R = Resistance of earth rod in W.
r = Resistivity of soil ( Meter) = 65 Meter
l = length of the rod (cm) = 262m = 26200 cm
d = internal diameter of rod(cm) = 36mm = 3.6cm
h = Depth of the buried strip/rod (cm)= 500mm = 50cm.
Here:
If = 50000 Amp
T = 1 Second
K = 80 (Material Constant, For GI=80, copper K=205, Aluminium K=126).
Cross Section Area of Earthing Conductor (A) = (500001)/80
Cross Section Area of GI Earthing Conductor (A) = 625 Sq.mm
Allowance for Corrosion = 1.0 % Per Year & Number of Year before replacement say
= 20 Years
Total allowance = 20 x 1.0% = 20%
Safety factor = 1.5.
Required Earthing Conductor size = Cross sectional area x Total allowance x Safety
factor
Required Earthing Conductor size = 1125 Sq.mm say 1200 Sq.mm
Hence, Considered 1Nox12x100 mm GI Strip or 2Nox6 x 100 mm GI Strips.
_____________________________________________________________________
____________________________________________________
5 : Calculate Number of Earthing Rod.
The approximate earth resistance of the Rod/Pipe electrodes can be calculated by:
Earth Resistance of the Rod / Pipe electrodes :
R= K x /L
Where:
= Resistivity of earth in Ohm-Meter
L = Length of the electrode in Meter.
d = Diameter of the electrode in Meter.
K = 0.75 if 25< L/d < 100.
K = 1 if 100 < L/d < 600
K = 1.2 o/L if 600 < L/d < 300
Number of Electrode if find out by Equation of R (d) = (1.5/N) x R
Where:
R(d) = Desired earth resistance
R = Resistance of single electrode
N = No. of electrodes installed in parallel at a distance of 3 to 4 Meter interval.
Example: Calculate Earthing Pipe Resistance and Number of Electrode for
getting Earthing Resistance of 1 ,Soil Resistivity of =40, Length = 2.5 Meter,
Diameter of Pipe = 38 mm.
Here:
L/d = 2.5/0.038=65.78 so K = 0.75
The Earth Resistance of the Pipe electrodes R= K x /L = 0.7565.78 = 12
One electrode the earth resistance is 12 .
To get Earth resistance of 1 the total Number of electrodes required = (1.512)/1 =
18 No
Calculating Resistance & Number of Earthing Rod
Reference: As per EHV Transmission Line Reference Book page: 290 and Electrical
Transmission & Distribution Reference Book Westinghouse Electric Corporation,
Section-I Page: 570-590.
Earthing Resistance of Single Rods:
R = x[ln (2L/a)-1]/(23.14xL)
Earthing Resistance of Parallel Rods:
R = x[ln (2L/A]/ (23.14xL)
Where:
L = length of rod in ground Meter,
a = radius of rod Meter
= ground resistivity, ohm-Meter
A = (axS)
S = Rod separation Meter
Earthing rod arrangements
_____________________________________________________________________
____________________________________________________
6 : Selection of Earthing System:
Installations/Isc Capacity IR Value Required Soil Type/Resistivity Earth System
House hold earthing/3kA 8 ohm Normal Soil/ up to 50 ohm-meter Single Electrode
9 : GI Earthing Plate
Plate Weight
600 x 600 x 3 mm 10 Kg App.
600 x 600 x 4 mm 12 Kg App.
600 x 600 x 5 mm 15 Kg App.
600 x 600 x 6 mm 18 Kg App.
600 x 600 x 12 mm 36 Kg App.
1200 x 1200 x 6 mm 70 Kg App.
1200 x 1200 x 12 mm 140 Kg App.
_____________________________________________________________________
____________________________________________________
10 : G I Earthing Pipe
Pipe Weight
3 meter Long BISE 5 Kg App.
3 meter r Long BISE 9 Kg App.
4.5 meter (15 Long BISE) 5 Kg App.
4.5 meter (15 Long BISE) 9 Kg App.
4.5 meter (15 Long BISE) 14 Kg App
_____________________________________________________________________
_______________________________________
11 : GI Earthing Wire.
Plate Weight
6 Swg 5 meter in 1 Kg
8 Swg 9 meter in 1 Kg
_____________________________________________________________________
____________________________________________________
Also See...
Resistance Grounding.
Reactance Grounding.
Resonant Grounding.
Pipe Earthing.
Earthing Grid.
Ground Mat.
Earthing cable.
Step potential.
Touch potential.
Soil resistivity.