Introduction
Often it is a requirement, that a quick estimate of the
Total Harmonic Voltage Distortion (THVD) be made.
This document presents a simple method of
estimating the voltage distortion caused by a nonlinear load such as a VLT Drive. The method takes
all the ac-side reactances (X) into account and the
effect of inserting an ac-side reactor can thus also be
evaluated.
XHV
PCC
XXFR
XCABLE
XAC
Non-linear load
Distribution Transformer
Definitions
The Total Harmonic Voltage Distortion is dependent
on the individual voltage drops (Vh) at all harmonic
frequencies (h) is defined as:
V
THVD = h
h = 2 V1
h = 40
THVD =
h X 1 Ih
X
100% = 1
V1
V1
h= 2
(h I )
h= 2
100% =
1
I sc
(h I )
h= 2
100%
I
H c = h h 100%
h=2 I 1
Equation 3: Definition of Harmonic Constant
Using this definition, THVD can be estimated based
on active power drive load (PVLT) and Short Circuit
Power (SSC) at PCC as
THVD = Hc
PVLT
[% ]
S SC
550
1400
500
1200
450
1000
400
HC
[%]
HC
[%]
350
300
800
600
HC=280-15*Lac
250
HC=425-30*Lac
400
200
200
150
100
10
Xtot [%]
Z B, VLT
10
Xtot [%]
2
Vnom
=
PVLT
nominal line-line rms voltage and the total threephase power. If the reactances of the system
(XHV,XXFR and XCABLE) are expressed on another perunit basis than the VLT drive per-unit, they have to
be transformed into the VLT-per-unit system. This is
done by multiplying the per-unit impedances by
multiplying the per-unit impedances by the ratio
Z B,OTHER
Z B,VLT
illustrated by an example.
using the
Example Calculation
ZMV
Ssc=100 MVA
Distribution Transformer
10/0.4 kV
Cable
500 kVA
er=1.1%
ex=4.9%
150 m
290 mm2 Cu
X=0.1/km
Optional 4%
ac- choke
S sc , XFR =
Snom, XFR
eX
500.000
0,049
= 10.20 MVA
THVD XFR = H c
PVLT
200e3
= 220
S SC
10.20e6 =
4.31%
THVD XFR = H c
PVLT
200e3
= 160
S SC
10.20e6 = 3.14%
THVD MV = Hc
PVLT
200e3
= 220
S SC
100e6
= 0.44%
THVD MV = H c
PVLT
200e3
= 160
S SC
100e6
= 0.32%