User's Manual
for Generator Control Unit
Table of Contents
1. Outline 3
2. Features 3
3. Specification and Functions 3
4. Conditions of Use 3
5. Description of LED display 4
6. Structure 4
7. Preparation before Use 4
8. Signals and Marks 5
9. Connection Sockets and Capacity 5
10. Manual Start Test 6
11. Automatic Operation Test 7
12. Engine and Generator Protection Device
Operation Test 7
13. Description of DIP S/W and Other Buttons 9
14. Cause of Breakdown and Solution 11
Warning
Potential injury or
Caution
instructions
product damage
electrocution
Warning
electrocution.
3. Please do not touch with wet hands as it may cause electrocution.
4. Please do not touch when sheath of electric wire is damaged as it may cause
electrocution.
5. Please do grounding of electric wire to prevent electrocution.
1. Please permit a correct power supply to prevent product damage
Caution
and fire
2. Please be sure no foreign substances enter into the product as
they may cause short circuit or fire.
3. Please connect wire with correct load to input and output sockets to prevent product
damage and fire.
4. Please connect wire as instructed to prevent product damage and fire.
5. Only technicians or properly trained personnel may use this product as irrational use of
this product may cause injuries or damages to the product and devices connected to
the product.
6. As this product comprises of electrical components, please separate the product before
performing the test which requires high voltage such as inner voltage test or insulation
resistance test.
7. Please use fuse and electric wire with correct capacity to prevent fire.
8. Please hold this product firmly as it is used for engine generator with high vibration.
9. Please make sure there are no untangled parts before installation.
1. Outline
GCU-DG4 is a diesel engine generator controller with engine protection function. It is specially
optimized for Korean environment which allows easy and convenient use.
2. Features
2.1. Ability to use commercial power or non-electrical interface with automatic operating signal
2.2. Ability to adjust waiting time for start and stop when on automatic operation.
2.3. When starting manually start button needs to be pressed for more than 3 seconds for the
safety
2.4. Double protection of starter motor by detecting engine RPM and oil pressure switch
2.5. Engine warm-up plug for small engine
2.6. Built-in alarm sound
2.7. Stop Solenoid anti burn out design
2.8. Generator stop function upon no detection of MPU signal or power during normal
operation
2.9. Over speed test switch
2.10 RPM METER output.
2.11. Easy-to-understand operation lamp
2.12. Circuit protection design regarding to SURGE
2.13. SILICON MODLING for earthquake-proof and waterproof
4. Conditions of Use
4.1. Operation temperature: -10 ~ 40C
4.3. Relative humidity: 0% ~ 90% non-congelation 4.7. Maximum delivery altitude: 10,668m
4.4. Vibration:
amplitude-0.35mm, frequency-0~30Hz
Function
LED Color
Control Power
GREEN
Automatic Signal
GREEN
Operating Engine
Automatic
Manual Start
Over speed
Over temperature
Start Failure
SPEED
Light on upon selection of automatic mode
Light on upon selection of manual mode
Light on upon when engine speed is above OVER
SPEED setting
Light on when engine temperature is too high
Light on when engine does not start after third try of
GREEN
GREEN
RED
RED
RED
RED
Emergency stop
RED
Reserve breakdown
YELLOW
Over voltage
YELLOW
Over current
YELLOW
Low Voltage
YELLOW
Stop
YELLOW
RED
6. Structure
6.1. Dimension : W120 * H210 * D48 (mm)
6.2. Cut-out : W112*H182
6.3. Mounting Holes : W60*H196 / 5-4H
6.4. Color : Dark gray
6.5. Weight : 700g
Caution
Upon input of power, control power lamp is on and lamp near wrong wiring
flickers.
stopped
5S
: Stop solenoid
6X
52G : ACB
SM
: Starting motor
26W
PS
: Pinion solenoid
88
Coolant
temperature
relay
48X : Start failure relay
Description
Control power input
Start output
Stop output
Preheating output
Commercial power input platform
Generator power input platform
Input socket when using voltage
for engine speed detection
Automatic start
Rated Capacity
DC 8~35V , 15A
BP+ voltage output, Max 15A
BP+ voltage output, Max 15A
BP+ voltage output, Max 5A
1P 220Vac
0~75 Hz ,7~300 Vac
0~7,000 Hz ,4~20 Vac
CNT
TM+
86X-a, 86X-c
86X-b, 86X-c
input)
RPM METER connetion socket
Breakdown indicating interface
Breakdown indicating interface
Engine operation indicating
interface
Input of over temperature switch
Input of oil pressure switch
Input of emergency stop switch
SPARE input socket
Over voltage input socket
Over current input socket
Low voltage input socket(operates
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
6X-a, 6X-c
WTS
OPS
EPB
AFR
OVR
OCR
UVR
G+
connect
connect
connect
connect
connect
connect
switch,
CNT socket must be connected with DC- power when receiving commercial power by
commercial outage signal and when receiving outside interface input by outage signal,
commercial power must not connected to CP1 and CP2 sockets.
NO
Engine Condition
CNT
Commercial Power
ON
Supply
Stop
ON
Blackout
Operate
OFF
Supply
Stop
OFF
Blackout
Stop
Note
Input of low voltage relay will be overridden when below 80% of normal speed and
will be recognized only above 80% of normal speed.
(1) Start engine.
(2) Check if operation lamp of GCU is on and RPM METER shows normal RPM.
(3) Press TEST button of UVR.
(4) Over current lamp is on and buzzer sounds and engine will stop/still run depend on the
DIP S/W setting.
(5) Press buzzer stop and RESET.
12.9. Reserve Breakdown ( AFR - AUX FAULT )
(1) Start engine.
(2) Check if opeation lamp of GCU is on and RPM METER shows normal RPM.
(3) Press TEST button of AFR.
(4) Over current lamp is on and buzzer sounds and engine will stop/still run depend on the
DIP S/W setting.
(5) Press buzzer stop and RESET.
Period
(CDT)
Cool
Down
Period
3 min
(SDT)
ndby
3 sec
5 sec
10 sec
30 sec
182
160
152
140
128
110
108
400Hz
50Hz
60Hz
MPU PULSE
Note
Number of
Ring Gears
Generator
Frequency
Functions
= ETS
UVR
OCR
AFR
Notes
= ETR
ON
ENGINE STOP
: DIP S/W ON
: DIP S/W OFF
Items regarding to engine stop method among above are applied upon restart of power.
Changes in generator protection devices(OCR, UVRM AFR) are not applied when changed
during the operation of generator. In order to have thme applied you need to change them
before you press RESET button or before you change automatic/manual mode.
When there is no
power(Control power lamp
is not on)
Cause
DC circuit breaker is open
DC fuse is disconnected
Wrong wiring
Flat battery
hours
is not working)
is working)
Cannot stop
while generator in
operation
RPM meter is not working
while generator is in
operation
No automatic operation of
generator upon
commercial power outage
diagram
Recharge battery at least 5 hours
Flat battery
Solution
Wrong or no wiring of
PICKUP
diagram.
Wrong or no wiring of
PICK-UP
diagram
Wrong or no wiring in