Design
RC (N)
45
35
25
45
35
25
45
35
25
Rectangular
Duct
3,500
2,500
1,700
2,500
1,750
1,200
2,000
1,450
950
Circular
Duct
5,000
3,500
2,500
4,500
3,000
2,000
3,900
2,600
1,700
Notes:
1. Branch ducts should have airflow velocities of about 80% of the values listed.
2. Velocities in final runouts to outlets should be 50% of the values or less.
3. Elbows and other fittings can increase airflow noise substantially, depending on the type.
Therefore, duct airflow velocities should be reduced accordingly.
Increased Flow
Circular vs Rectangular
1.43
1.40
1.47
1.80
1.71
1.67
1.95
1.79
1.79