Académique Documents
Professionnel Documents
Culture Documents
What Is to Be Covered?
Electrical Shock - Why Have GFCIs?
How GFCIs Operate
30.0
600
25.0
500
20.0
400
15.0
300
10.0
200
5.0
100
0.0
# of GFCI's
# Electrocutions
Electrocutions
700
19
94
19
97
20
00
35.0
19
70
19
73
19
76
19
79
19
82
19
85
19
88
19
91
GFCI's (millions)
10A
4A
50mA
30mA
15mA
10mA
4-6 mA
1mA
Double Insulation
Equipment Grounding
L
N
Equipment
6A
Equipment Grounding
Conductor (EGC)
The same amount of current flow from line to load and returns
from load to line.
Ground-Fault
12A
L
N
6A
EGC
5.94A
Ground-Fault
.06 A
Ground-Fault
6A
L
N
5.9A
.1 A
2.
3.
IIn
Load
IOut
Differential Current Transformer
If the current out = current back, the differential current transformer shows no
output.
IIN
240V
Load
L2
IOut
Differential Current Transformer
L1
IIN
L2
120/240V
Load
IOut
Differential Current Transformer
Load
IOut = 5.9A
.1A
Face Contacts
Middle Barrier
Terminals
Terminals
Printed Circuit Board
Base
120V Trip
Mechanism
Push-to-test Button
15K Resistor
Face
Hot
Load
Hot
Face
Line Terminals
Load Terminals
Load
Neutral
Neutral
EGC
Receptacle Face
Handle
(ON-OFF)
Trip
Mechanism
Primary
Current-carrying
Contacts
Line
Terminal
Push-To-Test
Button
Trip Solenoid
Printed Circuit
Board
Panel Neutral
wire
Load Power
Terminal
Sensing Coil
Load Neutral
Terminal
Trip Solenoid
Push-To-Test Button
Test Resistor
Trip
Mechanism
Line
Terminal
Sensing Coil
Load Power
Terminal
Primary
Current-carrying
Contacts
Load Neutral
Terminal
Panel
Neutral
wire
Current
Imbalance and
Grounded
Neutral
Sensors
Push-to-test Button
Electro
Mechanical
Latching
Device
Current Imbalance
and Grounded
Neutral Sensor
15k
Resistor
Load Hot
Load Neutral
EGC
Circuitry with
Open and
Grounded
Neutral
detection
120/240Vac Source
N L1 L2
HOT
1-POLE CIRCUIT
BREAKER WITH
GFCI
120
120
120
240
GND
NEUTRAL
EQUIPMENT GROUND
DUPLEX
RECEPTACLE
Line
Terminals
Load
Terminals
2-POLE CIRCUIT
BREAKER WITH
GFCI
120
240
120
240
GND
HOT A
EQUIPMENT GROUND
250V DUPLEX
RECEPTACLE
2-POLE CIRCUIT
BREAKER WITH
GFCI
120
120
240
GND
EQUIPMENT GROUND
120/240 VAC
LOAD
1A
L
120V
N
1A
Multi-Wire Circuits
One leg of multi-wire circuit in use
1A
120V
1A
120V
0A
Switch Open
Multi-Wire Circuits
Both legs of multi-wire circuit in use
1A
120V
120V
0A
1A
DUPLEX
RECEPTACLE
120
2-POLE CIRCUIT
BREAKER WITH
GFCI
120
120
240
GND
NEUTRAL
HOT A
120
NEUTRAL
EQUIPMENT GROUND
DUPLEX
RECEPTACLE
Junction Box
Separate Neutrals
R
Downstream
Receptacles
GFCI Receptacles
Downstream
Receptacles
N
?
6A
L2
Correct Wiring
To Downstream
Receptacle
To Panelboard
To Panelboard
To Downstream
Receptacle
1-POLE CIRCUIT
BREAKER WITH
GFCI
120
120
DUPLEX
RECEPTACLE
240
GND
NEUTRAL
EQUIPMENT GROUND
L
N
EGC
Leakage Current
?
Equipment
Neutral grounded downstream
UL GFCI Tests
Every GFCI must pass the following end-ofline manufacturing tests:
no trip below 4mA (no load)
must trip at 6mA (no load)
no trip below 4mA (with load) at rated voltage
must trip at 6mA (with load) at rated voltage
must trip with 2 ohm grounded neutral
must trip within 25 ms with a 500 ohm fault
must trip with test button at +10/-15% rated
voltage
8. must not trip with noise test of GFCI Standard
9. calibration test at +10/-15% rated voltage
1.
2.
3.
4.
5.
6.
7.
GFCI Testers
Why are testers used?
line/load reversal
which outlets are protected by GFCI
reverse polarity
presence of the equipment ground
Push-to-test Button
Reset Button
GFCI Testers
The GFCI will not trip with the external tester. The test
button must be used.
Summary
GFCIs have contributed significantly to the reduction in the
number of deaths due to electric shock
GFCIs look at the current going out and compare it to the
current coming back
Remember that GFCIs detect ground to neutral
connections downstream