Appendix B: Dead Load

Table B-1: Roof Level (Trusses)


Uniform Load (kPa)
Roof

0.20
0.46

Corrugated galvanized iron sheet


Total

Appendix C: Live load


Table C-1: Roof level
Uniform Load (kPa)
Roof live load (flat or rise less than
33.3% slope)
Total

0.75
0.75

Appendix D: Earthquake Load


Design Considerations
*Based on actual Geotechnical Investigation Report provided by Earthdrill
Geosystems, Inc. on June 2016
Occupancy category = IV (Standard Occupancy); Importance factor, I = 1
Seismic zone = 4; Seismic zone factor, Z = 0.4
Distance to seismic zone = 5.5 km
Seismic source type = A (active and capable of producing magnitude 7.0)
Near source factor: Na = 1.2, Nv = 1.6
Soil profile type = Sc (very dense soil and soft rock)
Seismic coefficient: Ca = 0.48Na; Cv = 0.896Nv
Ct = 0.0731 (for concrete)
Overstrength factor, R = 3.5 (ordinary RC moment frames, NSCP 2010 table 20811A)
Valley fault system
Appendix D: Wind Load
Design Considerations
*The design shall conform to Section 207 WIND LOADS of NSCP 2010
Laguna Area (zone 2)
Basic wind speed, V = 200kph

Occupancy category = IV (Standard Occupancy); Importance factor, Iw = 1


Surface roughness = C (207.5.6.2 Surface Roughness Categories, NSCP 2010)
Exposure category = C (207.5.6.3 Surface Roughness Categories, NSCP 2010)
Appendix E: Load Combinations
U = 1.4D
U = 1.2D + 1.6L
U = 1.2D + 1.0L 1.0E
U = 0.9D 1.0E
U = 1.2D + 1.6W +1.0L
Where:
D = dead load
L = live load
E = earthquake load
W = wind load