Académique Documents
Professionnel Documents
Culture Documents
Proportional
only, P
Proportional Gain
Integral Time
Kc
1 2.5
0.01 12.5
Derivativ
e Time
Integral
Gain
Derivative
Gain
(Kc /I)
(Kc *D)
450
8.325
= -500
Proportional
integral, PI
0.9 2.5
0.01 12.5
=
-54.054
= -450
Proportional
integral
derivative,
PID
1.2 2.5
0.01 12.5
2.0 2.5
=5
1
2.5
2
600
6001.25
= -750
= 1.25
= -600
= -120
Proportional Gain
Integral Time
Derivative Time
Kc
Integral
Gain (Kc /I)
Derivat
Gain
(Kc *
Proportional
integral, PI
0.758 2.5
0.01 12.5
0.861
12.5
1.02 0.323(0.2)
303.028
13.084
= 13.084
= -23.16
= -303.028
Proportional
integral
derivative,
PID
1.086 2.5
0.01 12.5
0.869
12.5
2.5
12.5
0.914
439.779
17.507
= -25.12
439.
0.9999
= -439.779
= 17.507
= -439.
= 0.9999
Table 2.2 Minimum Error Integral Tuning IAE Formulas for Set Point Changes
Controller
Type
Proportional
Gain
Integral Time
Derivative Time
12.5
1.03 0.165(0.2)
Kc
Proportiona
l integral,
PI
0.586 2.5
0.01 12.5
0.916
= -255.949
Proportiona
l integral
derivative,
PID
0.965 2.5
0.01 12.5
0.855
= -382.073
Derivative Gain
(Kc*D )
255.949
12.538
= -20.414
= 12.538
12.5
0.796 0.147(0.2)
Integral
Gain
(Kc/I )
2.5
0.308(12.5)
12.5
= 16.306
0.9292
= 0.863
382.073
16.306
382.07316.30
= -23.431
Table 2.3 Minimum Error Integral Tuning ITAE Formulas for Set Point Changes
Controller Type
Proportional
integral
derivative, PID
Proportional
Gain
Integral
Time
Derivativ
e Time
Kc
12.5
0.01(2.5 12.5)
= -83.333
= 12.5
2.5
2
=
1.25
Integral
Gain
(Kc/I )
Derivative
Gain
(Kc*D )
83.333
12.5
83.3331.25
= -104.166
= 6.667
= -329.729
Controller
Type
Proportiona
l only, P
Proportional Gain
Integral Time
Kc
Derivative
Time
1
5 1 25
0.01
312.5
Integral Gain
(Kc/I)
Derivative
Gain
(Kc*D)
458.333
3.385
= -533.333
Proportiona
l integral, PI
30 3(0.2)
1
5 9 2.5 2.5 22 3(0.2)
0.01 10 1212.5
= -458.333
Proportiona
l integral
derivative,
PID
1
5 4 2.5
0.01 3 412.5
= -691.667
= 3.385
2.5
32 6(0.2)
13 8(0.2)
= 5.685
= -135.401
2.5
4
11 2(0.2)
= 0.877
691.667
5.685
= -121.665
691.667 0.877
= -606.591
Minimum Error Integral Tuning IAE Formulas for Set Point Changes
PI-Controller
Minimum Error Integral Tuning IAE Formulas for Set Point Changes
PID-Controller
Minimum Error Integral Tuning ITAE Formulas for Set Point Changes
PI-Controller
Minimum Error Integral Tuning ITAE Formulas for Set Point Changes
PID-Controller
Tabulation of Overshoot Percentage, Settling Time & Integral of absolute error (IAE)
Tuning Formulas for Quarter Decay Ratio Response
P
PI
PID
Offset
0.025
0
0
OS
0.496
0.513
1.067
Ts
20.06
24.13
INFINITY
IAE
7.3
1.2
22.9
Minimum Error Integral Tuning IAE Formulas for Set Point Changes
PI
PID
Offset
0
0
OS
0.12
0.60
Ts
16.40
97.73
IAE
0.8
3.8
Minimum Error Integral Tuning ITAE Formulas for Set Point Changes
PI
PID
Offset
0
0
OS
0.04
0.47
Ts
15.07
43.87
IAE
0.8
1.6
Offset
0
OS
0
Ts
47.8
IAE
2.2
Ts
237.11
235.87
INFINITY
IAE
6.9
7.9
20.7
Offset
0.024
0
0
OS
0.49
0.913
0.993
as possible to the set point (responsive), minimize overshoot, and then hold the process variable
steady at the set point without excessive output changes (stable).
There are five methods of tuning available in this project. The evaluation of the best
controller for each respective method will be done based on the IAE value obtained when using
different controller systems.
controller. Moreover, PI controller settles faster than PID controller. Again, just like in Minimum
Error Integral Tuning IAE, both type of controllers do not have any offsets. Due to higher IAE
value, peak overshoot ratio and longer settling time, PID controller is eliminated as the option
and PI controller is chosen as the best controller suited for this method.
Dahlin Synthesis
There is only one choice of controller available for Dahlin Synthesis Method which is PID
controller. Thus, no comparison could be made to choose the best controller for this method.
Cohen Coon
From the computed table provided in excel, P Controller has the lowest IAE value whereas PID
controller has the highest IAE value. The IAE of PI controller is in between P controller and PID
controller. PID controller has the highest value of peak overshoot ratio followed by PI controller
and P controller. Among the three controllers, PID has the longest settling time whereas PI
controller has the shortest settling time. P controller has an offset of 0.024 while the other two
controllers do not have offsets. Thus, the best controller for this method would be P controller.
5.2 Determine the best tuning for each P, PI and PID controller from five methods
P Controller
The P-Only controller computes a CO action every loop sample time T as:
CO = CObias + Kce(t)
Where:
CObias = controller bias or null value
Kc = controller gain, a tuning parameter
e(t) = controller error = SP PV
SP = set point
PV = measured process variable
Time constant, Tp, and dead time, p, cannot affect the sign of Kc because they mark the
passage of time and must always be positive. The above tuning correlation thus implies that Kc
must always have the same sign as the process gain, Kp. When CO increases on a process that
has a positive Kp, the PV will increase in response. A process with a positive Kp is direct acting.
With negative feedback, the controller must be reverse acting for stable control. Conversely,
when Kp is negative (a reverse acting process), the controller must be direct acting for stable
control. Since Kp and Kc always have the same sign for a particular process and stable control
requires negative feedback, then:
Direct acting process (Kp and Kc positive) use a reverse acting controller
Reverse acting process (Kp and Kc negative) use a direct acting controller
In our project, P controller of Quarter Decay Ratio Response and Cohen Coon Controller
Settings are both reverse acting controller due to both having negative Kp values.
In feedback control system, it is best that the error, e(t), between any variable and its
demanded value is zero. However, in both the Quarter Decay Ratio Response and Cohen Coon
Controller Settings, the value of IAE is not zero, with P controller in Quarter Decay Ratio
Response having an error value of 0.025 and P controller in Cohen Coon Controller Settings
having an error value of 0.024. By comparing Cohen Coon and Quarter Decay Ratio Response
method, the value of Integral of Absolute Error (IAE) in Quarter Decay Ratio Response is
slightly larger compared to in Cohen Coon Controller Settings with a difference of 0.001. Due to
the e(t) not equal to zero in both of the controllers, there are areas between the set point line and
the process variable line. For the Cohen Coon graph, the area between the set point line and the
process variable is smaller, which signifies that the tuning system is able to bring the process
variable closer to the set point and gives a smaller offset.
Settling time is the time elapsed from the application of an ideal instantaneous step input
to the time at which the amplifier output has entered and remained within a specified error band,
usually symmetrical about the final value. The settling time of P controller in Quarter Decay
Ratio Response is slower whereas Cohen Coon has faster settling time. This is due to low value
of higher value proportional gain Kc used in Cohen Coon caused less oscillatory response in the
tuning system.
The peak overshoot ratio of P controller in Quarter Decay Ratio Response is also higher
than the one in Cohen Coon Controller Settings. Overshoot refers to an output exceeding its
final, steady-state value and the percentage overshoot (PO) is the maximum value divided by the
step value. Thus, it indicates that P controller in Quarter Decay Ratio Response has higher
maximum value than in Cohen Coon Controller Settings since the step value is constant for the
two controllers. In terms of offset, P controller in Quarter Decay Ratio Response is also higher
than the one in Cohen Coon Controller Settings.
In conclusion, Quarter Decay Ratio would be more ideal since it has faster settling time
and response of higher accuracy could be obtained since it also gives less error.
PI Controller
The PI controller computes a CO action every loop sample time T as:
Where:
CO = controller output signal
CObias = controller bias or null value; set by bumpless transfer as explained below
e(t) = current controller error, defined as SP PV
SP = set point
The PI-mode has an effect on controller output by varying the integral time with respect
to time. The integral time is changed and ultimately it directly affects the output of the controller.
As the integral time was increased the controller output was also changed with respect to time.
This might be due higher oscillations and lesser smoothness in case of PI mode. The PI-mode
also reaches the steady state set point slowly. Like the P-Only controller, the ProportionalIntegral (PI) algorithm computes and transmits a controller output (CO) signal every sample
time, T, to the final control element. The computed CO from the PI algorithm is influenced by
the controller tuning parameters and the controller error, e(t). Integral action enables PI
controllers to eliminate offset, a major weakness of a P-only controller. Thus, PI controllers
provide a balance of complexity and capability that makes them by far the most widely used
algorithm in process control applications.
By comparing four methods of Quarter Decay Ratio Response, Minimum Error Integral
Tuning IAE Formulas, Minimum Error Integral Tuning ITAE Formulas and Cohen Coon
controller settings, it is found out that Minimum Error Integral Tuning ITAE Formulas and
Minimum Error Integral Tuning IAE Formulas have the lowest value of IAE which is 0.8
followed by Quarter Decay Ratio Response and Cohen Coon controller settings.
In terms of settling time, Minimum Error Integral Tuning ITAE Formulas has the fastest
settling time among the five methods mentioned with the value of 15.07 whereas Cohen Coon
controller settings has the slowest settling time with value of 235.87.
All of the methods do not lead to any offsets, thus offset could not be used as an accurate
parameter to decide on which method is the best for PI Controller.
The peak overshoot ratio of Minimum Error Integral Tuning ITAE Formulas is also the
smallest which is 0.04 compared to Minimum Error Integral Tuning IAE Formulas of value 0.12,
Quarter Decay Ratio Response of value 0.5133 and Cohen Coon controller settings with biggest
peak overshoot ratio value which is 0.913.
In a nutshell, Minimum Error Integral tuning ITAE is the best PI controller. This because
it has the least Integral of Absolute Error (IAE) and peak overshoot ratio, fastest settling time, no
offset. The Quarter Decay Ratio Response and Minimum Error Integral Tuning IAE and Cohen
Coon controller settings method are not pursued because they have high values of IAE, peak
overshoot ratio and settles slower.
PID Controller
The PID controller is a three mode controller. That is, its activity and performance is based on
the values chosen for three tuning parameters, one each nominally associated with the
proportional, integral and derivative terms.
Where:
CO = controller output signal
CObias = controller bias; set by bumpless transfer
e(t) = current controller error, defined as SP PV
SP = set point
PV = measured process variable
Kc = controller gain, a tuning parameter
Ti = reset time, a tuning parameter
Td = derivative time, a tuning parameter
By comparing the 5 PID controllers from 5 different methods which are Quarter Decay
Ratio Response, Minimum Error Integral Tuning IAE Formulas, Minimum Error Integral Tuning
ITAE Formulas, Controller Modes & Tuning Formulas for Dahlin Synthesis and Cohen Coon
controller settings, it is shown that Minimum Error Integral Tuning ITAE Formulas has the
lowest IAE value followed by Controller Modes & Tuning Formulas for Dahlin Synthesis,
Minimum Error Integral Tuning IAE Formulas, Cohen Coon controller settings and Quarter
Decay Ratio Response.
Among all the five methods, Minimum Error Integral Tuning ITAE Formulas has the
fastest settling time with the value of 47.8 minutes whereas Cohen Coon controller settings and
Quarter Decay Ratio Response has infinite settling time.
Regarding the offset comparison of the five methods, it is found out that all the five
methods do not have offsets. Dahlin Synthesis has no overshoot thus zero peak overshoot ratio
while on the other hand, Quarter Decay Ratio Response has the highest value of peak overshoot
ratio.
It can be concluded that the recommended tuning method for PID Controller is Dahlin
Synthesis as it has no overshoot at all compared to the other four methods despite that it has
higher IAE value than Minimum Error Integral Tuning ITAE Formulas. Minimum Error Integral
Tuning IAE Formulas has overshoot thus it is not chosen. Besides that, Quarter Decay Ratio
Response is not preferable due to its high value of peak overshoot ratio. Cohen Coon controller
settings method is also eliminated because of its infinite settling time.