Vous êtes sur la page 1sur 4

Full Hydraulic Calculations Computer Printout Page No 1

Submitted by user number 1502


AIM TECH LTD

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Source:
Printout:

Tel: Fax:

Union Accessories
Mouza. Tayobpur. Savar. Dhaka
ESL_HY_300715
Most Unfavourable
ordinary
National Fire Protection Association
2871.5 l/min @ 6.677 bar
12-July-16 at 15:13

Project Data and Design Parameters


Project name
Area reference
Address / location
Project number
Installation number(s)
Drawing number(s)
Issue no / date
Designers reference
Project Data File
Hazard classification
Design authority
Insurance company
Specified density of discharge
Assumed maximum area of operation
Number of operating sprinkler heads
Maximum area covered per head
Highest head / nozzle above source
Number of pipes in system
Pressure loss equation used
Fluid
Pipe Data Table
Maximum fluid velocity
Volume of pipework and fittings
Elbows are welded for
Comment
Checked by & Date

:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:

Union Accessories
Most Unfavourable
Mouza. Tayobpur. Savar. Dhaka
ESL_HY_300715
01
------\\AIM-TECH-SERVER\Aimtech_Shaired_Files\AIMTEC~1\PR
ordinary
National Fire Protection Association
--0.00 mm/min (l/min/m2)
0.00 m2
3
0.00 m2
0.00 m
22
from 65 to 200 mm
Hazen-Williams
Water
STD_PIPE.PDT
4.34 m/s in pipe 117 119
1.62 m3
65
mm and above
---

Source duty = 2871.5 l/min @ 6.677 bar at node no 100

FHC - Hydraulic Analysis Software - Ver: 1.8.2


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com

Program FHC

Full Hydraulic Calculations Computer Printout Page No 2


Submitted by user number 1502
AIM TECH LTD

Tel: Fax:

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Source:
Printout:

Union Accessories
Mouza. Tayobpur. Savar. Dhaka
ESL_HY_300715
Most Unfavourable
ordinary
National Fire Protection Association
2871.5 l/min @ 6.677 bar
12-July-16 at 15:13

Operating Sprinkler Heads, Nozzles and Hydrants


Head|Node| Size | 'K' |F l o w|A
no | no | mm | factor| l/min |
1 121
445.95
963.8
2 125
445.95
946.0
3 135
445.95
961.7

r e a|Density mm/min|Pressure bar|Heights|Pipe


m2 |Req.d
Actual| Min
Actual|
m
| no
0.000
0.00
0.00
4.50
4.671 14.500
11
0.000
0.00
0.00
4.50
4.500 17.700
13
0.000
0.00
0.00
4.50
4.651 17.700
18

0 heads are under the required density / minimum pressures

FHC - Hydraulic Analysis Software - Ver: 1.8.2


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com

Program FHC

Full Hydraulic Calculations Computer Printout Page No 3


Submitted by user number 1502
AIM TECH LTD

Tel: Fax:

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Source:
Printout:

Union Accessories
Mouza. Tayobpur. Savar. Dhaka
ESL_HY_300715
Most Unfavourable
ordinary
National Fire Protection Association
2871.5 l/min @ 6.677 bar
12-July-16 at 15:13

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size
Type| L/min | Length VJ|Dir. | Eq.len | Start | Start
Frict
no | End |Bore
'C'| Vel m/s |EL T
VT|Slope| mbar/m |
End | End
Static
1 100 200mm
MW
2871.5
1.000
Up
15.96
0.000
6.677 -0.018
101 206.40 120
1.4
0 0
MV 90.0
1.1
1.000
6.561 -0.098
2 101 200mm
MW
2871.5
2.700
0
7.02
1.000
6.561 -0.008
103 206.40 120
1.4
1 0
0.0
1.1
1.000
6.553 +0.000
3 103 150mm
MW
1909.8
3.280
270
12.79
1.000
6.553 -0.028
105 155.32 120
1.7
0 1
0.0
2.2
1.000
6.525 +0.000
4 105 150mm
MW
1909.8
5.250
180
8.10
1.000
6.525 -0.017
107 155.32 120
1.7
1 0
0.0
2.2
1.000
6.508 +0.000
5 107 150mm
MW
1909.8
7.630
270
10.48
1.000
6.508 -0.023
109 155.32 120
1.7
1 0
0.0
2.2
1.000
6.485 +0.000
6 109 150mm
MW
1909.8
18.680
180
21.53
1.000
6.485 -0.046
111 155.32 120
1.7
1 0
0.0
2.2
1.000
6.439 +0.000
7 111 150mm
MW
1909.8
19.120
90
21.97
1.000
6.439 -0.047
113 155.32 120
1.7
1 0
0.0
2.2
1.000
6.391 +0.000
8 113 150mm
MW
1909.8
1.130
0
3.98
1.000
6.391 -0.009
115 155.32 120
1.7
1 0
0.0
2.2
1.000
6.383 +0.000
9 115 100mm
MW
1909.8
13.500
Up
15.59
1.000
6.383 -0.225
117 105.14 120
3.7
1 0
90.0
14.4
14.500
4.835 -1.322
10 117
65mm
MW
963.8
0.300
90
5.05
14.500
4.835 -0.164
119
68.67 120
4.3
0 1
0.0
32.4
14.500
4.672 +0.000
11 119
65mm
MW
963.8
0.010
90
0.01
14.500
4.672 -0.000
121
68.67 120
4.3
0 0
0.0
29.5
14.500
4.671 +0.000
12 117 100mm
MW
946.0
3.200
Up
3.20
14.500
4.835 -0.013
123 105.14 120
1.8
0 0
90.0
3.9
17.700
4.509 -0.313
13 123 100mm
MW
946.0
0.300
90
2.39
17.700
4.509 -0.009
125 105.14 120
1.8
1 0
0.0
3.9
17.700
4.500 +0.000
14 103 150mm
MW
961.7
2.050
90
11.56
1.000
6.553 -0.007
127 155.32 120
0.8
0 1
0.0
0.6
1.000
6.546 +0.000
15 127 150mm
MW
961.7
4.630
180
7.48
1.000
6.546 -0.005
129 155.32 120
0.8
1 0
0.0
0.6
1.000
6.541 +0.000
16 129 150mm
MW
961.7
0.740
90
3.59
1.000
6.541 -0.002
131 155.32 120
0.8
1 0
0.0
0.6
1.000
6.539 +0.000
17 131 100mm
MW
961.7
16.700
Up
18.79
1.000
6.539 -0.076
133 105.14 120
1.8
1 0
90.0
4.1
17.700
4.827 -1.636
18 133
65mm
MW
961.7
0.710
90
5.46
17.700
4.827 -0.176
135
68.67 120
4.3
0 1
0.0
32.3
17.700
4.651 +0.000

FHC - Hydraulic Analysis Software - Ver: 1.8.2


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com

Program FHC

Full Hydraulic Calculations Computer Printout Page No 4

MV

100

MRH

FHC - Hydraulic Analysis Software - Ver: 1.8.2


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com

Program FHC

Vous aimerez peut-être aussi