Operation
The 23AE21 board scans analog current- or voltage
signals and prepares them for the RTU560 on the basis of predefined parameters.
Processing functions
The micro controller EAP (Ein- Ausgabe-Prozessor /
Input- output processor) controls the A/D converter
and reads the digitized analog measured value. The
configuration parameters are loaded by the CMU
(communication unit). The used processing functions of the 23AE21 are defined by the RTU560.
In general the 23AE21 board can process the following functions per input channel.
Zero value supervision
Switching detection
Smoothing
Cyclic transmission to the CMU independent
from threshold supervision
V Threshold supervision
V Limit value monitoring
V
V
V
V
some input ranges with one shunt. With the information about the to be scanned input range set by the
switch registers S1 to S3, the 23AE21 board can do
the calculation for the 11 bit resolution for 100 %.
The sigma-delta method allows a high suppression
of line-frequency and line-harmonics interference
voltages. This is still specified by a deviation from the
nominal line-frequency of up to 10 %. On this occasion the suppression is still > 45 dB.
The 23AE21 transmits the measured value with 12 bit
plus sign to the CMU. The scaling to the telecontrol
transmission protocol presentation is done by the
CMU.
With a ninth internal measuring channel the 23AE21
does an automatic zero calibration at each cycle. The
A/D converter uses the result as an rating factor.
Settings
Input signal range
A measuring range can be differently configured for
each of the eight channels. Therefore the configuration has to be done for all eight channels. For each
channel:
V the switch registers S1 to S3
V the jumper X5x1
AND
S1
S2
S3
ON
1
1
1
ON 2
ON 2
ON 2
ON 2
1 2 3
x
1 2 3
ON 2
ON
ON
OFF
1 2 3
ON
not used
1 2 3
ON
OFF
ON
OFF
0 ... 20 V
1 2 3
ON 2
ON 2
ON
ON
OFF
ON
2V
1
ON 2
ON 2
ON 2
1
1
ON 2
ON 2
1
1
ON 2
40 mA
x
1 2 3
OFF
ON
OFF
x
1 2 3
ON 2
20 mA
1 2 3
ON
ON
OFF
ON 2
V
V
V
V
10 mA
X5x1
OFF
OFF
ON 2
OFF
ON 2
5 mA
ON 2
2V
20 V
S1-x
OFF
OFF
ON 2
x
1 2 3
2 mA
5 mA
10 mA
S2-x
ON 2
1 2 3
2 mA
S3-x
ON 2
20 mA
40 mA
measuring
range
ON 2
measuring range
ON 2
X5x1
1 2 3
ON 2
Pos.
ON
X5x1
ON
1 2 3
OFF 1
x = 1 to 8 = input channel
10
RTU560
Configuration of line-frequency
Beside the information about the configured measuring range the information about the line-frequency is
requested for the A/D-conversion. The configured
line-frequency is valid for all eight channels. Therefore jumper X401 has to be configured.
line-frequency
60 Hz
50 Hz
16.6 Hz
conversion
time per input
62.5 ms
72.5 ms
202.5 ms
scan cycle
per
23AE21 board
500 ms
580 ms
1620 ms
16.6 Hz
50 Hz
60 Hz
1 2 3
1 2 3
1 2 3
X401
Signalling
The board monitors and checks its functionality as
well as the dialog via the peripheral bus. Detected errors are indicated and/or transmitted by the board:
V by the red LED ST on the front plate
V by diagnostic messages
V in the process signal messages (signal status)
The ST LED indicates board errors, peripheral bus
errors and/or A/D converter failures.
The ST-LED indicates:
Factory calibration
An on-site calibration of the A/D converter is not necessary.
The 23AE21 will be calibrated for all channels and
measuring ranges at the factory. During the calibration the firmware calculates a rating value per measuring range and channel and stores this rating value
in an EEPROM. The rating values are protected by a
checksum.
The 23AE21 checks the checksum of all rating values
during initialization of the board. The 23AE21 does
11
suppressor circuit
ST
+ EA11
2
1
20 mA
40 mA
X5x1
z32
+ EA21
z30
+ EA31
- EA30
+ EA41
- EA40
+ EA51
Signalconditioning
EAP
- EA10
- EA20
Signalconditioning
b32
Signalconditioning
RAM
EPROM
2 mA
5 mA
10 mA
Signalconditioning
Multiplexer
ADC
Micro
controller
2V
20 V
- EA50
+ EA61
Signalconditioning
- EA60
+ EA71
Signalconditioning
- EA70
+ EA81
Signalconditioning
- EA80
d32
d30
b30
b28
z28
z26
d28
d26
b26
b24
z24
z22
d24
23AE21
X5x1
16
50
60
8
7
6
8
7
6
8
7
6
X401
8
7
S2
OFF
S3
OFF
3
1
OFF
ON
123
1/10 V
10/
1/2,5
20 mA
10 mA
1 23
S1
4
3
2
1
12
RTU560
23TP21
R0031
R0011
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
19
18
17
19
18
23ET23
Sub-connector
z32
b32
d32
z30
b30
d30
z28
b28
d28
z26
b26
d26
z24
b24
d24
A (Faston
Signal identification
Meaning
Identification
EA10 -
analog input 1 -
EA11 +
analog input 1 +
EA20 -
analog input 2 -
EA21 +
analog input 2 +
EA30 -
analog input 3 -
EA31 +
analog input 3 +
EA40 -
analog input 4 -
EA41 +
analog input 4 +
EA50 -
analog input 5 -
EA51 +
analog input 5 +
EA60 -
analog input 6 -
EA61 +
analog input 6 +
EA70 -
analog input 7 -
EA71 +
analog input 7 +
EA80 -
analog input 8 -
z22
EA81 +
analog input 8 +
6,3)
b22
ReRe
mark
cable shield
not used
d22
not used
The pin configuration of 23ET23 subrack corresponds to the direct pin configuration of the board connector
TP21
ET23
13
23TP21
R 0031
Signalidentific.
Process
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
b22
d22
18
19
Transducer
*
*
23TP21
R0031
23TP21
R0011
17
19
b22
18
17
d22
19
18
14
RTU560
03/2001
Subject to alteration
15