Académique Documents
Professionnel Documents
Culture Documents
Manufactured Marketed by :
Spirax Marshall Pvt. Limited
A Forbes Marshall Company
P. B. No. 29, Mumbai - Pune Road, Kasarwadi, Pune - 411 034. India.
Tel. : 91 (0) 020 27145595 Fax : 91 (0) 020 27147413, 27147593
URL : http://www.forbesmarshall.com/spirax
Branches
: Ahmedabad, Alibag, Bangalore, Bharuch, Chandigarh, Chennai,
Coimbatore, Delhi, Hyderabad, Jamshedpur, Kolkata, Mumbai, Nagpur,
Navi Mumbai, Pune, Surat, Vadodara, Visakhapatnam.
Dear User,
Thank you for purchasing the Automatic Blowdown Control System. To maximize your benefits from this
product, we request that you read these instructions thoroughly before using the Controller. If you
experience difficulty with the operation of this equipment, please contact our Customer Service
Representative.
Index
1. The ABCO plus Controller
1.1. General description
04
04
04
04
05
06
06
06
06
06
08
09
13
13
13
14
15
16
17
21
23
23
23
25
27
27
27
27
26
26
26
26
26
27
27
27
29
30
30
30
One
Up to three (max)
o
o
TDS
o
Temperature
Accuracy for Blowdown & feed water
Resolution for Blowdown & feed water
Range for Blowdown
5
+/- 1 deg C
0.1 deg C
0 250 deg C
0 150 deg C
Relay output
For Blowdown valve
For BHRS valve
boiler
Contact rating
with RC
User interface
Display
(Red Color)
Keypad
keys
Alarm signals
Continuous Green LED if no blowdown since 8 hours
Continuous Red in Failure Mode
Alarm messages in scrolling mode on LCD display
o
o
o
Operating voltage
Operating temperature
Storage temperature
1.2.2. Mechanical
7
2. Getting started
2.1. Included items
This product should come supplied with the following items:
o ABCO plus Blowdown Controller
1 nos.
o Conductivity Sensor for feed water K=0.1
1 nos. with 1.25 mtr cable
o User manual
1 nos.
Note: In case of the Panel Mount option, the Controller is delivered pre-mounted
on the Control Panel.
2.2. What you need
ABCO plus Blowdown Controller
Mechanical skid assembly that includes:
o Upstream & downstream isolation valves
o Blowdown valve with solenoid
o Downstream check valve
o Sensor chamber, etc
Set of spanners & screwdrivers
Air supply at a regulated pressure of 3 to 6 bar g
Single phase AC mains supply with proper Earth
2.3. Installation
2.3.1. Controller
For Wall Mount option, select a location which will keep the controller out of
direct sun and rain. Fix four M8 bolts into the wall with relative distances as shown
on the drawing. Using M8 plain washers and hex nuts, mount the controller onto
these bolts.
2.3.2. Sensors
CP10: Fit the joint gasket to the sensor and screw into the sensor chamber. A
graphite sealing compound is recommended to make subsequent removal
easier. PTFE tape sealing is not recommended.
CP32: This sensor type is supplied in nominal tip lengths of 300, 500 or 1000 mm,
and can not be cut to length. 300 mm and 500 mm probes can be installed
vertically or horizontally.
CAUTION: 1000mm probes must be installed vertically only.
WARNING:
Do not install the probe outdoors without additional weather protection.
The boiler must be depressurized and vented to atmosphere before
installation of the probe.
Wherever possible the boiler manufacturer must be consulted for advice on
the positioning of the probe and the optimum TDS level.
PT100: Mount the 1/8 BSP end of the Stud Coupling onto the sensor chamber.
Slide the Olive Nut over the sensor stem followed by the Olive. Tighten the Olive
Nut over the second end of the Stud Coupling such that the sensor tip does not
touch the opposite wall of the sensor chamber.
Feed Water Sensor: The sensor can be mounted either in-situ onto the feed water
tank such that the sensor is always below the minimum level of the feed water.
Alternatively it can be mounted downstream on the outlet pipe a shown.
10
To ABCO plus
controller
S
To ABCO plus
controller
Mounting
option B
S
Mounting
option A
2.3.3 Wiring
The detailed wiring connection schematics follow. These include the Sensor
connections, Solenoid Valve connections, 4-20 mA Output connections and
Mains connections. Please refer the following sheets for all the relevant details.
11
10
11
32/40/
46
BOILER 2
33
34
35
36
41
42
43
40
BOILER 3
12
13
14
32
Shield
Shield
HANGING
CONNECTOR
A: Female
B: Male
CP10 Sensor
NOTES
A: IC2, 5/8-ST-5.08 connector screw type
B: MSTB2, 5/8-ST-5.08 connector screw type
C: 4 core shielded wire 16/2, 0.5 sq.mm.(16/0.2)
D: PTFE insulated SPC cable 24/7/32Ex3cores, twisted
PTFE isolated, SPC shielded, overall PTFE jacketed
12
Red
White
White
Blue
Red
NC
PT100 Sensor
29
30
31
37
38
Shield
46
Shield
A: Female
B: Male
Shield
White
Red
Red
Brown
Yellow
Blue
Orange
HANGING
CONNECTOR
39
C
NOTES
A: IC2, 5/8-ST-5.08 connector screw type
B: MSTB2, 5/8-ST-5.08 connector screw type
C: PTFE insulated SPC cable 24/7/32Ex7cores, twisted
PTFE sheathed with drainwire of 7/32, overall
PTFE jacketed
D: PTFE insulated SPC cable 24/7/32Ex3cores, twisted
PTFE isolated, SPC shielded, overall PTFE jacketed
E: 4 core shielded wire 16/2, 0.5 sq.mm.(16/0.2)
13
14
4-20mA OUTPUT
CONNECTIONS
500 max
Solenoid
valve
Fuse 1A
slow blow
BOILER
BLOWDOWN VALVE
CONNECTIONS
Black
NEUTRAL
LIVE
Red
Solenoid
valve
Fuse 1A
slow blow
Red
BHRS VALVE
CONNE CTIONS
Black
NEUTRAL
LIVE
Red
52
51
27
26
45
44
B OILER 3
Red
50
49
25
24
18
17
BOILER 2
48
47
23
22
16
15
BOILER 1
MCB
Black
Green
3 core
Mains cable
Black Green
56
MAINS
CONNECTIONS
Red
Red
55
15
Relay outputs are provided per boiler, to operate the respective Blowdown
valves and the Blowdown Heat Recovery System valves. Operation of the
relay contacts:
BHRS valve is activated first
After completion of the blow down cycle blow down valve will be
closed
16
Typical operation
tPA
Valve
open
tPD
tPD
Purge
Purge
Valve
closed
Time
Purge cycles
High
Boiler water
TDS
Set
point
Low
15 sec
Valve
open
tBA
tPD
tBD
tBD
Purge
Blowdown
Blowdown
15 sec
Valve
closed
Blowdown
Purge
Blowdown
Blowdown Cycle
tPD: Purge Duration
tPA: Purge After
Time
Blowdown cycle
17
LCD display:
To set different values via Program menu and display other parameters &
calculated parameters in Run mode
Password for programming: 4 digit sequence
DN > UP > PURGE> ENT
Parameters displayed in Run mode (for the selected boiler):
TDS set point of Blowdown & Blowdown temperature on LCD.
Feed water TDS & feed water temperature
Blowdown loss (Kg) for each boiler
Blowdown flow rate (Kg/Hr) (instantaneous)
Energy total (Kcal / KJ).
% Blowdown
Total Purge Cycles
Alarm Indications & Sensor Short, Sensor Open message in rolling
mode
Parameters displayed in the Program menu:
All the programming parameters are displayed in Program Menu.
Bicolor LEDs to indicate
Red Flashing Blowdown cycle active
Green Flashing Purge cycle active
Constant Red Failed status
Constant Green Blowdown cycle has not occurred for more than
8 hrs
2.4.5. Programmable parameters
Calibration:
Used to calibrate the K factor of the conductivity sensor per boiler
Parameters:
Start Time in Hrs & Mins
Boiler Status (Enable/Disable) of each boiler
Units (SI/MKS) for each boiler
Purge After, Purge Duration, Blowdown after, Blowdown Duration
Line, Pressure, Capacity, Input sensor (CP10 / CP32) for each boiler
(blowdown only, not feed water)
Alarms (per boiler):
18
Boiler TDS High, Boiler TDS Low, feed water TDS High, % Blowdown
High
Service:
Data retrieval* Date, Time & TDS Value after valve close event of
each boiler
Electronic calibration - Boiler TDS circuits, Blowdown Temperature
circuits, feed water TDS circuit, feed water Temperature circuit, 4
20 mA current output circuit of Blowdown TDS of each boiler, test
mode for 4-20 mA current output.
* Number of records limited to 600 records per boiler.
Keyboard Matrix
Symbol of key
Description of key
PURGE
Purge
PROG /
Program / Enter
Up arrow
Down arrow
2.4.6.2.
Navigation
NOTE:
1. If BACK is selected and ENT key pressed then previous screen is displayed. While
on the PROGRAM menu screen, BACK is selected and ENT key is pressed then
the Controller will exit the program mode and the Run mode will be displayed.
2. In the LCD Screen Contents <v> is used to denote each numeral of the displayed
value.
19
Key
Key Action
PROGRAM MENU
1 CALIBRATION 5(%
2 PARAMETERS
3 ALARMS
4 RESET TOTALIZER
5 SERVICE/RTC/SP
BACK
PURGE
No Action
UP
CALIBRATION BLR<n>
CALIB VALUE
<vvvv> ppm
1.0
PURGE
Menu
Level
L1
L2
L3
<n>::boiler number
<v>::actual value
CALIBRATION BLR<n>
DONE/BACK
1.1
DN
ENT
UP
DN
ENT
PURGE
UP
No Action
DN
No Action
ENT
20
L1
L2
PROGRAM MENU
1 CALIBRATION
2 PARAMETERS
3 ALARMS
4 RESET TOTALIZER
5 SERVICE/RTC/SP
BACK
Screen2
L2
Screen3
L1
L2
No Action
UP
DN
ENT
PURGE
UP
DN
ENT
PURGE
PURGE AFTER:<vvvv> m
DURATION
:<vv> S
UP
BLD AFTER
DURATION
DN
ENT
PARAMETERS
STRT TIME H:<vv> M:<vv>
ENABLE BLR 1:Y/N
ENABLE BLR 2:Y/N
ENABLE BLR 3:Y/N
UNITS
:MKS/SI
DATA FOR BLR:1/2/3
2.0
Screen1
L2
PURGE
BACK
2.1
:<vv> S
:<vv> S
BACK
PURGE
LINE
PR
CAP
INPUT
UP
DN
ENT
PURGE
No Action
UP
2.2
:
:
:
:
0.5/1
<vv.v> kg/cm2
<vvvvv> kg/h
CP10/CP32
BACK
PROGRAM MENU
1 CALIBRATION
2 PARAMETERS
3 ALARMS
4 RESET TOTALIZER
5 SERVICE/RTC/SP
BACK
ALARMS
DN
ENT
PURGE
BLR
:1/2/3
BLR TDS HIGH:<vvvv>
UP
21
L1
L2
ENT
PURGE
No Action
UP
DN
ENT
PURGE
BOILER 1/2/3
UP
DN
ENT
PURGE
BACK
PROGRAM MENU
1 CALIBRATION
2 PARAMETERS
3 ALARMS
4 RESET TOTALIZER
5 SERVICE/RTC/SP
BACK
L2
SERVICE
ENTER PASSWORD
****
L1
PROGRAM MENU
1 CALIBRATION
2 PARAMETERS
3 ALARMS
4 RESET TOTALIZER
5 SERVICE/RTC/SP
BACK
L2
PROGRAM MENU
1 CALIBRATION
2 PARAMETERS
3 ALARMS
4 RESET TOTALIZER
5 SERVICE/RTC/SP
BACK
TOTALIZER RESET
4.0
L1
DN
SET
SET
SET
SET
HRS
MIN
SEC
DAY
:<vv>
:<vv>
:<vv>
:<vv>
UP
DN
ENT
PURGE
UP
DN
ENT
PURGE
UP
22
L1
L2
DN
ENT
PROGRAM MENU
1 CALIBRATION
2 PARAMETERS
3 ALARMS
4 RESET TOTALIZER
5 SERVICE/RTC/SP
PURGE
BACK
SET POINT BLR<n>
UP
DN
ENT
PURGE
UP
DN
ENT
2.4.7. Commissioning
Ensure that the Mains, Input and Output connections to ABCO plus
Controller are done as per the wiring diagram. Ensure that proper Earth
connection is provided to the ABCO plus Controller.
The ABCO plus Controller is despatched with the following factory-set
values. The settable Min & Max values of the programmable parameters are
also mentioned. User-specific changes can be done via the Program mode.
23
Calibration Value
Purge After (tPA)
0 ppm
1 minute
8
9
10
11
12
5 seconds
5 seconds
5 seconds
0.5 inch
2 kg/cm2
13
14
15
16
17
Capacity
Boiler TDS High Limit
Boiler TDS Low Limit
Feed water TDS High Limit
% Blow Down High Limit
0 kg /h
0 ppm
0 ppm
0 ppm
0
24
Min Value
Max Value
K = 0.2
K = 0.8
Factory-set
Value
K = 0.5
K = 0.08
K = 0.12
K = 0.1
0 ppm
0 kg
0 kJ/KCal
9999 ppm
9999999 kg
9999999
kJ/KCal
9999 ppm
1440
minute
60 seconds
60 seconds
60 seconds
1.0 inch
32 kg /
cm2
99999 kg/h
9999 ppm
9999 ppm
1000 ppm
100
3500 ppm
3500 ppm
30 minute
30 seconds
60 seconds
30 seconds
0.5 inches
9 kg / cm2
2000 kg/h
4000 ppm
3000 ppm
200 ppm
3
Please refer DOS and Donts section 2.4.9. For commissioning of the
Controller please follow the steps as given below after switching on the
ABCO plus Controller.
Normally, you will need to set the following parameters specific to the
installation. For the setting procedure please refer to the section 3. Please
set 1. The TDS set point as per the value specified by the boiler
manufacturer, per boiler.
2. The other parameters
i. Start time of the first shift for the daily basis calculation of
the heat loss and % blow down
ii. Boiler Enable / Disable option
iii. MKS / SI units option
iv. Purge After and Purge Duration
v. Blow Down After and Blow Down Duration
vi. Line size of the bottom blow down skid
vii. Pressure: Normal operating pressure of the boiler
viii. Capacity: Normal operating capacity of the boiler
ix. Input: Type of the sensor
3. The Alarms for each boiler
i. Boiler TDS High
ii. Boiler TDS Low
iii. Feed water TDS High
iv. % Blow Down High
All the modified values will be saved in the non-volatile memory and will remain
unchanged until re-programmed.
2.4.8. Maintenance
It is necessary to clean the CP10 sensor at regular intervals depending on
the installation.
2.4.9. Dos and Donts
Dos
Ensure that the wiring of the system is correct.
Ensure that the wiring is protected from any damage.
25
Donts
Do not try to repair the electronics on your own, contact your nearest
Spirax Marshall Service Centre for help.
Do not connect or disconnect any of the wires while the Controller is
in a powered up state.
Do not change any of the set parameters or perform calibration
without help of trained professionals or authorized personnel.
2.4.10. Fault finding
1. Controller does not Power On: Check power supply connection and
cable. Use a multimeter to check 230VAC at L-N-E terminals of the
Controller as mentioned in the wiring diagram.
2. Display shows fluctuating/unstable reading: check proper Earth to the
Controller. Check that the voltage across Neutral & Earth is within 8 VAC.
3. Temperature value not displayed / appears incorrect: check the
temperature sensor connections.
4. TDS value not displayed / appears incorrect: check the conductivity
sensor & temperature sensor connections.
5. Blowdown Valve Solenoid not operating: check the connections and
mains supply to the solenoid.
6. In case the RESET RTC message appears on the LCD display in scrolled
mode, please refer Section 3.2.2 for action to be taken.
26
3.1. PARAMETERS: Various parameters related to the boiler are entered in this menu.
A description follows.
3.1.1. START TIME: The start time of the first shift of the days operations is required
to be entered. This will be used for the calculation of the Heat Loss Total
and the % Blowdown on a daily basis. The time is in terms of Hours and
Minutes. Use PURGE, UP and DN keys for changing the start time. The
procedure for changing the start time is as follows:
1 Go to the PARAMETER menu in the PROGRAM MENU screen.
2 Press ENT key to enter the PARAMETER menu.
3 Select STRT TIME using the UP or DN keys.
4 Press PURGE key for editing the Hour time. Set the time by using UP, DN &
PURGE keys.
5 Press ENT key which saves the entered Hour time.
6 Press PURGE key for editing the Minute time. Set the time by using UP, DN
& PURGE keys.
7 Press ENT key which saves the entered Minute time.
After entering the correct START TIME press ENT key. The 24hrs calculation will
start immediately. The Heat Loss Total and % Blowdown will be calculated at
the end of every 24 hrs period after the START TIME. This value will be
retained until the end of the next 24 hrs period and then refreshed.
3.1.2. ENABLE BLR 1 / BLR 2 / BLR 3: This option can be used for enabling or
disabling the measurement and TDS control of a particular boiler. If the user
selects Y and presses the ENT key the corresponding boiler is enabled. If
the user selects N and presses the ENT key the corresponding boiler is
disabled. Depending on this selection the LCD screens for the respective
boiler are displayed in RUN mode. Also depending on this selection
particular boiler related settings will be enabled or disabled.
3.1.3. UNITS: This option is used to select between MKS or SI units. The MKS/SI
parameter details follow.
Sr. No.
Parameter
SI Unit
MKS Unit
Energy
Kg
KCal
Temperature
Flow rate
Kg/h
Kg/h
Total
Kg
Kg
27
3.1.4. DATA FOR BOILER 1/2/3: Individual boiler parameters are entered in this
mode. Select boiler 1/2/3 by using PURGE key. Press ENT key to enter
parameter setting mode for the corresponding boiler. Following are the
parameters that can be set.
3.1.4.1.
PURGE AFTER: PURGE AFTER is the time between two purge cycles.
This can be considered as the Purge Frequency. The settable range is 1
min to 1440 min.
3.1.4.2.
DURATION (Purge): This time is the time duration for which the purge
cycle is active. The settable range is 5 sec to 60 sec.
3.1.4.3.
BLD AFTER: Repetitive Blowdown cycles will occur until the boiler
TDS value is above the SET POINT. This time is the time between two
successive Blowdown cycles. The settable range is 5 sec to 60 sec.
3.1.4.4.
DURATION (Blowdown): This time is the time duration for which the
Blowdown cycle is active. The settable range is 5 sec to 60 sec.
LINE: This is used for the selection of boiler Blowdown line size. The
3.1.4.5.
selection is either 0.5 or 1.
3.1.4.6.
PR: The user has to enter the maximum pressure value at which the
boiler runs normally and not the maximum operating pressure of the
boiler. The settable range is 2 kg/cm2 to 32 kg/cm2.
3.1.4.7.
CAP: This is the capacity of the boiler at which the boiler operates
normally but NOT the maximum capacity. The user has to enter the
capacity value in kg/h. The settable range is 0 kg/h to 99999 kg/h.
3.1.4.8.
INPUT: The user has to select the sensor type for the Boiler from
which the input is taken. There are two types of the sensors - CP10 and
CP32.
3.2. ALARMS:
3.2.1. To meet the safety and efficiency requirements of the boiler we have to
apply certain limits for Boiler TDS, feed water TDS and % Blowdown. These
limits are set through the ALARMS menu. The user has to specify the Boiler
TDS high level, Boiler TDS Low Level, FW TDS High Level & % Blowdown High
Level. All these alarm values are programmable. Blowdown TDS HIGH and
LOW limits are programmable from 0 to 9999. FW TDS HIGH limit is
programmable from 0 to 1000. % Blowdown high limit is programmable from
0 to 100. All these parameters are to be set individually for each boiler. If the
measured value crosses the programmed ALARM value then the respective
alarm message for the particular boiler is displayed on the LCD display in
scrolling mode. Once the value comes within the alarm limit the message
will disappear.
28
3.2.2. A status message RESET RTC is displayed on the LCD display in scrolling
mode, alongwith other alarm messages under the following two conditions
3.2.2.1.
There is an internal RTC mismatch. The User must reprogram the RTC
values as explained under Section 3.4.2 RTC. Once reprogramed, the
RTC status message will disappear.
3.2.2.2.
The internal Battery voltage has dropped below operational level.
Please call FM Service Engineer.
3.3. RESET TOTALIZER: This function is used for resetting the Blowdown Totalizer, Heat
Totalizer, Number of Purge Cycles and % Blowdown of the selected boiler. Use
the PURGE key to select the boiler. Once selected, press the ENT key for resetting
the corresponding boiler data. After completion of the reset process RESET
COMPLETE message is displayed on LCD display.
3.4. SERVICE/RTC/SP: This has 3 options 3.4.1. SERVICE: Service menu is password protected and can be accessed only
by FM Service Engineer.
3.4.2. RTC (REAL TIME CLOCK): This parameter is used to set the RTC related
parameters. When the Controller is switched on for the first time the user has
to set the RTC. Later, the user can set the RTC parameters whenever
required. For setting the RTC please follow these steps.
1 Select SERVICE/RTC/SP option from the main programming
parameters menu & press ENT key.
2 Select RTC by PURGE key and press the ENT key. RTC parameter
screen will be displayed on the display.
3 Select the parameter by UP or DN key and press ENT key for
changing the particular parameter.
4 After pressing the ENT key use PURGE or Up or DN key to set the
value for that parameter.
5 After setting the value press ENT key, the entered value will get set
for that parameter.
6 Set Hours, Minutes, Seconds, Day, Date, and Month & Year by
following the above procedure.
3.4.3
SP (TDS SET POINT): It is recommended that the TDS value specified by the
boiler manufacturer is set from Boiler Efficiency perspective. The Blowdown
action takes place based on this set value. The procedure for boiler set
point is as follows:
1 Select SERVICE/RTC/SP option from the main programming
parameter menu.
2 Select SP option by using PURGE key and press ENT key. Set point
screen will be displayed on the display.
29
3
4
5
6
30
(10)6 * 0.5
10 If the computed K factor is within the limit (0.2 to 0.8 for Boiler Blowdown &
0.08 to 0.12 for Feed water) then CALIBRATION VALID message will be
displayed on the display else CALIBRATION INVALID message will be
displayed. In both the cases the calculated K factor is displayed on the
display. If calibration is valid then new calibrated value will be saved into
the non-volatile memory and considered for further processing. If the
calibration is invalid the last calibrated value will be considered for the
further processing. If the user is doing the calibration for the first time,
default K values of 0.5 for Boiler Blowdown and 0.1 for feed water are
considered for the calculations respectively.
11 If calibration is valid, please mark the channel details clearly on the
respective Sensor. Mentioning the channel name on the sensor in
mandatory.
12 Repeat the steps 1 to 11 for all channels (BLR1, BLR2, BLR3, and FW) as
necessary.
31
4 Spares
We recommend you the following spares for uninterrupted performance.
1) CPU PCB assembly
2) SMPS PCB assembly
3) Terminal PCB assembly
4) Fuse 500 mA Slow Blow 20mm glass cartridge for F1 on Terminal PCB
5) Fuse 1 A Slow Blow 20mm glass cartridge for Blowdown and BHRS
solenoid
6) Feed water Sensor
7) CP10 Sensor
8) PT100 Sensor
32
5 Service
5.1 Field service
In most of the cases, the problems can be identified by following the
instructions in the troubleshooting section. If ABCO plus Controller is still
not functioning to your complete satisfaction please contact your
nearest FM representative.
ABCO plus system is sold with 1 year warranty period for manufacturing
defects or malfunctions. During this period all the spares will be
replaced free of charge. In cases where damage has been caused
due to improper use of the product, Spirax Marshall can not be
responsible for the replacement.
Please ensure that the records of all service calls are maintained by
our service personnel in the Field Service Record section of this
manual.
5.2 Field service record
This record must be updated by the FM Service Engineer for all instances
of the field service problems and actions taken.
Date
Reported problem
Action taken
33
FM Engineer
34
Reported problem
Action taken
35
FM Engineer