Vous êtes sur la page 1sur 26

Chapter 2

Instruction for use IM & QM Cubicle


Cibitung, 2 5 March 2015

Chapter 2 : Instruction for use IM & QM


General Description

Schneider Electric - Services Division SM6 Cubicle Training March 2015

IM Switch cubicle
1. Bus bar compartment
2. LV compartment
3. Switch & earthing switch
4. Operating mechanism compartment
5. Cable compartment
A. Earth bar connection
B. Bus bar connection
C. Cable connection
D. Voltage indicator
E. Capacitive divider
F. Front panel
G. Inspection windows

Schneider Electric - Services Division SM6 Cubicle Training March 2015

QM Fused switch combination cubicle


1.
2.
3.
4.
A.
B.
C.
D.
E.
F.
G.
H.
I.

Schneider Electric - Services Division SM6 Cubicle Training March 2015

Bus bar compartment


LV compartment
Switch & earthing switch
Operating mechanism compartment
Earth bar connection
Bus bar connection
Voltage indicator
Tripping unit
Front panel
Cable connection
Inspection windows
Capacitive divider
Earthing switch

Chapter 2 : Instruction IM & QM


Installation

Schneider Electric - Services Division SM6 Cubicle Training March 2015

MV cable connection for QM/IM cubicle

Open the earthing


switch using the
operating lever

Fit the cable in same


order as for the IM
cubicle. Use a torque
wrench and a 16 mm
socket to tighten the
bolts. Tightening
torque : 50 Nm

Schneider Electric - Services Division SM6 Cubicle Training March 2015

Close the earthing switch

Chapter 2 : Instruction IM & QM


Operation Instruction

Schneider Electric - Services Division SM6 Cubicle Training March 2015

Operating instructions
IM and QM: operation and position indication

Schneider Electric - Services Division SM6 Cubicle Training March 2015

Continued ...

Schneider Electric - Services Division SM6 Cubicle Training March 2015

Continued ...

Schneider Electric - Services Division SM6 Cubicle Training March 2015

10

Continued ...

Schneider Electric - Services Division SM6 Cubicle Training March 2015

11

Continued ...

Schneider Electric - Services Division SM6 Cubicle Training March 2015

12

Fuse indications on QM cubicles

Schneider Electric - Services Division SM6 Cubicle Training March 2015

13

Discharging a CI2 operating mechanism

Cubicle de-energized:
Close the switch: button A
Then open : button B
(CIT operating mechanism)

Schneider Electric - Services Division SM6 Cubicle Training March 2015

Cubicle energized:
Press the open button B.
Attention: this operation can
damage the operating mechanism
perform only when stricly necessary.

14

Padlocking

Schneider Electric - Services Division SM6 Cubicle Training March 2015

15

Continued ...

Schneider Electric - Services Division SM6 Cubicle Training March 2015

16

Operating safety

Schneider Electric - Services Division SM6 Cubicle Training March 2015

17

Chapter 2 : Instruction IM & QM


Start-up Instruction

Schneider Electric - Services Division SM6 Cubicle Training March 2015

18

Check before energizing


Check that nothing has been left in the compartment, for all phases :
Check that the fuse has been properly fitted
Check that the field distributor covers have been properly closed on all
phases
Check that the fault detector has been properly connected

Schneider Electric - Services Division SM6 Cubicle Training March 2015

19

Operating test before energizing

Operate the switch several


times

Schneider Electric - Services Division SM6 Cubicle Training March 2015

Operate the earthing switch


several times

20

Voltage indicator

As soon as the cables have been energized, the


voltage indicator lamp should go on

Schneider Electric - Services Division SM6 Cubicle Training March 2015

21

Chapter 2 : Instruction IM & QM


Maintenance

Schneider Electric - Services Division SM6 Cubicle Training March 2015

22

Preventive maintenance
Never lubricate the operating mechanism
No particular maintenance is required under normal operating
conditions (temperature between 5 oC and 40 oC).
For severe operating conditions (aggressive environment, dust,
temperature below 5 oC or above 40 oC, etc.), please consult
Schneider Electric

Schneider Electric - Services Division SM6 Cubicle Training March 2015

23

Corrective maintenance
Replacing the fuses
The cubicle must be de-energized
The switch must be opened
The earthing switch must be closed
Open the front panel for access to the fuses

Important :
Standard IEC 282.1 & 23.2 states that all three of the MV fuses
should be changed whenever one of them blows.

Schneider Electric - Services Division SM6 Cubicle Training March 2015

24

Replacing a voltage indicator block


Pull out the voltage indicator block. The cubicle can remain energize.

Schneider Electric - Services Division SM6 Cubicle Training March 2015

25

End Presentation

Schneider Electric - Services Division SM6 Cubicle Training March 2015

26