Vous êtes sur la page 1sur 128

Low Voltage

Prisma iPM
system L

Wall mounted switchboards up to 630A

Catalogue
2011

Illustrated table of contents of


Index of commercial numbers

A-2

Standards

A-12

Overview

A-8

Prisma iPM a tested


switchboard

A-17

Functional unit description

B-2

B-4

B-8

Compact NSX 100/630 A

B-12

EasyPact CVS 100/630 A

Easypact EZC 100 / 400 A

B-14
Interpact INS 250/630 A

B-16
Fupact INF

B-24
Industrial and control devices

Distribution description

B-28

B-26
Other devices

Human / Machine interface

C-2

C-5

D-2

Reserve space

C-6

Multi-stage busbars

Enclosure description

B-29

C-14
Distribution blocks

Rear busbars

D-4

D-5

IP30/40 PAK wall mounted enclosures

D-6

IP30/31 wall mounted enclosures

Spare parts

E-2

Mechanical characteristics

E-8

Electrical characteristics

E-3

Environment

E-12

Assembling recommendations

F-2

Assembling tips

F-8

IP40 wall mounted enclosures

Wall mounted system L

A-18

Tools and services

A-22

Commercial reference

Index and
presentation

Prisma iPM system L


A-24

Circuit breakers
B-20
Multi 9 modular devices

B-20
NG125 modular device

Fusegear

Functional units

Switch-disconnectors

Other
B-30

Partitioning
PAK and wall mounted
enclosures
D-7

IP54 wall mounted enclosures

D-8
IP30/31/40/54 enclosure accessories

D-10
Dimensions

Characteristics

Accessories

C-19

Recommendations

C-16

Enclosures

Distribution

Distribution

Functional units accessories

A-4

Index and presentation

Contents

System L

Index

A-2

Presentation

A-6

Index of catalogue numbers

Overview
Standards
Prisma iPM a tested switchboard
Wall mounted system L up to 630 A
Tools and services

Commercial reference

Commercial reference numbering system


Determining the commercial number

A-2

A-8
A-12
A-17
A-18
A-22

A-24

A-24
A-25

A-1

Index and presentation

Index of catalogue numbers

System L
Index
Com. no.

Designation

Page

Com. no.

Designation

Page

03180

20 M4 clip-nuts for slotted mounting plates

B-28

LSL58108A

Plain door W600 H500 8M

03181

20 M5 clip-nuts for slotted mounting plates

B-28

D-4
D-5

03182

20 M6 clip-nuts for slotted mounting plates

B-28

LSL58112A

Plain door W600 H700 12M

D-4
D-5

03195

4 M6 hexagonal spacers, H=9mm

B-30

LSL58116A

Plain door W600 H900 16M

03196

4 M6 hexagonal spacers, H=23mm

B-30

D-4
D-5

03197

4 M6 hexagonal spacers, H=55mm

B-30

LSL58120A

Plain door W600 H1100 20M

03581

2 universal angle brackets

B-30

D-4
D-5

04031

Polybloc distribution block, 1P, 160A

C-15

LSL58124A

Plain door W600 H1300 24M

D-4
D-5

04033

Polybloc distribution block, 3P, 250A

C-15

LSL58128A

Plain door W600 H1600 28M

D-5

04034

Polybloc distribution block, 4P, 250A

C-15

LSL58132A

Plain door W600 H1800 32M

D-5

04045

Distribloc 125A

B-21
B-23
C-15

LSL58149A

IP54 plain door W600 H500 8M

D-6
D-7

04171

4 bars with threaded holes, 160A, L=1400mm

C-12
C-13

LSL58150A

IP54 plain door W600 H700 12M

D-4
D-6
D-7

04172

4 bars with threaded holes, 250A, L=1400mm

A-25
C-12
C-13

LSL58151A

IP54 plain door W600 H900 16M

D-4
D-6
D-7

04173

4 bars with threaded holes, 400A, L=1400mm

C-12
C-13

LSL58152A

IP54 plain door W600 H1100 20M

04174

4 bars with threaded holes, 630A, L=1400mm

C-12
C-13

D-4
D-6
D-7

LSL58153A

IP54 plain door W600 H1300 24M

04195

40 M6x16mm screws for bars with threaded holes,


less than 630A

A-25
C-13
C-18

D-4
D-6
D-7

LSL58154A

IP54 plain door W600 H1600 28M

04197

Busbar power supply barrier, 630A

A-25
C-13

D-6
D-7

LSL58155A

IP54 plain door W600 H1800 32M

04226

Modular device rail, L=1600mm

B-25
B-28

D-6
D-7

LSL58157T

IP54 transparent door W600 H900 16M

04239

12 horizontal cable straps

A-25
B-21
B-23
C-17

D-4
D-6
D-7

LSL58158T

IP54 transparent door W600 H1100 20M

D-4
D-6
D-7

LSL58159T

IP54 transparent door W600 H1300 24M

D-4
D-6
D-7

LSL58160T

IP54 transparent door W600 H500 8M

D-6
D-7

LSL58161T

IP54 transparent door W600 H700 12M

D-4
D-6
D-7

LSL58162T

Transparent door W600 H500 8M

D-4
D-5

LSL58163T

Transparent door W600 H700 12M

D-4
D-5

LSL58164T

Transparent door W600 H900 16M

D-4
D-5

LSL58165T

Transparent door W600 H1100 20M

A-25
D-4
D-5

LSL58166T

Transparent door W600 H1300 24M

D-4
D-5

LSL58167T

Transparent door W600 H1600 28M

D-5

LSL58168T

Transparent door W600 H1800 32M

D-5

LSL58169T

IP54 transparent door W600 H1600 28M

D-6
D-7

04243

4 covers for horizontal cable straps

A-25
B-21
B-23
C-17

04255

12 horizontal trunking supports

B-21
B-23
C-18

04742

Insulated flexible bar 20x2mm, L=1800mm

C-16

04743

Insulated flexible bar 20x3mm, L=1800mm

C-16

04751

Insulated flexible bar 32x5mm, L=1800mm

C-16

04753

Insulated flexible bar 32x8mm, L=1800mm

C-16

08903

12 adhesive label holders, H=24mm, W=432mm

B-31

08913

12 clip-on labels, 18x35mm

B-31

08940

Barrel lock no. 405

D-9

08945

DIN double bar insert

D-9

08946

Screwdriver slot insert

D-9

08963

Adhesive drawing holder

D-9

LSL58033A

Door spare parts for system L

E-2

LSL58104A

IP30-IP54 plain door W600 H300 4M

D-4
D-5
D-6
D-7

A-2

Index and presentation

Index of catalogue numbers

System L
Index
Com. no.

Designation

Page

Com. no.

Designation

Page

LSL58170T

IP54 transparent door W600 H1800 32M

D-6
D-7

LSL58332A

IP30 WM enclosure W600 D305 H1800 32M

D-5
D-6

LSL58204A

IP30 WM enclosure W600 D235 H300 4M

D-5
D-6

LSL58336A

IP30 WM enclosure + door W300 D305 H1600 28M

D-5
D-6

LSL58205A

PAK WM enclosure W600 D235 H300 4M

D-4

LSL58337A

IP30 WM enclosure + door W300 D305 H1800 32M

LSL58208A

IP30 WM enclosure W600 D235 H500 8M

D-5
D-6

D-5
D-6

LSL58504A

IP54 WM enclosure W600 D235 H300 4M

D-7

LSL58209A

PAK WM enclosure W600 D235 H500 8M

D-4

LSL58508A

IP54 WM enclosure W600 D235 H500 8M

D-7

LSL58212A

IP30 WM enclosure W600 D235 H700 12M

D-5
D-6

LSL58512A

IP54 WM enclosure W600 D235 H700 12M

D-7

LSL58213A

PAK235 WM enclosure W600 D235 H700 12M

D-4

LSL58516A

IP54 WM enclosure W600 D235 H900 16M

D-7

LSL58216A

IP30 WM enclosure W600 D235 H900 16M

D-5
D-6

LSL58520A

IP54 WM enclosure W600 D235 H1100 20M

D-7

LSL58524A

IP54 WM enclosure W600 D235 H1300 24M

D-7

LSL58528A

IP54 WM enclosure W600 D305 H1600 28M

D-7

LSL58532A

IP54 WM enclosure W600 D305 H1800 32M

D-7

LSL58541A

IP54 WM enclosure + door W300 D235 H500 8M

D-7

LSL58542A

IP54 WM enclosure + door W300 D235 H700 12M

D-7

LSL58543A

IP54 WM enclosure + door W300 D235 H900 16M

D-7

LSL58544A

IP54 WM enclosure + door W300 D235 H1100 20M

D-7

IP54 WM enclosure + door W300 D235 H1300 24M

D-7

LSL58217A

PAK235 WM enclosure W600 D235 H900 16M

D-4

LSL58220A

IP30 WM enclosure W600 D235 H1100 20M

A-25
D-5
D-6

LSL58221A

PAK235 WM enclosure W600 D235 H1100 20M

D-4

LSL58224A

IP30 WM enclosure W600 D235 H1300 24M

D-5
D-6

LSL58225A

PAK235 WM enclosure W600 D235 H1300 24M

D-4

LSL58545A

LSL58231A

IP30 WM enclosure + door W300 D235 H500 8M

D-5
D-6

LSL58546A

IP54 WM enclosure + door W300 D305 H1600 28M

D-7

LSL58547A

IP54 WM enclosure + door W300 D305 H1800 32M

D-7

D-5
D-6

LSL58604A

System L front plate support 4M

D-4

D-5
D-6

LSL58608A

System L front plate support 8M

D-4

LSL58612A

Front plate support 12M

D-4

LSL58616A

Front plate support 16M

D-4

LSL58620A

Front plate support 20M

D-4

LSL58624A

Front plate support 24M

D-4

LSL58801A

L modular device rail

A-25
B-20
B-28

LSL58802A

L adjustable modular device rail

B-20
B-22
B-28
D-10
D-11
D-12
D-13

LSL58232A
LSL58233A
LSL58234A

IP30 WM enclosure + door W300 D235 H700 12M


IP30 WM enclosure + door W300 D235 H900 16M
IP30 WM enclosure + door W300 D235 H1100 20M

A-25
D-5
D-6

LSL58235A

IP30 WM enclosure + door W300 D235 H1300 24M

D-5
D-6

LSL58266A

L IP31 canopy, D=235mm, W=620mm

D-8

LSL58267A

L IP31 canopy, D=235mm, W=300mm

D-8

LSL58268A

L IP31 canopy extension, D=235mm, W=600mm

D-8

LSL58269A

L IP31 canopy, D=300mm, W=620mm

D-8

LSL58270A

L IP31 canopy, D=300mm, W=300mm

D-8

LSL58271A

L IP31 canopy extension, D=300mm, W=600mm

D-8

LSL58272A

Flush-mount kit up to 24 modules

D-8

LSL58803V

L mounting plate EZC100 3P4P/250 3P vertical

B-13

LSL58273A

4 assembly kit IP30 / 31 / 40

D-5
D-6

LSL58804H

L mounting plate EZC100 horizontal

B-13

LSL58805H

L mounting plate EZC250 3P horizontal

B-13

LSL58806V

L mounting plate EZC250 4P vertical

B-13

LSL58807H

L mounting plate EZC250 4P horizontal

B-13

LSL58808V

L mounting plate EZC400 vertical

B-13

LSL58810V

L mounting plate fupact INF D160 vertical front


direct

B-17

LSL58815H

L mounting plate NSX-INS250 horizontal toggle

A-25
B-7
B-11
B-15

LSL58816V

L mounting plate NSX-INS250 vertical toggle

A-25
B-7
B-11
B-15
B-25

LSL58274A

2 additional lifting / fixing rings

D-8

LSL58275A

Assembly kit IP54

D-7

LSL58276A

L IP40 accessories + gasket kit

D-4
D-6

LSL58279V

L vertical partition 28M 32M

C-19

LSL58280V

L vertical partition 4M to 24M

C-19

LSL58281H

L horizontal partition W500 D235

C-19

LSL58282H

L horizontal partition W500 D305

C-19

LSL58293A

4 wall mounted cable tie supports, W=300mm

A-25
D-9

LSL58296A

4 wall mounted cable tie supports, W=600mm

A-25
D-9

LSL58328A

IP30 WM enclosure W600 D305 H1600 28M

D-5
D-6

A-3

Index and presentation

Index of catalogue numbers

System L
Index
Com. no.

Designation

Page

Com. no.

Designation

Page

LSL58820V

L mounting plate NSX-INS630 vertical toggle

B-5
B-9
B-15

LSX58884A

Front plate modular device 4M

LSL58824A

L slotted mounting plate 4M

B-25
B-28
D-10
D-11
D-12
D-13

A-25
B-21
B-23
B-25
B-28

LSX58885A

Front plate modular device 5M

B-21
B-23
B-28

B-25
B-28
D-10
D-11
D-12
D-13

LSX58886V

Front plate EZC100 vertical

B-13

LSX58887H

Front plate EZC100 horizontal

B-13

LSX58888H

Front plate EZC250 3P horizontal

B-13

LSX58889V

Front plate 3/4 EZC250 vertical

B-13

B-28
D-10
D-11
D-12
D-13

LSX58890H

Front plate EZC250 4P horizontal

B-13

LSX58892V

Front plate EZC400 3P vertical

B-13

LSX58895V

Front plate 4 FUPACT INFD32/40 3P vertical

B-17

LSX58896V

Front plate 3 FUPACT INFD63 3P vertical

B-17

LSX58897V

Front plate 2 FUPACT INFD100/160 3P vertical

B-17

LSX58900H

Front plate CVS250 horizontal toggle

A-25
B-11

LSX58901H

Front plate INS250 horizontal

B-15

LSX58902V

Front plate 3/4 CVS-NSX-INS250 vertical toggle

B-7
B-11
B-25

LSX58903V

Front plate 3/4 CVS-NSX-INS250 vertical toggle

B-7
B-11

LSX58904H

Front plate NSX250 horizontal

B-7

LSX58905V

Front plate INS250 vertical

A-25
B-15

LSX58911V

Front plate CVS630 vertical toggle

B-9

LSX58912V

Front plate CVS630 vertical vigi

B-9

LSX58913V

Front plate NSX630 vertical

B-5

LSX58914V

Front plate INS630 vertical

B-15

LSX58921V

Front plate NSX630 vertical vigi

B-5

LSX58931A

Plain front plate 1M

A-25
B-5
B-7
B-11
B-13
B-15
B-21
B-23
B-25
B-29

LSX58932A

Plain front plate 2M

A-25
B-5
B-7
B-9
B-11
B-13
B-15
B-17
B-29

LSL58825A

LSL58826A

LSL58827A

L slotted mounting plate 12M

L plain mounting plate 4M

L plain mounting plate 12M

B-28
D-10
D-11
D-12
D-13

LSX58030A

20 front plate screws+nuts

E-2

LSX58031A

Prisma iPM spare parts handle

E-2

LSX58052A

Multiclip 200A 2P

B-21
C-15

LSX58053A

Multiclip 200A 3P

A-25
B-21
B-23
C-15

LSX58054A

Multiclip 200A 4P

B-21
B-23
C-15

LSX58070A

Cu earth / neutral bar 24M

A-25
C-17

LSX58080A

Rear busbars support

C-13

LSX58081A

Rear busbar barrier

C-13

LSX58082A

Multi-stage busbars support

A-25
C-13

LSX58621A

Blanking strip modular device L1000

B-21
B-23
B-28
B-30

LSX58751A

Blanking strip CVS/NSX250 L148

B-7
B-11
B-25
B-30

LSX58752A

Blanking strip EZC250 L1000

B-13
B-30

LSX58776A

Front plate hinge kit

B-25
B-30

LSX58777A

4 front plate lead-sealable screws

B-30

LSX58883A

Front plate modular device 3M

B-21
B-25
B-28

A-4

Index and presentation

Index of catalogue numbers

System L
Index
Com. no.

Designation

Page

LSX58933A

Plain front plate 3M

B-5
B-9
B-15
B-25
B-29

LSX58934A

Plain front plate 4M

B-5
B-9
B-25
B-29

LSX58936A

Plain front plate 6M

B-25
B-29
C-13

LSX58955A

Metal front plate with cut-outs, 3 modules


(for four 96 x 96 mm devices)

B-27

LSX58956A

Metal front plate with cut-outs, 3 modules


(for six 72 x 72 mm devices)

B-27

LSX58960A

Blanking plate (for 96 x 96 mm hole)

B-27

LSX58961A

Blanking plate (for 72 x 72 mm hole)

B-27

LSX58964T

Transparent front plate 4M

B-25
B-29

LSX58966T

Transparent front plate 6M

B-25
B-29

A-5

Lets pool our


energies for building
dependability

Ensuring the dependability


of electrical installations
of tertiary and industrial
buildings: continuity of
service and safety of life
and property.

A-6

Prisma iPM, a dependable,


simple, innovative solution
for LV electrical distribution
and control switchboards.

100% dependable
switchboards
Seize the Prisma iPM opportunity when assembling switchboards
that are optimised, tested and compliant with the IEC 61439-1 standard.
Prisma iPM is a prefabricated, modular solution unique in the market,
that is reliable and upgradeable.
You control your costs and deadlines. Buildings run perfectly.
Users work efficiently and safely.

Make the most of your energy

A-7

Lets develop installation


dependability

As building market professionals, you are faced with growing demands


for electrical installation continuity of service, safety of life and property
and deadline and cost control.

A-8

Prisma iPM
> An

innovative solution based on the


experience, expertise and switchgear
offerings from the global specialist in
energy management.
> Quality

production certified ISO 9001.

Using our Prisma iPM solution, you can easily


design, implement and operate low voltage
electrical distribution and control switchboards
that are dependable, because they are optimised,
tested and compliant with the IEC 61439 -1
standard.

Improve the
continuity of
service

Ensure the
safety of life
and property

Control
deadlines
and costs

A-9

Dedicating ourselves
to safe, simple low
voltage switchboards
Prisma iPM, a modular and prefabricated solution based on a complete
system in kit form, that fully integrates Schneider Electric switchgear offerings.

Energy is available
in the buildings
The Prisma iPM solution perfectly integrates
Schneider Electric switchgear and includes our
distribution systems and enclosures.
These quality components have been designed
to operate together with optimised performances:
mechanical electrical and communications
consistency are ensured.
Switchboards designed and manufactured with
the Prisma iPM solution have all the qualities
needed to ensure energy availability. They
are organised by function and by zone, which
improves reliability and facilitates design,
installation, operation and upgrading.
All switchboard architectures are factory tested
in line with specifications that go well beyond
the IEC 61439-1 standard.
The same continuity of service is ensured
throughout the switchboards entire
life cycle.

4
5

> Example of 28 modules wall mounted switchboard

A cable connection
area with complete
accessibility.

2 A zone for functional

units* dedicated to each


application in the building
(lighting, HVAC, lifts, etc).

* A functional unit includes


switchgear, mounting plate, front
plate and connections.

> Example of floor standing switchboard

A-10

> Example of 16 modules wall


mounted switchboard

3 A zone for current

distribution with innovative


busbars. The multistage
current distribution brings
lightness, ergonomics,
and easy front access.

IPXXB front plates for


protecting people from
any direct access to live
parts and circuits opening
and closing.

Attractive finish to fit


into any facility.

7 expertise
fields
> Mechanical
> Electrodynamics
> Thermal
> Internal arc
> Electromagnetic compatibility
> Seismic
> Insulation

Schneider Electric low voltage assembly


expertise: an answer to customer requests
> Short-circuit withstand
> Electromagnetic compatibility
> Protection of persons against electric shock
> Protection of persons and the assembly
against risk of fire
> Protection of the assembly against
environmental conditions

People and properties


are safe
With the Prisma iPM solution, you can be sure
that the coordination between the switchgear
and the current distribution system has been
tested on all types of switchboard architecture.
This favours flawless equipment operation.
The busbars are located in a protected area.
The clearances between conductors have been
calculated to prevent any risk of internal arc
or current leakage.
The switchgear, installed behind a front
plate, reveals only the operating handles.
Cable connection is performed in dedicated
areas preventing any contact with live parts.
The electrical installation is protected,
the panelbuilder and contractor as well as
the operator are in perfect safety.

Deadlines and costs


are controlled
The Prisma iPM solution facilitates switchboard
upgrading allowing its size to be optimised
during the design phase.
It offers tools and support services to effectively
help designers, panelbuilders, contractors as
well as operators develop their skills.

The environment
is respected
The Prisma iPM solution reduces the
environmental impact of the installations through
a process of continual improvement in favour of
sustainable development.
Schneider Electric uses all its expertise to set up
switchboard architectures which optimise energy
consumption.

99%

of material used
can be recovered
by dismantling.

A-11

Index and presentation

Standards

International electrotechnical standards

System L
Presentation

IEC international standards


IEC member countries
South Africa
Germany
Argentina
Australia
Austria
Belarus
Belgium
Brazil
Bulgaria
Canada
China
Korea (Rep. of)
Croatia
Denmark
Egypt
Spain
Finland
France
Greece
Hungary
India
Iran
Indonesia
Ireland
Israel
Italy

Japan
Luxemburg
Malaysia
Mexico
Norway
New Zealand
Pakistan
Netherlands
Poland
Portugal
Rumania
United Kingdom
Russia
Singapore
Slovakia
Slovenia
Sweden
Switzerland
Czech Rep.
Thailand
Turkey
Ukraine
United States
Yugoslavia

DD382009

National standards

The IEC (International Electrotechnical Commission) is a worldwide organisation for


standardisation comprising all national electrotechnical committees (IEC National
Committees).
The object of the IEC is to promote international cooperation on all questions
concerning standardisation in the electrical and electronic fields.
To that end, the IEC publishes International Standards.
Their preparation is entrusted to technical committees and any IEC National
Committee interested in the subject dealt with may participate in the preparatory
work.

In Europe
The IEC documents are first studied by CENELEC, which establishes:
bb either a European standard (EN), often identical to the IEC standard, which then
becomes the applicable national standard in all the member countries
bb or, if problems arise, a harmonisation document (HD).
Other IEC member countries
Each country is autonomous and can accept the IEC standard as the national
standard, with or without modifications.
Even though they are IEC members, countries such as Japan and the United States
continue to develop their own standardisation systems.
Countries without a standardisation system
It is possible to refer to an IEC standard in the framework of a project.

CEI / IEC
International Electrotechnical Commission
CENELEC
European Committee for Electrotechnical Standardisation
UTE
Union Technique de llectricit (French electrotechnical
standardisation organisation)
VDE
Verband der Elektrotechnik, Elektronik und Informationstechnik
e.v. (German electrotechnical, electronics and computer
technology standardisation organisation)
BSI
British Standards Institution
CCC
China Certification Center

A-12

Index and presentation

Standards

Tools for quality assurance

System L
Presentation

DD381776

DD381775

The different types of standards

There are different types of standards, including:


bb management standards,
bb installation standards,
bb product standards.

Management standards

ISO 9004: Quality management system - guidelines for performance improvement.


Used in setting up quality management systems.
ISO 9001: Quality management system - requirements. Used for certification audits.

Switchgear assemblies.
DD381778

DD381777

Design and manufacture.

ISO 14004: Environmental management system - major guidelines on the principles.


Systems and techniques implemented.
ISO 14001: Environmental management system - specification with guidance for
use.
A majority of Schneider Electric development centres and factories are certified
ISO 9001 and ISO 14001.

Installation standards
Switchgear devices.

Installation.

The set of IEC 60364-X standards defines the main principles and rules on:
bb assessment of general characteristics of installations,
bb protection,
bb selection and erection of equipment,
bb verification and maintenance of installations.

Product standards

They apply to LV switchgear devices or LV switchgear assemblies, where the


purpose is to ensure the correct operation and safety of the concerned products.
bb standards on switchgear devices:
v IEC 60947-1: general rules,
v IEC 60947-2: circuit breakers,
v IEC 60947-3: switches and disconnectors,
v IEC 60947-4: contactors,
v IEC 62208 / EN 50298: empty enclosures.
bb standards on switchgear assemblies:
v IEC 61439-1: General rules
v IEC 61439-2: Power switchgear and controlgear ASSEMBLIES (PSCASSEMBLIES)
v IEC 61439-3: Distribution boards (to supersede IEC 60439-3)
v IEC 61439-4: ASSEMBLIES for construction sites (to supersede IEC 60439-4)
v IEC 61439-5: ASSEMBLIES for power distribution (to supersede IEC 60439-5)
v IEC 61439-6: Busbar trunking systems (to supersede IEC 60439-2).

Regulations

The regulations in a given country may make certain standards legally binding and
may also create additional safety requirements.

Quality assurance

In addition to providing proof of the conformity of its quality management system, a


product manufacturer can demonstrate the quality of products by providing proof
that their design and manufacture comply with the requirements in the applicable
standard.
Proof of conformity may be a declaration by the manufacturer or a certificate supplied
by an independent organisation.

A-13

Index and presentation


System L

Standards

Standards IEC 61439-1

Presentation
All elements making up the electrical switchboard are concerned.
The object of standard IEC 61439-1 is to lay down the definitions and to state the
service conditions, construction requirements, technical characteristics and tests for
low-voltage switchgear and controlgear assemblies (U < 1000 V).
The standard defines a low-voltage switchgear and controlgear assembly (the
electrical switchboard) as a combination of one or more low-voltage switching
devices together with associated control, measuring, signalling, protective,
regulating equipment, etc., completely assembled under the responsibility of the
manufacturer with all the internal electrical and mechanical inter-connections and
structural parts.

Standard IEC 61439-1

These tests ensure the conformity of the electrical switchboard and are intended to
check switchboard characteristics.
b tests are carried out on typical configurations
b routine tests are carried out on the completely finished switchboard. Their purpose
is the check that the characteristics validated by the type tests were not altered
during the manufacturing operations.

The 12 design points tested by


schneider electric

1 - Strength of materials and parts

The mechanical, electrical and thermal capability of constructional materials and


parts of the assembly shall be deemed to be proven by verification of construction
and performance characteristics.
where an empty enclosure in accordance with IEC 62208 is used, and it has not
been modified so as to degrade the performance of the enclosure, no repetition of
the enclosure testing is required.

2 - Degree of protection of assemblies

The degree of protection shall be verified in accordance with IEC 60529; the test
may be carried out on a representative equipped assembly. Where an empty
enclosure in accordance with IEC 62208 is used, and no external modification has
been carried out that may result in a deterioration of the degree of protection, no
further testing is required.

3 - Clearances and creepage distances

For dimensioning clearances and creepage distances between separate circuits, the
highest voltage ratings shall be used (rated impulse withstand voltage for clearances
and rated insulation voltage for creepage distances).
The clearances and creepage distances apply to phase to phase, phase to neutral,
and except where a conductor is connected directly to earth, phase to earth and
neutral to earth.

4 - Protection against electric shock and integrity of protective


circuits
b Effectiveness of the protective circuit
b Effective earth continuity between the exposed conductive parts of the assembly
and the protective circuit
b Short-circuit withstand strength of the protective circuit

5 - Incorporation of switching devices and components

Compliance with the design requirements, the incorporation of switching devices


and components shall be confimed by inspection and verified to the requirements of
this standard.
b Electromagnetic compatibility

6 - Internal electrical circuits and connections


7 - Terminals for external conductors

Compliance with the design requirements for terminals for external conductors shall
be confirmed by inspection.

8 - Dielectric properties

All the electrical equipment of the assembly shall be connected, except those items
of apparatus which, according to the relevant specifications, are designed for a lower
test voltage; current-consuming apparatus (e.g. windings, measuring instruments,
voltage surge suppression devices) in which the application of the test voltage would
cause the flow of a current, shall be disconnected. Such apparatus shall be
disconnected at one of their terminals unless they are not designed to withstand the
full test voltage, in which case all terminals may be disconnected.

A-14

Index and presentation


System L

Standards

Standards IEC 61439-1

Presentation
9 - Verification of temperature rise
b Verification by testing with current
b Derivation of ratings for similar variants
b Verification by calculation

10 - Short-circuit withstand strength

The short-circuit withstand strength declared by the originalmanufacturer shall be


verified. Verification may be by the application of design rules, by calculation or by
test as specified.
b Circuits of assemblies which are exempted from the verification of the short-circuit
withstand strength
b Verification by the application of design rules
b Verification by comparison with a reference design
b Verification by test

11 - Electromagnetic compatibility(EMC)
b Assembles not incorporating electronic circuits
b Assembles incorporating electronic circuits

12 - Mechanical operation

This verification test shall not be made on such devices of the assembly which have
already been type tested according to their relevant product standard unless their
mechanical operation is impaired by their mounting.
For parts, which need verification by test, satisfactory mechanical operation shall be
verified after installation in the assembly. The number of operating cycles shall be
200.

Routine Verification

Series of test under responsibility of the assemblers that must be performed for each
LV assembly.

1 - Degree of protection of enclosures


2 - Clearances and creepage distances
3 - Protection against electric shock and integrity of protective
circuits
4 - Incorporation of built-in components
5 - Internal electrical circuits and connections
6 - Terminals for external conductors
7 - Mechanical operation
8 - Dielectric properties
9 - Wiring, operational performance and function

A-15

Index and presentation


System L

Standards

Enclosure standards
IEC 62208 and EN 50298

Presentation
Standards IEC 62208 and EN 50298
Empty enclosures for low-voltage switchgear and
controlgear assemblies

General rules for empty enclosures


Standards IEC 62208 and EN 50298 lay down definitions, classifications,
characteristics and test requirements for the enclosures used for assemblies.
They apply to empty enclosures before installation of the devices by the panel
builder, as supplied by the manufacturer.
They apply to one-piece enclosures and to enclosures supplied in kit form.

Type tests

1 - Static load
2 - Hoisting
3 - Axial loads of metal inserts
4 - IK code
5 - IP code
6 - Thermal stability
7 - Resistance to heat
8 - Resistance to abnormal heat and to fire
9 - Dielectric strength
10 - Protective-circuit continuity
11 - Weather resistance
12 - Corrosion resistance
13 - Marking.

A-16

Index and presentation

Prisma iPM a tested switchboards

System L
Presentation
A switchboard must comply with the requirements in standard IEC 61439-1 to
guarantee the safety and reliability of the installation.
Managers of installations, fully aware of the professional and legal liabilities weighing on their
company and on themselves, demand a high level of safety for the electrical installation.
What is more, the serious economic consequences of prolonged halts in production
mean that the electrical switchboard must provide excellent continuity of service,
whatever the operating conditions.

The Schneider Electric solution

bb Specify switchboards that comply with standard IEC 61439-1.


bb Guarantee a level of safety that has been 100% tested, from the day the
switchboard is installed and throughout its service life.
bb Ensure the return on investment through easy upgrading of the installation in
compliance with the standard.
bb Guarantee that the switchboard complies with the technical specifications.

Prisma iPM tested switchboards

The conformity of the switchboard has been tested and proven.


A Prisma iPM switchboard is:
bb made up of Schneider Electric low-voltage devices and components that all
comply with the applicable standards,
bb based on configurations in the Schneider Electric catalogue,
bb made up of Prisma iPM mechanical and electrical components that have been
subjected to the twelve tests required by the standard,
bb mounted and wired by a panel builder in compliance with professional standards,
bb subjected to the three routine tests required by the standard.
Schneider Electric makes available to the panel builder everything required to create
tested Prisma iPM switchboards, including the basic configurations in the
low-voltage distribution catalogue, all the documentation for switchboard design and
mounting, calculation and design software, etc.
The panel builder can easily demonstrate conformity with standard IEC 61439-1 by
presenting the declarations or certificates of conformity concerning the type tests carried
out by independent laboratories (CCC, ASEFA) and supplied by Schneider Electric.
The panel builder is responsible for the three routine tests and delivers the
corresponding declarations of conformity.

Certifications

A-17

Index and presentation


System L
Presentation

DD800462

Incoming feeders and main LV


switchboards

Currents up to 6300 A.

Currents up to 4000 A.

Power distribution
and loads

Currents up to 4000 A.

Currents up to 630 A.

Currents up to 250 A.

A-18

Wall mounted system L


up to 630 A

Index and presentation


System L

Wall mounted system L


up to 630 A

Presentation

Main characteristics

In-door wall mounted system

DD800162

Electrical characteristics
Nominal rated current (A)
Rated insulation voltage Ui
(V AC)
Rated operation voltage
(V AC)
Rated impulse withstand
voltage (KV)
Frequency (Hz)
Main busbar rated current
max. Ie (A)
Rated short-time withstand
current Icw (KA/1 s.)
Rated peak withstand
current Ipk (KA)
Neutral network

630
1000
690
8
50/60
630
25
53
TNC

TNS

IT

TT

Enclosure characteristics (dimensions, IP, )


Overall height (mm)
300
500 700 900 1100 1300 1650 1850
Number of vertical modules 4
8
12
16
20
24
28
32
(functional height)
1 module = 50 mm
Depth (mm)
235
305
Width of enclosure for
600
devices (mm)
Width of cable duct (mm)
300
Partitioning
1
IP
30/31/40/54
IK
07/08/10
Aplicable standards
Type test
IEC61439-1
IP class
IEC60529
Insulation materials inside
IEC60695
of enclosures
Environment conditions
Operation
indoor
Altitude max. (m)
2000
Temperature average max. 35
(C)
Temperature max. (C)
45
Temperature min. (C)
0
Moisture
40% to 20%
Climatic class
T2
Degree of pollution
3
Others
Enclosure materials
sheet metal
Painting
epoxy resin powder electrostatic sprayed
Colour
RAL 7047 (enclosure) and RAL 9022 (functional unit)
Insulation materials inside
high-temperature withstand, combustion self-prevent
of enclosure
A-19

Index and presentation


System L

Wall mounted system L


up to 630 A

Configuration

DD800332

Presentation

PD800071

PD800069

Vigi

Functional
height in
modules

Application

A-20

Overall
height in
mm

This configuration is adapted for lighting, HVAC, lift, etc in tertiary and industrial
buildings.

Index and presentation


System L

Wall mounted system L


up to 630 A

NSX400 3P

PD800066

Configuration

DD800333

Presentation

Functional
height in
modules

Application

Overall
height
in mm

This configuration is adapted for lighting, HVAC, lift, etc in tertiary and industrial
buildings.

A-21

Tools and services

Index and presentation


System L
Presentation
Schneider Electric provides a large range of tools and
services to support you all along the life cycle of the
product.
For futher information, please consult us or see
Schneider Electric website:
www.schneider-electric.com.

Design, order
bb Catalogue
bb Technicial guide for Pnb
Software
bb Thermal calculation
Technical information
bb AutoCAD library
bb Bars drawings library
bb Derating tables
On-line support
bb Customer Care Center

Design &
implementation

Order

Advice, order
bb Catalogue
Software
bb Bom tool
On-line support
bb Customer Care Center

Specifications
& tendering

Promotional
bb Promotional leaflets
bb Posters, videos
bb Customer conferences
Advice, order
bb Catalogue
Specifications
bb Type tested conference
bb New IEC conference
bb Specification forms
Software
bb Flash quotation

A-22

Training
bb Training sessions

Index and presentation

Tools and services

System L

DD800163

Presentation

Commissioning

Operation
& recycling

Assembling

Guides
bb Technical guide for
Pnb

Recycling
bb Product Environmental
Profile

PD800039

Guides
bb Technical guide for Pnb
bb Mounting leaflets library
bb Busbar drawings

Operation
bb Technical guide for Pnb

A-23

Commercial reference
numbering system

Index and presentation


System L
Commercial reference

Commercial-number composition

L S p 5 p p p p p
bb One letter designating the voltage.
Voltage
Low

Code
L

bb One letter designating the product.


Type
Switchboard

Code
S

bb One letter designating the family.


Type

Code

Floor-standing system

Wall mounted system

Common

bb One number designating the brand.


Brand
Prisma iPM

Code
5

bb Four numbers designating the reference.


bb One number indicating characteristics specific to the
component.
Characteristic

Code

Drawout

Fixed

Non-significant

Horizontal

Transparent

Vertical

Rear connection

Five-figure commercial
numbers

A-24

Some products have 5-figure commercial numbers. These products are sold in other
Schneider Electric product ranges and are totally compatible with Prisma iPM
electrical switchboard range.

Determining the commercial


number

Index and presentation


System L

Using the circuit diagram

DD800137

Commercial reference

Draw up the list of devices to be installed grouping


them together in families.

And using the commercial


number tables

The selection of the functional unit is done after


selectioning the electrical devices (circuit breakers,
modular switchgears, etc.).

Circuit Mounting
breaker plate

Front plates
cut-out

upstream

No. of
downstream vertical
module

INS 250 LSL58816V LSX58905V LSX58931A LSX58932A

DD800006

Reminder: 1 module = 50 mm

determine:
bb the number of vertical modules required;
bb the commercial numbers for mounting plate and
front plates.

Set of
Busbar
4 drilled bars support
04172

DD800019

1 For the incoming unit, if it is not installed in the duct,


Front Mounting
barrier hardware

4 x LSX58082A

04197

04195

LSL58815H

NSX 100

Front plate

No. of vertical
module

LSX58900H
LSX58931A

Modular
devices

Modular
rail

Front plate Additional


front plate

No. of vertical
module

LSL58801A LSX58884A LSX58931A


1 row
Multi 9(1)
(1) 48 x 9 mm.
Distribution block Quantity
Multiclip 200 A, 3P

Com. no.
LSX58053A

18

Module total =

3 Add-up the number of modules required.


4 Based on the degree of protection IP, on the number
of modules required, choose the enclosure.

5 If the devices to be installed do not occupy the whole


enclosure, complete the front panel with an extra plain
front plate.

6 Determine the necessary accessories:


bb for distribution,
bb for cable running,
bb for the overall installation.

DD800139

bb the distribution block: Multiclip, comb, etc.

Circuit breaker Mounting plate

Height of the corresponding enclosure =


Enclosure

20

Com. no.

IP30/ wall mounted enclosure W = 600 mm,


D = 235 mm, H = 1100 mm, 20 modules

LSL58220A

IP30/ wall mounted enclosure with door W = 300 mm,


D = 235 mm, H = 1100 mm, 20 modules

LSL58234A

Transparent door W = 600 mm, H = 1100 mm,


20 modules

LSL58165T

Plain front plate


20 - 18 = 2 modules

Description

Com. no.
LSX58932A

DD800140

bb the number of vertical modules required,


bb the commercial numbers for the modular rail and the
front plate,

DD381583

2 For the outgoing units, determine:

DD800138

Determine the connection and its width so as to


connect the incoming unit to the busbars, or the
distribution block and its width.

Com. no.

12 cable straps for horizontal cables

04239

4 covers for horizontal cable straps L = 430 mm

04243

4 wall mounted cable tie supports, W = 300 mm

LSL58293A

4 wall mounted cable tie supports, W = 600 mm

LSL58296A

Cu earth/neutral bar, 24 modules

LSX58070A

A-25

Functional units

Contents

System L

Description

B-2

Commercial numbers

B-4

Functional units up to 630 A

Compact NSX 400 to 630 A


Compact NSX 100 to 250 A
EasyPact CVS 400 to 630 A
EasyPact CVS 100 to 250 A
Easypact EZC from 100 to 400 A
Interpact INS 250 to 630 A
Fupact INF 32 to 160 A
Widths of modular devices
Multi 9/Acti 9 63 A
NG 125, C120
INS 40/160 switch disconnectors
Industrial and control devices
Human/Machine interface
Other devices
Reserve space
Functional unit accessories

B-2

B-4
B-6
B-8
B-10
B-12
B-14
B-16
B-18
B-20
B-20
B-22
B-24
B-26
B-28
B-29
B-30

B-1

Functional units

Functional units up to 630 A

System L
Description
The functional unit is defined in the IEC 61439.1 standard as
followed:
A part of an assembly comprising all the mechanical and electrical
elements that contribute to the fulfilment of the same function.

PD800003

Each device is part of a functional unit comprising:


bb a dedicated mounting plate for device installation,
bb a front plate to block direct access to live parts,
bb the device connections or distribution solutions,
bb systems for on-site connections and running of auxiliary wires.
The functional units are modular and are arranged rationally, one on top of another,
within the enclosure.
The system includes everything required for functional unit mounting, supply and on
site connection.
The components of the Prisma iPM functional units have been designed and tested
taking into account device characteristics.
This design approach ensures a high degree of reliability in system operation and
optimum safety for people.

DD800432

Mounting plates

The devices are mounted on a mounting plate. The space occupied by the mounting
plate corresponds to the device dimensions: optimization of the occupied space.
Prisma iPM offers a complete range of mounting plates for each type of devices up
to 630 A:
bb EasyPact CVS and Compact NSX,
bb Interpact INS,
bb Easypact EZC,
bb modular devices,...
Plain or slotted mounting plates are available for other devices.
The mounting plates have threaded holes for direct mounting from the front.
The fixing screws of the mounting plate are supplied with.
The mounting plates have slots for tightening power cable and auxiliary connection.
It is front connected, without nuts, using thread-forming screws.
The use of thread-forming screws is mandatory to ensure electrical continuity
between exposed conductive parts.

B-2

Functional units

Functional units up to 630 A

System L
Description

DD800123

Modular rails

The modular rails are supplied ready for mounting with screws.
The symmetrical rail is made of an aluminium alloy and is very rigid.
The supports are factory mounted (crimped on the rails) and screw to the functional
uprights using two thread-forming, captive screws that also ensure the electrical
continuity of the exposed conductive parts.
The ends of the supports overrun the edge of the rails to act as a stop for the
modular devices.
Different type of rails:
bb modular devices rail
bb adjustable rail
bb rail for direct mounting on the functional uprights.
Rails can be fitted with devices, modular distribution blocks, contactors,
transformers, various auxiliary devices and terminal blocks and all cable-running
accessories such as straps and trunking supports, as well as the supports for
earth-neutral bars.

DD800279

Front plates

For more safety, the front plates only allow access to the device setting and control
devices. It ensures the IPxxB protection degree.
Each device has its own front plate with the appropriate cut-outs.
Prisma iPM offers a complete range of front plates for each type of devices up to 630
A:
bb EasyPact CVS and Compact NSX,
bb Interpact INS,
bb Easypact EZC,
bb modular devices,
bb 72 x 72 and 96 x 96 mm measurement devices, ...
The various front plates are coloured in grey aluminium RAL 9022.
There are blanking strips (L = 1000 mm) to blank off the unused space on the
cut-out front plate. Also available in the catalogue are labels that fit on the front plate
or may be screwed to a door or front plate.
Plain and transparent front plates are also available in the catalogue.
Each front plate is front mounted on the supports by captive screws and nuts.
Electrical continuity of exposed conductive parts is ensured by the studs of the nuts
and the fixing screws (supplied).
The front plates are mounted on a front frame. It enables to assemble the front plates
at the workshop and to mount it on the wall mounted enclosure at the worksite. All
the front plates can be removed in one operation, as they are fixed on the frame.
Plain front plates are available in the catalogue to blank off empty areas.

DD800465

Reserve space

B-3

Compact NSX 400 to 630 A

Functional units

Selection table

System L
Commercial numbers

Vertical installation

DD800023

Circuit breaker

Accessories

Front connection Control

Type

No. of pole

NSX400

direct by cables

toggle

fixed

3/4P

NSX630

direct by cables

toggle

fixed

3/4P

Vigi NSX400

direct by cables

toggle

fixed

3/4P

Vigi NSX630

direct by cables

toggle

fixed

3/4P

DD383974

For the functional unit accessories, see page B-30~B-31.

T
LIGH

Distribution solutions
DD800001

DD800002

For the distribution solutions, see page C-2~C-4.

Rear busbars

B-4

Multi-stage busbars

Compact NSX 400 to 630 A

Functional units

Selection table

System L
Commercial numbers

Mounting plate

11

LSL58820V

9 modules

LSX58913V

1 modules

LSX58931A

1 modules

LSX58931A

14

LSL58820V

9 modules

LSX58913V

2 modules

LSX58932A

3 modules

LSX58933A

13

LSL58820V

9 modules

LSX58921V

2 modules

LSX58932A

2 modules

LSX58932A

b
b

16

LSL58820V

9 modules

LSX58921V

3 modules

LSX58933A

4 modules

LSX58934A

Front plate
cut-out

+ upstream

Long terminal
shield

+ downstream
DD800181

DD800180

DD800179

DD800178

No. of vertical modules


(1 module = 50 mm)

Mandatory.
Optional.

B-5

Compact NSX 100 to 250 A

Functional units

Selection table

System L
Commercial numbers

Horizontal installation
Circuit breaker

Duct

Incoming No. of devices


per row

DD800184

NSX250

DD800183

DD800025

NSX100/160

DD800529

(1)

Vigi NSX100/160
DD800183

DD800184

Vigi NSX250

DD800529

(1)

Front
connection

Control

Type

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

(1) Maximum size of connection cables: 70 mm.


For cable cross-sections greater than 70 mm, use of a cable duct is mandatory.

Vertical installation

DD800024

Circuit breaker

Front
connection

Control

Type

No. of
pole

NSX100/160

4 x 3P, 3 x 4P

direct by cables

toggle

fixed

3/4P

NSX250

4 x 3P, 3 x 4P

direct by cables

toggle

fixed

3/4P

Vigi NSX100/160 4 x 3P, 3 x 4P

direct by cables

toggle

fixed

3/4P

Vigi NSX250

direct by cables

toggle

fixed

3/4P

4 x 3P, 3 x 4P

For the functional unit accessories, see page B-30~B-31.

DD383974

Accessories

No. of devices
per row

T
LIGH

Rear busbars

B-6

Multi-stage busbars

DD800463

DD800002

For the distribution solutions, see page C-2~C-4.


DD800001

Distribution

Polybloc distribution block

Compact NSX 100 to 250 A

Functional units

Selection table

System L
Commercial numbers

Front plate
cut-out

+ downstream
DD800181

+ upstream
DD800180

Mounting plate

DD800179

No. of vertical
modules
(1 module = 50 mm)

DD800182

No. of pole

3/4P

LSL58815H

4 modules

LSX58904H

1 module

3/4P

LSL58815H

4 modules

LSX58904H

3/4P

LSL58815H

4 modules

LSX58904H

2 modules

LSX58932A

LSX58904H

2 modules

LSX58932A

2 modules

LSX58932A

3/4P

LSL58815H

4 modules

3/4P

LSL58815H

4 modules

LSX58904H

1 module

LSX58931A

3/4P

LSL58815H

4 modules

LSX58904H

2 modules

LSX58932A

3/4P

LSL58815H

4 modules

LSX58904H

2 modules

LSX58932A

3/4P

LSL58815H

4 modules

LSX58904H

2 modules

LSX58932A

2 modules

Front plate
cut-out

2 modules

LSX58932A

LSX58932A

Blanking strip

LSL58816V

5 modules

LSX58902V

LSL58816V

5 modules

LSX58902V

2 modules

LSL58816V

7 modules

LSX58903V

11

LSL58816V

7 modules

LSX58903V

2 modules

DD800181

+ downstream

DD800180

+ upstream

DD800179

DD800178

No. of vertical modules Mounting plate


(1 module = 50 mm)

LSX58931A

1 modules

LSX58931A

LSX58751A

LSX58932A

2 modules

LSX58932A

LSX58751A

1 modules

LSX58931A

LSX58751A

LSX58932A

2 modules

LSX58932A

LSX58751A

Mandatory.
Optional.

B-7

EasyPact CVS 400 to 630 A

Functional units

Selection table

System L
Commercial numbers

Vertical installation

DD800000

Circuit breaker

Type

No. of pole

CVS400

direct by cables

toggle

fixed

3/4P

CVS630

direct by cables

toggle

fixed

3/4P

Vigi CVS400

direct by cables

toggle

fixed

3/4P

Vigi CVS630

direct by cables

toggle

fixed

3/4P

For the functional unit accessories, see page B-30~B-31.

DD383974

Accessories

Front connection Control

T
LIGH

Rear busbars

B-8

DD800002

For the distribution solutions, see page C-2~C-4.


DD800001

Distribution solutions

Multi-stage busbars

EasyPact CVS 400 to 630 A

Functional units

Selection table

System L
Commercial numbers

Front plate
cut-out

Long terminal
shield

+ downstream

DD800180

DD800181

+ upstream

DD800179

DD800178

No. of vertical modules Mounting plate


(1 module = 50 mm)

11

LSL58820V

7 modules

LSX58911V

2 modules

LSX58932A

2 modules

LSX58932A

14

LSL58820V

7 modules

LSX58911V

3 modules

LSX58933A

4 modules

LSX58934A

13

LSL58820V

9 modules

LSX58912V

2 modules

LSX58932A

2 modules

LSX58932A

b
b

16

LSL58820V

9 modules

LSX58912V

3 modules

LSX58933A

4 modules

LSX58934A

Mandatory.
Optional.

B-9

Functional units
System L

EasyPact CVS 100 to 250 A


Selection table

Commercial numbers

Horizontal installation
Circuit breaker

Duct

Incoming No. of devices


per row

DD800184

DD800183

DD800003

CVS100/160
CVS250

DD800529

(1)

Vigi CVS100/160
DD800183

DD800184

Vigi CVS250

DD800529

(1)

Front
connection

Control

Type

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

1 x 3P, 1 x 4P

direct by cables

toggle

fixed

(1) Maximum size of connection cables: 70 mm.


For cable cross-sections greater than 70 mm, use of a cable duct is mandatory.

Vertical installation

DD800004

Circuit breaker

Front
connection

Control

Type

No. of pole

CVS100/160

4 x 3P, 3 x 4P

direct by cables

toggle

fixed

3/4P

CVS250

4 x 3P, 3 x 4P

direct by cables

toggle

fixed

3/4P

Vigi CVS100/160 4 x 3P, 3 x 4P

direct by cables

toggle

fixed

3/4P

Vigi CVS250

direct by cables

toggle

fixed

3/4P

4 x 3P, 3 x 4P

For the functional unit accessories, see page B-30~B-31.

DD383974

Accessories

No. of devices
per row

T
LIGH

Rear busbars

B-10

Multi-stage busbars

DD800463

DD800002

For the distribution solutions, see page C-2~C-4.


DD800001

Distribution

Polybloc distribution block

EasyPact CVS 100 to 250 A

Functional units

Selection table

System L
Commercial numbers

Front plate
cut-out

+ upstream

+ downstream

DD800180

DD800181

Mounting plate

DD800179

No. of vertical
modules
(1 module = 50 mm)

DD800182

No. of
pole

3/4P

LSL58815H

4 modules

LSX58900H

1 module

3/4P

LSL58815H

4 modules

LSX58900H

3/4P

LSL58815H

4 modules

LSX58900H

2 modules

LSX58932A

LSX58900H

2 modules

LSX58932A

2 modules

LSX58932A

3/4P

LSL58815H

4 modules

3/4P

LSL58815H

4 modules

LSX58900H

1 module

LSX58931A

3/4P

LSL58815H

4 modules

LSX58900H

2 modules

LSX58932A

3/4P

LSL58815H

4 modules

LSX58900H

2 modules

LSX58932A

3/4P

LSL58815H

4 modules

LSX58900H

2 modules

LSX58932A

2 modules

Front plate
cut-out

2 modules

LSX58932A

LSX58932A

Blanking strip
+ downstream

LSL58816V

5 modules

LSX58902V

LSL58816V

5 modules

LSX58902V

2 modules

LSL58816V

7 modules

LSX58903V

11

LSL58816V

7 modules

LSX58903V

2 modules

DD800181

DD800180

+ upstream

DD800179

DD800178

No. of vertical modules Mounting plate


(1 module = 50 mm)

LSX58931A

2 modules

LSX58932A

LSX58751A

LSX58932A

2 modules

LSX58932A

LSX58751A

2 modules

LSX58932A

LSX58751A

LSX58932A

2 modules

LSX58932A

LSX58751A

Mandatory.
Optional.

B-11

Functional units
System L

Easypact EZC from 100 to 400 A


Selection table

Commercial numbers

Horizontal installation
Circuit breaker

Duct

Incoming No. of
devices
per row

DD800184

DD800183

DD800036

EZC100
EZC250

DD800529

(1)

Front
connection

Control

Type

1 x 3P

direct by cables

toggle

fixed

1 x 3/4P

direct by cables

toggle

fixed

1 x 3/4P

direct by cables

toggle

fixed

1 x 3/4P

direct by cables

toggle

fixed

(1) Maximum size of connection cables: 70 mm.


For cable cross-sections greater than 70 mm, use of a cable duct is mandatory.
(2) If EZC100 connected to rear busbars, add a 2 modules front plate LSX58932A.

Vertical installation

DD800007

Circuit breaker

No. of devices
per row

Front
connection

Control

Type

No. of pole

EZC100

5 x 3P, 3 x 4P

direct by cables

toggle

fixed

3 / 4P

EZC250

4 x 3P

direct by cables

toggle

fixed

3P

3 x 4P

direct by cables

toggle

fixed

4P

1 x 3P

direct by cables

toggle

fixed

3P

EZC400

For the functional unit accessories, see page B-30~B-31.

DD383974

Accessories
T
LIGH

Rear busbars

B-12

DD800002

For the distribution solutions, see page C-2~C-4.


DD800001

Distribution solutions

Multi-stage busbars

Easypact EZC from 100 to 400 A

Functional units

Selection table

System L
Commercial numbers

Front plate
cut-out

+ downstream
DD800181

+ upstream
DD800180

Mounting plate

DD800179

No. of vertical
modules
(1 module = 50 mm)

DD800038

No. of pole

LSL58804H

2 modules

LSX58887H

1 module

LSL58805H

3 modules

LSX58888H

4P

LSL58807H

4 modules

LSX58890H

3P

LSL58805H

3 modules

LSX58888H

2 modules

LSX58932A

4P

LSL58807H

4 modules

LSX58890H

2 modules

LSX58932A

3P

LSL58805H

3 modules

LSX58888H

2 modules

LSX58932A

2 modules

LSX58932A

4P

LSL58807H

4 modules

LSX58890H

2 modules

LSX58932A

2 modules

LSX58932A

No. of vertical
modules
(1 module = 50 mm)

Mounting plate

Front plate
cut-out

LSL58803V

5 modules

LSX58886V

2 modules

LSL58803V

9 modules

LSX58889V

LSL58806V

9 modules

LSX58889V

11

LSL58808V

10 modules

LSX58892V

1 module

LSX58931A

(2)

2 modules

LSX58932A

2 modules

LSX58932A

Blanking strip
L = 1000 mm

DD800181

+ downstream

DD800179

DD800038

3P
3P

LSX58932A

LSX58752A
LSX58752A
LSX58752A

LSX58931A

Mandatory.
Optional.

B-13

Functional units
System L

Interpact INS 250 to 630 A


Selection table

Commercial numbers

Horizontal installation
Duct

DD800184

DD800005

INS250

Incoming Front
connection

DD800183

Circuit breaker

DD800529

(1)

Control

No. of pole

direct by cables

direct front
rotary handle

3/4P

direct by cables

direct front
rotary handle

3/4P

direct by cables

direct front
rotary handle

3/4P

(1) Maximum size of connection cables: 70 mm.


For cable cross-sections greater than 70 mm, use of a cable duct is mandatory.

Vertical installation
Circuit breaker

DD800006

INS250
INS320/400
INS500/630

Front
connection

Control

No. of pole

3x3P, 3x4P

direct by cables

direct front
rotary handle

3/4P

1x3P, 1x4P

direct by cables

direct front
rotary handle

3/4P

1x3P, 1x4P

direct by cables

direct front
rotary handle

3/4P

For the functional unit accessories, see page B-30~B-31.

DD383974

Accessories

No. of device per


row

T
LIGH

Rear busbars

B-14

Multi-stage busbars

DD800463

DD800002

For the distribution solutions, see page C-2~C-4.


DD800001

Distribution solutions

Polybloc distribution block

Interpact INS 250 to 630 A

Functional units

Selection table

System L
Commercial numbers

Mounting plate

LSL58815H

4 modules

LSX58901H

LSL58815H

4 modules

LSX58901H

2 modules

LSX58932A

LSL58815H

4 modules

LSX58901H

2 modules

LSX58932A

2 modules

No. of vertical
modules
(1 module = 50 mm)

Mounting plate

Front plate
cut-out

LSL58816V

5 modules

LSX58905V

1 module

LSX58931A

2 modules

LSX58932A

10

LSL58820V

6 modules

LSX58914V

2 modules

LSX58932A

2 modules

LSX58932A

12

LSL58820V

6 modules

LSX58914V

3 modules

LSX58933A

3 modules

LSX58933A

Front plate
cut-out

DD800181

+ downstream

DD800180

DD800179

+ upstream

LSX58932A

2 modules

LSX58932A

Long terminal
shield

+ downstream

DD800180

DD800181

+ upstream

DD800179

DD800178

DD800182

No. of vertical
modules
(1 module = 50 mm)

Mandatory.
Optional.

B-15

Functional units
System L

Fupact INF 32 to 160 A


Selection table

Commercial numbers

Vertical installation

DD800144

Circuit breaker

No. of devices
per row

Front
connection

Control

No. of pole

INF32/40

4 x 3P

direct by cables

front control

3P

INF63

3 x 3P

direct by cables

front control

3P

INF100/160

2 x 3P

direct by cables

front control

3P

DD800145

Fupact INF32/40

Fupact INF100/160

DD383974

Accessories
T
LIGH

B-16

For the functional unit accessories, see page B-30~B-31.

Fupact INF 32 to 160 A

Functional units

Selection table

System L
Commercial numbers

Mounting plate

LSL58810V

4 modules

LSX58895V

LSL58810V

5 modules

LSX58896V

LSL58810V

5 modules

LSX58897V

2 modules

Front plate
cut-out

Long terminal
shield

DD800181

+ downstream

DD800179

DD800185

No. of vertical modules


(1 module = 50 mm)

b
LSX58932A

Mandatory.
Optional.

B-17

Functional units

Widths of modular devices

System L
Commercial numbers
All the devices listed below can be mounted on:
bb modular device rail,
bb adjustable modular rail ,
bb modular rail, length =1600 mm.
Modular, plain or transparent front plates are available in this catalogue.

Widths of Multi 9/Acti 9 devices (in number of 9 mm modules)


Description

Width in 9 mm
1P

Alarm, ATo4x technical


Ammeter, AMP analogue
Ammeter, multi-rating
Ammeter, AMP digital
Auxiliaries, for ID, C60, C120
Auxiliaries, for C32H-DC
Auxiliaries, NO/NF
Auxiliaries, ACTp and ACT for contactor
Auxiliaries, ACTo+f for contactor
Auxiliaries, NTVo and TTVo for remote dimmer
Bell or buzzer
Circuit breaker Dclic, Dclic XE
Circuit breaker Dclic Vigi
Circuit breaker DT40, DT40N
Circuit breaker DT40 Vigi
Circuit breaker C32H-DC
Circuit breaker C60, iC60 / N / H / L / LMA, iK60N
Circuit breaker C120/N/H
Circuit breaker NG125
Auxiliary 2 OF or OF + SD
Auxiliary MX + OF or MN
Auxiliary MN s
Circuit breaker NG125 Vigi s
Circuit breaker NG125 Vigi I/S/R
Circuit breaker P25 M
Auxiliary MN
Auxiliaries MX + OF
Circuit breaker, Reflex, XC40
Contactor, CT 16/25 A
Contactor, CT 40/63/100 A
Contactor, ACTc auxiliary
Contactor, CDS 1-ph load shedder
Contactor, CDSc 1-ph load shedder
Contactor, CDS 3-ph load shedder
Contactor, CT+ silent
Cooling spacer
Counter, CI pulse
Counter, CH time
Dimmer, Vo1000
Extension , ETL for TL impulse relay
Extension, ERL
Frequency meter, FREQ
Impulse relay, TL 16 A and 32 A, ETL 16 and 32 A
Impulse relay, TLI 16 A andTLc
Impulse relay, TLm and TLs
Impulse relay auxiliaries, ATLc+c and ATLc+s
Impulse relay auxiliaries, ATLt and ATLz
Impulse relay auxiliaries, ATL4
Impulse relay, TL+ silent
Insulation monitor, SM21
Kilowatt-hour meter, CE, CEr
Load shedder, DSEclic 2-channel
Load shedder, DSEclic 4-channel
Multimeter PM9
Optical repeater, RPo
Power socket, PC, 10 A and 16 A
Power socket, PC, 20 A

B-18

8
8
4
4
1-2-4
1-2
2
2
1
2
2

2
3
3
1
2
4

1P + N 3P
4P
2P
3P + N

2
4
2
4
4
4
6
6

6
9
9

8
12
12

11
11

18
20
5

21
23

8
2
4-6

10
4
4-6

12
4
6-12

1
2
2
2
10
16
16
2
1
4
4
10
2
2
4
2
2
2
2
2
4
2
8
12
6
8
8
2+2

5
8

Functional units

Widths of modular devices

System L
Commercial numbers
Widths of Multi 9/Acti 9 devices (in number of 9 mm modules)
Description

Width in 9 mm
1P

Pushbuttons
Rccb, IDclic
Rccb, IDclic XE
Regulator, REGad1/REGad2
Relay, RBN low level
Switch disconnector, INS 40 to 80 A
Switch disconnector, INS 100 to 160 A

2
4
4
12
2

1P + N 3P
4P
2P
3P + N

10
15

10
15

B-19

Functional units
System L
Commercial numbers

Multi 9/Acti 9 63 A
NG 125, C120
Modular devices
Selection table

Vertical installation

DD800008

Multi 9 63 A

No. of horizontal
modules per row

Fr connection

48

direct by cables

Acti 9 63 A

by multiclip

DD800009

NG125

48

direct by cables

C120

IERE
LUM

DD381308

Rear busbars

Distribloc distribution block

B-20

DD800002

For the distribution solutions, see page C-2~C-4.


DD800001

Distribution solutions

Multi-stage busbars

No. of
Modular device
vertical
rail (1)
modules
(1 module
= 50 mm)

1P

LSL58801A

2P

LSL58801A

3P

LSL58801A

4P

LSL58801A

2P

LSL58801A

3P

LSL58801A

4P

LSL58801A

1P

LSL58802A

2P

LSL58802A

3P

LSL58802A

4P

LSL58802A

For the functional unit accessories, see page B-30~B-31.

DD383974

Accessories

No. of
pole

DD800040

Circuit breaker

Multi 9/Acti 9 63 A
NG 125, C120

Functional units
System L

Modular devices
Selection table

Commercial numbers

Upstream connection

Distribution accessories(4)
12 horizontal
4 covers
cable straps
L = 430 mm

DD800187

Blanking strip
L=1000 mm

DD800186

Front plate
cut-out

12 trunking
supports

Multiclip 200 A(2) or

Distribloc(3)

3 modules

LSX58883A

LSX58621A

04239

04243

04255

3 modules

LSX58883A

LSX58621A

04239

04243

04255

3 modules

LSX58883A

LSX58621A

04239

04243

04255

3 modules

LSX58883A

LSX58621A

04239

04243

04255

4 modules

LSX58884A

LSX58621A

LSX58052A

04239

04243

04255

4 modules

LSX58884A

LSX58621A

LSX58053A

04239

04243

04255

4 modules

LSX58884A

LSX58621A

LSX58054A

04239

04243

04255

5 modules

LSX58885A

LSX58621A

04045

04239

04243

04255

5 modules

LSX58885A

LSX58621A

04045

04239

04243

04255

5 modules

LSX58885A

LSX58621A

04045

04239

04243

04255

5 modules

LSX58885A

LSX58621A

04045

04239

04243

04255

04239

04243

04255

Mandatory.
Optional.
Note:
(1) Capacity of modular rail: 48 Multi 9/Acti 9 modules (1 Multi 9/Acti 9 modules = 9 mm).
(2) Add 1 upstream plain plate (LSX58931A) when a modular row with a 200 A Multiclip
distribution block is positioned:
directly below a non-modular mounting plate (Compact, Interpact, etc);
at the top of a switchboard.
Add one vertical module (i.e. 4+1) = 5 M.
(3) When NG125 circuit breaker is incomer.
(4) See page C-16~C-18.

B-21

Functional units

INS 40/160 switch disconnectors


Modular devices
Selection table

System L
Commercial numbers

Vertical installation

DD800010

INS 40/63/80
INS 100/125/160

No. of
Front
horizontal connection
modules
per row

No. of
pole

No. of
vertical
modules
(1 module
= 50 mm)

Adjustable device rail

48

3P

LSL58802A

4P

LSL58802A

3P

LSL58802A

LSL58802A

LSL58802A

LSL58802A

48

direct by cables
direct by cables

4P

For the functional unit accessories, see page B-30~B-31.

DD383974

Accessories
IERE
LUM

For the distribution solutions, see page C-2~C-4.


DD800001

Distribution solutions

DD381308

Rear busbars

Distribloc distribution block

B-22

Multi-stage busbars

DD800039

Circuit breaker

INS 40/160 switch disconnectors

Functional units

Modular devices
Selection table

System L
Commercial numbers

Upstream connection
DD800187

Blanking strip
L=1000 mm

DD800186

Front plate
cut-out

Distribution accessories
12 horizontal
4 covers
cable straps
L = 430 mm

12 trunking
supports

Multiclip 200 A(1) or

Distribloc

4 modules

LSX58884A

LSX58621A

LSX58053A

04239

04243

04255

4 modules

LSX58884A

LSX58621A

LSX58054A

04239

04243

04255

4 modules

LSX58884A

LSX58621A

LSX58053A

04045

04239

04243

04255

5 modules

LSX58885A

LSX58621A

LSX58053A

04045

04239

04243

04255

4 modules

LSX58884A

LSX58621A

LSX58054A

04045

04239

04243

04255

5 modules

LSX58885A

LSX58621A

LSX58054A

04045

04239

04243

04255

Long terminal
shield

b
b

Mandatory.
Optional.
Note:
(1) Add 1 upstream plain plate (LSX58931A) when a modular row with a 200 A
Multiclip distribution block is positioned:
b directly below a non-modular mounting plate (Compact, Interpact, etc);
b at the top of a switchboard.
Add one vertical module (i.e. 4+1) = 5 M.

B-23

Functional units
System L
Commercial numbers

Industrial and control devices


Motor control up to 15kw
LV/LV tranformers
Selection table

Vertical installation
Circuit breaker + Contactors up to 45kw

NO. of vertical modules


(1 module=50mm)

DD800521

NSX100-MA

DD800522

Series D contactors <=95A

NO. of vertical modules


(1 module=50mm)
Series D contactor <=40A
(Side by side)

Series D contactor <=95A


(Side by side)

GV2 circuit breakers

NO. of vertical modules


(1 module=50mm)

DD800523

GV2 circuit breakers


(Side by side)

GV2+Series D contactor

NO. of vertical modules


(1 module=50mm)
GV2 + contactor

DD800041

DD800524

DD800525

Soft starter up to 11kw

NO. of vertical modules


(1 module=50mm)
ATS48D17 ATS48D22 ATS48D32
ATS48D38 ATS48D47

8
8

ATS48D62 ATS48D75
ATS48D88 ATS48C11
LV/LV transformers

NO. of vertical modules


(1 module=50mm)
LV/LV transformers

DD800526

4
8
12

DD800527

Accessories
T
LIGH

B-24

For the function unit and front plate accessories, see page B-30~B-31.

Industrial and control devices

Functional units

Motor control up to 15kw


LV/LV tranformers
Selection table

System L
Commercial numbers

Vertical installation
Mounting plate

Front plate

Optional

Comments

LSL58816V

LSX58902V + LSX58931A

LSX58751A

Number of device 4x3P or 3x4P

Mounting plate

Front plate

Optional

Comments

04226 (1)

LSX58933A

04226 rail, cut by customer

04226 (1)

Mounting plate

Front plate

Optional

Comments

04226

LSX58883A

Mounting plate

Front plate

Optional

Comments

04226 (1)

LSX58964T + LSX58931A

04226 rail, cut by customer

04226 (1)

LSX58884A + LSX58931A

04226 rail, cut by customer, add front plate


hinge kit Ref. LSX58776A

Mounting plate

Front plate

2xLSL58824A

2xLSX58931A + LSX58966T

only for 305mm depth cubicle

2xLSL58824A

2xLSX58934

only for 305mm depth cubicle, add front plate


hinge kit Ref. LSX58776A

Optional

2xLSL58824A

Comments

only for 305mm depth cubicle, without front


plate

Mounting plate

Front plate

LSL58824A

LSX58934A

2xLSL58824A

2xLSX58934A

LSL58825A

2xLSX58936A

Optional

Comments

(1)Capacity of modular rail: 48 Multi9 modules (1 Multi 9 module=9mm).

B-25

Human/Machine interface

Functional units

72 x 72 and 96 x 96 mm devices
Presentation

System L
Commercial numbers

Presentation

Dedicated front plates are available for 72 x 72 mm and 96 x 96 mm devices.


It is installed in the device zone.
Blanking plate are available to blank off any unused locations.
They have knock-outs to fit lights, push-buttons, etc..
72 x 72 mm and 96 x 96 mm devices can be directly adapted on plain door: cut-out to
be made by the customer.

DD800012

The degree of protection for installed devices is IP30.


To maintain the IP54 degree of protection, the devices must be installed behind a
transparent door.

DD800013

Front plate of 72x72 mm diameter for 6 devices.

Front plate of 96x96 mm diameter for 4 devices.

B-26

Human/Machine interface

Functional units

72 x 72 and 96 x 96 mm devices
Presentation

System L
Commercial numbers

72 x 72 mm measurement devices

Com. no.
LSX58956A

Blanking plate (for 72 x 72 mm hole)

LSX58961A

DD382637

DD381689

Designation
Metal front plate with cut-outs, 3 modules (for six 72 x 72 mm devices)

The blanking plates have knock-outs:


bb 3 holes, 22 mm diameter,
bb 1 hole, 45 x 45 mm.

Designation

Com. no.

Metal front plate with cut-outs, 3 modules (for four 96 x 96 mm devices)

LSX58955A

Blanking plate (for 96 x 96 mm hole)

LSX58960A

DD382637

DD381711

96 x 96 mm measurement
devices

The blanking plates have knock-outs:


bb 3 holes, 22 mm diameter,
bb 1 hole, 45 x 45 mm,
bb 1 hole, 72 x 72 mm.

B-27

Other devices

Functional units

For all type of device


Selection table

System L
Commercial numbers

Installation on modular rail


DD800393

Designation

Depth behind
front plate (mm)

Useful length
(mm)

Com. no.

Adjustable modular device rail

47 to 114

432

LSL58802A

2 modular device rails

144

1600

04226

L modular device rail

49

1600

LSL58801A

DD800394

Adjustable modular device rail (LSL58802A).

Modular rail, L=1600 mm (04226).

Installation on slotted plate


DD800044

Designation
Slotted mounting plate

No. of vertical modules


(1 module = 50 mm)

Depth behind front Com. no.


plate (mm)

122

LSL58824A

12

122

LSL58825A

Clip-nuts for slotted mounting plates (for device fixing)


Designation

Com. no.
03180

20 M5 clip-nuts for slotted mounting plate

03181

20 slotted mounting plate clip-nuts M6

03182

DD381312

20 M4 clip-nuts for slotted mounting plate

Installation on plain plate

Designation

DD800042

Plain mounting plate

Cut-out front plate for modular


devices

No. of vertical modules Depth behind front Com. no.


(1 module = 50 mm)
plate (mm)
4

116

LSL58826A

12

116

LSL58827A

Designation

DD800161

Front plate for modular devices

No. of vertical modules


(1 module = 50 mm)

Com. no.

LSX58883A

LSX58884A

LSX58885A

Blanking strip (for blanking off unused locations)


Designation
DD380805

Blanking strip modular device, L = 1000 mm

B-28

Com. no.
LSX58621A

Functional units
System L

Reserve space
Selection table

Commercial numbers

Plain front plate


DD381583

Transparent front plate


DD381582

Designation
Plain front plate

Designation
Transparent front plate

No. of vertical modules (1 module = 50 mm) Cat. no.


1

LSX58931A

LSX58932A

LSX58933A

LSX58934A

LSX58936A

No. of vertical modules (1 module = 50 mm) Cat. no.


4

LSX58964T

LSX58966T

B-29

Functional unit accessories

Functional units

Selection table

System L
Commercial numbers

Universal angle bracket


DD800390

The angle brackets are used for:


bb vertical mounting of the earth/neutral bar in the duct,
bb mounting of the modular rail L = 1600 mm (com. no. 04226).
Designation

Com. no.
03581

DD381577

2 universal angle brackets

Hexagonal spacers
DD800159

The hexagonal spacers are used for:


bb the raising and the mounting of the modular rail,
bb the raising and the mounting of the earth/neutral bar.
Designation

Com. no.
H = 9 mm

03195

H = 23 mm

03196

H = 55 mm

03197

DD800160

4 M6 hexagonal spacers

Blanking strip

DD800015

Hinge kit

DD800014

Lead-sealable screws

The blanking strips are used to fill the space on the cut-out front plates.
Designation

LSX58621A

Blanking strip CVS/NSX250/INS250, L = 148 mm

LSX58751A

Blanking strip EZC250, L = 1000 mm

LSX58752A

Designation
Front plate hinge kit

Com. no.
LSX58776A

For restricted access, the front plate can be sealed as visual checking.
Designation
4 front plate lead-sealable screws

B-30

Com. no.

Blanking strip modular device, L = 1000 mm

Com. no.
LSX58777A

Functional units

Functional unit accessories


Selection table

System L
Commercial numbers

DD381715

Identification labels

The labels are used on front plates for the identification of the outgoings.
Designation

Com. no.

12 adhesive label holders, W = 432 mm, H = 24 mm

08903

12 clip-on labels 18 x 35

08913

DD383974

Adhesive label.

T
LIGH

Clip-on label.

B-31

C-2

Distribution

Contents

System L

Description

Overview of distribution solutions


Different type of distribution solutions
Busbars
Multi-stage busbars
Rear busbars
Distribution blocks
Distribloc distribution block
Polybloc distribution block
Multiclip distribution block
Multi-stage current distribution blocks
Comb busbars

Commercial numbers

Busbars from 160 to 630 A


Distribution blocks
Distribution accessories
Partitioning

C-2

C-2
C-4
C-5
C-5
C-6
C-7
C-7
C-8
C-9
C-10
C-11

C-12
C-12
C-14
C-16
C-19

C-1

Distribution
System L

Overview of distribution
solutions

Description

For incoming devices

160 to 630 A multi-stage busbar

bb Traditional, highly versatile solution.


bb Installation position:
v horizontal in the 600 mm wide enclosure,
v vertical in the cable duct.

160 to 400 A rear busbar

bb Traditional, highly versatile solution.

C-2

Distribution
System L

Overview of distribution
solutions

Description

For rows of modular devices


125 A Distribloc

DD800158

bb Spring terminals for


electrical connections
that stay tight.
bb Front designed to
integrate perfectly with
modular devices.

200 A Multiclip
bb Reliable springterminal connections
requiring no maintenance
bb Fast installation.
bb Easy upgrades through
replacement or addition
of devices.
bb Easy balancing of
phases.

80 to 125 A comb busbars


bb Fast and direct
connections, adaptable to
all needs.
bb Fast, economical
connections.

C-3

Distribution
System L

Different type of distribution


solutions

Description
Prisma iPM enclosures provide you with distribution solutions adapted to your
requirements.

DD800157

Centralised distribution

Centralised distribution consists of a distribution block that redistributes electricity to


the various switchboard feeders. It is placed as close as possible to the incomer and
is simple and easy to install.
The splitter or distribution block is perfectly suited to medium-sized electrical
switchboards and is used as a sub-distribution block.
It can be used with all types of switchgear making it suitable for industrial control
applications.
Prisma iPM centralised distribution solutions
No. of
connection
points
6 to 16

DD800398

Split distribution

Distribution

Rating (A)

Distribloc distribution block

Devices

125

Multi 9

Multi-stage current distribution 125


block

Multi 9

9 per phase

Polybloc distribution block

EasyPact CVS,
Interpact INS

13 per phase

horizontal multi-stage busbars 160, 250 and 400 EasyPact CVS,


Interpact INS

> 15

rear busbar or busbar in duct (see split distribution)

160 and 250

Split distribution consists of distributing the current from the incomer to the
enclosures various feeders by providing connection points as close as possible to
the feeders.
The current is distributed via a full-height rear busbar or side mounted busbar that is
as close as possible to the devices. The busbars, made up of offset and stepped
bars, allow direct and easy front access to all the connection points.
Split distribution is suited to large electrical switchboards and offers:
bb a nominal current rating of 125 to 630A,
bb a high connection capacity,
bb connections that can be added and changed at any time,
bb the possibility of having more than 10 feeder groups.
It is also ideal for the electrical distribution between 2 switchboards when enclosures
are combined.
With split distribution, you have the guarantee of a tested solution.
Prisma iPM split distribution solutions
Busbar

Sub-distribution for modular


switchgears

Rating (A)

Implantation

Rear busbar

160, 250 and 400

in device area

Vertical multi-stage busbar

160, 250, 400 and 630

in duct

Sub-distribution consists of either a 200A Multiclip distribution block or a comb


busbar connected directly to the centralised distribution block or the busbar. They
thus feed each row of modular devices.

DD800397

Prisma iPM sub-distribution solutions


Devices
All type of devices

Distribution blocks
Distribloc distribution block
Multi-stage current distribution block
Polybloc distribution block

Dedicated to one type of Multi 9 device

200 A multiclip distribution block


Comb busbar
Multi-stage current distribution block

Easypact 100 A

C-4

Comb busbar

Distribution
System L

Busbars

Multi-stage busbars

Description

DD800047

Multi-stage busbar presentation

The multi-stage busbars can be installed:


bb horizontally in a 600 mm wide enclosures in the device zone. They have
13 outgoers per phase, max. 50 mm2,
bb vertically in the 300 mm wide duct. They are particularly useful for distribution to
2 enclosures on each side of the duct. All connection points are easily accessible
from the front. The inclination of the bars facilitates connections and improves cable
running.
They are valid for three and four-pole versions with ratings from 160 to 630 A.
Available in one length, 1400 mm, they can be cut as needed.
Composition
Flat, copper bars with threaded M6 holes every 25 mm for connection along the
entire length of the busbars. There are 8.2 mm diameter holes at each end for
supply. The staggered supports are made of an insulating material.
An optional, front barrier is available to protect against direct contact from the front
(IPxxB degree of protection).
Electrical characteristics
bb Rated current :160A,250A,400A,630A.
bb Rated insulation level Ui : 750V.
bb Impulse withstand voltage Uimp: 8kV.

Busbar supports
Horizontal multi-stage busbar in 600 mm wide enclosure
2 supports are needed.
DD800028

DD800019

Horizontal multi-stage busbar installed in a 600 mm wide


enclosure.

Rating (A)

Size of a bars (mm)

Distance between support centres (mm)


Icw (kA rms/1 s.)
10

160

15 x 5

250

20 x 5

400

32 x 5

630

32 x 8

13

450

15

20

25

300

300(1)

(1) Icw (kA rms/0.6 s.).


DD800027

Vertical multi-stage busbar installed in a 300 mm wide duct.

Vertical multi-stage busbar in 300 mm wide duct


The table below indicates:
bb the size of the bars to be used, depending on the permissible current level in the
busbars,
bb the number of supports depends on the rated short-time withstand current (Icw),
bb the distance between supports, depending on the rated short-time withstand
current (Icw).

C-5

Distribution
System L

Busbars

Rear busbars

Description

DD800018

Rear busbars presentation

The rear busbar is installed in a 600 mm wide enclosures and is mounted directly on
the uprights of the frameworks.
It is valid for three or four-pole versions with ratings from 160 to 400 A.
Available in one length, 1400 mm, the bars can be cut as needed.
The connection with a Compact or Interpact incoming device occupies two vertical
modules ( 50 mm each).
Composition
Flat, copper bars with threaded M6 holes every 25 mm for connection along the
entire length of the busbars.
The insulating supports can receive a fifth bar, 15 x 5 mm or 20 x 5 mm, to create an
earth bar.
Installation
The busbars are mounted directly on the functional uprights of a 600 mm wide
enclosure.
Connection
bb 16 mm2 to 50 mm2 flexible cables, with crimped lugs,
bb insulated flexible bars.

Rear busbar installed in a 600 mm wide enclosure.

Electrical characteristics
bb Rated peak withstand current Ipk (k)
v 30 k for 160 A busbars,
v 40 k for 250 A busbars,
v 55 k for 400 A busbars.
bb Rated insulation level Ui = 1000 V.

Busbar calculation

Busbar size and distance between supports


The table below indicates:
bb the size of the bars to be used, depending on the permissible current level in the
busbars,
bb the distance between supports, depending on the rated short-time withstand
current (Icw).
Rating (A)

Size of a bars (mm)

Distance between support centres(1) (mm)


Icw (kA rms/1 s.
10

160

15 x 5

250

20 x 5

400

32 x 5

13

15

20

25

300

250

450

(1) Multiclip 200 A distribution blocks equipped with connections (04029) can be used as
intermediate supports (200 mm max. distance between centres) in addition to the top and bottom
supports.

C-6

Distribution blocks

Distribution

Distribloc distribution block

System L
Description

Distribloc distribution block


presentation
DD800464

The Distribloc distribution block is particularly suited to small and medium-sized


enclosures. It gives lots of flexibility when there are few feeders. It provides safety
and makes maintenance easy.
It has been optimised for enclosures containing mainly modular devices. It can be
used equally as a main or sub-distribution block, or for industrial control applications.
It is easily installed by simply clipping it onto the modular rail. It can also be fixed to
the backplate for industrial control applications.
The Distribloc distribution block provides you with:
bb safety
v IPxxB protection of live conductors,
v tightening quality guaranteed by spring terminals,
v electrical performance levels adapted to your needs,
bb simplicity
v easy installation and wiring,
v simple choice depending on device rating,
bb flexibility
v selection of combinations,
v possibility of adding and changing feeders.

Distribloc distribution block supplying the modular devices.

DD381608

DD381609

Dimensions

Composition
The four-pole distribution block is made up of:
bb a fully insulated, one-piece distribution block complying with the degree of
protection IPxxB (protection against direct contacts),
bb a modular cover.
The design of the front (45 mm nose) blends perfectly into a row comprising modular
devices.
Electrical characteristics
bb Rated insulation level: Ui = 750 V.
bb Rated operational current Ie (40C):
v 125 A for the 125 A Distribloc,
bb Short-circuit withstand current: the reinforced breaking capacity due to cascading
in circuit-breaker combinations is maintained. The worst-case situations have been
tested.
bb Complies with the low-voltage device standard IEC 60947.7.1 and/or
IEC 61439.1
bb Impulse withstand voltage Uimp = 8 kV.
Supply
bb Tunnel terminal on 125 A Distribloc 125 for 6 to 35 mm2 flexible cables (10 to
35mm2 rigid cables).
Distribution
bb Spring terminals:
v 2 outgoers from 1 to 10 mm2, flexible or rigid,
v 3 outgoers from 1 to 6 mm2, flexible or rigid,
v 7 outgoers from 1 to 4 mm2, flexible or rigid.
bb Tunnel terminals:
v 1 outgoer from 4 to 16 mm2, flexible (4 to 25 mm2 rigid).
Supply
bb An identification label.
bb Adhesive labels for phase identification.
Installation
bb Clipped onto a modular rail.
bb Width occupied is 12 modules (9 mm each).
bb Screwed to plain or slotted backplate. Distances between centres = 100 x 75 mm.

DD381399

The spring terminals

Downstream circuits are connected from the front, to spring terminals.


Contact pressure automatically adapts to the size of the conductor. It does not
depend on the operator.
Contacts are insensitive to vibrations and thermal variations.
Only one cable (flexible or rigid, without a metal ferrule) can be inserted in a spring
terminal.
Degree of protection: IPxxB.
Advantages
bb A reliable electrical connection, no maintenance required (tightness guaranteed
over time).
bb Very fast connection.
bb Easy phase balancing.
bb Rewiring is very easy if the switchboard is expanded or modified.

C-7

Distribution
System L

Distribution blocks

Polybloc distribution block

Description

DD800441

Polybloc distribution block


presentation

DD800147

250 A Polybloc distribution block installed


in a 600 mm wide enclosure.

The Polybloc distribution block is particularly suited to small and medium-sized


enclosures. It gives lots of flexibility when there are few feeders. It provides safety
and makes maintenance easy.
It has been optimised for enclosures containing mainly modular devices. It can be
used equally as a main or sub-distribution block.
The Polybloc is available in two versions :
bb the 250 A Polybloc distribution block is designed for installation directly
downstream of Compact circuit breakers and Interpact switch-disconnectors devices
up to 250 A. It can be rapidly mounted in the vertical position. Electrical connections
are made directly to the device terminals. The connection terminals are slanted to
facilitate cable entry and not exceed the bending radius of the flexible and rigid
cables,
bb the 160 A Polybloc is made up of individual elements that can be used alone or
with others to make two-pole, three-pole or four-pole distribution blocks.
Mounting is very fast. It clips onto a modular rail and is supplied by cables via a tunnel
terminal. The connection spring terminals are slanted to facilitate cable entry and
bending of the flexible and rigid cables. It is supplied with a cover that also guides the
cables.
Electrical characteristics
bb Rated insulation level Ui = 750 V.
bb Short-circuit withstand current: the reinforced breaking capacity due to cascading
in circuit-breaker combinations is maintained. The worst-case situations were tested.
bb Impulse withstand voltage Uimp = 8 kV.
Supply
bb 250 A Polybloc distribution block:
v directly to the terminals of the Compact NSX and Interpact INS devices up to
250 A.
bb 160 A Polybloc distribution block:
v direct to a tunnel terminal, for cables up to 70 mm2.
Distribution
bb 250 A Polybloc distribution block:
v via cables, up to six 10 mm2 cables and three 16 mm2 cables per phase.
bb 160 A Polybloc distribution block:
v via cables, up to six 16 mm2 cables.

160 A Polybloc distribution block installed


in a 600 mm wide enclosure.

Installation
bb 250 A Polybloc distribution block:
bb It is mounted downstream of vertically mounted Compact NS100/250 and
NSX100/250 and Interpact INS250 devices in the enclosures. The Polybloc is
mounted on the modular device rail (LSL58801A).
bb 160 A Polybloc distribution block:
v the blocks clip onto a modular rail.
Dimensions
70

95

38
250 A Polybloc distribution block

DD381399

The spring terminals

160 A Polybloc distribution block

Downstream circuits are connected from the front, to spring terminals.


Contact pressure automatically adapts to the size of the conductor. It does not
depend on the operator.
Contacts are insensitive to vibrations and thermal variations.
Only one cable (flexible or rigid, without a metal ferrule) can be inserted in a spring
terminal.
Degree of protection: IPxxB.
Advantages
bb A reliable electrical connection, no maintenance required (tightness guaranteed
over time).
bb Very fast connection.
bb Easy phase balancing.
bb Rewiring is very easy if the switchboard is expanded or modified.

C-8

Distribution

Distribution blocks

Multiclip distribution block

System L
Description

DD383483

200 A Multiclip distribution block


presentation

The 200A Multiclip distribution block has been optimised to feed rows of modular
devices. It is easily installed by simply clipping it onto the modular rail, either above
or below the row of devices. Its flexibility means it can be fitted before or after the
devices have been mounted.
Its dimensions have been kept to a minimum to ensure the best possible integration
into the switchboard.
To ensure compatibility with all installation types, we recommend you connect the
supply to the distribution block at its centre.
The 200A Multiclip distribution block provides you with:
bb flexibility
v compatibility with all types of switchgear,
v possibility of mixing all types of modular devices,
v distribution blocks with different numbers of available poles,
bb safety
v insulation of upstream terminal pads,
v flawless connection reliability thanks to its spring terminals,
v full protection (IPxxB) against direct contact,
bb protection degree
v a protective cover on the busbar ensures IPxxB from the front,
bb easy modifications
v increased connection capacity (number of points and cross-section),
v possibility of adding or changing feeders, whatever type of device is to be added,
v continuity of service.
Application
Distribution over full rows of modular devices.
The distribution block is generally supplied by busbars in enclosures.

DD800048

Electrical characteristics
bb Rated insulation level Ui = 750 V.
bb Impulse withstand voltage Uimp = 8 kV.
bb Short-circuit withstand current: the reinforced breaking capacity due to cascading
in circuit-breaker combinations is maintained. The worst-case situations have been
tested.
bb 200 A Multiclip distribution blocks:
v 10 mm2 cable outgoer: Imax = 50 A,
v two 10 mm2 cables: Imax = 63 A.
Supply
bb Direct to terminals:
v 50 mm2 cables with crimped lugs,
v 20 x 3 mm flexible bars.
bb From busbars in the rear of a wall mounted enclosure (04029).
Busbar connection
The Multiclip distribution block is supplied by the rear busbar through a connection
(04029).
No. of poles

H (mm)

2P

24

3P

44

4P

52

Distribution
bb 200 A Multiclip, 2P and 3P (LSX58052A and LSX58053A):
v 3 x 12 connection points for phase and neutral.
bb 200 A Multiclip, 4P (LSX58054A):
v 3 x 12 connection points for each phase,
v 18 connection points for the neutral.
Each connection point can receive a single 10 mm2 cable, either flexible or rigid.
Installation
bb Clipped onto the rear of modular rail.
bb Screwed to plain or slotted backplate.
Supplied with:
bb 100 mm long, bared 10 mm2 copper connections:
v 200 A Multiclip, 2P, 3P and 4P (LSX58052A, LSX58053A et LSX58054A): 2 sets of
12 connections.
bb Protection covers for the supply terminals (IPxxB).
bb The hardware required for the supply terminals.

The spring terminals

See previous page.

C-9

Distribution
System L

Distribution blocks

Multi-stage current distribution blocks

Description

DD382813

Multi-stage current distribution


block presentation

The multi-stage current distribution block is easy to install and can be either clipped
onto the modular rail or fixed to a solid or perforated mounting plate.
Electrical characteristics
bb Rated operating current: Ie (40 C) = 125 A.
bb Rated insulation level Ui = 500 V.
bb Rated short-time withstand current Icw = 3.5 kA rms/1 s.
bb Peak withstand current Ipk = 20 k.
bb Impulse withstand voltage Uimp = 8 kV.
Supply
bb Connected with flexible or rigid cable with or without crimped lugs.
Installation
bb Clipped onto the modular rail.
bb Screwed to plain or slotted backplate.
Supplied with:
bb transparent, insulating cover,
bb mounting hardware.

E19453

Dimensions

C-10

Distribution blocks

Distribution

Comb busbars

System L
Description

Comb busbars presentation


E40638

The comb busbars are used for the distribution over full rows of modular devices.
They may be supplied by either the incoming device fitted on the row or via
connectors.
They can be cut to length. The cutting locations are marked on the copper bar and on
the insulation.
They are fully insulated.
Markers can be fitted for circuit identification.
The tooth-caps ensure the IPxxB protection. The unused teeth may be insulated by
fitting tooth-caps.

Comb busbars for C60 devices


Description
bb Range of comb busbars for 18 mm spacing.

E40639-32

E40637-32

The insulated connectors are firmly clipped onto insulated


parts of comb busbars.

I . ON

I . ON

Picture N1.

Picture N2.

The tooth-caps may be fitted to insulate unused teeth of the


comb busbar for the C60 devices (picture n1) or the
NG125 devices (picture n2).

Electrical characteristics
bb Rated insulation level Ui:
v 250 V for 1P + N and 3P + N comb busbars,
v 500 V for 1P, 2P, 3P and 4P comb busbars.
bb Rated operational current Ie (40C) :
v 80 A with 1 central supply point for 1P, 2P, 3P and 4P comb busbars only,
v 100 A with 1 central supply point for 1P + N and 3P + N comb busbars and
2 central points for 1P, 2P, 3P and 4P comb busbars,
v 125 A with 2 supply points for 1P + N and 3P + N comb busbars only.
bb short circuit withstand capacity compatible with the breaking capacities of
Schneider modular circuit breakers.
Connection
bb Can be supplied by the rear busbar through insulated connectors.
bb Direct connection to a device terminals.
Supplied with:
bb two IP2 end caps.

Comb busbars for NG125 devices


Description
bb Range of 1P, 2P, 3P and 4P comb busbars for 27 mm terminal spacing.
bb Length:
v 432 mm (16 x 27 mm) for 1P, 2P and 4P comb busbars,
v 405 mm (15 x 27 mm) for 3P comb busbar.
Electrical characteristics
bb Rated insulation level Ui: 690 V.
bb Rated operating current Ie (40C) = 125 A.
bb Maximum rated current per outgoing circuit = 63 A.
bb Rated impulse withstand voltage Uimp = 8 kV.
bb short circuit withstand capacity compatible with the breaking capacities of
Merlin Gerin modular circuit breakers.
Connection
bb Supply by cables with a maximum cross-section of 50 mm2, directly in the tunnel
terminals of the device.
bb To supply the comb busbar from a busbar set located at the rear of the enclosure,
use a 100 A connection.
Supplied with:
bb 8 tooth-caps + 2 end-caps for 2P comb busbar.
bb 4 tooth-caps + 2 end-caps for 3P and 4P comb busbars.

C-11

Distribution
System L

Busbars from 160 to 630 A


Selection table

Commercial numbers

Rear busbar for enclosures W = 600 mm


DD3800018

Rating (A)

Length (mm)

Size of bars (mm)

160

1400

15 x 5

250

1400

20 x 5

400

1400

32 x 5

Length (mm)

Size of bars (mm)

160

1400

15 x 5

250

1400

20 x 5

400

1400

32 x 5

630

1400

32 x 8

Vertical multi-stage busbar for enclosures W = 300 mm


DD800019

Rating (A)

Horizontal multi-stage busbar for enclosures W = 600 mm


DD800047

Rating (A)

DD381398

Accessories

C-12

Length (mm)

Size of bars (mm)

Set of 4 drilled bars


with threaded holes

160

1400

15 x 5

04171

250

1400

20 x 5

04172

400

1400

32 x 5

04173

630

1400

32 x 8

04174

For the distribution accessories, see page C-16~C-18.

Busbars from 160 to 630 A

Distribution

Selection table

System L
Commercial numbers

Set of 4 drilled bars


with threaded holes

Busbar support

Barrier

Mounting hardware

04171

LSX58080A

LSX58081A

04195

04172

LSX58080A

LSX58081A

04195

04173

LSX58080A

LSX58081A

04195

Set of 4 drilled bars


with threaded holes

Busbar support(1)

Barrier

Mounting hardware

04171

LSX58082A

04197

04195

04172

LSX58082A

04197

04195

04173

LSX58082A

04197

04195

04174

LSX58082A

04197

04195

40 M6 x 16 screws + 40 washers for threaded bars

40 M6 x 16 screws + 40 washers for threaded bars

(1) The number of supports depends on the rated short-time withstand current (Icw), see the
table in Busbar calculation.
Busbar support

Barrier

Plain front plate, 6 modules

Mounting hardware

2 x LSX58082A

04197

LSX58936A

04195

2 x LSX58082A

04197

LSX58936A

04195

2 x LSX58082A

04197

LSX58936A

04195

2 x LSX58082A

04197

LSX58936A

04195

40 M6 x 16 screws + 40 washers for threaded bars

C-13

Distribution blocks

Distribution

Selection table

System L
Commercial numbers
No. of
poles

Rating

Rated
insulation
voltage Ui

Rated impulse
withstand voltage
Uimp

Rated
Rated short-time
operational
withstand current Icw
current Ie (40C)

Distribloc distribution block

125 A

750 V

8 kV

125 A

depending on
connected device

Polybloc distribution block

1P

160 A

750 V

8 kV

160 A

depending on
connected device

3P

250 A

750 V

8 kV

160 A

depending on
connected device

4P

250 A

750 V

8 kV

160 A

depending on
connected device

2P

125 A

500 V

8 kV

125 A

3.5 kA rms/1 s.

4P

125 A

500 V

8 kV

125 A

3.5 kA rms/1 s.

2P

200 A

750 V

8 kV

200 A

depending on
connected device

3P

200 A

750 V

8 kV

200 A

depending on
connected device

4P

200 A

750 V

8 kV

200 A

depending on
connected device

DD382981

DD381660

Designation

DD382813

Multi-stage current distribution


block

DD381671

DD381670

DD381672

200 A Multiclip distribution block

C-14

Distribution

Distribution blocks
Selection table

System L
Commercial numbers
Rated peak
withstand current
Ipk

Connection capacity

Com. no.

Installation/comments

upstream

downstream

depending on
connected device

tunnel terminals for 6 to 35 mm2


flexible cables (10 to 35 mm2 rigid
cables)

b spring terminals
04045
v 2 outgoers from: 1 to 10 mm2, flexible or rigid
2
v 3 outgoers from: 1 to 6 mm , flexible or rigid
v 7 outgoers from: 1 to 4 mm2, flexible or rigid
b tunnel terminals
v 1 outgoer from: 4 to 16 mm2, flexible or rigid
(4 to 25 mm2 rigid)

b modular rail
b plain or slotted backplate

depending on
connected device

tunnel terminal, for cables up to


70 mm2

via cables, up to six 16 mm2 cables.

04031

b modular rail
b plain or slotted backplate

depending on
connected device

directly to the incoming device:


EasyPact CVS 100/250 and
Compact NSX 100/250, Interpact
INS250

b spring terminals
v 6 x 10 mm2 + 3 x 16 mm2, flexible or rigid

04033

b directly downstream of the incoming


device:
v EasyPact CVS 100/250 and
Compact NSX 100/250, Interpact
INS250
b modular rail

depending on
connected device

directly to the incoming device:


EasyPact CVS 100/250 and
Compact NSX 100/250, Interpact
INS250

b spring terminals
v 6 x 10 mm2 + 3 x 16 mm2, flexible or rigid

04034

b directly downstream of the incoming


device:
v EasyPact CVS 100/250 and
Compact NSX 100/250, Interpact
INS250
b modular rail

20 k

via flexible or rigid cable with or


without crimped lugs

via flexible or rigid cable with or without


crimped lugs

See
Schneider
corresp.

b 2 x13 holes:
1 x 8.5 mm2 + 2 x 7 mm2 + 5 x 5.5 mm2
+ 5 x 4.4 mm2
b clipped onto modular rail
b screwed to plain or slotted backplate

20 k

via flexible or rigid cable with or


without crimped lugs

via flexible or rigid cable with or without


crimped lugs

See
Schneider
corresp.

b 4 x13 holes:
1 x 8.5 mm2 + 2 x 7 mm2 + 5 x 5.5 mm2
+ 5 x 4.4 mm2
b clipped onto modular rail
b screwed to plain or slotted backplate

See
Schneider
corresp.

b 4 x17 holes:
1 x 8.5 mm2 + 2 x 7 mm2 + 7 x 5.5 mm2
+ 7 x 4.4 mm2
b clipped onto modular rail
b screwed to plain or slotted backplate

depending on
connected device

b via connection from rear busbar


b 50 mm2 cables with crimped lugs
b 20 x 3 mm flexible bars

b supplied flexible cables:


b 10 mm2

LSX58052A

b clipped onto rear of modular rail


b screwed to plain or slotted backplate
b the Multiclip distribution block is
supplied by the rear busbar through a
connection (04029).

depending on
connected device

b via connection from rear busbar


b 50 mm2 cables with crimped lugs
b 20 x 3 mm flexible bars

b supplied flexible cables:


b 10 mm2

LSX58053A

b clipped onto rear of modular rail


b screwed to plain or slotted backplate

depending on
connected device

b via connection from rear busbar


b 50 mm2 cables with crimped lugs
b 20 x 3 mm flexible bars

b supplied flexible cables:


b 10 mm2

LSX58054A

b clipped onto rear of modular rail


b screwed to plain or slotted backplate

C-15

Distribution accessories

Distribution

Selection table

System L
Commercial numbers

Insulated flexible bars


DD381659

The insulated flexible bars are tested in a type-tested switchboard environment.


Their design takes into account the switchboard architecture where they are often in
close proximity to a protection device (circuit breaker or fuse) with significant heat
losses.
In-depth knowledge of switchboard architecture and the connected devices led to
the establishment of a selection table based on the type of device.
Flexible bars are 1800 mm long and made of copper with an insulating sheath.
Rated insulation level Ui = 1000 V.
The sizes for the flexible bars indicated below take into account the heat losses of
Schneider devices in a Prisma iPM switchboard.

Connection between device and busbars

The flexible bars are determined taking into account the connected device, whatever
the internal temperature of the switchboard.
The bar sizes indicated below take into account the derating curves of devices.
Size (mm)

Com. no.

NSX100

Device

20 x 2

04742

NSX160/250

20 x 3

04743

NSX400

32 x 5

04751

NSX630

32 x 8

04753

NS100

20 x 2

04742

NS160/250

20 x 3

04743

NS400

32 x 5

04751

NS630

32 x 8

04753

EZC100

20 x 2

04742

EZC160/250

20 x 3

04743

EZC400

32 x 5

04751

INS125/160

20 x 2

04742

INS250

20 x 3

04743

INS400

32 x 5

04751

INS630

32 x 8

04753

200 A Multiclip

20 x 3

04743

Connection between busbars

Flexible bars are designed for connections between busbars taking into account the
following characteristics:
bb a maximum temperature of 60C inside the switchboard. This corresponds to the
average temperature inside a switchboard for an ambient temperature of 35C,
bb the maximum withstand temperature for the insulating material is 125C.

DD382008

Ie max. (A)

C-16

Size (mm)

Com. no.

200

20 x 2

04742

250

20 x 3

04743

520

32 x 5

04751

660

32 x 8

04753

Distribution accessories

Distribution

Selection table

System L
Commercial numbers

Earth/neutral bar
DD800020

The earth bar (450 mm long) is equipped with 40 clamps with captive screws.
It is supplied with 1 connector for rigid or semi-rigid cable 35 mm2, 2 insulating
spacers for use on a neutral bar and mounting hardware.
It is directly installed in horizontal position on functional uprights.
The neutral bar is created by inserting 2 insulating spacers (supplied) behind the
earth bar.
Designation

Com. no.
LSX58070A
E56845

E56846

Cu earth/neutral bar, 24 modules

Neutral bar.

Horizontal cable straps

Designation

DD381618

12 cable straps for horizontal cables

Earth bar.

Com. no.
04239

DD800021

Horizontal cable straps have the same capacity as 60 x 30 mm trunking.

Designation
4 covers for horizontal cable straps L = 430 mm

Com. no.
04243

DD800029

DD381621

Cover for horizontal cable


straps

C-17

Distribution accessories

Distribution

Selection table

System L
Commercial numbers

DD381626

Horizontal trunking support

For cable trunking, height = 60 or 80 mm.


Designation

Com. no.
04255

DD800016

12 horizontal trunking supports

DD381398

Mounting hardware

C-18

Designation
Set of 40 M6 x 16 screws (40 screws + 40 contact washers)

Com. no.
04195

Distribution
System L

Partitioning
Selection table

Commercial numbers

DD800051

Horizontal partition

The partition is a metal barrier installed in a wall mounted enclosure or a 300 mm


wide enclosure.
It is used to:
bb separate the functional units from one another,
bb create a physical separation between devices and a terminal block, for example.
It is mounted directly on the functional uprights.
Lateral and rear knock-outs are available for cable running or the installation of
busbars at the rear of the switchboard.
Designation
Horizontal partition W = 500 mm

DD800052

Vertical partition

Com. no.
D = 235 mm

LSL58281H

D = 305 mm

LSL58282H

The metal partition creates a physical separation between the device compartment
and the 300 mm wide duct of a wall mounted enclosure.
It is used to:
bb separate the devices from busbars or a distribution block installed in the duct,
bb set up a special zone for terminal blocks in the duct.
There are knock-outs for cable running.
Vertical partitioning It can be cut to length every 150 mm and can be used for
partitioning up to 32-module in wall mounted enclosure (H = 1850 mm).
Designation
Vertical partition

Com. no.
4 to 24 modules

LSL58280V

28 and 32 modules

LSL58279V

C-19

D-2

Enclosures

Contents

System L

Description

D-2

Commercial numbers

D-4

IP30/31/40/54 in-door enclosures

IP30/40 PAK wall mounted enclosures


IP30/31 wall mounted enclosures
IP40 wall mounted enclosures
IP54 wall mounted enclosures
IP30/31/40/54 enclosures accessories

Dimensions

D-2

D-4
D-5
D-6
D-7
D-8

D-10

D-1

IP30/31/40/54 in-door enclosures

Enclosures

General information

System L
Description

Full kit
DD800467

PAK
DD800466

Wall mounted enclosures

IP30/40

IP

IP30/31/40/54
up to 630 A

In

07 (without door), 08 (IP30 door), 10 (IP54 door)

Functional height
(1 module = 50 mm)

DD800162

IK

12 16 20

24

12 16 20

24

28

Overall height (mm)

300 500 700 900 1100 1300 300 500 700 900 1100 1300 1650

Overall depth (mm)

235

235

32
1850

305
RAL 7047

Enclosure color

Same plain or transparent doors


DD800468

Same front frame


and plain door or
transparent door

yes
vertically and horizontally

yes
vertically and
horizontally

Cable duct
(width = 300 mm)

no

yes

yes

DD800470

flush mounted or surface


mounted

flush mounted or surface


mounted

surface mounted

D-2

DD800472

DD800472

DD800474

Installation

DD800471

no

DD800469

Association

Enclosures
System L

IP30/31/40/54 in-door enclosures


General information

Description

DD800054

Enclosure description

1 The enclosure

Enclosure size is determined simply according to the switchgear installed, the


connection method and positioning and the required free rows.
The enclosures can be flush mounted or surface mounted.
Pre punch-outs at the wall mounted enclosure back are provided for rear cable
insertion.
Square holes every 50 mm make it easy to count modules.
The 600 mm wide wall mounted enclosures are dedicated for functional unit area.
The 300 mm wide duct is dedicated to the cables and busbar area.
The panelling is assembled after mounting devices and cabling to maintain complete
accessibility in the switchboard during its implementation.

2 Removable chassis

It enables to install the empty enclosure on site; then to assemble and cable the
devices on the removable frame at the workshop and to mount it in the PaK
enclosure at the worksite.

3 Front frame/Front Plate support

The Front frame/Front Plate support is supplied with the full kit enclosures. It enables
the mounting of the front plates.
It can be removed for fast, direct access to all the devices, with all the front plates
mounted on.

4 Doors

Both plain and transparent doors are reversible and designed for quick and easy left
or right-hand mounting by a single person.
A handle is only available on the 600 mm wide doors. The 300 mm wide duct is
dedicated to the professional staff. For greater safety, it is closed with screws.
A range of locks are available for the push and pull handle.

DD800032

Enclosure combination

The wall mounted enclosures must have the same depth to be combined each other
horizontally and vertically.
The 28-module and 32-module height enclosures can be horizontally combined only.
An assemby kit is supplied with the 300 mm wide duct.
For other combinations than 600 + 300 mm wide enclosures, assembly kits are
available in option.
The degrees of protection are maintained.

Side-by-side combination

It ensures the mechanical connection between the wall mounted enclosures and the
duct.

Vertical combination

A combination kit ensures the mechanical connection between the two functional
unit wall mounted enclosures.

L shape combination

The L shape is created by combining two enclosures (extension or duct) with a


600 mm wide enclosure.

Square combination

The square shape is created by combining three enclosures (extension or duct) with
a basic enclosure.
Square combinations are only possible with enclosures that have the same number
of vertical modules.

DD800473

Enclosure fixing

IP30/31/40 wall mounted enclosures

bb From 4 to 24 modules, switchboards is mounted on a wall through the holes at the


rear of the switchboard. It is possible to mount the switchboards on a wall by using
external wall mounted fixing rings (2 x LSL58274A).
bb From 28 to 32 modules, switchboards is mounted on a wall by using external wall
mounted fixing rings (LSL58274A).

IP54 wall mounted enclosures

bb Switchboards is mounted on a wall by using external wall mounted fixing rings


(supplied).

D-3

DD380624

The enclosures can be flush mounted or surface mounted.

DD800545

PAK
IP30

Selection table

DD380623

Commercial numbers

DD800546

System L

IP30/40 PAK
wall mounted enclosures

DD800548

Enclosures

Overall
depth
(mm)

Functional Overall
height
height
(1 module (mm)
= 50 mm)

Enclosure
Front plate
W = 600 mm support (1)

Door
plain

or transparent

300

LSL58205A

LSL58604A

LSL58104A

500

LSL58209A

LSL58608A

LSL58108A

LSL58162T

12

700

LSL58213A

LSL58612A

LSL58112A

LSL58163T

16

900

LSL58217A

LSL58616A

LSL58116A

LSL58164T

20

1100

LSL58221A

LSL58620A

LSL58120A

LSL58165T

24
1300
LSL58225A LSL58624A LSL58124A
(1) Mandatory for front plate mounting.
For the flush mounting kit and enclosure accessories, see page D-8.

LSL58166T

235

Enclosure weight
Empty weight
No. of vertical modules
(1 module = 50 mm)

Enclosure W = 600 mm
Without door

With door

11

13

12

12

17

16

14

21

20

15

24

24

17

27

DD380624

DD380623

DD800546

DD800548

The enclosures can be flush mounted or surface mounted.

DD800545

PAK
IP40

Weight (kg)

Overall
depth
(mm)

Functional Overall
height
height
(1 module (mm)
of 50 mm)

Enclosure
Front plate
W = 600 mm support (1)

Door

300

LSL58205A

LSL58604A

LSL58104A

500

LSL58209A

LSL58608A

LSL58149A

LSL58160T

12

700

LSL58213A

LSL58612A

LSL58150A

LSL58161T

16

900

LSL58217A

LSL58616A

LSL58151A

LSL58157T

20

1100

LSL58221A

LSL58620A

LSL58152A

LSL58158T

24
1300
LSL58225A
(1) Mandatory for front plate mounting.

LSL58624A

LSL58153A

LSL58159T

235

Gasket kit

plain

Com. no.
LSL58276A

L IP40 accessories + gasket kit

For the flush mounting kit and enclosure accessories, see page D-8.

Enclosure weight
Empty weight
No. of vertical modules
(1 module = 50 mm)

D-4

Weight (kg)
Enclosure W = 600 mm
Without door

With door

11

13

12

12

17

16

14

21

20

15

24

24

17

27

or transparent

DD380624

The enclosures 4-24M can be flush mounted or surface mounted.


The enclosures 28-32M can be surface mounted.
To ensure compliance with the degree of protection IP31, the addition of a canopy
with a gasket is needed.
DD800478

DD800054

Full kit

Selection table

DD380623

Commercial numbers

DD800057

System L

IP30/31
wall mounted enclosures

DD800546

Enclosures

Overall Functional Overall Enclosure Front plate Duct with


Door
depth height
Height W = 600
support (1) door
plain
(mm)
(mm)
mm
W = 300 mm or
235

305

transparent

300

LSL58204A

LSL58604A

LSL58104A

500

LSL58208A

LSL58608A

LSL58231A

LSL58108A

LSL58162T

12

700

LSL58212A

LSL58612A

LSL58232A

LSL58112A

LSL58163T

16

900

LSL58216A

LSL58616A

LSL58233A

LSL58116A

LSL58164T

20

1100

LSL58220A

LSL58620A

LSL58234A

LSL58120A

LSL58165T

24
28
32

1300
1650
1850

LSL58224A
LSL58328A
LSL58332A

LSL58624A
LSL58628A
LSL58632A

LSL58235A
LSL58336A
LSL58337A

LSL58124A
LSL58128A
LSL58132A

LSL58166T
LSL58167T
LSL58168T

(1) Mandatory for front plate mounting.


For the flush-mount kit and enclosure accessories, see page D-8.

Enclosure weight
Empty weight
No. of vertical
Weight (kg)
modules
Enclosure W = 600 mm
(1 module = 50 mm)
Without door
With door
4

With door

13

10

13

17

12

15

21

12

16

18

25

15

20

20

29

17

24

22

33

19

28

33

46

26

32

35

50

28

An assembly kit is supplied with the 300 mm wide duct in standard.


Designation

Cat. no.
LSL58273A

4 assembly kit IP30/31/40

Horizontal combination of
3 enclosures W = 600 + 300 +
600 mm with 1 x LSL58273A

DD800061

Vertical and horizontal


combination with
2 x LSL58273A

Horizontal combination of
2 enclosures W = 600 mm
with 1 x LSL58273A
DD800064

Vertical combination
with 1 x LSL58273A

DD800060

DD800058

Combinations possibilities

DD800062

DD800088

Assembly kit

10

Enclosure + door W = 300 mm

Horizontal combination of
Square combination of
2 enclosures W = 600 + 300 mm 4 enclosures W = 600 mm with
with 1 x LSL58273A
4 x LSL58273A

D-5

DD800054

DD800478

Full kit

Overall Functional Overall


depth height
Height
(mm) (1 module (mm)
= 50 mm)
235

305

Enclosure Front plate Duct with


Door
W = 600 mm support (1) door
plain
W = 300 mm

DD380624

Selection table

DD380623

Commercial numbers

DD800057

System L

IP40
wall mounted enclosures
DD800546

Enclosures

or transparent

300

LSL58204A LSL58604A -

500

LSL58208A LSL58608A LSL58231A LSL58149A LSL58160T

LSL58104A -

12

700

LSL58212A LSL58612A LSL58232A LSL58150A LSL58161T

16

900

LSL58216A LSL58616A LSL58233A LSL58151A LSL58157T

20

1100

LSL58220A LSL58620A LSL58234A LSL58152A LSL58158T

24
28
32

1300
1650
1850

LSL58224A LSL58624A LSL58235A LSL58153A LSL58159T


LSL58328A LSL58628A LSL58336A LSL58154A LSL58169T
LSL58332A LSL58632A LSL58337A LSL58155A LSL58170T

(1) Mandatory for front plate mounting.


To ensure the degree of protection IP40, the gasket kit (LSL58276A) is needed.

Enclosure weight
Empty weight
No. of vertical
Weight (kg)
modules
Enclosure W = 600 mm
(1 module = 50 mm)
Without door
With door
4

DD800088

Assembly kit

10

Enclosure + door W = 300 mm


With door

13

10

13

17

12

15

21

12

16

18

25

15

20

20

29

17

24

22

33

19

28

33

46

26

32

35

50

28

An assembly kit is supplied with the 300 mm wide duct in standard.


Designation

Cat. no.
LSL58273A

4 assembly kit IP30/31/40

Horizontal combination of
3 enclosures W = 600 + 300 +
600 mm with 1 x LSL58273A

D-6

Horizontal combination of
2 enclosures W = 600 mm
with 1 x LSL58273A
DD800064

Vertical and horizontal


combination with
2 x LSL58273A
DD800063

DD800062

Vertical combination
with 1 x LSL58273A

DD800061

DD800060

DD800058

Combinations possibilities

Horizontal combination of
2 enclosures W = 600 + 300
mm with 1 x LSL58273A

Square combination of
4 enclosures W = 600 mm with
4 x LSL58273A

Selection table

DD800054

DD800478

Full kit

Overall Functional Overall


depth
height
Height
(mm)
(vertical
(mm)
modules of
50 mm)
235

305

Enclosure
W = 600 mm

Duct with
door
W = 300 mm

DD380624

Commercial numbers

DD380623

System L

IP54
wall mounted enclosures

DD800057

Enclosures

Door
plain

or

transparent

300

LSL58504A

LSL58104A

500

LSL58508A

LSL58541A

LSL58149A

LSL58160T

12

700

LSL58512A

LSL58542A

LSL58150A

LSL58161T

16

900

LSL58516A

LSL58543A

LSL58151A

LSL58157T

20

1100

LSL58520A

LSL58544A

LSL58152A

LSL58158T

24
28
32

1300
1650
1850

LSL58524A
LSL58528A
LSL58532A

LSL58545A
LSL58546A
LSL58547A

LSL58153A
LSL58154A
LSL58155A

LSL58159T
LSL58169T
LSL58170T

For enclosure accessories, see page D-8.

Enclosure weight
Empty weight
No. of vertical
modules
4

Enclosure W = 600 mm

Enclosure + door W = 300 mm

Without door

With door

With door

10

13

10

13

17

12

15

21

12

16

18

25

15

20

20

29

17

24

22

33

19

28

33

46

26

32

35

50

28

An assembly kit is supplied with the 300 mm wide duct in standard.


Designation

Cat. no.
LSL58275A

Assembly kit IP54

Horizontal combination of
3 enclosures
W = 600 + 300 + 600 mm
with 1 x LSL58275A

Horizontal combination of
2 enclosures
W = 600 + 300 mm with
1 x LSL58275A

DD800090

DD800091

Vertical and horizontal


combination with
2 x LSL58275A

Horizontal combination of
2 enclosures W = 600 mm
with 1 x LSL58275A
DD800094

Vertical combination
with 1 x LSL58275A

DD800093

DD800089

Combinations possibilities

DD800092

Assembly kit

Weight (kg)

Square combination of
4 enclosures W = 600 mm
with 4 x LSL58275A

D-7

IP30/31/40/54 enclosures
accessories

Enclosures
System L
Commercial numbers

The addition of a canopy over a wall mounted enclosure equipped with a door
ensures compliance with the degree of protection IP31.

Canopy (IP31)
DD800026

Designation
IP31 canopy

Com. no.
W = 620 mm

LSL58266A

W = 300 mm

LSL58267A

W = 620 mm

LSL58269A

W = 300 mm

LSL58270A

D = 235

W = 600 mm

LSL58268A

D = 300

W = 600 mm

LSL58271A

D = 235 mm
D = 300 mm

IP31 canopy extension

DD800121

15

Combination of 600 mm and 300 mm


wide wall mounted enclosures.

15

Combination of 2 x 600 mm wide wall mounted


enclosures.

15

Combination of 600 mm + 300 mm +


600 mm wide wall mounted enclosures.

DD381256

Flush-mount kit (IP30/31)

Designation

Designation
2 additional lifting/fixing rings

DD800491

Combination of more than three 600 mm wide


wall mounted enclosures.

When the enclosure is embedded into the wall, a flush-mounted kit is mandatory to
fix it and to hide free spaces.
The flush-mounted enclosure exceeds of 63 mm from the wall.
Flush-mount kit up to 24 modules

Lifting/fixing rings

15

Com. no.
LSL58272A

Com. no.
LSL58274A

IP30/31/40 wall mounted enclosures


bb From 4 to 24 modules, switchboards is mounted on a wall through the holes at the
rear of the switchboard. It is possible to mount the switchboards on a wall by using
external wall mounted fixing rings (2 x LSL58274A).
bb From 28 to 32 modules, switchboards is mounted on a wall by using external wall
mounted fixing rings (LSL58274A).
IP54 wall mounted enclosures
bb Switchboards is mounted on a wall by using external wall mounted fixing rings
(supplied).

D-8

DD800189

DD800126

Dimensions of combined wall mounted enclosures with canopies

IP30/31/40/54 enclosures
accessories

Enclosures
System L
Commercial numbers

Barrel lock and insert


DD800122

Designation

Com. no.

Barrel lock no. 405

08940

DIN double bar insert

08945

Screwdriver slot insert

08946

08940
08945
08946

Cable tie supports


DD800141

Drawing holder
DD381208

Designation
4 wall mounted cable tie
supports

Com. no.
W = 300 mm

LSL58293A

W = 600 mm

LSL58296A

Designation
Adhesive drawing holder, colour RAL 9001

Com. no.
08963

D-9

IP30/40 PAK
wall mounted enclosures

Enclosures
System L
Dimensions

Aperture

DD800476

DD800477

DD800479

DD800410

Door

DD800095

Wall mounted enclosures

No of modules
H

12

16

20

24

300

500

700

900

1100

1300

DD800077

DD800538

Wall mounting

No of modules
4

12

16

20

24

400

600

800

1000

1200

1400

220

420

620

820

1020

1220

DD800547

Top cable entry


105
320
527

Functional uprights

49
93

LSL58802A

D-10

Slotted mounting plates


DD800116

DD800109

DD800115

Adjustable device rail

LSL58824A and LSL58825A

Plain mounting plate


DD800117

Depth behind front plate

LSL58826A and LSL58827A

IP30/31
wall mounted enclosures

Enclosures
System L
Dimensions
Wall mounted enclosures

DD800100

DD800102
DD800103

150

DD800101

82.5

82.5

165
DD800095

Door

300 mm wide duct

From 28 to 32 modules

DD800097

From 4 to 24 modules

40 x 40

165
150
450

DD800066

600

Aperture

12

16

20

24

28

32

300

500

700

900

1100

1300

1650

1850

DD800410

No of modules

Wall mounted enclosures

DD800076

From 28 to 32 modules

DD800149

From 4 to 24 modules

DD800077

Fixing hole diameters

No of modules
4

12

16

20

24

28

32

400

600

800

1000

1200

1400

1700

1900

220

420

620

820

1020

1220

1610

1810

554

46

254

23

Functional uprights

202.8

DD800115

Adjustable device rail


49
93

LSL58802A

Slotted mounting plates

LSL58824A and LSL58825A

Plain mounting plate


DD800117

Depth behind front plate

DD800480

23

DD800116

137.8

237.5

225

Cable entry for base frame


DD800105

DD800104

Top cable entry

DD800108

Fixing to floor for 28 and 32-module


enclosures

LSL58826A and LSL58827A

301.5

63

D-11

IP40
wall mounted enclosures

Enclosures
System L
Dimensions
Wall mounted enclosures

DD800100

DD800102
DD800103

150

DD800101

82.5

82.5

165
DD800095

Door

300 mm wide duct

From 28 to 32 modules

DD800097

From 4 to 24 modules

40 x 40

165
150
450

DD800066

600

Aperture

12

16

20

24

28

32

300

500

700

900

1100

1300

1650

1850

DD800410

No of modules

Wall mounted enclosures

DD800076

From 28 to 32 modules

DD800149

From 4 to 24 modules

DD800077

Fixing hole diameters

DD800108

Fixing to floor for 28 and 32-module


enclosures
No of modules
4

12

16

20

24

28

32

400

600

800

1000

1200

1400

1700

1900

220

420

620

820

1020

1220

1610

1810

23

23

236.5

63

202.8

Adjustable device rail


DD800115

DD800109

Functional uprights

49
93

LSL58802A

D-12

254

301.5

Slotted mounting plates

Plain mounting plate


DD800117

Depth behind front plate

63

46

DD800116

137.8

237.5

554

Cable entry for base frame


DD800105

DD800104

Top cable entry

172.5 143.5

225

LSL58824A and LSL58825A

LSL58826A and LSL58827A

IP54
wall mounted enclosures

Enclosures
System L
Dimensions
Wall mounted enclosures

DD800100

150

DD800102

82.5

82.5

165
DD800095

Door

300 mm wide duct

From 28 to 32 modules

DD800097

From 4 to 24 modules

40 x 40

165
150
450

DD800103

DD800101

DD800066

600

Aperture

12

16

20

24

28

32

300

500

700

900

1100

1300

1650

1850

DD800410

No of modules

Wall mounted enclosures


DD800106

From 28 to 32 modules

Fixing hole diameter


9

DD800107

DD800150

From 4 to 24 modules

16

No of modules
A

12

16

20

24

28

32

400

600

800

1000

1200

1400

1700

1900

DD800108

Fixing to floor for 28 and 32-module


enclosures
225

23

Top cable entry

254

23

DD800105

49
93

LSL58802A
237.5

Slotted mounting plates

Plain mounting plate


DD800117

236.5

63

DD800115

172.5 143.5

Adjustable device rail


DD800116

DD800104

Functional uprights
DD800109

46

Cable entry for base frame

Depth behind front plate

DD800480

554

LSL58824A and LSL58825A

LSL58826A and LSL58827A

301.5

63

D-13

E-2

Characteristics

Contents

System L

Spare parts

E-2

Electrical characteristics

E-3

Mechanical characteristics

E-8

Designing Prisma iPM power circuits


Designing connections y 630 A
Designing connections with cables
Designing the PEN conductor

Degree of protection
Properties of metal enclosure

Environment

Environmental profile of Prisma iPM switchboards

E-3
E-4
E-6
E-7

E-8
E-10

E-12

E-12

E-1

Characteristics

Spare parts

System L
Spare parts

Door accessories

E-2

Wall mounted enclosure


Door spare parts for system L
20 front plate screws + nuts
Prisma iPM spare parts handle

Com. no.
LSL58033A
LSX58030A
LSX58031A

Designing Prisma iPM


power circuits

Characteristics
System L

Presentation and approach

Electrical characteristics

In the following pages you will find a number of examples, validated for Prisma iPM
switchboards, intended to assist in determining the busbars as well as the upstream
and downstream connections for the installation.
The examples assume that the devices have already been selected.
A complete process involves a number of steps before making final choices
(transformer, conductors, protection, etc.).
Schneider Electric offers a number of tools to assist in designing a complete
installation (technical guides, software).

PD800000

PD800010

The Prisma iPM system takes into account the


installation and connection conditions of Schneider
Electric devices.
The entire installation complies with standard IEC
61439-1. The result is a type tested switchboard.

Busbar sizing

The factors that must be taken into account in determining the size of busbars
include:
bb the diversity factor.
Not all the loads supplied by a set of busbars are used at full rated load or at the
same time. The diversity factor is the means to determine the maximum load current
used to size the busbars.
Standard IEC 61439-1.
Number of circuits
2 and 3
4 and 5
6 to 9
10 and more

Diversity factor
0.9
0.8
0.7
0.6

bb the degree of protection IP.


For information on defining the necessary degree of protection IP.
bb the ambient temperature around the switchboard.

E-3

Characteristics
System L

Designing connections y 630 A


Device connections

Electrical characteristics

Insulated flexible copper bars

Switchboards that comply with standard IEC 61439-1

It is imperative to use the values indicated below that have been validated for the
installation of devices in Prisma iPM switchboards.
The parameters determining the size of flexible bars are:
bb the environment in which the devices are installed:
v position in the enclosure,
v dimensions of other conductors in the circuit,
v ambient temperature around the switchboard,
bb the characteristics of the connected devices:
v device heat losses,
v the type of installation (horizontal or vertical),
v the type of device (fixed or withdrawable).
Only the equipment manufacturer with in-depth knowledge on:
bb the characteristics of the installed devices
the configuration of the installation in the enclosure can provide the correct sizes of
flexible bars for a given permissible current. Insulated, flexible bars make for easy,
fast and flexible implementation up to 630 A, but higher ratings require sizes that
cancel these advantages.
For high Isc values, it is advised to use rigid bars which require fewer supports.

Insulated flexible bars are better than cables, they offer:

bb flexible copper bars with an insulating sheath,


bb better insulation temperature withstand (125C for bars, 105C for cables) and a
larger exchange surface for an equivalent size, i.e. a smaller size for a given current,
bb greater rigidity offering better electrodynamic characteristics for short-circuit
currents,
bb no intermediate parts (lugs) for a direct connection between the device and the
busbars therefore less temperature rise and less risk of error,
bb fast implementation of prefabricated connections already cut to length, formed and
drilled.
Technical characteristics
bb thickness of the insulation: variable depending on the bar size, 2 mm on average,
bb rated insulation level Ui = 1000 V,
bb impulse withstand voltage Uimp = 12 kV,
bb maximum withstand temperature of insulating material = 125C.

Connection

In all cubicles with IP y 54


bb the switchboard internal temperature is 60C,
bb the withstand temperature of the insulating material is 125C.
If the withstand temperature of the insulation is only 105C, use the next largest
flexible bar.
The bar sizes indicated below take into account the derating curves of devices.

Connection of devices and distribution blocks to busbars


Device
S (mm)

Device
S (mm)

Device
S (mm)

INS125 (1) INS160 (1) INS250 (1) INS320 (1)


INS400 (1)
20 x 2
20 x 2
20 x 3
32 x 5
NS250(1) NS400(1) NS630 (1) NSX100 (1)

INS500 (1) NS100(1) NS160(1)


INS630 (1)
32 x 8
20 x 2
20 x 3
NSX160 (1) NSX250 (1) NSX400 (1)

20 x 3

20 x 3

32 x 5

32 x 8

20 x 2

20 x 3

32 x 5

NSX630 (1) EZC100 (1) EZC160 (1) EZC250 (1) EZC400 (1)
32 x 8

20 x 2

20 x 3

20 x 3

32 x 5

(1) The values for circuit breakers apply to contactors with the same ratings.

Device
S (mm)

Multiclip distribution
block (200 A)
20 x 3

Disconnectors, terminal blocks, connections, busbars to


busbars
I max. (60 C)
S (mm)

200 A
20 x 2

250 A
20 x 3

400 A
24 x 5

400 A
24 x 5

480 A
24 x 6

520 A
32 x 5

Note: The values indicated above have been validated for Prisma iPM switchboards.

E-4

660 A
32 x 8

Characteristics

Designing connections y 630 A


Compact circuit breakers
NSX100 to NSX630

System L
Electrical characteristics

Compact NSX100 to NSX250


Insulated flexible copper bars
Devices

Permissible current (A)


Average ambient temperature around the switchboard

25 C

30 C

35 C

40 C

45 C

50 C

IP y 54
NSX100
TMD-TMG
NSX125
TMD-TMG
NSX160 (1)
TMD-TMG
NSX250 (1)
TMD-TMG
NSX100
STR
NSX160
STR
NSX250 (2)
STR

Size per phase


I (A)
Size per phase
I (A)
Size per phase
I (A)
Size per phase
I (A)
Size per phase
I (A)
Size per phase
I (A)
Size per phase
I (A)

20 x 2
100
20 x 2
125
20 x 3
160
20 x 3
250
20 x 2
100
20 x 3
160
20 x 3
250

20 x 2
20 x 2
20 x 2
20 x 2
20 x 2
97.5
95
92.5
90
85
20 x 2
20 x 2
20 x 2
20 x 2
20 x 2
122
119
116
113
100
20 x 3
20 x 3
20 x 3
20 x 3
20 x 3
156
152
147
144
140
20 x 3
20 x 3
20 x 3
20 x 3
20 x 3
244
238
231
225
198
20 x 2
20 x 2
20 x 2
20 x 2
20 x 2
100
100
100
100
100
20 x 3
20 x 3
20 x 3
20 x 3
20 x 3
160
160
160
160
160
20 x 3
20 x 3
20 x 3
20 x 3
20 x 3
250
237.5
237.5
225
225
(1) For a withdrawable NSX160 or NS250 equipped with a Vigi or an insulation-monitoring
module, multiply the In values by 0.9.
(2) For a withdrawable NSX250 equipped with a Vigi or an insulation-monitoring module, multiply
the In values by 0.86.

Compact NSX400 to NSX630


Insulated flexible copper bars
Devices

Permissible current (A)


Average ambient temperature around the switchboard

25 C

30 C

35 C

40 C

45 C

50 C

32 x 5
400
32 x 5
400
32 x 8
630
32 x 8
570

32 x 5
400
32 x 5
390
32 x 8
615
32 x 8
550

32 x 5
400
32 x 5
380
32 x 8
600
32 x 8
535

32 x 5
390
32 x 5
370
32 x 8
585
32 x 8
520

32 x 5
380
32 x 5
360
32 x 8
570
32 x 8
505

32 x 5
370
32 x 5
350
32 x 8
550
32 x 8
490

IP y 54
NSX400N/H/L
fixed
NSX400N/H/L
with Vigi
NSX630N/H/L
fixed
NSX630N/H/L
with Vigi

Size per phase


I (A)
Size per phase
I (A)
Size per phase
I (A)
Size per phase
I (A)

E-5

Characteristics
System L

Designing connections with


cables

Electrical characteristics

Cables

Practical guidelines

Schneider Electric provides cabling recommendations according to the rating of the


circuit breaker.
The size of cables must be selected according to:
bb the level of current,
bb the ambient temperature around the conductors,
bb the degree of protection for the switchboard.
The tables below take into account the installation conditions for each type of device
(permissible temperature at connection terminals, etc.).
They follow the temperature derating values for installed devices in all cubicles with
cover panels rated IP y 55.
bb switchboard internal temperature 60C,
bb connections using copper cables.
For wall mounted enclosures, the volumes, ratings and connection lengths are low.
Select the values in the Cables tied together column, according to the IP.

Supply of devices
for outgoers y 630 A

Flexible copper bars with an insulating cover.


To determine the required sizes for flexible bars, see the tables starting on, which
indicate the correct size for each type of connected device.
bb an insulated flexible bar (not connected) must meet standards IEC 60243-1
(dielectric) and IEC 60332-1 (fire),
bb a flexible bar connected to a device in an enclosure must comply with standard
IEC 61439-1 (see explanations on).
Cables
To determine the cables required, see the table on.
They can be used to determine:
bb the size of cables as a function of:
v the circuit breaker rating,
v the current,
v the ambient temperature around the switchboard,
bb the permissible current for individually tied cables or touching cables as a function
of:
v the size of the cables,
v the degree of protection for the switchboard.

Connection of circuit breakers

Size of
cables
(mm)
1.5
2.5
4
6
10
16
25
35
50
70
95

Permissible current (A)


Cables tied individually
IP y 31
IP > 31
16
25
32
40
63
90
110
135
180
230
275

14
25
29
39
55
77
100
125
150
190
230

Cable tied together


IP y 31
IP > 31
14
22
28
36
55
80
100
125

12
20
24
33
50
70
93
120

Note: Schneider Electric recommends connecting NSX400/630 circuit breakers with insulated
flexible bars or rigid bars.

Connection of other devices

Size of
cables
(mm)
1.5
2.5
4
6
10
16
25
35
50
70
95

E-6

Permissible current (A)


Cables tied individually
IP y 31
IP > 31
13
23
28
36
55
80
100
120
165
210
250

12
21
26
35
50
70
90
115
135
176
210

Cable tied together


IP y 31
IP > 31
12
20
25
32
50
72
90
110

10
19
22
30
46
63
84
103

Characteristics
System L

Designing the PEN conductor


Power circuit

Electrical characteristics

Size of PEN protective conductor

Practical guidelines

The size of the PEN is determined in the same manner as a neutral conductor, i.e.:
bb for copper single-phase circuits or sized y 16mm, it must be the same size as the
phase conductors
bb for copper three-phase circuits sized > 16 mm, it can be:
v the same size as the phase conductors,
v smaller on the condition that:
- the current likely to flow in the neutral during normal operation is less than the
permissible current for the conductor,
- the power rating of single-phase loads does not exceed 10% of the total rating.
The conductor must be accessible to enable connections both in the factory and on
site, as well as checks on the tightness of connections.

Implementing the PEN protective


conductor

Practical guidelines

According to standard IEC 61439-1, the practical guidelines for implementing the
PEN are the following:
bb at the entry to the assembly, the PEN connection must be next to the phase
connections,
bb within the assembly, the PEN does not need to be insulated from the exposed
conductive parts (except on sites where there is a risk of fire or explosion),
bb the size of the conductor must be at least equal to that of the neutral,
bb the size must remain constant throughout the main busbars,
bb the change from a TNC to a TNS system must take place at a single point in the
switchboard, via a marked neutral-disconnection bar that is accessible and can be
dismantled to facilitate the impedance measurement of the fault loop,
bb after the TNS creation point, it is forbidden to recreate a TNC system.
The PE and the neutral must meet their specific requirements.

E-7

Degree of protection

Characteristics

General

System L
Mechanical characteristics

Standard IEC 60364-5-51 listed and codified a large number of external


influences to which electrical installations can be subjected, including the
presence of water, solid objects, shocks, vibrations, corrosive substances,
etc.

Degree of protection IP

Standard IEC 60529 (IP code, February 2001) indicates the degrees of protection
provided by an enclosure for electrical devices against access to hazardous parts,
against penetration of solid foreign objects and against penetration of water.
These standards do not apply for the protection against the risks of explosion or
conditions such a humidity, corrosive vapour, fungus or vermin.
The IP code is made up of two characteristic numerals and can include an additional
letter when the actual protection for persons against access to the hazardous parts
is better than that indicated by the first numeral.
The first numeral characterises the protection provided against the ingress of solid
foreign objects and the protection of persons.
The second numeral characterises the protection provided against the ingress of
water with harmful effects.

Protected against
access with a wire

E-8

DD381963
DD381961
DD381962
DD381964
DD381965

DD381962
DD381962

Dust tight

Protected against
splashing water from
all directions

Protected against
water jets from all
directions

Protected against
powerful water jets
from all directions

Protected against the


effects of temporary
immersion in water

Protected against the


effects of continuous
immersion in water

DD381966

Protected against dust


(dust protected)

Protected against
spraying water up to
60 from vertical

DD381967

Protected against
access with a wire

DD381968

Protected against
solid foreign objects
larger than 1mm

Protected against
vertically falling water
drops when enclosure
tilted up to 15

DD381969

Protected against
access with a wire

DD381970

Protected against
solid foreign objects
larger than 2.5mm

Protected against
vertically falling water
drops (condensation)

DD381971

Protected against
access with a tool

DD381972

Protected against
solid foreign objects
larger than 12.5mm

2nd numeral
Protection against ingress of water

DD381973

Protected against
access with a finger

Protected against
solid foreign objects
larger than 50mm

DD381959

DD381959

Protected against
access with back of
hand

DD381960

DD381961

Protection against ingress of solid objects

DD381962

1st numeral
Protection of persons

Characteristics
System L

Degree of protection
General

Mechanical characteristics

Additional letter (optional)

Protection of persons against access to hazardous parts.


Designation

Protection

A
B
C
D

Protected against access with back of hand


Protected against access with a finger
Protected against access with a tool
Protected against access with a wire

The additional letter is used only if the actual protection of persons is higher than that
indicated by the first characteristic numeral of the IP code.
If only the protection of persons is of interest, the two characteristic numerals are
replaced by X, e.g. IPxxB.
Example
Protected against solid foreign objects
larger than 2.5 mm

IP30D

No protection
Protected against access with
a tool 1mm in diameter

Remarks on the degree of


protection IP

bb the degree of protection IP must always be read and understood numeral by


numeral and not as a whole.
For example, an IP31 wall mounted enclosure is suitable for an environment that
requires a minimum degree of protection IP21. But an IP30 wall mounted enclosure
is not suitable.
bb the degrees of protection indicated in this catalogue are valid for the enclosures as
presented. However, the indicated degree of protection is guaranteed only when the
installation and device mounting are carried out in accordance with professional
standards.

Degree of protection against


mechanical impacts IK

Standard IEC 62262 defines an IK code characterising the capacity of products to


resist mechanical impacts from all sides.
IK code

Impact energy (joules(1))

01
0.14
02
0.2
03
0.35
04
0.5
05
0.7
06
1
07
2
08
5
09
10
10
20
(1)The SI derived unit used to measure energy or work. One joule is equal to the energy used to
accelerate a body with a mass of one kilogram using one newton of force over a distance of one
meter. One joule is also equivalent to one watt-second.

Recommendation

In terms of the risks of impacts, selection of the IK code can be summed up as


indicated below.
No risk of major impact

Site

Recommended IK

Technical rooms

07

Significant risk of impact that


Hallways
can damage devices
Maximum risk of impact that can Workshops
damage the switchboard

08 (switchboard with door)


10

E-9

Characteristics

Properties of metal enclosure

System L
Mechanical characteristics
Schneider Electric enclosures comply with standard EN 50298 for empty enclosures.
The sheet metal used for Schneider Electric enclosures receives a thermosetting,
polyester-resin-modified epoxy powder for colour and appearance.
This coat system provides excellent finish and corrosion protection.

Mechanical properties of powder


coated surfaces

Test conditions

Adhesion (cross-hatch and pull-off)


class 0 required
(ISO 2409)
> 1 kg/40 cm
(ISO 6272)
Impact strength (1)
< 10 mm
(ISO 6860)
Mandrel bending test (2)
Persoz hardness
300 s
(ISO 1522)
(1) No cracking of the paint film after dropping a weight of one kilogram on the test piece from a
height of 50 centimetres.
(2) Film cracks over a length of 10 millimetres maximum.

Artificial ageing test on powder


coating

Test conditions:
Two tests carried out on the same 1 mm thick steel sheet test piece.
bb cyclical damp-heat test:
v as per standard IEC 68-2-30,
- six 24-hour cycles at temperatures higher than 40C,
bb continuous resistance to neutral salt mist:
v the tests were carried out over a period of 400 hours, far more than the 48 hours
required by the standard for indoor installations,
v as per standard IEC 68-2-11 and ISO 7253
- 400 hours without blistering for normal surface on test piece,
- 250 hours for a scratched surface.
Evaluation of corrosion as per ISO 4628:
bb adhesion: class y 1,
bb blistering: degree 1 dim.1,
bb rusting: Ri 1,
bb cracking: class 1,
bb flaking imp. 1 dim. 1.
propagation of corrosion under scratch with respect to the scratch axis: 3 mm
max.

E-10

Characteristics

Properties of metal enclosure

System L
Mechanical characteristics

Chemical properties of
powder coating

Tests carried out at ambient temperature on phosphated test pieces coated


with a 150 to 200 micron film.
Test duration (months)

Acids

Bases
Water

Solvents

Acetic
Sulphuric
Nitric
Phosphoric
Hydrochloric
Lactic
Citric
Soda
Ammonia
Distilled water
Seawater
Tap water
Diluted bleach
Petrol
High alcohols
Aliphatics
Aromatics
Ketones, esters
Tri-perchlorethylene

Concentration
20 %
30 %
30 %
30 %
30 %
10 %
10 %
10 %
10 %

10

12

Film intact.
Film damaged (blisters, yellowing, loss of shine).

E-11

Environmental profile of
Prisma iPM switchboards

Characteristics
System L
Environment
Schneider Electric is committed to a
long-term environmental policy.
Its intention is to promote respect of all natural
resources and to work towards constant active
improvement of conditions for a clean environment for
the satisfaction of its customers, staff and the
communities in which it is based.

Prisma iPM has reaped the benefits of an ecological design process which has
improved its environmental performance.
This committed approach, aiming to integrate environmental protection right from the
design phase, has been a deciding factor on different aspects:
bb the choice of materials used to preserve natural resources,
bb use of environmentally friendly manufacturing procedures,
bb a degree of product recyclability which is well over the environmental
recommendations.
For Schneider Electric, acting responsibly as a company with regard to the
environment and on a wider scale, to society in general, contributes to performance:
bb by obtaining ISO 14001 certification for all its sites,
bb by making pertinent decisions for the long term,
bb by encouraging all its partners, in particular its suppliers and customers, to support
the initiative.

Product design

Use of high-performance tools has guided the designers in the choice of


materials and has enabled them to assess the impact of the product on the
environment throughout its life-cycle.
Published on 13th February 2003 and applicable as from 1st July 2006, directive
2002/95/EC concerning the restriction of use of certain dangerous substances in
electrical and electronic equipment is more commonly known as the RoHS directive
(Restriction of Hazardous Substances).
Among these substances which are considered dangerous to the environment and
health we find lead, mercury, cadmium, hexavalent chromium, polybrominated
biphenyls(1) (PBB) and polybrominated diphenyl ethers(1) (PBDE).
These six substances are banned or restricted (if exemption) in the electrical and
electronic equipment listed in the WEEE directive and replaced by more
environmentally friendly substances.
Schneider Electric products are little or only indirectly affected by this
restriction. However all low voltage products will be subject to compliance as
from December 2008.

Production

PD395090

PD395023

Production is an important phase in the switchboard life-cycle.


Schneider Electric has adopted a dynamic, ambitious environmental policy in its
initiative to integrate environmental protection into its industrial processes, in
particular by obtaining ISO 14001 certification for all its sites.

(1) They are self-timer of brominated flames.

E-12

Characteristics
System L

Environmental profile of
Prisma iPM switchboards

Environment
The concept of a switchboard delivered in kit form, combined with particularly well
thought-out packaging has made it possible to significantly reduce volumes and
therefore limit the risks and pollution caused by transport.
A significant reduction
in volumes transported
With the kit system, the
products are delivered
flat-packed and are easy
to store and handle.

PD395096

PD395122

Distribution

PD395011

Optimum use of packaging


Schneider Electric complies with the packaging directive. Published for the first time
on 31st December1994, directive 94/62/EC concerning packaging and packaging
waste has since been updated many times.
This directive applies to all packaging put on the market and all waste produced by it
with the aim of reducing its impact on the environment.
The obligations mainly concern reducing the volume, weight and quantity of heavy
metals used in packaging, its reuse or recovery at the end of its life and
implementation of a system for collecting packaging waste.

Switchboard use

Use of the Prisma iPM electrical switchboard is a phase of the life-cycle which
can have a significant impact on the environment.
Prisma iPM contains products in compliance with the EUP directive. Published on
22nd July 2005, directive 2005/32/EC relating to ecological design requirements to
be applied to energy consuming products is more commonly known as the EUP
(Energy Using Products) directive.
The aim of this directive is to achieve a high level of environmental protection by
reducing the impact of energy consuming products and fostering acceptance of the
concept of ecological design within companies.
As the switchboard consumes electricity, a certain number of criteria have been
taken into account:
bb reducing energy consumption in the usage phase to a minimum,
bb reducing leaks and release into the environment to a minimum
bb increasing product durability,
bb easier product maintenance and repair (product reliability, product modularity,
etc).
Schneider Electric undertakes to comply with recycling rates and to recover the
products at the end of their life. The group meets the WEEE (Waste Electrical and
Electronic Equipment) directive. Published on 13th February 2003, directive
2002/96/EC concerning electrical and electronic equipment waste is more
commonly known as the WEEE directive.
An easily-dismantled product.
The product is in kit form. All components can be
removed, which facilitates sorting the different types of
materials.

PD395051

End-of-life

E-13

Characteristics
System L
Environment

Environmental profile of
Prisma iPM switchboards
(Example)

Example with a 250 A switchboard:


Design:
bb functional units:
v incomer: fixed Compact NSX 250 A circuit breaker,
v feeders: 3 rows of Multi 9 devices,
bb current distribution
v Multiclip distribution block,
bb enclosure:
v 24 module enclosure,
v 24 module transparent door.
Technical characteristics:
bb product reference standard: IEC 61439 - 1,
bb rated insulation voltage for the main busbar: Ui up to 1000 V,
bb rated operating current: In up to 630 A,
bb rated short-time withstand current: Icw up to 25 kA rms/1s.
1 Materials used in the switchboard.
The total weight of the enclosure is 29.4kg in the following proportions:
Material
Steel
Copper
Aluminium
Stainless steel
Brass
Zamak
Thermoplastic
Total

Weight (kg)
28.5
0.14
0.6
0.003
0.004
0.014
0.15
29.4

Percentage of the total


weight (%)
96.9
0.5
2
0.01
0.01
0.01
0.5
100

2 Energy consumption.
The electrical energy dissipated by the 250 A switchboard depends on the operating
conditions.
The following assumptions have been chosen to calculate energy consumption:
bb annual rate of load for the equipment (Tc): 30%,
bb estimated length of use of the equipment (d): 20 years (equivalent to
175,200 hours),
bb energy consumption for the enclosure (E): 3322.6 kWh/20 years.
Method of calculation
If P is the power dissipated in the enclosure, energy consumption is calculated using
the following formula:
E = P x Tc x d

Prisma iPM enclosures do not contain either storage cells or batteries.

3 Packaging.
Materials used in packaging:
Materials
Cardboard
PE polyethylene
EPE
PA66
Total

Weight (kg)
2
0.18
0.19
0.01
2.38

Percentage of the total


weight (%)
84
8
8
0
100

Every care is taken in collaboration with our services, suppliers and subcontractors
to ensure that the packaging does not contain any substances which are forbidden
under European regulations.

E-14

System L
Environment

Environmental profile of
Prisma iPM switchboards
(Example)

4 Switchboard end-of-life management.


At the end of their service lives, the enclosures can be either dismantled or crushed
in order to make best use of the various component materials. This can take the form
of recycling or incineration.
99% of materials used in the 250 A switchboard can be recovered by
dismantling.
This percentage includes iron and non-iron materials used in the product.
0.5% can be incinerated, which includes the thermoplastics and thermosetting
plastics, in the knowledge that they do not contain any brominated flame retarders.
No particular precautions must be taken before crushing or dismantling unless the
enclosure is fitted with a transparent door. The glass used for this door weighs
approximately 4 kg and must be recycled separately.

PD800004

Characteristics

E-15

F-2

Recommendations

Contents

System L

Assembling recommendations

F-2

Assembling tips

F-8

Assembling sequences

Assemble the wall mounted enclosure Install the busbars


Install the mounting plates
Run and cable the power circuits
Route and cable the low power and auxiliary circuits
Finish and fit the switchboard with panels

F-2

F-8
F-9
F-10
F-11
F-12

F-1

Assembling sequences

Recommendations
System L

PD800067

Assembling recommendations
8

F-2

10

10

Recommendations

Assembling sequences

System L
Assembling recommendations
Chronology of the opposite switchboard configuration assembly:

1 - Wall mounted enclosure structure

bb Rear panel.

2 - Mounting plates and switchgears


bb Mounting plate with NSX 400
bb Mounting plate with Compact NSX100.
bb Modular device rails.
bb Multi9 and IC devices.

3 - Distribution blocks
bb 200 A Multiclip distribution block.

4 - Cable duct association


bb Cable duct.
bb Assembly kit.

5 - Busbars
bb Vertical multi-stage busbar.

6 - Wiring trunking
bb Trunking.
bb Tunking for the fine wiring.

7 - Power cables
bb Connection devices to busbar.
bb Terminal blocks.
bb Earth/neutral bar.
bb Connection devices to terminal blocks.

8 - Wall mounted enclosure covering


bb Pillars.
bb 2 side panels.
bb Top and bottom plates.
bb Front frame.

9 - Front plates
bb Front plates.

10 - Doors
bb Transparent door.
bb Plain door.

F-3

Recommendations

Assembling sequences

System L
Assembling recommendations

DD800494

Preparation of the rear panel

DD800490

Install the mounting plate with its circuit breaker

DD800488

Install the modular device rail

DD800400

Install the distribution block

DD800487

Install the modular devices

F-4

Recommendations

Assembling sequences

System L
Assembling recommendations

DD800401

x2

DD800402

DD800484

DD800485

DD800486

Install the cable duct

DD800403

DD800483

Install the selected busbar

F-5

Recommendations

Assembling sequences

System L
Assembling recommendations

DD800528

Wiring trunking

Power cables
E56846

Neutral bar

E56845

Earth bar

F-6

Recommendations

Assembling sequences

System L
Assembling recommendations

DD800437

DD800436

DD800438

Wall mounted enclosure covering

DD800482

Install the front plates

DD800481

Install the doors

F-7

Recommendations
System L

Assemble the wall mounted


enclosure Install the busbars

Assembling tips

DD800413

Assemble the wall mounted


enclosure

DD800088

Couple the enclosures

bb The wall mounted enclosure must be assembled


horizontally on a table that is protected to ensure the
paintwork is not damaged.
bb The assembly is quick and reliable.

NB
The cover panels
are assembled
once the internal
components have
been mounted and
cabled, thus
guaranteeing
100% access to
components
throughout
assembly and
installation.

bb The mounting hardware must be carefully


associated with each wall mounted enclosure.
During storage, take measures to prevent damaging
component paintwork.
bb Do not use the pillars to handle the rear panel of the
wall mounted enclosure.
Take care to ensure the enclosure rear panel remains
level during cabling operations.

DD800118

IP30/31/40 combination kit.

IP54 combination kit.

DD800018

Install the busbar

bb Busbar overall dimensions do not vary with current


strength.
bb Whatever the busbar type, the order of the bars is
always the same: from the front to the rear N, L1, L2
and L3.
bb With the rear busbar, the Neutral is to the left, then
L1, L2, L3.

F-8

NB
If cutting oil is used,
the busbars must
be cleaned prior to
assembly as oil
adversely affects
insulation
properties.

Recommendations

Install the mounting plates

System L
Assembling tips

DD800414

Install the mounting plates

bb To define the position of a mounting plate of a functional unit, you need to know the
overall dimensions of the functional unit (H), i.e. the number of modules
(1 module = 50 mm). This number is given in the functional unit pages catalogue.
The reference starting point for the installation of the mounting plate (b) is given in
the leaflets.

bb Table showing the assembly order according to the device type:


Device

Assembly order

EasyPact CVS and Compact NSX, Interpact


INS and Easypact EZC and EZC y 630 A

bb Place the device on the mounting plate.


bb Install the equipped mounting plate.

DD800415

Assemble order

bb The order of assembly of the mounting plates and devices depends on the
technical features of the devices.

DD800416

Modular devices

bb This operation allows operators inspection and prevents incorrect positioning of


the functional unit with respect to the front panel, before the wall mounted enclosure
has been cabled.

DD800495

Checking switchgear position

bb Install the rail system.


bb Place the modular devices on the rail.

F-9

Run and cable the power circuits

Recommendations
System L
Assembling tips

Installing the secondary


distribution blocks

bb You need to comply with connection capacities, stripping lengths, the number of
cables connected and use the appropriate tools.
bb Do not use ferrules with the spring loaded terminals. Each terminal may only take
a single wire.
bb On the Multiclip 200 A, cable entry is via the bottom only to allow assembly of the
insulating covers and production of cable straps.
bb Table showing the connections of the distribution blocks:
Connection capacity

Connection principle
DD800420

DD800417

DD800421

b Power supply

b Distribution

b Distribution

DD800422

DD800426

DD800427

Polybloc

DD800422

Type
Distribloc(1)

b Power supply

Multiclip 200 A (1)

b Power supply

DD800419

DD382235

DD800418

DD382813

DD800425

Multi-stage current distribution block

Comb busbar

b Power supply
DD800428

DD800424

DD800423

b Distribution

(1) The downstream device connecting cables are delivered with the Multiclip and Distribloc.

F-10

Recommendations
System L

Route and cable the low power


and auxiliary circuits

Assembling tips
bb Human switchboard interface with 72 x 72 mm,
96 x 96 mm, diameter 22 mm, lighting, push-button,
etc.

Cabling the auxiliary circuits

bb We recommend that you use protection devices for


wiring through uprights or to doors

DD800430

DD800013

Install the devices on door or


front plate

bb Mark the wires to simplify on-site connection and


maintenance of wall mounted enclosures, thus
avoiding laborious switchboard reworking that could
cause errors.

NB
The devices can be
installed on
conventional plain
doors by making a
cut-out.

NB
Thoroughly secure
cables onto the
door to avoid
disconnecting the
devices when
opening.
We recommend
you use protection
devices for wiring
through the front
panel or to the
doors.

F-11

Recommendations
System L

Finish and fit the switchboard


with panels

Assembling tips

DD800190

Labelling and marking

bb Device marking: this enables users of the system to


identify clearly the various circuits involved. Marking
should be fully legible, durable and properly attached to
the device.

NB
Barriers preventing
access to live parts
should be marked
with a DANGER
sign.

DD382180

E20578

bb Inside the switchboard: marking identifies the


devices, thus avoiding all risk of confusion when
working inside the switchboard

DD800431

Fitting the switchboard

bb When the doors are fitted, for safety reasons, ensure


that the door opening direction will not obstruct on site
access to an evacuation corridor or passageway. The
door must open in the direction of the evacuation.
bb It is advisable to install barrels and inserts before
fitting the handle on the door and before installation on
the wall mounted enclosure.

F-12

NB
Take care to
degrease surfaces
thoroughly before
sticking on the
gaskets.

Notes

F-13

Notes

F-14

35, rue Joseph Monier


CS 30323
F - 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com

LVED210001EN

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
This document has been printed on ecological paper.
Design: Schneider Electric
Photos: Schneider Electric
Publishing: Altavia Connexion

02-2012