Significant Changes

to the
Philippine Electrical Code
2009 Edition

Jaime V. Mendoza, MTM


Board Member

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

PEC 2009 (8th Edition)


BEE Resolution No. 12 Series of 2009
Adoption of the Revised (8th Edition)
Philippine Electrical Code Part I as Part of
the Rules and Regulations Concerning the
Practice of Electrical Engineering and as
Referral Code in Accordance with the
National Building Code Sept. 14, 2009.
Published in the Philippine Star last
February 18, 2010 (Thursday) page B-10
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

R. A. 7920
An Act For, A More Responsive and
Comprehensive Regulation For the Practice,
Licensing, and Registration of Electrical
Engineers and Electricians.
Sec. 4 Powers and Duties of the Board
The Board shall exercise executive
/administrative or quasi-legislative (rulemaking) or quasi-judicial (investigative)
powers in carrying out the provisions of
this Act.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

Powers of the Board


Sec. 29. Revocation of Certificates of
Registration and Suspension from the
Practice of the Profession.
The Board shall have the power, upon proper
notice and hearing, to revoke any certificate of
registration of any registrant, to suspend him
from the practice of the profession or to
reprimand him for any specified in the preceding
section, or for the use of perpetration of any
fraud or deceit in obtaining a certificate of
registration, or for gross negligence or
incompetence or for unprofessional or
dishonorable conduct, for violation of this Act, the
rules and regulations and other policies of the
Board and the Code of Professional Ethics.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

Licensing
Definition a permission granted by competent
authority to engage in a practice of profession or
business or in an activity.
A PEE who designed, signed, and sealed an electrical
plans means he/she guaranteed the safety of the
electrical plans for 15 years in accordance to Civil
Code.
PEE, REE or RME who signed as in-charge of
installations also guaranteed the safety of the
electrical installations for 15 years.
You can only guaranteed the safety of your electrical
designs/installations if you are well-versed in the
Philippine Electrical Code.
Licensing guarantees the safety
of your works!!!!
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

THE PHILIPPINE ELECTRICAL CODE


KEY TO SAFETY AND FIRE PREVENTION
PURPOSE OF PEC
The primary objective of the code is to
establish basic materials quality and electrical
works standards for the safe use of electricity
for light, heat, power, communications,
signaling and for other purposes.
Practical safeguarding of persons and
property from hazards arising from the use of
electricity
COMPLIANCE TO THE PEC WILL ENSURE SAFETY AND
PREVENT ELECTRICAL FIRES
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

The Philippine
Grid/Distribution
Codes
Performance
Standards

The Philippine
Electrical Code
Safety
Standards
Design and Specifications
Installation
Operation & Maintenance

Power Quality
Reliability
System Loss

GRID/DISTRIBUTION
DEVELOPMENT
PLANNING CRITERIA
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

THE PHILIPPINE ELECTRICAL CODE


The PEC is a safety standard,
not a design guide. Electrical
designs must comply with
the requirements of PEC to
ensure safety.
Energy management,
maintenance, and power
quality issues arent within
the scope of the PEC.
Consideration should be
given for future expansion
of electrical systems but this
is not a Code requirement.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

Philippine Electrical Code


Enforcement
1. This Code is intended for mandatory application
by government bodies exercising legal
jurisdiction over electrical installation.
2. These government bodies will have the
responsibility of implementing the provision of
this Code in deciding on the approval of
equipment and materials and for granting the
special permission contemplated in this Code,
where it assured that equivalent objectives can
be achieved by establishing and maintaining
effective safety.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

10

Philippine Electrical Code


Interpretation
Upon recommendation of the Code
Committee, the Board of Electrical
Engineering shall render the final
decision in the interpretation of any
portion of the Philippine Electrical
Code, in case of controversy.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

11

The National Electrical Code


The first documented case of a Code as a
requirement of rules was published on 16th Nov.
1881 entitled The Dangers of Electric Lighting.
The first NEC was developed in 1897, eighteen after
the invention of incandescent light bulb by Thomas
A. Edison.
Since 1911, the NFPA of Quincy, Massachussets, has
been responsible for the maintenance and
publication of the NEC.
Regularly revised (every three years) to reflect the
evolution of products, materials, and installation
techniques.
21 Separate Committee, each consisting of 15-20
persons. Members of each committee meet several
times, discuss proposed changes, accepting some
and rejecting others, and rewrite (as required) the
sections of the Code that were assigned to their
committee.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

12

THE PHILIPPINE ELECTRICAL CODE

Code Arrangement
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

13

THE PHILIPPINE ELECTRICAL CODE

CLASSIFICATION OF CODE
RULES
1. Wiring Design Rules
2. Installation Rules
3. Manufacturing Rules
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

14

THE PHILIPPINE ELECTRICAL CODE


CLASSIFICATION OF CODE RULES
Wiring design rules used to determine
sizes and rating of circuit conductors and
devices.
Example:
1. Branch circuit conductors supplying a single
motor shall have an ampacity not less than
125% of the full-load current. Section 4.30.2.2
2. The disconnecting means for motor circuits shall
have an ampere rating of at least 115% of the
full-load current rating of the motor. Section
4.30.10.10(a)
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

15

THE PHILIPPINE ELECTRICAL CODE


CLASSIFICATION OF CODE RULES
Installation rules
Example:
1. A disconnecting means shall be located within
sight from the motor controller. Section
4.30.102
2. In class II Division I Locations, motors,
generators,
and
other
rotating
electric
machinery shall be dust ignition proof or totally
enclosed pipe ventilated and shall be approved
for class II locations. Sections 5.02.8
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

16

THE PHILIPPINE ELECTRICAL CODE


CLASSIFICATION OF CODE RULES
Manufacturing rules
Example:
Section 4.30.1.7
A motor shall
information:

be

marked

with

the

following

1) Manufacturers Name
2) Rated Volts and Full-load Amperes
3) Rated Frequency and Number of Phases, if
an alternating current motor, etc.
4) Rated full-load speed
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

17

The Philippine Electrical Code

Various Categories of the Code Rules which apply in a Motor and the Circuits
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

18

ELECTRICAL FIRES
If a fault develops, the current (and heat energy)
can increase to the extent that either the appliance
burns out, the connecting wiring overheats and
melts the plastic insulation or the plug and socket
may burn out.
An electrical fire then occur where the overheated
wiring, motor, plug, etc. are in contact with or close
to flammable or combustible material.

ELECTRICAL FIRE can be defined as a fire


where an electric current or electrical fault
is found to have been the source of ignition.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

19

Components that Create a Fire or


Explosion

combustion

Triangle of Fire

Very Significant on PEC Installation Rules!!!


BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

20

Significant Changes to the


Philippine Electrical Code 2009 Edition
Regularly revised (every three years) to
reflect the evolution of products, materials,
and installation techniques.
21 Separate Committee, each consisting of
15-20 persons. Members of each committee
meet several times, discuss proposed
changes, accepting some and rejecting
others, and rewrite (as required) the
sections of the Code that were assigned to
their committee.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

21

Change Type in the PEC 2009


1. New
2. Revision
3. Relocated
4. Reorganization
5. Universal Change
6. Deletion (310.5)

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

22

New - Definitions
AHJ Authority Having Jurisdiction
Bonding Jumper, System
Coordination (Selective)
Electrical Practitioner, Licensed
Electrical Practitioner, Non-Licensed
Guest Rooms
Guest Suite
Handhole Enclosure
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

23

Guest Room

An accommodation combining living, sleeping,


sanitary and storage facilities.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

24

Guest Suite

An accommodation with two or more contiguous rooms


comprising a compartment, with or without doors between
such rooms, that provides living, sleeping, sanitary, and
storage facilities.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

25

New Provision
PEC 2.10.1.5 (c) Identification for Branch
Circuits, page 69
(c) Ungrounded Conductors
Where the premises wiring system has branch
circuits supplied from more than one nominal
voltage system, each ungrounded conductor of a
branch circuit, where accessible shall be
identified by system. The means of identification
shall be permitted to be by separate color
coding, marking tape, tagging, or other
approved means and shall be permanently
posted at each branch-circuit panelboard or
similar branch-circuit distribution equipment.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

26

PEC 2.10.1.5 (c) Identification for Branch


Circuit for Ungrounded Conductors

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

27

New Provision
2.10.1.8(b)(2) GFCI
Protection Other than
Dwelling
Commercial and
institutional kitchens
for the purposes of this
section, a kitchen is an
area with a sink and
permanent facilities for
food preparation and
cooking. (Culinary
Schools)

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

28

New Provision
2.10.1.8(b)(4) GFCI
Protection Other than
Dwelling
Outdoor in Public
Spaces for the
purpose of this section
a public space is
defined as any space
that is for use by, or is
accessible to the
public.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

29

New Provision
2.10.1.8(b)(5) GFCI
Protection Other than
Dwelling
(5)Outdoor , where
installed to comply with
2.10.3.14 Heating, Airconditioning, and
Refrigeration Outlet

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

30

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

31

New Provision
2.10.1.8(c)Boat Hoists
GFCP for personnel
shall be provided for
outlets that supply
boat hoists installed in
dwelling unit locations

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

32

2.10.1.8 GFCI Protection for


Personnel
b) Other than Dwelling Units
1) Bathrooms*
2) Commercial and institutional kitchens
3) Rooftops*
4) Outdoors in public spaces
5) Outdoors, where installed to comply with
2.10.3.14

* Including in PEC 2000

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

33

GFCI Protection for Personnel


PEC-2.10.1.8 (a)
a) Dwelling Units
1. Bathrooms
2. Garages
3. Outdoors
4. Crawl spaces at or
below grade level
5. Unfinished
basements
6. Kitchens for
countertop
appliances
7. Wet bar sinks
8. Boathouses (New Provision)
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

34

New Provision
2.10.1.12.Arc-Fault
Circuit Interrupter
Protection
(b) Dwelling Unit
Bedrooms All single
phase, 15 and 20 A
branch circuits supplying
outlets installed in
dwelling unit bedrooms
shall be protected by a
listed AFCI. Combination
type installed to provide
protection of the branch
circuit.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

35

Arc-Fault Circuit Interrupter

An AFCI is a device intended to open the circuit when


it detects the current waveform characteristics that are
unique to an arcing fault.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

36

AFCI

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

37

Ground Fault Circuit Interrupter

A GFCI is designed to protect persons against electric shock.


It operates on the principles of monitoring the unbalanced current
Between the ungrounded and the grounded neutral conductor.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

38

New Provision

p88
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

39

Revised - Definition
Dwelling Unit one or more rooms for
the use of one or more persons as a
housekeeping unit with space for eating,
living, sleeping, and permanent
provisions for cooking and sanitation. PEC
2000
Dwelling Unit a single unit, providing
complete and independent living facilities
for one or more persons, including
permanent provisions for living, sleeping,
cooking, and sanitation. (PEC 2009)
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

40

Revised - Definition
2.10.1.8(a)(8)

GCFI Protection

Laundry, utility, and wet bar sinks


where the receptacles are installed to
serve the countertop surfaces and are
located within 1.8 m (6 ft) of the outside
edge of the sink.
Laundry, utility, and wet bar sinks
where the receptacles are installed within
1.8 m (6 ft) of the outside edge of the
sink.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

41

GFCI Protection for Personnel


7. Dwelling Wet Bar Sinks

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

42

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

43

Revised - Definition
Garage a building or portion of a
building in
which one or more self-propelled vehicles
carrying volatile flammable liquid, for fuel or
power are kept for use, sale, storage, rental,
repair, exhibition, or demonstrating purposes,
and all that portion of a building that is on or
below the floor or floors in which such vehicles
are kept and that is not separated there from by
suitable cutoffs.
Garage A building or portion of a building in
which one or more self-propelled vehicles can be
kept for use, sale, storage, rental, repair,
exhibition, or demonstration purposes.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

44

Relocated -Definition
Solidly Grounded PEC 2000
Grounded, Solidly PEC 2009

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

45

2.1.1.6(b) Means of Identying


Grounded Conductors PEC-2000
(b)
Sizes Larger than 14 mm2. An
insulated rounded conductor larger than
14 mm2 shall be identified either by a
continuous white or natural gray outer
finish or by three continuous white stripes
on other than green insulation along its
entire length or at the time of installation
by a distinctive white marking at its
terminations. This marking shall encircle
the conductor or insulation.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

46

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

47

2.1.1.6(b) Means of Identying


Grounded Conductors PEC-2009
Sizes Larger Than 14 mm2. An insulated
conductor larger than 14 mm2 shall be
identified by one of the following means:
1) By a continuous white or gray cover finish.
2) By three continuous white stripes along its
entire length on its entire length on other
than green insulation
3) At the time of installation, by a distinctive
white or gray marking at its terminations.
This marking shall encircle the conductor or
insulation.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

48

Section 2.0.1.6 (a)

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

49

2.1.1.6(d) Means of Identifying


Grounded Conductors PEC-2000
(d) Grounded
Conductors
of
Different
Systems. Where conductors of different
systems are installed in the same raceway,
cable, box, auxiliary gutter, or other type of
enclosure, one system grounded conductor, if
required, shall have an outer covering
conforming to Section 2.1.1.6(a) or (b). Each
other system grounded conductor shall have an
outer covering of white with a readily
distinguishable different colored stripe (not
green) running along the insulation, or other and
different means of identification as allowed by
Section 2.1.1.6(a) or (b) that will distinguish
each system grounded conductor.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

50

2.1.1.6(d) Means of Identifying


Grounded Conductors PEC-2009
(d) Grounded Conductors of Different Systems. Where grounded
conductors of different systems are installed in the same raceway,
cable, box, auxiliary gutter, or other type of enclosure, each grounded
conductor shall be identified by system. Identification that distinguishes
each system grounded conductor shall be permitted by one of the
following means:
(1) One system grounded conductor shall have an outer
covering
conforming to 2.0.1.6(a) or 2.0.1.6(b).
(2) The grounded conductor(s) of other systems shall have a
different outer covering conforming to 2.0.1.6(a) or 2.0.1.6(b) or by an
outer covering of white or gray with a readily distinguishable colored
stripe other than green running along the insulation.
(3) Other and different means of identification as allowed by
2.0.1.6(a) or 2.0.1.6(b) that will distinguish each system grounded
conductor.
This means of identification shall be permanently posted at each
branch-circuit panelboard.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

51

An Example of Conductor
Color Coding

Phase A

120/240
V, Single
Phase
Black

208Y/120 480Y/277V, ThreeV, ThreePhase


Phase
Black
Brown

Phase B

Red

Red

Orange

Blue

Yellow

White with
red Stripe

Gray

Phase C
Neutral

White

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

52

Section 2.0.1.6 (d) (1)

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

53

Mixing Grounded Neutral Conductors


Different System Sec. 2.0.1.6(d)(2)

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

54

Section 2.0.1.7(c)

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

55

Branch Circuits
A. Tamper-Resistant Receptacles in
Dwellings Unit (406.11) (NEC-2008)
Why do you think it is a tamperresistant receptacle?

..To increase safety for children.

..maybe that your son, daughter, or


grandchildren that you will save

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

56

Branch Circuits
A. Tamper-Resistant Receptacles in
Dwellings Unit (406.11) (NEC-2008)

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

57

Reorganization Article 2.20


Branch-Circuit, Feeder, and Service Calculations
2000 Article 2.20
Part

2009 Article 2.20


Sections

Part

Sections

I. General

2.20.1.1- 4

I. General

2.20.1.1 -5

II. Feeders and


Services

2.20.2.1 - 14

II. Branch Circuit 2.20.2.1 - 7


Load Calculations

III. Optional
2.20.3.1 - 7
Calculations for
Computing Feeder
and Service Loads

III. Feeder and


Service Load
Calculations

2.20.3.1 - 23

IV. Method for


2.20.4.1 - 2
Computing Farm Loads

IV. Optional Feeder2.20.4.1 - 9


And Service Load
Calculations
V. Farm Calculation 2.20.5.1- 4

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

58

Universal Change
A universal change throughout the 2009
PEC is the replacement of computed
load and demand load with calculated
load. For example, the term demand
load is being replaced with calculated load
to improve clarity and to reduce
confusion, especially when related to
calculated load and demand factor.
The term calculated load includes demand
factor, the concepts of diversity, and
historical data.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

59

2.30.6 Service Equipment


Disconnecting Means
a) Location
a) Readily Accessible Location. The service
disconnecting means shall be installed at a
readily accessible location of a building or a
structure. For a building, the service
disconnecting means shall be installed either
at the outside wall or inside nearest point of
entrance of the service conductors to the
building.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

60

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

61

2.30.6 Service Equipment


Disconnecting Means
a) Location
2) Bathrooms. Service disconnecting means
shall NOT be installed in bathrooms.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

62

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

63

Article 2.50 Grounding


and Bonding
The title of Article 2.50 has been changed from
Grounding to Grounding and Bonding.
Change Significance: The scope of the article
clearly covers both grounding and bonding.
Adding the term bonding to the title of the
article is appropriate, and is consistent with the
fact that there are generally as many bonding
requirements and provisions included within
Article 2.50 as there are grounding
requirements, if not more.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

64

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

65

2.50.1.2 Definitions (Revision)


Effective Ground-Fault Current Path An
intentionally constructed, permanent, low
impedance electrically conductive path
designed and intended to carry current
under ground-fault conditions from the
point of a ground fault on a wiring system
to the electrical supply source and that
facilitates the operation of the
overcurrent protective device or groundfault detectors on high-impedance
grounded systems.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

66

Effective Ground-Fault Current Path

Metal parts of premises wiring are bonded to an effective


ground-fault current path that has sufficiently low impedance
to quickly clear line-to-case faults by opening the circuit
protection device.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

67

Effective Ground-Fault Current Path

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

68

Effective Ground-Fault Current Path

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

69

Earth is Not an Effective GroundFault Current Path

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

70

2.50.1.2 Definitions
Ground Fault- An unintentionally, electrically
conducting connection between an ungrounded
conductor of an electrical circuit and the
normally non-current-carrying conductors,
metallic enclosures, metallic raceways, metallic,
or earth.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

71

2.50.1.2 Definitions
Ground-Fault Current
Path- An electrically
conductive path from
the point of ground
fault on a wiring
system through
normally noncurrent-carrying
conductors,
equipment, or the
earth to the electrical
supply source.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

72

Article 2.50
2.50.2.5(b) Main Bonding Jumper
2.50.2.11 Grounding Separately Derived
Alternating-Current Systems
2.50.2.13 Buildings or Structures Supplied by
Feeder(s) or Branch Circuit(s)
2.50.3 Grounding Electrode System and
Grounding Electrode Conductor
2.50.10 Grounding of Systems and Circuits of 1
kV and Over (High Voltage)
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

73

3.10.1.4 Conductors in Parallel


The paralleled conductors in each phase,
polarity, neutral, or grounded circuit
conductor shall comply with all the
following:
1. Be the same length
2. Have the same conductor material
3. Be the same size in circular mil area
4. Have the same insulation type
5. Be terminated in the same manner.
Why??????
.. See FPN:
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

74

3.10.1.5 Minimum Size of Conductors


The minimum size of conductors shall be
as shown in Table 3.10.1.5, except as
permitted elsewhere in this Code.
Removal of 10 previous exceptions were
not needed

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

75

3.10.1.6 Shielding
In this sections exception, the voltage
has been reduced from 8 kV to 2.4 kV for
use of unshielded conductors. Cables
operated at a voltage higher than 2.4 kV
will now be required to be shielded.
Many cable manufacturers specifically
recommend against the use of nonshielded cable above 2 kV because of
arcing problems and cables without
shielding have a very high failure rate.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

76

3.10.1.8 Locations
d) Locations Exposed to Direct Sunlight. Insulated
conductors and cables used where exposed to
direct rays of the sun shall comply with one of
the following: (be of a type listed for sunlight
resistance or listed and marked sunlight
resistant)
1) Cables listed, or listed and marked , as being sunlight
resistant
2) Conductors listed, or listed and marked , as being
sunlight resistant
3) Covered with insulating material, such as tape or
sleeving, that is listed and marked ,as being sunlight
resistant.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

77

3.10.1.10 Temperature Limitation


of Conductors
The PEC 2009 has added a new Fine Print
Note with information on derating for
conduits on rooftops that have direct
sunlight exposures; 17C is the indicated
value to be added to the outdoor ambient
temperature to compensate for the direct
solar gain.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

78

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

79

3.10.1.15(b)(2) Adjustment Factors


A new last sentence has been added to
3.10.15(b)(2)(a) to require that individual
conductors of paralleled sets be counted as
current-carrying conductor. This is intended to
clarify varying interpretations of whether each
conductor of a paralleled set of conductors is
required to be counted individually or if all of the
conductors count as one for the purpose of
derating. Clearly, each conductor of the parallel
set is required to be counted individually for the
purposes of rating.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

80

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

81

Configuration

All conductors
in single
conduit

Conductor if
Neutral is
Counted

Derating
Percentage

Conductors
if Neutral is
Not Counted

12

All conductors
in metal
wireway or
auxiliary gutter

12

All conductors
in nonmetallic
wireway or
auxiliary gutter

12

4 conductors in
3 conduits or
cables

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Derating
Percentage

Significant Changes to the


Philippine Electrical Code 2009

82

Table 3.10.1.15(b)(2)(a) Adjustment Factors for More than Three CurrentCarrying Conductors in a Raceway or Cable

Number of CurrentCarrying Conductors

Percent of Values in Tables 3.10.1.16


Through 3.10.1.19 as Adjusted for
Ambient
Temperature if Necessary

46
79
10 20
21 30
31 40
41 and above

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

80
70
50
45
40
35

Significant Changes to the


Philippine Electrical Code 2009

83

Configuration

All conductors
in single
conduit
4 conductors in
3 conduits or
cables

Conductor if
Neutral is
Counted

12

Derating
Percentage

Conductors
if Neutral is
Not Counted

Derating
Percentage

50

70
Not

80

Not

required

All conductors
in metal
wireway or
auxiliary gutter

12

required

required

All conductors
in nonmetallic
wireway or
auxiliary gutter

12

50

70

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Not

Significant Changes to the


Philippine Electrical Code 2009

84

Section 3.10.1.15(b)(4)
(4) Neutral Conductor.
a) A neutral conductor that carries only the unbalanced current
from other conductors of the same circuit shall not be required
to be counted when applying the provisions of
Section3.10.1.15(b)(2)(a).
b) In a 3-wire circuit consisting of two phase wires and the
neutral of a 4-wire, 3-phase wye-connected system, a common
conductor carries approximately the same current as the lineto-neutral load currents of the other conductors and shall be
counted when applying the provisions of Section
3.10.1.15(b)(2)(a).
c) On a 4-wire, 3-phase wye circuit where the major portion of the
load consists of nonlinear loads, harmonic currents are
present in the neutral conductor; the neutral shall therefore be
considered a current-carrying conductor.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

85

Notes
For metal auxiliary gutters, 3.66.2.14(a)
indicates that derating is not required so long as
the number of current-carrying conductors at
any cross section does not exceed 30. A similar
statement is included for sheet metal wireways
in 3.76.2.13.
Derating for the number of current-carrying
conductors in non-metallic auxiliary gutters and
wireways is required, beginning at four-current
carrying conductors, because conductors in nonmetallic enclosures do not dissipate heat as well
as those in sheet-metal enclosures.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

86

Introduction
Art. 6.95 contains many requirements to
keep that supply of water uninterrupted.
For example:
1. Locating the pump so as to minimize its
exposure to fire.
2. Ensuring that the fire pump and its jockey
pump have a reliable source of power.
3. It makes sense to keep fire pump wiring
independent.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

87

Introduction
Other requirements seem wrong at first
glance, until you remember why the fire
pump is there in the first place.
For example:
1. The disconnect must be lockable in the
closed position.
2. Fire pumps power circuits cannot have
automatic protection against overload.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

88

Introduction
Its better to run the fire pump until
its winding melt, than to save the fire
pump and lose the facility
And the intent of Article 6.95 is to
save the facility.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

89

6.95.1.1 Scope
a) Covered
1) Electric power sources and interconnecting
circuits
2) Switching and control equipment dedicated
to fir pump drivers
b) Not Covered
1) The performance, maintenance, and
acceptance testing of the fire pump system,
and the internal wiring of the components
of the system
2) Pressure maintenance (jockey or makeup)
pumps
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

90

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps
a) Individual Source
1) Electric Utility Service. A separate
service from a connection located ahead
of but not within the service
disconnecting means.
2) On-Site Power. An on-site power supply,
such as generator, located and
protected to minimize damage by fire is
permitted to supply a fire pump.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

91

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps

a) Electric-Utility Service Connection


BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

92

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps

a) Electric-Utility Service Connection


BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

93

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps

2) On-Site Power Production Facility


BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

94

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps
b) Multiple Sources
1) Generator Capacity. Shall have
sufficient capacity to allow normal
starting and running 0f the motor(s)
driving the fire pump(s) while supplying
other simultaneously operated load.
2) Feeder Sources.
3) Arrangement. The power sources shall
be arranged so that a fire at one will not
cause an interruption at the other
source.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

95

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps

2) Feeder Sources
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

96

6.95.1.5 Transformers
Dedicated transformer and overcurrent
protection sizing can be broken down into
three requirements.
1. The transformer must be size to at least 125%
of the sum of the loads.
2. The transformer primary overcurrent device
must be at least a specified minimum size.
3. The transformer secondary must not contain any
overcurrent device whatsoever.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

97

6.95.1.5 Transformers

The overcurrent device in the primary of a transformer supplying


a fire pump installation. The device is required to be sized to carry
the locked-rotor current motor(s) and associated fire pump
accessory equipment indefinitely.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

98

6.95.1.6 Power Wiring


a) Service and Feeder Conductors.
Supply conductors must be
physically routed outside buildings
and must be installed in accordance
with Article 2.30. Where supply
conductors cannot be routed outside
buildings, they must be encased in 2
inches or 50 mm of concrete or brick.

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

99

6.95.1.6 Power Wiring


b) Circuit Conductors.
Fire pump supply conductors on the load
side of the final disconnecting means and
overcurrent device(s) must be kept entirely
independent of all other wiring. They can
be routed through a building using one of
the following methods:
1) Be encased in a minimum 2 inches or 50 mm of
concrete
2) Be within an enclosed construction dedicated to
the fire pump circuit(s) and having a minimum
of a 1-hour fire-resistant rating
3) Be listed electrical circuit protective system with
a minimum 1-hour fire rating.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

100

6.95.1.6(c)(2) BC Conductor Size


Fire Pump Motor
Branch Circuit Conductor Size
From Table
4.30.14.5(b)

Branch circuit conductors to a single fire pump


motor must have a rating not less than 125% of the
motor
FLC as listed in Table 4.30.14.2 or 4.30.14.4
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

101

6.95.1.7 Voltage Drop

The voltage drop at the line terminals of the controller


when the motor starts (locked-rotor current), must not
drop more than 15% below the controllers rated voltage.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

102

6.95.1.7 Voltage Drop


Fire Pump Conductor Size Voltage Drop

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

103

6.80 Swimming Pools, Fountains,


and Similar Installations
Article 6.80 - applies to decorative pools
and fountains; swimming, wading, and
wave pools; therapeutic tubs and tanks;
hot tubs; spas; hydromassage bathtubs;
and similar installation including pools
used in religious services where
participants are immersed in water. The
installations covered by this article can be
indoors or outdoors, permanent or
storable, and may or may not be directly
supplied by electrical circuits of any
nature.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

104

6.80.1.2 Definitions

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

105

6.80.1.2 Definitions

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

106

6.80.1.3 Other Articles

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

107

6.80.1.8 Overhead Conductor Clearance

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

108

6.80.1.8 Overhead Conductor Clearance

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

109

6.80.1.12 Maintenance Disconnecting Means

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

110

6.80.2 Permanently Installed Pools

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

111

6.80.2 Permanently Installed Pools

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

112

6.80.2.3(a)(4) Restricted Space

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

113

6.80.2.3(a)(5) GFCI Protection

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

114

6.80.2.3(a)(5) GFCI Protection

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

115

6.80.2.3(a)(5) GFCI Protection

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

116

4.11.1.4(b) Lighting Systems


Operating at 30 V or less

10 ft = 3 m

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

117

6.80.2.3(b) Luminaires

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

118

6.80.2.4(a)(4) Underwater Luminaires

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

119

6.80.2.4(f) Branch-Circuit Wiring

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

120

6.80.2.7 Equipotential Bonding

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

121

6.80.2.7 Equipotential Bonding

Bonding of conductive metal parts in a swimming pool.


BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

122

6.80.4.2 Emergency Switch for


Spas and Hot tubs

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

123

6.80.4.4 Indoor Installations of


Spas and Hot Tubs

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

124

6.80.4.5 GFCI Protection

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

125

6.80.5 Fountains

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

126

6.80.7 Hydromassage bathtubs

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

127

6.82 Natural and Artificially Made


Bodies of Water (New Article)

An artificially made of body of water. The electrical equipment


associated with pumps used to circulate water in this artificial
pond is subject to the requirements of Article 6.82.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

128

Definitions
Artificially Made of Bodies of Water Bodies of
water that have been constructed or modified to
fit some decorative or commercial purpose such
as, but not limited to, aeration ponds, fish farm
ponds, storm retention basins, treatment ponds,
irrigation (channel) facilities. Water depths may
vary seasonally or be controlled.
Natural Bodies of Water Bodies of water such
as lakes, streams, ponds, river, and other
naturally occuring bodies of water, which may
vary in depth throughout the year.
BOARD OF ELECTRICAL ENGINEERING
PROFESSIONAL REGULATION COMMISSION

Significant Changes to the


Philippine Electrical Code 2009

129

Thank You !!!!


&