing)
TICS (Technical Issue Conformance Statement)

4.- ELECTROMAGNETIC COMPATIBILITY


The Teleprotection device shall comply with the following standards: ANSI C37.90.1
and ANSI C37.90.2.