Miniature Power Relays

MY
CSM_MY_DS_J_7_3

New Latching Levers for Circuit Checking


Added to Our Best-selling
MY General-purpose Relays
Now lead-free to protect the environment.
VDE certification (Germany).
Different colors of coil tape for AC and
DC models to more easily distinguish them.
MY(S) models with latching levers added for
easier circuit checking.

Refer to the Common Relay Precautions.

Model Number Structure


Relays with Plug-in Terminals

PCB terminals

Structure
Number of
poles

Classification

MY2N*

2
Standard models (compliant with
Electrical Appliances and
Material Safety Act)

With operation
indicator

MY2*

Bifurcated MY2ZN

MY2-02

MY2F

MY2Z
MY3

MY3-02

MY3F

MY4N*

MY4*

MY4IN(S)*

MY4-02

MY4F

MY4Z*

MY4ZIN(S)*

MY4Z-02

MY4ZF

MY2-D*

MY2IN-D2(S)*

MY2N-D2*
Bifurcated MY2ZN-D2

MY2Z-D

MY3N-D2

MY3-D

MY4N-D2*

MY4-D*

MY4IN-D2(S)*

Bifurcated MY4ZN-D2*

MY4Z-D*

MY4ZIN-D2(S)*

MY2N-CR*

MY2-CR*

MY4N-CR*

MY4-CR*

MY4IN-CR(S)*

MY4Z-CR*

MY4ZIN-CR(S)*

Bifurcated MY4ZN-CR*
Models with high contact
reliability

MY2IN(S)*

MY3N

Bifurcated MY4ZN*

Models with CR circuit for coil


surge absorption (AC coil
specification only)

With latching lever

2
Models with diode for coil surge
absorption (DC coil specification
only)

Without operation
indicator

Case-surface
mounting

4 Bifurcated

--MYQ4N

---

---

---

MY4Z-CBG
MYQ4

MYQ4-02

Plastic sealed models


Bifurcated
Latching models (coil latching)

MYQ4Z

MYQ4Z-02

MY2K

MY2K-02

MY4H

MY4H-0

MY4ZH

MY4ZH-0

Hermetic models
Bifurcated

Note: 1. The models in this table are UL/CSA certified. This is indicated with a certification mark on the products.
(This does not include models with high contact reliability or plastic sealed, latching, or hermetically sealed models.)
2. Models with an asterisk (*) next to them are new versions.
3. The standard models with plug-in terminals, models with coil surge absorption diodes, and models with coil surge absorption CR circuits were used in
combination with the PYF-E and PYFS (2-pole and 4-pole) for the EC Declaration of Conformity. These products display the CE Marking.
4. Products cannot be manufactured for the cells with a diagonal line. Ask your OMRON representative for details on manufacturing products for cells containing
--- in the above table.

Refer to Connection Socket and Mounting Bracket Selection Table on page 33 in Options for information on the
possible combinations of Models with Plug-in Terminals and Sockets.

MY

Miniature Power Relays: MY2


Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.

Ordering Information

When your order, specify the rated voltage.

Classification

Rated voltage (V)

Model

Standard products

Made-to-order items

12, 24, 100/110, or 200/220 VAC

110/120 or 220/240 VAC

Standard models

MY2

Models with built-in operation indicators

MY2N

Models with built-in diodes

MY2-D

12, 24, or 100/110 VDC

Models with built-in diodes and operation


indicators

MY2N-D2

12, 24, 48, or 100/110 VDC

Models with built-in CR circuits

MY2-CR

100/110 or 200/220 VAC

110/120 or 220/240 VAC

Models with built-in CR circuits and operation


indicators

MY2N-CR

100/110 or 200/220 VAC

110/120 or 220/240 VAC

12, 24, 48, or 100/110 VDC


12, 24, 100/110, 110/120, 200/220, or 220/240 VAC
12, 24, 48, or 100/110 VDC
48 VDC

Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than
the above coil specifications.
3. The above models and specifications are new versions in the MY Series.
4. Except for MY2(N)-CR Relays with the above voltage specifications, all Relays have a height of 53 mm or less.
If Mounting Brackets are required, refer to page 33 for selection information.

Ratings and Specifications


Ratings
Operating Coils (Standard Models)
Item

Rated current (mA)

Rated
voltage (V)

50 Hz

60 Hz

Coil resistance
()

12

106.5

91

24

53.8

46

100/110

11.7/12.9

110/120

9.9/10.8

200/220

6.2/6.8

220/240

4.8/5.3

AC

DC

Coil inductance (H)


Armature
OFF

Armature
ON

46

0.17

0.33

180

0.69

1.3

10/11

3,750

14.54

24.6

8.4/9.2

4,430

19.2

32.1

5.3/5.8

12,950

54.75

94.07

4.2/4.6

18,790

83.5

136.4
1.37

12

72.7

165

0.73

24

36.3

662

3.2

5.72

48

17.6

2,725

10.6

21.0

100/110

8.7/9.6

11,440

45.6

86.2

Mustoperate
voltage (V)

Mustrelease
voltage (V)

Maximum
voltage (V)

Power consumption
(VA, W)
Approx. 1.0 to 1.2
(at 60 Hz)

30% min. *2
110% of rated
voltage

80% max. *1

10% min. *2

Approx. 0.9 to 1.1


(at 60 Hz)

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value (at a coil temperature of +23 C).
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.

Contact Ratings
Load
Item

Resistive load

Rated load

5 A at 220 VAC
5 A at 24 VDC

Rated carry current

5A

Maximum contact voltage

250 VAC, 125 VDC

Maximum contact current

5A

Contact configuration

DPDT

Contact structure

Single

Contact materials

Ag

Inductive load
(cos = 0.4, L/R = 7 ms)
2 A at 220 VAC
2 A at 24 VDC

Type
Item

Standard
models

Ambient
operating
temperature*1

55 to 70C

Ambient
operating
humidity

5% to 85%

Model with built-in operation


indicator, diode, or CR circuit
55 to 60C*2

*1. With no icing or condensation.


*2. This limitation is due to the diode junction temperature and elements used.

MY
Characteristics
Item

Type

Standard
models

Models with builtin operation


indicators

Contact resistance*1

50 m max.

Operation time*2

20 ms max.

Release time*2

20 ms max.

Maximum
operating
frequency

18,000 operations/h

Mechanical
Rated load

Models with
built-in CR
circuits

Models with
built-in
diodes

Model with built-in


operation indicator
and diode

Model with built-in


operation indicator
and CR circuit

1,800 operations/h

Insulation resistance*3

100 M min.

Between coil and contacts


Dielectric
strength

Between contacts of
different polarity

2,000 VAC at 50/60 Hz for 1 min.

Between contacts of the


same polarity

1,000 VAC at 50/60 Hz for 1 min.

Vibration
resistance

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Shock
resistance

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

AC: 50,000,000 operations min.


DC: 100,000,000 operations min.
(switching frequency: 18,000 operations/h)

Electrical*4

500,000 operations min.


(rated load, switching frequency: 1,800 operations/h)

Endurance

Item

Number of poles

2 poles

Failure rate P value


(reference value)*5

1 mA at 5 VDC

Weight

Approx. 35 g

Note: These are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method.
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength
measurement.
*4. Ambient temperature condition: 23C
*5. This value was measured at a switching frequency of 120 operations per minute.

Dimensions

(Unit: mm)

MY2, MY2N, MY2-D, MY2N-D2, MY2-CR,


and MY2N-CR

Terminal Arrangement/Internal Connections


(Bottom View)
Standard Models

MY2N
DC Models

AC Models

2.6

Eight, 1.2-dia. 2.2 oval holes


0.5
28 max.
(The coil has no polarity.)

36 max.

6.4

Check the coil polarity when wiring


and wire all connections correctly.

21.5 max.

(The coil has no polarity.)

Note: 1. An AC model has coil disconnection selfdiagnosis.


2. For the DC models, check the coil polarity when
wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.
MY2-D

Check the coil polarity when wiring


and wire all connections correctly.

MY2N-D2

Check the coil polarity when wiring


and wire all connections correctly.

MY2-CR

MY2N-CR

(The coil has no polarity.)

(The coil has no polarity.)

MY

Miniature Power Relays: MY2Z


Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.

Ordering Information

When your order, specify the rated voltage.

Classification

Rated voltage (V)

Model

Standard models

Standard products

Made-to-order items

100/110 or 200/220 VAC

MY2Z

12, 24, 100/120, or 200/240 VAC

12 or 24 VDC

48 or 100/110 VDC

100/110 or 200/220 VAC

12, 24, 100/120, or 200/240 VAC

Models with built-in operation indicators

MY2ZN

24 VDC

12, 48, or 100/110 VDC

Models with built-in diodes

MY2Z-D

24 VDC

12 or 100/110 VDC

Models with built-in diodes and operation


indicators

MY2ZN-D2

24 or 100/110 VDC

12 VDC

Models with built-in CR circuits

MY2Z-CR

Models with built-in CR circuits and operation


indicators

MY2ZN-CR

100/110 or 200/220 VAC


100/110 VAC

200/220 VAC

Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than
the above coil specifications.

Ratings and Specifications


Ratings
Operating Coil (Standard Models)
Item

Rated current (mA)

Coil resistance
()

Coil inductance (H)

Rated
voltage (V)

50 Hz

12

106.5

91

24

53.8

46

100/110

11.7/12.9

10/11

3,750

14.54

24.6

110/120

9.9/10.8

8.4/9.2

4,430

19.2

32.1

200/220

6.2/6.8

5.3/5.8

12,950

54.75

94.07

220/240

4.8/5.3

4.2/4.6

18,790

83.5

136.4
1.37

AC

DC

60 Hz

Armature
OFF

Armature
ON

46

0.17

0.33

180

0.69

1.3

12

75

160

0.73

24

36.9

650

3.2

5.72

48

18.5

2,600

10.6

21.0

100/110

9.1/10

11,000

45.6

86.2

Mustoperate
voltage (V)

Mustrelease
voltage (V)

Maximum
voltage (V)

Power consumption
(VA, W)
Approx. 1.0 to 1.2
(at 60 Hz)

30% min.*2

80% max.

110% of rated
voltage

*1

10% min.*2

Approx. 0.9 to 1.1


(at 60 Hz)

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.

Contact Ratings
Load
Item

Resistive load

Rated load

5 A at 220 VAC
5 A at 24 VDC

Rated carry current

5A

Maximum contact voltage

250 VAC, 125 VDC

Maximum contact current

5A

Contact configuration

DPDT

Contact structure

Bifurcated

Contact materials

Au plating + Ag

Inductive load
(cos = 0.4, L/R = 7 ms)
2 A at 220 VAC
2 A at 24 VDC

Type
Item

Standard
models

Ambient
operating
temperature*1

55 to 70 C

Ambient
operating
humidity

5% to 85%

Model with built-in operation


indicator, diode, or CR circuit
55 to 60 C*2

*1. With no icing or condensation.


*2. This limitation is due to the diode junction temperature and elements used.

MY
Characteristics
Item

Type

Standard
models

Models with builtin operation


indicators

Contact resistance*1

50 m max.

Operation time*2

20 ms max.

Release time*2

20 ms max.

Maximum
operating
frequency

18,000 operations/h

Mechanical
Rated load

Models with
built-in
diodes

Model with built-in


operation indicator
and diode

Models with
built-in CR
circuits

Models with built-in


CR circuits and
operation indicators

1,800 operations/h

Insulation resistance*3

100 M min.

Between coil and contacts


Dielectric
strength

Between contacts of
different polarity

2,000 VAC at 50/60 Hz for 1 min.

Between contacts of the


same polarity

1,000 VAC at 50/60 Hz for 1 min.

Vibration
resistance

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Shock
resistance

Destruction

1,000 m/s2

Malfunction

200 m/s2

Endurance

Item

Mechanical

50,000,000 operations min. (operating frequency: 18,000 operations/h)

Electrical*4

200,000 operations min. (rated load, switching frequency: 1,800 operations/h)

Number of poles

Failure rate P value


(reference value)*5
Weight

2 poles

Note: These are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method.
100 A at 1 VDC *2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
Approx. 35 g
*4. Ambient temperature condition: 23C
*5. This value was measured at a switching frequency of 120 operations per minute.

Dimensions

(Unit: mm)

MY2Z, MY2ZN, MY2Z-D, MY2ZN-D2, MY2Z-CR,


and MY2ZN-CR

Terminal Arrangement/
Internal Connections
(Bottom View)
Standard Models

MY2ZN
DC Models

AC Models

2.6

Eight, 1.2-dia. 2.2 oval holes


0.5
28 max.
(The coil has no polarity.)

36 max.

6.4

Check the coil polarity when wiring


and wire all connections correctly.

21.5 max.

* For the MY2Z-CR and MY2ZN-CR,


this dimension is 53 mm max.

MY2Z-D

(The coil has no polarity.)

Note: 1. An AC model has coil disconnection selfdiagnosis.


2. For the DC models, check the coil polarity when
wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.
MY2ZN-D2

MY2Z-CR

MY2ZN-CR
1

Check the coil polarity when wiring


and wire all connections correctly.

Check the coil polarity when wiring


and wire all connections correctly.

(The coil has no polarity.)

12

13

14

(The coil has no polarity.)

MY

Miniature Power Relays: MY3


Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.

Ordering Information

When your order, specify the rated voltage.

Classification

Rated voltage (V)

Model

Standard models

Standard products

Made-to-order items

24, 100/110, 200/220, or 220/240 VAC

MY3

12, or 110/120 VAC

12, 24, or 100/110 VDC

48 VDC

24, 100/110, 200/220, or 220/240 VAC

12, or 110/120 VAC

Models with built-in operation indicators

MY3N

24 VDC

12, 48, or 100/110 VDC

Models with built-in diodes

MY3-D

24 VDC

12 or 100/110 VDC

Models with built-in diodes and operation


indicators

MY3N-D2

24 VDC

12 or 100/110 VDC

Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.

Ratings and Specifications


Ratings
Operating Coil (Standard Models)
Item

Rated current (mA)

Coil resistance
()

Coil inductance (H)

Rated
voltage (V)

50 Hz

12

106.5

91

24

53.8

46

100/110

11.7/12.9

10/11

3,750

14.54

24.6

110/120

9.9/10.8

8.4/9.2

4,430

19.2

32.1

200/220

6.2/6.8

5.3/5.8

12,950

54.75

94.07

220/240

4.8/5.3

4.2/4.6

18,790

83.5

136.4
1.37

AC

DC

60 Hz

Armature
OFF

Armature
ON

46

0.17

0.33

180

0.69

1.3

12

75

160

0.73

24

36.9

650

?3.2

5.72

48

18.5

2,600

10.6

21.0

100/110

9.1/10

11,000

45.6

86.2

Mustoperate
voltage (V)

Mustrelease
voltage (V)

Maximum
voltage (V)

Power consumption
(VA, W)
Approx. 1.0 to 1.2
(at 60 Hz)

30% min.*2
110% of rated
voltage

80% max.*1

10% min.*2

Approx. 0.9 to 1.1


(at 60 Hz)

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.

Contact Ratings
Load
Item

Resistive load

Rated load

5 A at 220 VAC
5 A at 24 VDC

Rated carry current

5A

Maximum contact voltage

250 VAC, 125 VDC

Maximum contact current

5A

Contact configuration

3PDT

Contact structure

Single

Contact materials

Ag

Inductive load
(cos = 0.4, L/R = 7 ms)
2 A at 220 VAC
2 A at 24 VDC

Type
Item

Standard
models

Ambient
operating
temperature*1

55 to 70 C

Ambient
operating
humidity

5% to 85%

Operation indicator and diode


55 to 60 C*2

*1. With no icing or condensation.


*2. This limitation is due to the diode junction temperature and elements used.

MY
Characteristics
Item

Type

Contact resistance*1

50 m max.

Operation time*2

20 ms max.

Release time*2

20 ms max.

Maximum
operating
frequency

Mechanical

18,000 operations/h

Rated load

1,800 operations/h

Insulation resistance*3

Models with built-in


operation indicators

Standard models

Models with built-in


diodes

Model with built-in operation


indicator and diode

100 M min.

Between coil and contacts


Dielectric
strength

2,000 VAC at 50/60 Hz for 1 min.

Between contacts of
different polarity
Between contacts of the
same polarity

1,000 VAC at 50/60 Hz for 1 min.

Vibration
resistance

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Shock
resistance

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

AC: 50,000,000 operations min.


DC: 100,000,000 operations min.
(switching frequency: 18,000 operations/h)

Electrical*4

500,000 operations min. (rated load, switching frequency: 1,800 operations/h)

Endurance

Item

Number of poles

3 poles

Failure rate P value


(reference value)*5

1 mA at 5 VDC

Weight

Approx. 35 g

Note: These are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23C
*5. This value was measured at a switching frequency of 120 operations per minute.

Dimensions

(Unit: mm)

MY3, MY3N, MY3-D, and MY3N-D2

Terminal Arrangement/
Internal Connections
(Bottom View)
Standard Models

MY3N
DC Models

AC Models

2.6

Eleven, 1.2-dia. 2.2 oval holes


0.5
28 max.
6.3

(The coil has no polarity.)

0.5
36 max.

6.4

21.5 max.

Check the coil polarity when wiring


and wire all connections correctly.

(The coil has no polarity.)

Note: 1. An AC model has coil disconnection selfdiagnosis.


2. For the DC models, check the coil polarity
when wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.
MY3-D

Check the coil polarity when wiring


and wire all connections correctly.

MY3N-D2

Check the coil polarity when wiring


and wire all connections correctly.

MY

Miniature Power Relays: MY4


Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.

Ordering Information

When your order, specify the rated voltage.

Classification

Rated voltage (V)

Model

Standard products

Made-to-order items

24, 100/110, or 200/220 VAC

12, 110/120, or 220/240 VAC

Standard models

MY4

Models with built-in operation indicators

MY4N

Models with built-in diodes

MY4-D

12, 24, 48, or 100/110 VDC

Models with built-in diodes and operation


indicators

MY4N-D2

12, 24, or 100/110 VDC

48 VDC

Models with built-in CR circuits

MY4-CR

100/110 or 200/220 VAC

110/120 or 220/240 VAC

Models with built-in CR circuits and operation


indicators

MY4N-CR

100/110, 110/120, or 200/220 VAC

220/240 VAC

12, 24, 48, or 100/110 VDC


12, 24, 100/110, 110/120, 200/220, or 220/240 VAC
12, 24, 48, or 100/110 VDC

Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.
3. The above models and specifications are new versions in the MY Series.
4. Except for MY4(N)-CR Relays with the above voltage specifications, all Relays have a height of 53 mm or less.
If Mounting Brackets are required, refer to page 33 for selection information.

Ratings and Specifications


Ratings
Operating Coil (Standard Models)
Item

Rated current (mA)

Coil resistance
()

Coil inductance (H)

Rated
voltage (V)

50 Hz

12

106.5

91

24

53.8

46

100/110

11.7/12.9

10/11

3,750

14.54

24.6

110/120

9.9/10.8

8.4/9.2

4,430

19.2

32.1

200/220

6.2/6.8

5.3/5.8

12,950

54.75

94.07

220/240

4.8/5.3

4.2/4.6

18,790

83.5

136.4

AC

DC

60 Hz

Armature
OFF

Armature
ON

46

0.17

0.33

180

0.69

1.3

12

72.7

165

0.73

1.37

24

36.3

662

3.2

5.72

48

17.6

2,725

10.6

21.0

100/110

8.7/9.6

11,440

45.6

86.2

Mustoperate
voltage (V)

Mustrelease
voltage (V)

Maximum
voltage (V)

Power consumption
(VA, W)
Approx. 1.0 to 1.2
(at 60 Hz)

30% min.*2
110% of rated
voltage

80% max.*1

10% min.*2

Approx. 0.9 to 1.1


(at 60 Hz)

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.

Contact Ratings
Load
Item

Resistive load

Inductive load
(cos = 0.4, L/R = 7 ms)

Rated load

3 A at 220 VAC
3 A at 24 VDC

0.8 A at 220 VAC


1.5 A at 24 VDC

Rated carry current

3A

Maximum contact voltage

250 VAC, 125 VDC

Maximum contact current

3A

Contact configuration

4PDT

Contact structure

Single

Contact materials

Au cladding + Ag alloy

Type
Item
Ambient
operating
temperature*1
Ambient
operating
humidity

Standard
models
55 to 70 C

Model with built-in operation


indicator, diode, or CR circuit
55 to 60 C*2

5% to 85%

*1. With no icing or condensation.


*2. This limitation is due to the diode junction temperature and elements used.

MY
Characteristics
Item

Standard
models

Type

Contact resistance*1

50 m max.

Operation time*2

20 ms max.

Models with builtin operation


indicators

Release time*2

20 ms max.

Maximum
operating
frequency

Mechanical

18,000 operations/h

Rated load

1,800 operations/h

Insulation resistance*3

Models with
built-in CR
circuits

Models with
built-in
diodes

Model with built-in


operation indicator
and diode

Model with built-in


operation indicator
and CR circuit

100 M min.

Between coil and contacts


Dielectric
strength

2,000 VAC at 50/60 Hz for 1 min.

Between contacts of
different polarity
Between contacts of the
same polarity

1,000 VAC at 50/60 Hz for 1 min.

Vibration
resistance

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Shock
resistance

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

AC: 50,000,000 operations min.


DC: 100,000,000 operations min.
(switching frequency:: 18,000 operations/h)

Electrical*4

200,000 operations min.


(rated load, switching frequency: 1,800 operations/h)

Endurance

ItemNumber of poles

4 poles

Failure rate P value


(reference value)*5

1 mA at 1 VDC

Weight

Approx. 35 g

Note: These are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23 C
*5. This value was measured at a switching frequency of 120 operations per minute.

Engineering Data
List of Actual Load Endurance (Refer to Engineering Data on page 20.)
Model

Load type

AC magnetic switch

MY4 DC24V
DC solenoid

Conditions

Switching frequency

Electrical durability
(operations min.)

35 VA at 100 VAC
ON: 1s
Making current: 4 A,
OFF: 3s
Steady-state current: 0.35 A

500,000

40 W at 24 VDC
Steady-state current:
ON: 0.5s
1.6 A, L/R = 10 ms
OFF: 1.5s
Surge-absorbing diode connected

500,000

20 W at 24 VDC
ON: 0.5s
Steady-state current:
OFF: 1.5s
0.8 A, L/R = 10 ms
Surge-absorbing diode connected

1,000,000

MY

Dimensions

(Unit: mm)

MY4, MY4N, MY4-D, MY4N-D2,


MY4-CR, and MY4N-CR

MY4N
Terminal Arrangement/
Internal Connections
(Bottom View)
Standard Models

DC Models

AC Models

2.6

Fourteen, 1.2-dia. 2.2 oval holes


0.5
28 max.
Check the coil polarity when wiring
and wire all connections correctly.

(The coil has no polarity.)

(The coil has no polarity.)

36 max.

6.4
21.5 max.

MY4-D

Check the coil polarity when wiring


and wire all connections correctly.

MY4N-D2

Check the coil polarity when wiring


and wire all connections correctly.

Note: 1. An AC model has coil disconnection selfdiagnosis.


2. For the DC models, check the coil polarity when
wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.
MY4-CR
MY4N-CR

(The coil has no polarity.)

(The coil has no polarity.)

10

MY

Miniature Power Relays: MY4Z


Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.

Ordering Information

When your order, specify the rated voltage.

Classification

Rated voltage (V)

Model

Standard models

MY4Z

Models with built-in operation indicators

MY4ZN

Models with built-in diodes

Standard products

Made-to-order items

100/110 or 200/220 VAC

110/120 or 220/240 VAC

12, 24, 48, or 100/110 VDC


100/110 or 200/220 VAC

24, 110/120, or 220/240 VAC

24 or 100/110 VDC

12 or 48 VDC

MY4Z-D

24 or 100/110 VDC

12 or 48 VDC

Models with built-in diodes and operation


indicators

MY4ZN-D2

12, 24, 48, or 100/110 VDC

Models with built-in CR circuits

MY4Z-CR

100/110 or 200/220 VAC

110/120 or 220/240 VAC

Models with built-in CR circuits and operation


indicators

MY4ZN-CR

100/110 or 200/220 VAC

110/120 or 220/240 VAC

Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.
3. The above models and specifications are new versions in the MY Series.

Ratings and Specifications


Ratings
Operating Coil (Standard Models)
Item

Rated current (mA)

Coil resistance
()

Coil inductance (H)

Rated
voltage (V)

50 Hz

12

106.5

91

24

53.8

46

100/110

11.7/12.9

10/11

3,750

14.54

24.6

110/120

9.9/10.8

8.4/9.2

4,430

19.2

32.1

200/220

6.2/6.8

5.3/5.8

12,950

54.75

94.07

220/240

4.8/5.3

4.2/4.6

18,790

83.5

136.4
1.37

AC

DC

60 Hz

Armature
OFF

Armature
ON

46

0.17

0.33

180

0.69

1.3

12

72.7

165

0.73

24

36.3

662

3.2

5.72

48

17.6

2,725

10.6

21.0

100/110

8.7/9.6

11,440

45.6

86.2

Mustoperate
voltage (V)

Release
voltage (V)

Maximum
voltage (V)

Power consumption
(VA, W)
Approx. 1.0 to 1.2
(at 60 Hz)

30% min.*2
110% of rated
voltage

80% max.*1

10% min.*2

Approx. 0.9 to 1.1


(at 60 Hz)

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.

Contact Ratings
Load
Item

Resistive load

Inductive load
(cos = 0.4, L/R = 7 ms)

Rated load

3 A at 220 VAC
3 A at 24 VDC

0.8 A at 220 VAC


1.5 A at 24 VDC

Rated carry current

3A

Maximum contact voltage

250 VAC, 125 VDC

Maximum contact current

3A

Contact configuration

4PDT

Contact structure

Bifurcated

Contact materials

Au cladding + Ag alloy

Type
Item

Standard
models

Ambient
operating
temperature*1

55 to 70 C

Ambient
operating
humidity

5% to 85%

Model with built-in operation


indicator, diode, or CR circuit
55 to 60 C

*1. With no icing or condensation.


*2. This limitation is due to the diode junction temperature and elements used.

11

MY
Characteristics
Item

Type

Standard
models

Models with builtin operation


indicators

Contact resistance*1

50 m max.

Operation time*2

20 ms max.

Release time*2

20 ms max.

Maximum
operating
frequency

Mechanical

18,000 operations/h

Rated load

1,800 operations/h

Insulation resistance

*3

Models with
built-in CR
circuits

Models with
built-in
diodes

Model with built-in


operation indicator
and diode

Model with built-in


operation indicator
and CR circuit

100 M min.

Between coil and contacts


Dielectric
strength

Between contacts of
different polarity

2,000 VAC at 50/60 Hz for 1 min.

Between contacts of the


same polarity

1,000 VAC at 50/60 Hz for 1 min.

Vibration
resistance

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Shock
resistance

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

20,000,000 operations min.


(switching frequency: 18,000 operations/h)

Electrical*4

100,000 operations min.


(rated load, switching frequency: 1,800 operations/h)

Endurance

Item

Number of poles

Failure rate P value


(reference value)*5
Weight

4 poles

Note: These are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
100 A at 1 VDC *2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength
Approx. 35 g
measurement.
*4. Ambient temperature condition: 23 C
*5. This value was measured at a switching frequency of 120 operations per minute.

Dimensions

(Unit: mm)

MY4Z, MY4ZN, MY4Z-D, MY4ZN-D2,


MY4Z-CR, and MY4ZN-CR

MY4ZN
DC Models

AC Models

Terminal Arrangement/
Internal Connections
(Bottom View)
Standard Models
2.6

Fourteen, 1.2-dia. 2.2 oval holes


0.5
28 max.

Check the coil polarity when wiring


and wire all connections correctly.

(The coil has no polarity.)

(The coil has no polarity.)

36 max.

Note: 1. An AC model has coil disconnection selfdiagnosis.


2. For the DC models, check the coil polarity when
wiring and wire all connections correctly.
3. The indicator is red for AC and green for DC.
4. The operation indicator indicates the
energization of the coil and does not represent
contact operation.

6.4
21.5 max.

MY4Z-D

Check the coil polarity when wiring


and wire all connections correctly.

MY4ZN-D2

Check the coil polarity when wiring


and wire all connections correctly.

MY4Z-CR

MY4ZN-CR

(The coil has no polarity.)

(The coil has no polarity.)

12

MY

Miniature Power Relays with Latching Levers: MY(S)

LR

Refer to the standards certifications and compliance


section of your OMRON website for the latest
information on certified models.

Ordering Information
Classification

Be sure to clearly indicate the rated voltage and add (S) when you place your order.
Example: MY2IN 110/110 VAC (S)

Contact configuration

2
Models with built-in operation
indicators

Standard products

MY2IN (S)

MY4IN (S)

Made-to-order items

---

100/110 or 200/220 VAC

12, 24, or 48 VDC

---

---

100/110 or 200/220 VAC

12, 24, or 48 VDC

---

---

100/110 or 200/220 VAC

---

12, 24, or 48 VDC


48 VDC

4 bifurcated

MY4ZIN (S)

MY2IN-D2 (S)

12 or 24 VDC

MY4IN-D2 (S)

24 VDC

12 or 48 VDC

4 bifurcated

MY4ZIN-D2 (S)

24 VDC

12 or 48 VDC

Models with built-in diode for


coil surge absorption
Models with built-in CR circuit
for coil surge absorption

Rated voltage (V)

Model

MY4IN-CR (S)

---

100/110 or 200/220 VAC

4 bifurcated

MY4ZIN-CR (S)

---

100/110 or 200/220 VAC

Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.

Ratings and Specifications


Ratings
Operating Coil
Item

Rated current (mA)

Rated voltage (V)


AC?

50 Hz

60 Hz

Coil inductance (H)

Coil resistance
()

Armature OFF

Armature ON

100/110

11.7/12.9

10/11

3,750

14.54

24.6

200/220

6.2/6.8

5.3/5.8

12,950

54.75

94.07

DC?

12

75

160

0.73

1.37

24

37.7

636

3.2

5.72

48

18.8

2,560

10.6

21

Must-operate
voltage (V)

Must-release
voltage (V)

Maximum
voltage (V)

Approx. 0.9 to
1.1 (at 60 Hz)

30% min.*2
80% max.*1
10% min.*2

Power consumption
(VA, W)

110% of
rated
voltage

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value.
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.

Contact Ratings
Number of poles

2 poles

Load

Resistive load
(cos = 1)

Item
Rated load

5 A at 250 VAC
5 A at 30 VDC

Rated carry current

10 A*

Inductive load (cos


= 0.4, L/R = 7 ms)
2 A at 250 VAC
2 A at 30 VDC

4 poles
Resistive load
(cos = 1)
3 A at 250 VAC
3 A at 30 VDC

Inductive load (cos


= 0.4, L/R = 7 ms)
0.8 A at 250 VAC
1.5 A at 30 VDC

4 poles (bifurcated)
Resistive load
(cos = 1)
3 A at 250 VAC
3 A at 30 VDC

Inductive load (cos


= 0.4, L/R = 7 ms)
0.8 A at 250 VAC
1.5 A at 30 VDC

5 A*

Maximum contact voltage 250 VAC, 125 VDC


Maximum contact current 10 A

5A

Contact configuration

Single

Single

Bifurcated

Contact materials

Ag

Au cladding + Ag alloy

Au cladding + Ag alloy

* If you use a Socket, do not exceed the rated carry current of the Socket.
Type
Item

Model with built-in operation indicator, diode, or CR circuit

Ambient operating temperature*1

55 to 60 C*2

Ambient operating humidity

5% to 85%

*1. With no icing or condensation.


*2. This limitation is due to the diode junction temperature and elements used.

13

MY
Characteristics
Item

Type

2 poles

Contact resistance*1

100 m max.

Operation time*2

20 ms max.

Release time*2

20 ms max.

Maximum
operating
frequency

18,000 operations/h

Mechanical
Rated load

Insulation resistance*3

4 poles

4 poles (bifurcated)

1,800 operations/h
1,000 M min.

Between coil
and contacts

Dielectric
strength

Between
contacts of
different
polarity

2,000 VAC at 50/60 Hz for 1 min.

Between
contacts of the
same polarity

1,000 VAC at 50/60 Hz for 1 min.

Vibration
resistance

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Shock
resistance

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

AC: 50,000,000 operations min., DC: 100,000,000 operations min. (switching


frequency: 18,000 operations/h)

20,000,000 operations min. (switching


frequency: 18,000 operations/h)

Electrical*4

500,000 operations min.


(rated load, switching frequency: 1,800
operations/h)

200,000 operations min.


(rated load, switching frequency: 1,800
operations/h)

100,000 operations min.


(rated load, switching frequency: 1,800
operations/h)

Failure rate P value


(reference value)*5

1 mA at 5 VDC

1 mA at 1 VDC

100 A at 1 VDC

Weight

Approx. 35 g

Endurance

Note: These are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: When rated operating power is applied and ambient temperature is 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23 C
*5. This value was measured at a switching frequency of 120 operations per minute.

14

MY

Dimensions

(Unit: mm)

List of Models
MY2IN (S)
MY2IN-D2 (S)
2.6

Eight, 1.2-dia. 2.2 oval holes


6.3
0.5

28 max.

6.4

36 max.

8.05

14.2

21.5 max.

Terminal Arrangement/Internal Connections (Bottom View)

MY2IN(S)
(AC Model)

MY2IN(S)
(DC Models)

MY2IN-D2(S)
(DC Models Only)

12

13

14

13

12

14

13

12

14

Note: For the DC models, check the coil polarity when wiring and wire all connections correctly.

MY4 (Z) IN (S)


MY4 (Z) IN-D2 (S)
MY4 (Z) IN-CR (S)

2.6

Fourteen, 1.2-dia. 2.2 oval holes


6.3
0.5

28 max.

8.05

14.2

6.4

36 max.

21.5 max.

Terminal Arrangement/Internal Connections (Bottom View)

MY4(Z)IN(S)
(DC Models)

MY4(Z)IN(S)
(AC Models)

MY4(Z)IN-D2(S)
(DC Models Only)

MY4(Z)IN-CR(S)
(AC Models Only)

10

11

12

10

11

12

13

14

13

14

13

14

13

14

Note: For the DC models, check the coil polarity when wiring and wire all connections correctly.

15

MY

Relays with PCB Terminals: MY@-02


Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.

Ordering Information
Number
of poles

Classification

Standard products

MY3-02

Models with single


contacts

MY4-02

4 poles
Bifurcated contacts

Made-to-order items

100/110, 200/220, or 200/240 VAC

MY2-02

Models with single


contacts

3 poles

Rated voltage (V)

Model

Models with single


contacts

2 poles

When your order, specify the rated voltage.

MY4Z-02

12, 24, 100, or 110/120 VAC

12, 24 or 48 VDC

100/110 VDC

100/110 or 200/220 VAC

12, 24, 110/120, or 220/240 VAC

24 VDC

12, 48, or 100/110 VDC

100/110 or 200/220 VAC

12, 24, 110/120, or 220/240 VAC

12, 24 or 100/110 VDC

48 VDC

---

100/110, 110/120, or 200/220 VAC

100/110 VDC

12, 24, or 48 VDC

Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.

Ratings and Specifications


Ratings
Operating Coil (Standard Models)
Item

Rated current (mA)

AC

Coil inductance (H)

Coil
resistance ()

Armature OFF

Armature ON

91

46

0.17

0.33

46

180

0.69

1.3

11.7/12.9

10/11

3,750

14.54

24.6

110/120

9.9/10.8

8.4/9.2

4,430

19.2

32.1

200/220

6.2/6.8

5.3/5.8

12,950

54.75

94.07

220/240

4.8/5.3

4.2/4.6

18,790

83.5

136.4
1.37

Rated voltage (V)

50 Hz

60 Hz

12

106.5

24

53.8

100/110

12

75

160

0.73

24

36.9

650

3.2

5.72

48

18.5

2,600

10.6

21.0

100/110

9.1/10

11,000

45.6

86.2

DC

Must-operate
voltage (V)

Must-release
voltage (V)

Maximum
voltage (V)

Power consumption
(VA, W)
Approx. 1.0 to 1.2
(at 60 Hz)

30% min.*2
110% of
rated
voltage

80% max.*1

10% min.*2

Approx. 0.9 to 1.1


(at 60 Hz)

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value.
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the specified value.

Contact Ratings
Number of poles
Load

2 or 3 poles

4 poles

4 poles, bifurcated contacts

Resistive load

Inductive load
(cos = 0.4, L/R = 7 ms)

Rated load

5 A at 220 VAC
5 A at 24 VDC

2 A at 220 VAC
2 A at 24 VDC

Rated carry current

5A

3A

Maximum contact voltage

250 VAC, 125 VDC

250 VAC, 125 VDC

250 VAC, 125 VDC

Maximum contact current

5A

3A

3A

Contact configuration

DPDT, 3PDT

4PDT

4PDT

Contact structure

Single

Single

Bifurcated

Contact materials

Ag

Au plating + Ag

Au plating + Ag

Item

Type
Ambient operating temperature
Ambient operating humidity
* With no icing or condensation.

3 A at 220 VAC
3 A at 24 VDC

Resistive load

Inductive load
(cos = 0.4, L/R = 7 ms)

0.8 A at 220 VAC


1.5 A at 24 VDC

3 A at 220 VAC
3 A at 24 VDC

0.8 A at 220 VAC


1.5 A at 24 VDC

3A

Standard models

Item
*

Resistive load

Inductive load
(cos = 0.4, L/R = 7 ms)

55 to 70 C
5% to 85%

16

MY
Characteristics
Item

2 or 3 poles

Number of poles

Contact resistance*1

50 m max.

Operation time*2

20 ms max.

Release time*2
Maximum
operating
frequency

4 poles

4 poles, bifurcated contacts

20 ms max.
Mechanical

18,000 operations/h

Rated load

1,800 operations/h

Insulation resistance*3

100 M min.

Between coil and contacts


Dielectric
strength

Vibration
resistance
Shock resistance

2,000 VAC at 50/60 Hz for 1 min.

Between contacts of
different polarity
Between contacts of the
same polarity

1,000 VAC at 50/60 Hz for 1 min.

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

AC: 50,000,000 operations min.


DC: 100,000,000 operations min.
(switching frequency: 18,000 operations/h)

AC: 20,000,000 operations min.


(switching frequency: 18,000
operations/h)

Electrical*4

500,000 operations min.


(rated load, switching frequency:
1,800 operations/h)

100,000 operations min.


(rated load, switching frequency:
1,800 operations/h)

Endurance

Item

Number of poles

200,000 operations min.


(rated load, switching frequency:
1,800 operations/h)

2 or 3 poles

Failure rate P value (reference value)*5

1 mA at 5 VDC

Weight

Approx. 35 g

4 poles

4 poles, bifurcated contacts

1 mA at 1 VDC

100 A at 1 VDC

Note: These are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23 C
*5. This value was measured at a switching frequency of 120 operations per minute.

Dimensions

(Unit: mm)

Relays with PCB Terminals


MY@-02

PCB Processing Dimensions (Bottom View)


3.5

2 poles

3 poles

4 poles

13.2

13.2

13.2
4.4

3.3 (2.6)*
4.3
4.1
12.65
6.35
0.5

6.3
28 max.
3.75

The figures and dimensions given


here are for the MY4-02.
The 2-pole and 3-pole models
conform to these dimensions.

6.3
21.5 max.

0.5
36 max.

4
*Dimensions in parentheses are for the MY4-02.

Eight, 1.3-dia. 0.1 holes

Fourteen, 1.3-dia. 0.1 holes

Eleven, 1.3-dia. 0.1 holes

Note: 1. The dimensional tolerance is 0.1.


2. Refer to the terminal arrangement and
internal connections diagrams for the
MY2, MY3, MY4, and MY4Z.

17

MY

Case-surface-mounting Relays: MY@F


Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.

Ordering Information
Number of poles

Classification

Standard products

MY2F

Models with single


contacts

3 poles

Rated voltage (V)

Model

Models with single


contacts

2 poles

When your order, specify the rated voltage.

MY3F

Models with single


contacts

MY4F

4 poles
Bifurcated contacts

MY4ZF

Made-to-order items

24, 110/110, 100/120 or 200/220 VAC

220/240 VAC

12 or 24 VDC

48 or 100/110 VDC

100/110 VAC

24 or 200/220 VAC

---

24 or 100/110 VDC

100/110 or 200/220 VAC

24 or 110/120 VAC

12 or 24 VDC

48 or 100/110 VDC

200/220 VAC

---

---

12 or 24 VDC

Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.

Ratings and Specifications


Ratings
Operating Coil (Standard Models)
Item

Rated current (mA)

AC

Coil inductance (H)

50 Hz

60 Hz

Coil
resistance ()

Armature OFF

Armature ON

24

53.8

46

180

0.69

1.3

100/110

11.7/12.9

10/11

3,750

14.54

24.6

110/120

9.9/10.8

8.4/9.2

4,430

19.2

32.1

200/220

6.2/6.8

5.3/5.8

12,950

54.75

94.07

220/240

4.8/5.3

4.2/4.6

18,790

83.5

136.4

160

0.73

1.37

Rated voltage (V)

12

75

24

36.9

650

3.2

5.72

48

18.5

2,600

10.6

21.0

100/110

9.1/10

11,000

45.6

86.2

DC

Must-operate
voltage (V)

Release
voltage (V)

Maximum
voltage (V)

Power consumption
(VA, W)
Approx. 1.0 to 1.2
(at 60 Hz)

30% min.*2

Approx. 0.9 to 1.1


(at 60 Hz)
110% of
rated voltage

80% max.*1

10% min.*2

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the specified value.

Contact Ratings
Number of poles

2 or 3 poles

Load

Resistive load

Item

4 poles

Inductive load
(cos = 0.4, L/R = 7 ms)

Rated load

5 A at 220 VAC
5 A at 24 VDC

Rated carry current

5A

3A

Maximum contact voltage

250 VAC, 125 VDC

250 VAC, 125 VDC

Maximum contact current

5A

3A

Contact configuration

DPDT, 3PDT

4PDT

Contact structure

Single

Single

Contact materials

Ag

Au plating + Ag

Type
Item

2 A at 220 VAC
2 A at 24 VDC

Resistive load

3 A at 220 VAC
3 A at 24 VDC

Inductive load
(cos = 0.4, L/R = 7 ms)

0.8 A at 220 VAC


1.5 A at 24 VDC

Standard models

Ambient operating temperature*

55 to 70 C

Ambient operating humidity

5% to 85%

* With no icing or condensation.

18

MY
Characteristics
Item

Number of poles

2 or 3 poles

Contact resistance*1

50 m max.

Operation time*2

20 ms max.

Release time*2

20 ms max.

Maximum
operating
frequency

Mechanical

18,000 operations/h

Rated load

1,800 operations/h

Insulation resistance

*3

4 poles

100 M min.

Between coil and contacts


Dielectric
strength

Vibration
resistance
Shock
resistance

2,000 VAC at 50/60 Hz for 1 min.

Between contacts of
different polarity
Between contacts of the
same polarity

1,000 VAC at 50/60 Hz for 1 min.

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude


(1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude


(1.0-mm double amplitude)

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

AC: 50,000,000 operations min.


DC: 100,000,000 operations min.
(switching frequency: 18,000 operations/h)

Electrical*4

500,000 operations min.


(rated load, switching
frequency: 1,800 operations/h)

Endurance

Item

Number of poles

2 or 3 poles

Failure rate P value


(reference value)

1 mA at 5 VDC

Weight

Approx. 35 g

200,000 operations min.


(rated load, switching
frequency: 1,800 operations/h)

4 poles
1 mA at 1 VDC

Note: These are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied.
Ambient temperature condition: 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23 C
*5. This value was measured at a switching frequency of 120 operations per minute.

Dimensions

(Unit: mm)

Case-surface mounting
MY@F
2.6

Mounting Hole Dimensions


Two, 3.5-dia. holes
or M3 screw holes

Fourteen, 1.2-dia. 2.2 oval holes

38 0.2
4.35
0.5

The above figure is for the MY4F.

0.5
36 max.

29 max.

38

44 max.

6.4
3.5
22.5 max.

4 poles, bifurcated contacts


The 1-pole, 2-pole, and 3-pole models
conform to these dimensions.

Note: Refer to the terminal arrangement and


internal connections diagrams for the MY2,
MY3, MY4, and MY4Z.

19

MY

Engineering Data MY2, MY3, MY4, MY4Z, MY@-02, and MY@F


Engineering Data
Endurance Curve

MY2 and MY3

MY2 and MY3

MY2 and MY3

AC resistive load

AC inductive load
(cos = 0.4)

DC resistive load

0.5

DC inductive load
(L/R = 7 ms)

0.1

500
110 VAC resistive load
220 VAC resistive load
100
50
24 VDC resistive load

100

500

AC resistive load

AC inductive load
(cos = 0.4)

1
0.5
DC resistive load
DC inductive load
(L/R = 7 ms)

0.1

50

100

220 VAC inductive load


(cos = 0.4)

50
24 VDC inductive load
(L/R = 7 ms)

500
110 VAC resistive load

220 VAC resistive load

100
50

500

Contact current (A)

30 VDC
resistive load

500

110 VAC inductive load (cos = 0.4)

100
50

220 VAC inductive load


(cos = 0.4)

10

0.5

30 VDC inductive load


(L/R = 7 ms)

1.0

Contact current (A)

Contact voltage (V)

MY4Z
Number of operations (104 operations)

10

100

MY4

10

MY4

10

Number of operations (104 operations)

MY4 and MY4Z

110 VAC inductive load


(cos = 0.4)

Contact current (A)

Contact voltage (V)

Number of operations (104 operations)

50

1.5

Contact current (A)

MY4Z

500

100
50

220 VAC resistive load

Number of operations (104 operations)

10

500

10

10

Contact current (A)

Number of operations (104 operations)

10

Number of operations (104 operations)

Contact current (A)

Maximum Switching Capacity

500

100
110 VAC inductive load (cos = 0.4)

50
24 VDC inductive load (L/R = 7 ms)

10

10

24 VDC resistive load


220 VAC inductive load (cos = 0.4)

2
3
Contact current (A)

0.5

1.0

1.5

Contact current (A)

20

MY

MY2 AC Models

MY2 AC Models, 50 Hz
Must-operate voltage
Must-release voltage

80

60

110

When rated voltage is applied

100

Operating temperature limit value


(E-class insulation, 120 C)

90
80
70
60

40

30

30

60

90

No contact current

Must-operate voltage
Must-release voltage

80

60

20
10
10

20

30

40

5 A contact current 2 circuits


2.5 A contact current 2 circuits

50

60

70

80

No contact current

10

20

30

40

Ambient temperature (C)

110

When rated voltage is applied

100

Operating temperature limit value


(E-class insulation, 120 C)

90
80
70

50

50

60

70

80

Ambient temperature (C)

MY4 DC Models

120

60
40

70

10

MY4 AC Models, 50 Hz

Number of Relays: 10
(average value)

80

20

Temperature rise (C)

100

90

30

Ambient temperature (C)

MY2 DC Models

When rated voltage is applied


Operating temperature limit value
(E-class insulation, 120 C)

40

Temperature rise (C)

0
60

110
100

50

2.5 A contact current 2 circuits

40
30

120

60

5 A contact current 2 circuits

50

20

Must-operate/must-release voltage (%)

MY2 DC Models

120

Temperature rise (C)

100 Number of Relays: 10


(average value)

Temperature rise (C)

Ambient Temperature vs. Coil Temperature Rise

Must-operate/must-release voltage (%)

Ambient Temperature vs.


Must-operate and Must-release Voltage

120
110

When rated voltage is applied

100

Operating temperature limit value


(E-class insulation, 120 C)

90
80
70
60

3 A contact current 4 circuits

50
3 A contact current 4 circuits

40

40

1.5 A contact current 4 circuits

1.5 A contact current 4 circuits

30
20

0
60

30

30

60

90

30

No contact current

20

20

10

10

10

20

30

40

50

60

70

80

No contact current

10

20

30

40

Ambient temperature (C)

Ambient temperature (C)

50

60

70

80

Ambient temperature (C)

Models with built-in diodes


The diode absorbs surge from the coil. This type is best suited for applications with semiconductor circuits.

MY4 AC Models
Must-operate/must-release voltage (%)

100

Must-operate voltage
Must-release voltage

80
ON

ON

OFF

OFF

60

40

140 V

A
24 VDC

20

0
60

30

60

24 VDC

Number of Relays: 10
(average value)

To digital
memory

90

Ambient temperature (C)

100

To digital

Di memory
A

30

MY4 DC Models
Must-operate/must-release voltage (%)

Without Diode

With Diode

Number of Relays: 10
(average value)

Must-operate voltage
Must-release voltage

Note: 1. Make sure that the polarity is correct.


2. The release time will increase, but the 20-ms specification for standard models is satisfied.
3. Diode properties:The diode has a reversed dielectric strength of 1,000 V.
Forward current: 1 A

Models with Built-in CR Circuits


With CR

80

Without CR

60

282 V
2.5
msec
ms

282 V
40
80 V
20
9.4 ms

4.12 ms

600 V

A
0
60

30

30

60

90

Ambient temperature (C)

A
200 AC

C = 0.033 F
R = 6.8 k
A

200 AC

To digital
memory
scope

21

MY

Engineering Data MY(S)


Engineering Data
MY2(S)

50
30
AC resistive load

AC inductive load
(cos = 0.4)

10
5
3
DC resistive load

1
0.5
DC inductive load
(L/R = 7)

0.3

MY2(S)

10,000
5,000
250 VAC
resistive load

3,000

1,000
30 VDC
resistive load

500
30 VDC
resistive load

300

250 VAC
resistive load

100

10

30 50

100

5
3
DC resistive load

DC inductive load
(L/R = 7)

100

30 VDC
resistive load

500
300
30 VDC
resistive load

100
250 VAC
resistive load

250 500

5,000
3,000
30 VDC
inductive load

1,000
30 VDC
inductive load

500
300
250 VAC
inductive load

100

250 VAC
inductive load

50

10
1

0.5

Contact current (A)

Contact voltage (V)

MY4Z(S)

MY4Z(S)

10,000
5,000
3,000

250 VAC
resistive load

1,000
500
300

30 VDC
resistive load

100
30 VDC
resistive load

50

1.5

Contact current (A)

Number of operations (103 operations)

Number of operations (103 operations)

Contact current (A)

30

10
0

0.1
30 50

250 VAC
resistive load

1,000

30

10

10,000

3,000

50

250 VAC
inductive load

100

MY4(S)

5,000

0.3

30 VDC
inductive load

300

10

10,000

0.5

500

Contact current (A)

Number of operations (103 operations)

AC inductive load
(cos = 0.4)

AC resistive load

10

MY4(S)

30

30 VDC
inductive load

10
2

Contact voltage (V)

50

250 VAC
inductive load

1,000

30

100

3,000

50

250 500

MY4(S) and MY4Z(S)

5,000

30

Number of operations (103 operations)

10,000

50

10

0.1

Contact current (A)

Number of operations (103 operations)

100

Number of operations (103 operations)

Endurance Curve

MY2(S)
Contact current (A)

Maximum Switching Capacity

10,000
5,000
3,000

1,000
30 VDC
inductive load

500
300

30 VDC
inductive load

100

250 VAC
inductive load

50
250 VAC
resistive load

30

30

10

250 VAC
inductive load

10
0

Contact current (A)

0.5

1.5

Contact current (A)

Common Specifications for MY2, MY3, MY4, MY4Z, MY@-02, MY@F, and MY(S)
Malfunctioning Shock
Y
Energized
550

Not energized

400
X

Z'
700

600
600

300

N = 20
Measurement: Shock was applied 3 times each in 6 directions along 3 axes with
the Relay energized and not energized to check the shock values that cause the
Relay to malfunction.
Criteria: Non-energized: 200 m/s2 ,
Energized: 200 m/s2
Shock direction

250
550
Z

600

600
X'

400
Unit: m/s

600
Y'

22

MY
Detailed Information on Models Certified for Safety Standards, MY2Z, MY3, MY@-02, and MY@F
Refer to Model Number Structure on page 1 for a list of applicable models.
The standard models are certified for UL and CSA standards.
The rated values for safety standard certification are not the same as individually defined performance values. Always check the specifications before use.

TUV-certified Models (File No. R50030059)


Model

MY@

Coil
ratings

6 to 125
VDC
6 to 240
VDC

CSA-certified Models (File No. LR31928)

Number
of poles

Contact ratings

5 A, 250 VAC (cos = 1.0)

7A, 240 VAC (Resistive)


7A, 24 VDC (Resistive)

5 A, 250 VAC (cos = 1.0)


0.8 A, 250 VAC (cos =
0.4)

Certified number
of operations

Model

Coil
ratings

Number
of poles

5A, 240 VAC (General Use)

10,000 operations
2

3 A, 120 VAC (cos = 1.0)


0.8 A, 120 VAC (cos =
0.4)

Coil
ratings

Number
of poles

Contact ratings

Certified number
of operations

5A, 28 VDC (Resistive)


7A, 240 VAC (General Use)
3

6,000

MY

6 to 240
VAC
6 to 125
VDC

1/6HP, 250 VAC

5A, 240 VAC (General Use)


(Same polarity)

1,000

1/10HP, 120 VAC

3
MY

6 to 240
VAC
6 to 125
VDC

5A, 240 VAC (General Use)


1/6 HP, 250 VAC

4
6,000
6,000

1/6HP, 250 VAC

When ordering models that are certified for Lloyds Register (LR) Standards,
be sure to specify LR-certified Model with your order.
6,000

0.2A, 120 VDC (Resistive)


(Same polarity)

1/10HP, 120 VAC


(Same polarity)
B300 Pilot Duty
(Same polarity)

1,000

1/10HP, 120 VAC

5A, 250 VAC (Resistive)


(Same polarity)

1/6HP, 250 VAC


(Same polarity)

5A, 30 VDC (Resistive)

0.2A, 120 VDC (Resistive)

1,000

5A, 240 VAC (General Use)


(Same polarity)

6,000

5A, 250 VAC (Resistive)


(Same polarity)

5A, 28 VDC (General Use)


(Same polarity)

5A, 30 VDC (Resistive)


(Same polarity)

1,000

7A, 24 VDC (Resistive)


(Same polarity)

1/6HP, 250 VAC

5A, 28 VDC (Resistive)

6,000

7A, 240 VAC (General Use)


(Same polarity)

3A, 265 VAC (Resistive)

B300 Pilot Duty

7A, 24 VDC (Resistive)


5A, 240 VAC (General Use)

5A, 30 VDC (Resistive)

1/8HP, 265 VAC

1,000

1/10HP, 120 VAC

7A, 24 VDC (Resistive)

5A, 250 VAC (Resistive)

6,000

5A, 250 VAC (Resistive)

1/6HP, 250 VAC

7A, 240 VAC (General Use)

5A, 240 VAC (General Use)

Certified number
of operations

5A, 30 VDC (Resistive)

UL-certified Models (File No. E41515)


Model

Contact ratings

LR-certified Models (File No. 90/10270)


Model

Coil ratings

MY@

6 to 240
VAC
6 to 125
VDC

Number
of poles

Contact ratings

2 A, 30 VDC inductive load


2 A, 200 VAC inductive load

1.5 A, 30 VDC inductive load


0.8 A, 200 VAC inductive load
1.5 A, 115 VAC inductive load

1,000

6,000

23

MY
Detailed Information on Models Certified for Safety Standards, MY2, MY4, MY4Z, and
MY(S) Newly Released Models
Refer to Model Number Structure on page 1 for a list of applicable models.

VDE-certified Models (Certificate No. 112467UG, EN 61810-1)


Model
MY@
(New model)

Coil ratings

Number of poles

6, 12, 24, 48/50, 100/


110, 110/120, 200/
220, and 220/240 VAC
6, 12, 24, 48, 100/
110, and 125 VDC

Contact ratings

10 A, 250 VAC (cos = 1)


10 A, 30 VDC (L/R = 0 ms)

5 A, 250 VAC (cos = 1)


5 A, 30 VDC (L/R = 0 ms)

Certified number of operations


MY2: 10,000 operations
MY4: 100,000 operations
MY4Z: 50,000 operations (AC)

UL508-certified Models (File E41515)


Model

Coil ratings

Number of poles

Contact ratings

Certified number of operations

10A, 250 VAC (General Use)


10A, 30 VDC (General Use)
7A, 240 VAC (General Use)
7A, 24 VDC (Resistive)
5A, 240 VAC (General Use)
2

6,000

5A, 250 VAC (Resistive)


5A, 30 VDC (Resistive)
3A, 265 VAC (Resistive)
1/6HP, 250 VAC

MY@
(New model)

1/8HP, 265 VAC

6 to 240 VAC
6 to 125 VDC

1,000

1/10HP, 120 VAC


B300 Pilot Duty (Same polarity)

6,000

5A, 28 VDC (General Use) (Same polarity)


5A, 240 VAC (General Use) (Same polarity)
5A, 30 VDC (Resistive) (Same polarity)
4

6,000

5A, 250 VAC (Resistive) (Same polarity)


0.2A, 120 VDC (Resistive) (Same polarity)
1/6HP, 250 VAC (Same polarity)
1/10HP, 120 VAC (Same polarity)
B300 Pilot Duty (Same polarity)

1,000
6,000

CSA 22.2 No. 14-certified Models (File No. LR31928)


Model

Coil ratings

Number of poles

Contact ratings

Certified number of operations

7A, 240 VAC (General Use)


7A, 24 VDC (Resistive)
5A, 240 VAC (General Use)
5A, 250 VAC (Resistive)
2

6,000

5A, 30 VDC (Resistive)


3A, 265 VAC (Resistive)
1/6HP, 250 VAC
1/8HP, 265 VAC

MY@
(New model)

1,000

1/10HP, 120 VAC

6 to 240 VAC
6 to 125 VDC

B300 Pilot Duty (Same polarity)

6,000

5A, 240 VAC (General Use) (Same polarity)


5A, 28 VDC (General Use) (Same polarity)
5A, 250 VAC (Resistive) (Same polarity)
4

6,000

5A, 30 VDC (Resistive) (Same polarity)


0.2A, 120 VDC (Resistive) (Same polarity)
1/6HP, 250 VAC (Same polarity)
1/10HP, 120 VAC (Same polarity)
B300 Pilot Duty (Same polarity)

1,000
6,000

LR-certified Models (File No. 98/10014)


Model

MY@
(New model)

Coil ratings

Number of poles

Contact ratings

10 A, 250 VAC (resistive)


2 A, 250 VAC (PF0.4)
10 A, 30 VDC (resistive)
2 A, 30 VDC (L/R = 7 ms)

5 A, 250 VAC (resistive)


0.8 A, 250 VAC (PF0.4)
5 A, 30 VDC (resistive)
1.5 A, 30 VDC (L/R = 7 ms)

6 to 240 VAC
6 to 125 VDC

Certified number of operations

MY2: 50,000 operations


MY4: 50,000 operations

24

MY

Miniature Power Relays: MY4Z-CBG


Ordering Information
Classification

When your order, specify the rated voltage.


Rated voltage (V)

Model

Standard models

MY4Z-CBG

Models with built-in


operation indicators

MY4ZN-CBG

Standard products

Made-to-order items

100/110 or 200/220 VAC

110/120 VAC

24 or 100/110 VDC

12 or 48 VDC

---

100/110 or 200/220 VAC

---

24 VDC

Note: Ask your OMRON representative for details on the time required to deliver made-to-order products.

Ratings and Specifications


Ratings
Operating Coil
Item
Rated voltage (V)

AC

Rated current (mA)


50 Hz

60 Hz

Coil
resistance ()

Coil inductance (H)


Armature OFF Armature ON

100/110

11.7/12.9

10/11

3,750

14.54

24.6

110/120

9.9/10.8

8.4/9.2

4,430

19.2

32.1

200/220

6.2/6.8

5.3/5.8

12,950

54.75

94.07

12

75

160

0.73

1.37

24

36.9

650

3.2

5.72

100/110

9.1/10

11,000

45.60

86.20

DC

Must-operate
voltage (V)

Must-release
voltage (V)

Maximum
voltage (V)

Power consumption
(VA, W)
Approx. 0.9 to 1.1
(at 60 Hz)

30% min.*2
110% of
rated
voltage

80% max.*1
10% min.*2

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.

Characteristics

Contact Ratings
Load

Resistive load

Item
Rated load
Rated carry
current

1 A at 220 VAC
1 A at 24 VDC

Inductive load
(cos = 0.4, L/R = 7 ms)

Contact resistance*1

100 m max.

Operation time*2

20 ms max.

0.3 A at 220 VAC


0.5 A at 24 VDC

Release time*2

20 ms max.

Maximum
operating
frequency

18,000 operations/h

1A

Maximum contact
voltage

250 VAC, 125 VDC

Maximum contact
current

1A

Contact structure

Crossbar bifurcated

Contact materials

Au cladding + AgPd

Mechanical
Electrical

Insulation resistance*3
Between coil
and contacts

1A
Dielectric
strength

Between contacts
of different polarity

1,800 operations/h
100 M

2,000 VAC at 50/60 Hz for 1 min.

Between contacts
700 VAC at 50/60 Hz for 1 min.
of the same polarity
Vibration
resistance
Shock
resistance

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude


(1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude


(1.0-mm double amplitude)

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

5,000,000 operations min. (operating


frequency: 18,000 operations/hr)

Electrical*4

50,000 operations min. (switching


frequency: 1,800 operations/h) at rated load

Endurance

Failure rate P value (reference value)*5 100 A at 1 VDC


Ambient operating temperature

25 to 70C (with no icing or condensation)

Ambient operating humidity

5% to 85%

Weight

Approx. 35 g

Note: The above values are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied, not including contact bounce.
Ambient temperature condition: 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength
measurement.
*4. Ambient temperature condition: 23 C
*5. This value was measured at a switching frequency of 120 operations per minute.

25

MY

Engineering Data
Engineering Data
Contact Reliability Test
(Modified Allen Bradley Circuit)

MY4Z-CBG

Contact load: 5 VDC, 1 mA resistive load


Malfunction criteria level: Contact resistance of 100

Contact current (A)

10
5
AC resistive load
AC inductive load
(cos = 0.4)

1
0.5

Contact resistance (m)

Maximum Switching Capacity

30
Number of Relays: 10 (average value)
Malfunction rate: 60 = 0.0046 10-6 per operation

28

(switching frequency: 200 operations/ min.)

26

24
DC resistive load

0.1

22

DC inductive load
(L/R = 7 ms)

0.05

Current-carrying contact

20

Open contacts
Self-latching contacts

0.01

10

50

100

500

Closed contacts

5 10

Contact voltage (V)

50 100

500 1,000

Number of operations (104 operations)

Dimensions

(Unit: mm)

MY4Z-CBG

Terminal Arrangement/Internal
Connections (Bottom View)
Standard Models

2.6

Fourteen, 1.2-dia. 2.2 oval holes

0.5
28 max.
6.3
0.5
36 max.

21.5 max.

(The coil has no polarity.)

6.4

Safety Precautions
Refer to the Common Relay Precautions.

Applicable Sockets
Use only combinations of OMRON Relays and Sockets.

26

MY

Plastic Sealed Relays: MYQ


Ordering Information

Ratings and Specifications

Relays with Plug-in or Soldered


Terminals

Ratings
Operating Coil
Item Rated current (mA)

When your order, specify the rated voltage.

Rated voltage (V)


Type
Model

Standard
models

Bifurcated
contacts

100/110, 110/
120, 200/220, or
220/240 VAC

MYQ4

AC

Models
with builtin
operation
indicators

MYQ4N

24, 100/110,
110/120,
200/220, or
220/240 VAC

Standard
models

MYQ4Z

100/110,
110/120, or
200/220 VAC
12 or 24 VDC

Relays with PCB Terminals


Type

4 poles
Model

Models with
single contacts

MYQ4-02

Bifurcated
contacts

MYQ4Z-02

24

53.8

46

180

0.69

1.3

11.7/12.9

10/11

3,750

14.54

24.6

110/120

9.9/10.8

8.4/9.2

4,430

19.2

32.1

200/220

6.2/6.8

5.3/5.8

12,950

54.75

91.07

220/240

4.8/5.3

4.2/4.6

18,790

83.5

136.4
1.37

12

75

160

0.734

24

36.9

650

3.2

5.72

48

18.5

2,600

10.6

21.0

100/110

9.1/10

11,000

45.6

86.0

DC

12, 24, 48, or


100/110 VDC

Coil inductance (H)


MustMustPower
Coil resisMaximum
operate
release
consumpti
tance () Armature OFF Armature ON
voltage (V)
voltage (V) voltage (V)
on (VA, W)

100/110

Rated voltage (V)

24 VDC

Classification

60 Hz

4 poles

Classification

Models
with single
contacts

50 Hz

30%
min.*2
80%
max.*1
10%
min.*2

Approx.
1.0 to
1.2 (at
110% of 60 Hz)
rated
voltage
Approx.
0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of
+15%/20% for AC rated current and 15% for DC coil resistance.
2. The AC coil resistance and coil inductance values are reference values only.
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC.
To ensure release, use a value that is lower than the specified value.

Contact Ratings

Rated voltage
(V)

Type

Resistive load

Item

50, 200/220, or
220/240 VAC
24 VDC
100/110 VAC
24 or 48 VDC

Rated load

1 A at 220 VAC, 1 A at 24 VDC

Rated carry current

1A

Maximum contact voltage

250 VAC, 125 VDC

Maximum contact current

1A

Maximum switching capacity


220 VAC, 24 W
(reference value)

Inductive load
(cos = 0.4, L/R = 7 ms)
0.5 A at 220 VAC, 0.5 A at 24 VDC

110 VAC, 12 W

Failure rate P value


(reference value)

Single contacts: 1 mA at 1 VDC, Bifurcated contacts: 100 A at 1 VDC

Contact structure

Single/bifurcated

Contact materials

Au plating + Ag

* This value was measured at a switching frequency of 120 operations per minute.
Ambient operating temperature

55 to 60 C*

Ambient operating humidity

5% to 85%

* With no icing or condensation.

Characteristics
Contact resistance*1

50 m max.

Operation time*2

20 ms max.

Release time*2

20 ms max.

Maximum
operating
frequency
Dielectric
strength

Mechanical

18,000 operations/h

Rated load

1,800 operations/h

Between coil and contacts

1,500 VAC at 50/60 Hz for 1 min.

Between contacts of different polarity

1,500 VAC at 50/60 Hz for 1 min.

Between contacts of the same polarity

1,000 VAC at 50/60 Hz for 1 min.

*3

Insulation resistance

100 M min.

Vibration
resistance

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)

Shock
resistance

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

AC: 50,000,000 operations (5,000,000*4) min., DC: 100,000,000 operations


(5,000,000*4) min. (switching frequency: 18,000 operations/h)

Electrical*5

200,000 operations min. (100,000 operations*4) (rated load, switching


frequency: 1,800 operations/h)

Endurance

Weight

Approx. 35 g

Note: The values at the left are initial


values.
*1. Measurement conditions: 1 A at 5
VDC using the voltage drop
method
*2. Measurement conditions: With
rated operating power applied, not
including contact bounce.
Ambient temperature condition:
23 C
*3. Measurement conditions: For 500
VDC applied to the same location
as for dielectric strength
measurement.
*4. This value is for bifurcated
contacts.
*5. Ambient temperature condition:
23 C

27

MY

Engineering Data
Engineering Data
H2S Gas Data

MYQ4(Z)

MYQ4

MYQ4
AC resistive load

AC inductive load
(cos = 0.4)

1
0.7
0.5
0.3

DC resistive load
DC inductive load
(L/R = 7 ms)

0.1
0.07
0.05

1,000
700
500
300
220 VAC resistive load
24 VDC resistive load

100
70
50

10

30 50 100

Y
Energized

80
N=10
70 Measurements: Temperature: 40 C, Humidity: 60% to 70%,
H2S concentration: 5 3 ppm
The change in contact resistance was measured after
60 leaving the Relay in the above environment for a fixed
amount of time, then removing it to a constant-temperature
50 and constant-humidity environment for at least 30 minutes.

550

Not energized

400
X

600

220 VAC inductive load (cos = 0.4)

10
7
5

300 500 1,000

Z
700

600
300

250
550

30

max.
min.

24 VDC inductive load (L/R = 7 ms)

20

600

600
X

400
Unit: m/s2
600

Malfunctioning Shock

40

30

0.03

0.01

Contact resistance (m)

10
7
5

Number of operations (104 operations)

Contact current (A)

Maximum Switching Capacity Endurance Curve

10
1

0.2

0.4

0.6

0.8

1.0

1.2

10

30 50 100

Contact current (A)

Contact voltage (V)

300 500 1,000


Standing time (h)

Note: The durability of bifurcated


contacts is one-half that of
single contacts.

Y
N = 20
Measurement: Shock was applied
3 times each in 6 directions along
3 axes with the Relay energized
and not energized to check the
shock values that cause the Relay
to malfunction.
Criteria: Non-energized: 200 m/s2
Energized: 200 m/s2

Dimensions

Shock
direction

(Unit: mm)

Relays with Plug-in Terminals


or Soldered Terminals
MYQ4(Z)(N)

MYQ4(Z)N
DC Models

AC Models

2.6
21.5 max.

Fourteen, 1.2-dia. 2.2 oval holes


6.4

28 max.

28 max.

35.5 max.

21.5 max.

Check the coil polarity when wiring


and wire all connections correctly.

(The coil has no polarity.)

Note: 1. An AC model has coil disconnection selfdiagnosis.


2. For the DC models, check the coil polarity
when wiring and wire all connections
correctly.

Relays with PCB Terminals


MYQ4(Z)-02
21.5 max.

1.0

PCB Processing Dimensions


(Bottom View)
13.2

2.6

Terminal Arrangement/Internal
Connections (Bottom View)
Standard Models

4.4

0.6
4.3
4.1

4.1
0.5
6.35

28 max.

28.5 max.

6.3
3.75

35.5 max.

21.5 max.

12.65

Note:

Fourteen, 1.3-dia. holes

(The coil has no polarity.)

The dimensional tolerance is 0.1.

Safety Precautions
For models with built-in operation indicators, check the coil polarity when
wiring and wire all connections correctly (DC operation).
Use only combinations of OMRON Relays and Sockets.
The UL and CSA certifications for this model are the same as for the MY402.

Relay Replacement
To replace the Relay, turn OFF the power supply to the load and Relay coil
sides to prevent unintended operation and possible electrical shock.

28

MY

Latching Relays MYK


Ordering information

When your order, specify the rated voltage.

Relays with Plug-in or Soldered Terminals


Number of poles

Relays with PCB Terminals

2 poles

Classification

Model

Number of poles

Rated voltage (V)

Classification

MY2K

Rated voltage (V)

12 VAC

24 VAC

24 VAC

100 VAC

Standard models

100 VAC
Standard models

2 poles
Model

MY2K-02

12 VDC

100/110 VAC

24 VDC

12 VDC
24 VDC
48 VDC

Ratings and Specifications


Ratings
Operating Coil
Item

Set coil
Rated current (mA)

Rated voltage (V)


AC

DC

50 Hz

60 Hz

Reset coil

Power consumption (VA, W)

Rated current (mA)


Coil
Coil
resistance () 50 Hz
60 Hz resistance ()

12

57

56

72

39

38.2

130

24

27.4

26.4

320

18.6

18.1

550

100

7.1

6.9

5,400

3.5

3.4

3,000

12

110

110

50

24
48

235

52

470

25

940

27

1,800

16

3,000

Set voltage
(V)

80% max.

Reset
voltage (V)

80% max.

Maximum
voltage (V)

110% max. of
rated voltage

Set coil

Reset coil

Approx. 0.6
to 0.9
(at 60 Hz)

Approx. 0.2
to 0.5
(at 60 Hz)

Approx. 1.3

Approx. 0.6

Note: 1. The rated current for AC is the value measured with a DC ammeter in half-wave rectification.
2. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the
DC coil resistance.
3. The AC coil resistance is a reference value only.
4. Operating characteristics were measured at a coil temperature of 23C.
5. The maximum voltage capacity was measured at an ambient temperature of 23C.

Characteristics

Contact Ratings
Load

Resistive load

Item

Inductive load
(cos = 0.4, L/R = 7 ms)

Contact resistance*1

0.8 A at 220 VAC


1.5 A at 24 VDC

Set

Rated load

3 A at 220 VAC
3 A at 24 VDC

Rated carry
current

3A

Reset

Maximum contact
voltage

250 VAC, 125 VDC

Maximum contact
current

Maximum
operating
frequency

3A

Contact structure

Single

Contact materials

Au plating + Ag

Ambient operating
temperature

55 to 60 C*

Ambient operating
humidity

5% to 85%

3A

50 m max.

Time*2

AC: 30 ms max., DC: 15 ms max.

Minimum pulse width AC: 60 ms, DC: 30 ms


Time*2

AC: 30 ms max., DC: 15 ms max.

Minimum pulse width AC: 60 ms, DC: 30 ms


Mechanical

18,000 operations/h

Rated load

1,800 operations/h

Insulation resistance

*3

Between coil
and contacts
Dielectric
strength

Between contacts of
different polarity
Between contacts of
the same polarity
Between set/
reset coils

* With no icing or condensation.


Vibration
resistance
Shock
resistance

100 M
1,500 VAC at 50/60 Hz for 1 min.

1,000 VAC at 50/60 Hz for 1 min.

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude


(1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude


(1.0-mm double amplitude)

Destruction

1,000 m/s2

Malfunction

200 m/s2

Mechanical

100,000,000 operations min.


(switching frequency: 18,000 operations/h)

Electrical*4

200,000 operations min.


(at 1,800 operations/hr, rated load)

Endurance
Failure rate P value (reference value)*5

1 mA at 1 VDC

Weight

Approx. 30 g

Note: The above values are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied, not including contact bounce.
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength
measurement.
*4. Ambient temperature condition: 23 C
*5. This value was measured at a switching frequency of 120 operations per minute.

29

MY

Engineering Data
Engineering Data

AC resistive load

AC inductive load
(cos = 0.4)

1
0.5
DC resistive load
DC inductive load
(L/R = 7 ms)

500
110 VAC resistive load
220 VAC resistive load

100
50

110 VAC inductive load


(cos = 0.4)

100
50

100

500

30 VDC inductive load


(L/R = 7 ms)

0.5

MY2K 100 VAC


Malfunctioning Shock

MY2K 24 VDC
Magnetic Interference
(External Magnetic Field)

Not energized Y
1000

800

(Average values)

1000
Z

400
700

N = 20
Measurement: Shock was applied 2
times each in 6 directions along 3
axes with the Relay energized and not
energized to check the shock values
that cause the Relay to malfunction.

300
350
X
1000

1000
900

1000

S
80

400

400

400

Latching Deterioration Over


Time

N=5
Measurement: The percentage of change in the operating and
release voltages in a uniform external magnetic field
were measured (worst magnetic field direction).

900

Criteria: Non-energized: 200 m/s2


Energized: 200 m/s2

Unit: m/s2

60
40
20
80

60

Percentage
change (%)

Energized
Armature deviation
when set

1.5

Contact current (A)

Contact current (A)

Contact voltage (V)

Latching deterioration over time (%)

50

220 VAC
inductive load
(cos = 0.4)

10

10

10

500

30 VDC resistive load

0.1

Number of operations (104 operations)

Endurance Curve

10

Number of operations (104 operations)

Contact current (A)

MY2K(-02)
Maximum Switching Capacity

Set voltage

40
20

40

40

60

80

N = 24
Measurement: The rate of deterioration in latching ability was
measured over time with the Relay left at a normal temperature
(20 to 30C) after latching by applying the rated voltage.

100
Average value

90

80

Reset voltage

70

60
80

60
0 50 100

300 500 1,000

Uniform magnetic field strength (0e)

Dimensions

(Unit: mm)

Relays with Plug-in Terminals


or Soldered Terminals
MY2K

Terminal Arrangement/Internal
Connections (Bottom View)
For AC

2.6

Safety Precautions
For applications that use a 200 VAC power
supply, connect external resistors Rs and Rr to
a 100 VAC Relay.
1

Ten, 1.2-dia. 2.2 oval holes

13

0.5

5,000 10,000
Elapsed time (h)

10

11

12
14
Rr

28 max.

Note: R is a resistor for ampereturn correction. This resistor


is built-in to 50-VAC and
higher models.
(The coil has no polarity.)

6.3
0.5
36 max.

6.4

Relays with PCB Terminals


MY2K-02

21.5 max.

PCB Processing Dimensions


(Bottom View)
Note: The dimensional
tolerance is 0.1.

For DC

2.6
1

3.5

Ten, 1.3-dia. holes

0.5
28 max.
6.3
36 max.

21.5 max.

Note: Pay close attention to the set


coil and reset coil polarities. If
the connections are not
correct, unintended operation
may occur.

Rs
Set power supply

Rs: 7.3 k, 3 W min.


Rr: 14.3 k, 1 W min.

Reset power supply

Do not apply a voltage to the set and reset coils at the


same time. If you apply the rated voltage to both coils
simultaneously, the Relay will be set.
The minimum pulse width in the performance column is
the value for the following measurement conditions: an
ambient temperature of 23 C with the rated operating
voltage applied to the coil. The performance values
given here may not be satisfied due to use over time
and a reduction in latching performance due to
changes in the ambient temperature or in the
conditions of the application circuit.
For actual use, apply the rated operating voltage with a
pulse width based on the actual load and reset the
Relay at least once per year to prevent degradation
over time.
If the Relay is used in an environment with strong
magnetic fields, the surrounding magnetic field can
demagnetize the magnetic body and cause unintended
operation. Therefore, do not use these Relays in
environments with strong magnetic fields.

Relay Replacement
To replace the Relay, turn OFF the power supply
to the load and Relay coil sides to prevent
unintended operation and possible electrical
shock.

Applicable Sockets
Use only combinations of OMRON Relays and
Sockets.

30

MY

Hermetically Sealed Relays: MYH


Ordering Information

When your order, specify the rated voltage.

Relays with Plug-in or Soldered Terminals


Type

Relays with PCB Terminals

4 poles

Classification

Model

Models with single


contacts

24, 100/110, or 110/120 VAC

MY4H

Bifurcated contacts

Type

Rated voltage (V)


12, 24, 48, or 100/110 VDC
24, 100/110, or 110/120 VAC

MY4ZH

12, 24, 48, or 100/110 VDC

4 poles

Classification

Model

Models with single


contacts

MY4H-0

Bifurcated
contacts

MY4ZH-0

Rated voltage (V)


110/120 VAC
24 VDC
24 or 100/110 VDC

Ratings and Specifications


Ratings
Operating Coil
Item
Rated voltage (V)
AC

DC

Rated current (mA)


50 Hz

60 Hz

Coil
resistance ()

Coil inductance (H)


Armature OFF

Armature ON

24

53.8

46

180

0.69

1.3

100/110

11.7/12.9

10/11

3,750

14.54

24.6

110/120

9.9/10.8

8.4/9.2

4,430

19.2

32.1

160

0.73

1.37

12

75

24

36.9

650

3.2

5.72

48

18.5

2,600

10.6

21.0

100/110

9.1/10

11,000

45.6

86.2

Must-operate
voltage (V)

Must-release
voltage (V)

Maximum
voltage (V)

Power consumption
(VA, W)
Approx. 1.0 to 1.2
(at 60 Hz)

30% min.*2
110% of
rated voltage

80% max.*1
10% min.*2

Approx. 0.9

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C with tolerances of +15%/20% for the AC rated current and 15% for the
DC coil resistance.
2. The AC coil resistance and inductance values are reference values only
3. Operating characteristics were measured at a coil temperature of 23C.
4. The maximum voltage capacity was measured at an ambient temperature of 23C.
*1. There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the
specified value.

Characteristics

Contact Ratings
Load

Models with single


contacts
Resistive
load

Item

Inductive load
cos = 0.4
L/R = 7 ms

Bifurcated contacts
Resistive
load

Inductive load
cos = 0.4
L/R = 7 ms

3 A at 110 VAC 0.8 A at 110 VAC 3 A at 110 VAC 0.8 A at 110 VAC
Rated load
3 A at 24 VDC 1.5 A at 24 VDC 3 A at 24 VDC 1.5 A at 24 VDC
Rated carry
3A
current

3A

Maximum contact 125 VAC


voltage 125 VDC

125 VAC
125 VDC

Maximum contact
3A
current

3A

Contact structure Single

Bifurcated

Contact materials Au plating + Ag


Ambient operating
temperature

25 to 60 C*

Ambient operating
humidity

5% to 85%

* With no icing or condensation.

Contact resistance*1

50 m max.

Operation time*2

20 ms max.

Release time*2

20 ms max.

Maximum
operating
frequency

Mechanical

18,000 operations/h

Rated load

1,800 operations/h

Insulation resistance*4
Dielectric
strength

Vibration
resistance

Between coil
and contacts
Between contacts
of different polarity

100 M min.
1,000 VAC at 50/60 Hz for 1 min.
(700 VAC between contacts of the same polarity.)

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude


(1.0-mm double amplitude)

Malfunction

10 to 55 to 10 Hz, 0.5-mm single amplitude


(1.0-mm double amplitude)

Destruction
Shock
resistance Malfunction

1,000 m/s2
200 m/s2

Mechanical

50,000,000 operations (5,000,000 operations*4) min.


(operating frequency: 18,000 operations/h)

Electrical*5

100,000 operations (50,000 operations*4) min. rated


load, switching frequency: 1,800 operations/h)

Endurance

Failure rate P value


(reference value)*6

Single contacts: 100 A at 1 VDC


Bifurcated contacts: 100 A at 100 mVDC

Weight

Approx. 50 g

Note: The above values are initial values.


*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method
*2. Measurement conditions: With rated operating power applied, not including contact
bounce.
Ambient temperature condition: 23 C
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric
strength measurement.
*4. This value is for bifurcated contacts.
*5. Ambient temperature condition: 23 C
*6. This value was measured at a switching frequency of 120 operations per minute.

31

MY

Engineering Data
Engineering Data
MY4H
Number of operations (104 operations)

Endurance Curve

MY4(Z)H
Contact current (A)

Maximum Switching Capacity

AC contact load

AC inductive load
(cos = 0.4)

1
0.5
DC contact load
DC inductive load
(L/R = 7 ms)

0.1

500
110 VAC resistive load

24 VDC resistive load

100
50

10
110 VAC inductive load
(cos = 0.4)

10

50

100

500

24 VDC inductive load (L/R = 7 ms)

Contact voltage (V)

Contact current (A)

Note: The durability of bifurcated contacts is one-half that of single contacts.

Dimensions

(Unit: mm)

Relays with Plug-in Terminals


or Soldered Terminals
MY4(Z)H

2.6

Fourteen, 1.2-dia. 3 oval holes

22 max.

Terminal Arrangement/
Internal Connections
(Bottom View)

0.5
28.5 max.

35 max.

6.4

Relays with PCB Terminals


MY4(Z)H-0

PCB Processing Dimensions


(Bottom View)
(The coil has no polarity.)

13.2

1.3 dia.

4.4
22 max.

5.5

3.95
4.9

1.3 dia.

6.35

28.5 max.

11.85

6.8
7

Fourteen, 2-dia. holes


35 max.

3.9

Safety Precautions
PCB Design for Hermetically Sealed Relays
When a Relay with PCB Terminals is mounted, a short-circuit can occur
depending on the design of the PCB pattern because the Relay itself is made
out of metal.

Solution
Refer to the external dimensions of the Relay and design the PCB pattern with
enough space to prevent this problem.

Applicable Sockets

Application Environment for Hermetically Sealed


Relays
Humid environments can cause insulation problems, which may result in shortcircuiting or unintended operation.

Solution
Do not use these Relays in any environment where the Relay will come into
contact with water vapor, condensation, or water droplets. This can reduce the
surface tension of the insulating beads and cause short-circuiting or unintended
operation due to poor insulation.

Use only combinations of OMRON Relays and Sockets.

Relay Replacement
To replace the Relay, turn OFF the power supply to the load and Relay coil
sides to prevent unintended operation and possible electrical shock.

32

MY
Options (Order Separately)
Connection Socket and Mounting Bracket Selection Table
Type

Front-mounting Sockets
Track or screw mounting
Terminal cover
structure

--Model

Screw terminal size: M3

MY2@
MY2(S)

PYF08A
(PYC-A1)

PYF08A-E
(PYC-A1)

MY2Z@-CR

PYF08A
(Y92H-3)

PYF08A-E
(Y92H-3)

MY3@

PYF11A
(PYC-A1)

MY4@
MY4(S)
MY4Z@
MY4Z-CBG
MYQ4@
MY4H
MY4ZH
MY2K@

Back-mounting Sockets

Screw
mounting only

Solder terminals
Screwless
Socket

--Screw terminal
size: M3.5
PYF08M
(PYC-P)

PYF08S

Wrapping terminals
Without Mounting
Brackets

Relays with
PCB
Terminals

With Mounting Brackets

Without
Mounting
Brackets

With
Mounting
Brackets

PY08
(PYC-P)

PY08-Y1

PY08QN
(PYC-P)

PY08QN2
(PYC-P)

PY08
(PYC-1)

PY08-Y3

PY08QN
(PYC-1)

PY08QN2
(PYC-1)

PY11
(PYC-P)

PY11-Y1

PY11QN
(PYC-P)

PY11QN2
(PYC-P)

PY11QN-Y1

PY11QN2-Y1

PY11-02
(PYC-P)

PY14
(PYC-P)

PY14-Y1

PY14QN
(PYC-P)

PY14QN2
(PYC-P)

PY14QN-Y1

PY14QN2-Y1

PY14-02
(PYC-P)

Terminal
Terminal
Terminal
Terminal
length: 25 mm length: 20 mm length: 25 mm length: 20 mm
PY08QN-Y1

PY08-02
(PYC-P)

PY08QN2-Y1

PY08-02
(PYC-1)

Screw terminal size: M3


PYF14A
(PYC-A1)

Screw terminal
size: M3.5

PYF14S

PYF14A-E
(PYC-A1)

PYF14T
(PYC-A1)

Note: 1. The information in parentheses is the model number of the applicable Mounting Bracket. Mounting Brackets are sold in sets of two. However, the PYC-P is
just one Mounting Bracket.
2. The PYF@A-E has a terminal cover with finger protection. Round terminals cannot be used. Use forked terminals or ferrules instead.
3. Refer to Common Socket and DIN Track Products for the external dimensions of the Socket Relays.
4. The Mounting Brackets are applicable for Relays with a height of 36 mm or less. If the Relay height is greater than 53 mm, use Y92H-3 for the Front-mounting
Socket and PYC-1 for the Back-mounting Socket. (The Y92H-3 is a set of two Brackets and the PYC-1 is just one Bracket.)
5. Refer to PYF@@S/P2RF-@-S for details on Screwless Sockets.
6. The terminal cover is integrated into the Socket.
7. If an MY@(S) Relay with a Latching Lever is used in combination with a PY@@-02 Socket for Relays with PCB Terminals and a PYC-P Mounting Brackets,
the lever will not operate.
8. We recommends using the PYC-E1 Mounting Bracket for a MY2(S) Relay with Latching Lever. (If the PYC-A1 is used with the MY2(S), the latching lever
will be blocked by the Mounting Bracket and the lever will not operate.)

Mounting Heights with Sockets (Unit: mm)


Front-mounting Sockets

Back-mounting
Sockets

Screwless Sockets
MY

MY
MY
70 (87)

66 (83)

73.6

MY
39 (56)

54 (71)

64

MY

64

28.6

28.6

PY@
PYF@A or PYF14T

72.6

PYF08S

PYF14S

(3.4)

PYF08M

(3.4)

Note: 1. The PYF@A can be mounted on a track or with screws.


2. The heights given in parentheses are the measurements
for 53-mm-high Relays.
3. Use the PYC-P Mounting Bracket for the PYF08M.

Socket Mounting Plate (t = 1.6) (Unit: mm)


Use a Socket Mounting Plate to mount multiple connection Sockets in a row.
Item

Applicable Sockets

Type For mounting


1 Socket

For mounting
8 Sockets

For mounting
36 Sockets

PYP-18

PYP-36

Without protective bracket PY08, PY08QN(2), PY11, PY11QN(2), PY14, and PY14QN(2)
With protective bracket

PYP-1

PY08-Y1, PY08QN(2)-Y1, PY11-Y1, PY11QN(2)-Y1, PY14-Y1,


and PY14QN(2)-Y1

PYP-18
72, oval holes

hole

Note: You can cut the PYP-18


and PYP-36 to any required
length.

PYP-36

Two, 3.4-dia. holes 5.1

Square

PYP-1

21.6

420.1 49

28

492
27.417 = 465.80.6
0.15
13.1
27.4 4.5
3.4
R1.7

492
72, oval holes
5.1

21.6

27.417 = 465.80.6
13.1
27.4
4.5
3.4
R1.7
0.15

21.4 +0.2
0

5.1

420.1 49

39.70.2
86.4

t = 1.6

The minimum order for the PYP-1 is 10 pieces.

39.70.2

13.1
27.417 = 465.80.6

21.6

t = 1.6

33

MY
Compliance with Electrical Appliances and Material Safety Act
All standard models comply with the Electrical Appliances and Material
Safety Act.
Always protect any exposed terminals (including Socket terminals) after
wiring with insulation tubes or resin coating on PCBs.

Model

MY

Number of
poles

Coil ratings

Contact ratings

1
2
3

6 to 220 VAC
6 to 120 VDC

5 A, 200 VAC

4*

6 to 110 VAC
6 to 120 VDC

3 A, 115 VAC

* Under the Electrical Appliances and Material Safety Act, do not use any 4pole models with a voltage that exceeds 150 VAC. However, this restriction
can be ignored if compliance with the Electrical Appliances and Material
Safety Act is not required.

Safety Precautions
Refer to the Common Relay Precautions.

Precautions for Correct Use


Handling

About the Built-in Diode and CR Elements

For models with a built-in operation indicator, models with a built-in diode, or
high-sensitivity models, check the coil polarity when wiring and wire all
connections correctly (DC operation).

The diode or CR element that are built into the Relay are designed to absorb
the reverse voltage from the Relay coil. If a large surge in voltage is applied to
the diode or CR element from an external source, the element will be destroyed.
If there is the possibility of large voltage surges that could be applied to the
elements from an external source, take any necessary surge absorption
measures.

Installation
There is no specifically required installation orientation, but make sure that
the Relays are installed so that the contacts are not subjected to vibration or
shock in their movement direction.

Latching Levers
Turn OFF the power supply when operating the latching lever. After you use
the latching lever always return it to its original state.
Do not use the latching lever as a switch.
The latching lever can be used for 100 operations min.

Relay Replacement
To replace the Relay, turn OFF the power supply to the load and Relay coil
sides to prevent unintended operation and possible electrical shock.

Attaching and Removing Relay Hold-down Clips


Use two M3 screws to attach case-surface-mounted models (MY@F) and
tighten the screws securely (tightening torque: 0.98 Nm).

When you attach a Hold-down Clip to or remove it from a Socket, wear gloves
or take other measures to prevent injuring your fingers on the Hold-down Clip.

Using MY-series Relays with Microloads with


Infrequent Operation
If any standard MY-series Relays (e.g., MY4) are used infrequently to switch
microloads, the contacts may become unstable and eventually result in poor
contact. In this case, we recommend using the MY4Z-CBG Series, which has
high contact reliability for microloads (Refer to page 25.)

34

Terms and Conditions Agreement


Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omrons exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omrons sole obligation hereunder shall be, at
Omrons election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omrons analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyers application or use of the Product. At Buyers request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyers application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the users programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omrons test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omrons Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omrons representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.