Safety instructions
This instrument is constructed and tested according to the current EUdirectives and packed in technically safe condition. In order to maintain
this condition and to ensure safe operation, the user must follow the
instructions and warnings given in this instruction.
During the installation local standards have to be observed. Ignoring
the warnings may lead to severe personal injury or substantial damage
to property.
The product must be operated by trained staff. Correct and safe
operation of this equipment is dependent on proper transport, storage,
installation and operation.
All electrical wiring must conform to local standards and the connection must be made according to the connecting diagrams.
Before switching on the power supply take care that other equipment
is not affected. Ensure that the supply voltage and the conditions in the
environment comply with the specification of the device.
Before switching off the supply voltage check the possible effects on
other equipment and the processing system.
To obtain the specified protection degree, the LBFS must be mounted
with a compliant cable.
WARNING
This product contains no replaceable parts.
In case of malfunction the product must be shipped to Baumer for
repair.
Description
The Level Switch LBFS designed to detect levels in tanks, media
separation and provide empty-pipe detection or dry-run protection for
pumps.
A high frequency sweep signal is radiated from the sensor tip into the
tank. The media will act as a virtual capacitor, which together with a
coil in the sensor head, will form a circuit creating the switch point
signal. This virtual capacitance will depend of the di-electric value of
the media.
Two output signals are available, Normally Open (NO) and Normally
Closed (NC). By means of the FlexProgrammer 9701, a damping of
the output signal can be activated in case of a fluctuating media level,
e.g. during tank filling. Additionally the output signals NO and NC can
be reversed.
www.baumer.com
Design and specifications subject to change without notice
The Level Switch LBFS measures liquids such as water and oil.Even
dry medias can be measured, eg. coal dust or plastic granulate.
Level Switch LBFS can be delivered with PNP output as well as NPN
output.
The process connection can easily be sealed by use of Teflon Tape or
by use of special welding adapter for the hygienic edition.
Measuring principle
The frequency sweep technology
The capacity (C) of the media is directly proportional to the
dielectric value of the media
A frequency between 100 and 180MHz is swept into the media
When the coil (L) and the capacitor (C) reach a resonance
frequency, it will be detected by the electrical circuit
Mounting
The thread must be sealed e.g. by Teflon tape and tightened into the counterpart.
Recommended tighten max. 25...30 Nm
Dimensional Drawings
LBFS xx1x x
www.baumer.com
Design and specifications subject to change without notice
LBFS xx2x x
LBFS xx3x x
Dimensional Drawings
68
97
97
NV22 mm
48
G A
ISO288/1
NV24 mm
27
G hygienic
G reverse assembly
LBFS xx4x x
LBFS xx5x x
Electrical Connection
4
M12 plug
1
2
3
4
Cable
Brown
White
Blue
Black
Funktion
+ VDC
Normally Closed
- VDC
Normally Open
Electrical Installation
Normally Open
0 mA
+
20 mA
LED
+
12...30 VDC
PNP Output
20 mA max.
www.baumer.com
Design and specifications subject to change without notice
12...30 VDC
NPN Output
20 mA max.
Normally Closed
20 mA
0 mA
LED
+
-
12...30 VDC
12...30 VDC
PNP Output
20 mA max.
NPN Output
20 mA max.
Configuration
FlexProgrammer 9701
M12 plug
Note: Ambient temperature range 0...50C
Brown
Cable
Blue
1
2
Accessories
FlexProgrammer 9701
The FlexProgrammer 9701 is a dedicated tool to configure Baumer
configurable products.
Type No. 9701-0001 comprises:
FlexProgrammer
Cable with 2 aligator clips
Cable from FlexProgrammer to M12 plug for TE2
Cable from FlexProgrammer to M12 Plug for LFFS, LBFS, CPX
USB cable
CD with the FlexProgram software
www.baumer.com
Design and specifications subject to change without notice
Press
Press
120,00
115,00
110,00
105,00
100,00
95,00
Tprocess (0C)
90,00
85,00
80,00
75,00
70,00
65,00
60,00
55,00
50,00
50
55
60
65
70
75
80
Tambient (0C)
www.baumer.com
Design and specifications subject to change without notice
85
90
95
100
105
Ambient Temperature
Application
LBFS xx5x x
www.baumer.com
Design and specifications subject to change without notice
LBFS xx5x x
Ex-data
Supply range
24...30 VDC
Temperature class
T1...T4:
T1...T5:
Internal inductivity
Li < 10 H
Internal capacity
Ci < 43 nF
Barrier data
Zone 0/1
Safe area
3
2
Brown
C+
Blue
Black
A PNP NO
M12 plug
Cable
NO
NC
COM
22 ...120VDC or
+ 90...253VAC
Isolating Module
PROFSI3-B25100-ALG-LS
Zone 0/1
Safe area
Brown
M12 plug
Cable
24VDC
Blue
Black
OUT
www.baumer.com
Design and specifications subject to change without notice
Two-channel
ZENER BARRIER
Ex-data
Supply range
Temperature class
T100
Black or white
LOAD
M12 plug
Cable
Brown
Blue
320140 05/2011 ind.a_EN This data sheet may only be reproduced in full.
NB : The cable must be fixed to an external strain relief not more than 5 cm from the Level Switch.
Only IP 67 compliant cable must be used for installation.
See below.
Ex-data
Supply range
Temperature class
T1...T5
Black or white
LOAD
M12 plug
Brown
Cable
www.baumer.com