Now it's time to use what we've learned in this column over the last several issues
and calculate the service load for feeders No. 1 through No. 6 in our hypothetical
industrial plant. See the April and May 2001 articles for amperage values of feeders
No. 1 through No. 6. Refer to the Figure for a one-line diagram of the electrical
equipment.
When computing the load for an existing electrical system or when designing an
entirely new system an important tool is a good, up-to-date line diagram of the
system.
Step 1: Calculate the amps of each feeder and the total load [Sec. 220-2(a)].
This involves adding up the individual loads each feeder must supply. Determine
these loads by looking at specification sheets and estimating receptacle loads. From
previous parts of this series, we have the following values:
Step 2: Calculate kVA of feeders 1, 3, 5, and 6, based on supply voltage and load.
To do this, multiply the current by the voltage. Then, multiply that answer by the
square root of three because this is a 3-phase system now you have your VA. Divide
your answer by 1000 so you can express the value in kVA.
Feeder No. 1.
kVA=684.65A x 480V x 1.732/1000
kVA=569.19kVA
Feeder No. 3.
kVA=534.525A x 208V x 1.732/1000
kVA=192.57kVA
Feeder No. 5.
kVA=588.05A x 480V x 1.732/1000
kVA=488.88kVA
Feeder No. 6.
kVA=405A x 4160V x 1.732/1000
kVA=2918.07kVA
Step 3: Calculate amps of each feeder, based on supply voltage and load.
To do this, convert kVA to VA by multiplying your kVA values by 1000. Because it's 3phase, next multiply your voltage by the square root of three. Divide your first
answer by your second answer, and you have your current. Be sure to round
decimals up, not down no matter how small the extra is.
Feeder No. 1.
I=kVA x 1000/(V x 1.732)
I=569.19kVA x 1000/(13,800V x 1.732)
I=23.82A
Feeder No. 2.
Amps at 13,800V=27.88A
Feeder No. 3.
I=kVA x 1000/(V x 1.732)
I=192.57kVA x 1000/(13,800V x 1.732)
I=8.06A
Feeder No. 4.
Amps at 13,800V=15A
Feeder No. 5.
I=kVA x 1000(V x 1.732)
I=488.88kVA x 1000/(13,800V x 1.732)
I=20.46A
Feeder No. 6.
I=kVA x 1000/(V x 1.732)
I=2918.07kVA x 1000/(13,800V x 1.732)
I=122.09A
Solution: Summing the individual amps for each feeder yields a total amperage of
217.31A.
Current of 217.31A at 13.8kV requires No. 4 cu., per Table 310-77. Note, we are not
using Table 310-16 because we are dealing with MV.
Step 2: Select the transformer. Based on the Code, you need a transformer bank
that can handle 5194.06kVA at 13.8kV.
AFC=FLA of transformer/Z
AFC=217.31A/.02
AFC=10,865.5A
The OCPD for the future load will be 15A. Conductors for the future load will be No. 6
cu., based on Table 310-77.
Lessons learned
Always develop a one-line diagram when calculating feeder loads. This will help you
clearly see the distribution system and avoid calculation errors. If you are using
engineering software or even a spreadsheet to do your calculations, this step will
help you avoid the garbage in/garbage out problem. You must work methodically,
first determining your loads and then determining what size transformers you need
to supply them. Size your overcurrent protection so you can run your loads, and size
your conductors large enough to handle the current load demand.