Catalogue | 2011
SM6
Modular units
Air insulated switchgear up to 36 kV
AMTED398078EN.indd 1
20/06/11 15:43
AMTED398078EN.indd 2
20/06/11 15:43
SM6
AMTED398078EN.indd
AMTED398078EN.indd Sec:1
General contents
Presentation
Generalities
11
Characteristics
of the functional units
43
Connections
83
Installation
91
Appendices
Order form
99
20/06/11 15:43
AMTED398078EN.indd Sec:2
AMTED398078EN.indd
20/06/11 15:43
Presentation
AMTED398078EN.indd
AMTED398078EN.indd Sec:3
Contents
Quality assurance
20/06/11 15:43
Presentation
MT20140
MT20141
1975: innovation
Sulphur hexauoride (SF6) is rst used in an MV switch for an MV/LV
transformer substation, with the VM6.
1989: experience
Over 300,000 VM6 cubicles equipped networks throughout the world.
1991: innovation and experience
Cumulated with the second generation of SM6 modular SF6 cubicles.
2010: a leading position
b with over 1,000,000 SM6 cubicles installed around the world,
Schneider Electric consolidates its position as uncontested leader
in the Medium Voltage eld.
AMTED398078EN.indd Sec:4
AMTED398078EN.indd
20/06/11 15:43
Presentation
MT20142
Upgradability
SM6, a comprehensive range
b
b
b
b
b
MT20143
Compactness
SM6, an optimised range
b compact units, with low increment cubicles
b rationalised space requirement for switchboard installation
b reduction of civil works costs
b easy integration in factory-built outdoor substations for which the SM6
is particularly well designed.
MT20144
Maintenance
SM6, a range with reduced maintenance
b the active parts (breaking and earthing) are integrated in an SF6-lled, sealed for
life unit
b the control mechanisms, are intented to function with reduced maintenance under
normal operating conditions
b enhanced electrical endurance when breaking.
MT20145
Ease of installation
SM6, a simple range to incorporate
b
b
b
b
MT20146
MT20147
MT20148
AMTED398078EN.indd
AMTED398078EN.indd Sec:5
20/06/11 15:43
Presentation
61051N
The materials used, both conductors and insulators, are identied in product
At the end of its life, SM6 can be processed, recycled and its materials
61016N
RoHS restricts the use of six hazardous materials in the manufacture of various
24 kV
36 kV
Switch
unit
Circuit breaker
unit
Switch
unit
Ferrous metal
84%
65%
74%
Non-ferrous metal
4%
10.6%
8%
Thermohardening
9.5%
22%
15%
Thermoplastics
2.35%
2.3%
2%
Fluid
0.15%
0.1%
1%
MT55145
01
ISO 140
AMTED398078EN.indd Sec:6
AMTED398078EN.indd
20/06/11 15:43
Presentation
61052N
b consumption monitoring
b on site work
b maintenance contracts
PE57151
Sales Ofce.
AMTED398078EN.indd
AMTED398078EN.indd Sec:7
20/06/11 15:43
Presentation
Asia/Middle East
b Canal Electrical Distribution Company, Egypt
b General Motors Holden, Australia
b Pasteur Institute, Cambodia
b Tian he City, China
b Sanya Airport, China
b Bank of China, Beijing, Jv Yanta, China
b Plaza Hotel, Jakarta, Indonesia
b Bali Airport, Indonesia
b Wakasa Control Center, Japan
b Otaru Shopping center, Japan
b New City of Muang, Thong Than, Kanjanapas,
Thailand
b Danang and Quinhon Airport, Vanad, Vietnam
b British Embassy, Oman
b KBF Palace Riyadh, Saudi Arabia
b Raka Stadium, Saudi Arabia
b Bilkent University, Turkey
b TADCO, BABOIL development, United Arab Emirates
b Melbourne Tunnel City Link, Australia
b Campus KSU Qassim Riyad, Saudi Arabia
61001N
Africa
b
b
b
b
b
b
b
b
b
b
South America/Pacic
b
b
b
b
b
b
b
b
b
b
b
Europe
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
AMTED398078EN.indd Sec:8
AMTED398078EN.indd
20/06/11 15:43
Presentation
Quality assurance
Quality certified to ISO 9001
A major advantage
Schneider Electric has integrated a functional organisation into each
of its units. The main mission of this organisation is to check the quality
But it is above all its strict application that has enabled recognition
MT55055
MT55054
The quality system for the design and manufacture of SM6 units
ISO
900 1
ISO
9002
61002N
61003N
The results obtained are written and reported on the test certicate for each device
by the quality control department.
AMTED398078EN.indd
AMTED398078EN.indd Sec:9
20/06/11 15:43
10
AMTED398078EN.indd Sec:10
AMTED398078EN.indd
20/06/11 15:43
Generalities
Contents
Field of application
12
14
Operating conditions
20
Standards
21
Main characteristics
22
24
Compartments description
26
Safety of people
By switchgear
By operating mechanism safety
By internal arc protection
28
28
30
31
32
Fault indicators
34
Ammeter
35
36
36
AMTED398078EN.indd
AMTED398078EN.indd Sec:11
TLP130, CLP2 sensors and Sepam series 20, 40, 80 protection units
41
41
42
11
20/06/11 15:43
Field of application
Generalities
MV consumer substation
(MV metering)
IM
CM
DM2
QM
PM
IM
MT55148
DE59670EN
IM
MV consumer substation
(LV metering)
IM
IM
QM DM1-S
Substation
GAM2 QM
MT55147
Other standards
MV consumer substations
(MV metering)
IM
DM1-D
GBC-A
QM
DM1-S
MT55146
IM
12
AMTED398078EN.indd Sec:12
AMTED398078EN.indd
20/06/11 15:43
Field of application
Generalities
DE59200EN
HV/MV substation
Distribution switchboard
GBC-B
QM QM IM
IM
GBC-B
DM1-A
61004N
DM1-A
Incoming
line
ATS
Incoming
line
Unit denitions
Below is the list of SM6 units used in MV/LV
transformer substations and industrial distribution
substations:
b IM, IMC, IMB switch
b PM fused switch
b QM, QMC, QMB fuse-switch combination
b CRM, CVM contactor and contactor with fuses
b DM1-A, DM1-D, DM1-S single-isolation
disconnectable SF6 type circuit breaker
b DMV-A, DMV-D, DMV-S single-isolation
vacuum type circuit breaker frontal
b DMVL-A, DMVL-D single-isolation disconnectable
vacuum type circuit breaker lateral
b DM1-W, DM1-Z withdrawable single-isolation
SF6 type circuit breaker
b DM2 double-isolation disconnectable SF6 type
circuit breaker
b DM2-W withdrawable double-isolation SF6 type
circuit breaker only for 36 kV
b CM, CM2 voltage transformers
b GBC-A, GBC-B current and/or voltage measurements
b NSM-cables for main incoming and standby
b NSM-busbars for main incoming and cables
for standby
b GIM intermediate bus unit
b GEM extension unit
b GBM connection unit
b GAM2, GAM incoming cable connection unit
b SM disconnector
b TM MV/LV transformer unit for auxiliaries
b Other units, consult us
b Special function EMB busbar earthing only for 24 kV.
QM NSM-busbarsGBM SM TM
Standby
generator source
Standby
source
Distribution switchboard
QM QM GBC-B
IM
IMB GBM IM
GBC-B
DM1-S
DM1-S
ATS
Incoming
line
Incoming
line
AMTED398078EN.indd
AMTED398078EN.indd Sec:13
13
20/06/11 15:43
Generalities
45
IM
Switch unit
24 kV: 375 or 500 mm
36 kV: 750 mm
DE59673
DE59672
page
DE59671
IMC
Switch unit
24 kV: 500 mm
36 kV: 750 mm
IMB
Switch unit with or without
earthing disconnector
right or left outgoing line
24 kV: 375 mm
36 kV: 750 mm
QM
Fuse-switch combination unit
24 kV: 375 or 500 mm
36 kV: 750 mm
DE59676
QMC
Fuse-switch combination unit
24 kV: 625 mm
36 kV: 1000 mm
QMB
Fuse-switch combination unit
right or left outgoing line
24 kV: 375 mm
36 kV: 750 mm
DE59677
46
DE59675
DE59674
Fuse-switch protection
47
PM
Fuse-switch unit
24 kV: 375 mm
36 kV: 750 mm
14
AMTED398078EN.indd Sec:14
AMTED398078EN.indd
20/06/11 15:43
Generalities
DE59202
CRM
Fuse-contactor unit
24 kV: 750 mm
DE59231
48
49
CRM
Contactor unit
24 kV: 750 mm
DE59232
page
DE59201
Motor starter
CVM
Fuse-contactor unit
24 kV: 750 mm
CVM
Contactor unit
24 kV: 750 mm
50
DE59679
DE59678
DM1-A
Single-isolation, disconnectable
circuit breaker unit
24 kV: 750 mm
36 kV: 1000 mm
AMTED398078EN.indd
AMTED398078EN.indd Sec:15
DM1-D
24 kV: 750 mm
36 kV: 1000 mm
15
20/06/11 15:43
Generalities
DE53490
DM1-S
Single-isolation, disconnectable
circuit breaker unit with
autonomous protection
24 kV: 750 mm
51
52
DM1-Z
Withdrawable single-isolation
circuit breaker unit
right outgoing line
24 kV: 750 mm
DE59691
DM1-W
Withdrawable single-isolation
circuit breaker unit
24 kV: 750 mm
36 kV: 1000 mm
DE59680
51
52
DE53487
page
DE59681
DM2
Double-isolation, disconnectable
circuit breaker unit right or left outgoing line
24 kV: 750 mm
36 kV: 1500 mm
DM2-W
Withdrawable double-isolation
circuit breaker unit right outgoing line
36 kV: 1500 mm
53
DMV-A
Single-isolation
circuit breaker unit
24 kV: 625 mm
16
AMTED398078EN.indd Sec:16
DE53493
DE53492
DE53491
DMV-D
Single-isolation
circuit breaker unit
right outgoing line
24 kV: 625 mm
DMV-S
Single-isolation
autonomous protection
24 kV: 625 mm
AMTED398078EN.indd
20/06/11 15:43
Generalities
54
DE59694
page
DE53485
DMVL-A
Single-isolation, disconnectable
circuit breaker unit
24 kV: 750 mm
DMVL-D
Single-isolation, disconnectable
circuit breaker unit right outgoing line
24 kV: 750 mm
56
GBC-A
Current and/or voltage
measurement unit
right or left outgoing line
24 and 36 kV: 750 mm
AMTED398078EN.indd
AMTED398078EN.indd Sec:17
CM2
Voltage transformers for mains
with insulated neutral system
24 kV: 500 mm
36 kV: 750 mm
DE53497
CM
Voltage transformers for mains
with earthed neutral system
24 kV: 375 mm
36 kV: 750 mm
DE53496
55
DE59684
DE59863
MV metering
GBC-B
Current and/or voltage
measurement unit
24 and 36 kV: 750 mm
17
20/06/11 15:43
Generalities
GBM
Connection unit
right or left outgoing line
24 kV: 375 mm
36 kV: 750 mm
58
DE59685
GEM
Extension unit VM6/SM6
24 kV: 125 mm
GIM
Intermediate bus unit
24 kV: 125 mm
36 kV: 250 mm
DE59688
DE59687
57
DE53498
page
DE59686
Casings
GAM2
Incoming cable-connection unit
24 kV: 375 mm
36 kV: 750 mm
18
AMTED398078EN.indd Sec:18
GAM
Incoming cable-connection unit
with earthing
24 kV: 500 mm
36 kV: 750 mm
AMTED398078EN.indd
20/06/11 15:43
Generalities
Other functions
59
DE59690
DE59689
DE53504
page
SM
Disconnector unit
24 kV: 375 mm or 500 (1) mm
36 kV: 750 mm
62
NSM-cables
Cables power supply
for main incoming line
and standby line
36 kV: 1500 mm
AMTED398078EN.indd
AMTED398078EN.indd Sec:19
NSM-busbars
Busbars power supply
for main incoming line on right or left
and cables for standby line
24 kV: 750 mm
DE59697
NSM-cables
Cables power supply
for main incoming line
and standby line
24 kV: 750 mm
DE59696
60
EMB
Busbar earthing compartment
24 kV: 375 mm
DE59693
DE59692
TM
MV/LV transformer unit
for auxiliaries
24 kV: 375 mm
36 kV: 750 mm
NSM-busbars
36 kV: 1500 mm
19
20/06/11 15:43
Operating conditions
All control functions are centralised on a front plate, thus simplifying operation.
PE57152
Generalities
b Solar radiation
1) no solar radiation inuence is permitted.
b Ambient air pollution
1) no signicant pollution by dust, smoke, corrosive and/or ammable gases,
vapours or salt.
b Humidity
1) average relative humidity over a 24 hour period, less than or equal to 95%
2) average relative humidity over a 1 month period, less than or equal to 90%
3) average vapor pressure over a 24 hour period, less than or equal to 2.2 kPa
4) average vapor pressure over a 1 month period, less than or equal to 1.8 kPa.
For these conditions, condensation may occasionally occur. Condensation can be
expected where sudden temperature changes occur in periods of high humidity.
To withstand the effects of high humidity and condensation, such as breakdown of
insulation, please pay attention on Civil Engineering recommendations for design
of the building or housing, by suitable ventilation and installation.
Severe operating conditions (please consult us).
20
AMTED398078EN.indd Sec:20
AMTED398078EN.indd
20/06/11 15:43
Generalities
Standards
62271-1
60265-1
62271-105
60255
Electrical relays.
62271-100
62271-102
60044-1
60044-2
60044-8
61958
High-voltage prefabricated switchgear and controlgear assemblies Voltage presence indicating systems.
AMTED398078EN.indd
AMTED398078EN.indd Sec:21
21
20/06/11 15:43
Main characteristics
Generalities
The hereunder values are for working temperatures from -5C up to +40C
and for a setting up at an altitude below 1000 m.
PE57150
Electrical characteristics
Rated voltage
Ur
kV
7.2
12
17.5
24
36
Insulation level
Insulation
Ud
20
28
38
50
70
Isolation
Ud
23
32
45
60
80
Insulation
Up
60
75 (1)
95
125
170
Isolation
Up
70
85
110
145
195
Breaking capacity
Transformer off load
16
31.5
50
630-1250
25
630 - 1250
1250
20 (3)
630 - 1250
Rated current
Ir
Ik/tk (2)
kA/1 s
Ima
kA
16
630 - 1250
12.5
62.5
630
50
630
40
630
630
31.25
400 - 630
630
630
630-1250
NA
630
kA
25
PM
kA
25
20
CRM
kA
10
kA
25
CVM
kA
6.3
NA
kA
25
NA
20
20
NA
NA
kA
kA
DM1-Z
DM2-W
kA
25
630-1250
20
630-1250
1250
25
630
NA
25
1250
NA
25
NA
1250
20
NA
630
kA
25
630-1250
DMVL-A
kA
20
630
NA
DMVL-D
kA
25
630
NA
22
AMTED398078EN.indd Sec:22
AMTED398078EN.indd
20/06/11 15:43
Generalities
Main characteristics
Endurance
Units
Mechanical endurance
Electrical endurance
IEC 60265
1 000 operations
class M1
IEC 60265-1
100 breaks at Ir,
p.f. = 0.7, class E3
CRM
Disconnector
IEC 62271-102
1 000 operations
Rollarc 400
IEC 60470
300 000 operations
IEC 60470
100 000 breaks at 320 A
300 000 breaks at 250 A
Rollarc 400D
Disconnector
IEC 62271-102
1 000 operations
CVM
IEC 60470
250 000 breaks at Ir
Disconnector
IEC 62271-102
1 000 operations
SF circuit breaker
IEC 62271-100
10 000 operations
class M2
IEC 62271-100
30 breaks at 12.5 kA for 24 kV
25 breaks at 25 kA for 24 kV
40 breaks at 16 kA for 36 kV
15 breaks at 25 kA for 36 kV
10 000 breaks at Ir,
p.f. = 0.7, class E2
Switch
IEC 60265
1 000 operations
class M1
IEC 60265
100 breaks at Ir,
p.f. = 0.7, class E3
Evolis circuit
breaker
IEC 62271-100
10 000 operations
class M2
IEC 62271-100
10 000 breaks at Ir,
p.f. = 0.7, class E2
Disconnector
IEC 62271-102
1 000 operations
Evolis circuit
breaker
IEC 62271-100
10 000 operations
class M2
DMVL-A
DMVL-D
IEC 62271-100
10 000 breaks at Ir,
p.f. = 0.7, class E2
b SM6 24 kV:
b SM6 36 kV:
Protection index:
b classes: PI (insulating partition)
b loss of service continuity classes: LSC2A
b units in switchboard: IP3X
b between compartments: IP2XC
b Cubicle: IK08.
Electro-magnetic compatibility:
b relays: 4 kV withstand capacity, as per recommendation IEC 60801.4
b compartments:
v electrical eld:
Temperatures:
The cubicles must be stored and installed in a dry area free from dust and with
limited temperature variations.
b for stocking: from 40C to +70C
b for working: from 5C to +40C
b other temperatures, consult us.
AMTED398078EN.indd
AMTED398078EN.indd Sec:23
23
20/06/11 15:43
Factory-built cubicles
description
Generalities
PE50780
2
1
2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
(positive break).
5 low voltage: installation of a terminal block (if motor option installed), LV fuses
If more space is required, an additional enclosure may be added on top of the cubicle.
PE50781
2
1
2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
5 low voltage: installation of compact relay devices (Statimax) and test terminal
boxes. If more space is required, an additional enclosure may be added on top
of the cubicle.
24
AMTED398078EN.indd Sec:24
AMTED398078EN.indd
20/06/11 15:43
Factory-built cubicles
description
Generalities
1 switchgear: load break switch and earthing switch(es), in enclosure lled with
SF6 and satisfying and one vacuum circuit breaker, sealed pressure system
requirements.
2
1
2 busbars: all in the same horizontal plane, thus enabling later switchboard
the disconnector(s), the circuit breaker and the earthing switch and actuate
5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
If more space is required, an additional enclosure may be added on top of the cubicle.
and satisfying and one vacuum circuit breaker, sealed pressure system
requirements.
2 busbars: all in the same horizontal plane, thus enabling later switchboard
2
1
5
4
the disconnector(s), the circuit breaker and the earthing switch and actuate
5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
If more space is required, an additional enclosure may be added on top of the cubicle.
Contactor cubicles
1 switchgear: disconnector and earthing switch and contactor in enclosures lled
PE50784
2 busbars: all in the same horizontal plane, thus enabling later switchboard
2
1
5
4
the disconnector(s), the contactor and the earthing switch and actuate
5 low voltage: installation of compact relay devices and test terminal boxes.
4
AMTED398078EN.indd
AMTED398078EN.indd Sec:25
25
20/06/11 15:43
Compartments description
DE53507
61007N
Generalities
Busbar compartment
DE53508
61006N
The three insulated busbars are parallel-mounted. Connection is made to the upper
pads of the enclosure using a eld distributor with integrated captive screws.
Ratings 400 - 630 - 1250 A.
DE53509
DE53510
With basic equipment, the maximum allowable cross-section for cable is:
b 240 mm2 or 2 x 240 mm2 for incoming or outgoing units 400 - 630 A
See in fonctional units characteristics chapter for each unit allowable section.
The earthing switch must be closed before the cubicle may be accessed.
The reduced depth of the cubicle makes for easy connection of all phases.
A stud incorporated in the eld distributor makes it possible to position and secure
the cable-end lug with a single hand.
26
AMTED398078EN.indd Sec:26
AMTED398078EN.indd
20/06/11 15:43
Compartments description
Operating-mechanism cover
61008N
DE53511
Generalities
b disconnector(s)
b circuit breaker
b contactor
The operating-mechanism cover may be accessed with the cables and busbars
According to the volume, it is available in 3 versions: cover, wiring duct and cabinet.
DE53512
C - LV control cabinet
h = 2050 mm
PE57153
C
B
A
transformers.
AB
DE59695
PE58270
A - LV cover
h = 2250 mm
AMTED398078EN.indd
AMTED398078EN.indd Sec:27
1500
1615
27
20/06/11 15:43
Safety of people
Generalities
By switchgear
61010N
pressure of 0.4 bar (400 hPa) for 24 kV and 1 bar (1000 hPa) for 36 kV. It satises
checked, and leakage rate is less than 0.1% for 30 years life span.
b Operating safety
v the earthing switch placed in the SF6 has a short-circuit making capacity,
membrane, in which case the gas is directed toward the back of the unit,
MT20184
PE57226
Switch-disconnector for 24 kV
Switch-disconnector for 36 kV
Closed position
Open position
Earth position
61011N
DE53513
b Operating safety
Accidental over-pressures are eliminated by the opening of the safety membrane.
Rollarc contactor
Contacts closed
28
AMTED398078EN.indd Sec:28
Main contacts
separated
Arcing period
Contacts open
AMTED398078EN.indd
20/06/11 15:43
Safety of people
Generalities
By switchgear
61012N
DE53514
b Operating safety
Accidental over-pressures are eliminated by the opening of the safety membrane.
61058N
Contacts closed
PE50798
Precompression
Arcing period
Contacts open
This process diffuses the arc in a regular manner with high currents.
b Vacuum tightness
Vacuum contactor comprises three separate poles xed on a structure supporting
the control mechanism. Each pole encloses all of the active parts in an insulating
enclosure under vacuum and its vacuum tightness is checked in the factory.
AMTED398078EN.indd
AMTED398078EN.indd Sec:29
29
20/06/11 15:43
Generalities
Safety of people
By operating mechanism safety
61013N
PE50796
Mechanical and electrical controls are side by side on the front fascia, on a panel
including the schematic diagram indicating the devices status (closed, open, earthed):
b Closed: the drive shaft is operated via a quick acting mechanism, independent of
the operator. No energy is stored in the switch, apart from when switching operations
For combined switch fuses, the opening mechanism is armed at the same time
b Opening: the switch is opened using the same quick acting mechanism,
For circuit breakers and the combined switch fuses, opening is controlled by:
v a push-button,
v a fault.
b Earthing: a specic control shaft enables the opening or closing of the earthing
contacts. Access to this shaft is blocked by a cover that can be slid back if the switch
PE57166
The position of main contacts is clearly visible from the front of the cubicle through
the window.
PE56366
30
AMTED398078EN.indd Sec:30
AMTED398078EN.indd
20/06/11 15:43
Generalities
Safety of people
By internal arc protection
Consequently:
DE59732
b Technological control:
v choice of materials,
b
v
v
v
Installation of an SM6 switchboard installed against the wall
downwards exhaust 12.5 kA 1 s and 16 kA 1 s, IAC: A-FL:
3-sides internal arc protection
DE59733
b
v
v
b
v
In its internal arc version, the SM6 has successfully passed all of the type testing
The materials used meet the constraints for which the SM6 is designed.
The thermal and mechanical forces that an internal arc can produce are perfectly
An operator situated in the front of the SM6 switchboard during an internal fault
DE59734
For SM6 switchboards installed in the middle of a room, 4-sides internal arc
AMTED398078EN.indd
AMTED398078EN.indd Sec:31
b Choice of exhaust:
(civil engineering document for internal arc protected cubicles to be considered)
v For 24 kV upwards exhaust
A ceiling height greater or equal than 2 800 mm is necessary.
v For 24 kV downwards exhaust
Civil engineering with an adequate volume is necessary.
v For 36 kV downwards exhaust
Civil engineering with an adequate volume is necessary.
31
20/06/11 15:43
MV electrical network
management
Generalities
PE15074
Easergy T200 S
Easergy T200 S is a simplied MV substation control unit for secondary distribution
T200 S, a version of the T200 I unit, is integrated in the SM6 cubicle LV control
cabinet.
for source transfer switching and back up generator set switching in NSM cubicle.
b acquisition of various data types: switch position, fault detectors, current values, etc.
Particularly used during network incidents, Easergy T200 S has proven its reliability
and availability to be able to operate the switchgear at all times. It is easy to implement
and operate.
PE15079
Easergy T200 S is installed in the low voltage control cabinet of NSM cubicles
for remote control of one or two switches.
It has a simple panel for local operation to manage electrical controls (local/remote
It integrates a fault current detector (overcurrent and zero sequence current) with
PE15078
Control command
Data transmission system standards are: RS232, RS485, PSTN, FSK, FFSK,
GSM/GPRS.
is not supplied.
VD23
b 1 Ph-N or Ph-Ph or residual voltage: V1, V2, V3, U12, U13, U23, V0.
VD23 can display the MV network voltage (in % of service voltage), active the relay
output R1 to monitor a loss of voltage on 1 phase at least and active the relay output
b Assembly: compact DIN format, mounted in the same place as fault passage
VPIS-Voltage Output
32
AMTED398078EN.indd Sec:32
AMTED398078EN.indd
20/06/11 15:43
MV electrical network
management
Generalities
PE56311
PE56422
PE56421
all the functional units necessary for remote supervision and control of the SM6:
current values...
reliability and availability, being able to ensure switchgear operation at any moment.
PE56824
PE56423
b It has a simple front plate for local operation, which allows management of
zero sequence) with detection set points that can be congured channel by channel
AMTED398078EN.indd
AMTED398078EN.indd Sec:33
Polarized connectors
hours in case of loss of the auxiliary source, and supplies power to the Easergy T200
b Ready to plug
v Easergy T200 I is delivered with a kit that makes it easy to connect the motor
v the telecontrol cabinet connectors are polarized to avoid any errors during
their installation.
33
20/06/11 15:43
direct earthing.
b Easergy Flair 279 and 219, have a wall-mounted case for the MV cubicles
substation or LV compartment and anexternal power supply which can be backed up.
PE57155
PE57921
PE57922
Fault indicators
PE57154
Generalities
Easergy Flair
Usage
279 - 219
200C
Installation
Flush tted
Casing
Casing
Power supply
Self-powered
or dual power
230 Vac
or battery
230 Vac
Fault detection
Indication
LCD display
Measurement
Current,
frequency
Communication
SCADA interface
by dry contact
Indicator light
SCADA interface
by dry contact
v displaying settings,
v displaying the load current including peak demand and frequency meter.
b Maintenance free.
Flair 21D
Flair 22D
Flair 23DV
b (battery)
b (external)
Power supply
Self-powered
Dual power supply
Display of settings
Short-circuit fault thresholds
L1-L2-L3
L1-L2-L3
Reset timer
Faulty phase and measurements
Faulty phase
50/60 Hz
b
50/60 Hz
b
Residual current
Load current
MV network frequency
34
AMTED398078EN.indd Sec:34
L1-L2-L3
b
AMTED398078EN.indd
20/06/11 15:43
Ammeter
Generalities
PE56822
display of currents.
Functions
b Display of 3 phase current: I1 , I2 , I3. Range: 3 A to 800 A
b Display of 3 phase current maximeter: I1 , I2 , I3. Range: 3 to 800 A.
Display principle
b
v
b
v
v
v
Assembly
Small size enclosure
b DIN format : 93 x 45 mm
b Secured, extraction-proof mounting
b Terminal connections.
Technical data
Application
DE58404
Frequency
Load current
Measurement
Range
Reset of maximeter
Power supply
Self power
Battery
Auxiliary supply
Display
Amp 21D
L1
L2
50 Hz and 60 Hz
> 3A
Phase current
Accuracy (I < 630 A)
Manual from device
3 to 800 A
5%, 2 A
Yes
I load > 3 A
No
No
Display
Current per phase
Maximeter per phase
4 digits LCD
Yes (resolution 1 A)
Yes
Phase CTs
3 split core CT
Test
Yes
IEC 60255-5
IEC 61000-4-4 (level 4)
IEC 61000-4-12
Operating temperature
Storage temperature
Salt fog
IEC 60068-2-6
IEC 60068-2-29
Insulation 10 kV
Shock wave 20 kV
25C to + 70C
40C to + 85C
200 h
Vibrations 10 to 500 Hz: 2 g
Protection IP23
Sensors
Miscellaneous
L3
Characteristics
Dielectric
Electromagnetic
PE57169
Minimum current
Climatic
Mechanical
AMTED398078EN.indd
AMTED398078EN.indd Sec:35
35
20/06/11 15:43
Generalities
b Protection of transformers.
Simplicity
Easy to install
b Light, compact base unit.
b User friendly and powerful PC parameter and protection setting software to utilize
User-friendly
b Intuitive User Machine Interface, with direct data access.
b Local operating data in the users language.
Series 10
Series 20
Series 40
Protections
Current
Voltage
Frequency
Specics
b
b
b
Phase and
earth fault
overcurrent
Breaker
failure
b
b
b
b
b
Disconnection
by rate of
change of
frequency
b
b
b
b
b
b
Directional
earth fault
Directional
earth fault
and phase
overcurrent
S41, S43
S42
Applications
Substation
Busbar
Transformer
Motor
Generator
Capacitor
10A, 10B
S20
S24
S40
B21
10A, 10B
T20
M20
B22
T24
T40
T42
M41
G40
Characteristics
Logic inputs
Logic outputs
Temperature sensors
Channel Current
0 to 10
0 to 10
0 to 10
4 to 8
4 to 8
4 to 8
0 to 8
0 to 8
0 to 16
3V + Vo
3V, 2U + Vo
3 I + Io
3 I + Io
Voltage
LPCT (1)
Communication ports
IEC61850 Protocol
Control Matrix (2)
3 I + Io
b
1
1 to 2
1 to 2
1 to 2
b
b
b
b
b
b
b
Other
Memory cartridge
with settings
Backup battery
Lithium battery
48 hours
(1) LPCT: low-power current transformer complying with standard IEC 60044-8.
(2) Control matrix for simple assignment of information from the protection, control and monitoring functions.
(3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions.
36
AMTED398078EN.indd Sec:36
AMTED398078EN.indd
20/06/11 15:43
Generalities
Monitoring switchgear status: sensors and trip circuit, mechanical switchgear status.
Disturbance recording.
Series 80
b
b
b
S80
B80
b
b
b
b
b
b
b
b
b
b
b
b
Directional
earth fault
Directional
earth fault
and phase
overcurrent
Disconnection
by rate of
change of
frequency
S81
S82
T81
M81
T82
b
b
b
b
b
b
b
b
b
Capacitor-bank
unbalance
S84
B83
G82
T87
M88
G88
M87
G87
C86
0 to 42
0 to 42
0 to 42
0 to 42
5 to 23
5 to 23
5 to 23
5 to 23
0 to 16
0 to 16
0 to 16
0 to 16
3 I + 2 x Io
2 x 3 I + 2 x Io
3 I + Io
2 x 3 I + 2 x Io
3V + Vo
3V + Vo
2 x 3V + 2 x Vo
3V + Vo
2 to 4
2 to 4
2 to 4
2 to 4
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
Lithium battery
Lithium battery
Lithium battery
Lithium battery
AMTED398078EN.indd
AMTED398078EN.indd Sec:37
37
20/06/11 15:43
Generalities
PE57159
VIP 35 provides protection against phase-to-phase faults and against earthing faults.
Phase protection
b phase protection is achieved by a denite time threshold which functions
from 1.2 times the operating current (Is).
Earthing protection
b earthing fault protection functions with the residual current measurement taken
from the sum of the secondary currents in the sensors. This is taken via a CRc,
8 A to 80 A gauge.
b earthing protection is inverse denite time: its threshold and time delay can be set.
VIP 35
Is: the phase operating current is adjusted directly in accordance with the transformer
Io: the earth current threshold is adjusted according to the network characteristics.
200
250
315
400
500
630
800
3
3.3
10
15
20
25
36
45
55
68
80
115
140
170
200
10
15
18
22
28
36
45
56
70
90
115
140
200
4.2
12
15
18
22
28
36
45
55
70
90
115
140
200
5.5
8*
12
15
18
22
28
36
45
55
68
90
115
140
170
8*
8*
10
12
18
20
25
36
45
55
68
80
115
140
170
200
6.6
8*
8*
10
12
15
18
22
28
36
45
56
70
90
115
140
200
10
8*
8*
8*
10
12
15
20
25
30
37
55
68
80
115
140
170
11
8*
8*
8*
8*
10
12
15
18
22
28
36
45
55
68
90
115
140
170
13.8
8*
8*
8*
8*
10
12
15
18
22
28
36
45
55
68
90
115
140
170
15
8*
8*
8*
8*
8*
10
15
18
20
25
36
45
55
68
80
115
140
170
200
20
8*
8*
8*
8*
8*
8*
10
12
15
20
25
30
37
55
68
80
115
140
170
200
22
8*
8*
8*
8*
8*
8*
10
12
15
18
22
28
36
45
55
68
90
115
140
170
200
PE57160
A choice of trip curves and the large number of possible settings mean that it can be
VIP 300 is an independent relay powered by the current sensors; it does not require
VIP 300 LL
Phase protection
b phase protection is via two independently adjustable thresholds:
v the lower threshold can be chosen to be inverse denite time or denite time.
The denite time curves are in conformity with IEC standard 60255-3.
Earthing protection
b protection against phase-to-earth faults uses the residual current measurement,
taken from the sum of the secondary currents in the sensors. This is taken via
Signalling
b two indicators show the origin of the trip operation (phase or earth).
They remain in position after the relay power supply has been cut.
two led indicators (phase and earth) show that the lower threshold
has been exceeded and that its time delay is currently in progress.
38
AMTED398078EN.indd Sec:38
AMTED398078EN.indd
20/06/11 15:43
Generalities
b 10B: Sepam series 10B protects against overloads, phase-to-phase faults and
earth faults.
b 10A: Sepam series 10A provides the same functions as model B, but with a
communication port, more inputs and outputs, and additional protection and
monitoring functions.
Sepam series 10
Is: the phase operating current is adjusted directly in accordance with the transformer
Io: the earth current threshold is adjusted according to the network characteristics.
160
200
250
315
400
500
630
800
1000
1250
1600
2000
2500
3000
31
38
48
61
77
96
121
154
192
241
308
385
481
577
28
35
44
55
70
87
110
140
175
219
280
350
437
525
22
27
34
43
55
69
87
110
137
172
220
275
344
412
481
5.5
21
26
33
42
52
66
84
105
131
168
210
262
315
367
19
24
30
38
48
61
77
96
120
154
192
241
289
337
22
28
35
44
55
70
87
109
140
175
219
262
306
10
23
29
36
46
58
72
92
115
144
173
202
11
21
3
3.3
4.2
6.6
19
24
22
3500
26
33
42
52
66
84
105
131
157
184
13.8
21
26
33
42
52
67
84
105
126
146
15
19
24
31
38
48
62
77
96
115
135
20
23
29
36
46
58
72
87
101
22
21
26
33
42
52
66
79
92
AMTED398078EN.indd
AMTED398078EN.indd Sec:39
CRb 1250/1
39
20/06/11 15:43
Generalities
Weight
(kg)
Ratio of
Class of precision
transformation
CRa
Dimensions (mm)
External Internal Thickness
(without
fastening)
143.5
81
37.5
2.18
1/200
CRb
143.5
1.26
1/1250
CRc
143.5
81
81
37.5
37.5
VIP 35
2% from 10 A to 100 A
On load 5.7 (cal. x 1)
1% from 100 A to 1600 A
1% from 10 A to 10 kA
On load 0.67 (cal. x 4)
1% from 10 A to 11 kA
On load 5.7 (cal. x 1)
S1-S2: 1/200
DE58402
S1-S3: 1/500
1 % from 10 A to 25 kA
On load 0.67 (cal. x 4)
S1-S2:
On load 0.6
5% from 10 A to 80 A
2.5 % from 80 A to 600 A
S1-S3:
2% from 20 A to 2200 A
Three-phase overcurrent
Zero-sequence overcurrent
Directional zero-sequence current
Undervoltage
Overvoltage
Thermal image
Zero-sequence overvoltage
Negative sequence overcurrent
Long start-up and rotor blocking
Maximum number of start-ups
Single-phase undercurrent
Communication
Code
Protection units
Sepam
series 10
50 - 51
b
50N - 51N b
67N
27
59
49
b
59N
46
51LR
66
37
b
series 20
b
b
b
b
b
b
b
b
series 40
b
b
b
b
b
b
b
b
b
b
b
b
series 80
b
b
b
b
b
b
b
b
b
b
b
b
VIP
35
300
b (2)
b (3)
b (1)
b (1)
40
AMTED398078EN.indd Sec:40
AMTED398078EN.indd
20/06/11 15:43
Generalities
Standard
applications
PE88012
PE57172
Sepam series 20, series 40, series 80 protection units are at the heart
of the LPCT protection chain.
Sepam series 20, series 40, series 80 performs the following functions:
Advantages
Sepam series 20
b Consistent protection chain with the same sensor measures phase currents
from 5 A to 630 A
b Simple to install and implement:
v installation of LPCT sensors
- TLP130, TLP160 and TLP190 are installed around MV cable
- CLP2 is installed on the MV circuit
v LPCT connected directly to Sepam series 20, series 40, series 80
v accessories available to test the LPCT protection chain by secondary current
injection.
b LPCTs range of use
LPCT measuring and protection function guaranteeing the accuracy up to
the short-time current.
Following the range of use of LPCT:
v from 5 A up to 1250 A respecting the error limits imposed by the accuracy class 0,5
v from 1250 A up to 50 kA respecting the error limits imposed by the accuracy class 5P.
Sepam series 40
PE88010
Custom
applications
Sepam series 80
DE58405EN
PE88011
Demanding
applications
5.00
4.75
4.50
4.25
4.00
3.75
3.50
3.25
3.00
2.75
2.50
2.25
2.00
1.75
1.50
1.25
1.00
0.75
0.50
0.25
Ratio error
Protective class 5P
Measuring class 0.5
A
5
20
100
1000
1250
2000
3000
31500
40000
50000
MT11325
v monitoring of LPCT sensor by Sepam series 20, series 40, series 80 (detection of
phase loss).
Connections
1 LPCT sensor, equipped with a shielded cable tted with an RJ45 connector
3 Card interface that adapts the voltage delivered by the LPCT sensors,
AMTED398078EN.indd
AMTED398078EN.indd Sec:41
41
20/06/11 15:43
Generalities
DE58407
Description
b The EGX300 is an Ethernet-based device providing a simple transparent interface
between Ethernet-based networks and eld devices as protective relays (Sepam).
b The EGX300 has the ability to be used as a simple web based monitoring solution
providing real-time data views, on-board data logging/trending, and simple control
for eld devices.
b The DM range of circuit breakers cubicles with Sepam ranges and one EGX300
per switchboard for remote monitoring via the Intranet
b An RJ45 Ethernet connector on the front of the switchboard, directly accessible
from the front panel (option).
For other SM6 congurations (with other devices or other Sepam product ranges), it
is possible to integrate Web Remote Monitoring capability, consult your local
Schneider Electric correspondent.
Range selection
This chart presents the different SM6 24 kV cubicles proposed with an industrialised
Web Remote Monitoring system.
Functionalities provided
Description
Single-isolation circuit breaker unit
Single-isolation circuit breaker unit, right or left outgoing line
Withdrawable single-isolation circuit breaker unit
Withdrawable single-isolation circuit breaker unit, right outgoing line
Double-isolation circuit breaker unit, right or left outgoing line
Instantaneous readings
Displays automatically updated meter values
Circuit summary
Displays the RMS current 3-phase average (A), the real power
(kW), the power factor, the circuit breaker status (if applicable),
etc.
Load current summary
Displays the current RMS value for each phase (A),
for all circuits
Power summary
Displays the present demand (kW), the peak demand (kW)
and the times and dates of the records
Energy summary
Displays the energy (kWh) the reactive energy (kvarh),
and the times and dates of the records
Typical design
You need to have a Web server in only one CB unit to monitor the whole switchboard.
DE59215EN
Type of units
DM1-A, DMVL-A
DM1-D
DM1-W
DM1-Z
DM2
Sepam
Sepam
Sepam
Sepam
42
AMTED398078EN.indd Sec:42
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
Contents
AMTED398078EN.indd
AMTED398078EN.indd Sec:43
45
45
46
48
50
53
55
57
59
60
62
61
61
63
64
65
Operating mechanisms
66
Auxiliaries
69
71
73
74
76
77
Protection of transformers
78
Interlocks
80
43
20/06/11 15:43
44
AMTED398078EN.indd Sec:44
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
IM
Switch unit
IMC
Switch unit
DE53519
IMB
Switch unit with earthing switch
Right or left outgoing
DE53518
DE59700
Network connection
kA
DE59711
DE59710
Electrical characteristics
Ik/1s
25
kA
Ima
62.5
20
50
Ir = 630 A
Ir = 630 A
16
40
12.5
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
36
31.25
kV
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
36
kV
Basic equipment:
b
b
b
b
b
Versions:
b CI2 operating mechanism
b CI1 operating mechanism
Optional accessories:
b
b
b
b
b
b
b
b
b
b
b
b
b fault indicators
b Connection pads for two dry-type single-core cables for 36 kV
b digital ammeter
b surge arresters (for 36 kV and for 24 kV in 500 mm
wide cubicle)
AMTED398078EN.indd
AMTED398078EN.indd Sec:45
45
20/06/11 15:43
Characteristics of
the functional units
QM
Fuse-switch combination unit
QMC
Fuse-switch combination unit
DE53524
QMB
Fuse-switch combination unit
Outgoing line right or left
DE53523
DE59701
Fuse-switch protection
kA
DE59713
DE59712
Electrical characteristics
Ik/1s
kA
25
25
20
20
Ir = 200 A
Ir = 200 A
Ir =
63 A
16
12.5
12
17.5
24
36
Ir =
63 A
16
Ur
7.2
Isc
12.5
kV
Ur
7.2
12
17.5
24
36
kV
Basic equipment:
b
b
b
b
b
b
b
three-phase busbars
Version:
b equipment for three UTE striker fuses for 24 kV
b CI2 operating mechanism
Optional accessories:
b
b
b
b
b
b
b
b
b
b
b
b
b
b
auxiliary contacts
key-type interlocks
digital ammeter
cable connection by the top for 24 kV (no internal arc withstand if selected)
46
AMTED398078EN.indd Sec:46
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
Fuse-switch protection
DE53526
PM
Fused-switch unit
DE59714
Electrical characteristics
kA
25
20
Ir = 200 A
Ir =
63 A
16
12.5
Ur
7.2
12
17.5
24
36
kV
Basic equipment:
b
b
b
b
b
b
b
b
three-phase busbars
Version:
b CI1 operating mechanism
Optional accessories:
b
b
b
b
b
b
b
b
b
b
b
b
b
b
AMTED398078EN.indd
AMTED398078EN.indd Sec:47
47
20/06/11 15:43
CRM
Contactor unit
CRM
Contactor unit with fuses
Contactor protection
DE53528
DE53527
Characteristics of
the functional units
kA
DE59224
DE59223
Electrical characteristics
Ik/1s & Isc
kA
Isc
25
10
20
Ir = 250 A
16
Ir = 400 A
Ur
7.2
12
12.5
kV
Ur
7.2
12
kV
Basic equipment:
b
b
b
b
b
b
b
b
b
b
b
b
SF6 contactor
three-phase busbars
contactor operating mechanism with magnetic holding or contactor with mechanical latching
Optional accessories:
b
v
v
v
v
v
v
v
cubicle:
auxiliary contacts on the disconnector
protection using Sepam programmable electronic unit
one to three voltage transformers
key-type interlocks
50 W heating element
1250 A three-phase upper busbars
630 A three-phase upper busbars for severe operating conditions
b contactor:
v mechanical interlocking
b DIN striker fuses
48
AMTED398078EN.indd Sec:48
AMTED398078EN.indd
20/06/11 15:43
CVM
Disconnectable contactor unit
CVM
Disconnectable contactor unit with fuses
Contactor protection
DE53528
DE53527
Characteristics of
the functional units
kA
DE59221
DE59220
Electrical characteristics
Ik/1s & Isc
kA
Isc
25
10
20
Ir = 250 A
8
16
6.3
Ir = 400 A
Ur
7.2
12
12.5
kV
Ur
7.2
12
kV
Basic equipment:
b
b
b
b
b
b
b
b
b
b
b
b
b
vacuum contactor
three-phase busbars
contactor operating mechanism with magnetic holding or contactor with mechanical latching
Version:
b LPCT (only with Sepam series 20, series 40, series 80)
Optional accessories:
b
v
v
v
v
v
v
v
cubicle:
auxiliary contacts on the disconnector
protection using Sepam programmable electronic unit
one to three voltage transformers
key-type interlocks
50 W heating element
1250 A three-phase upper busbars
b contactor:
v mechanical interlocking
b DIN striker fuses
AMTED398078EN.indd
AMTED398078EN.indd Sec:49
49
20/06/11 15:43
Characteristics of
the functional units
DM1-A
Single-isolation
disconnectable CB unit
DM1-D
Single-isolation
disconnectable CB unit
Outgoing line on right
DM1-D
Single-isolation
disconnectable CB unit
Outgoing line on left
DE53533
DE53532
DE53531
kA
DE59213
DE59715
Electrical characteristics
Ik/1s & Isc
Ir =
1250 A
25
kA
25
20
20
Ir = 630 - 1250 A
Ir = 630 - 1250 A
16
16
12.5
12
17.5
24
12.5
Ur
36
kV
12
17.5
24
Ur
kV
Basic equipment:
b
b
b
b
b
b
b
b
b
b
Version:
b LPCT (only with Sepam series 20, series 40, series 80)
b SFset circuit breaker disconnectable (only for 400-630 A performances and 24 kV)
Optional accessories:
b cubicle:
v auxiliary contacts on the disconnector
v protection using Sepam programmable electronic unit
v three voltage transformers
v key-type interlocks
v 1250 A three-phase upper busbars at Ir 630 A
v cable connection by the top for 24 kV (no internal arc
withstand if selected)
v
v
v
v
v surge arresters
50
AMTED398078EN.indd Sec:50
AMTED398078EN.indd
20/06/11 15:43
DM1-S
Single-isolation
disconnectable CB unit
with independent protection
DM2
Double-isolation
disconnectable CB unit
Outgoing line on right
DE53537
DM2
Double-isolation
disconnectable CB unit
Outgoing line on left
DE53536
DE58360
Characteristics of
the functional units
25
kA
DE59213
kA
DE59715
DE59212-Isc
Electrical characteristics
Ik/1s & Isc
Ir =
1250 A
25
20
20
Ir = 630 - 1250 A
Ir = 630 - 1250 A
16
16
Ir = 400 - 630 A
7.2
12
17.5
25
20
Ir = 630 A
12.5
kA
Ur
24
16
12.5
kV
12
17.5
24
Ur
36
kV
12.5
12
17.5
24
Ur
kV
Basic equipment:
b
b
b
b
b
b
b
b
b
b
b
b
VIP relay
three CR sensors for VIP relay protection
voltage presence indicator
connection pads for dry-type cables
downstream earthing switch 2 kA rms making capacity
b three CTs
b 150 W heating element for 36 kV
Version:
b Sepam series 10 with auxiliary supply and
three CR sensors
Optional accessories:
b cubicle:
v three voltage transformers
v key-type interlocks
b
v
v
v
cubicle:
protection using Sepam programmable electronic unit
auxiliary contacts on disconnectors
2 voltage transformers phase-to-phase or 3 voltage transformers phase-to-earth
v
v
v
v
v
b
v
v
v
circuit breaker:
AMTED398078EN.indd
AMTED398078EN.indd Sec:51
51
20/06/11 15:43
Characteristics of
the functional units
DM1-W
Withdrawable single-isolation
circuit breaker unit
DM1-Z
Withdrawable single-isolation CB unit
Outgoing line on right
DM2-W
Withdrawable double-isolation CB unit
Outgoing line on right
DE59702
DE53539
DE53538
25
kA
DE59716
kA
DE59226
DE59715
Electrical characteristics
Ik/1s & Isc
25
20
25
20
Ir = 1250 A
16
16
12
17.5
24
Ur
36
kV
20
Ir = 630 - 1250 A
12.5
kA
16
12.5
Ur
7.2
12
17.5
24
kV
Ir =
630 - 1250 A
12.5
Ur
36
kV
Basic equipment:
b
b
b
b
b
b
b
b
b
b three-phase busbars
Version:
b LPCT (only with Sepam series 20, 40 and 80)
Optional accessories:
b
v
v
v
v
v
v
v
cubicle:
auxiliary contacts on the disconnector
protection using Sepam programmable electronic unit
three voltage transformers
key-type interlocks
connection enclosure for cabling from above for 24 kV
50 W heating element for 24 kV
enlarged low-voltage control cabinet for 24 kV
52
AMTED398078EN.indd Sec:52
b circuit breaker:
v motor for operating mechanism
v release units (coil)
v operation counter on manual
operating mechanism
b cubicle:
v auxiliary contacts on the disconnector
v key-type interlocks
v protection using Sepam
programmable electronic unit
b circuit breaker:
v motor for operating mechanism
v operation counter on manual
operating mechanism
v opening and closing shunt trips
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
DMV-S
Single-isolation circuit breaker unit
with independent protection
DE53543
DE53542
DMV-D
Single-isolation circuit breaker unit
Outgoing line on right
DE53541
DMV-A
Single-isolation
circuit breaker unit
DE59227
Electrical characteristics
kA
25
20
Ir = 630 - 1250 A
16
12.5
12
17.5
Ur
24
kV
Basic equipment:
b
b
b
b
b
b
b
b
b three CTs
Optional accessories:
b
v
v
v
v
v
v
v
v
cubicle:
b circuit breaker:
key-type interlocks
v operation counter on manual operating mechanism
50 W heating element
connection enclosure for cabling from above
1250 A three-phase upper busbars at Ir 630 A
630 A three-phase upper busbars for severe operating conditions
enlarged low-voltage control cabinet
AMTED398078EN.indd
AMTED398078EN.indd Sec:53
53
20/06/11 15:43
DMVL-A
Single-isolation disconnectable circuit breaker unit
DMVL-D
Single-isolation disconnectable circuit breaker unit
Outgoing line on right
DE59703
DE53535
Characteristics of
the functional units
kA
DE59717
DE59228
Electrical characteristics
Ik/1s & Isc
kA
25
25
20
20
Ir = 630 A
16
16
Ir = 630 A
12.5
Ur
7.2
12
17.5
24
kV
12.5
Ur
7.2
12
17.5
24
kV
Basic equipment:
b
b
b
b
b
b
b
b
b
b
Optional accessories:
b
v
v
v
v
v
v
v
v
v
v
cubicle:
b circuit breaker:
auxiliary contacts on the disconnector
v motor for operating mechanism
three voltage transformers
v release units (coil)
key-type interlocks
v operation counter on manual operating mechanism
50 W heating element
connection enclosure for cabling from above
1250 A three-phase upper busbars at Ir 630 A
630 A three-phase upper busbars for severe operating conditions
enlarged low-voltage control cabinet
Sepam relay protection
surge arresters
54
AMTED398078EN.indd Sec:54
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
MV metering
CM2
Voltage transformers unit for network
with insulated neutral system
DE53547
DE53546
CM
Voltage transformers unit for network
with earthed neutral system
DE59718
Electrical characteristics
kA
Ik/1s
25
20
Ir = 50 A
16
12.5
Ur
7.2
12
17.5
24
36
kV
Basic equipment:
b
b
b
b
b
b
b
b three-voltage transformers
(phase-to-earth)
Optional accessories:
b
b
b
b
b
b
b
AMTED398078EN.indd
AMTED398078EN.indd Sec:55
auxiliary contacts
mechanical signalling and auxiliary contact for blown fuses
1250 A three-phase upper busbars
cable connection by the top for 24 kV (no internal arc withstand if selected)
50 W heating element for 24 kV
630 A three-phase upper busbars for severe operating conditions for 24 kV
enlarged low-voltage control cabinet for 24 kV
55
20/06/11 15:43
Characteristics of
the functional units
GBC-A
Current and/or voltage measurements unit
Outgoing line on right
GBC-A
Current and/or voltage measurements unit
Outgoing line on left
GBC-B
Current and/or voltage measurements unit
DE53551
DE53550
DE53549
MV metering
DE59709
Electrical characteristics
kA
Ik/1s
Ir =
1250 A
25
20
Ir = 630 - 1250 A
16
12.5
12
17.5
24
Ur
36
kV
Basic equipment:
b
b
b
b
b
connection bars
three-phase busbars
Optional accessories:
b
b
b
b
56
AMTED398078EN.indd Sec:56
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
GBM
Connection unit
Outgoing line right or left
GEM
Extension unit VM6/SM6
DE58361
GIM
Intermediate bus unit
DE53552
DE53553
Casings
kA
DE59212
DE59709
Electrical characteristics
Ik/1s
Ir =
1250 A
25
kA
Ik/1s
25
20
20
Ir = 630 A
Ir = 630 - 1250 A
16
12.5
16
12
17.5
24
Ur
36
kV
12.5
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
kV
Basic equipment:
b connection bars
b three-phase busbars for outgoing lines right or left
b 150 W heating element for 36 kV
b three-phase busbars
b metallic envelop
b three-phase busbars for 36 kV
Optional accessories:
b 1250 A three-phase upper busbars at Ir 630 A
b enlarged low-voltage control cabinet for 24 kV
b cable connection by the top for 36 kV (no internal
arc withstand if selected)
AMTED398078EN.indd
AMTED398078EN.indd Sec:57
57
20/06/11 15:43
Characteristics of
the functional units
GAM2
Incoming-cable-connection unit
GAM
Incoming-cable-connection unit
DE53555
DE53554
Casings
kA
DE59709
DE59719
Electrical characteristics
Ik/1s
Ir =
1250 A
25
20
16
Ir = 400 - 630 A
12
17.5
Ir =
1250 A
20
Ir =
630 1250 A
7.2
Ik/1s
25
Ir = 630 A
12.5
kA
Ir = 630 - 1250 A
16
Ur
24
36
kV
12.5
12
17.5
24
Ur
36
kV
Basic equipment:
b
b
b
b
b
three-phase busbars
voltage presence indicator
connection pads for dry-type cables
connection bars
150 W heating element for 36 kV
b downstream earthing switch 25 kA rms making capacity
b operating mechanism CC for 24 kV
b operating mechanism CS1 for 36 kV
Optional accessories:
b
b
b
b
b
b
fault indicator
digital ammeter
1250 A three-phase upper busbars at Ir 630 A
enlarged low-voltage control cabinet for 24 kV
cable connection by the top for 24 kV (no internal arc withstand if selected)
50 W heating element for 24 kV
58
AMTED398078EN.indd Sec:58
b auxiliary contacts
b key-type interlocks
b surge arresters for 24 kV
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
Other functions
DE53558
EMB
Busbars earthing
compartment unit
DE53557
TM
MV/LV transformer unit
for auxiliaries
DE59704
SM
Disconnector unit
Ik/1s
Ir =
1250 A
25
kA
DE59212
kA
DE59718
DE59709
Electrical characteristics
Ik/1s
20
20
Ir = 630 - 1250 A
Ir = 630 A
Ir = 50 A
16
16
16
12.5
12
17.5
24
Ik/1s
25
25
20
kA
Ur
36
kV
12.5
Ur
7.2
12
17.5
24
36
kV
12.5
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
kV
Basic equipment:
b
b
b
b
b earthing switch
b connection bars
b operating mechanism CIT
b installation on 630 A IM 375 mm or
DM1-A units (except additional
enclosure or connection enclosure
for cabling from above)
b require an key-type interlocks
adapted to the switchboard network
Optional accessories:
b
b
b
b
b
b
b
auxiliary contacts
key-type interlocks
1250 A three-phase upper busbars at Ir 630 A
cable connection by the top for 24 kV (no internal arc withstand if selected)
enlarged low-voltage control cabinet for 24 kV
50 W heating element for 24 kV
630 A three-phase upper busbars for severe operating conditions for 24 kV
AMTED398078EN.indd
AMTED398078EN.indd Sec:59
b auxiliary contacts
59
20/06/11 15:43
Characteristics of
the functional units
NSM-cables
Cables power supply for
main incoming line (N)
and standby line (S)
NSM-busbars
Cables power supply for
main incoming line on left (N) and
busbars for standby line (S) on right
NSM-busbars
Busbars power supply for
main incoming line on left (N) and
cables for standby line (S) on right
DE53561
DE58401
DE53559
kA
DE59218
DE59212
Electrical characteristics
Ik/1s
kA
Ima
62.5
25
50
20
Ir = 630 A
Ir = 630 A
40
16
12.5
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
kV
31.25
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
kV
Basic equipment:
b
b
b
b
b
b
b
b
three-phase busbars
mechanical interlocking
additional enclosure
Optional accessories:
b
b
b
b
b
b
b
b
auxiliary contacts
key-type interlocks
50 W heating element
control and monitoring
visibility of main contacts
pressure indicator device
1250 A three-phase upper busbars
630 A three-phase upper busbars for severe operating conditions
60
AMTED398078EN.indd Sec:60
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
DE55991EN
Network back up
Vn
The transfer switch automatic control system gives automatic control and
management of sources in the MV secondary distribution network with voltage
presence detectors.
Voltage on SW1
0V
C
T1
Operating modes
Operating mode is selected using the Easergy T200 S conguration tool.
b Semi-Auto mode, SW1 XV SW2
C
TR SW2
T2
When the voltage disappears on the channel in service, the automatic control
O
switches to the other channel after a time delay T1. The automatic control does not
switch back, unless there is a voltage break on the new channel in service.
TR: transfer switch response time (< 180 ms - depending on
The automatic control only switches once from channel 1 or 2 to the back up channel.
b Setting of time delay before switching: congurable from 0.1 s
SW1
DE58362EN
DE55992EN
SW1
SW2
Generator back up
Switching sequence
Vn
Voltage on SW1
0V
1
T1
0
Vg
T2
0V
6s
Voltage on generator
TR
SW1
O
C
TR
SW2
T3
O
TR: transfer switch response time (< 180 ms - depending on
switchgear).
DE58363EN
Line
SW1
G
SW2
AMTED398078EN.indd
AMTED398078EN.indd Sec:61
61
20/06/11 15:43
NSM-cables
Cables power supply for
main incoming line (N)
and standby line (S)
NSM-busbars
Cables power supply for
main incoming line on left (N) and
busbars for standby line (S) on right
NSM-busbars
Busbars power supply for
main incoming line on left (N) and
cables for standby line (S) on right
DE59708
DE59707
DE59706
Characteristics of
the functional units
DE59720
Electrical characteristics
kA
25
20
16
Ir = 630 A
12.5
36
kV
Basic equipment:
b
b
b
b
b
b
b
b
b
Optional accessories:
b auxiliary contacts
b key-type interlocks
b telecontrol
62
AMTED398078EN.indd Sec:62
AMTED398078EN.indd
20/06/11 15:43
DE59726EN
Characteristics of
the functional units
Current
is required.
Execution time
b The automation systems can be switched on and off from the local operator panel
Id
Voltage
drop
In
Sectionaliser (SEC)
Time
DE56654
b Congurable parameters:
v Number of faults: from 1 to 4
v Execution time: from 20 s to 4 mins congurable
in 5 s steps
v Automation system valid/invalid.
SW1
The sectionaliser automation system opens the switch after a predened number of
faults (1 to 4) during the voltage dip in the reclosing cycle of the top circuit breaker.
b The automation system counts the number of times a fault current followed
by a voltage loss is detected. It sends an open order if:
v the switch is closed
v the fault has disappeared
v the MV supply is absent.
b The automation system is reset at the end of the execution time delay.
SW2
MT10013EN
The transfer switch automation system allows for the automatic control and
management of power supply sources in the MV secondary distribution network.
It is linked to voltage presence detectors VD23.
Operating modes
Vn
When the voltage is lost on the channel that is in use, the automation system
switches to the other channel after a time delay T1. The automation system returns
no data unless there is a loss of voltage on the new channel.
SW2 voltage
O
SW1 voltage
Vn
O
C
SW1
T1
T1
C
SW2
Switching sequence
SW1 voltage
Vn
b The MV supply on the priority channel is correct for the time delay T2.
The close order on the back-up channel is given once the opening of the channel
in use is reported.
O
C
O
T1
SW1
C
O
SW2
T2
AMTED398078EN.indd
AMTED398078EN.indd Sec:63
63
20/06/11 15:43
Characteristics of
the functional units
DE56655
The BTA (Bus Tie Automatism) is an automation system for switching sources
between two incoming lines (SW1 and SW2) and a busbar coupling switch (SW3).
SW1
SW3
SW2
It must be used in conjunction with voltage presence detectors and the fault current
detection function on the busbar incoming lines.
Operating mode
Operating mode is selected using Easergy T200 I conguration tool.
Normal position
SW1
SW3
SW2
Coupling sequence
b Coupling takes place if the following conditions are met:
v the automation system is switched on
v the switches on incoming channels SW1 and SW2 are closed
v the earthing switches SW1, SW2 and SW3 are open
v there is no voltage on an incoming line SW1 or SW2
v there is no fault current detection on SW1 and SW2
v there is no transfer interlock
v voltage is present on the other incoming line.
b The coupling sequence in standard mode is as follows:
v opening of the de-energised incoming line switch after a delay T1
v closing of the coupling switch SW3.
b The coupling sequence in Interlock on loss of voltage after coupling mode
is completed as follows:
v monitoring of the voltage stability for a delay T3
v opening of the coupling switch SW3 if this condition is not met
v locking of BTA automation system.
b The system returns to standard mode after coupling if:
v the return to SW1 or SW2 option is activated
v voltage on the channel has been normal for a delay T2
v the automation system is activated
v the automation system is not locked
v v there is no coupling interlock.
DE56656EN
Active coupling
V2
V1
SW2 voltage
SW1 voltage
O
F
O
T1
SW1
T3
F
O
SW3
T2
Congurable parameters:
b Operating mode
b Automatic return SW1/SW2
b Automation system on/off
b Delay before switching
T1: 100 ms to 60 s in 100 ms steps
b Delay before return
T2: 5 s to 300 s in 1 s steps
b Interlock delay on voltage loss
T3: 100 ms to 3 s in 100 ms steps
b Motorisation type: command time.
64
AMTED398078EN.indd Sec:64
If the voltage is lost on one busbar, the automation system opens the incoming line
(SW1 or SW2) and closes the coupling switch SW3. Coupling is conditional upon
After execution of the automation system in standard mode, the voltage presence
is checked for a congurable period. If the voltage is lost during this period,
the coupling switch SW3 is opened and the automation system interlocked.
Coupling interlock
A digital input can be used to prohibit the issuing of orders from the local operator
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
DE53729EN
PE56312
Easergy T200I
Easergy T200I
IM, DM1,
IM, DM1
IM, DM1, IM
IM, IM,
QM, QM
MV ring
Network control centre
Communication network
IM, IM,
QM, IM
IM, DM1, IM
Easergy T200I
Existing SCADA
Easergy L500
DE58403
Communication
network: radio,
PSTN, GSM/GPRS,
Ethernet
AMTED398078EN.indd
AMTED398078EN.indd Sec:65
65
20/06/11 15:43
Operating mechanisms
Characteristics of
the functional units
Units
b
b
b
IM, IMB
IMC
PM
QM
QMC, QMB
v
v
b
b
Circuit breaker
CC
b
b
P2
RI
b
b
NSM-cables, NSM-busbars
GAM
SM, TM
EMB
b Provided as standard
v Other possibility
(*) 1250 A version
CIT
CI1
CI2
CS1
Load-break switch
Fused switch
Closing
Opening
Load-break switch
Fuse switch combination
Closing
Opening
Disconnector
Hand lever
Hand lever
Motor
Motor
1 to 2 s
1 to 2 s
Remote control
network management
Hand lever
Push button
Motor
Coil
4 to 7 s
35 ms
Remote control
transformer protection
Earthing switch
Manual operating mode
Closing
Hand lever
Closing
Hand lever
Load-break switch
Fuse switch combination
Mechanism Closing
Opening
charging
Hand lever
Push button Push button
Motor
Coil
Coil
4 to 7 s
55 ms
35 ms
Remote control
network management, need of quick
reconguration (generator source, loop)
N/A
Closing
Opening
Hand lever
Hand lever
Hand lever
Unit applications
Main circuit switch
Opening
Hand lever
Opening
Hand lever
Closing
Opening
Hand lever
N/A
N/A
N/A
Hand lever
N/A
N/A
Closing
Hand lever
Opening
Hand lever
61029N
b Auxiliary contacts
v switch (2 O + 2 C) *,
b Mechanical indications
b Motor option
(*) Included with the motor option
66
AMTED398078EN.indd Sec:66
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
Operating mechanisms
61030N
b Earthing-switch function
b Auxiliary contacts
v switch (2 O + 2 C) *,
b Mechanical indications
b Opening releases
v shunt trip,
b Motor option
61031N
b Earthing-switch function
b Auxiliary contacts
v switch (2 O + 2 C) *,
b Motor option
61032N
61033N
b Auxiliary contacts
DM1-A, DM1-D, DM1-W, DM2, DMVL-A, DMVL-D, CVM and CRM without VT,
b Mechanical indications
Fuses blown in units CM, CM2 and TM.
b Auxiliary contacts
Earthing switch (1 O + 1 C).
AMTED398078EN.indd
AMTED398078EN.indd Sec:67
67
20/06/11 15:43
Characteristics of
the functional units
Operating mechanisms
PE57163
61035N
Undervoltage
SFset
Combinations
1
Combinations
4
b
b
b
b
b
68
AMTED398078EN.indd Sec:68
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
Auxiliaries
61036N
Un
DC
Power supply
(V)
24
AC (50 Hz)*
48
110
125
220
120
230
Motor option
(W)
(VA)
Operating time for CIT
Charging time for CI1, CI2
200
200
1 to 2 (s)
4 to 7 (s)
1 to 2 (s)
4 to 7 (s)
Opening releases
Shunt trip
Response time
Undervoltage
Pick-up
Hold
Response time
(W)
(VA)
(ms)
(W)
(VA)
(W)
(VA)
(ms)
200
250
300
300
300
35
400
35
750
280
550
50
45
40
400
55
750
160
4
45
Closing release
Shunt trip
Response time
(W)
(VA)
(ms)
200
250
300
300
300
55
PE57164
Un
DC
Power supply
(V)
24
(W)
(VA)
(s)
300
AC (50 Hz)*
48
110
125
220
120
230
Motor option
Charging time
380
15
15
(W)
(ms)
(W)
(VA)
(ms)
3
30
85
30
45
45
(W)
(VA)
(W)
(VA)
(ms)
160
Opening releases
Mitop (low energy)
Response time
Shunt trip
Response time
Undervoltage
Pick-up
Hold
Response time
180
280
550
50
55
40
10
55
Closing release
Shunt trip
Response time
(W)
(VA)
(ms)
85
180
65
65
AMTED398078EN.indd
AMTED398078EN.indd Sec:69
69
20/06/11 15:43
Characteristics of
the functional units
Auxiliaries
61035N
Threshold
Consumption
24/30
48/60
100/130
200/240
48/60
100/125
200/250
0.85 to 1.1 Ur
(VA or W)
180
Motor overcurrent
2 to 3 Ir during 0.1 s
Charging time
6 s max.
Switching rate
CH contact
10 A 240 V
Direct current
Threshold
Response time
to the circuit breaker at Ur
24
48
100/130
200/250
(Vdc)
24/30
48/60
100/130
200/250
Threshold
Consumption
0.7 to 1.1 Ur
(VA or W)
Response time
to the circuit breaker at Ur
50 ms 10
24
48
100/130
200/250
(Vdc)
24/30
48/60
100/130
200/250
Threshold
Consumption
0.85 to 1.1 Ur
(VA or W)
PE57842
auxiliary contacts),
Characteristics
Operating voltage
Rated current
Breaking capacity
Minimum
Maximum
Vdc
Vac
70
AMTED398078EN.indd Sec:70
48 V
480 V
10 A
60 W (L/R 150 ms)
700 VA (power factor 0.35)
125
680
20-41
250
640
20-40
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
b
b
ARM3
b
b
ARJP2
b
b
ARJP3
TLP130
CLP2
61040N
Transformer ARJP1/N2F
b characteristics according to IEC standard 60044-1
b single primary winding
b double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
10
20
30
50
75
100
150
200
Ith (kA)
1.2
2.4
3.6
10
10
10
10
t (s)
Measurement
and protection
5A
15 VA - class 0.5
5A
2.5 VA - 5P20
61040N
Transformer ARJP1/N2F
b characteristics according to IEC standard 60044-1
b single primary winding
b double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
50
100
Ith (kA)
10
t (s)
Measurement
and protection
150
200
1
5A
15 VA - class 0.5
5A
2.5 VA - 5P20
61041N
Transformer ARM3/N2F
b characteristics according to IEC standard 60044-1
b double primary winding
b single secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
10/20
20/40
50/100
100/200
200/400
300/600
Ith (kA)
12.5
12.5/21*
12.5/25*
12.5/25*
25
t (s)
0.8
Measurement and 5 A
protection
1A
5A
1 VA - 10P30
5 VA - 5P10
5 VA - 5P15
* For 5 A protection
50/100
100/200
200/400
300/600
Ith (kA)
14.5
25
25
25
t (s)
Measurement
and protection
AMTED398078EN.indd
AMTED398078EN.indd Sec:71
5A
30 VA - class 0.5
5A
5 VA - 5P15
7.5 VA - 5P15
5A
7.5 VA - 5P10
15 VA - 5P10
71
20/06/11 15:43
Characteristics of
the functional units
61042N
Transformer ARJP2/N2F
b characteristics according to IEC standard 60044-1
b single primary winding
b double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
50
Ith (kA)
25
t (s)
Measurement
and protection
100
200
400
600
1
5A
10 VA
class 0.5
15 VA
class 0.5
15 VA
class 0.5
15 VA
class 0.5
20 VA
class 0.5
5A
2.5 VA
5P20
2.5 VA
5P20
5 VA
5P20
5 VA
5P20
7.5 VA
5P20
61044N
Transformer ARJP3/N2F
b characteristics according to IEC standard 60044-1
b single primary winding
b double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
1000
Ith (kA)
25
PE55661
t (s)
1250
Measurement
and protection
1A
30 VA - class 0.5
1A
10 VA - 5P20
Measurement
and protection
5A
30 VA - class 0.5
5A
10 VA - 5P20
PE57162
5A
100 A
1250 A
22.5 mV
0.5
5P
400
40 kA 1 s
24 kV
50 kV
72
AMTED398078EN.indd Sec:72
5A
100 A
1250 A
22.5 mV
0.5
5P
250
25 kA 1 s
0.72 kV
3 kV
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
PE57222
50-100
Ith (kA)
16 - 20
25
t (s)
5A
30 VA
- class 0.5
5A
2.5 VA - 5 VA - 5P20
10 VA
- 5P20
Measurement
and protection
AMTED398078EN.indd
AMTED398078EN.indd Sec:73
TLP 130
TLP 190
5A
5A
1250 A
2500 A
Secondary output
22.5 mV @ 100 A
22.5 mV @ 100 A
0.5
0.5
5P
5P
250
400
25 kA 1 s
40 kA 1 s
0.72 kV
0.72 kV
3 kV
3 kV
73
20/06/11 15:43
Characteristics of
the functional units
CVM
b
b
b
b
TM
b
b
b
61045N
24
10/3
100/3
250
Accuracy class
0.5
30
15/3
15-20/3
30
20/3
30
30-50
17.5
10/3
100/3
250
Accuracy class
0.5
30
15/3
61046N
24
10
100
500
Accuracy class
0.5
50
15
20
PE55648
First secondary
Second secondary
74
AMTED398078EN.indd Sec:74
12
17.5
24
10/3
15/3
20/3
100/3 - 100/3
200
Accuracy class
0.5
30-50
100
Accuracy class
3P
Rated output
50
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
DE52402
DE53562
7.2
3.3
5.5
6.6
110
100
110
100
110
300
Accuracy class
0.5
100
24
10
220
Output (VA)
2500
15
20
2500
2500
4000
4000
DE58408
Surge arresters
For units IM500, DM1-A, DM1-W, GAM, DMV-A*, DMVL-A
In (A)
400/630
Un (kV)
7.2
10
12
17.5
24
Note: the rated voltage of the surge arrester is according to units rated voltage.
(*) limited up to 17.5 kV for DMV-A circuit breaker cubicles.
AMTED398078EN.indd
AMTED398078EN.indd Sec:75
75
20/06/11 15:43
Characteristics of
the functional units
PE57223
36
303
333
1003
1003 or 1103
450
Accuracy class
0.5
3P
30-50
30
36
30
33
100
100 or 110
700
Accuracy class
0.5
50-100
For units TM
Transformer VRC3/S1 (phase-to-phase)
b single primary winding
b single secondary
DE58408
36
30
220
1000
Surge arresters
For units IM, DM1-A, SM, GAM2
76
AMTED398078EN.indd Sec:76
In (A)
630
Un (kV)
36
AMTED398078EN.indd
20/06/11 15:43
Characteristics of
the functional units
Example:
Consider a 950 kW motor at 5 kV.
In =
P
pf
= 130 A
Id = 6 x In = 780 A
Then select the next higher value, i.e. 790 A.
For six 5-second starts per hour, select fuses
rated 200 A.
Note: the same motor could not be protected for 12 starts
per hour since the maximum service voltage for the required
250 A rated fuses is 3.3 kV.
Maximum service
voltage (kV)
20
12
1410
250
1290
250
250
250
1140
250
250
250
250
250
1030
250
250
250
250
250
250
890
250
250
250
250
250
250
790
200
250
250
250
250
250
710
200
200
200
250
250
250
640
200
200
200
200
200
250
610
200
200
200
200
200
200
540
160
200
200
200
200
200
480
160
160
160
200
200
200
440
160
160
160
160
160
200
310
160
160
160
160
160
160
280
125
160
160
160
160
160
250
125
125
125
160
160
160
240
125
125
125
125
125
160
230
125
125
125
125
125
125
210
100
125
125
125
125
125
180
100
100
100
100
100
125
170
100
100
100
100
100
100
3.3
6.6
11
3.3
6.6
Starting
current (A)
Rated operational
current (continous
duty) (A)
10
30
Id = 6 x Ie
Ie
1100
183
250
250
250
942
157
250
250
250
250
250
250
785
131
200
200
200
200
200
250
628
105
160
160
160
200
200
200
565
94
160
160
160
160
160
160
502
84
125
160
160
160
160
160
439
73
125
125
125
160
160
160
377
63
100
125
100
125
125
160
314
52
100
100
100
100
100
125
251
42
100
100
100
100
100
100
188
31
80
100
100
100
100
100
21
50
50
63
80
80
80
126
AMTED398078EN.indd
AMTED398078EN.indd Sec:77
77
20/06/11 15:43
Characteristics of
the functional units
Protection of transformers
PE57161
Fuse ratings for SM6 protection units such as PM, QM, QMB and QMC depend,
b service voltage
b transformer rating
v Fusarc CF fuses as per IEC 60.282.1 recommendation and dimensions are related
For fuse-switch combination unit type QM, QMB, QMC, refer only to the selection
table and reference list of fuses. For all other type of fuses, consult us.
Example: for the protection of a 400 kVA transformer at 10 kV, select either Solefuse
Please consult us for overloads and operation over 40C for France Transfo
Type of
fuse
Service
Transformer rating (kVA)
Rated
voltage
25
50
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 voltage
(kV)
(kV)
Solefuse (UTE NFC standards 13.100. 64.210)
5.5
6.3 16
31.5 31.5 63
63
63
63
63
7.2
10
6.3 6.3 16
16
31.5 31.5 31.5 63
63
63
63
15
6.3 6.3 16
16
16
16
16
43
43
43
43
43
63
20
6.3 6.3 6.3 6.3 16
16
16
16
43
43
43
43
43
63
24
Solefuse (general case, UTE NFC standard 13.200)
3.3
16
16
31.5 31.5 31.5 63
63
100 100
7.2
5.5
6.3 16
16
31.5 31.5 63
63
63
80
80
100 125
6.6
6.3 16
16
16
31.5 31.5 43
43
63
80
100 125 125
10
6.3 6.3 16
16
16
31.5 31.5 31.5 43
43
63
80
80
100
12
13.8
6.3 6.3 6.3 16
16
16
16
31.5 31.5 31.5 43
63
63
80
17.5
15
6.3 6.3 16
16
16
16
16
31.5 31.5 31.5 43
43
63
80
20
6.3 6.3 6.3 6.3 16
16
16
16
31.5 31.5 31.5 43
43
63
24
22
6.3 6.3 6.3 6.3 16
16
16
16
16
31.5 31.5 31.5 43
43
63
Fusarc CF and SIBA (1) (general case for QM, QMB and QMC cubicle according to IEC 62271-105)
7.2
3.3
16
25
40
50
50
80
80
100 125 125 160(1) 200(1)
5
10
16
31.5 40
40
50
63
80
80
125 125 160(1)
5.5
10
16
31.5 31.5 40
50
50
63
80
100 125 125 160(1) 160(1)
6
10
16
25
31.5 40
50
50
63
80
80
125 125 160(1) 160(1)
6.6
10
16
25
31.5 40
50
50
63
80
80
100 125 125 160(1)
10
6.3 10
16
20
25
31.5 40
50
50
63
80
80
100 100 125(1) 200(1)
12
11
6.3 10
16
20
25
25
31.5 40
50
50
63
80
100 100 125(1) 160(1)
13.8
6.3 10
16
16
20
25
31.5 31.5 40
50
50
63
80
80
100(1) 125(1) 125(1) 17.5
15
6.3 10
10
16
16
20
25
31.5 40
50
50
63
80
80
100(1) 125(1) 125(1)
20
6.3 6.3 10
10
16
16
25
25
31.5 40
40
50
50
63
80
100(1) 125(1) 24
22
6.3 6.3 10
10
10
16
20
25
25
31.5 40
40
50
50
80
80
100(1)
(2)
Fusarc CF for dry type transformers
30
10
10
16
20
25
31.5 31.5 50
50
63
63
36
31.5
10
10
16
20
25
25
31.5 50
50
63
63
33
6.3
10
16
20
25
25
31.5 40
50
50
63
34.5
6.3
10
16
20
25
25
31.5 40
50
50
63
Fusarc CF oil immersed type transformers (2)
30
10
10
16
20
25
31.5 31.5 40
40
50
63
36
31.5
10
10
16
20
25
31.5 31.5 40
40
50
63
33
10
10
16
20
25
25
31.5 31.5 40
40
50
34.5
10
10
16
20
25
25
31.5 31.5 40
40
50
78
AMTED398078EN.indd Sec:78
AMTED398078EN.indd
20/06/11 15:43
Protection of transformers
Characteristics of
the functional units
Fuses dimensions
DE53563
23
450
35
Ur
(kV)
Ir
(A)
L
(mm)
(mm)
Weight
(kg)
7.2
6.3 to 125
450
55
12
100
450
55
17.5
80
450
55
24
6.3 to 63
450
55
Ur
(kV)
Ir
(A)
L
(mm)
(mm)
Weight
(kg)
7.2
125
292
86
3.3
12
6.3
292
50.5
1.2
10
292
50.5
1.2
35
DE57467
23
L
33
33
24
36
16
292
50.5
1.2
20
292
50.5
1.2
25
292
57
1.5
31.5
292
57
1.5
40
292
57
1.5
50
292
78.5
2.8
63
292
78.5
2.8
80
292
78.5
2.8
2.8
100
292
78.5
6.3
442
50.5
1.6
10
442
50.5
1.6
16
442
50.5
1.6
20
442
50.5
1.6
25
442
57
2.2
31.5
442
57
2.2
40
442
57
2.2
50
442
78.5
4.1
63
442
78.5
4.1
80
442
86
5.3
10
537
50.5
1.8
16
537
50.5
1.8
25
537
57
2.6
31.5
537
78.5
4.7
40
537
78.5
4.7
50
537
86
6.4
63
537
86
6.4
Ir
(A)
L
(mm)
(mm)
Weight
(kg)
DE57467
SIBA
45
Ur
(kV)
7.2
12
AMTED398078EN.indd
AMTED398078EN.indd Sec:79
33
292
85
3.8
292
85
5.4
125
292
67
160
292
85
3.8
3.8
200
292
85
17.5
125
442
85
5.4
24
100
442
85
5.4
125
442
85
5.4
23
L
33
160
200
79
20/06/11 15:43
Characteristics of
the functional units
Interlocks
Switch units
Functional interlocks
These comply with IEC recommendation 62271-200 and EDF specication HN 64-S-41
(for 24 kV).
Unit interlock
Circuit-breaker units
Units
DE53565
A1
C1 C4 A3
b
A4
b
A5
50
P2
P3
P5
b
b
GAM
P1
b
b
b
NSM
52
CRM, CVM
SM
DM2, DM2-W
Key-type interlocks
A1 type
O
Outgoing units
Aim:
b to prevent the closing of the earthing switch on a transformer protection unit
unless the LV circuit breaker is locked in open or disconnected position.
DE53566
Interlock
C1 type
b to prevent the access to the transformer if the earthing switch for transformer
protection has not rst been closed.
S
DE53567
C4 type
S
O
MT20240EN
80
AMTED398078EN.indd Sec:80
free key
captive key
panel or door
AMTED398078EN.indd
20/06/11 15:43
DE53568
Characteristics of
the functional units
Interlocks
A3 type
Ring units
Aim:
b to prevent the closing of the earthing switch of a load-side cubicle
unless the line-side switch is locked open.
DE53569
A4 type
DE53570
A5 type
b to prevent the closing of the earthing switch of the casing unit unless
the downstream and the upstream switches are locked in the open position.
DE53571
O
S
50 type
Prevents
b on-load switching of the disconnectors.
O O
Allows
b off-load operation of the circuit breaker with the disconnectors open (double isolation).
b off-load operation of the circuit breaker with the disconnector open (single isolation).
DE59203
Type 52
Prevents
b on-load switching of the disconnectors.
O O
Allows
b off-load operation of the contactor with the disconnectors open (double isolation).
b off-load operation of the contactor with the disconnector open (single isolation).
MT20240EN
AMTED398078EN.indd
AMTED398078EN.indd Sec:81
free key
captive key
panel or door
81
20/06/11 15:43
Interlocks
DE53572
Characteristics of
the functional units
P1 type
O
DE53573
b to prevent the closing of an earthing switch if the switch of the other unit
has not been locked in the open position.
b to prevent on-load operation of the disconnector unless the switch is locked open
b to prevent the closing of the earthing switches unless the disconnector and
the switch are locked open.
P2 type
X
DE53574
P3 type
AX
DE53575
b to prevent on-load operation of the disconnector unless the switch is locked open
b to prevent the closing of the earthing switches with the unit energised, unless
b to prevent the closing of the earthing switch of the incoming unit unless
the disconnector and the switch is locked open.
P5 type
P
MT20240EN
82
AMTED398078EN.indd Sec:82
free key
captive key
panel or door
AMTED398078EN.indd
20/06/11 15:43
Connections
Contents
AMTED398078EN.indd
AMTED398078EN.indd Sec:83
84
84
85
85
86
87
88
89
89
90
90
83
20/06/11 15:43
Connections
Selection table
PE57840
PE50775
b square connection round shank for cables > 240 mm2 only.
Access to the compartment is interlocked with the closing of the earthing disconnector.
A 12 mm pin integrated with the eld distributor enables the cable end terminal
to be positioned and attached with one hand. Use a torque wrench set to 50 mN.
PE50776
Round connector
Square connector
X-section mm2
Supplier
Number of cables
Comments
3 to 24 kV
400 A - 630 A
Round connector
50 to 240 mm2
1 or 2 per phase
3 to 24 kV
1250 A
Round connector
50 to 630 mm2
1 or 2 per phase
y 400 mm2
Square connector
Performance
X-section mm2
Supplier
Number of cables
Comments
3 to 24 kV
400 A - 630 A
Round connector
50 to 240 mm2
1 per phase
3 to 24 kV
1250 A
Round connector
50 to 630 mm2
1 per phase
Note:
b The cable end terminals, covered by a eld distributor, can be square,
b PM/QM type cubicle, round end connections 30 mm max.
84
AMTED398078EN.indd Sec:84
AMTED398078EN.indd
20/06/11 15:43
Connections
Cable positions
945
SM
945
IMC
400
PM, QM
400
QMC
400
CRM, CVM
430
DM1-A
430
DMVL-A
430
DMV-S
320
DM1-W
370
GAM2
760
1250 A
CRM, CVM
945
320
320
GAM
470
620
DMV-A
320
313
DM1-S
543
GAM2
GAM
200 200
420
200 200
420
200 200
420
DE53581
DE53580
DE53579
630 A
IM, NSM-cables, NSM-busbars
DE53576
IM, NSM-cables,
NSM-busbars, SM
DE53578
Cable-connection height H
measured from oor (mm)
200 200
420
200 200
420
DMV-A (1250 A)
DE58417
DE53582
275
165 165
313
333
200 200
420
510,5
330
789
200 200
420
145 145
445
371,5
X
313
AMTED398078EN.indd
AMTED398078EN.indd Sec:85
85
20/06/11 15:43
Connections
Trenches depth
DE53585
b With oor void: the trench depth P is given in the table opposite for commonly
625
500
375
50
70
95
120
150
185
240
400
630
187.5
Bending
radius
(mm)
IM,
SM,
NSM-cables,
NSM-busbars
1250 A units
IMC, DM1-A,
DM1-W,
DM1-S,
DMVL-A,
GAM
370
400
440
470
500
540
590
800
940
CRM
CVM
DMV-A,
DMV-S
PM,
QM,
QMC (1)
SM,
GAM
DM1-A (2)
DM1-W (2)
DMV-A (3)
P2
400
430
470
500
P2
500
530
570
600
650
770
830
P3
350
350
350
P4
P5
P6
1000
1000
1350
1350
1450
1450
In double-trench installations, depth P must be taken into account for each type of unit
140
630 A units
DMV-A, DMV-S
For single cables
140
DE53589
DM1-A, DM1-W
For single-core cables
DE58350
DE53587
DE53586
140
140
80
50
740
50
50
50
740
740
740
100
445
P4
P2
P5
P6
480
600
86
AMTED398078EN.indd Sec:86
600
840
600
AMTED398078EN.indd
20/06/11 15:43
Connections
DE58410
DE58411
630 A units
Rear entry or exit
with conduits
DE58409
630 A units
Cable entry or exit
through right or left side
140
140
80
80
140
P1
P1
P2
P2
P3
600
22
IM
70
22
22
IM
QMC
IM
IM
IM
DM1
DM1
IM
Note 1: for connection with conduits, the bevel (C) must correspond to the following
trench dimensions: P1 = 75 mm or P2/P3 = 150 mm.
Note 2: please refer to chapter Layout examples for a site application.
PE50797
On each 630 A unit of the range, except those including a low-voltage control cabinet
and EMB compartment, the connection is made with dry-type and single-core cables.
Remark : not available for internal arc IEC 62271-200 in busbar compartment.
AMTED398078EN.indd
AMTED398078EN.indd Sec:87
87
20/06/11 15:43
Connections
Downwards exhaust
Upwards exhaust
DE58413
Installation with
trench
DE58412
Installation with
oor void
220
100
P1
200
600
220
740
1060
1060
22
22
IM
200
IM
200
IM
DM1-A
IM
DM1-A
Note: to evacuate gases through the bottom, the oor void volume must be over
or equal to 2 m3.
88
AMTED398078EN.indd Sec:88
AMTED398078EN.indd
20/06/11 15:43
Connections
Selection table
Single-core cables
Bending
Cable
radius
section
(mm)
(mm2)
Units 630 A
IM, IMC, QM, CM, CM2,
PM, DM1-A, DM1-W,
GAM, GAM2, SM, TM, NSM
Depth P (mm)
P1
P2
1 x 35
525
350
550
1 x 50
555
380
580
1 x 70
585
410
610
1 x 95
600
425
625
1 x 120
630
455
655
1 x 150
645
470
670
1 x 185
675
500
700
1 x 240
705
530
730
b ventilation control
The dimension of the grills must be appropriate for the power dissipated
in the substation. They must only traverse the transformer area.
Network cables are connected:
b on the switch terminals
b on the lower fuse holders
Access to the compartment is interlocked with the closing of the earthing disconnector.
A 12 mm pin integrated with the eld distributor enables the cable end terminal
to be positioned and attached with one hand. Use a torque wrench set to 50 mN.
Note: the unit and the cables requiring the greatest depth
must be taken into account when determining the depth P
for single-trench installations. In double-trench installations
must be taken into account to each type of unit and cable
orientations.
Trench diagrams
100
100
P2
300
IM
100
AMTED398078EN.indd
AMTED398078EN.indd Sec:89
100
QM
100
200
200
P2
300
1000
1000
IM
100
P1 P2
200
QM
DE59724
DE59723
100
200
1000
QM
100
IM
IM
IM
IM
100
100
100
200
100
89
20/06/11 15:43
Connections
Cable positions
Side view
GAM2 unit
DE59730
DE59728
QM, PM units
DE59727
IM, SM units
1210
632
475
632
400
350
350
700
350
350
380
700
700
700
380
350
350
Front view
QMC
GAM
GAM2
QM, PM
DM1-A, DM1-W
375
375
750
90
AMTED398078EN.indd Sec:90
1000
470
750
375
750
430
540
620
490
620
1200
DE59731
IM, SM
375
510
750
1000
AMTED398078EN.indd
20/06/11 15:43
Installation
AMTED398078EN.indd
AMTED398078EN.indd Sec:91
Contents
92
93
95
96
97
91
20/06/11 15:43
Installation
Height
(mm)
1600 (1)
Width
(mm)
375/500
Depth
(mm)
940
Weight
(kg)
120/130
IMC
1600 (1)
500
940
200
1600 (1)
375/500
940
130/150
QMC
1600 (1)
625
940
180
CRM, CVM
2050
750
940
390
1600 (1)
750
1220
400
DM1-S
1600 (1)
750
1220
340
DMV-A, DMV-D
1695 (1)
625
940
340
DMV-S
1600 (1)
625
940
260
CM
1600 (1)
375
940
190
CM2
1600 (1)
500
940
210
GBC-A, GBC-B
1600
750
1020
290
NSM-cables, NSM-busbars
2050
750
940
260
GIM
1600
125
840
30
GEM (2)
1600
125
GBM
1600
375
940
120
GAM2
1600
375
940
120
GAM
1600
500
1020
160
SM
1600 (1)
375/500 (3)
940
120/150 (3)
TM
1600
375
940
200
750
1220
420
Add to height:
(1) 450 mm for low-voltage enclosures for control/monitoring and protection functions.
To ensure uniform presentation, all units (except GIM and GEM) may be equipped with
low-voltage enclosures.
(2) depending on the busbar conguration in the VM6 unit, two types of extension units
may be used:
b to extend a VM6 DM12 or DM23 unit, use an extension unit with a depth of 1060 mm
Ground preparation
Units may be installed on ordinary concrete ground, with or without trenches
depending on the type and cross-section of cables.
a
b
Fixing of units
15
DE53595
15
50
740
840
12.3 x 12.3
92
AMTED398078EN.indd Sec:92
On the ground
b for switchboards comprising up to three units, the four corners of the switchboard
v M8 bolts (not supplied) screwed into nuts set into the ground using a sealing pistol,
b for switchboards comprising more than three units, each unit may be xed as
necessary.
a (mm)
125
375
500
625
750
b (mm)
95
345
470
595
720
AMTED398078EN.indd
20/06/11 15:43
IM, IMB, PM, QM, QMB, SM, IMC, QMC, CM, CM2
450
450
1600
840
1600
1600
840
30
70
840
30
70
DE53601
140
840
30
70
920
EMB
450
DE58414
GBC-A, GBC-B
DE59229
1600
1600
1600
840
30
70
GEM
DE53600
GIM
DE53599
GAM
80
GBM, GAM2
DE53598
DE53597
DE53596
Installation
503
1600
80
840
AMTED398078EN.indd
AMTED398078EN.indd Sec:93
100
93
20/06/11 15:43
450
1600
80
1680
1600
200
100
840
DE58415
450
DMV-A 1250 A
DE53604
DE53603
Installation
330
840
DE53607
1600
1680
1680
100
100
150
150
85
840
100
DMV-S
DE53606
DMV-D
DE53605
DMV-A 630 A
74
200
100
832
840
80
85 445
85
85
100
840
100
100
DE53608
840
450
600
450
1600
220
94
AMTED398078EN.indd Sec:94
1600
220
AMTED398078EN.indd
20/06/11 15:43
Installation
PE57168
DE58416EN
940
200
22 (minimum)
1200 (*)
DE53611
DE53612
1160
200
1200 (*)
600 (min.)
600
1 600
AMTED398078EN.indd
AMTED398078EN.indd Sec:95
95
20/06/11 15:43
Installation
Height
(mm)
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
IM, SM
IMC, IMB
QM, PM, QMB
QMC
DM1-A
DM1-D
DM1-W
NSM
GIM
DM2
DM2-W
CM, CM2
GBC-A, GBC-B
GBM
GAM2
GAM
(1) The depth measures are given for the oor surface.
(2) The depth in these units are 1615 mm with the enlarged
low voltage compartment.
(3) The depth in these units are 1500 mm with the standard
low voltage compartment.
Depth (1)
(mm)
1400 (3)
1400 (2)
1400 (3)
1400 (3)
1400 (2)
1400 (2)
1400 (2)
1400 (2)
1400
1400 (2)
1400 (2)
1400 (2)
1400 (3)
1400 (3)
1400 (3)
1400 (3)
Width
(mm)
750
750
750
1000
1000
1000
1000
1500
250
1500
1500
750
750
750
750
750
Weight
(kg)
310
420
330
420
600
560
660
620
90
900
920
460
420
260
250
295
Ground preparation
Units may be installed on ordinary concrete grounds, with or without trenches
Fixing of units
With each other
The units are simply bolted together to form the MV switchboard (bolts supplied).
Busbar connections are made using a torque wrench set to 28 mN.
On the ground
b for switchboards comprising up to three units, the four corners of the switchboard
must be secured to the ground using:
v bolts (not supplied) screwed into nuts set into the ground using a sealing pistol
v screw rods grouted into the ground
b for switchboards comprising more than three units, the number and position of
xing points depends on local criteria (earthquake withstand capacities, etc.)
b position of xing holes depends on the width of units.
150
50
DE5961
1100
1400
Unit type
150
14.2 x 25
A (mm)
B (mm)
750
650
1000
900
1500
1400
GIM
250
150
Dimensions
215
2250
1400
96
AMTED398078EN.indd Sec:96
32
100
DE59663
DE59662
215
2250
2250
1400
32
1400
32
230
AMTED398078EN.indd
20/06/11 15:43
Installation
DE59665
DE59666
Top view
100
100
2550
2650
5200 min.
(2)
(1)
min.
min.
1770 min.
100
100
100
DE59667
Top view
3430 min.
100
1715 min.
100
AMTED398078EN.indd
AMTED398078EN.indd Sec:97
97
20/06/11 15:43
98
AMTED398078EN.indd Sec:98
AMTED398078EN.indd
20/06/11 15:43
Appendices
Order form
Contents
Appendices
100
101
Fusarc CF fuses
102
Solefuse fuses
103
Order form
AMTED398078EN.indd
AMTED398078EN.indd Sec:99
104
105
106
SM6 - MV metering
108
SM6 - Casing
109
110
111
112
113
114
115
99
20/06/11 15:43
DE53614
Appendices
t>
t>
t >>
t >>
Is 1.2 Is
10 Is
I >>
Is 1.2 Is 10 Is
I >>
SI curve
t (s)
DE53615
t (s)
100
100
10
10
1
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
0.1
0.1
I/Is
0.01
1 1.2
10
I/Is
0.01
1 1.2
100
EI curve
10
100
RI curve
t (s)
DE53616
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
t (s)
1000
10
100
1
10
0.6
0.4
0.3
0.2
0.15
1
0.1
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
0.1
0.01
1 1.2
100
AMTED398078EN.indd Sec:100
10
I/Is
100
0.1
0.07
0.05
I/Is
0.01
1
10
100
AMTED398078EN.indd
20/06/11 15:43
Appendices
DE53617EN
10
0.1
Type
0.01
I/Is
0 1.2
AMTED398078EN.indd
AMTED398078EN.indd Sec:101
10
15
20
25
30
101
20/06/11 15:43
Fusarc CF fuses
Appendices
250 A
160 A
125 A
100 A
31.5 A
40 A
50 A
63 A
80 A
10 A
16 A
20 A
25 A
4A
1000
8
6
4
6.3 A
DE53618
Time (s)
8
1000
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
2
10
100
10000
Current (A)
100
Ia
8
1.
Ik
Is
Ik
2
250 A
200 A
160 A
125 A
100 A
80 A
63 A
50 A
40 A
10
31.5 A
25 A
20 A
16 A
10 A
6.3 A
2
4A
0.1
0.1
10
100
102
AMTED398078EN.indd Sec:102
AMTED398078EN.indd
20/06/11 15:43
Solefuse fuses
Appendices
1000
8
6
4
16 A
20 A
25 A
31.5 A
43 A
63 A
80 A
6.3 A
10 A
DE53620
Time (s)
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
2
10
100
8
1000
10000
Current (A)
DE53621
Ia
8
1.
Ik
Is
Ik
2
125 A
100 A
80 A
63 A
10
43 A
31.5 A
25 A
20 A
16 A
10 A
6.3 A
2
0.1
0.1
10
100
AMTED398078EN.indd
AMTED398078EN.indd Sec:103
103
20/06/11 15:43
Order form
SM6
Connection to the network
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
Type of cubicle
24 kV
SM 375
IM 375
IM 500
IMC 500
IMB 375
SM 750
IM 750
IMC 750
Position number in the switchboard (from left to right)
IMB 750
36 kV
Right
Options
Common options
Replacement of CIT by
Electrical driving motorization
and/or coil voltage
(not applicable on SM cubicle)
Signalling contact
CI1
CI2
24 Vdc
110 Vdc
32 Vdc
120-125 Vdc
48 Vdc
137 Vdc
60 Vdc
220 Vdc
Interlocking
A3 SM6-SM6
P1 SM6-SM6
On switch
On earthing switch
Cubicle no.
SM cubicle only
P3 SM6-SM6
P2 SM6-SM6
Replacement of 630 A upper busbar by 1250 A (not possible for IMB)
Internal arc version 16 kA 1 s (not possible with top incomer option)
Digital ammeter or
fault current indicator
AMP 21D
Flair 21D
Flair 22D
Flair 23DV
24 kV options
Remote control signalling
2 lights
2 lights and 2 PB
Voltage of the lights (must be the same than electrical driving mechanism)
24 V
48 V
110/125 V
Roof conguration (A, B or C only one choice possible)
220 V
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
B - Low voltage control cabinet (h = 450 mm)
2 x single core
With unpunched door
C - Wiring duct
Cable connection by the bottom (not applicable on IMB, cable maxi 240 mm2)
Three core
Single core
2 x single core
12 kV
17.5 kV
24 kV
50 W heating element
Surge arresters for IM 500
7.2 kV
10 kV
Operation counter
CTs for IMC (quantity)
Visibility of main contacts
Pressure indicator device
Pressure switch
Analogic manometer with visibility of main contacts
Upper eld distributor for severe conditions (only for 630 A)
36 kV options
Electrical driving mechanism (with O/C coils and AC contacts)
O/C coils without electrical driving mechanism
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Cable connection by the bottom (2 x single core, cable maxi 240 mm2, not applicable on IMC)
Surge arresters (not applicable on IMB, IMC cubicles)
36 kV
104
AMTED398078EN.indd Sec:104
AMTED398078EN.indd
20/06/11 15:43
Order form
SM6
Fuse switch protection
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
Type of cubicle
24 kV
QM 375
QMB 375
QMC 625
PM 375
36 kV
QM 750
QMB 750
QMC 1000
Position number in the switchboard (from left to right)
PM 750
QM 500
Right
Options
Common options
Fuses (see fuse price structure)
Service voltage y 12 kV
Replacement of mechanism
Shunt trip
24 Vdc
110 Vdc
32 Vdc
120-125 Vdc
48 Vdc
137 Vdc
60 Vdc
220 Vdc
24 Vdc
110 Vdc
32 Vdc
120-125 Vdc
48 Vdc
137 Vdc
60 Vdc
220 Vdc
1 C on SW and 1 O & 1 C on ES
2 O & 2 C on SW
Interlocking
A1
C4
C1
24 kV options
Replacement of mechanism
48 V
110/125 V
220 V
Blown fuse signalling contact (mechanical indication PM, electrical for the other cubicles)
Roof conguration (A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
B - Low voltage control cabinet (h = 450 mm)
2 x single core
With unpunched door
C - Wiring duct
50 W heating element
Operation counter
Digital ammeter (not applicable for QMB)
AMP21D
Pressure switch
Analogic manometer with visibility of main contacts
Field distributor for severe conditions (only for 630 A)
Internal arc version 16 kA 1 s (not possible with top incomer option)
36 kV options
Replacement of mechanism
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
AMTED398078EN.indd
AMTED398078EN.indd Sec:105
105
20/06/11 15:43
Order form
SM6
Circuit breaker protection
Basic cubicle
Quantity
Common 24/36 kV
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
Type of cubicle
24 kV For SF1 circuit breaker
DM1-A 750
DM1-S 750
DM1-Z 750
DM1-W 750
DMV-S
DMV-D right
DMV-A
DMVL-A
DMVL-D
DM1-A 1000
DM1-W 1000
Basic 24 kV
Busbar (Ir u Ir cubicle)
For DM1-A, DM1-S, DM1-W, DMVL-A, DMVL-D ,DM1-D, DM2
400 A
630 A
1250 A
630 A
1250 A
For DMV-S
630 A
1250 A
Protection
For DM1-S, DMV-S
For DM1-S
Statimax 5 A, 2 s
Statimax 1 A, 2 s
48/60 Vdc
Voltage of signalling
48/60 Vdc
110/125 Vdc
220/250 Vdc
220/240 Vac (50 Hz)
Basic 36 kV
Voltage of the auxiliaries
48/60 Vdc
Voltage of signalling
48/60 Vdc
110/130 Vac (50 Hz)
Options
106
AMTED398078EN.indd Sec:106
110/125 Vdc
220/250 Vdc
220/240 Vac (50 Hz)
See following page
AMTED398078EN.indd
20/06/11 15:43
Order form
SM6
Circuit breaker protection (cont.)
Options
Common options
Interlocking
C1
C4
24 kV options
Roof conguration (not applicable on DMV-A, DMV-S, DMV-D)
(A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
2 x single core
1 set
2 sets
DM2
B - Low voltage control cabinet
DM2
C - Wiring duct
1 cabinet
2 cabinets
DM2
1 set
Other cubicles
1 set
2 sets
Surge arrester
50 W heating element
Replacement of 630 A upper busbars 400-630 A by 1250 A
Field distributor for severe conditions (only for 630 A)
Internal arc version 16 kA 1 s (not possible with top incomer option)
36 kV options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Cable connection by the bottom (for DM1-A and DM1-W only)
3 x 2 x single core cable maxi 240 mm2
Surge arrester
Sepam relay protection
AMTED398078EN.indd
AMTED398078EN.indd Sec:107
36 kV
See specic order form
107
20/06/11 15:43
Order form
SM6
MV metering
Basic cubicle
Quantity
Common 24/36 kV
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
CM
CM2
TM
GBC-A
GBC-B
CM
CM2
TM
GBC-A
GBC-B
CM
CM2
TM
GBC-A
GBC-B
GBC-A
GBC-B
CM 750
CM2 750
GBC-A 750
TM 750
GBC-B 750
Right
1 O and 1 C on SW
See fuse price structure
Basic 24 kV
VTs for GBC (to see price structure)
CTs for GBC (to see price structure)
Phase/phase
Quantity
Phase/earth
2
1 secondary
1 high secondary
2 secondaries
1 low secondary
Basic 36 kV
Voltage transformers
Options
24 kV options
Roof conguration (A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
B - Low voltage control cabinet (h = 450 mm)
C - Wiring duct
2 x single core
With unpunched door
1 O and 1 C
36 kV options
Current transformers and voltage transformers for GBC
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
108
AMTED398078EN.indd Sec:108
AMTED398078EN.indd
20/06/11 15:43
Order form
SM6
Casing
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
GAM 500
GAM2 375
GAM 500
GAM2 375
GAM 500
GBM 375
GBM 375
GBM 375
GAM 750
GAM2 750
GBM 750
Right
Options
24 kV options
Roof conguration (A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
B - Low voltage control cabinet (h = 450 mm)
2 x single core
With unpunched door
C - Wiring duct
Wiring duct for GBM
ES auxiliary contact (only on GAM 500)
1 O and 1 C
10 kV
12 kV
17.5 kV
24 kV
Round key type
A3 SM6-SM6
Localisation of 2nd lock for P5
P5 SM6-SM6
Cubicle no.
Flair 21D
Flair 22D
Internal arc version 16 kA 1 s (not possible with top incomer option)
Flair 23DV
36 kV options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Replacement of 630 A busbar by 1250 A (for GAM2 only)
Surge arresters for GAM2
AMTED398078EN.indd
AMTED398078EN.indd Sec:109
109
20/06/11 15:43
Order form
SM6
Automatic Transfer System
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
NSM busbar
NSM cable
NSM busbar
NSM cable
NSM cable
NSM busbar
NSM cable
Stand by source
Right
English
Spanish
Portuguese
Chinese
Options
Common options
Signalling contact
1 C on SW and 1 O & 1C on ES
Operation counter
Interlocking SM6-SM6
Right cubicle
2 x P1
Left cubicle
Right and left cubicle
1 x A3
Right cubicle
Left cubicle
On switch
On earthing switch
2 x A3 Right cubicle
On switch
On earthing switch
Left cubicle
On switch
On earthing switch
IEC 101/204
FFSK
RS485
PSTN
GSM
FSK
Telecontrol
Protocol type
Modem type
DNP3
24 kV options
2 heating elements
110
AMTED398078EN.indd Sec:110
AMTED398078EN.indd
20/06/11 15:43
Order form
SM6
Vacuum contactor motor starter
for SM6 24 kV
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
7.2
(A)
Busbar Ir
Phase current sensors
400 A
630 A
1250 A
1 CT
2 CT
3 CT
Options
MV fuses
50 A
63 A
80 A
100 A
125 A
160 A
200 A
Upper eld distributor for severe conditions (only for 630 A busbar)
25 A
250 A
31.5 A
40 A
Contactor
Vacuum contactor
Open release
Closing coil
AMTED398078EN.indd
AMTED398078EN.indd Sec:111
Magnetic hold
Mechanical latching
48 Vdc
125 Vdc
250 Vdc
110 Vac/dc
120 Vac/dc
125 Vac/dc
220 Vac/dc
240 Vac/dc
250 Vac/dc
111
20/06/11 15:43
Order form
SF1
Lateral disconnectable or withdrawable
by
Only one of the boxes (ticked X or lled
the needed value) have to be considered between each
horizontal line.
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
Impulse voltage Up
(kVbil)
(kA)
Rated current Ir
(A)
Frequency
Mechanism position
60 Hz
50 Hz
A1
B1
Disconnectable
Withdrawable
B1
60 Vdc
220 Vdc
30 Vdc
110 Vdc
125 Vdc
48 Vdc
Undervoltage release YM
24 Vdc
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
Mitop
125 Vdc
Without contact
With contact
60 Vdc
220 Vdc
30 Vdc
110 Vdc
125 Vdc
48 Vdc
Undervoltage release YM
24 Vdc
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
Mitop
125 Vdc
Without contact
With contact
Remote control
Electrical motor M
2432 Vdc
110127 Vdc/ac
4860 Vdc/ac
220250 Vdc/ac
220 Vac (50 Hz)
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
125 Vdc
French
English
Leaets language
112
AMTED398078EN.indd Sec:112
1
1
1
1
1
1
1
1
1
AMTED398078EN.indd
20/06/11 15:43
Order form
SFset
Lateral disconnectable
for SM6 24 kV
by
Only one of the boxes (ticked X or lled
the needed value) have to be considered between each
horizontal line.
Green box X corresponds to none priced functions.
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
Impulse voltage Up
(kVbil)
(kA)
Rated current Ir
630 A maximum
Frequency
60 Hz
50 Hz
A1
B1
Mechanism position
Colour for push buttons and indicators
Push buttons open/close: Red/black
Indicator open/close: Black/white
Operating mechanism charged/discharged: White/yellow
CSa 200/1
Is = 10 to 50 A
Is = 40 to 200 A
electrical characteristics)
CSb 1250/1
Is = 63 to 312 A
Is = 250 to 1250 A
VIP 300LL
CSa 200/1
Is = 10 to 50 A
Is = 40 to 200 A
CSb 1250/1
Is = 63 to 312 A
Is = 250 to 1250 A
60 Vdc
220 Vdc
30 Vdc
110 Vdc
125 Vdc
48 Vdc
Undervoltage release YM
24 Vdc
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
125 Vdc
Remote control
Electrical motor M
2432 Vdc
110127 Vdc/ac
4860 Vdc/ac
220250 Vdc/ac
220 Vac (50 Hz)
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
125 Vdc
French
English
AMTED398078EN.indd Sec:113
1
1
1
1
113
20/06/11 15:43
Order form
Evolis
Frontal fixed version
for SM6 24 kV (up to 17.5 kV)
Quantity
12
17.5
Service voltage
(kV)
25 kA
630
1250
Phase distance
185 mm
2430 Vdc
100130 Vdc/ac
48 Vac
Low energy release Mitop
4860 Vdc
200250 Vdc/ac
100125 Vdc
200250 Vdc
4860 Vdc/ac
Shunt closing release XF
100130 Vac
200240 Vac
24 Vac
2430 Vdc
100130 Vdc/ac
48 Vac
4860 Vdc
200250 Vdc/ac
If locks
2 identical locks
1 lock
Disabling of O/C circuit breaker push buttons
114
AMTED398078EN.indd Sec:114
1
1
2 different locks
1
1
AMTED398078EN.indd
20/06/11 15:43
Order form
Evolis
Lateral disconnectable version
for SM6 24 kV (up to 24 kV)
Quantity
24 (kV)
Rated voltage Ur
Service voltage
(kV)
Impulse voltage Up
(kVbil)
630 A maximum
Phase distance
250 mm
Mechanism position
B1
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
Undervoltage release YM
24 Vdc
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
Undervoltage release YM
24 Vdc
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
2432 Vdc
110127 Vdc/ac
4860 Vdc/ac
220250 Vdc/ac
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
AMTED398078EN.indd Sec:115
1
1
1
1
1
1
1
115
20/06/11 15:43
Notes
116
AMTED398078EN.indd Sec:116
AMTED398078EN.indd
20/06/11 15:43
AMTED398078EN.indd Sec:117
20/06/11 15:43
AMTED398078EN.indd Sec:118
in this publication.
06-2011