Vous êtes sur la page 1sur 12

Large-scale Photovoltaic

Power Generation Systems

01D1-E-0001

Our photovoltaic power generation systems provide eco-friendly energy.

Maximizing Output Power from


Photovoltaic Power Generation

High-eciency three-level inverter with our original


RB-IGBT
At Fuji Electric we develop and manufacture high-efficiency power
conditioner systems (PCS) in-company using our unique
proprietary reverse-blocking insulated gate bipolar transistor
(RB-IGBT) technology. Our power conditioners, which are at the
industrys highest level and use the maximum power point
tracking control (MPPT) that we have refined through long
development, enable maximum output power from photovoltaic
power generation.
1

Total System Construction from


PCS to System Interconnection

Fuji Electric offers a wide product lineup from high-voltage


and extra-high-voltage interconnection facilities that we have
developed as a heavy electrical equipment manufacturer to
supply-and-demand monitoring and PCS units. We support
total system introduction of photovoltaic power generation
facilities for our customers.

System Stabilization Technology

Power stabilizers, private power generators, and


hybrid power supplies such as wind power
generation and fuel cells
Fuji Electric has developed its system stabilization technology for
more than 20 years.
We make use of various types of power supply equipment such as
private power generators and wind power generators and power
accumulation technology developed for UPS to supply stable
power by combining power supply types tailored to each region.

Secure Support System in Japan


and Abroad

Our service engineers provide secure maintenance support for


customer facilities from Hokkaido to Okinawa in Japan and at
international service locations.

Total Engineering Solutions from System


Planning to Maintenance
Fuji Electric is a full-service equipment manufacturer, a peripheral equipment supplier, and a total
engineering solution provider of photovoltaic power generation systems from system design to
construction management.

Fuji Electric provides comprehensive system


proposals for efficient operation from solar cells
to power transmission.

One-line Diagram

Fuji Electric System Solutions


Fuji Electric provides photovoltaic power generation systems
optimized for each region by combining our in-depth experience
and advanced technologies.

PCS
High eciency
(98.5% for DC 1,000 V specifications) (Power conditioner system)
Series expanded to DC 600 V
specications
Substation conguration for easy
construction*

Long history of accomplishments and experience since


foundation in 1923 (Solar cell characteristics, inverter
technology, and system interconnection technology)
Advanced technologies (RB-IGBT and system
interconnection technology)
Transformation system

System interconnection technology


Smart grid monitoring technology
Large-scale plant technology

Interconnection with
transmission line of
electric power utility
company

PV panel

PCS

Connection
box,
current
collection
box

PV panel

Main transformer
GIS

VCT

Extra-high-voltage facility
(22 to 154 kV)

High-voltage
facility
(6.6 kV)

*: Integrated configuration includes power conditioner


system (PCS), switchgear, and step-up transformer.

System-matched Modules

PCS

Connection
box,
current
collection
box

Overseas and Japanese


power generation operators
(public and private sector)

PV module

Sales and after-sales service

PCS

PCS

Power conditioner

Key technology

PCS

PCS

PCS

PCS

Other principal components

Total system design


(Electric equipment, system interconnection, stabilizer, IT, etc.)

Total engineering

(Installation, construction, quality assurance, after-sales service, etc.)

As the PCS is the core of the system, we provide


a large-capacity PCS of the highest efficiency that
incorporates advanced power semiconductors.
(The series lineup was reinforced with the addition of a new 500 kW model.)

Features
Adoption of new IGBT and new circuit system
Fuji Electric commercialized the worlds first three-level module
in which a new RB-IGBT* and an existing IGBT are integrated in
one package.
Application of this new module to a new three-level conversion
circuit enables a large reduction both in power loss and in the
number of parts, resulting in high efficiency and low noise in the
equipment.
: RB-IGBT: Reverse Blocking-Insulated Gate-Bipolar Transistor

World
s highest eciency 98.5%
(DC 1,000 V product)

Single unit capacity 1,000 kW

Compared to existing products, our new power conversion


technology, which uses a new three-level conversion circuit in
the new module, reduces switching loss in the IGBT device and
also reduces filter loss by reducing to one half the harmonic
content in PWM waveform outputted by the inverter. This results
in the world highest efficiency of 98.5% (DC 1,000 V product).
We have also achieved EURO efficiency of 98.2% (DC 1,000 V
product).

New IGBT module

Fuji Electric successfully developed a PCS with a single unit


capacity of 1,000 kW.
For large-scale photovoltaic power generation systems, this
large single unit capacity enables the number of PCS units to

be optimized, resulting in significant reductions in construction


and building costs.

INV1

99

1000 kVA

LB

INV2

98

Efficiency [%]

97
96
95
94

INV3

93
92
91
90
89

20

40

60

80

100

INV4

Output [%]
New IGBT module

New three-level conversion circuit

Outdoor substation type

Output line voltage waveform


Existing system
(two-level system)

Output line voltage waveform


New system
(new three-level system)

Reduction of power loss

Standard FRT function


The fault ride through (FRT) function that is becoming
essential in PCS for large-scale photovoltaic power
generation is provided as a standard function.
Even if a three-phase or two-phase short circuit accident

occurs in the system, the inverter can output three-phase


current in a specified range to suppress power supply
variations in the system.

AC voltage
U-V phase (red)
V-W phase (green)
200 V/DIV
AC current
U phase (red)

80

Loss[%]

Fuji Electric provides a substation type of PCS that can be


installed outdoors.
A switchgear, a step-up transformer, and PCS that can be
installed outdoors are integrated on a common base in a single
unit. This eliminates the need for a building for storing panels
and air-conditioning facilities. Since this substation is
transported to the site as an integrated unit, on-site construction
costs can be greatly reduced.
With the installation of an optional fuse for a DC branch in the
PCS, the panel output collected in the current collection box can
be connected to the PCS as is.

W-U phase (blue)


ACL and wiring loss
Switching loss

100

Note: Internal power supply is not included. IEC61683 efficiency tolerance is indicated.

V phase (green)

60

W phase (blue)
25 A/DIV

40
20
0

Existing system
(two-level system)

New system
(new three-level system)

3.6

3.62

3.64

3.66

4.6

4.62

4.64

Example of outside dimensions


Step-up transformer
LBS panel

(Front view)

PCS

PCS

DC main circuit
cable and ground wire

PCS (DC 1000 V) specifications (Outdoor self-standing type)


Item

Electric specifications
(DC input)
Electric specifications
(AC output)

System interconnection

Series name
Rated output
Insulation system
DC input voltage range
DC input voltage (MPPT range)
Number of DC input branches
Rated output capacity
Rated output voltage
Rated frequency
Number of output phases
Rated output current
Output power factor
Output current distortion factor (total)
Output current distortion factor (each)
Equipment highest efficiency
Equipment efficiency (Euro efficiency)
Overload capacity
Noise
System protection
Individual operation detection system (passive)
Individual operation detection system (active)
Voltage rise suppression function

FRT
Installation system
Applicable IP
System type
Cable lead-in
Cooling system
Dimensions
PCS single unit (W D H)
Substation (W D H)
Mass
PCS single unit
Substation
Environmental conditions Storage temperature
Operating temperature
Relative humidity
Altitude
Relevant standard
Communication system
Panel structure

PVI1000-3/1000
Remarks
1000 kW
Transformerless system
1000 V
460 V to 950 V
4
24 branches (Option)
1000 kW
270 V10 to 12
50/60 Hz 5
Three-phase, three-wire; isolated neutral system supported.
2138 A
>0.99(at rated output)
Individual operation Q output excluded
(when output is 1/8 of rated output).
<5 % (at rated output)
<3 % (at rated output)
98.5 %
98.2 %
100 % continuous
85 dB
OV, UV, OF, UF
Detection of voltage phase jump
Reactive power variation system
Reactive current compensation,
active current output suppression
Vmin=15 0.625 SRecovery time 3 s Based on the countrys grid code.
Outdoor self-standing type
Measures against salt damage are optional.
IP54
Integrated step-up transformer and switchgear
Substation system
Lower part
Forced-air cooling
360021302830 mm
615024002830 mm
About 7000 kg
About 12500 kg
20 to +50
High-temperature option available for +50 C.
10 to +40
Non-condensing
15 to 95
High-altitude option available for over 2000 m.
2000 m or less
IEC62109-1
RS-485/MOD BUS/TCP

Switchgear and step-up transformer (1000 kW) specifications


Item
Rated output
Electric specifications of Power supply voltage
switchgear
Power supply frequency
Number of power supply phases
Rated current
Breaking capacity
Electric specifications of Capacity
step-up transformer
Number of phases
Frequency
Cooling system
Connection system
Others

1000 kW
4.16 to 34.5 kV
50/60 Hz
Three-phase, three-wire
200 A
12.5 kA
1000 kVA
Three-phase
50/60 Hz
Oil-immersed self-cooling

Contact prevention plate is provided.

Remarks

Base (1)

High-voltage main circuit


Cable and ground wire

1000

150

800
Concrete foundation

Step-up transformer
LBS panel

(Top view)

1000

800

1200

2400

Operation screen

2130

Example of appearance

2830

Specifications

1200

2550

3600
6150

(Unit: mm)

PCS (DC 750 V) specifications (Outdoor self-standing type)


Item

Electric specifications
(DC input)
Electric specifications
(AC output)

Series name
Rated output
Insulation system
DC input voltage range
DC input voltage (MPPT range)
Number of DC input branches
Rated output capacity
Rated output voltage
Rated frequency
Number of output phases
Rated output current
Output power factor

Output current distortion factor (total)


Output current distortion factor (each)
Equipment highest efficiency
Equipment efficiency (Euro efficiency)
Overload capacity
Noise
System interconnection System protection
Individual operation detection system (passive)
Individual operation detection system (active)
Voltage rise suppression function
FRT
Panel structure

Dimensions
Mass
Environmental
conditions

Installation system
Applicable IP
System type
Cable lead-in
Cooling system
PCS single unit (W D H)
Substation (W D H)
PCS single unit
Substation
Storage temperature
Operating temperature
Relative humidity
Altitude

Relevant standard
Communication system

PVI7503/750
Remarks
750kW
Transformerless system
750 V
320 V to 750 V
4
16 branches (Option)
750 kW
200 V10 to 12
50/60 Hz 5
Three-phase, three-wire; isolated neutral system supported.
2165 A
>0.99(at rated output)
Individual operation Q output excluded
(when output is 1/8 of rated output).
<5 % (at rated output)
<3 % (at rated output)
97.8 %
97.4 %
100 % continuous
85 dB
OV, UV, OF, UF
Detection of voltage phase jump
Reactive power variation system
Reactive current compensation,
active current output suppression
JEAC97012010
Based on the countrys grid code
(conforms to supplementary version of 2011)
Outdoor self-standing type
Measures against salt damage are optional.
IP54
Substation system
Integrated step-up transformer and switchgear.
Lower part
Forced-air cooling
360021302830 mm
615024002830 mm
About 7000 kg
About12500 kg
20 to +50
10 to +40
High-temperature option available for +50 C.
15 to 95
Non-condensing
2000 m or less
JIS, JEM, JEC
RS485/MOD BUS/TCP

Switchgear and step-up transformer (750kW) specifications


Item
Electric specifications
of switchgear

Values other than the left value are optional.


Electric specifications
of step-up transformer

Rated output
Power supply voltage
Power supply frequency
Number of power supply phases
Rated current
Breaking capacity
Capacity
Number of phases
Frequency
Cooling system
Connection system
Others

750 kW
6.6 kV
50/60 Hz
Three-phase, three-wire
200 A
12.5 kA
750 kVA
Three-phase
50/60 Hz
Oil-immersed self-cooling

Contact prevention plate is provided.

Remarks

Values other than the left value are optional.

System Configuration Example

PCS optional

New
Series !

One-line diagram (10MW, Outdoor self-standing type, Example of a 1,000 kW PCS)

PCS (DC 750 V) specifications (Indoor self-standing type)


Item

Series name
Rated output
Insulation system
Electric specifications DC input voltage range
(DC input)
DC input voltage (MPPT range)
Number of DC input branches
Electric specifications Rated output capacity
(AC output)
Rated output voltage
Rated frequency
Number of output phases
Rated output current
Output power factor
Output current distortion factor (total)
Output current distortion factor (each)
Equipment highest efficiency
Equipment efficiency (Euro efficiency)
Overload capacity
Noise
System
System protection
Individual operation detection system (passive)
interconnection
Individual operation detection system (active)
Voltage rise suppression function
FRT
Installation system
Panel structure
Applicable IP
System type
Cable lead-in
Cooling system
Dimensions
PCS single unit (W D H)
Substation (W D H)
Mass
PCS single unit
Substation
Environmental
Storage temperature
conditions
Operating temperature
Relative humidity
Altitude
Relevant standard
Communication system

PVI7503/500
500kW
Transformerless system
750V
320V to 700V
5
500kW
200V10 to +12
50/60Hz
Three-phase, three-wire; isolated neutral system supported.
1444A
>0.99 (at rated output)
<5% (at rated output)
<3% (at rated output)
97.7%
97.3%
100% continuous
75dB or less
OV, UV, OF, UF
Detection of voltage phase jump
Reactive power variation system
Reactive current compensation, active current output suppression
Vmin=15%0.625s Recovery time 3 s
Outdoor self-standing type

Lower part
Forced-air cooling
24009001950 mm

2000kg

20 to +50
10 to +40
5 to 90
1000m or less
JIS, JEM, JEC
RS485

Remarks

Optional

Demarcation point

Individual operation Q output excluded

Based on the countrys grid code

Station service transformer panel


VCB
52F1

Non-condensing

500 kW
6.6 kV
50/60 Hz
Three-phase, three-wire
200 A
12.5 kA
500 kVA
Three-phase
50/60 Hz
Oil-immersed self-cooling

Contact prevention plate is provided.

DT

-MC

-MC
V
Wh

MCCB

SD

MCCB

Rectifier panel
MCCB Storage
battery
Rectifier panel
MCCB MCCB

2CT
A

MCCB

MCCB

MCCB

High-voltage panel

U>
Z >

Monitoring protection cubicle

Spare
High-voltage panel

Monitoring protection cubicle

MCCB MCCB MCCB

Values other than the left value are optional.

PAS
(with VT, LA and SOG)

V
Wh

Spare

DC panel

MCCB

Aerial wire

Spare

Storage
battery

Remarks

ZCT

U>
DT

2CT

Switchgear and step-up transformer (500kW) specifications


Item
Rated output
Electric specifications Power supply voltage
of switchgear
Power supply frequency
Number of power supply phases
Rated current
Breaking capacity
Electric specifications Capacity
of step-up transformer Number of phases
Frequency
Cooling system
Connection system
Others

U>

From temporary
generator

F-MPC60B

LA3

Station service transformer


three-phase mold

NGR

51G

2CT

LBS

PF

MCCB

MCCB
Others(meteorological
equipment, display)

Monitoring protection cubicle

No.1 Substation

No. 1 high-voltage air break switch


LBS
No. 1 step-up transformer
(Outdoor oil-immersed self-cooling type)

No.1 PCS

MCCB
CT1, 2
MC11

MC21

MC31

L12

L22

L32

L42

C1 L11

C2 L21

C3 L31

C4 L41

DCCT11,12
PWU1

DCCT21,22
PWU2

DCCT31,32
PWU3

DCCT41,42
PWU4

F11,12

F21,22

F31,32

F41,42

DCCT10

DCCT30

MCB11

MCB31

Solar cell

Solar cell

Solar cell
4 blocks

10

MC41

Solar cell

27
59
64
67S
95LH

System Configuration Example

One-line diagram (10MW, Outdoor self-standing type, Example of a 1,000 kW PCS)

66 kV transmission line

Demarcation point
Monitoring and control panel (outdoor)
3BCT
ES (manual)

F-MPC

LA3

DS
89R(Electrically operated)

ES (manual)
Outdoor meter panel
(Supplied by electric power
utility company)

VD

W/TD
Var/TD

VCB(52R) C-GIS
ES (manual)

CLR

EVT

VCT

VCT

F-MPC

Monitoring and control panel


(indoor)

F-MPC

3BCT
Bus duct

Tr-1
Main transformer
Three-phase outdoor oil-immersed self-cooling

EVT

LA3

V/TD

5CT

CLR

F-MPC

Incoming panel

64G
To each PCS panel

F-MPC

52S
VCB

Feeder panel

Station service transformer panel


VCB
52F1

U>

From temporary
generator

DT

-MC

-MC
V
Wh

SD

MCCB

Rectifier panel
MCCB Storage
battery
Rectifier panel
MCCB MCCB

2CT
A

MCCB

MCCB

High-voltage panel

U>
Z >

Monitoring protection cubicle

Spare
High-voltage panel

MCCB

Monitoring protection cubicle

DC panel

MCCB

Wh

MCCB

MCCB
Others(meteorological
equipment, display)

Monitoring protection cubicle

No.2

No.1 Substation

No.3

No.4

No. 1 step-up transformer


(Outdoor oil-immersed self-cooling type)

PAS
(with VT, LA and SOG)
No.5 Substation

No. 5 high-voltage air break switch


LBS

No.6

No.7

No.8

No. 5 step-up transformer


(Outdoor oil-immersed self-cooling type)
No.1 PCS

MCCB

No.5 PCS

MC21

MC31

MC41

L12

L22

L32

L42

C1 L11

C2 L21

C3 L31

C4 L41

DCCT11,12
PWU1

DCCT21,22
PWU2

DCCT31,32
PWU3

DCCT41,42
PWU4

F11,12

F21,22

F31,32

F41,42

DCCT10

DCCT30

MCB11

MCB31

Solar cell

Solar cell

Same as
on the left

Same as
on the left

Same as
on the left

MC11

27
59
64
67S
95LH

Same as
on the left

Solar cell

Same as
on the left

Same as
on the left

CT1,2
MC21

MC31

MC41

L12

L22

L32

L42

C1 L11

C2 L21

C3 L31

C4 L41

DCCT11,12
PWU1

DCCT21,22
PWU2

DCCT30

MCB11

MCB31

Solar cell

Solar cell
4 blocks

11

DCCT31,32
PWU3

DCCT10

Solar cell

No.10

No.9 PCS

MCCB

CT1,2

MC11

No.9 Substation

No. 5 high-voltage air break switch


LBS
No. 5 step-up transformer
(Outdoor oil-immersed self-cooling type)

MCCB

CT1, 2

4 blocks

10

Aerial wire

PAS
(with VT, LA and SOG)

No. 1 high-voltage air break switch


LBS

Solar cell

F-MPC60B

ZCT

Aerial wire

Spare

MCCB MCCB MCCB

ZCT

PAS
(with VT, LA and SOG)

VCB
(52F3)

LA3

Aerial wire

Spare

Storage
battery

F-MPC

LA3

ZCT

U>
DT

2CT

MCCB

F-MPC60B

LA3

Station service transformer


three-phase mold

NGR

51G

2CT

2CT

2CT

LBS

PF

VCB
54F2

Same as
on the left

Same as
on the left

Same as
on the left

DCCT41,42
PWU4
27
59
64
67S
95LH

Solar cell

Same as
on the left

Same as
on the left

Same as
on the left

MC11

MC21

MC31

MC41

L12

L22

L32

L42

C1 L11

C2 L21

C3

L31

C4

L41

DCCT11,12
PWU1

DCCT21,22
PWU2

DCCT31,32
PWU3

DCCT41,42
PWU4

F11,12

F21,22

F31,32

F41,42

DCCT10

DCCT30

MCB11

MCB31

Solar cell

Solar cell

Solar cell

Same as
on the left

Solar cell

27
59
64
67S
95LH

Same as
on the left

4 blocks

12

System Configuration Example

One-line diagram (2MW, Outdoor self-standing type, Example of a 1,000 kW PCS)


6.6 kV transmission line
Demarcation point
Installation of electric pole

VCT

PAS

Supply meter panel

Incoming panel

VD

Installation of
electric pole

DS
89R
(remote manual operation)

Incoming panel

2VT
VCB52R

RPS
Wh

64G

2CT

RPS

F-MPC60B

To each PCS panel

Wh

ZPD

Station service transformer panel

PF:20A

LBS

VCB
52F2

VCB
52F1

Station service transformer three-phase mold


PV feeder panel
V

2CT

2CT

F-MPC60B

2CT

MCCB

2CT
Wh

MCCB

Wh

MCCB

Power load
Spare

6.6 kV cubicle

No.1 Substation

No. 1 high-voltage air break switch


LBS

MCCB

F-MPC60B

ZCT

ZCT

No. 1 step-up transformer


(Outdoor oil-immersed self-cooling type)

MCCB

No. 2 step-up transformer


(Outdoor oil-immersed self-cooling type)
No.1 Substation

MCB11

Spare
Remote monitoring

No.2 Substation

No. 2 high-voltage air break switch


LBS

No.2 Substation

MCB11

CT1,2

CT1,2

Measuring instrument

MC11

MC21

L12
C1

L11

L22
C2

DCCT11,12
PWU1

MC31

MC41

L32
C3

L21

DCCT21,22
PWU2

L31

L42
C4

DCCT31,32
PWU3

DCCT41,42

27
59
64

F31,32

67S

MCB11

MCB31

95LH

Solar cell

Solar cell
4 blocks

13

PWU1

F11,12

Solar cell

Solar cell

L11

MC31

L22
C2

DCCT11,12

PWU4

DCCT30

MC21

L12
C1

L41

DCCT10

MC11

MC41

L32
C3

L21

DCCT21,22
PWU2

L31

L42
C4

DCCT31,32
PWU3

L41
DCCT41,42
PWU4

DCCT10
F11,12

F31,32

MCB11

MCB31

Solar cell

27

DCCT30

Solar cell

Solar cell

59
64
67S
95LH

Solar cell

4 blocks

14

System Configuration Example

One-line diagram (2MW, Indoor self-standing type, Example of a 500 kW PCS)


6.6 kV transmission line
Demarcation point
Installation of electric pole

VCT

PAS
Installation of
electric pole

Incoming panel

VD

DS(89R)(remote manual operation)

Supply meter panel

Incoming panel

2VT
VCB(52R)

RPS
Wh
RPS

64G
To each PCS panel

2CT

Wh

FMPC60B

ZPD

Station service transformer panel

PF:20A

LBS

VCB(52F2)

VCB(52F1)

Station service transformer three-phase mold


PV feeder panel
V

2CT

2CT

FMPC60B

ZCT

FMPC60B

ZCT

No. 1 high-voltage air break switch


2CT

Wh

No. 2 high-voltage air break switch

LBS

2CT
Wh

LBS

No. 1 step-up transformer


(Outdoor oil-immersed self-cooling type)
MCCB

MCCB

MCCB

Power load
Spare

6.6 kV cubicle

MCCB

MCCB

Stored inside container

Spare
Remote monitoring

No.1PCS
(500kW)

MCB

MC21

L12

L11

L21

DCCT

Solar
cell
Solar
cell

MCB5

MCB4

Solar
cell

PWU2

MCB3

Solar
cell

DCCT

PWU1

MCB2

Solar
cell

Branch circuit breaker


(standard equipment)

L22
L21

DCCT

MCB1

Solar
cell

MCB5

Solar
cell

L11

PWU2

MCB4

Solar
cell

MC21

L12

DCCT

MCB3

Solar
cell

MCB2

Solar
cell

L22

PWU1

Branch circuit breaker


(standard equipment)

MC11

L21

DCCT

MCB1

Solar
cell

MCB5

Solar
cell

L11

PWU2

MCB4

Solar
cell

MC21

L12

DCCT

MCB3

Solar
cell

Branch circuit breaker


(standard equipment)

MCB2

Solar
cell

L22

PWU1

CT

MC11

L21

DCCT

MCB1

Solar
cell

MCB5

MCB4

Solar
cell

L11

PWU2

MCB3

MCB2

MCB1

Solar
cell

L12

DCCT

PWU1

MC21

No.2PCS
(500kW)

MCB

CT

MC11

L22

No.1PCS
(500kW)

MCB

CT

MC11
C

Stored inside container

No.2PCS
(500kW)

MCB

CT

Measuring instrument

15

No. 2 step-up transformer


(Outdoor oil-immersed self-cooling type)

Branch circuit breaker


(standard equipment)

Solar
cell
Solar
cell

16

A monitoring unit quickly collects information


on proper photovoltaic power generation and
the state of each component.

Features
The SCADA system has the highest quality and cost performance in the industry.
The system has many features such as a web function, multilingual function,
high speed, extensibility, and reliability.
The system can be applied to a large-scale power generation system with several to more than 400,000 I/O points.

High speed

Extensibility

Optimal performance is achieved


every time.

The number of signals can be


extended from 75 to 400,000.

High-speed data collection and display


are achieved even in large-scale
systems by optimizing every
communication and reducing
unnecessary communication.

Various systems from small- to


large-scale configurations can be
supported. Also partial system
introduction is possible to reduce initial
investment.

Web functions and multilingual functions

Reliability
A system with minimal data loss is
achieved with a PC-based
conguration.
Communication functions and server
functions can be provided in
completely redundant configurations to
build a system that is safe, secure and
trouble-free, even in the event of any
malfunctions in a PC or in the network.

Real-time information on plant status can be accessed from


anywhere in the world at any time. (Web connection license is
provided)
Language switching is based on a table system for easy
switching to other languages. (For display, Windows fonts are
used.)

Graphic screen display


Menu screen (top menu, overall area)

Monitoring of each area of photovoltaic panel

System Configuration Example

Large-scale photovoltaic power generation installation area

PV facility
Thermometer

PV facility

RS panel

Client display

RS panel

RS panel

RS-485

(Selling power)

AI: Signal line

(Purchasing power)

Sunshine
recorder

AI: Signal line

Remote monitoring
server

22 to154kV

Extra-high-voltage
incoming panel

Sunshine
recorder

Modbus, etc.

Thermometer

System
interconnection
facility

Common screen functions


(for example, trends)

Skeleton monitoring screen

Form output function

RS panel

Citect SCADA using smartphone

Remote monitoring control area

A smartphone can be used as a maintenance management


tool for facilities.

Internet(WAN/VPN)

Trends and alarms can be checked through a wireless


The state of
installation areas such
as skeleton areas can
be monitored from a
remote site.

17

Remote monitoring
from existing personal
computers is possible.

Windows remote desktop connection.

Radio equipment
Remote monitoring control personal computer

18

About Microgrids
Fuji Electric also develops renewable energy solutions such as photovoltaic power generation and
wind power generation for isolated islands. These microgrid congurations can achieve balanced
operation with diesel power generation using a system with an advanced high-performance power
PCS and a lithium ion capacitor mounted stabilizer. We participate in many verication tests aiming
to reduce CO2 emissions and power generation costs.

MEMO

Conceptual diagram of microgrid


Load curve (old)
(New)

Electric power network on isolated islands

Interconnection point
total output

Interconnection point output

Large output
variation

Compensation
output

Output

PCS
Storage battery

PCS
On-island diesel
power generation system

Large output variation


Wind power generation(WT)

Control unit

Output
PCS

PCS: Power conditioner

Photovoltaic (PV) power generation

Electric power network based on renewable energy

Description of verication tests


6 islands in Kyushu (verification research in progress)
3 islands in Okinawa (verification research in progress)
<Case Study on Tarama Island in Okinawa>
Our lithium ion capacitor equipped stabilizer was introduced to enable high charging and discharging output and
high reliability.

Kuroshima Island (Kyushu)

19

Takarajima Island (Kyushu)

Tarama Island (Okinawa)

20

Printed on recycled paper

Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
Phone : (03)5435-7111

Internet address : http://www.fujielectric.co.jp


Information in this catalog is subject to change without notice.

2012-8(H2012/E2012)PST/CTP10Ok Printed in Japan

Vous aimerez peut-être aussi