Vous êtes sur la page 1sur 26

Structural Analysis Report Version 1 - Site Busunju (3141)

STRUCTURAL ANALYSIS REPORT

SITE NAME:

BUSUNJU - 3141

DESCRIPTION:

3-LEGGED ANGULAR 60m

Date:
Dec 04, 2013
Version:
Ver.01
Prepared By: Civil Eng. Michal Salomon

Ver.

Revision Table
Date Issued

Page 1 of 26

Description

Structural Analysis Report Version 1 - Site Busunju (3141)

CONTENTS
1. Executive Summary and Recommendations
2. Site Information
3. Issues Register and Details (Maintenance Report)
4. Load (Equipment) Table
5.

Analysis Introduction

6.

Design Information

7.

Assumptions

8.

Tower Key Plan

9.

Tower Model Diagram

10. Foundation
11. Summary of Results
12. Assessment and Recommendations
13. Potential Allowable EPA/Additional Loading
14. Shop Drawings for Replacement Members
Appendix 1: Bill of Materials
Appendix 2: Pictures
Appendix 3: Detailed Design Calculations

Page 2 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

1. Executive Summary and Recommendations


The tower, under its current antenna configuration, is exceeding the allowable loads up to
261.4% of its full capacity. The most stressed elements are the redundant diagonal #3
member at the 1st section.
The tower was not surveyed, thus no maintenance recommendations are advised.

Summary and Results of Tower with current loadings:


Maximum current stress on tower:
Stress in leg:
Stress in brace:
Stress in leg bolt:
Stress in brace bolt:
Max. rotation (deflection)
Material thickness of steel profile from
Materiel type:
Galvanizing thickness:
Bolt grade:
Factor of safety in overturning
Soil Bearing Pressure

94.9%
261.4%
51.0%
95.1%
0.4 deg
V200x200x15 L38x38x5
JIS-SS540 - JIS-SS400
80m to 250m
ISO 8.8
2.2
180kg/cm^2

Recommendations:
1. Reinforcing the tower according to the table in chapter 12
2. Should a new tenant use the existing structure, a new analysis will be executed.

Page 3 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

2. Site Information
Site Name:
Name & Num.

Busunju - 3141

Site Coordinates:
Longitude:
Latitude:
Site Elevation:

E 032.20139
N 00.58347
1316m

General Information:
Tower Type:
Tower base face width:
Tower top face width:
Tower Configuration:
Structural Steel Grade:
Bolt Grade:
Foundation Type (P&P / S.F):
Foundation Size:

3-Legged, Le Blanc 60m


7780mm
1890mm
Angular
JIS-SS540 - JIS-SS400
ISO 8.8
S.F
3(3.75x3.75x0.6m)

Page 4 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

3. Issues Register and Details (Maintenance Report)


Tower maintenance details per section:
Site survey has not been performed; therefore maintenance recommendation is not
applicable.

Page 5 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

4. Load (Equipment) Table


Existing Antenna Loading:

Antenna Loads
TYPE

MODEL

RF
RF
RF
MW
MW
RF
RF
RF
MW
MW
MW
MW
MW
MW
MW

K-742266
K-742266
K-742266
K-742266
K-742266
K-742266
-

DIM
(LXWXD/O)
2580/260/120
2580/260/120
2580/260/120
1200
3000
2580/260/120
2580/260/120
2580/260/120
2000
3000
3000
3000
600
600
3000

LEG
A
B
C
B
B
A
B
C
B
B
C
C
B
C
C

HEIGHT
(m)
56.6
56.6
56.6
55.5
52.5
48.8
48.8
48.8
45.7
40
38.6
33.2
22.4
22.4
18.5

AZIMUTH
(deg)
50
120
240
140
120
50
130
300
140
120
280
280
130
280
280

HEIGHT
(m)
59.5
59.5
56.4
56.4
56.4
56.4
56.4
56.4

AZIMUTH
(deg)
180
300
130
190
220
300
0
80

Additional Antenna Loading:

Antenna Loads
TYPE

MODEL

MW
MW
RF
RF
RF
RF
RF
RF

ANDREW
ANDREW
K-742266
K-742266
K-742266
K-742266
K-742266
K-742266

DIM
(LXWXD/O)
600
600
2580/260/120
2580/260/120
2580/260/120
2580/260/120
2580/260/120
2580/260/120

LEG
B
C
A
A
B
B
C
C

*Since no information was provided for feeder line cables, we have estimated
EPA 0.4m^2/m

Page 6 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

5. Analysis Introduction
This report covers the structural analysis of Site 3141 Busunju with an overall height of
60m, with a self-support 3 legged steel lattice tower. The tower is triangular in plan, with a
face width tapering from 7780mm at the bottom and 1890mm at the top (center-center).
The tower consists of angular profile legs and diagonal, horizontal bracing members of
varying sizes as listed in the tables and drawings. The bracing members are bolted to the
legs with bolt connections. All legs and braces are shown on the enclosed tower layout
drawing.
The tower and its members are analyzed to design standard code TIA-222-G, Structural
standard for antenna supporting structure and antennas. The tower is modeled and
analyzed using Structural Engineering Software for the Tower Industry "RISATower".
The purpose of the analysis is to make an assessment of the structural adequacy of both the
steel tower and concrete foundation in its current condition.
The tower has been checked for a deflection criteria based on a maximum allowable
rotation of the microwave dishes of 0.5 degrees, as per ANS/TIA-222-G. This is the limit
generally accepted by the telecommunications industry.
Tower leg reactions are used to check the existing foundation for the tower
The following design criteria apply:

Deflections calculated using a wind speed of 100.0 kph "operational speed".


Connections use galvanized bolts Grade 8.8, and locking devices (nut, washer and
spring washer).
Tower members are hot-dipped galvanized in accordance with ASTM A123 and
ASTM A153 Standards.

Page 7 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

6. Design Information
Analysis Standard
Exposure Conditions:
Maximum Design Wind Speed:
Wind Return Period:
Topographical Category:
Site Altitude:
Structure Class:
Steel Grade:
Bolt grade:
Soil Bearing Capacity:
Concrete Grade:

TIA-222-G standard
Exposure Category C
144.0 kph
50 years
3
1376m
I
JIS-SS540 - JIS-SS400
ISO 8.8
200 Kpa
C-25

Page 8 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

7. Assumptions
The tower is analyzed to ANSI TIA/EIA-222-G1 (2007).
The foundation concrete compressive strength is 200kg/cm2 and the rebars strength is
3400kg/cm2.
Members assumed to be comply with the tower design analysis.
Equipment loadings as listed are based on the info got from EATON.
All steel and bolts assumed in good condition and has not deteriorated over time.
The anchors bolts assumed to be 32mm in total quantity 24 units, the anchors are in good
condition and well anchored to the concrete.
Sections are determined according to the connectivity between legs

Page 9 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

8. Tower Key Plan

Page 10 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

9. Tower Model Diagram


Computerized tower model showing equipment
Structural Analysis Report Final load

Page 12 of 26

159.3

1.89

T1

60.0 m

59.5
59.1
59
55.5
52.5
51.3
45.7
40
38.6
33.2
22.4
18.5
- 56.4
- 48.8
56.6
DESIGNED
APPURTENANCE LOADING

TYPE
54.0 m

178.5

N.A.

6@2

330.5

L65x65x5

N.A.

K-739686
K-742266
Andrews
Andrew
4'3.0m
2'
2.0m
(additional
w/Radomeequipment)
(additional
equipment)

52.0 m
209.8

N.A.
C
N.A.
L38x38x5
N.A.
N.A.
N.A.
N.A.

50.0 m
204.4

L50x50x5
L50x50x6

V90x90x7

T5

T4

T3

T2

58.0 m

59.5

Andrew 2' w/Radome (additional


equipment)
K-742266
K-742266
K-742266

59.5

K-739686 (additional equipment)


K-739686 (additional equipment)
K-739686 (additional equipment)
K-739686 (additional equipment)
K-739686 (additional equipment)
K-739686 (additional equipment)

59 - 56.4
59 - 56.4
59 - 56.4
59 - 56.4
59 - 56.4
59 - 56.4

59.1 - 56.6
59.1 - 56.6
59.1 - 56.6

A
B

438.7

2.25813

L65x65x5

MARK

SIZE

N.A.
L65x65x5
2.99437
2.62625

51.3 - 48.8
51.3 - 48.8
45.7
40
38.6
33.2
22.4
22.4

Andrews 3.0m

18.5

509.4

JIS-SS540

357000 kPa

Fu
510000 kPa

GRADE
JIS-SS400

Fy
240000 kPa

Fu
365000 kPa

TOWER DESIGN NOTES


1.
2.
3.
4.
5.
6.
7.

Tower designed for Exposure C to the TIA-222-G Standard.


Tower designed for a 144.0 kph basic wind in accordance with the TIA-222-G Standard.
Deflections are based upon a 100.0 kph wind.
Tower Structure Class I.
Topographic Category 3 with Crest Height of 50.000 m
Connections use galvanized Grade 8.8 bolts, nuts and locking devices.
Tower members are hot-dipped galvanized in accordance with ASTM A123 and ASTM
A153 Standards.
8. TOWER RATING: 261.4%

1169.8

L65x65x5

L38x38x5

Fy

39.0 m

3.3625
9@3

L50x50x5

SIZE
L65x65x5

MATERIAL STRENGTH

552.4

L75x75x6

T8

V130x130x12

T9

666.8

4.09875

30.0 m
N.A.

T10

K-742266
K-742266
Andrews 2.0m
Andrews 3.0m
Andrews 3.0m
Andrews 3.0m
Andrew 2' w/Radome
Andrew 2' w/Radome

MARK

L38x38x5
L50x50x5

GRADE

36.0 m

V150x150x12
JIS-SS540
L65x65x6
JIS-SS400

ELEVATION
55.5
52.5
51.3 - 48.8

SYMBOL LIST

45.0 m

42.0 m

T11

TYPE
Andrew 4' w/Radome
Andrews 3.0m
K-742266

398.2

L50x50x5

L65x65x6

T6
T7

V120x120x10

48.0 m

ELEVATION

Andrew 2' w/Radome (additional


equipment)

770.5

N.A.
4.46687

L75x75x6

T12

L75x75x6

27.0 m

793.7

4.835

21.0 m

1566.7

1@6

5.20313

L38x38x5
L50x50x5

N.A.
L38x38x5

N.A.
N.A.
L50x50x5

L65x65x5
L80x80x6

T14

T13

V150x150x15

24.0 m

1001.2

L65x65x5
6.3075
5.93938
1@3

L38x38x5

12.0 m

7.04375
2@6

L50x50x5

1873.7

ALL REACTIONS
ARE FACTORED

6.0 m

MAX. CORNER REACTIONS AT BASE:


DOWN: 145714 kg
UPLIFT: -124510 kg
SHEAR: 18621 kg
AXIAL
19012 kg

2136.3

N.A.
L65x65x5

T17

V200x200x15

L80x80x6

L75x75x6

V175x175x15

T16

T15

L75x75x6

15.0 m

SHEAR
32559 kg

MOMENT
941529 kg-m

Section
Legs
Leg Grade
Diagonals
Diagonal Grade
Top Girts
Horizontals
Sec. Horizontals
Red. Horizontals
Red. Diagonals
Red. Hips
Inner Bracing
Face Width (m)
7.78
# Panels @ (m)
12959.9
Weight (kg)

0.0 m

TORQUE 17253 kg-m


REACTIONS - 144.0 kph WIND

LeadCom
4 Hatnufa St.
Pethach Tikva - Israel
Integrated Solutions

Phone: 03-9706269
FAX: 03-9706001

Job:

TIA-222-G - 40m/s (EPA 53.3m2@top40m)

Project: LeBlanc-TRI-60m
Client:
Code:
Path:

Eaton
TIA-222-G

-As built- Uganda- Busunju site (3141)


App'd:
rong
Date:
Scale:
12/03/13
NTS
Dwg No.
E-1
Drawn by:

C:\Documents and Settings\rong\Desktop\Hellios Tower Analysis\Uganda- Busunju site (3141)\LeBlanc-TRI-60m - As Built (TIA-222-G, 40ms -EPA53.3m2@top40m).eri

Structural Analysis Report Version 1 - Site Busunju (3141)

Structural Analysis Report Reinforced

Page 14 of 26

159.3

1.89

T1

60.0 m

59.5
59.1
59
55.5
52.5
51.3
45.7
40
38.6
33.2
22.4
18.5
- 56.4
- 48.8
56.6
DESIGNED
APPURTENANCE LOADING

TYPE
54.0 m

178.5

N.A.

6@2

330.5

L65x65x5

N.A.

K-739686
K-742266
Andrews
Andrew
4'3.0m
2'
2.0m
(additional
w/Radomeequipment)
(additional
equipment)

52.0 m
209.8

N.A.
C
N.A.
L38x38x5
N.A.
N.A.
N.A.
N.A.

50.0 m
204.4

L50x50x5
L50x50x6

V90x90x7

T5

T4

T3

T2

58.0 m

59.5

Andrew 2' w/Radome (additional


equipment)
K-742266
K-742266
K-742266

59.5

K-739686 (additional equipment)


K-739686 (additional equipment)
K-739686 (additional equipment)
K-739686 (additional equipment)
K-739686 (additional equipment)
K-739686 (additional equipment)

59 - 56.4
59 - 56.4
59 - 56.4
59 - 56.4
59 - 56.4
59 - 56.4

59.1 - 56.6
59.1 - 56.6
59.1 - 56.6

A
B

438.7

2.25813

L65x65x5

MARK

SIZE

N.A.
L65x65x5
2.99437
2.62625

51.3 - 48.8
51.3 - 48.8
45.7
40
38.6
33.2
22.4
22.4

Andrews 3.0m

18.5

522.5

JIS-SS540

Fy

Fu

357000 kPa

510000 kPa

39.0 m

GRADE
JIS-SS400

Fy
240000 kPa

Fu
365000 kPa

TOWER DESIGN NOTES


1.
2.
3.
4.
5.
6.
7.

Tower designed for Exposure C to the TIA-222-G Standard.


Tower designed for a 144.0 kph basic wind in accordance with the TIA-222-G Standard.
Deflections are based upon a 100.0 kph wind.
Tower Structure Class I.
Topographic Category 3 with Crest Height of 50.000 m
Connections use galvanized Grade 8.8 bolts, nuts and locking devices.
Tower members are hot-dipped galvanized in accordance with ASTM A123 and ASTM
A153 Standards.
8. TOWER RATING: 98.5%

3.3625
9@3
L65x65x5

1217.8

L38x38x5

L50x50x5

SIZE
L65x65x5

MATERIAL STRENGTH

552.4

L50x50x5

T8

V130x130x12

T9

27.0 m
784.3

N.A.
4.46687

L50x50x5

L75x75x6

706.1

4.09875

30.0 m
N.A.

T10

V150x150x12
JIS-SS540
L75x75x6
JIS-SS400

K-742266
K-742266
Andrews 2.0m
Andrews 3.0m
Andrews 3.0m
Andrews 3.0m
Andrew 2' w/Radome
Andrew 2' w/Radome

MARK

L38x38x5
L50x50x5

GRADE

36.0 m

T11

ELEVATION
55.5
52.5
51.3 - 48.8

SYMBOL LIST

45.0 m

42.0 m

T12

TYPE
Andrew 4' w/Radome
Andrews 3.0m
K-742266

398.2

L50x50x5

L65x65x6

T6
T7

V120x120x10

48.0 m

ELEVATION

Andrew 2' w/Radome (additional


equipment)

793.7

4.835

21.0 m

1620.9

1@6

5.20313

N.A.
L38x38x5
L38x38x5
L38x38x5
L50x50x5

N.A.
N.A.
L50x50x5

L65x65x5
L80x80x6

T14

T13

V150x150x15

24.0 m

1019.0

L65x65x5
6.3075
5.93938
1@3

L38x38x5

12.0 m

7.04375
2@6

L50x50x5

1968.5

ALL REACTIONS
ARE FACTORED
MAX. CORNER REACTIONS AT BASE:
DOWN: 146733 kg
UPLIFT: -125110 kg
SHEAR: 18850 kg

6.0 m

AXIAL
19428 kg

2202.0

N.A.
L65x65x5

T17

V200x200x15

L80x80x6

L75x75x6

V175x175x15

T16

T15

L75x75x6

15.0 m

SHEAR
32990 kg

MOMENT
947443 kg-m

Section
Legs
Leg Grade
Diagonals
Diagonal Grade
Top Girts
Horizontals
Sec. Horizontals
Red. Horizontals
Red. Diagonals
Red. Hips
Inner Bracing
Face Width (m)
7.78
# Panels @ (m)
13306.7
Weight (kg)

0.0 m

TORQUE 17266 kg-m


REACTIONS - 144.0 kph WIND

LeadCom

Integrated Solutions

Job:

TIA-222-G - 40m/s (EPA 53.3m2@top40m)

Project: LeBlanc-TRI-60m

4 Hatnufa St.
Pethach Tikva - Israel

Client:

Phone: 03-9706269
FAX: 03-9706001

Path:

Code:

Eaton
TIA-222-G

-As built-reinforced- Uganda- Busunju site (3141)


Drawn by:
App'd:
rong
Date:
Scale:
12/03/13
NTS
Dwg No.
E-1

C:\Documents and Settings\rong\Desktop\Hellios Tower Analysis\Uganda- Busunju site (3141)\LeBlanc-TRI-60m - As Built- reinforced (TIA-222-G, 40ms -EPA53.3m2@top40m).eri

Structural Analysis Report Version 1 - Site Busunju (3141)

10. Foundation
Foundation drawing, condition, design check etc.
Soil Bearing Capacity:
Concrete Grade:

200
C25

Maximum Support Reaction on existing tower with current loading


A.

B.

C.

D.

Tower Base
1. Maximum overturning Moment:
2. Base Shear:
3. Vertical Load:

5921kN.m
206kN
162kN

Tower Leg
1. Max downward leg load:
2. Max upward leg load:

917kN
782kN

Holding down Bolts


1. Bottom Flange thickness:
2. HDBs:
3. HDBs Stress:

30mm
8no. M32 assumed at Grade 5.8
0.82<1.0, Safe

Overturning Factor of safety and bearing capacity


1. Surveyed size of tower base is:
3x (3.75m x 3.75m x 0.6m) separate footings
2. The resulting ground bearing pressure is: 180kN/m2 < 200kN/m2, Safe
3. Factor of Safety against overturning of:
2.2>2.0, Safe

Page 16 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

11. Summary of Results


Tower legs, braces and bolts stress ratios according to Risa Tower output per section
Legs and Braces summary results (Final loading):
SECTION
LEG SIZE
LEG STRESS

BRACE SIZE

BRACE STRESS

Section 1

V200x200x15

0.771

L38x38x5

2.614

Section 2

V175x175x15

0.813

L38x38x5

2.541

Section 3

V175x175x15

0.840

L50x50x5

1.111

Section 4

V150x150x15

0.949

L38x38x5

2.153

Section 5

V150x150x15

0.822

L65x65x5

0.740

Section 6

V150x150x15

0.774

L38x38x5

1.050

Section 7

V150x150x15

0.698

L38x38x5

1.282

Section 8

V150x150x12

0.715

L65x65x6

1.231

Section 9

V130x130x12

0.698

L75x75x6

0.797

Section 10

V130x130x12

0.660

L38x38x5

1.086

Section 11

V120x120x10

0.677

L65x65x6

0.807

Section 12

V120x120x10

0.518

L65x65x6

0.745

Section 13

V90x90x7

0.644

L65x65x6

0.440

Section 14

V90x90x7
V90x90x7
V90x90x7
V90x90x7

0.578
0.545
0.323
0.149

L50x50x6
L50x50x6
L50x50x5
L38x38x5

0.745
0.443
0.317
0.104

Section 15
Section 16
Section 17

Page 18 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

Bolts summary results (Final loading):


SECTION
LEG BOLT SIZE
LEG BOLT STRESS

BRACE BOLT SIZE

Section 1

M20 Gr8.8 bolts

0.490

M20 Gr8.8 bolts

BRACE BOLT
STRESS
0.838

Section 2

M20 Gr8.8 bolts

0.464

M20 Gr8.8 bolts

0.871

Section 3

M20 Gr8.8 bolts

0.510

M20 Gr8.8 bolts

0.596

Section 4

M20 Gr8.8 bolts

0.446

M20 Gr8.8 bolts

0.951

Section 5

M20 Gr8.8 bolts

0.456

M18 Gr8.8 bolts

0.629

Section 6

M20 Gr8.8 bolts

0.426

M16 Gr8.8 bolts

0.600

Section 7

M20 Gr8.8 bolts

0.426

M16 Gr8.8 bolts

0.590

Section 8

M20 Gr8.8 bolts

0.385

M16 Gr8.8 bolts

0.651

Section 9

M20 Gr8.8 bolts

0.282

M16 Gr8.8 bolts

0.657

Section 10

M20 Gr8.8 bolts

0.279

M16 Gr8.8 bolts

0.514

Section 11

M18 Gr8.8 bolts

0.316

M12 Gr8.8 bolts

0.537

Section 12

M18 Gr8.8 bolts

0.246

M12 Gr8.8 bolts

0.552

Section 13

M16 Gr8.8 bolts

0.702

M12 Gr8.8 bolts

0.573

Section 14

M16 Gr8.8 bolts


M16 Gr8.8 bolts
M16 Gr8.8 bolts
M16 Gr8.8 bolts

0.702
0.293
0.162
0.010

M12 Gr8.8 bolts


M12 Gr8.8 bolts
M12 Gr8.8 bolts
M12 Gr8.8 bolts

0.522
0.299
0.187
0.025

Section 15
Section 16
Section 17

The maximum rotation of dishes at elevation 48-60 m: 0.4

Page 19 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

Legs and Braces summary results (Final reinforced):


SECTION
LEG SIZE
LEG STRESS

BRACE SIZE

BRACE STRESS

Section 1

V200x200x15

0.775

L65x65x5

0.901

Section 2

V175x175x15

0.817

L50x50x5

0.863

Section 3

V175x175x15

0.845

L50x50x5

0.969

Section 4

V150x150x15

0.954

L50x50x5

0.889

Section 5

V150x150x15

0.826

L65x65x5

0.746

Section 6

V150x150x15

0.777

L75x75x6

0.791

Section 7

V150x150x15

0.699

L75x75x6

0.759

Section 8

V150x150x12

0.710

L38x38x5

0.985

Section 9

V130x130x12

0.697

L75x75x6

0.794

Section 10

V130x130x12

0.666

L65x65x6

0.933

Section 11

V120x120x10

0.679

L65x65x6

0.807

Section 12

V120x120x10

0.517

L65x65x6

0.745

Section 13

V90x90x7

0.644

L65x65x6

0.440

Section 14

V90x90x7
V90x90x7
V90x90x7
V90x90x7

0.578
0.545
0.323
0.149

L50x50x6
L50x50x6
L50x50x5
L38x38x5

0.745
0.443
0.317
0.104

Section 15
Section 16
Section 17

Page 20 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

Bolts summary results (Final reinforced):


SECTION
LEG BOLT SIZE
LEG BOLT STRESS

BRACE BOLT SIZE

Section 1

M20 Gr8.8 bolts

0.493

M20 Gr8.8 bolts

BRACE BOLT
STRESS
0.847

Section 2

M20 Gr8.8 bolts

0.466

M20 Gr8.8 bolts

0.876

Section 3

M20 Gr8.8 bolts

0.512

M20 Gr8.8 bolts

0.600

Section 4

M20 Gr8.8 bolts

0.448

M20 Gr8.8 bolts

0.956

Section 5

M20 Gr8.8 bolts

0.457

M18 Gr8.8 bolts

0.634

Section 6

M20 Gr8.8 bolts

0.427

M16 Gr8.8 bolts

0.603

Section 7

M20 Gr8.8 bolts

0.427

M16 Gr8.8 bolts

0.593

Section 8

M20 Gr8.8 bolts

0.385

M16 Gr8.8 bolts

0.658

Section 9

M20 Gr8.8 bolts

0.282

M16 Gr8.8 bolts

0.653

Section 10

M20 Gr8.8 bolts

0.279

M16 Gr8.8 bolts

0.515

Section 11

M18 Gr8.8 bolts

0.316

M12 Gr8.8 bolts

0.537

Section 12

M18 Gr8.8 bolts

0.246

M12 Gr8.8 bolts

0.552

Section 13

M16 Gr8.8 bolts

0.702

M12 Gr8.8 bolts

0.573

Section 14

M16 Gr8.8 bolts


M16 Gr8.8 bolts
M16 Gr8.8 bolts
M16 Gr8.8 bolts

0.702
0.293
0.162
0.010

M12 Gr8.8 bolts


M12 Gr8.8 bolts
M12 Gr8.8 bolts
M12 Gr8.8 bolts

0.522
0.299
0.187
0.025

Section 15
Section 16
Section 17

The maximum rotation of dishes at elevation 48-60 m: 0.4

Page 21 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

12. Assessment and Recommendation


The current tower capacity is 261.4%; therefore Reinforcement of the tower needs to be
done.

Rectification table:
ITEM

MEMBER SIZE

SECTION

QTY

COMMENT

Replacement of Diagonals

L-75xx75x6

T10-T11

18

H=27.0-36.0m

L-50x50x5

T14, T16

12

H=9.0m ,
H=18.0m

L-65x65x5

T15

H=14.0m

L-65x65x5

T14, T16

12

L-50x50x5

T8,
T11-T12

18

L-50x50x5

T14

12

H= 19.5-21.0m

L-65x65x5

T16-T17

12

H=4.5-6.0m
H=10.5-12.0m

Replacement of "redundant
horizontals #2"
Replacement of "redundant
horizontals #2"
Replacement of "redundant
horizontals #3
Replacement of "redundant
diagonals #1"
Replacement of "redundant
diagonals #3"
Replacement of "redundant
diagonals #3"

H=10.5m,
H= 20.5m
H= 39.0- 40.5m,
H= 25.5-27.0m,
H= 27.0 - 28.5m

General Comments for additional Works:


Site survey has not been performed; therefore maintenance recommendation is not
applicable.

Rectification recommendation based on severity level:


Level 1 - To be done immediately
Level 2 - To be done within 6 months
Level 3 - Best practice
LEVEL
1

DESCRIPTION
Rectification table should be implemented
N.A

N.A

N.A
Page 22 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

13. Potential Allowable EPA/Additional Loading


N.A

Page 23 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

14. Shop Drawings for Replacement Members


N.A

Page 24 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

APPENDIX
Appendix 1: Bill of Materials
N.A

Page 25 of 26

Structural Analysis Report Version 1 - Site Busunju (3141)

Appendix 2: Pictures
N.A

Page 26 of 26

Vous aimerez peut-être aussi