Vous êtes sur la page 1sur 3

KIP: SES & WES Preliminary Design Approval Check List

2016.06.16
S.NO

DESCRIPTION

CLIENT SPECIFICATION

ELECTRICAL
1

S/S
1 1 Capacity
1.1
1.2 Voltage Level
1.3 Power Factor compensator VAR

50MW
132 or 230/33kV
8MVAR

Power House
2.1 Transformer for shade

2.1.1 Min.Transformer for 3,000sq.mm

315kVA

2.1.2 Min.Transformer for 5,500sq.mm

800kVA

2.1.3 Min.Transformer for 11,000sq.mm

630kVA

2.2 Transformer for comm & admin bldg


2.2.1 Full load Capacity
3

Power Distribution
3.1 MV distribution

33kv

3.2 LV distribution

0.6/1kv

Power Distribution Boards


3.1 Electrical Board for shade

3.1.1 LTG PDB

categorized
With Data Logger For Power Quality
Control And Monitoring

3.1.2 General Socket PDB

ditto

3.1.3 UPS Socket PDB

ditto

3.2 Electrical Board for comm & admin


3.2.1 LTG PDB

categorized
With Data Logger For Power Quality
Control And Monitoring

3.2.2 General Socket PDB

ditto

3.2.3 UPS Socket PDB

ditto

Power socket
4.1 Power socket for shades

one normal and 2 ups per 6sqm


except the production area

4.2 Power socket for comm & admin

one normal and 2 ups per 6sqm

Lighting
5 1 LTG for shades
5.1

5.1.1 General Purpose lighting

300lux

5.1.2 Office Lighting

400Lux

5.1.3 Florescent light fittings


5.2 LTG for comm & admin bldg
5.3 Perimeter Ltg
5.4 Road Ltg
7

T5
LED, Louvered, ip 65, prismatic
30Lux
30Lux, LED

Cable Tray & Conduit


6.1
6 1 conduit
d it for
f shades
h d

steel
t l

6.2 Cable Tray/Ladder


8

Emergency Power System


7.1 Generator for Comm & admin bldg
7.2 UPS for comm & admin bldg

75%
30min, 100% load

7.3 Shade emergency LTG

30Min EL With Battery Shall Be Adopted


For Each Shade.

7.4 Shade Generator & UPS

Provision for Generator & UPS by


Tenants

PROPOSED BY
CONTRACTOR

COMPLY
STATUS

REMARK

S.NO
9

DESCRIPTION

CLIENT SPECIFICATION

PROPOSED BY
CONTRACTOR

Cabling system

9.1

33kV Cable system for external Power


Distribution

9.2

Cable system for Internal Distribution

10

PVC Sheathed With XLPE Insulated


Armored
Pvc Sheathed And Pvc Insulated
Cable 0.6/1Kv Insulation

Lightning & Grounding system


9.1 For shades

5ohm & 10ohm

9.2 For comm & admin bldg

5ohm & 10ohm

11

Site Duct and Man hall

10.1 Cable Duct


12

Electric Fence

13

Electric Utility Meter

13 1 kWH metering
t i
ffor shades
h d
13.1

Concert with steel cover for manholes

I di id l
Individual

WEAK ELECTRIC SYSTEM


Factory automation & energy saving
system

1.1 One card system


1.1.1 AC, AM, PM & CM
1.1.2 Centralized card issuing system

One Card for four system


with full software and accessories

1.2 ECS
1.3 LCS
1.4 MFCS
2

Telecommunication system
2.1 SCS

2.1.1 Dual Gang Data/telephone outlet


2.1.2 Horizontal cabling
g for indoor
2.1.3 Back Bone Cabling

One Telecom Outlet per 6SQM except


production area
Cat6
MM FO cable

2.1.4 Back Bone cabling for site Data ntk

Outdoor SM Approved specification as


per Ethiotelecom requirements

2.1.5 Back Bone cabling for site Voice ntk

Outdoor multi core Jelli filled copper


cable approved type as per
Ethiotelecom requirements

2.2 PBX

Digital PBX system with type approved


as per ethiotelecom requirements

2.3 LAN
2.4 Wireless ntk system

Park wirless LAN for employees, visitors


& related personnel,

2.5 CATV
2.5.1 TV Video source
2.5.1 TV distribution

Satellite TV & Local TV via UHF/VHF


antenna
Cable TV distribution network

2.6 Digital PA
2.7

Public telephone & Telephone


Booth

2.7.1 BGM, paging and evacuation system


3

Security
3.1 CCTV

2189

Digital Integrated Voice system for


shade & commercial bldg with
convenient number of zones.

801 Analogue Telephone


lines & expandable to
1200 lines

COMPLY
STATUS

REMARK

S.NO

DESCRIPTION

3.1.1 Type
3.1.2 Minimum storage capacity

3.1.3 Area to be covered

3.1.4

Centralized Monitoring station at one


stop service bldg

3.1.5 Separate
Management
station
p
g

CLIENT SPECIFICATION
Digital, integrated security &
protection system interfaced with AC
& FA system
30 Days
Admin & com bldg Important areas,
Main Road intersection, Main Entrance
& exit, Perimeter Fence

All the camera shall be real-time


monitored all at the same time on a
fixed wall mount Monitoring screen
Duty room/guard room at each
building

3.2 VACS
3.2.1 Main Gate
3.2.2 Logistic Gate

Security Mgt of VAC & Truck Charring


system
ditto

3.3 AC & AM
3.3.1 For all comm & Office Bldg

One machine for AC & AM system,


convinet location & qty shall be
adopted

3.4 IAS
3.6.1 Perimeter IAS
4

Electronic Railing with central


monitoring station via electronic map
& management software

Safety
4.1 FA

4.1.1 FA for shades

per Chinese standards


As p

4.1.2 FA for commercial bldgs

As per Chinese standards

4.1.3 Centralized monitoring station


5

Integrated site Pipe work

5.1.1

Manholes

5.1.2

Telecom integrated ntk PVC pipe line

concrete MH with Cast Iron cover &


Should Be Labeled In English
Si and
Size
d type
t
shall
h ll SSatisfy
ti f reserve
requirement for phase-I and later
phases and shall comply ET
requirements

Data Center and Disaster Recovery


6.1 Data Center and Disaster Recovery

at one stop service in the FA ctrl room

Room Space and provision pipe line

Service
provider
S
i
id SPC exchange
h
7.1 Service provider SPC exchange

Room Space and provision pipe line

PROPOSED BY
CONTRACTOR

COMPLY
STATUS

REMARK

Vous aimerez peut-être aussi