Powerformer
chosen for Swedish
combined heat
and power plant
been chosen for a combined heat and power plant in Eskilstuna, Sweden.
This first commercial order for Powerformer from the thermal power sec-
tor is for a generator rated at 42 MVA, 136 kV and 3000 rev/min. It will be
neering [1].
ules 2 .
of a conventional generator.
plant.
High-voltage cables with XLPE insulation are available today for voltages of up
to 400 kV. When XLPE-insulated cables
were introduced in the 1960s there were
some initial problems with their reliability,
Lars Andersson
Biomass,
mainly
forest
and
Mats Kjellberg
Christer Parkegren
Torbjrn Srqvist
Annika Karlsson
Kre Gundersen
ABB Generation AB
19
Boiler
High-pressure steam turbine
Low-pressure steam turbine
Powerformer (high-voltage generator)
5
6
7
8
The use of HV cables offers some important advantages. Firstly, the circular
conductor geometry allows an evenly distributed electric field. This means that the
insulation material is stressed uniformly.
Secondly, the cable is designed for an
electrical field stress of 10 kV/mm, a
1
2
The use of high-voltage cables also ensures full insulation of the generator wind-
7
8
20
Powerformer generator rated 136 kV for the Eskilstuna combined heat and power plant
magnitude.
the range of 97.5 to 98.5 %; for the Eskilstuna combined CHP plant the figure is
Cooling system
design. The rotor and coil-ends are aircooled by a closed ventilation system
which uses air/water coolers to re-cool
the air. The stator core is water-cooled by
Table 1
Powerformer for Eskilstuna CHP plant: technical data
Output
Power factor
Voltage
Speed
Frequency
Cooling
rotor
end winding
stator core
Efficiency
MVA
kV
rev/min
Hz
42
0.93
136
3000
50
IC8A1W7 (air)
IC8A1W7 (air)
IC9W7W7 (water)
98.2 %
21
traditional
generator
breaker,
with
Conventional plant
utility 4 :
(%)
100
44
7
26
5
22
11
Not evaluated
Not evaluated
Not evaluated
100
115
Conditions:
interest rate
operating hours
life-cycle
loss evaluation
6%
5000 pa
20 years
USD 25/MWh
less maintenance.
plant.
electrical package
Fewer components
year.
Not only the active losses are reduced.
A step-up transformer also consumes
reactive power; since the step-up trans-
Table 3
Powerformer for thermal power (output range 20200 MW)
Output
Voltage
Speed
Frequency
Drive
MW
20200
kV
25250
rev/min
3000/3600
Hz
50/60
Steam turbine/gas turbine
Single-end drive/double-end drive
22
136kV
136kV
4
9
3
advantages.
15 percent
11kV
1
2
3
etc.
5
6
7
8
9
Authors
for 20 to 200 MW
Lars Andersson
Reference
Christer Parkegren
Torbjrn Srqvist
Annika Karlsson
2/98, 2126.
Kre Gundersen
ABB Generation AB
S-721 76 Vsters
Sweden
Telefax: +46 21 41 95 77
E-mail:
20200
mats.kjellberg@segen.mail.abb.com
MW
and
with
voltages
of
23