REINFORCED CONCRETE DESIGN

Ref

Calculation
Design of slab for Residence Area on Second Floor
Durability and fire resistance
Nominal cover for very moderate conditions of exposure = 25mm
Nominal cover for 1.5 hours fire resistance = 20mm
Since 25>20, provide nominal cover = 25mm
Therefore durability and fire resistance are satisfactory.
Preliminary sizing of Slab

SLAB SKETCH

Basic span/ effective depth (d) <26*1=26 Modification factor =1


d>span /26
Minimum effective depth = 3800/26 =146.15mm
Assuming R12 bars D = d + concrete cover+ (bar diameter/2)
D = 146.15 + 25 + 6 =177.15mm
Choose D = 150mm
Therefore, d1 = 150-25-6 =119mm
d2 = 150-25-6-12 = 107mm

Table
3.14

Loading
Self weight of slab = conc. *0.150
= 24 *0.150 = 3.60KN/m2
Ceilings and floors = 0.5KN/m2
Walls and partitions = 1KN/m2
Total Dead load = (3.60+0.5+1)KN/m2 Gk =5.10KN/m2
Imposed load = 3.0KN/m2

Design load, n = 1.4Gk + 1.6Qk


n= 11.94KN/m2
For a unit width n = 11.94KN/m

Qk= 3.0KN/m2

Output

Hence the slab is a two way with three edges continuous.


Short Span
Mx =xnLx2
=0.062*11.94*3.82 =10.68KNm(hogging)
Mx = xnLx2
= 0.045*11.94*3.82 =7.76KNm(sagging)
Long Span
2
My =ynLx
=0.014*11.94*3.82 =2.41KNm(hogging)
My = ynLx2
= 0.010*11.94*3.82 =1.72KNm(sagging)
Reinforcement Analysis
K=Ms/bd2 fcu
K=10.68*106/(1000*1492*30)
=0.016<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.016/0.9)1/2]
Z=0.98d , choose Z=0.95d
Area of Steel(Hogging)
As = Mx/0.95fyZ
=10.68*106/(0.952*119*250)
As=397.7mm2
Provide 24R12@275c/c(411mm2) Top

No comp.
required

Ref

REINFORCED CONCRETE DESIGN


Calculations
As = My/0.95fyZ
=2.41*106/(0.952*107*250)
As=99.8mm2
Provide 14R12@300c/c(376mm2) Top
Area of Steel (Sagging)
As = Mx/0.95fyZ
=7.76*106/(0.952*119*250)
As=289.0mm2
Provide 22R12@300c/c(376mm2) bottom
As = My/0.95fyZ
=1.72*106/(0.952*107*250)
As=71.2mm2
Provide 14R12@300c/c(376mm2) bottom

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

BS 8110
Steel Area Check
1997
Short span
Table
3.27
Allowable steel Area As:
0.24% bd < As < 4%bd
0.24% *1000*150 < 376 mm2 < 4% *1000*150
360 mm2 < 376 mm2 <6000mm2
Area of steel provided is satisfactory.

Output

As
satisfactory

Long span
Allowable steel Area As:
0.24% bd < As < 4%bd
0.24% *1000*107 < 376 mm2 < 4% *1000*107
256.8mm2 < 376 mm2 <4280mm2
Area of steel provided is satisfactory.
BS 8110
Cracking Check
3.1211.2 Maximum clear distance between bars in tension <3d or 750
Short span
3*119 = 357mm
Maximum clear distance between bars in tension =300-12 =
288mm<750mm
Therefore cracking width is satisfactory.
Long span
3*107 =321mm
Maximum clear distance between bars in tension =300-12 =
288mm<750mm
Therefore cracking width is satisfactory.
BS8110
Table
3.16

Shear check
If depth of slab is<200mm no shear reinforcement is required.
Depth of slab =180mm<200mm
Therefore provide no shear reinforcement.

Cracking
width o.k

No shear
rnft required

REINFORCED CONCRETE DESIGN


Calculations

Ref
BS
8110
Table
3.10
Eq 7.0

Output

Deflection Check
Short span
Actual span/ d should not be greater than allowable span/d
Actual span/d =3800/119 =32.0
Allowable span/d = modification factor (Mf)*26
Mf= 0.55+(477- fs) / 120(0.9+ (M/bd2)) less or equal to 2
M/bd2= 10.68 *106/1000*1192 =0.75
Design stress fs = 2fy Asreq./ 3Asprov.
fs=( 2*250*397.7) / (3*411)
fs= 161.27
Therefore , Mf = 0.5
Hence select Mf = 0.5 , (0.5*26=13)
Also; 32>13
Deflection is not within limits

Mf =1 is
good

Long span
Actual span/ d should not be greater than allowable span/d
Actual span/d =6300/107=58.87
Allowable span/d = modification factor (Mf)*26
Mf= 0.55+(477- fs) / 120(0.9+ (M/bd2)) less or equal to 2
M/bd2= 1.72*106/1000*1072=0.15
Design stress fs = 2fy Asreq./ 3Asprov.
fs=(2*250*71.2)/(3*376)
fs= 31.56
Therefore , Mf = 3.54
Hence select Mf = 3.54 , (3.54*26=92.04)
Also; 58.87<92.04
Deflection is within limits

Mf=3.5 is
better

Ref

REINFORCED CONCRETE DESIGN


Calculations
DETAIL SLAB DRAWING

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations
Design of slab for counselors Apartment

SLAB SKETCH

Durability and fire resistance


Nominal cover for very moderate conditions of exposure = 25mm
Nominal cover for 1.5 hours fire resistance = 20mm
Since 25>20, provide nominal cover = 25mm
Therefore durability and fire resistance are satisfactory.
Preliminary Sizing of slab
Basic span/ effective depth (d) <26*1=26 Modification factor =1
d>span /26
Minimum effective depth = 3800/26 =146.15mm
Assuming R12 bars D = d + concrete cover+ (bar diameter/2)
D = 146.15 + 25 + 6 =177.15mm
Choose D = 150mm
Therefore, d1 = 150-25-6 =119mm
d2 = 150-25-6-12 = 107mm
Loading
Self weight of slab = conc. *0.180
= 24 *0.150 =3.6KN/m2
Ceilings and floors = 0.5KN/m2
Walls and partitions = 1KN/m2
Total Dead load = (3.6+0.5+1)KN/m2 Gk =5.1KN/m2
Imposed load = 3.0KN/m2
Qk= 3.0KN/m2

Output

Design load, n = 1.4Gk + 1.6Qk


n= 11.94KN/m2
For a unit width n = 11.94KN/m
Hence the slab is a two way with three edges continuous.
Short Span
Mx =xnLx2
=0.082*11.94*3.82 =14.48KNm(hogging)
Mx = xnLx2
= 0.062*11.94*3.82 =10.69KNm(sagging)
Long Span
My =ynLx2
=0.016*11.94*3.82 =2.75KNm(hogging)
My = ynLx2
= 0.012*11.94*3.82 =2.07KNm(sagging)
Reinforcement Analysis
K=Ms/bd2fcu
K=14.48*106/(1000*1192*30)
=0.034<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.034/0.9)1/2]
Z=0.97d , choose Z=0.95d
Area of Steel(Hogging)
As = Mx/0.95fyZ
=14.48*106/(0.952*119*250)
As=539.3mm2
Provide 33R12@200c/c(565mm2) Top

No comp.
Required

Ref

REINFORCED CONCRETE DESIGN


Calculations
Reinforcement Analysis
K=Ms/bd2fcu
K=2.75*106/(1000*1072*30)
=0.008<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.008/0.9)1/2]
Z=0.99d , choose Z=0.95d
As = My/0.95fyZ
=2.75*106/(0.952*107*250)
As=113.9mm2
Provide 14R12@300c/c(376mm2) Top
Area of Steel (Sagging)
As = Mx/0.95fyZ
=10.67*106/(0.952*119*250)
As=397.4mm2
Provide 24R12@275c/c(411mm2) bottom
As = My/0.95fyZ
=2.07*106/(0.952*107*250)
As=85.74mm2
Provide 14R12@300c/c(376mm2) bottom

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations
DETAIL SLAB DRAWING

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

BS 8110
Steel Area Check
1997
Short span
Table
3.27
Allowable steel Area As:
0.24% bd < As < 4%bd
0.24% *1000*150 < 376 mm2 < 4% *1000*150
360 mm2 < 376 mm2 <6000mm2
Area of steel (As) provided is satisfactory.

Output

As
satisfactory

Long span
Allowable steel Area As:
0.24% bd < As < 4%bd
0.24% *1000*107 < 376 mm2 < 4% *1000*107
256.8 mm2 < 376 mm2 <4280mm2
Area of steel provided is satisfactory.
BS 8110
Cracking Check
3.1211.2 Maximum clear distance between bars in tension <3d or 750
Short span
3*119 = 357mm
Maximum clear distance between bars in tension =300-12 =
288mm<750mm
Therefore cracking width is satisfactory.
Long span
3*107 =321mm
Maximum clear distance between bars in tension =300-12 =
288mm<750mm
Therefore cracking width is satisfactory.
BS8110
Table
3.16

Shear check
If depth of slab is<200mm no shear reinforcement (rnft) is
required. Depth of slab =180mm<200mm
Therefore provide no shear reinforcement.

Cracking
width ok

No shear
rnft required

REINFORCED CONCRETE DESIGN


Calculations

Ref
BS
8110
Table
3.10
Eq 7.0

Output

Deflection Check
Short span
Actual span/ d should not be greater than allowable span/d
Actual span/d =3800/119 =31.9
Allowable span/d = modification factor (Mf)*26
Mf= 0.55+(477- fs) / 120(0.9+ (M/bd2)) less or equal to 2
M/bd2= 14.48 *106/1000*1192 =1.02
Design stress fs = 2fy Asreq./ 3Asprov.
fs=( 2*250*565) / (3*376)
fs= 250.4
Therefore , Mf = 0.98
Hence select Mf = 0.98 , (0.98*26=25.48)
Also; 31.9>25.48
Deflection is not within limits
Long span
Actual span/ d should not be greater than allowable span/d
Actual span/d =6300/107=58.87
Allowable span/d = modification factor (Mf)*26
Mf= 0.55+(477- fs) / 120(0.9+ (M/bd2)) less or equal to 2
M/bd2= 2.75*106/1000*1072=0.24
Design stress fs = 2fy Asreq./ 3Asprov.
fs=(2*250*113.9)/(3*376)
fs= 50.48
Therefore , Mf = 3.12
Hence select Mf = 3 , (3.0*26=78)
Also; 58.87<78
Deflection is within limits

Mf=1.0

Ref

REINFORCED CONCRETE DESIGN


Calculations

Design of Slab in the Corridor

Durability and fire resistance


Nominal cover for very moderate conditions of exposure = 25mm
Nominal cover for 1.5 hours fire resistance = 20mm
Since 25>20, provide nominal cover = 25mm
Therefore durability and fire resistance are satisfactory.
Preliminary Sizing of slab
Ly/Lx = 47600/2600
= 18.30>2.0
Hence slab is designed as a one way.
Basic span/ effective depth (d) <26*1=26 Modification factor =1
d>span /26
Minimum effective depth = 3800/26 =146.15mm
Assuming R12 bars D = d + concrete cover+ (bar diameter/2)
D = 146.15 + 25 + 6 =177.15mm
Choose D = 150mm
Therefore, d1 = 150-25-6 =119mm
d2 = 150-25-6-12 = 107mm
Loading
Self weight of slab = conc. *0.150
= 24 *0.150 = 3.6KN/m2
Ceilings and floors = 0.5KN/m2
Walls and partitions = 1KN/m2
Total Dead load = (3.6+0.5+1)KN/m2 Gk =5.1KN/m2
Imposed load = 3.0KN/m2

Qk= 3.0KN/m2

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations
Moment at mid span Mx = nLx2
8
= 11.34*2.62 = 9.58KN/m
8
Fixed end moment Mx2= nLx2
12
= 11.34*2.62 = 6.38KN/m
12
Reinforcement Analysis
K=Ms/bd2fcu
K=9.58*106/(1000*1192*30)
=0.00225<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.00225/0.9)1/2]
Z=0.98d , choose Z=0.95d
As = Mx/0.95fyZ
=9.58*106/(0.952*119*250)
As=356.8mm2
Provide 160R12@300c/c(376mm2) top
K=Ms/bd2fcu
K=6.38*106/(1000*1072*30)
=0.018<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.018/0.9)1/2]
Z=0.98d , choose Z=0.95d
As = My/0.95fyZ
=2.24*106/(0.952*107*250)
As=224049mm2
Provide 10R12@300c/c(376mm2) top

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

Reinforcement Analysis
K=Ms/bd2fcu
K=10.94*106/(1000*1492*30)
=0.00164<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=149[0.5 +(0.25-0.00164/0.9)1/2]
Z=0.98d , choose Z=0.95d
As = Mx/0.95fyZ
=10.94*106/(0.95*149*250)
As=309.148mm2
Provide 160R12@300c/c(376mm2) bottom
K=Ms/bd2fcu
K=6.38*106/(1000*1072*30)
=0.018<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.018/0.9)1/2]
Z=0.98d , choose Z=0.95d
As = My/0.95fyZ
=6.38*106/(0.952*107*250)
As=264.3mm2
Provide 10R12@300c/c(376mm2) bottom

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

DESIGN OF
ROOF BEAM

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

Output

Design of roof beam on grid O-O

1.05KN/m roof loading


6.3m

Part
1
1997
Tabl
e 3.2
&3.3

2.3m

Cover
=25mm

6.3m

Durability and fire resistance


Nominal cover for very moderate conditions of exposure = 25mm
Nominal cover for 1.5 hours fire resistance = 20mm
Since 25>20, provide nominal cover = 25mm
Therefore durability and fire resistance are satisfactory.
Preliminary Sizing of Beam

Basic span/ effective depth (d) <26*1=26 Modification factor =1


d>span /26
Minimum effective depth = 6300/26 =242.3mm
Assuming R12 bars D = d + concrete cover+ (bar diameter/2)
D = 242.3 + 25 + 6 =273.3mm
Design decisions
Choose D = 450mm
Chart Choose R8 as links bar
Choose R12 as reinforcement bar
7
Therefore, d1 = 450-25-6-8=411mm
Loading
Self weight of the beam= conc. *0.450
= 24*.450 =10.8KN/m2
Assumed loading from the roof = 1.05KN/m

D
=450mm
b=
300mm
d1=411m
m

Total dead weight = (10.8+1.05)=11.85 KN/m2


Total dead weight per span (A1)=11.85/6.3 =1.88KN/m
Total dead weight per span (A2)=11.85/2.3 =5.15KN/m
Total dead weight per span (A3)=11.85/6.3 =1.88KN/m
Imposed load per meter span =0.75*6.3 =4.725KN/m
Design loads
Design load n= 1.4Gk+1.6Qk
Span 6.3m n1= (1.4*1.88)+(1.6*4.725) =10.19 KN/m
Span 2.6m n2= (1.4*5.15)+(1.6*4.725) =14.77KN/m
Span 6.3m n3= (1.4*1.88)+(1.6*4.725) =10.19 KN/m

NB: the calculation and distribution of loads was done with a


program Beamax

Ref

REINFORCED CONCRETE DESIGN


Calculations
Support reinforcement
Maximum Hogging moment=20.54KNm
K=Ms/bd2fcu
K=20.54*106/(300*4112*30)
=0.0014<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.0014/0.9)1/2]
Z=0.98d , choose Z=0.95d
As = My/0.87fyZ
=20.54*106/(0.87*0.95*411*250)
As=241.86m2
Provide 3R12(339.3mm2)bottom
Mid span reinforcement
Maximum sagging moments=15.57KNm
K=Ms/bd2fcu
K=15.57*106/(300*4112*30)
=0.0102<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.0102/0.9)1/2]
Z=0.98d , choose Z=0.95d
As = Ms/0.87fyZ
=15.57*106/(0.87*0.95*411*250)
As=183.34mm2
Provide 3R12(339.3mm2) top

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations
Support reinforcement
Maximum Hogging moment=26.8KNm
K=Ms/bd2fcu
K=26.8*106/(300*4112*30)
=0.017<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.017/0.9)1/2]
Z=0.98d , choose Z=0.95d
As = My/0.87fyZ
=26.8*106/(0.87*0.95*411*250)
As=315.58mm2
Provide 3R12(339.3mm2) bottom

Output

REINFORCED CONCRETE DESIGN


Calculations

Ref
BS
8110
1997
3.12.61
Table
3.27

Steel Area Check


Allowable steel Area As:
0.24% bd < As < 4%bd
0.24% *300*450 < 339.6 mm2 < 4% *300*450
324 mm2 < 339.6mm2 <5400mm2
Area of steel (As) provided is satisfactory.

Output

As is
satisfactory

Shear Check
BS 8110
Table
3.7

Maximum shear =35.19KN


Actual shear v =V/bd
v = 35. 19*103/(411*300)
v =0.285N/mm2
but v<0.8fcu1/2 =4.38N/mm2
therefore ultimate shear is avoided
shear reinforcement
Vc=[0.79*(100As/bd)1/3*(400/d)1/4]/Ym
Vc=[0.79*(100*339.3/411*300)1/3*(400/411)1/4]/1.25
Vc =0.47
0.5Vc<v<Vc+0.4
0.24<0.285<0.64
Above condition is satisfied
Therefore no shear reinforcement is required
Hence the minimum no. of links for the length of the beam is
provided.
Asv=2*R2/4
= 2**8*2
Asv=201.088mm2
Sv< (Asv*.95fy/0.4d)
Sv< (201.088*.95*250/0.4*411)
Sv<290.5
Therefore provide R8 links @250c/c

No shear
Rnft
required
Asv=201.08

Ref

REINFORCED CONCRETE DESIGN


Calculations

Output

Deflection Check
BS
8110
Table
3.10
Eq
7.0

Actual span/ d should not be greater than allowable span/d


Actual span/d =6300/411 =15.32
Allowable span/d = modification factor (Mf)*26
Mf= 0.55+(477- fs) / 120(0.9+ (M/bd2)) less or equal to 2
M/bd2= 20.54 *106/300*4112 =0.41
Design stress fs = 2fy Asreq./ 3Asprov.
fs=( 2*250*248.6) / (3*339.3)
fs= 122.1
Therefore , Mf = 2.26
Hence select Mf = 2.0, (2.0*26=52)
Also; 15.32<52
Mf=2.0
Deflection is within limits
Detailed Roof beam

Ref

REINFORCED CONCRETE DESIGN


Calculations
Continuous Roof beam grid A,B,C,D

1.05KN/m Roof loading

Durability and fire resistance


Nominal cover for very moderate conditions of exposure = 25mm
Nominal cover for 1.5 hours fire resistance = 20mm
Since 25>20, provide nominal cover = 25mm
Therefore durability and fire resistance are satisfactory.
Preliminary Sizing of Beam
Basic span/ effective depth (d) <26*1=26 Modification factor =1
d>span /26
Minimum effective depth = 3800/26 =146.15mm
Assuming R12 bars D = d + concrete cover+ (bar diameter/2)
D = 146.15 + 25 + 6 =177.15mm
Design decisions
Choose D = 450mm
Choose R8 as links bar
Choose R12 as reinforcement bar
Therefore, d1 = 450-25-6-8=411mm
Loading
Self weight of the beam= conc. *0.450
= 24*.450 =10.8KN/m2
Assumed loading from the roof = 1.05KN/m2
Total dead weight = (10.8+1.05)=11.85 KN/m2
Total dead weight per span (A)=11.85/3.8 =3.12KN/m
Total dead weight per span (B)=11.85/3.8 =3.12KN/m
Total dead weight per span (C)=11.85/3.8 =3.12KN/m
Total dead weight per span (D)=11.85/3.8 =3.12KN/m

Output

Imposed load per meter span =0.75*3.8=2.85KN/m

Design loads
Design load n= 1.4Gk+1.6Qk
Span 3.8m nA= (1.4*3.12)+(1.6*2.85) =8.928KN/m
Span 3.8m nB= (1.4*3.12)+(1.6*2.85) =8.928KN/m
Span 3.8m nC= (1.4*3.12)+(1.6*2.85) =8.928KN/m
Span 3.8m nD= (1.4*3.12)+(1.6*2.85) =8.928KN/m

Maximum Bending and Shear Force diagrams

Ref

REINFORCED CONCRETE DESIGN


Calculations
Support reinforcement
Maximum Hogging moment from Bending moment diagram
=5.37KNm
K=Ms/bd2fcu
K=5.37*106/(300*4112*30)
=0.0035<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.0035/0.9)1/2]
Z=0.99d , choose Z=0.95d
As = My/0.87fyZ
=5.37*106/(0.87*0.95*411*250)
As=63.2mm2
Provide 3R12(339.3mm2) bottom
Mid span reinforcement
Maximum sagging moments=10.75KNm
K=Ms/bd2fcu
K=10.75*106/(300*4112*30)
=0.0071<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.0071/0.9)1/2]
Z=0.99d , choose Z=0.95d
As = Ms/0.87fyZ
=10.75*106/(0.95*0.87*411*250)
As=126.58mm2
Provide 3R12(339.3mm2) top

Output

REINFORCED CONCRETE DESIGN


Calculations

Ref

Output

Steel Area Check


BS
8110
1997
Table
3.27

BS 8110
Table
3.7

Allowable steel Area As:


0.24% bd < As < 4%bd
0.24% *300*450 < 339.3mm2 < 4% *300*450
324 mm2 < 339.3 mm2 <5400mm2
Area of steel (As) provided is satisfactory.

As is
satisfactory

Shear Check
Maximum shear =16.97KN
Actual shear v =V/bd
v = 16.97*103/(411*300)
v =0.13N/mm2
but v<0.8fcu1/2 =4.38N/mm2
therefore ultimate shear is avoided
shear reinforcement
Vc=[0.79*(100As/bd)1/3*(400/d)1/4]/Ym
Vc=[0.79*(100*339.3/411*300)1/3*(400/411)1/4]/1.25
Vc =0.058
0.5Vc<v<Vc+0.4
0.0028<0.13<0.458
Above condition is satisfied
Therefore no shear reinforcement is required
Hence the minimum no. of links for the length of the beam is
provided.
Asv=2*R2/4
= 2**8*2
Asv=201.088mm2
Sv< (Asv*.95fy/0.4d)
Sv< (201.088*.95*250/0.4*411)
Sv<290.5
Therefore provide R8 links @250c/c

No shear
Rnft
required
Asv=201.08

Ref
BS
8110
Table
3.10
Eq
7.0

REINFORCED CONCRETE DESIGN


Calculations
Deflection Check
Actual span/ d should not be greater than allowable span/d
Actual span/d =3800/411 =9.25
Allowable span/d = modification factor (Mf)*26
Mf= 0.55+(477- fs) / 120(0.9+ (M/bd2)) less or equal to 2
M/bd2= 5.37 *106/300*4112 =0.106
Design stress fs = 2fy Asreq./ 3Asprov.
fs=( 2*250*63.4) / (3*339.3)
fs= 31.14
Therefore , Mf = 3.5
Hence select Mf = 3.5 , (3.5*26=91)
Also; 9.25<91
Deflection is within limits
Detailed Roof beam

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

DESIGN
OF FLOOR BEAM

Output

REINFORCED CONCRETE DESIGN


Calculations

Ref

Design of beam on grid E-E to J-J

bf
A1
3800mm

A2
3800mm

A3
3800mm

A4

hf

3800mm
D d

bw

Area of A1 between grid lines E-F


B=3.8m h= tan45o *3.8/2 =1.9m
A1 = *b*h
= *3.8*1.9 =3.61m2
But A1=A2=A3=A4=3.61m2
Durability and fire resistance
Nominal cover for very moderate conditions of exposure = 25mm
Nominal cover for 1.5 hours fire resistance = 20mm
Since 25>20, provide nominal cover = 25mm
Therefore durability and fire resistance are satisfactory.

Preliminary Sizing of T-Beam


Interpolating for span to depth ratio
(26-R)/(1-X)= (20-16)/(1-0.3)
X =bw/bf =0.35/0.9=0.38
R=20-3.1976
R=16.464
Span/depth <16.464
3800/16.46 <D
D>230.86mm

Output

Design decisions
Choose D = 450mm
Choose R8 as links bar
Choose R12 as reinforcement bar
Therefore, d1 = 450-25-6-8=411mm
h1=150mm
bw=350mm
bf <bw+1/5(0.7*effective span)
bf <0.35+1/5(0.7*3.8)
bf <0.35+0.532
bf=900mm

REINFORCED CONCRETE DESIGN


Calculations

Ref

Output

Loadings
Dead loads:
Self weight of slab= (3.61*0.15*24)/3.8
=3.42KN/m
Self weight of beam =(0.45-.15)*24*.35 =2.52KN/m
Weight of walls and furnishes= (3.61*3)/3.8 =1.425KN/m
Total dead weight = 3.42+2.52+1.425=7.37KN/m

Gk=7.37

Imposed load = (3*3.61)/3.8 =2.85KN/m

Qk =2.85

NB: since all the beams have the same area n1=n2=n3=n4=n
Ultimate moment n=1.4Gk+1.6Qk
N= (1.4*7.37)+(1.6*2.85)=14.87KN/m
n1=n2=n3=n4=n=14.871KN/m

beaming moment and shear force diagram 1

maximum sagging moment =8.95KNm


maximum Hogging moment =17.89KNm

n=14.871
KN/m

Ref

REINFORCED CONCRETE DESIGN


Calculations
Mid span reinforcements
maximum sagging moment =8.95KNm
K=Ms/bFd2fcu
K=8.95*106/(900*4112*30)
=0.00196<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.00196/0.9)1/2]
Z=0.99d , choose Z=0.95d
As = My/0.87fyZ
=8.95*106/(0.87*0.95*411*250)
As=105.27mm2
Provide 2R12(226.2mm2) bottom
Maximum hogging=17.89KNm
K=Ms/bFd2fcu
K=17.89*106/(900*4112*30)
=0.0039<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.0039/0.9)1/2]
Z=0.99d , choose Z=0.95d
As = Mx/0.87fyZ
=17.89*106/(0.87*0.95*411*250)
As=105.27mm2
Provide 2R12(226.2mm2) top

Output

REINFORCED CONCRETE DESIGN


Calculations

Ref
BS
8110
1997
3.12.61
Table
3.27

BS 8110
Table
3.7

Steel Area Check


Allowable steel Area As:
0.24% bd < As < 4%bd
0.24% *350*450 < 226.2mm2 < 4% *350*450
378 mm2 < 226.2 mm2 <5400mm2
Area of steel (As) provided not is satisfactory.

Shear Check
Maximum shear =28.25KN
Actual shear v =V/bd
v = 28.25*103/(411*350)
v =0.196N/mm2
but v<0.8fcu1/2 =4.38N/mm2
therefore ultimate shear is avoided
shear reinforcement
Vc=[0.79*(100As/bd)1/3*(400/d)1/4]/Ym
Vc=[0.79*(100*226.2/411*350)1/3*(400/411)1/4]/1.25
Vc =0.338
0.5Vc<v<Vc+0.4
0.1696<0.196<0.738
Above condition is satisfied
Therefore no shear reinforcement is required
Hence the minimum no. of links for the length of the beam is
provided.
Asv=2*R2/4
= 2**8*2
Asv=201.088mm2
Sv< (Asv*.95fy/0.4d)
Sv< (201.088*.95*250/0.4*411)
Sv<290.5
Therefore provide R8 links @250c/c

Output

REINFORCED CONCRETE DESIGN


Calculations

Ref
BS
8110
Tabl
e
3.10
Eq
7.0

Deflection Check
Actual span/ d should not be greater than allowable span/d
Actual span/d =3800/411 =9.25
Allowable span/d = modification factor (Mf)*26
Mf= 0.55+(477- fs) / 120(0.9+ (M/bd2)) less or equal to 2
M/bd2= 8.25 *106/350*4112 =0.139
Design stress fs = 2fy Asreq./ 3Asprov.
fs=( 2*250*105.27) / (3*226.2)
fs= 77.56
Therefore , Mf = 3.2
Hence select Mf = 3.2 , (3.2*26=83.41)
Also; 9.25<83.41
Deflection is within limits
Detailed of beam

01

2R12
15R8@250c/c

15R8@250c/c

2R12

3800mm

3800mm

3800mm

01

900mm
150mm

/c

450mm

0c
25
8@

25cover

Output

REINFORCED CONCRETE DESIGN


Calculations

Ref

Output

Design of beam on grid 1-1 to4-4 of the 1st floor

01

03

02

A1
6300mm

A2
2300mm

04

A3
6300mm

bf
hf

D
d

L-BEAM SECTION
bw

Area of A1 between grid lines 1-1 and 2-2


A1 = *h(a+b)
a=6.3m b=1.26m h= tan45o *3.8/2 =1.9m
A1 = *1.9(6.3+1.26) =7.182m2
But area (A1=A3) therefore A3=7.182m2
A2 is between grid 2-2 and 3-3
A2 = *b*h
= *2.3*1.9 =2.185m2
Durability and fire resistance
Nominal cover for very moderate conditions of exposure = 25mm
Nominal cover for 1.5 hours fire resistance = 20mm
Since 25>20, provide nominal cover = 25mm
Therefore durability and fire resistance are satisfactory.

A1=7.182m2
A3=7.182m2
A2=2.185m2

Preliminary Sizing of L-Beam


Interpolating for span to depth ratio
(26-R)/(1-X)= (20-16)/(1-0.3)
X =bw/bf =0.35/0.45=0.77
R=20-3.1976
R=24.686
Span/depth <24.686
6300/24.686 <D
D>255.20mm
Design decisions
Choose D = 450mm
Choose R8 as links bar
Choose R12 as reinforcement bar
Therefore, d1 = 450-25-6-8=411mm
h1=150mm
bw=350mm
bf <bw+1/10(0.7*effective span)
bf <0.35+1/10(0.7*6.3)
bf <0.35+.441, bf<0.79m
bf=450mm

REINFORCED CONCRETE DESIGN


Calculations

Ref

Output

Loadings
Dead loads:
Self weight of slab= (7.182*0.15*24)/6.3
=4.104KN/m
Self weight of beam =(0.45-.15)*24*.35 =2.52KN/m
Weight of walls and furnishes= (7.182*1.5)/6.3 =1.71KN/m
Total dead weight = 3.42+1.71+4.104=9.13KN/m
Imposed load
Imposed load = (3*7.182)/6.3 =3.42KN/m
Ultimate moment n=1.4Gk+1.6Qk
N1= (1.4*9.13)+(1.6*3.42)=18.26KN/m
However N3=18.26

N1=18.26
N3=18.26

Dead loads:
Self weight of slab= (2.185*0.15*24)/2.3
=3.42KN/m
Self weight of beam =(0.45-.15)*24*.35 =2.52KN/m
Weight of walls and furnishes= (2.185*1.5)/2.3 =1.425KN/m
Total dead weight = 3.42+2.52+1.425=7.364KN/m
Imposed load
Imposed load = (3*2.185)/2.3=2.85KN/m
Ultimate moment n=1.4Gk+1.6Qk
N2= (1.4*7.364)+(1.6*2.85)=14.87KN/m

N2=14.87

beaming moment and shear force diagram 2

Ref

REINFORCED CONCRETE DESIGN


Calculations
Mid span reinforcements
maximum sagging moment =36.68KNm
K=Ms/bFd2fcu
K=36.68*106/(450*4112*30)
=0.0016<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.0016/0.9)1/2]
Z=0.98d , choose Z=0.95d
As = My/0.87fyZ
=36.68*106/(0.87*0.95*411*250)
As=431.92mm2
Provide 4R12(452.4mm2) bottom
Maximum hogging=27.84KNm
K=Ms/bFd2fcu
K=27.84*106/(450*4112*30)
=0.0122<0.156
There is no compression reinforcement needed
Lever arm
Z=d[0.5 +(0.25-K/0.9)1/2]
Z=d[0.5 +(0.25-0.0122/0.9)1/2]
Z=0.98d , choose Z=0.95d
As = Mx/0.87fyZ
=27.84*106/(0.87*0.95*411*250)
As=327.8mm2
Provide 3R12(339.3mm2) top

Output

REINFORCED CONCRETE DESIGN


Calculations

Ref
BS
8110
1997
3.12.61
Table
3.27

Steel Area Check


Allowable steel Area As:
0.24% bd < As < 4%bd
0.24% *350*450 < 339.3 mm2 < 4% *350*450
378 mm2 < 339.3 mm2 <5400mm2
Area of steel (As) provided is satisfactory.

Shear Check
BS 8110
Table
3.7

Maximum shear =62.92KN


Actual shear v =V/bd
v = 62.92*103/(411*350)
v =0.44N/mm2
1/ 2
but v<0.8fcu =4.38N/mm2
therefore ultimate shear is avoided
shear reinforcement
Vc=[0.79*(100As/bd)1/3*(400/d)1/4]/Ym
Vc=[0.79*(100*339.3/411*350)1/3*(400/411)1/4]/1.25
Vc =0.095
0.5Vc<v<Vc+0.4
0.22<0.44<0.495
Above condition is satisfied
Therefore no shear reinforcement is required
Hence the minimum no. of links for the length of the beam is
provided.
Asv=2*R2/4
= 2**8*2
Asv=201.088mm2
Sv< (Asv*.95fy/0.4d)
Sv< (201.088*.95*250/0.4*411)
Sv<290.5
Therefore provide R8 links @250c/c

Output

REINFORCED CONCRETE DESIGN


Calculations

Ref
BS
811
0
Tabl
e
3.10
Eq
7.0

Deflection Check
Actual span/ d should not be greater than allowable span/d
Actual span/d =6300/411 =15.32
Allowable span/d = modification factor (Mf)*26
Mf= 0.55+(477- fs) / 120(0.9+ (M/bd2)) less or equal to 2
M/bd2= 27.84 *106/350*4112 =0.47
Design stress fs = 2fy Asreq./ 3Asprov.
fs=( 2*250*327.8) / (3*339.3)
fs= 161.02
Therefore , Mf = 1.9
Hence select Mf = 1.9 , (1.9*26=50.06)
Also; 15.32<50.06
Deflection is within limits
Detailed of beam

2
6300mm

3
2300mm
K

6300mm

3R12
25R8@250c/c

9R8@250c/c

25R8@250c/c
3R12

K
300mm

450mm

SECTION K-K

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

COLUMN
DESIGN

Output

REINFORCED CONCRETE DESIGN


Calculations

Ref

Output

Design of column on gridline A1


BS
8110
part
1
1997
Tabl
e 3.3

Durability and fire resistance


Nominal cover for very moderate conditions of exposure = 25mm
Nominal cover for 1.5 hours fire resistance = 20mm
Since 25>20, provide nominal cover = 25mm
Therefore durability and fire resistance are satisfactory.

Cover=25
mm

Preliminary column sizing


Column is braced due to the presence of walls to resist lateral loads.
Choose cross sectional area of column =300mm*450mm
Width of column =300mm
Depth of cross section of column = 450mm
Clear height between end restraints =3075mm
Lo
=3075mm
Design Decision
Column sizing =300mm*450mm
Stirrup diameter = R8mm

450mm

3075mm

2nd
Floor

150mm
300mm
3075mm

1st
Floor

150mm
300mm
4200mm

Ground
Floor

150mm
Below
Ground
Floor
300mm

A SKETCH OF
A TYPICAL
COLUMN
SECTION

REINFORCED CONCRETE DESIGN


Calculations

Ref
`

Column Design Analysis


Clear height of second floor column= 3075mm
End Conditions
Condition at top
End of column is connected monolithically to beams on either side and
are at least as deep as the overall dimension of the column.
D=450mm b=300mm
End condition at top=1.0
Condition at the bottom
End of column is connected monolithically to beams on either side and
are at least as deep as the overall dimension of the beam. D=450mm
b=300mm. the end condition at bottom is=1
Beta() =075 (braced column)
Effective height of column Le= Lo
Le =075*3075
Le = 2306.25mm
Lex = effective height in respect of the major axis
Ley = effective height in respect of the minor axis
Lex=Ley= 2306.25mm
Lex/b =2306.25/300 =7.69<15
Ley/h =2306.25/450 =5.125<15
Hence the column is designed as a short braced axially loaded column.
Loading of column

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations
Loading of column due ot beam A1
N1= *(6.3*10.8)=34.02KN
Loading on column due to beam A2
N2= *8.33*3.8=15.827KN
Self weight of column
N3= (0.3*0.45*24*3.075)*1.4=13.95KN
Total axial load on second floor=(13.95+15.827+34.02)=63.80KN

BS
8110
Part 1
1997
Clause
3.8.4.3

Output

N=63.80KN

Design of second floor column


Total axial load =63.80KN
N=0.4fcuAc+0.75fyAsc
For rectangular column to allow for the area of concrete displayed
by longitudinal reinforcement.
Modified formula N =0.4fcubh +Asc(0.75fy-0.4fcu)
Ac is the net area of concrete
Asc is the area of longitudinal reinforcement
Therefore Asc =(N-0.4fcubh)/(0.75fy-0.4fcu)
Asc =(63.80*103-0.4*30*300*450)/[(0.75*250)-(0.4*30)]
Asc =-8871.79mm2
The negative sign indicates that compression reinforcement is not
required since N<0.4*fcubh
Hence provide nominal reinforcement.

Asc=
-8871.9mm2

Ref

REINFORCED CONCRETE DESIGN


Calculations
st

Design of 1 floor column

BS 8110
clause
3.8.1.6.2

Column Design Analysis


Clear height of second floor column= 3075mm
End Conditions
Condition at top
End of column is connected monolithically to beams on either
side and are at least as deep as the overall dimension of the
column.
D=450mm b=300mm
End condition at top=1.0
Condition at the bottom
End of column is connected monolithically to beams on either
side and are at least as deep as the overall dimension of the beam.
D=450mm b=300mm. the end condition at bottom is=1

BS 8110
table 3.19
clause3.8.1.6
.1

Beta() =075 (braced column)


Effective height of column Le= Lo
Le =075*3075
Le = 2306.25mm
Lex = effective height in respect of the major axis
Ley = effective height in respect of the minor axis
Lex=Ley= 2306.25mm
Lex/b =2306.25/300 =7.69<15
Ley/h =2306.25/450 =5.125<15
Hence the column is designed as a short braced axially loaded
Loading of column

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

Output

Loading of column due ot beam A1


N1= *(6.3*18.26)=57.52KN
Loading on column due to beam A2
N2= *14.87*3.8=28.25KN
Self weight of column
N3= (0.3*0.45*24*3.075)*1.4=13.95KN
Total axial load on second floor=(13.95+57.52+28.25)=99.723KN
Design of first floor column
BS
8110
Part 1
1997
Clause
3.8.4.3

Total axial load =99.723KN


N=0.4fcuAc+0.75fyAsc
For rectangular column to allow for the area of concrete displayed by
longitudinal reinforcement.
Modified formula N =0.4fcubh +Asc(0.75fy-0.4fcu)
Ac is the net area of concrete
Asc is the area of longitudinal reinforcement
Therefore Asc =(N-0.4fcubh)/(0.75fy-0.4fcu)
Asc =(99.723*103-0.4*30*300*450)/[(0.75*250)-(0.4*30)]
Asc =-8662.55mm2
The negative sign indicates that compression reinforcement is not required
since N<0.4*fcubh
Hence provide nominal reinforcement.
In the design of the ground floor columns the net axial loading will increase
and it will be the total sum of the axial loading from the 1st floor and the axial
loads of the ground floor.

Nominal steel reinforcement


100As/bd>0.4
BS
As= total area of longitudinal steel
8110
3.12.6. Acol(bd) = cross sectional area of column
As>0.4bd/100
2
As>0.4*300*450/100
As>540mm2
Provide 4R20 bars(1257mm2) for ground floor
Provide 4R16 bars(804mm2) for the first floor
Provide 4R16 bars(804mm2) for the second floor

Asc =8662.55m
m2

COLUMN DRAWING

150mm

300mm
Roof beam

B 3675mm

300mm
B

300mm

4R16

SECTION B-B
150mm 2nd floor beam
300mm
C

300mm

3675mm

SECTION C-C

4R16
150mm
D

1st floor beam


D

4200mm

300mm

300mm

4R20
Ground floor

SECTION D-D

Ref

REINFORCED CONCRETE DESIGN


Calculations

BS
Hence concrete grade is o.k
8110
No reinforcement is required. Provide nominal links
3.12.6.2
Size and spacing of links
Minimum size= *size of the largest compression bar or not less
than 5mm
Minimum size=1/4*20=5mm
Provide R8 links
BS 8110
Part 1997
clause
3.8.5

BS
8110
1997
3.8.6

Maximum spacing =12* size of the smallest compression bar


= 12*16=192mm
Choose Sv=150mm
Therefore provide R8@150c/c links

Output
No shear rnft
required.
Provide
nominal links

Sv=150mm
Provide
R8@150c/c
links

Ref

REINFORCED CONCRETE DESIGN


Calculations

FOUNDATION
DESIGN

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations

Output

Estimation of width of strip footing


Design decisions
Material used: Mass concrete select 6 sandcrete block
Width of block =150mm
Height of wall =2425mm

BR 1

Soil lab
data

Design Analysis
Assuming a unit width of blockwall
Area in contact width ground = 0.15*1 =0.15m2
Volume of blockwall, V =0.15*2.425=0.364m3
Unit width of sandcrete block =18KN/m3
Dead load, w =18*0.364=6.55KN
Ultimate design load =1.4*6.55
n =9.17KN

N=9.17KN

Minimum soil bearing capacity at 1.5m below ground


level=200KN/m2
Minimum area of strip footing, Af= 9.17/200=0.046m2
Af>0.046m2
Width of strip footing=0.046/1=0.046m
Therefore minimum width=46mm
Select width of strip footing =150mm
Design pressure
Sigma =Ultimate design load/area of strip footing
= 9.17/0.2*1
=45.85KN/m2
Design pressure S< minimum bearing capacity of soil
Hence design pressure is satisfactory and footing width=200mm is
ok since 45.85KN/m2<200KN/m2

Provide width
of strip
footing=150mm

S=45.85KN/m2
Strip width is
ok

Ref

REINFORCED CONCRETE DESIGN


Calculations

Output

Design of column base A


This is being designed as an isolated pad footing
Durability and fire resistance
BS
Nominal cover for concrete surfaces cast against adequate
8110clause blinding>40mm
3.8.1.4
Nominal cover for 1.5 hours fire resistance =35mm
Choose nominal cover=50mm
Blinding =50mm
Durability and fire resistance are satisfactory

Cover=
50mm
Blinding =
50mm

Preliminary sizing
Minimum depth of 1.5hrs fire resistance = 100mm
Choose thickness of footing = 300mm
Assume square footing of 2.2m*2.2m
Bearing capacity of soil=200KN/m2
Loading
Serviceability Limit state
Total axial design load N=243.3KN
Assume weight of footing =20KN
Total axial load = 243.3+20=263.341KN
Minimum required base area
= 263.34/200
=1.317m2
Minimum length of square base =(1.317)1/2=1.15m
Hence provide a 2.2m*2.2m pad footing(4.84m2)
Design pressure
S=Ultimate design axial load /area of footing
S=263.34/4.84
S=54.41KN/m2
Design pressure< minimum bearing capacity of soil
Hence design pressure is satisfactory and footing size is ok
Effective depth
Assuming R25 bars
Thickness of footing =D=300mm
Therefore d= D-cover-25/2

S=54.41
KN/m2

D=300mm
D=237.5mm

REINFORCED CONCRETE DESIGN


Calculations

Ref

Output

Reinforcements
BS 8110
1997
3.11.2.2

Ultimate bending moment


The critical section of bending is at the face of the column
Square footing
Sketch`

For a square footing


Mxx=Myy=N*(1-b)2/81
=263.34*(2.2-0.3)2/8*2.2
Mu=54.01KN/m
2
BS 8110 K=Mu/bd fcu
6
2
97 3.4.4 K=54.04*10 /2200*237.5 *25

K= 0.017
k<k
Hence provide no compression reinforcement required.
Lever arm
Z=d{0.5+(0.25-k/0.9)1/2}
Z=d{0.5+(0.25-0.017/0.9)1/2}
Z=0.98d, Z=0.95d
Choose Z=0.95d
Area of steel required
As=Mu/0.95fyz
=54.01*106/(0.95*250*0.95*237.5)
=1008.5mm2
Provide 11R25@225c/c(2181mm2) bottom

W/A
code of
practice

Provide
11R25
@225c/c

Ref
BS
8110
85
table
3.27

BS
8110
97
.12.3.2

BS
8110
Table
2.11.27

RCD
By
Choo

REINFORCED CONCRETE DESIGN


Calculations
Steel Area Check
Allowable steel Area As:
0.24% bd < As < 4%bd
0.24% *300*300 < 2181mm2 < 4% *300*400
216 mm2 < 2181 mm2 <3600mm2
Area of steel (As) provided is satisfactory
Distribution reinforcement
Lc=1/2*2200=1100
(3c/4)+(9d/4)=(3*300/4)+(9*237.5/4)
=759.375
Provide 11R20@225c/c and two thirds of the required
reinforcement should be concentrated within the zone from the
centerline of the column to 1.5d from the face of the
column=(1.5*237.5)+150=506.25mm at one end
And (1.5*237.5)+225=581.25mm at the other end.
Cracking shear
Allowable clear distance between bars<3d or 750
D=237.5mm
3d=3(237.5)=712.5mm
Maximum clear distance between bars=225-2(25/2)=200mm
200mm<712.5mm
Therefore cracking width is satisfactory.
Shear stress check
The critical section is at a distance d=240mm from the face of the
column.
Design shear force
V=load on shaded area
V=S(1*a)
A =2200/2-(d+175)
= 750-237.5-175
=687.5mm
V=S(1*a)
=54.51(2.2*0.6875)=82.3KN
Design shear stress v=V/bd
V =82.3*103/2200*237.5
Design concrete shear stress
Vc=(0.79*(100As/bd)1/3*(400/d)1/4/Ym

Output

Ref

REINFORCED CONCRETE DESIGN


Calculations
Vc=(0.79*(100*2181/2200*237.5)1/3*(400/237.5)1/4/1.25
Vc=0.538
V=0.157N/mm2<0.538N/mm2
Hence section is adequate in shear and no reinforcement is required

RCD
by
Choo

Punching Shear
Perimeter for checking punching shear is 1.5d from the loaded
area. 1.5d=1.5*237.5=356.25mm
Sketch

Critical perimeter= column perimeter+8(1.5d)


= (2*300) +(2*450)+(8*1.5*237.5)
=4350mm
Area within perimeter
=1.0622=1.13m2
=1.13m2 (area of shaded excluded)
Therefore shaded area=2.22 -1.13=3.71m2
Punching shear force
V=S*shaded area=54.51*3.741=201.92KN
Punching Shear stress
V=V/perimeter*d
= 201.92*103/4350*237.5
=0.195N/mm2
Hence v=0.195<Vc
But vmax=N/column perimeter*d
= 243.34*103/1500*237.5=0.658N/mm2
Vmax<0.8*fcu1/2=4N/mm2
Therefore punching shear is satisfactory
No shear reinforcement is required.