Presentation
Sepam 2000
standard applications
Each Sepam 2000 is designed to fulfil all the
requirements of a given application and includes
all the necessary functions, ready for use. Simply
choose the appropriate Sepam 2000 from the list
of standard types for:
c substations,
c busbars,
c transformers,
c motors,
c capacitors,
c generators.
c
In addition to the protection and metering functions,
Sepam 2000 also includes control logic
and annunciation.
The standard control logic is adapted to suit
the usual schemes by simple parameter setting
at the time of commissioning.
This allows optimized cabling and ensures more
dependable operation (the schemes have been
rigorously tested and specified to meet the most
frequent needs).
Avantages
This capacity makes Sepam 2000 especially suitable for:
c the creation of your own protection and control unit (user standard).
This solution enables optimization of the functions on the same site
(simple management, commissioning, maintenance) or the most cost-effective
adaptation for a particular application that would otherwise have required several
devices,
c adaptation for an existing installation for revamping needs.
c adaptation to the control command and visualization of specific part of equipment.
(1)
(2)
Principle
L1
L2
L3
Sepam 2000
Control
fault
Metering
I
Protection
50
I/O
51 51N
67 67N 32P
27
59
81
boards / slots
1
2
compact S26
LT
CE40
ECM or ECA
3U / V0
ESB
ESTOR1
ESTOR2
LX
LS
SONDE
XT
3U / V0
LS
ECM or ECA(*)
ECM or ECA(*)
3U / V0
ESB
ESTOR1
ESTOR2
SONDE1
LR
ESTOR3
KZ
SONDE1
KR
ESTOR3
ZR
SONDE1
SS
3U / V0
SONDE2
SR
ESTOR3
TR
3U / V0
TS
SONDE1
XR
YR
CR
ECMD
ECMD
ESTOR3
CC
standard S36
S46
10
RR
CE40
SBW
STOR
STOR
STOR
ETOR
ETOR
NR
CE40
EANA
SBW
STOR
STOR
STOR
ETOR
XR
CE40
ECM
3V +V
SBW
STOR
STOR
STOR
ETOR
ZR
CE40
EANA
Sonde
SBW
STOR
STOR
STOR
ETOR
slot 3
ECM
ECM
ECA
ECM
ECA
ECA
ECMD
11
12
13
ETOR ETOR
ETOR
ETOR ETOR
14
ETOR
ETOR ETOR
ETOR
ETOR ETOR
ETOR
ETOR ETOR
ETOR
ETOR ETOR
ETOR
ETOR ETOR
ETOR
ETOR ETOR
CE40
: power supply.
ECM / ECMD : current inputs board (I1, I2, I3, Io) for CT.
ECA
: current inputs board (I1, I2, I3) for CSP sensors.
3U / V0
: voltage inputs board (U21, U32, U13, Vo).
ESB / ESTOR : digitale inputs and outputs boards.
3V +V: board with 4 voltage inputs (V1, V2, V3, VN),
SONDE: temperature sensor input board,
ESB: board with 2 logic inputs and 2 logic outputs,
SBW: board with 8 logic outputs,
EANA: board with 8 analog inputs,
ESTOR: board with 8 logic inputs / 4 logic outputs,
ETOR: board with 16 logic inputs,
STOR: board with 10 logic outputs.
For customized applications
ANSI code
phase overcurrent
50-51
50V-51V
metering functions
earth fault
50N-51N
phase currents
resistive earth
50G-51G
directional overcurrent
67
tripping currents
67N
residual current
67NC
thermal overload
49
frequency
negative sequence/unbalance
46
51LR
number of starts
66
phase undercurrent
37
temperatures
phase-to-phase undervoltage
27
remanent undervoltage
27
27D-47
59
residual overvoltage
59N
underfrequency
81L
overfrequency
81H
81R
real overpower
32P
reactive overpower
32Q
temperature monitoring
49T-38
motor/generator differential
87M-87G
real underpower
37P
reverse overvoltage
47
breaker failure
50BF + 62
synchro check
25
64REF
50-51
(1)
Logipam
Resources available for programming in relay language (2)
c 64 different messages on the 11-character alphanumerical display,
c internal process control relays:
v 512 relays (k1 to k512) with an unlimited number of internal NO / NC contacts,
v 60 time delays (T1 to T60),
v 24 event counters (C1 to C24),
v 128 bistable relays (B1 to B128).
c internal relays for communication:
v 96 remote controllable relays (KTC1 to KTC96),
v 64 contacts for remote signiling (KTS1 to KTS64).
c relays associated with the TSM 2001 pocket terminal
or SFT 2801 / SFT 2821 softwares:
v 64 relays which can be switched via the keyboard (KP1 to KP64).
(1)
(2)
Logipam simulator
The Logipam simulator function is used for functional testing of the diagrams during
the design phase. Simulation is carried out by:
c fictitious activation of logic inputs,
c activation of internal relays,
c continuous or step by step running of logic sequences.
The simulation results are observed by:
c fictitious activation of logic outputs,
c display of messages,
c lighting up of indicators,
c incrementation of counters.
The simulator is high-performing and easy to use, making it a very effective tool.
The schemes that are tested in this way are more reliable and substantial
adjustment time is saved.
Connection schemes
Sepam 2000 S26, S36
Logic input and output boards with connections.
Each terminal has a number reference which includes
the slot location number in Sepam 2000 (1 to 8 from right to
left).
ESB board
(2 inputs and 2 outputs)
ESB
DPC
CDG
O2
O1
l2
l1
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
(1)
ESTOR board
(8 inputs and 4 outputs)
ESTOR
DPC
"watchdog"
contacts
l18
l17
l16
l15
l14
l13
contacts dedicated
to breaking
device control
O14
O13
O12
O11
inputs with no
common point
l12
l11
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
(1)
inputs with a
common point
normaly open
output contacts
with no common
point
inputs with no
common point
(1)
The connection should be made on terminals 20 and 21 to take into account the presence
of the plugged connector in the control scheme.
Notes:
c the inputs are galvanically isolated and potential-free and require an external
power supply source.
c the input I11 or I21, (chosen by setting) is reserved for external synchronization
of the Modbus/Jbus communication option (see Modbus/Jbus communication manual).
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
SBW
DPC
CDG
O008
O007
O006
O005
O004
O003
O002
O001
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
ETOR
DPC
I116
I115
I114
I113
I112
I111
I110
I109
I108
I107
I106
I105
I104
I103
I102
I101
Notes :
c the inputs are galvanically isolated and potential-free and require an external power
supply source,
c the input I413 or I501 (chosen by setting) is reserved for external synchronization
of the Modbus/Jbus communication option (see Modbus/Jbus communication manual),
c detection of Plugged Connectors (DPC) does not require any wiring.
Communication
All Sepam 2000s may be equipped with the communication option in order
to connect Sepam 2000s to a remote monitoring and control system or central
computer equipped with a communication channel.
There are several communication option choices (please consult us).
The following data may be accessed via the communication link:
c reading of measurements,
c reading/writing of logical data (1),
c protection function settings,
c time-tagging,
c disturbance recording file.
Please refer to the Sepam 2000 communication documentation.
MERLIN GERIN
Communication between
Sepam 2000 and the remote
monitoring and control
system.
10
(1)
Notes
11
Service
Customized service
Developing electrical installations and designing monitoring and control architectures
involve not only making an efficient analysis of the requirements, but also finding
a technical and economic compromise which is the fruit of experience.
Merlin Gerin has an organization of skilled staff to help you make your choices
and confirm solutions. This team has acquired irreplaceable experience
by being confronted with a wide variety of situations.
(1)
Kirchhoff protection testing laboratory.
EMTP, MORGAT network simulation software Calculation software
(short-circuit current, dynamic stability, etc.).