Selecting a Fan
Select a fan using the required air flow. The air flow of a mounted
fan can be found from the air flow static pressure characteristics
and the pressure loss of the machinery. It is difficult to calculate the
pressure loss of the machinery, so a fan with a maximum air flow of
1.3 to 2 times as the required air flow may be used.
Width 700 mm
Height 1000 mm
Depth 400 mm
Linear &
Rotary
Actuators
2.37 m2
SPCC
5 W/ (m2/K)
Cooling
Fans
Pressure Loss
Servo
Motors
Standard
AC
Motors
Brushless
Motors/AC
Speed Control
Motors
Gearheads
Cooling
Fans
Obtaining by a Graph
Search for the cross point A between heat generation Q (450 W)
and permissible temperature rise T (20C).
Draw a line parallel with the horizontal axis from point A.
Search for the cross point B between the parallel line and surface
area S (2.37 m2) line.
Draw a line perpendicular to the horizontal axis from point B.
Required air flow is approximately 0.5 m3/min.
Allow for a safety factor (Sf ) of 2 times. Required air flow will be
1.00 m3/min.
0
10 9
8
6
4
2
0
7
5
3
1
Heat Radiation Area S [m2]
10
Permissible Temperature Rise T [C]
Stepper
Motors
Service
Life
450 W
60 Hz 115 VAC
20C
Ambient temperature T1: 25C
Internal permissible temperature T2: 45C
Operating Point
Surface Area
Material
Overall Heat Transfer Coefficient
W
H
D
V = 1 20 (Q T U S) Sf
= 1 20 (450 20 5 2.37) 2
1.07 [m3/min]
Motors
Obtaining by Calculations
Control
Box
Specifications
Factory Floor
Selection
Calculations
15
20
25
30
A
1500
1000
500
Applicable Fans
Based on the above, MU Series MU925M-21 is selected.
Select a fan
Select a fan with a maximum air ow of 1.3 to 2 times as the
required air ow.
MU925M-21 Specifications
Input Voltage
VAC
Single-Phase 115
CAD Data
Manuals
www.orientalmotor.com
Technical
Support
Frequency Input Current Speed Max. Air Flow Max. Static Pressure Noise Level
Hz
W
A
r/min
m3/min
Pa
dB (A)
60
0.1
2700
44
36
H-29